Simatic SIMATIC Modbus/TCP Communication Using CP 343-1 and CP 443-1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 70

Preface

Product description 1

Step-by-step instructions 2
SIMATIC
Putting the function block
into operation 3
SIMATIC Modbus/TCP Parameter assignment for
4
Modbus/TCP communication
communication using CP 343-1 and
CP 443-1
MODBUSCP licensing 5
Programming Manual

MODBUSCP function block 6

Additional blocks 7

Diagnostics 8

Examples of applications 9

Reference A

09/2014
A5E32489434-AA
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
indicates that minor personal injury can result if proper precautions are not taken.

NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens AG A5E32489434-AA Copyright © Siemens AG 2014.


Industry Sector Ⓟ 09/2014 Subject to change All rights reserved
Postfach 48 48
90026 NÜRNBERG
GERMANY
Preface

Purpose of the document


With the information in this document, you can establish and commission a link between a
CP 343-1 or CP 443-1 and a device that supports the Modbus/TCP protocol.

Contents of the document


This document describes the function and parameter assignment of the MODBUSCP
function block.
The document covers the following topics:
● Product description (Page 9)
● Step-by-step instructions (Page 11)
● Putting a function block into operation (Page 13)
● Parameter assignment for Modbus/TCP communication (Page 31)
● MODBUSCP licensing (Page 37)
● MODBUSCP function block (Page 41)
● Additional blocks (Page 55)
● Diagnostics (Page 57)
● Examples of applications (Page 65)

Additional sources of information


For all other information relating to the CP 343 and CP 443, please refer to the following
documents:
SIEMENS
SIMATIC NET
S7 CPs for Industrial Ethernet
manual
C79000-G8976-C155
SIEMENS
SIMATIC NET
S7 CPs for Industrial Ethernet
manual, Part B1
CP 343 1 / CP 343 1EX20
C79000-G8976-C158

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 3
Preface

SIEMENS
SIMATIC NET
S7 CPs for Industrial Ethernet
manual, Part B4
CP 443 1
C79000-G8976-C152
SIEMENS
SIMATIC NET
NCM S7 for Industrial Ethernet
manual
C79000-G8976-C129
You will find further information relating to STEP 7 in the following manuals:
SIEMENS
SIMATIC Software
Basic Software for S7 and M7
STEP 7 user manual
C79000-G7076-C502-..
SIEMENS
SIMATIC Software
System Software for S7-300/400
System and Standard Functions
reference manual
C79000-G7076-C503-02

Technical support
You can reach Technical Support using the Web form for the Support Request
(https://support.automation.siemens.com/WW/view/en/38718979).

Area of application
The function block described in this manual establishes a connection between the CP 343-
1/CP 443-1 and Modbus/ TCP devices of other manufacturers.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


4 Programming Manual, 09/2014, A5E32489434-AA
Preface

Scope of validity
This documents applies to:
● SIMATIC communication processor CP 343-1
● SIMATIC communication processor CP 443-1
This document applies to the following software:

Product Identification number As of version


SIMATIC Modbus/TCP CP 2XV9 450-1MB00 5.0
FB 108 "MODBUSCP" 4.0
FB 106 "MB_CPCLI" 2.3
FB 107 "MB_CPSRV" 2.2

Note
This document contains the description of the FB valid at the time the document was
published.

Note
Observe the following points:
· You are also going to need this document whenever the system is recommissioned.
· Keep this supplementary documentation in a safe place for the entire life cycle of the
software.
· Pass on all of these documents to any future owner of the software.

Knowledge required
General knowledge of automation engineering and process communication is needed to
understand this document. To create a project, knowledge of the "STEP 7" engineering
software is necessary.

Style conventions

Style Convention Scope


"Add screen" · Terminology for the user interface, e.g. dialog name, tab, button,
menu command
· Necessary entries, e.g. limit value, tag value
· Path information
"File > Edit" Operational sequences, e.g, menu command, shortcut menu command
<F1>, <Alt+P> Designation of a key on a keyboard

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 5
Preface

You should also observe the notes that are marked as follows:

Note
A note contains important information about the product described in the document and its
handling, or a specific section of the document to which you should pay particular attention.

Naming conventions

Term Applies to
CP · CP 343-1
· CP 443-1

Figures
This document includes illustrations of the described software. The detail of the images may
deviate from the supplied software.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


6 Programming Manual, 09/2014, A5E32489434-AA
Table of contents

Preface ........................................................................................................................................ 3
1 Product description ........................................................................................................................ 9
1.1 Scope of delivery ................................................................................................................. 9
1.2 Possible applications ........................................................................................................... 9
1.3 Hardware and software requirements ................................................................................ 10
2 Step-by-step instructions .............................................................................................................. 11
3 Putting the function block into operation ......................................................................................... 13
3.1 Installing the library on the STEP 7 PG/PC ........................................................................ 13
3.2 Assigning CP parameters .................................................................................................. 14
3.3 Assigning link partner parameters...................................................................................... 15
3.4 Configuring the communication connection ........................................................................ 17
3.4.1 Configuring the connection in "CP is Client" ....................................................................... 17
3.4.2 Configuring an unspecified connection with "CP is server" ................................................. 22
3.5 Inserting Modbus/TCP function blocks ............................................................................... 25
3.6 Using connections on port 502 .......................................................................................... 27
3.7 Startup behavior of the CP 343-1 and CP 443-1 ................................................................ 28
3.8 Migrating from Modbus/TCP CP V4.x to Modbus/TCP CP V5.x ......................................... 29
4 Parameter assignment for Modbus/TCP communication .................................................................. 31
4.1 Parameter assignment for Modbus/TCP communication with the Wizard ........................... 32
4.2 Manual parameter assignment for Modbus/TCP communication ........................................ 33
4.2.1 Structure of the connection parameters ............................................................................. 33
4.2.2 Parameter assignment for Modbus/TCP communication .................................................... 35
5 MODBUSCP licensing ................................................................................................................. 37
5.1 MODBUSCP licensing ....................................................................................................... 37
5.2 Missing or incorrect licensing ............................................................................................. 40
6 MODBUSCP function block .......................................................................................................... 41
6.1 How the MODBUSCP function block works ....................................................................... 41
6.2 Parameters of the MODBUSCP function block................................................................... 44
6.3 Address mapping of MODBUSCP function block ............................................................... 49
6.4 Data and standard functions of the MODBUSCP function block ......................................... 52
6.5 Rewiring blocks ................................................................................................................. 54
7 Additional blocks ......................................................................................................................... 55

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 7
Table of contents

7.1 Job list for cyclic frame exchange .......................................................................................55


7.2 Support in CFC ..................................................................................................................56
8 Diagnostics ................................................................................................................................ 57
8.1 Diagnostics with the display elements of the CPU...............................................................57
8.2 Diagnostics messages of FB MODBUSCP .........................................................................58
8.3 Diagnostics messages from FC5/FC6 and FC50/FC60 .......................................................63
8.4 Diagnostics messages of the blocks used...........................................................................63
8.5 Diagnostics messages of SFC24 ........................................................................................63
9 Examples of applications ............................................................................................................. 65
9.1 Sample project in STL ........................................................................................................65
9.2 Sample project in CFC .......................................................................................................67
A Reference .................................................................................................................................. 69

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


8 Programming Manual, 09/2014, A5E32489434-AA
Product description 1
1.1 Scope of delivery
The scope of delivery includes the following order units:
● 1 × CD "SIMATIC Modbus/TCP CP"
The CD contains a setup for installation in the relevant STEP 7 directories:
– "Modbus_TCP_CP" library
– 2 Sample projects
– Documents in German and English
The CD also contains the documents in PDF format.

1.2 Possible applications

Driver in the system environment


The following driver represents a software product for the communication processor (CP).
● The CP 343-1 can be used in the S7-300 automation systems and can establish
communication connections to partner systems.
● The CP 443-1 can be used in the S7-400 automation systems and can establish
communication connections to partner systems.

Function of the FBs


With the supplied function blocks, a communication connection is possible between the
communication module CP and a device that supports the Modbus/TCP protocol. The
function codes 1, 2, 3, 4, 5, 6, 15 and 16 are supported.
Data transfer is handled based on the client-server principle. The SIMATIC S7 can be
operated as client as well as server during the transfer.

TCP/IP with CP
The TCP/IP connections via the CP are static connections that are not terminated during
error-free operation.
With the TCP stack used on the CP, the STEP 7 connection configuration only allows one
use of a particular port number. Certain CP types can maintain and operate connections to
multiple clients simultaneously via the local port 502.
The technical details of this topic are explained in the section "Using connections on port 502
(Page 27)".

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 9
Product description
1.3 Hardware and software requirements

1.3 Hardware and software requirements

Modules for FB MODBUSCP


You will find the current hardware requirements in: SIMATIC Modbus/TCP
(www.siemens.com/s7modbus)

Software versions
The blocks can be used as of STEP 7 V5.4. The blocks AG_LSEND/AG_LRECV V3.1 from
the update of the SIMATIC NET library
(http://support.automation.siemens.com/WW/view/en/22172239) must be used.

