BESS VENCON Battery - Specs - 820V

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Dokument: VENCON Battery – General Data

Datum / Kürzel: 23.03.2021 / GME

General Data VENCON Battery 150 VENCON Battery 300


Dimensions (W x D x H) 1208 x 656 x 2352* mm 1208 x 656 x 2352* mm
Weight 790 kg 980 kg
Degree of protecttion (indoor) IP20 IP20
Noise emission < 70 dB(A)@1m < 70 dB(A)@1m
Operating ambient temperature –20 bis +40 °C, –20 bis +40 °C,
range >40 bis +50 °C = derating >40 bis +50 °C = derating
Cable insertion Bottom bottom
Cooling Air cooling Air cooling
Max. altitude 2000 m, >2000m optional 2000 m, >2000m optional
Max. allowable relative humidity < 95% non-condensing < 95% non-condensing
range (non-condensing)
Standby-consumption <100 W <100 W
Efficiency > 97% > 97%
*incl. 200mm base *incl. 200mm base

Communication
Display Touch screen Touch screen
Communication MODBUS-TCP / Ethernet MODBUS-TCP / Ethernet
Web-User Interface inclusive inclusive

AC-side (Grid)
Nominal AC voltage 400 V 400 V
AC voltage range 360 – 440 V 360 – 440 V
Apparent power 167 kVA 333 kVA
Rated power 150 kW 300 kW
Rated current 216 A 433 A
Rated frequency 50 / 60 Hz 50 / 60 Hz
Frequency range 45-55 Hz / 55-65 Hz 45-55 Hz / 55-65 Hz
Power factor 0,9 cap bis 0,9 ind 0,9 cap bis 0,9 ind
Reactive power -75 kVar … 75 kVar -150 kVar … 150 kVar
THDI <2,5% at nominal power <2,5% at nominal power
AC connection 3/PEN / 3/N/PE 3/PEN / 3/N/PE
Grid protection U<<, U<, U>, U>>, f<, f> U<<, U<, U>, U>>, f<, f>

AC- side (Off-Grid)


Unbalanced load capacity 100% 100%
Overload capability 10% - permanent 10% - permanent
Transfer between on/off grid < 30 ms < 30 ms
Online UPS operation optional optional
Black start capability yes yes
THDU <1,5% at nominal power <1,5% at nominal power
Automatic transfer switch optional optional

DC-side
Nominal DC voltage 600 V DC 600 V DC
Voltage/operating range 0 V – 820 V DC 0 V – 820 V DC
Max. DC voltage 820 V DC 820 V DC
Number of DC connections 1 3 1 3
Max. DC current per connection 600 A 200 A 600 A 200 A
Nominal power 1 x 360 kW 3 x 120 kW 1 x 360 kW 3 x 120 kW

Protection
AC output protection Circuit breaker + fuse Circuit breaker + fuse
DC input protection fuse + contactor fuse + contactor
Grid monitoring inclusive inclusive
Overheat protection inclusive inclusive
Overvoltag protection optional optional
Insulation monitoring optional optional
Certifications IEC62477-1, VDE-AR-N 4110, IEC 61000-6-2, IEC61000-6-4, EN55011
VENSYS Elektrotechnik GmbH Seite 1 von 1
Dieselstr. 12 | 49356 Diepholz
T + 49 5441 92630-0 | F +49 5441 92630-11