Overview
The DigitroniKTM SDC40A is a compact (96mm x 96mm)
digital controller. The SDC40A features a wide variety
of input options: thermocouples, resistance temperature
detectors, DC voltage and DC current inputs are supported.
Control outputs consist of time proportional PID (relay
output, voltage output), cur rent output PID, position
propor tional PI D, a nd heat /cool PI D. T he SDC4 0A
simplifies control with PID auto tuning and systems. The
SDC40A can optionally be provided with a maximum of 12
remote switch inputs and a maximum of 8 event outputs for
automatic operation in combination with a PLC.

Features
• Four or five digit display.
• Accuracy of ±0.1% FS.
• 100ms input sampling cycle. • Two user-defined pushbuttons are available.
• Input type and range are selectable by operator keys. • A 10-segment bargraph displays 0-100% control output
• Up to eight individual set points. at a glance. It can also be used as a "Green belt" OK
• Eight groups of PID control constants. These can also be indicator, event output monitor, remote switch input or
automatically set by autotuning. motor opening monitor.
• Group of gain constants enables variable gain control. • To enable use in a wide range of application options
• Set point change rate can be set using the SP ramp function. include:
• Two event outputs are standard. H Events (3, 8 points) H Digital inputs (4, 12 points)
• The remote SP model features one group of ratio H Auxiliary output (1 or 2 points)
constants for ratio control. H Serial communications (RS-485, RS-232C)
• Computer backup of process data is available in the • Basic models:
remote SP model. · Standard model · Remote SP model
• Internal cascade algorithm provides internal linking of · Internal cascade model
the primary and secondary controllers in one device. • CE approval obtained

Basic function block diagram


• Standard model, and remote SP model
Analog Input 1 Output limits Fixed MV output Control output OUT
Process variable (PV) inputs • Range selection • Bias
• Square root • Filter • High/low limit • Fixed MV value 1 • A/M • Current
• Thermocouple • RTD
• Scaling • Broken line approximation • Variation limit • Fixed MV value 2 • Voltage
• mA • mV PV
• Ratio (1) (12 segments) • Fixed MV value 3 • Relay
• Motor drive
Event output (2, ★ 3 to 8) • Heat/cool
★ Remote switch input (RSW) • LSP number (8) • RSP ration (8)
• SP • MV
(4, 12 inputs) • PID group number (7) • LSP shift RSW EV
Control unit • PV • MFB
• A/M • RUN/READY
• PID (8) • DEV • Status event
• R/L • Computer backup
• RSP • Instrument alarm
• Direct/reverse • AT • Auto tuning+
• Process diagnosis
• Fixed MV value output (3) Neuro & Fuzzy
• RUN/READY ★ Auxiliary outputs (1, 2)
Local set point • SP setting • SP ramp LSP R/L SP selection AUX
• SP • RSP
(LSP) • LSP selection (8) • SP limit selection • Gain (9)
• PV • MV
• Direct/reverse • DEV • MFB
(Remoto SP model only) action selection
Analog input 2 RSP • SP limit
Remote set point (RSP) • Input selection • Filter
• 4 to 20mA • Square root extraction • Broken line approxi-
• 1 to 5V operation mation (12 segments)
• Scaling • SP limit ★ Communication input/output
• Ratio (1) • RSP ratio (7)
• Bias COMM • RS-485
• RS-232C
Motor feedback MFB
• Full open/full close adjustment
Smart loader
• Data transmit/receive

Instrument power supply


AC Model 90 to 264Vac
DC Model 21.6 to 26.4Vdc ★ : Optional functions

1
• Internal cascade model
Analog input 2 • Range selection • Broken line Control
Process variable • Square root approximation Output limit Fixed mV output output OUT
input (2) (PV2) • Scaling (12 segments)
• 4 to 20mA • Current
• Ratio (1) • PV1 PV2
• 1 to 5V exchange PV2 • High/low • Fixed mV value 1 • Voltage MV 2
• Bias • A/M
limit • Fixed mV value 2 • Relay
• Filter
Slave control unit • Fixed mV value 3 • Motor drive
★ Remote switch (RSW) • LSP number • Fixed MV • PID • Heat/cool
inputs, (4 or 12) • PID group number value output • Auto tuning
• A/M • LSP shift • RUN/READY
Event output (2, *3 to 8)
• R/L • RUN/READY
• Direct/reverse • AT SP2 • SP1, 2 • MV1, 2
R/L • PV1, 2 • MFB
Slave setting • LSP setting • SP limit S-LSP
selection • DEV1, 2 • Each status event
(S-LSP) • LSP selection (2) EV • RSP • Instrument alarm
RSP • RSP scaling • Process diagnosis
• RSP ratio (7)
• SP limit MV 1 ★ Auxiliary output (1, 2)
• Variation limit Main control unit
• SP1, 2 • MV1, 2
Motor feedback MFB • PID
• Full open/full close adjustment • PV1, 2 • DEV1, 2
• Gain (9)
Analog input 1
AUX • S-LSP • RSP
• Auto tuning +
Process variable • Input system • Filter • MFB
Neural & Fuzzy
input 1 (PV1) selection • Broken line • Direct/reverse
• Thermocouple • RTD • Square root approximation selection ★ Communications
• DC current • DC voltage • Scaling (12 segments) PV1 • RUN/READY
• Ratio (1) • PV1 PV2 COMM • RS-485
• Bias exchange • RS-232C
Main setpoint • LSP setting • LSP ramp SP1
(M-LSP) • LSP selection (6)
Smart loader
• Data transmit/receive