Memory requirements
● FB MODBUSCP requires approximately 9 KB of work memory and 10 KB of load
memory.
● FB MB_CPCLI requires approximately 9 KB of work memory and 10 KB of load memory.
● FB MB_CPSRV requires approximately 8 KB of work memory and 9 KB of load memory.
You will find the precise lengths of the function blocks in their properties in the SIMATIC
Manager.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


10 Programming Manual, 09/2014, A5E32489434-AA
Step-by-step instructions 2
The following list provides an overview of the steps in the procedure and the sections in
which the steps are described in this document:
1. Installation of "SIMATIC Modbus/TCP CP" –
refer to the section "Installing the library on the STEP 7 PG/PC (Page 13)"
2. Setting the connection parameters according to the plant configuration -
refer to the section "Configuring the communication connection (Page 17)"
3. Inserting the Modbus/TCP blocks in the user project -
refer to the section "Inserting Modbus/TCP function blocks (Page 25)"
4. Calling the Modbus/TCP block FB108 in the necessary OBs –
refer to the section "How the MODBUSCP function block works (Page 41)"
5. Setting the parameter DB MODBUS_PARAM_CP according to the requirements
(client/server, Modbus/TCP addresses, DB areas, etc.) –
refer to the section "Parameter assignment for Modbus/TCP communication with the
Wizard (Page 32) and Structure of the connection parameters (Page 33)"
6. Parameter assignment of the Modbus/TCP block for initialization and for the runtime -
refer to the section "Parameters of the MODBUSCP function block (Page 44)"
7. Downloading the user program to the CPU and licensing the Modbus/TCP block for this
CPU -
refer to the section "MODBUSCP licensing (Page 37)"

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 11
Putting the function block into operation 3
The CP can be configured via MPI or LAN/Industrial Ethernet. The STEP 7 configuration
software is required.
The following information on STEP 7 and on configuring the communication connection
relates to STEP 7 V5.4. In later versions, sequences, names and directories may change.
Requirements for the configuration are as follows:
● Knowledge of STEP 7
● Knowledge of STL
● Knowledge of PLCs

3.1 Installing the library on the STEP 7 PG/PC

Requirements
The STEP 7 configuration software must be installed.

Procedure
1. Insert the Modbus/TCP CD in the CD-ROM drive of your PG/PC.
If the setup program does not start automatically, install as follows:
– Select the CD-ROM drive in the Windows Explorer
– Open the Setup directory
– Start the file "Simatic S7 ModbusTCP CP V5.0.exe"
2. Follow the instructions displayed by the installation program step by step.
On completion of the installation, you will find the following:
– "Modbus_TCP_CP" library in
\Program Files\Siemens\Step 7\S7LIBS
– 2 sample projects in
\Program Files\Siemens\Step 7\EXAMPLES
– The programming manual in
\Program Files\Siemens\Step 7\S7MANUAL\S7Comm
– The software registration form in
\Program Files\Siemens\Step 7\S7LIBS\Modbus_TCP_CP
The first time you call the Modbus/TCP library or the example, use the "File > Open >
Browse" function of the "Open" dialog to access the library or the example.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 13
Putting the function block into operation
3.2 Assigning CP parameters

This document can be opened using the shortcut as follows:


● "\Program Files\Siemens\Documentation" from the directory "S7MANUAL\S7Comm"
● "Start > SIMATIC > Documentation"

3.2 Assigning CP parameters


The CP is connected to Industrial Ethernet in the "Subnet" list. If you have interconnected
your stations without routers, they must be located in the same subnet.

Procedure
1. Select the list entry with the name of your network.
For a new network, this is normally the list entry "Ethernet(1)".

2. Confirm by clicking "OK".


The parameter assignment is compiled and saved.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


14 Programming Manual, 09/2014, A5E32489434-AA
Putting the function block into operation
3.3 Assigning link partner parameters

3.3 Assigning link partner parameters


In the "CP is Client" mode, an "Other station" is necessary for the connection configuration.

Procedure
1. Select "Properties > Other station > Interfaces".

2. Click on the "New" button.


3. In the type selection box that then appears, select "Industrial Ethernet".

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 15
Putting the function block into operation
3.3 Assigning link partner parameters

4. Confirm by clicking "OK".


The following dialog is displayed.

5. Enter an IP address located in the same subnet as the link partner station.
The subnet mask should be the same as for the partner station.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


16 Programming Manual, 09/2014, A5E32489434-AA
Putting the function block into operation
3.4 Configuring the communication connection

6. Select the subnet that represents the connection between CP interface and the link
partner interface.
7. Confirm by clicking "OK".
The following dialog is displayed.

No settings are required in the "General" tab.

3.4 Configuring the communication connection


For the connection between an S7 CPU and a communication partner/bus connected via
Industrial Ethernet, the CP represents the link. To connect the relevant interface to the link
partner/bus, the connection must be configured.

3.4.1 Configuring the connection in "CP is Client"

Procedure
1. In the STEP 7 project, select the CPU in your open S7-300/400 station.
2. By double-clicking on "Connections" you open the connection configuration.
The "NetPro" program opens with which you can configure your connections.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 17
Putting the function block into operation
3.4 Configuring the communication connection

3. Select "Insert > New Connection...".


The following dialog is displayed.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


18 Programming Manual, 09/2014, A5E32489434-AA
Putting the function block into operation
3.4 Configuring the communication connection

4. For the new connection, select the connection partner "Other station" and "TCP
connection" as the connection.
The following dialog is displayed.

5. Select the "Display properties before inserting" check box.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 19
Putting the function block into operation
3.4 Configuring the communication connection

6. Confirm by clicking "OK".


The following dialog is displayed.

In the dialog, you can set the properties for the connection.

Note
Note that the connection ID (local ID) must be used in the user program when calling the
FB.

7. Set the ID based on the project requirements.


8. Enter a name for the connection.
The "Via CP" box displays the communication processor used to establish the
connection. If you want to use a different plugged-in CP, this can be selected with the
"Route..." button.
– If the S7 is operating as a Modbus client, the "Active connection establishment" check
box must be enabled.
– If the S7 is operating as a Modbus server, the check box must be disabled.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


20 Programming Manual, 09/2014, A5E32489434-AA
Putting the function block into operation
3.4 Configuring the communication connection

9. Change to the "Addresses" tab.


The following dialog is displayed.

In this dialog, the port numbers for both communication partners are specified.
10.Specify the port numbers in the "Addresses" tab.

Note
Selecting the port number:
· In Modbus/TCP communication, the Modbus/TCP servers are normally addressed via
port 502.
· With Modbus/TCP clients, port numbers higher than 2000 are used.

11.Confirm by clicking "OK".


The entries are applied.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 21
Putting the function block into operation
3.4 Configuring the communication connection

3.4.2 Configuring an unspecified connection with "CP is server"

Procedure
1. If the CP operates as a server on a link, communication is activated via an unspecified
connection.
The client needs to handle active connection establishment.
2. After selecting Insert > New connection..., you change to the "Insert New Connection"
dialog.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


22 Programming Manual, 09/2014, A5E32489434-AA
Putting the function block into operation
3.4 Configuring the communication connection

3. For the new connection, instead of the connection partner, select "Unspecified" and "TCP
connection" as the connection.

4. Select the "Display properties before inserting" check box.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 23
Putting the function block into operation
3.4 Configuring the communication connection

5. Confirm by clicking "OK".


This brings you to the "Properties - TCP connection" dialog.

6. Disable the "Active connection establishment" check box.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


24 Programming Manual, 09/2014, A5E32489434-AA
Putting the function block into operation
3.5 Inserting Modbus/TCP function blocks

In the "Addresses" dialog, no settings are made for the "Partner". "IP" and "PORT" do not
have an entry.

7. Confirm by clicking "OK".


The entries are applied.

3.5 Inserting Modbus/TCP function blocks


The following FBs are required for Modbus/TCP communication:
● MODBUSCP
● MB_CPCLI
● MB_CPSRV
To be able to insert these in your project, you need to copy the blocks from the library.
You will also see the parameter data block MODBUS_PARAM_CP as a template in the
library. To simplify your work, you can also copy this to your project.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 25
Putting the function block into operation
3.5 Inserting Modbus/TCP function blocks

Procedure
1. Copy the blocks from the library to insert them in your project.
To do this, open the "Modbus_TCP_CP" library by selecting "File > Open...".
2. In the "Open project" dialog, change to the "Libraries" tab.
3. Select the "Modbus_TCP_CP" library.
4. Click "OK" to confirm the selection.
The library opens.
5. Depending on your configuration, open the "CP 300" or "CP 400" folder by double-
clicking on it.
6. Select the function blocks and copy them with "Edit > Copy".
7. Change to your project.
8. In the STEP 7 project, select the CPU in your open S7-300/S7-400 station.
9. Open the block folder by double-clicking on "S7 Program" and then on "Blocks".
10.Insert the blocks in your program with "Edit > Insert".

Inserting communication blocks


The Modbus/TCP function blocks use the functions AG_SEND and AG_RECV for S7-300 or
AG_LSEND and AG_LRECV for S7-400 and the AG_CNTRL block. You will find these
communication blocks in the "SIMATIC_NET_CP" library.
● CP 300
Copy the functions FC5 (AG_SEND), FC6 (AG_RECV) and FC10 (AG_CNTRL) from the
"CP 300" folder and insert the functions in your project.
● CP 400
Copy the functions FC50 (AG_LSEND), FC60 (AG_LRECV) and FC10 (AG_CNTRL) from
the "CP 400" folder and insert the functions in your project.