Instrument power supply


AC Model 90 to 264Vac
DC Model 21.6 to 26.4Vdc ★ : Optional functions

Specifications
Analog Type of inputs A variety of thermocouples, RTDs, mV and mA.
input 1 Input display ±0.1% FS±1U (under standard conditions)
(PV1 input) accuracy This may be affected by indication value conversion.
Input sampling 100ms
cycle
Input digital filter Variable 0.0 to 120.0s (there is no filter at 0.0)
Input bias -1000 to +1000U (U: °C, KPa, % and other standard industrial units)
Input ratio 0.001 to 9.999
Input broken line 12 point broken line approximation can be assigned to analog inputs 1 or 2.
approximation
Square root 0.0 to 10.0% FS (no square root calculation is performed at 0.0)
operation dropout
Input bias current Thermocouple, DC voltage input: ±1.3µA max. (peak, standard conditions)
-3µA max. in the linear V range above 1V
Input impedance DC current input: 50Ω ±10% (under operating conditions)
Measuring current RTD input: 1.04mA ±0.02mA, terminal A (under operating conditions)
Influence of wiring Thermocouple: Variation in the displayed value due to input conversion when the wiring resistance
resistance at both ends is 250Ω:
・ M01, L02; 35µV max. ・ L01; 60µV max. ・ Others; 750µV max.
RTD: ±0.01% FS/Ω max. within wiring resistance range of 0 to 10Ω.
±0.02% FS/Ω in the range whose minimum resolution is 0.01°C.
The allowable wiring resistance is 85Ω max. (except for 0.01°C resolution)
(A zener barrier is available for on site adjustment.)
Allowable parallel Allowable parallel resistance for thermocouple break detection is 1MΩ min.
resistance
Maximum Thermocouple, mV input: -5 to +15V
allowable input mA input: 28mA
Burnout Thermocouple input: Upscale + Alarm indication (AL01) (including the DC mV range)
DC voltage input: Downscale + Alarm indication (AL02)
DC current input: Downscale + Alarm indication (AL02)
However, near 0% FS in the 0 to 20mA range, neither burnout nor alarm indication
is performed.
RTD input: When "C" wire is broken: Upscale + Alarm indication (AL01 + AL09)
When resistance element and "A" wire, or resistance element and "B" wire, or "A" wire
and "B" wire are broken: Upscale + Alarm indication (AL01 + AL07)
When "B" wire, or resistance element and "C" wire, "A" wire and "C" wire, or "B" wire and
"C" wire, or resistance element, "B" wire and "C" wire, or "A" wire, "B" wire and "C" wire
are broken: Upscale + Alarm indication (AL01 + AL08)
Over range detec- Higher than 110% FS: Upscale
tion threshold Lower than -10% FS: Downscale (however, downscaling is not performed by F50 and P50 models.
The lower indication limit of the B19 model is 20°C/60°F.)
Cold junction compen- ±0.5°C (standard conditions)
sation accuracy
Cold junction compen- Compensation inside the instrument or compensation outside the instrument (0°C only) is
sation method selectable.

2
Analog Type of input 4 to 20mA or 1 to 5Vdc
input 2 Input indication ±0.1% FS±1U (standard conditions), when converted to displayed value (may differ, depending on
(RSP input accuracy range)
of remote
Input sampling cycle 0.1s
SP model or
PV2 input Input digital filter Variable 0.0 to 120.0s (there is no filter at 0.0)
of internal Input bias -19999 to +30000U
cascade Input ratio 0.001 to 30,000 (gain cannot be used in case of selection of the multi ratio of 8 groups. Trade off.)
model)
Input broken line 12 broken lines of approximation
approximation (which can be assigned to either of analog inputs 1 or 2.)
Square root 0.0 to 10.0% FS (no square root calculation is performed at 0.0.)
operation threshold
Scaling -19999 to +26000U (reverse scaling is also possible. The decimal point position can be changed.
Resolution is 1/26000.)
Input bias current 1 to 5V input: +10µA max. (under operating conditions)
Input impedance 1 to 5V input: 1MΩ min. (under operating conditions)
4 to 20mA input: 50Ω ±10% (under operating conditions)
Allowable 1 to 5V input: 0 to 6V
maximum input 4 to 20mA input: 28mA
Burnout Downscale + Alarm indication (AL04)
Over range detection More than 110% FS: Regarded as upscale..
threshold Less than -10% FS: Regarded as downscale
PV1 PV2 switch Internally switchable in the internal cascade model.
Indications PV and SP indication 5-digit 7-segment LED
and setting Function indication 2-digit 7-segment LED
LED bar Ten LED segments out of twelve indicate control output:
・ When motor opening indication (2G) is selected, ten segments are used.
・ When the OK indicator function is selected, all twelve segments are used as a "green belt".
・ This LED bar can also be used to monitor events 4 to 8 and RSW 1 to 12.
Status indication 18 LEDs (some models do not include all indicators)
Operating keypad 13 rubber keys (there may be dead keys depending on model).
Number of set 1 to 8 points (selection and changeover use available) with the internal cascade model, up to 6
points points are allowed on the master side, up to 2 points are allowed on the slave side.
Memory storage Non-volatile semiconductor memory (EEPROM)
Indication ranges -10 to +110% FS of range or scaling value (-10% FS is not applicable for F50, P50 and B18 models.)
Setting range -19999 to +26000U (when an SP limit is applied, the relevant value is used.)
Indication masking The least significant digit can be masked for 4-digit indication.
SP limits Low limit: -19999U to high limit value
High limit: Low limit value to 26000U
SP ramp UP ramp: 0 to 26000U (no ramp at 0) Down ramp: 0 to 26000U (no ramp at 0)
(separately set for The measurement interval can be selected from among the following:
LSP and RSP) ・ U/hr ・ 0.1U/hr ・ U/min ・ 0.1U/min
Control Model number 0D 2G 5G 6D 3D, AK, 5K, 9K, BK
output Type of output SPDT relay M/M driving relay Current output Voltage output (load *See Table 1.
contact output contact output (4 to 20mAdc) current is adjustable)
Control action Time proportional Position propor- Current propor- Time proportional 2-stage (heat/
PID tional PID tional PID PID cool) PID
No. of PID groups 8 groups 8 groups 8 groups 8 groups 4groups on each of
heat and cool sides
PID autotuning Autotuning allowed. Autotuning allowed. Autotuning allowed. Autotuning allowed. Autotuning not allowed.
Output rating Contact rating: Contact ratings: Max, allowable load Max. allowable load Table 1
5A 2.5A (30Vdc L/R= 0.7ms) resistance: internal resistance:
Heat side Cool side
(30Vdc/ 120Vac, 4A (120Vac COS f = 0.4) 680Ω (under operating 680Ω (under operating
resistive load) 2A (240Vac COS f = 0.4) conditions) conditions) 3D 0D 0D
4A Allowable contact voltage: Output accuracy: Load current setting AK 0D 5G
(240Vdc, resistive load) 250Vac, resistive load ±0.1% FS max. accuracy: 5K 5G 5G
Allowable contact voltage: 125Vdc, resistive load (under operating ±0.2% FS max. (under
9K 0D 6D
250Vac, resistive load 125Vdc L/R= 0.7ms conditions) operating conditions)
125Vdc, resistive load 250Vac COS f = 0.4 Output resolution: Load current setting BK 5G 6D
Maximum switching Maximum switching 1/2000 min resolution: 1/200min
power: power: Inrush current: Inrush current: In the heat/cool model,
150W, 960VA (resistive 75W (L/R= 0.7ms) 25mA max., 50ms max. 25mA max. 50ms max. the output type differs
load) 480VA (COS f = 0.4) (with 250Ω load) (with 250Ω load) between the heat side
Mechanical life: Mechanical life: Maximum output current: Maximum output current: and cool side as shown in
10,000,000 repetitions 10,000,000 repetitions 21.6mAdc 21.6mAdc the above table.
Electrical life: Electrical life: Minimum output current: Minimum output current: Each output rating is the
100,000 repetitions (at 100,000 repetitions 2.4mAdc 2.4mAdc same as for 0D, 2G, 5G,
contact rating, COS f =1, (at contact rating, Opening terminal voltage: Off time leak current: or 6D.
frequency 30 times/min) COS f = 0.4, frequency 25V max. 100µA max. (with load is
Minimum switching 30 times/min) Output update cycle: shorted under operating ・ The heat side and cool
voltage: 5V Minimum switching 100ms conditions) side ca be switched.
Minimum switching voltage: 5V Output update cycle: ・ Direct or reverse action
current: 100mA Minimum switching 100ms can be selected by
Minimum on/off time: current: 100mA Minimum on-off time: remote switching, as in
100ms on, on/off 100ms on, on-off the other models.
control 100ms on, time control 100ms on, time
proportional control proportional control
(cycle time: 10s min.)
0.1% of cycle time (cycle
time: less than 10s)
Proportional band 0.0 to 1000.0% FS 0.1 to 1000.0% FS 0.1 to 1000.0% FS 0.0 to 1000.0% FS 0.1 to 1000.0% FS
(P) (On-off operation (On-off operation (On-off operation (On-off operation (On-off operation
when P= 0) is not allowed) is not possible) when P= 0) is not allowed)