Note
Note that the following versions of the FCs are required for error-free operation of FB
MODBUSCP.
S7-400:
· AG_LSEND V3.1 or higher
· AG_LRECV V3.1 or higher
S7-300:
· AG_SEND V4.2 or higher
· AG_RECV V4.8 or higher

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


26 Programming Manual, 09/2014, A5E32489434-AA
Putting the function block into operation
3.6 Using connections on port 502

The Modbus blocks were compiled with the SIMATIC NET Library Update for STEP 7 V5.4.
The SIMATIC NET Library Update for STEP 7 V5.5 + SP2 and PCS 7 V8 also contain the
blocks AG_LSEND and AG_LRECV with version number V3.1. These, however, have a
different time stamp from that of the V3.1 blocks from the update for STEP 7 V5.4.
For this reason, there may be a time stamp conflict when the Modbus blocks are inserted. In
this case, rewire the AG_LSEND and AG_LRECV blocks in the project to a different number
and then wire them back again. This updates all time stamps internally.

AG_CNTRL
With the FC10 AG_CNTRL function from the SIMATIC_NET library, it is possible to terminate
and re-establish an existing connection. To be able to use the resources of the CPU/CP
more effectively, this block was also included in the Modbus/TCP blocks.

Note
The older CPs or older firmware versions do not support this AG_CNTRL. You will find
information about which CP supports AG_CNTRL with which firmware version here: Ethernet
CP and AG_CNTRL (http://support.automation.siemens.com/WW/view/en/33414377)
If the CP being used is not listed here, it cannot be used with the Modbus/TCP blocks
supplied.

3.6 Using connections on port 502


Some CPs can multiplex TCP connections. This means that several Modbus/TCP clients can
connect to port 502 of the CP. The CP functions as a Modbus/TCP server.
Here, you will find information about which CP allows multiple use of port 502 and with which
firmware version: SIMATIC Modbus/TCP (www.siemens.com/s7modbus)

Requirements
To be able to use this function, the following settings need to be made in the connection
parameter assignment in NetPro:
● CP is server
● Port 502 as local port
● Unspecified TCP connection in NetPro
● Passive connection establishment

Note
Note that only 1 connection is configured in NetPro regardless of how many clients access
the CP as a server.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 27
Putting the function block into operation
3.7 Startup behavior of the CP 343-1 and CP 443-1

Number of connections
Via port 502, the CP can communicate with a maximum of 4 clients at any one time.

Displaying the status of the connection


Both in NetPro online and in the special diagnostics of the CP, the status of the connection
can be displayed.
Since only 1 connection is configured in NetPro, the display represents the status of all TCP
connections to the various clients.
If no client has yet established a connection, "Passive connection establishment in progress"
is displayed. As soon as a client has established a connection, "Connection established" is
displayed. It is not possible to recognize how many clients are currently connected to the CP.

Response to errors
In certain error situations, the CP needs to terminate and then re-establish the connection to
be able to return to the basic status. This action is handled by FB MODBUSCP. All existing
connections via port 502 are then terminated.

Tips for the user program


If there are multiple connections via port 502, it is not possible to tell in the user program
which client sent the current Modbus/TCP request. If the clients use different UNIT numbers,
a distinction can be made by evaluating these in the program.

3.7 Startup behavior of the CP 343-1 and CP 443-1


The startup of the CP is divided into the following phases:
● Initialization (CP network on)
As soon as power is applied to the CP, the firmware on the CPU is prepared for operation
after running through a hardware test program.
● Parameter assignment
During the parameter assignment, the CP receives the module parameters assigned to
the current slot. The CP is now ready for operation.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


28 Programming Manual, 09/2014, A5E32489434-AA
Putting the function block into operation
3.8 Migrating from Modbus/TCP CP V4.x to Modbus/TCP CP V5.x

3.8 Migrating from Modbus/TCP CP V4.x to Modbus/TCP CP V5.x


If an earlier version V4.x of "Modbus/TCP CP" is already being used, the S7 program needs
several adaptations. Updating using the menu item "File > Check and Update Accesses" is
not possible because the interface of the block has changed.

Procedure
1. Copy the new Modbus/TCP blocks FB106, FB107, FB108 and DB3 to your project.
If these block numbers are already being used for other blocks, you can also rename
FB108 and DB3 or rewire FB106 and FB107.
2. Open the blocks in which the previously used Modbus/TCP block was called (OB100 and
the cyclic OB).
3. Call the new block FB108 MODBUSCP directly below the previous MODBUSCP call with
a new instance DB.
4. In OB100, transfer the "id" parameter from the previous block call to the new block.
– Start the "Modbus/TCP CP Wizard" and configure the remaining initialization
parameters.
See section "Parameter assignment for Modbus/TCP communication (Page 31)".
– Specify the set DB in the new parameter "db_param".
– If configured, transfer the output parameters ERROR, STATUS and STATUS_FUNC
to the new block.
5. In the cyclic OB, transfer the following parameters from the previous block call to the new
block:
MONITOR, REG_KEY, ENQ_ENR, LICENSED, BUSY, DONE_NDR, ERROR, STATUS,
STATUS_FUNC, IDENT_CODE, UNIT, DATA_TYPE, START_ADDRESS, LENGTH and
WRITE_READ.
6. Delete the previous Modbus/TCP call or comment it out.
7. Download the program to the CPU.
8. Restart the CPU.

Note
You will find the latest information on "SIMATIC Modbus/TCP CP V5.0" in: SIMATIC
Modbus/TCP (www.siemens.com/s7modbus).

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 29
Parameter assignment for Modbus/TCP
communication 4
For communication via a CP 343 and a CP 443, the connection must be configured in
NetPro.
Several connections to different communication partners can be configured and established
at the same time. The number of simultaneously established connections depends on the
CPU and the CP being used.

Parameter data block MODBUS_PARAM_CP


The data required to assign the connections and process the Modbus/TCP frames is defined
in a data block (the parameter data block MODBUS_PARAM_CP). The connection-specific
data is first saved. The connection-specific data is followed by the Modbus/TCP parameters.
A parameter block in which the connection parameters of the NetPro configuration and the
Modbus/TCP parameters are defined is required for each connection. For each new
connection, the data block can be expanded or a new block created and the matching
parameter block inserted with the connection and Modbus/TCP parameters.
The parameter data block can contain the configuration data of all connections. You can also
create a separate parameter data block for each connection.

Note
If there is more than one CP in a station and Modbus/TCP connections are configured via
these, connections with the same ID cannot be saved in the same parameter data block. In
this case, a separate parameter data block must be created for each CP.

A completed parameter data block is included in the "Modbus_TCP_CP" library as an


example.

Structure of DB MODBUS_PARAM_CP

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 31
Parameter assignment for Modbus/TCP communication
4.1 Parameter assignment for Modbus/TCP communication with the Wizard

● Connection parameters
In the first block, the connection-specific parameters "id" and "laddr" are defined. Based
on these parameters, the connection configured in NetPro can be assigned.
● Modbus/TCP parameters
The data required for the mode and address reference is saved in the Modbus/TCP
parameters, for example the mode of the S7 as Modbus/TCP server or Modbus/TCP
client, the Modbus/TCP register addresses and the numbers of the DBs in which the data
is mapped. You must keep to the data structure of the Modbus/TCP parameters because
they cannot be processed correctly otherwise.

Configuration options
You have two options for configuring the connection and Modbus/TCP parameters. On the
one hand, the entries can be made with a Wizard making the parameter assignment
extremely convenient. On the other hand, the parameters can be set by editing the
parameter data block.
These two options are described in the sections "Parameter assignment for Modbus/TCP
communication with the Wizard (Page 32)" and "Structure of the connection parameters
(Page 33)".

4.1 Parameter assignment for Modbus/TCP communication with the


Wizard
The "Modbus/TCP CP Wizard" allows convenient configuration of the connection ID, the
CPU address and the Modbus/TCP parameters in the parameter data block
MODBUS_PARAM_CP. The entire parameter block is created with connection parameters
and Modbus/TCP parameters.
You will find the Wizard in:
· Modbus/TCP CP Wizard
(http://support.automation.siemens.com/WW/view/en/60735352) or
· SIMATIC Modbus/TCP (www.siemens.com/s7modbus).