3
Control Model number 0D 2G 5G 6D 3D, AK, 5K, 9K, BK
output Cycle time 5 to 120s — — 1 to 60s Same as for each
(setting possible (setting possible type of output
every second) every second)
Integral time (I) 0 to 3600s 0 to 3600s 0 to 3600s 0 to 3600s 0 to 3600s
(PD action when I=0) (PD action when I=0) (PD action when I=0) (PD action when I=0) (PD action when I=0)
Derivative time (D) 0 to 1200s 0 to 1200s 0 to 1200s 0 to 1200s 0 to 1200s
(PI action when D=0) (PI action when D=0) (PI action when D=0) (PI action when D=0) (PI action when D=0)
Differential gap 0 to 1000U — 0 to 1000U 0 to 1000U Same as in each
(in on-off operation) (in on-off operation) (in on-off operation) output type.
Dead band — 0.5 to 25.0% OUT — — -100.0 to +5.0% OUT
Output limiter Low limit value: Low limit value: Low limit value: Low limit value: Low limit value:
-10% to high limit value -10% to high limit value -10% to high limit value -10% to high limit value -10% to high limit value
(-10 to 0% become 0%) High limit value: High limit value: (-10 to 0% become 0%) High limit value:
High limit value: Low limit value to 110% Low limit value to 110% High limit value: Low limit value to
Low limit value to 110% Low limit value to 110% 110%
(100 to 110% become (100 to 110% become
100%) 100%)
Manipulated variable 1 to 100% 1 to 100% 1 to 100% 1 to 100% 1 to 100%
change rate limiter (every 100 ms) (every 100 ms) (every 100 ms) (every 100 ms) (every 100 ms)
MFB (Motor Feed — 100 to 2500Ω — — —
back) input range
MFB (Motor Feed — Whe ther action is — — —
back) break to be continued is
control selected by MFB
position assumption.
Variable gain If the load characteristic of the control system is non-linear, stable control characteristics are
obtained by changing the gain according to the deviation. Control conforms to the following equation:
Set proportional band (p) x Gain1value = Real proportional band.
Set value range: 0.01 to 300.00
Gain 1: when -20% FS Gain 6: when 2% FS
Gain 2: when -10% FS Gain 7: when 5% FS
Gain 3: when -5% FS Gain 8: when 10% FS
Gain 4: when -2% FS Gain 9: when 20% FS
Gain 5: when 0% FS
The gain ramp is automatically calculated using set gains, when the deviation is less than -20% or
more than 20%, calculation uses the extended characteristic.
Remote No. of input points 4 or 12 (option)
switch Input Connectable outputs Dry contact (relay contact) and open collector (current sink to ground)
(RSW)
Opening terminal voltage 12V +0.6V
-1.6V between common terminal (No. 25) and each input terminal (under operating conditions)

Shorting terminal current The current from each terminal is 5.0 to 6.6mA (under operating conditions)
Allowable contact On: Less than 700Ω (under operating conditions)
resistance (dry contact) Off: More than 10kΩ (under operating conditions)
Residual voltage at 3V max. (under operating conditions)
open collector on time
Leak current at open 100µA max. (under operating conditions)
collector off time
Parallel connection Interconnection of SDC40A units is possible. Connection with compatible units other than SDC40A
with other instrument is also allowed.
Input sampling cycle 0.1s
Minimum hold time 0.2s
of on detection
Function allocation NOP, RUN/READY, AUTO/MANUAL, REMOTE/LOCAL, AT start/stop, direct/reverse action, LSP
number and PID number selection 0/+1, 0/+2, and 0/+4 (PID No. 0 cannot be selected)
Fixed MV value output 1, 2 and 3
LSP shift 0/+1, 0/+2, 0/+4, 0/+8, 0/+16, 0/+32, 0/+64, 0/+128, 0/+256, 0/+512
Analog input 2 ratio number selection 0/+1, 0/+2, 0/+4
Computer backup system 1 and 2
How to use LSP number / LSP shift Computer backup system usage
SDC40A Normal operations On computer error
Sensor Sensor
50 PV PV
LSP 0 to 7
RSW
LSP number Set value by Set value LSP
selection LSP number by LSP shift shift width
(binary input)
Error
selection
Control Remote Control
LSP shift
50 + 3 x 2 output (mV) switch output (mV)
(binary input) SDC40A SDC40A
OFF Sensor ON Sensor
56 PID PID
LSP PV PV
Set value
shift width
Set by config-
The control output is used directly.
uration C55
(-10000 to +10000U)

The output is changed over by remote switch input to control by SDC40A


One of the following two configurations must then be selected by the remote switch:
1 PV at changeover is used as SP.
2 LSP preset is used as SP.

4
Event No. of output 2 points: standard (SPST relay contact).
points 1 point (SPDT relay contact) and 5 points (open collector output) can optionally be added.
Event setting Direct PV Reverse PV Direct deviation Reverse deviation Direct absolute
deviation value
EV EV SP+EV SP+EV EV EV
ON
ON ON ON ON
OFF
OFF OFF OFF OFF

PV PV PV PV PV
SP
Differential Differential Differential Differential Differential Differential
gap gap gap gap gap gap

Reverse absolute Direct MV Reverse MV Direct RSP Reverse RSP


deviation value
EV EV EV EV EV EV
ON ON ON ON ON

OFF OFF OFF OFF OFF

PV PV PV MV MV
SP Differential Differential Differential Differential
Differential Differential
gap gap gap gap gap gap

Direct SP Reverse SP Direct motor Reverse motor All alarm sum


feedback feedback
EV EV EV EV
ON ON ON ON ON

OFF OFF OFF OFF


OFF
PV PV MFB MFB PV range alarm
Differential Differential Differential Differential Instrument alarm
gap gap gap gap

PV range alarm Instrument alarm Manual status READY status Local status
ON ON ON ON ON

OFF OFF OFF OFF OFF

During PV over range Manual status READY status Local status


–10% FS max.
+110% FS min During instrument AL indication

Auto tuning status Process * Process diagnosis event:


diagnosis This is turned ON if the event on delay time is exceeded,
ON ON but the temperature does not rise beyond the differential
gap (does not lower in the case of direct action) when the
OFF manipulated variable is larger than the event set output
During AT
OFF
value.
ON delay time

Setting range PV (direct, reverse): -19999 to +26000U RSP (direct, reverse): -19999 to +26000U
Deviation (direct, reverse): -19999 to +26000U MFB (direct, reverse): -10.0 to +110.0%
Absolute deviation value: 0 to 26000U Process diagnostics: -10.0 to +110.0%
MV (direct, reverse): -10.0 to +110.0%
Differential gap MV event, other than MFB: 0 to 200U,
(hysteresis) MV event, MFB: 0.0 to 20.0%
setting range However, when alarm event or status alarm is set, no differential gap can be set.
On delay time 0 to 20000s(min) The on delay time can be set for event output EV1 to EV3.
Output action On-off
Output rating Event EV1, EV2 (standard) EV3 (option) EV4 to EV8 (option)
Item
Type of output SPST (1a) relay contact SPDT (1a1b) relay contact Open collector output
Contact rating 1A (30Vdc/250Vac with 2A (30Vdc/250Vac with ­—
resistive load) resistive load)
Allowable contact 250Vac with resistive load 250Vac with resistive load —
voltage 30Vdc with resistive load 30Vdc with resistive load
Mechanical life 20,000,000 cycles 50,000,000 cycles —
Electrical life 100,000 cycles (at contact 100,000 cycles (at contact —
rating, and frequency of rating, and frequency of
20 times/min.), COS f =1 20 times/min.), COS f =1
Minimum on-off voltage 10V 10V —
Minimum on-off current 10mA (Use a bleeder 10mA (Use a bleeder —
resistor if necessary.) resistor if necessary.)
Load drive power — — 10 to 29Vdc
voltage range
Maximum output — — 70mA/point max. (under
current operating conditions)
Off time leak current — — 0.1mA/point max. (under
operating conditions,
within load drive power
voltage range)
Off time residual — — 1.6V max. (under
voltage operating conditions,
within load drive power
voltage range, and at
maximum output current)