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


32 Programming Manual, 09/2014, A5E32489434-AA
Parameter assignment for Modbus/TCP communication
4.2 Manual parameter assignment for Modbus/TCP communication

4.2 Manual parameter assignment for Modbus/TCP communication

4.2.1 Structure of the connection parameters

Structure of the connection parameters

Each parameter begins with the prefix "ID_x_", where x stands for the number of the
connection ID. In this documentation, this prefix will be omitted below to improve clarity.
The first two parameters of the block are connection parameters that are used internally in
FB MODBUSCP for the AG_SEND/AG_RECV or AG_LSEND/AG_LRECV calls.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 33
Parameter assignment for Modbus/TCP communication
4.2 Manual parameter assignment for Modbus/TCP communication

The remaining parameters specify the mode of the Modbus/TCP communication and the
mapping of the Modbus/TCP addresses to the SIMATIC addresses. Up to 8 data areas can
be set. At least the first of these data areas must be defined; the other 7 are optional.
The parameters are explained below.

id
A connection ID is assigned for each configured connection in STEP 7 (NetPro). The
connection ID uniquely describes the connection from the CPU via the CP to the link partner.
The number from the connection configuration is entered here. The range of values for this
parameter is 1 to 64.

laddr
The "laddr" parameter is the base address of the CP from HW Config (I address). The
configured value is entered here. The range of values for this parameter depends on the
CPU. The "id" and "laddr" parameters can also be taken from the "Properties" dialog of the
TCP connection.

server_client
This parameter distinguishes client and server mode. If the input is TRUE, the "CP is server"
mode is used. If the setting is FALSE, the "CP is client" mode is used.

single_write
In the "CP is client" mode, if the "single_write" parameter = TRUE, the function codes 5 and
6 are used for write jobs with length 1. If "single_write" = FALSE, function codes 15 and 16
are used for all write jobs.

data_type_x
The "data_type_x" parameter specifies which Modbus/TCP data type is mapped in this DB. If
the value 0 is entered in data_type_x, the corresponding data area is not used.

Identifier Data type Data width


0 Area not used –
1 Coils Bit
2 Inputs Bit
3 Holding register Word
4 Input register Word

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


34 Programming Manual, 09/2014, A5E32489434-AA
Parameter assignment for Modbus/TCP communication
4.2 Manual parameter assignment for Modbus/TCP communication

db_x
The "db_x" parameter specifies the data block in which Modbus/TCP registers or bit values
defined below are mapped. When using a global DB, the DB number 0 is not permitted
because it is reserved for the system. If a data collector block is used in CFC, the DB
number 0 must be specified.
DB number 1 to 65535 (W#16#0001 to W#16#FFFF)

start_x, end_x
"start_x" specifies the first Modbus/TCP address that is mapped in data word 0 of the DB.
The "end_x" parameter defines the address of the last Modbus/TCP address.
● When accessing registers, the data word number in the S7 DB in which the last
Modbus/TCP address is entered is calculated as follows:
DBW number = (end_x – start_x) ∗ 2
● With bit access, the data byte number in the S7 DB in which the last Modbus/TCP
address is entered is calculated as follows:
DBB number = (end_x – start_x) / 8
The defined data areas must not overlap. The "end_x" parameter must not be lower than
"start_x". In case of an error, startup of the FB is aborted with an error. If both values are
identical, one Modbus/TCP address (1 register or 1 bit value) is assigned.
In the section "Address mapping of MODBUSCP function block (Page 49)", there is an
example of the mapping of the Modbus/TCP addresses to S7 memory areas.

4.2.2 Parameter assignment for Modbus/TCP communication

Procedure
1. Copy DB2 from the "Modbus_TCP_CP" library and insert it in your project.
If the number is already being used elsewhere, the DB can be renamed. The parameters
in the MODBUS_PARAM_CP block must not be changed during runtime.
2. Following a change to the parameters, restart the CPU with STOP > RUN.
A parameter block is required for each connection.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 35
MODBUSCP licensing 5
5.1 MODBUSCP licensing
The MODBUSCP block must be licensed on each CPU individually. Licensing takes place in
two steps:
● Reading out the IDENT_CODE and
● entering the registration key REG_KEY.
OB121 must be present in the CPU.

Procedure

Reading out the IDENT_CODE


1. Set the parameters for the MODBUSCP block according to your requirements in a cyclic
OB (OB1 or a cyclic interrupt OB) and in OB100.
Download the program to the CPU and set it to RUN.
2. Open the instance DB of the Modbus/TCP block.

With the menu item "Data block > Open Online" open the DB online. "Monitor block" with
the button is not adequate.

An 18-character string is displayed at the IDENT_CODE output.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 37
MODBUSCP licensing
5.1 MODBUSCP licensing

3. Copy this string from the DB and paste it in the SOFTWARE REGISTRATION FORM.
This form is stored during installation in the library path ..\Program Files\Siemens\Step
7\S7LIBS\Modbus_TCP_CP and is also available on the installation CD.
4. Enter the license number from the product packaging in the form.

5. Send the form to Customer Support


(https://support.automation.siemens.com/WW/view/en/38718979) using a service
request. You will then receive the registration key for your CPU.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


38 Programming Manual, 09/2014, A5E32489434-AA
MODBUSCP licensing
5.1 MODBUSCP licensing

Entering the registration key REG_KEY


The registration code REG_KEY must be specified with each MODBUSCP block call. You
should save the REG_KEY in a global data block via which all MODBUSCP blocks
instructions receive the necessary registration key. The following steps are an example.
1. Copy the ready-made licensing block DB3 from the "Modbus_TCP_CP" library to your
project.
If the DB number is already being used in the project, the license DB can also be
renamed.
2. Open the license DB and copy the 17-character registration key and paste it into the
"Initial value" column.

To

avoid having to enter the registration key REG_KEY again after reloading the CPU, it
needs to be entered permanently in the data block.
3. Change to the data view of the DB with the menu item "View > Data View".
With the menu command "Edit > Initialize Data Block", all the values from the "Initial
value" column are transferred to the "Actual value" column.
4. In the cyclic OB, enter the value "DB3.REG_KEY" for the REG_KEY parameter of the
MODBUSCP block.
5. Download the modified blocks to the CPU.
The registration key REG_KEY can be entered during runtime. It is not necessary to
change from "STOP > RUN".

Result
The Modbus/TCP block is now licensed for this CPU; the LICENSED output bit is set to
TRUE.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 39
MODBUSCP licensing
5.2 Missing or incorrect licensing

5.2 Missing or incorrect licensing


If no or an incorrect registration key is entered, the following LED flashes:
● CPU S7-300: LED SF
● CPU S7-400: LED INTF
An entry relating to the missing license is entered in the diagnostics buffer cyclically.

Description
The error number for a missing license is W#16#A090.

WARNING
If OB121 is missing in the controller, the CPU is set to STOP.

In the case of a missing or incorrect registration key, the Modbus/TCP communication is


processed but W#16#A090 "No valid license available" is always displayed at the STATUS
output. The output bit LICENSED is FALSE.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


40 Programming Manual, 09/2014, A5E32489434-AA
MODBUSCP function block 6
6.1 How the MODBUSCP function block works
The MODBUSCP function block allows communication to be established between a CP 443-
1 or CP 343-1 and a partner that supports the Modbus/TCP protocol. The function codes 1,
2, 3, 4, 5, 6, 15 and 16 are supported.
Depending on the parameter assignment, the FB can be operated both as client and server.
It is also possible to operate a CP as client and server at the same time. To achieve this, to
NetPro connections and 2 FB calls are required.
In terms of the library, there is no limitation regarding the maximum number of Modbus/TCP
blocks running at the same time. There is, however a CPU- and CP-dependent maximum
number of PLC function calls that can run at the same time. The maximum number of PLC
calls can be found in the CPU manual in "Technical specifications > Communication". In the
manual of the CP, you will find how many AG_SEND/AG_RECV or AG_LSEND/AG_LRECV
blocks can be processed simultaneously by the CP.
Internally, the MODBUSCP function block calls the MB_CPCLI (FB106) and MB_CPSRV
(107) blocks. The MB_CPCLI block contains the functionality of the Modbus/TCP client and
the MB_CPSRV block implements the functionality of the Modbus/TCP server.

Tasks of the blocks


● Calling the standard functions for data transfer between CPU and CP
● Generating Modbus/TCP-specific frame headers
● Checking the Modbus/TCP-specific frame headers when received
● Checking whether the addressed data areas exist
● Generating exception frames if an error has occurred (only when the CPU is the server)

Exception code Meaning


1 The sent function code is not supported.
2 There was access to an address that is non-existent or is not permitted.
3 An invalid length was specified for this function code.

● Data transfer from/to the set DB


● Time monitoring of the receipt of data
● License check

Online Help
For the MODBUSCP function block, there is a block online help available in the SIMATIC
Manager. By selecting the block and pressing the "F1" key, the online help with the most
important information on the module opens.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 41
MODBUSCP function block
6.1 How the MODBUSCP function block works

Calling the FB
The MODBUSCP function block must be installed in 2 OBs for the program to run correctly:
● In the startup OB100
● In a cyclic OB
OB1 or in a time-driven OB e.g. OB35.
The same instance data block must be used in both.
The other FBs in the library MB_CPCLI and MB_CPSRV are called at a lower level and must
not be called extra in an OB.
The simultaneous call for FB MODBUSCP in OB1 and in a time-driven OB (e.g. OB35) is not
permitted.
OB121 must be exist in the CPU. You will find more detailed information on this in the
section "MODBUSCP licensing (Page 37)".

Startup behavior of the FB


The MODBUSCP function block is called once unconditionally in OB100.
● The initialization parameters must be assigned according to the plant configuration.
● The initialization parameters are checked for plausibility and entered in the instance DB.
● The runtime parameters are not evaluated during startup.

Cyclic operation of the FB


In cyclic operation, FB MODBUSCP is called in OB1 or in a cyclic interrupt OB.
● The block functions are activated based on the runtime parameters.
● Changes to the runtime parameters are not evaluated while a job is in progress.
● Initialization parameters are not evaluated.

Response to programming errors OB121


If the Modbus/TCP block is not yet licensed for this CPU, OB121 is called.

WARNING
CPU STOP if OB121 is missing
If OB121 is missing, the CPU changes to STOP mode and unforeseeable plant statuses
can arise.
Before putting the plant into operation, make sure that OB121 exists.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


42 Programming Manual, 09/2014, A5E32489434-AA
MODBUSCP function block
6.1 How the MODBUSCP function block works

Job start - CP is client


A positive edge change at the trigger input ENQ_ENR initiates a job. Depending on the input
parameters UNIT, DATA_TYPE, START_ADDRESS, LENGTH and WRITE_READ, a
Modbus/TCP request frame is generated and sent to the partner station via the TCP/IP
connection. The client waits for a reply from the server for the set MONITOR time.
If there is a timeout (no reply from the server), the activated job is ended with an error. A new
job can be initiated.
A validity check is performed after the reply message has been received. If this check is
successful, the required actions are performed and the job is ended without error and the
output DONE_NDR is set. If errors were detected during the check, the job is ended with
error, the ERROR bit is set and an error number is displayed in STATUS.

Activating FB - CP is server
With a positive level at the ENQ_ENR trigger input, the FB is ready to receive a request
frame from the client. The server is passive in this case and waits for a frame from the client.
When the server receives a request frame, it checks the received frame. If the check is
successful, the server sends a reply frame. The server signals the end of frame exchange
with the bit DONE_NDR = TRUE. At this time, the executed function is indicated at the
outputs UNIT, DATA_TYPE, START_ADDRESS, LENGTH and WRITE_READ.
A request frame with an error results in an error message. The ERROR bit is set, the error
number is indicated in STATUS and the request from the client is not replied to.

Data transfer CPU - CP


Data is transferred between the CP and CPU using the standard blocks AG_SEND and
AG_RECV or AG_LSEND and AG_LRECV.
If the user activates a job (CP is client) or if the user receives a frame from the client (CP is
server), the FB calls the standard blocks for the CP in the required number and order.
If the CP receives a frame, initially 6 bytes are read with an AG_(L)RECV. These 6 bytes
contain the length of the remainder of the frame. AG_(L)RECV is then called a second time
with the remaining length. The user data is evaluated only after the frame has been fully
received.

Connection termination by the communication partner


If the TCP connection is terminated by the communication partner, due to system properties
in the "CP is server" mode, the next frame can only be received after 1 second.
In this case in the "CP is client" mode, data can only be sent again after 150 ms. This delay
time is implemented by the function block.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 43
MODBUSCP function block
6.2 Parameters of the MODBUSCP function block

6.2 Parameters of the MODBUSCP function block

Parameter Decl. Type Description Range of val- Init


ues
id IN WORD Connection ID from NetPro 1 to 64 yes
db_param IN BLOCK_ Number of the parameter DB MODBUS_PARAM_CP Depends on yes
DB CPU
MONITOR IN TIME Monitoring time for receiving data from the link partner T#20ms to no
The minimum time that can be set is 20 ms T#+24d20h31
m23s647ms
REG_KEY IN STRING Registration key for licensing Character no
[17]
ENQ_ENR IN BOOL CP is client: Start of job on positive edge TRUE/FALSE no
CP is server: Ready to receive if positive level
LICENSED OUT BOOL License status of block no
Block is licensed TRUE
Block is not licensed FALSE
BUSY OUT BOOL Processing status of the AG_(L)SEND or AG_(L)RECV no
functions
being processed TRUE
not being processed FALSE
DONE_NDR OUT BOOL CP is client: TRUE: Activated job completed without TRUE/FALSE no
error
CP is server: TRUE: Request from client was executed
and reply was sent
ERROR OUT BOOL An error occurred TRUE no
No error occurred FALSE
STATUS OUT WORD Error code 0 to FFFF no
STATUS_FUNC OUT STRING Name of the function that caused the error at STATUS Character no
[8]
IDENT_CODE OUT STRING Identification for licensing Character no
[18] Request the license with this identification string.
UNIT IN/OUT BYTE Unit identifier (INPUT for CLIENT function, OUTPUT for 0 to 255 no
SERVER function)
DATA_TYPE IN/OUT BYTE Data type to be processed (INPUT for CLIENT function, no
OUTPUT for SERVER function)
Coils 1
Inputs 2
Holding register 3
Input register 4
START_ IN/OUT WORD MODBUS start address (INPUT for CLIENT function, 0 to 65535 no
ADDRESS OUTPUT for SERVER function)
LENGTH IN/OUT WORD Number of values to be processed (INPUT for CLIENT no
function, OUTPUT for SERVER function)
Coils: Read function 1 to 2000
Coils: Write function 1 to 1968
Inputs: Read function 1 to 2000

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


44 Programming Manual, 09/2014, A5E32489434-AA
MODBUSCP function block
6.2 Parameters of the MODBUSCP function block

Parameter Decl. Type Description Range of val- Init


ues
Holding register: Read function 1 to 125
Holding register: Write function 1 to 123
Input register: Read function 1 to 125
WRITE_ READ IN/OUT BOOL Write access or read access TRUE/FALSE no
INPUT for CLIENT function, OUTPUT for SERVER func-
tion

General information
The parameters of FB MODBUSCP are divided into two groups:
● Initialization parameters
The initialization parameters are only evaluated and entered in the instance DB when
OB100 is called. The initialization parameters are identified with "yes" in the "Init" column
in the above table.
A change to the initialization parameters during operation has no effect. After changing
these parameters, e.g. in test mode, the instance DB needs to be re-initialized with CPU
"STOP > RUN".
● Runtime parameters
Runtime parameters can be changed during cyclic operation.
In the "CP is client" mode, it does not, however, make any sense to change input
parameters while a job is running. Preparations for the next job and the associated
changes to the parameters should only start after the previous job was ended with
DONE_NDR or ERROR.
In the "CP is server" mode, the output parameters may only be evaluated when
DONE_NDR is set.
The output parameters are dynamic indicators and are therefore only pending for 1 CPU
cycle. This means they have to be copied to other memory areas for further processing or
display in the variable table.

Ranges of values
With the ranges of values of the various parameters, CPU-specific restrictions may need to
be taken into account.

id
A connection ID is assigned for each configured connection in STEP 7 (NetPro). The
connection ID uniquely describes the connection from the CPU via the CP to the link partner.
This connection ID is configured in the connection parameter block included in the parameter
data block. This ID must be entered here.
The range of values for this parameter is 1 to 64.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 45
MODBUSCP function block
6.2 Parameters of the MODBUSCP function block

db_param
The db_param parameter contains the number of the MODBUS_PARAM_CP data block.
The connection-specific and Modbus-specific parameters required for communication
between the CPU and the communication partner are stored in this parameter data block.
The range of values for this parameter depends on the CPU. The DB number 0 is not
permitted because it is reserved for the system. The DB number is entered in plain text as
"DBxy".
If you want to implement several connections, the parameter data block can include the
necessary parameters of all connections in sequence. You can also create a separate
parameter data block for each connection.

MONITOR
The monitoring time MONITOR monitors the incoming data from the communication partner.
The monitoring time is specified in the time format T#... A monitoring time of approximately
1.5 s is recommended.
In "CP is client" mode, the input of the entire reply frame from the server is monitored with
the MONITOR time. If the monitoring time is exceeded, the activated job is ended with an
error. The time is started after the request frame has been sent completely and stopped after
reception of the entire data.
In "CP is server" mode, the input of the second part of the frame is monitored with the
MONITOR time. If the monitoring time is exceeded, an error is signaled. The time is started
after receipt of the Modbus/TCP-specific frame header and stopped after receipt of the
request frame is complete.

REG_KEY
The block must be licensed on every CPU. With correct entry of the registration key in this
parameter, the block is licensed and Modbus/TCP communication can be used without
restrictions.
You will find further information in the section "Licensing".

ENQ_ENR
"CP is client" mode:
The data transfer is initiated on a positive edge. The request message is generated with the
values of the input parameters UNIT, DATA_TYPE, START_ADDRESS, LENGTH and
WRITE_READ. A new job can only be sent if the previous job has been completed with
DONE_NDR or ERROR.
"CP is server" mode:
With a positive level at the input, the FB is activated. Frames can be received from the client.
If the ENQ_ENR input is not set and a connection exists, the received data is discarded.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


46 Programming Manual, 09/2014, A5E32489434-AA
MODBUSCP function block
6.2 Parameters of the MODBUSCP function block

LICENSED
If this output is set to TRUE, the Modbus/TCP block is licensed on this CPU. If the output
has the status FALSE, no or an incorrect license string was entered. You will find further
information in the section "Licensing".

BUSY
If this output is set, AG_(L)SEND or AG_(L)RECV is active.

DONE_NDR
In "CP is client" mode, the activated job ended error-free. With a read function, the response
data from the server has already been entered in the DB; with a write function, the response
to the request message was received from the server.
In "CP is server" mode, the output indicates error-free completed frame exchange with the
client. The job parameters of the client are indicated in the UNIT, DATA_TYPE,
START_ADDRESS, LENGTH and WRITE_READ parameters. These outputs are only valid
as long as DONE_NDR is set.