5
Auxiliary No. of output points 1 or 2 (1 point in 2G, 3D, AK, 5K, 9K, and BK models)
output Type of output Selectable from PV, SP, DEV, RSP, MV and MFB.
Output rating 4 to 20mAdc. Max. allowable load resistance: 680Ω
Output accuracy ±0.1% FS (under standard conditions)
Output resolution 1/10000 (numeric value of independent resolution; for example, the input resolution of PV or MFB is not included)
Inrush current 25mA max. 50ms max. (with 250Ω load)
Maximum output 21.6mA
current
Minimum output 2.4mA
current
Opening terminal 25V max.
voltage
Output update cycle 0.1s
Communi- Communication Communication protocols RS-485 (Note 1) RS-232C
cation system Network Multidrop The device is provided only with the
The device is provided only with the slave station function
slave station function, 1 to 16 units max.
(DIM), 1 to 31 units max. (CMA, SCM).
Data flow Half duplex Half duplex
Synchronization Start/stop synchronization Start/stop synchronization
Interface system Transmission system Balanced (differential) Unbalanced
Data line Bit serial Bit serial
Signal lines 5 transmit/receive lines 3 transmit/receive lines
(3-wire connection is also possible)
Transmission speed 4800, 9600 bps 4800, 9600 bps
Communication distance 500m max. (total) 15m max.
Protocol RS-485 RS-232C
Message characters Character configuration 11 bits/character 11 bits/character
Format 1 start bit, even parity, and 1 stop bit, 1 start bit, even parity, and 1 stop bit,
or 1 start bit, no parity, and 2 stop bits or 1 start bit, no parity, and 2 stop bits
Data length 8 bits 8 bits
Isolation Completely isolated between the input and output.
Note 1. For RS-485, communications, the device can be connected not only to computers equipped with RS-485, but also
to Azbil Corporation's MX200, MA500 (DK link II DIM) or CMC10 controllers.
General Memory backup Non-volatile semiconductor memory (EEPROM)
specifica- Rated power voltage AC model: 100 to 264Vac 50/60Hz, DC model: 24Vdc
tions
Power consumption AC model: 30VA max., DC model: 12W max.
Power switching 30A max. 10ms (under operating conditions)
inrush current Caution: When applying power to a number of SDC40As simultaneously, ensure sufficient power is supplied, or
start up the SDC40As in series. Otherwise, the controllers may not start up normally due to voltage drop
from the inrush current. It is necessary to reach the stable voltage within 2s of power being supplied.
Insulation resistance More than 20MΩ between power terminal 1 or 2 and ground terminal 3 (using 500Vdc megger).
Dielectric strength 1500Vac (AC model) or 500Vac (DC model), 50/60Hz for 1 min between power terminal and ground terminal
1500Vac, 50/60Hz for 1 min between relay output and ground terminal
500Vac, 50/60Hz for 1 min between any other part and ground terminal
500Vac, 50/60Hz for 1 min between isolated terminals
Standard conditions Ambient temperature 23 ±2°C
Ambient humidity 60 ±5% RH
Rated power voltage AC Model 105Vac ±1%
DC Model 24Vdc ±5%
Power frequency AC model: 50 ±1Hz or 60 ±1Hz
Vibration resistance 0m/s2
Shock resistance 0m/s2
Mounting angle Reference plane (vertical) ±3°
Operating conditions Ambient temperature 0 to 50°C
Ambient humidity 10 to 90% RH (non-condensing)
Rated power voltage AC Model 100 to 264Vac
DC Model 24Vdc
Power frequency 50 ±2Hz or 60 ±2Hz
Vibration resistance 0 to 1.96m/s2
Shock resistance 0 to 9.81m/s2
Mounting angle Reference plane (vertical) ±10°
Transport/storage Ambient temperature -20 to +70°C
conditions Ambient humidity 10 to 95% RH (non-condensing)
Vibration resistance 0 to 4.90m/s2 (10 to 60Hz, for 2hr each in X, Y and Z directions)
Shock resistance 0 to 490m/s2 (3 times in vertical direction)
Package drop test Drop height: 90cm (1 angle, 3 edges, 6 planes, freefall)
Materials of mask Mask: Multilon
and case Case: Polycarbonate

6
General Colors of mask Mask: Dark gray
specifica- and case Case: Light gray
tions Mounting Panel flush type, using the dedicated mounting bracket
Weight Approx. 750g (Extension terminal base: Approx. 150g)
Standard Name Model No. Q’ty Options Name Model No.
accessories Unit indicating label N-3132 1 Hard dust-proof cover set 81446083-001
Mounting bracket 81405411-003 2 brackets Soft dust-proof cover set 81446087-001
Instruction manual CP-UM-1580E 1 Terminal cover 81446084-001
PC loader SLP-C40AJ20