ERROR
An error is detected when this output is set.
In "CP is client" mode, the activated job ended with an error. The corresponding error
number is indicated at the STATUS output.
In "CP is server" mode, an error was detected in a request frame of the client or when
sending the reply frame. The corresponding error number is indicated at the STATUS output.

STATUS
If ERROR is set, the STATUS output indicates the error number. The error numbers are
described in the section "Diagnostics (Page 57)".
Status information continues to be indicated at this output.

STATUS_FUNC
This parameter indicates the name of the function that caused the error in the form of a
character string.

IDENT_CODE
After the CPU has started up, an 18-character identification code with which the registration
key for Modbus/TCP communication is requested is indicated at this parameter.
You will find further information in the section "MODBUSCP licensing (Page 37)".

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 47
MODBUSCP function block
6.2 Parameters of the MODBUSCP function block

UNIT
In the "CP is client" mode, the UNIT parameter is an input parameter. This input needs to be
set according to the requirements. The FB enters this value in the request frame and checks
the value when it receives the reply.
The UNIT parameter is typically used with protocol converters to address serial slaves
concealed behind a common IP address.
Most devices can be addressed with UNIT = 1.
In the "CP is server" mode, the UNIT parameter is an output parameter. The FB enters the
value from the request frame in the reply. When the job is completed, the output is set to the
received value.

DATA_TYPE
The DATA_TYPE parameter indicates which Modbus/TCP data type is processed with the
current frame. The following values are permitted:

Coils B#16#1
Inputs B#16#2
Holding register B#16#3
Input register B#16#4
In the "CP is client" mode, this is an input parameter, in the "CP is server" mode, it is an
output parameter.
The different data types are directly related to the used function codes.

Data type DATA_TYPE Function Length single_write Function code


Coils 1 read any irrelevant 1
Coils 1 write 1 TRUE 5
Coils 1 write 1 FALSE 15
Coils 1 write >1 irrelevant 15
Inputs 2 read any irrelevant 2
Holding register 3 read any irrelevant 3
Holding register 3 write 1 TRUE 6
Holding register 3 write 1 FALSE 16
Holding register 3 write >1 irrelevant 16
Input register 4 read any irrelevant 4

START_ADDRESS
The START_ADDRESS parameter determines the first Modbus/TCP address that is written
or read.
In the "CP is client" mode, this is an input parameter, in the "CP is server" mode, it is an
output parameter.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


48 Programming Manual, 09/2014, A5E32489434-AA
MODBUSCP function block
6.3 Address mapping of MODBUSCP function block

LENGTH
The LENGTH parameter determines the number of Modbus/TCP values that are written or
read.
In the "CP is client" mode, this is an input parameter, in the "CP is server" mode, it is an
output parameter.
With read functions, a maximum of 125 registers are possible per frame for holding and input
registers. For coils and inputs, a maximum of 2000 bits are possible. With write functions, the
maximum number of registers is 123 for holding registers and 1968 bits for coils. The
registers or bit values processed with a request frame must be located within one DB.

WRITE_READ
This parameter defines whether a read or write function is to be performed. If the
input/output has the value FALSE, it is a read function. The value TRUE defines a write
function.
Only holding registers and coils can be written to. Input registers and inputs can only be
read.
In the "CP is client" mode, this is an input parameter, in the "CP is server" mode, it is an
output parameter.

6.3 Address mapping of MODBUSCP function block

Interpretation of the Modbus/TCP addresses


The Modbus/TCP data model is based on a series of memory areas that have different
characteristics. With some systems, for example MODICON PLCs, the memory areas are
distinguished using the register or bit address. As an example, the holding register with
offset 0 is called register 40001 (memory type 4xxxx, reference 0001).
This often causes confusion because some manuals describe and mean the register
address of the application layer and others the register/bit address actually transferred in the
protocol.
In its parameters, FB MODBUSCP uses start_x and START_ADDRESS; in other words, the
actually transferred Modbus/TCP address. This means that register/bit addresses from
0000H to FFFFH can be transferred with each function code.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 49
MODBUSCP function block
6.3 Address mapping of MODBUSCP function block

Example: Parameter assignment for the data areas

Address mapping
The figure below shows a comparison of the SIMATIC memory areas with the register-
oriented and bit-oriented memory allocation of the Modbus/TCP devices. The figure
references the parameter assignment described above.
The Modbus/TCP addresses shown in black relate to the data link layer, those shown gray
the application layer.
The SIMATIC addresses shown in the "Address" column are the offsets in the DB. In
addition to this, the Modbus/TCP register numbers are entered in the "Name" column in
square brackets, for example Coils[640]

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


50 Programming Manual, 09/2014, A5E32489434-AA
MODBUSCP function block
6.3 Address mapping of MODBUSCP function block

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 51
MODBUSCP function block
6.4 Data and standard functions of the MODBUSCP function block

6.4 Data and standard functions of the MODBUSCP function block

Instance DB
The MODBUSCP function block saves its data in an instance DB. This instance DB is
generated by STEP 7 the first time the FB is called.
The instance data block contains parameters of the type Input, Output, Input/Output and
static variables it requires to run. These variables are retentive and remain valid between FB
calls. The internal execution of the FB is controlled by the variables.
Memory requirements of the instance DB:

Instance DB Work memory Load memory


MODBUSCP Approx. 2 KB Approx. 3 KB

Local variables
In total, the MODBUSCP block requires a maximum of 288 bytes of local data.

Timers
The function block does not use any timers

Memory bits
The function block does not use any memory bits.

Standard FCs for data transfer


FB MB_CPCLI or MB_CPSRV called in FB MODBUSCP uses the blocks
AG_SEND/AG_RECV (S7-300) or AG_LSEND/AG_LRECV (S7-400) from the
SIMATIC_NET library for transferring data between the CPU and the CP.
The MB_CPCLI and MB_CPSRV blocks also use the AG_CNTRL block.
FB MODBUSCP has been tested and released with the following versions of the FCs:

S7-300: FC5 "AG_SEND" version 4.2


FC6 "AG_RECV" version 4.7
FC10 "AG_CNTRL" version 1.4
S7-400: FC50 "AG_LSEND" version 3.1
FC60 "AG_LRECV" version 3.1
FC10 "AG_CNTRL" version 1.0

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


52 Programming Manual, 09/2014, A5E32489434-AA
MODBUSCP function block
6.4 Data and standard functions of the MODBUSCP function block

MODBUSCP – SFCs for other functions


FB MODBUSCP uses the following SFCs from the standard library:
● SFB4 "TON"
● SFC6 "RD_SINFO"
● SFC20 "BLKMOV"
● SFC51 "RDSYST"
● SFC52 "WR-USMSG"

MB_CPCLI and MB_CPSRV – SFCs for other functions


FBs MB_CPCLI and MB_CPSRV use the following SFCs from the standard library:
● SFC20 "BLKMOV"
● SFC24 "TEST_DB"
● SFB4 "TON"

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 53
MODBUSCP function block
6.5 Rewiring blocks

6.5 Rewiring blocks


If the numbers of the functions and function blocks are already being used in your project or
if the number range is reserved for other applications, you can rewire the called functions
internally FC5/FC50, FC6/FC60, FC10 or the function blocks MB_CPCLI and MB_CPSRV.
The MODBUSCP block can be rewired or renamed.
The system functions SFC6, SFC20, SFC24, SFC51 and SFC52 and the system function
block SFB4 cannot be renamed/rewired.

Sequence when rewiring


In the SIMATIC Manager of STEP 7, several rules relating to block numbers need to be kept
in mind when rewiring.
If you want to rewire blocks from the Modbus/TCP library, keep to the following order:
1. FC5/FC50 AG_SEND/AG_LSEND
FC6/FC60 AG_RECV/AG_LRECV
2. FB106 MB_CPCLI
FB107 MB_CPSRV
3. FB108 MODBUSCP
Not all functions or function blocks need to be rewired. Even if you only want to rewire some
of these, the order must be adhered to.

Procedure
1. Call up information about the addresses used with "Options > Reference Data > Display".
2. Set the address priority in the object properties of the block folder to "Absolute value".
3. In the SIMATIC Manager, select the "Options > Rewire" function to rewire the addresses
into free areas.
4. To be able to continue using symbols in diagnostics tools, update the symbol table with
the changes.
5. If you want to check the changes, select "Options >Reference Data >Display".

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


54 Programming Manual, 09/2014, A5E32489434-AA
Additional blocks 7
To allow convenient configuration of the Modbus/TCP blocks, several open source blocks
are available. The options for downloading the blocks and a detailed description can be
found here:
● FAQ add-on blocks for Modbus/TCP
(http://support.automation.siemens.com/WW/view/en/62830463)
● SIMATIC Modbus/TCP (www.siemens.com/s7modbus)

7.1 Job list for cyclic frame exchange

Functionality
With the "Job_List" block, it is possible to process several Modbus/TCP frames one after the
other with little programming effort. The block is inserted before the Modbus/TCP block and
connected to it. As default, the number of frames is 5, but this can be increased to any
number. The cyclic processing of the list is controlled by the CYCLICAL input.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 55
Additional blocks
7.2 Support in CFC

7.2 Support in CFC

Functionality
To support configuration in CFC, it is possible to configure the Modbus values not using
global DBs but using "data collector FBs". In this case, the send and receive buffers for the
values are dragged to the CFC chart.