Table of selectable inputs and ranges


Symbol °C Range °F Range Symbol °C Range °F Range
K (CA) 0.0 to 1200.0 0 to 2400 JIS ‘89 Pt100 -200.0 to +500.0 -300.0 to +900.0
(IEC/DIN) -200.0 to +200.0 -300.0 to +400.0
K (CA) 0.0 to 800.0 0 to 1600
K (CA) 0.0 to 400.0 0 to 750 -100.0 to +150.0 -150.0 to +300.0
K (CA) -200.0 to +1200.0 -300 to +2400 -50.0 to +200.0 -50.0 to +400.0
K (CA) -200.0 to +300.0 -300 to +700 -60.00 to +40.00 -76.00 to +104.00
K (CA) -200.0 to +200.0 -300 to +400 -40.00 to +60.00 -40.00 to +140.00
E (CRC) 0.0 to 800.0 0 to 1800 0.0 to 500.0 0.0 to 900.0
J (IC) 0.0 to 800.0 0 to 1600 0.0 to 300.0 0.0 to 500.0
T (CC) -200.0 to +300.0 -300 to +700 0.00 to 100.00 0.00 to 200.00
B (PR30-6) 0.0 to 1800.0 0 to 3300 JIS ‘89 JPt100 -200.0 to +500.0 -300.0 to +900.0
R (PR13) 0.0 to 1600.0 0 to 3100 -200.0 to +200.0 -300.0 to +400.0
S (PR10) 0.0 to 1600.0 0 to 3100 -100.0 to +150.0 -150.0 to +300.0
W (WRe5-26) 0.0 to 2300.0 0 to 4200 -50.0 to +200.0 -50.0 to +400.0
W (WRe5-26) 0.0 to 1400.0 0 to 2552 -60.00 to +40.00 -76.00 to +104.00
PR40-20 0.0 to 1900.0 0 to 3400 -40.00 to +60.00 -40.00 to +140.00
Ni-Ni · Mo 0.0 to 1300.0 32 to 2372 0.0 to 500.0 0.0 to 900.0
N 0.0 to 1300.0 32 to 2372 0.0 to 300.0 0.0 to 500.0
PL II 0.0 to 1300.0 32 to 2372 0.00 to 100.00 0.00 to 200.00
DIN U -200.0 to +400.0 -300 to +750 4 to 20mA
DIN L -200.0 to +800.0 -300 to +1600 0 to 20mA
Gold iron-chromel 0.0 to 300.0K — 0 to 10mV
-10 to +10mV
The ±0.1% FS input indication accuracy is not applicable to 0 to 100mV Scaling setting range: -19999 to +26000
the following input conditions: (Decimal point position is variable.)
0 to 1V (Reverse scaling possible)
Lower than -100°C on K thermocouple and T thermocouple: ±1°C ±1U
-1 to +1V
Lower than 260°C on B thermocouple: ±4.0% FS ±1U
1 to 5V
260°C to 800°C of B thermocouple: ±0.4% FS ±1U
800°C to 1800°C of B thermocouple: ±0.2% FS ±1U 0 to 5V
Lower than 100°C on R thermocouple and S thermocouple: ±0.2% FS 0 to 10V
±1U
100 to 1600°C on R thermocouple and S thermocouple: Input type
±0.15% FS ±1U
Lower than 300°C on PR40-20 thermocouple: ±2.5% FS ±1U Thermocouple: K, E, J, T, B, R, S (JIS C 1602-1981)
300 to 800°C on PR40-20 thermocouple: ±1.5% FS ±1U WRe5-26 (Hoskins Data)
800 to 1900°C on PR40-20 thermocouple: ±0.5% FS ±1U PR40-20 (Johnson Matthey Data)
Gold iron-chromel: ±1.5K ±1U Ni-NiMo (General Electric Data)
The range of two decimal digits of RTD input: ±0.15% FS ±1U N (N.B.S. Monograph 161)
0 to 10mV range: ±0.15% FS ±1U PL II (Engelhard Industries Data (IPTS68))
Lower than -100°C on DIN U: ±2°C ±1U DIN U, DIN L (DIN 43710-1985)
Between -100°C and 0°C on DIN U: ±1°C ±1U Gold iron chromel (Hayashidenko Data)
Lower than -100°C on DIN L: ±1.5°C ±1U Resistance temperature detector (RTD): Pt100, JPt100
(JIS C 1604-1989)

7
Model selection guide table
Example: C40A5G0AS04100
Basic Control Function Power Options Options Additional Description
model No. output supply 1 2 processing
C40A Digital indicating controller
0D Relay output (on-off or time proportional)
6D Voltage output (with current value adjusting function, on-off
or time proportional)
2G Position proportional output
5G Current output (4 to 20mA)
3D Heat/cool control, relay output + relay output
AK Heat/cool control, relay output + current output
5K Heat/cool control, current output + current output
6K Heat/cool control, voltage output + voltage output
9K Heat/cool control, relay output + voltgage output
BK Heat/cool control, current output + voltage output
0 Standard model
1 Remote SP function model
2 Internal cascade function model
AS AC power supply (90 to 264Vac: Free power supply)
00 Option 1 is not provided (2 SPST relay contact event outputs
are provided)
01 With 4 points of remote switching
02 With one SPDT relay contact event output added
03 With 4 points of remote switching + 1 SPDT relay contact
event output added
04 With 4 points of remote switching + 1 point of auxiliary output
05 With 1 SPDT of event output + 1 point of auxiliary output
06 With 4 points of remote switching + 1 SPDT relay contact
event output + 1 point of auxiliary output
07 With 4 points of remote switching + 2 points of auxiliary
output
08 With 1 SPDT of event output + 2 points of auxiliary output
09 With 4 points of remote switching + 1 SPDT of event output
(SPDT relay contact) + 2 points of auxiliary output
Notes: 0 Option 2 is not provided (if option 1 is not designated, 0 will
The two auxiliary output points of option 1 be selected.)
cannot be specified for the following control 1 With 8 points of added remote switching + 5 event output
outputs: points (with open collector output)
2G, 3D, AK, 5K, 6K, 9K, BK 2 With 8 points of added remote switching + event output (open
Any of 1 to 3 of option 2 can be selected only collector output) + RS-485 communication
when four points of remote switching are 3 With 8 points of added remote switching + event output (open
provided in option 1 (01, 03, 04, 06, 07, 09). collector output) + RS-232C communication
Selection guide table 00 Additional processing not provided
: Combination possible D0 Data attached
×: Combination not possible. Y0 Comply with the traceability
Option 2 0 1 2 3
Option 1
00 × × ×
01
02 × × ×
03
04
05 × × ×
06
07
08 × × ×
09
Note: If any of 1 to 3 of option 2 are
selected the extension terminal base
is provided.