Example
The data collector FBs are placed in the CFC chart. The "IDB" output is connected to the db
parameters in the parameter data block.
The Modbus values can subsequently be connected directly from the channel blocks to the
data collector FB.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


56 Programming Manual, 09/2014, A5E32489434-AA
Diagnostics 8
Diagnostics functions
The diagnostics functions of the CP allow you to localize errors quickly. The following
diagnostics options are available:
● Diagnostics using the display elements of the CP
● Diagnostics via the STATUS output of the MODBUSCP function block

Display elements
Display elements are LEDs on the CP. The display elements indicate the operating status or
possible error states of the CP. The display elements give you an initial overview of any
internal or external errors that have occurred as well as interface-specific errors.

STATUS output of FB MODBUSCP


To allow error diagnostics, the MODBUSCP function block has a STATUS output. By
reading the STATUS output, you can obtain general information about errors that have
occurred in the communication. You can evaluate the STATUS parameter in the user
program.
The STATUS_FUNC outputs the name of the function that caused the error.

8.1 Diagnostics with the display elements of the CPU


The display elements of the CP provide information about the module. The following display
functions need to be distinguished:

Group error displays

INTF Internal errors


EXTF External errors

Special displays

CP 343-1
RX/TX a frame is transferred via the interface
CP 443-1
TXD a frame is sent via the interface
RXD a frame is received via the interface

You will find a detailed description of the display elements in the manual of the CP.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 57
Diagnostics
8.2 Diagnostics messages of FB MODBUSCP

8.2 Diagnostics messages of FB MODBUSCP

Messages at the STATUS outputs of the FB


The MODBUSCP function block has 2 status outputs: STATUS and STATUS_FUNC.
STATUS indicates all error messages. STATUS_FUNC indicates the name of the function
that caused the error. The STATUS values are valid if ERROR is set. Below is a listing of the
error messages of specific to the FBs.

Error messages from the called SFCs and FBs


FBs MODBUSCP, MB_CPCLI and MB_CPSRV use the standard blocks SFC6, SFC20,
SFC24, SFC51 and SFC52 as well as AG_SEND/AG_LSEND and AG_RECV/AG_LRECV.
The error messages of these blocks are passed unchanged to STATUS.
You will find information on these error messages in the diagnostics buffer or the online help
for the SFCs/FBs in the SIMATIC Manager.

Status Event text Remedy


(hex)
A001 The parameter DB MODBUS_PARAM_CP is too short. Correct the length of the DB
MODBUS_PARAM_CP.
A002 The end_x parameter is lower than start_x. Correct the parameter settings
for start_x and end_x.
A003 A DB to which Modbus addresses are to be mapped is Lengthen the DB.
too short. CP is client:
Minimum length: Correct the job parameters
with registers: START_ ADDRESS or
(end_x - start_x + 1 ) * 2 + 2 LENGTH.
- with bit values: CP is server:
(end_x - start_x ) / 8 + 3 Change the client request.
other possible causes:
• CP is client: wrong call parameter
• CP is server: incorrect address range in the client
request frame. The CP replies with an exception
frame.
A004 Only CP is client: Correct the call parameters.
An invalid combination of DATA_TYPE and Only data types 1 and 3 can be
WRITE_READ was specified. written.
A005 CP is client: CP is client:
An invalid value was specified in the LENGTH pa- Correct the LENGTH parameter.
rameter. CP is server:
CP is server: Change the number in the re-
The number of registers/bits in the request frame is quest frame.
invalid. The CP replies with an exception frame.
Ranges of values:
Read coils/inputs 1 to 2000
Write coils 1 to 1968
Read registers 1 to 125
Write holding registers 1 to 123

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


58 Programming Manual, 09/2014, A5E32489434-AA
Diagnostics
8.2 Diagnostics messages of FB MODBUSCP

Status Event text Remedy


(hex)
A006 The area specified with DATA_TYPE, CP is client: Correct the pa-
START_ADDRESS and LENGTH does not exist in rameter combination
data_type_1 to data_type_8. DATA_TYPE, START_
CP is server: ADDRESS and LENGTH.
The CP replies with an exception frame. CP is server: Change the cli-
ent's request or correct the
parameter assignment for da-
ta_type_x.
A007 CP is client: An invalid monitoring time was set for Correct the parameter assign-
MONITOR. A value >= 20 ms must be entered. ment.
A008 Within the set monitoring time MONITOR, the activat- Check the settings and if appli-
ed AG-RECV signals nothing received, e.g. partner not cable error messages of the link
ready. partner. Check whether or not
All connections via port 502 are terminated and re- the link partner requires a spe-
established. cific UNIT identifier.
A009 CP is client: The received Transaction Identifier TI Record frames to check the data
does not match the identifier sent. of the link partner.
All connections via port 502 are terminated and re-
established.
A00A CP is client: The received UNIT does not match the
one that was sent.
All connections via port 502 are terminated and re-
established.
A00B CP is client: The received function code is not the CP is client:
same as the one sent. Record frames to be able to
CP is server: An invalid function code was received. check the data of the communi-
The CP replies with an exception frame. cation partner.
All connections via port 502 are terminated and re- CP is server:
established. Change the client request. The
FB MODBUSCP processes the
function codes 1, 2, 3, 4, 5, 6,
15 and 16.
A00C The received byte count does not match the number of Record frames to check the data
registers/bits. of the communication partner.
CP is server: The CP sends an exception frame.
All connections via port 502 are terminated and re-
established.
A00D Only when CP is client: The register address/bit ad-
dress or the number of registers/bits in the reply frame
is not the same as in the request frame.
A00E The length information in the Modbus-specific frame Record frames to check the data
header does not match the specified number of regis- of the communication partner
ters/bits or the byte count in the frame. The FB dis-
cards the data.
All connections via port 502 are terminated and re-
established.
A00F A Protocol Identifier other than 0 was received.
All connections via port 502 are terminated and re-
established.
A010 A DB number was assigned twice in the parameters Correct the parameter assign-
db_1 to db_8. ment for db_x.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 59
Diagnostics
8.2 Diagnostics messages of FB MODBUSCP

Status Event text Remedy


(hex)
A011 An invalid value was specified for the DATA_TYPE Correct the call parameters.
input parameter (valid values are 1, 2, 3 and 4).
A012 The configured areas data_type_1 and data_type_2 Correct the parameter assign-
overlap. ment.
A013 The configured areas data_type_1 and data_type_3 The data areas must not have a
overlap. common register address area.

A014 The configured areas data_type_1 and data_type_4


overlap.
A015 The configured areas data_type_1 and data_type_5
overlap.
A016 The configured areas data_type_1 and data_type_6
overlap.
A017 The configured areas data_type_1 and data_type_7
overlap.
A018 The configured areas data_type_1 and data_type_8
overlap.
A019 One of the db_x parameters was set to 0 even though Correct the parameter setting for
the associated data_type_x is set to > 0. DB0 must not db_x to > 0.
be used because this is reserved for the system. If you use a data collector FB,
check the parameter assign-
ment in CFC.
A01A Incorrect length in the header: 3 to 253 bytes are per- Record frames to check the data
mitted. of the communication partner.
All connections via port 502 are terminated and re-
established.
A01B CP is server and function code 5:
An invalid status for Coil was received.
An exception frame is sent.
A01E Invalid data was received that could not be assigned. Check the error message of the
All connections via port 502 are terminated and re- link partner. If necessary, check
established. the data by recording frames.
A01F FB MODBUSCP is in an illegal operating status. Contact Product Support.
A023 The configured areas data_type_2 and data_type_3 Correct the parameter assign-
overlap. ment.
A024 The configured areas data_type_2 and data_type_4 The data areas must not have a
overlap. common register address area.

A025 The configured areas data_type_2 and data_type_5


overlap.
A026 The configured areas data_type_2 and data_type_6
overlap.
A027 The configured areas data_type_2 and data_type_7
overlap.
A028 The configured areas data_type_2 and data_type_8
overlap.
A034 The configured areas data_type_3 and data_type_4
overlap.
A035 The configured areas data_type_3 and data_type_5
overlap.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


60 Programming Manual, 09/2014, A5E32489434-AA
Diagnostics
8.2 Diagnostics messages of FB MODBUSCP

Status Event text Remedy


(hex)
A036 The configured areas data_type_3 and data_type_6
overlap.
A037 The configured areas data_type_3 and data_type_7
overlap.
A038 The configured areas data_type_3 and data_type_8
overlap.
A045 The configured areas data_type_4 and data_type_5
overlap.
A046 The configured areas data_type_4 and data_type_6
overlap.
A047 The configured areas data_type_4 and data_type_7
overlap.
A048 The configured areas data_type_4 and data_type_8
overlap.
A056 The configured areas data_type_5 and data_type_6
overlap.
A057 The configured areas data_type_5 and data_type_7
overlap.
A058 The configured areas data_type_5 and data_type_8
overlap.
A067 The configured areas data_type_6 and data_type_7
overlap.
A068 The configured areas data_type_6 and data_type_8
overlap.
A078 The configured areas data_type_7 and data_type_8
overlap.
A079 The connection ID specified for the id parameter is not Correct the parameter assign-
included in the parameter DB MODBUS_PARAM_CP. ment for the id input.
A07A An invalid value was specified for the id parameter
(value range from 1 to 64).
A07B The specified ID is included twice in the parameter DB. Correct the parameter assign-
A07C An invalid value was specified for the data_type_x ment in the DB
parameter (valid values are 0 to 4). MODBUS_PARAM_CP.