8
Dimensions
(Unit: mm)
C40A
(18) Terminal cover set (option)
81446084-001
Hard dust-proof cover set (option) 15 159.5
81446083-001 137
12
Mounting bracket
96 81405411-001
Standard terminal base

1 11 21 26
RDY
REM CH1
MAN CH2 2 12 22 27

COM CH3
3 13 23 28
SP
DEV

(106 x 104)
OUT 4 14 24 29

OUT

91.5
5 15 25 30
96
EV1 EV2 EV3 OT1 OT2 AT UF
UF1 UF2 DISP 6 16 31

7 17 32
SP/EV A/M R/L PARA
8 18 33

LOADER AT ENT
9 19 34

10 20

Standard Extension terminal base Terminal


screw M3.5
terminal base Extension
Soft dust-proof cover set (option)
81446087-001 terminal base
1 26
41 49 57
2 27

42 50 58
3 28

4 43 51 59 29

110.5
5 44 52 60 30

6 45 53 61 31

7 46 54 62 32

8 55 33
47 63

9 34
48 56 64

10

37

Soft dust-proof cover set: Part No. 81446087-001 Terminal cover set: Part No. 81446084-001
(silicon rubber, transparent)  This can be fitted to both the standard terminal base and to
the extension terminal base. (construction: incombustible
polyvinyl chloride sheet (gray))
15
12 90
(0.5) 45
98 17 5-3.6 hole
(3.2)

1.5

5.5
13.7

R1.8
69.6
51.6
95
98

79
90
14
29.5

(86) 2.7

Hard dust-proof cover set: Part No. 81446083-001


(polycarbonate, transparent) Packing
16 6 106
8 4 4.7 96.6
4.7
1.1
(96.8)

96.6
106
106

9
Panel cutout (Unit: mm)
For standard application or When the hard dust-proof cover Lateral series mounting
with soft dust-proof cover is used

92 +0.8 92 +0.8
0
46 (N – 1) x 96 46
0
92 +0.8

92 +0.8
92 +0.8
0

0
0
150 or more

150 or more
N x 96 – 4
(N: No. of mounted units)

99 or more 107 or more

Standard terminal layout


• AC model

Instrument power
supply 90 to 264Vac
1 OPEN + 11 21 RSW1 26
NO
2 – 12 MV1 22 RSW2 27
GND NC
3 CLOSE 13 23 RSW3 28 +
4 to 20mA Analog input 2
4 1a Y + 14 24 RSW4 29 – (remote SP, and internal

EV1 NO NO 1 to 5V cascade models only)
COM +
5 T
– 15 MV2 25 30
NC
6 1a G 16 31 +
EV2 NO current input

Event output 7 + 17 32
RTD input
8 – 18 33 Analog input 1
NO –
+
EV3 9 19 34
NC * Voltage input
10 20
– Thermocouple
+
input

* Auxiliary output * For 2G, 3D, AK, 5K, 9K and BK models,


4 to 20mA the auxiliary output terminals are 17 and 18 .
for 0D, 6D and 5G models, the auxiliary output 1 terminals are
Recorder or other
similar device
14 and 15 , and the auxiliary output 2 terminals are 17 and 18 .

• DC model
Instrument power supply
21.6 to 26.4 Vdc OPEN
1 + 11 21 RSW1 26
+ NO

2 – 12 MV1 22 RSW2 27
GND NC
3 CLOSE 13 23 RSW3 28 +
4 to 20mA Analog input 2
4 1a Y + 14 24 RSW4 29 – (remote SP, and internal

EV1 NO NO 1 to 5V cascade models only)
COM +
5 T – 15 MV2 25 30
NC
6 1a G 16 31 +
EV2 NO current input
7 + 17 32 –
Event output
RTD input
8 – 18 33
– Analog input 1
NO
+
EV3 9 19 34
NC * Voltage input
10 20

+ Thermocouple
input

* Auxiliary output
* For 2G, 3D, AK, 5K, 9K and BK models,
4 to 20mA
the auxiliary output terminals are 17 and 18 .
Recorder or other for 0D, 6D and 5G models, the auxiliary output 1 terminals are
similar device 14 and 15 , and the auxiliary output 2 terminals are 17 and 18 .

10
Extension terminal layout
• With RS-485 • With RS-232C

EV4 SDA RD
RSW5 41 Load 49 57 59
EV5 SDB SD
RSW6 42 Load 50 58 60
EV6 RDA SG
RSW7 43 Load 51 59 61
EV7 RDB
RSW8 44 Load 52 60
External
EV8 SG communication
RSW9 45 Load 53 61

RSW10 46 54
62
RSW11 47 55 Bias circuit 63

RSW12 48 + – 56 64
External
To terminal 25 power
supply

11
1st edition: Issued in May 1994
11th edition: Issued in May 2015