A07D The data_type_1 parameter does not contain an entry. Correct the parameter assign-
The parameter area "_1" is the initial area and must be ment in the DB
set. MODBUS_PARAM_CP.
A07E The number of the instance DB of the MODBUSCP
block was specified in db_x.
A080 Different instance DBs were used for the MODBUS The MODBUS block must be
block in OB100 and in the cyclic OB. called with the same instance
DB in the startup OB and in the
cyclic OB.
A081 Only for CP is client and function code 5: Record frames to check the data
The data of the reply frame is not the echo of the re- of the communication partner.
quest.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 61
Diagnostics
8.2 Diagnostics messages of FB MODBUSCP

Status Event text Remedy


(hex)
A082 Only for CP is client and function code 6: Record frames to check the data
The received register value is not the same as the one of the communication partner.
sent.
A083 CP is client: A job was triggered while the previous job Only start a new job when the
is still in progress. The job will not be executed. previous job ended with DONE_
This is status information. The ERROR bit is not set. NDR = TRUE or ERROR =
TRUE.
A085 Due to an illegal write access an internal error has Check that there is no illegal
occurred during the license check. write access to the license DB in
the S7 program. The structure of
REG_KEY must not be modi-
fied. If necessary, contact Prod-
uct Support.
A086 An attempt was made to write to a write-protected data Remove the write protection or
block. use a different DB.
A090 The MODBUSCP block has not yet been licensed for Read out the identification code
this CPU. for this CPU at the
This is status information. The ERROR bit is not set. IDENT_CODE output and re-
MODBUS communication is possible even without quest the registration key. Refer
license. to the section "Licensing
(Page 37)".
A091 Only when CP is client: An exception frame with ex- The communication partner
ception code 1 was received as the reply. does not support the requested
function.
A092 Only when CP is client: An exception frame with ex- Correct LENGTH or
ception code 2 was received as the reply. START_ADDRESS in the FB
There was access to a non-existent or illegal address call.
on the communication partner.
A093 Only when CP is client: An exception frame with ex- The communication partner
ception code 3 was received as the reply. cannot process the received
frame (for example, it does not
support the requested length).
A094 Only when CP is client: An exception frame with ex- The communication partner is in
ception code 4 was received as the reply. a status in which it cannot pro-
cess the received frame.
A095 Only when CP is client: An exception frame with an Check the error messages of
unknown exception code was received as the reply. the communication partner and
if necessary record the frames
to check the data.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


62 Programming Manual, 09/2014, A5E32489434-AA
Diagnostics
8.3 Diagnostics messages from FC5/FC6 and FC50/FC60

8.3 Diagnostics messages from FC5/FC6 and FC50/FC60


Error messages of the linked blocks AG_SEND/AG_RECV (FC5/FC6) or
AG_LSEND/AG_LRECV (FC50/FC60) at the STATUS output.

STATUS Event text Remedy


(hex)
7xxx You will find more detailed information Refer to the online help
in the online help of the SIMATIC "SIMATIC Manager > select block
Manager. > F1 key > Ethernet > see also > Evaluation
of the displays"
8xxx You will find more detailed information Refer to the online help
in the online help of the SIMATIC "SIMATIC Manager > select block
Manager. > F1 key > Ethernet > see also > Evaluation
of the displays"

8.4 Diagnostics messages of the blocks used


Error messages of the linked in blocks RD_SINFO (SFC6), BLKMOV (SFC20), SFC51
(RDSYSST), SFC52 (WR_USMSG) and AG_CNTRL at the STATUS output.

STATUS Event text Remedy


(hex)
7xxx You will find more detailed information in the Refer to the online help
online help of the SIMATIC Manager. (SIMATIC Manager -> select
block
-> F1 key)
8xxx You will find more detailed information in the Refer to the online help
online help of the SIMATIC Manager. (SIMATIC Manager -> select
block
-> F1 key)

8.5 Diagnostics messages of SFC24


Error messages of SFC24 at the STATUS output.

STATUS Event text Remedy


(hex)
80A1 DB number = 0 or too high for the CPU Select a permitted DB number.
80B1 The DB does not exist on the CPU All data blocks specified in db_x
must be created and transferred
to the CPU.
80B2 DB UNLINKED Do not generate DB as
UNLINKED.

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 63
Diagnostics
8.5 Diagnostics messages of SFC24

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


64 Programming Manual, 09/2014, A5E32489434-AA
Examples of applications 9
During the installation, 2 sample projects are stored in \Program
Files\Siemens\Step7\Examples:
● 1 sample project in STL "MB_TCP_CP" and
● 1 sample project in CFC "MB_TCP_CP_CFC".

Note
Please note that the supplied sample projects are only intended to provide orientation when
handling the Modbus/TCP blocks and that they are not suitable for use in productive plants.

The program examples consist of the following blocks:


● Startup block OB100 with an FB108 call
● Programming error OB121
● Cyclic mode OB1 or OB35 with an FB108 call
● Global data blocks for starting a job (e.g. with the aid of a variables table) and for
licensing
● Data blocks for register and bit values
The following sections illustrate the use of the MODBUSCP FB in a simple program
example.

9.1 Sample project in STL


In the sample project in STL, SIMATIC stations were created for all function variants.
● SIMATIC station is S7-300 and S7-400
● SIMATIC station is client or server

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 65
Examples of applications
9.1 Sample project in STL

Blocks used
The blocks listed are used in the supplied sample project for S7 stations with FB
MODBUSCP.

Block Symbol Comment


OB 1 CYCL_EXC Cyclic program execution
OB 100 COMPLETE RESTART Startup OB for cold restart
OB 121 PROG_ERR Programming error OB
FB 108 MODBUSCP User block FB MODBUSCP
FB 106 MB_CPCLI FB MB_CPCLI called internally
FB 107 MB_CPSRV FB MB_CPSRV called internally
DB 1 CONTROL_DAT Work DB CONTROL DAT for FB MODBUSCP
DB 2 MODBUS_PARAM_CP_DB2 Parameter DB for FB MODBUSCP
DB 3 LICENSE_DB License DB for FB MODBUSCP
DB 11 DATA_AREA_1 Values DB for area 1
DB 12 DATA_AREA_2 Values DB for area 2
DB 13 DATA_AREA_3 Values DB for area 3
DB 14 DATA_AREA_5 Values DB for area 5
DB 15 DATA_AREA_6 Values DB for area 6
DB 16 DATA_AREA_7 Values DB for area 7
DB 108 IDB_MODBUS Instance DB for FB MODBUSCP

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


66 Programming Manual, 09/2014, A5E32489434-AA
Examples of applications
9.2 Sample project in CFC

9.2 Sample project in CFC


In the sample project in CFC, stations were created for the variants SIMATIC S7-400 station
is client or server.

Blocks used
The blocks listed are used in the supplied sample project for S7 stations with FB
MODBUSCP. The system functions and system function blocks and the blocks generated by
CFC are not listed.

Block Symbol Comment


OB 35 CYC_INT5 Cyclic program execution
OB 100 COMPLETE RESTART Startup OB for cold restart
OB 121 PROG_ERR Programming error OB
FB 8 R_TRIG Detection of a positive edge
FB 24 CTU Count up counter
FB 99 Save_STATUS Save the error
FB 106 MB_CPCLI FB MB_CPCLI called internally
FB 107 MB_CPSRV FB MB_CPSRV called internally
FB 108 MODBUSCP User block FB MODBUSCP
FC100 AG_CNTRL FC for connection establishment and termination
FC 500 AG_LSEND FC for sending data
FC 600 AG_LRECV FC for receiving data
DB 1 MEMORY_DB DB for runtime parameters (only when S7 is server)
DB 2 MODBUS_PARAM_CP_DB2 Parameter DB for FB MODBUSCP
DB 3 LICENSE_DB License DB for FB MODBUSCP
DB 11 DATA_AREA_1 Values DB for area 1
DB 12 DATA_AREA_2 Values DB for area 2
DB 13 DATA_AREA_3 Values DB for area 3
DB 14 DATA_AREA_5 Values DB for area 5
DB 15 DATA_AREA_6 Values DB for area 6
DB 16 DATA_AREA_7 Values DB for area 7

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 67
Examples of applications
9.2 Sample project in CFC

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


68 Programming Manual, 09/2014, A5E32489434-AA
Reference A
The MODBUS Organization
MODBUS APPLICATION PROTOCOL SPECIFICATION
V1.1b, December 28, 2006
Modbus home page (http://www.modbus.org)

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


Programming Manual, 09/2014, A5E32489434-AA 69
Reference

SIMATIC Modbus/TCP communication using CP 343-1 and CP 443-1


70 Programming Manual, 09/2014, A5E32489434-AA

You might also like