Drawing For 8kw Duct Heater (1.5kwx4,1kwx2)
Drawing For 8kw Duct Heater (1.5kwx4,1kwx2)
Drawing For 8kw Duct Heater (1.5kwx4,1kwx2)
A V
D S
AUTO/MANUAL AUTO/MANUAL AUTO/MANUAL AUTO/MANUAL AUTO/MANUAL AUTO/MANUAL
SWITCH-1 SWITCH-2 SWITCH-3 SWITCH-4 SWITCH-5 SWITCH-6
E
1200 HTR-1 OFF HTR-2 OFF HTR-3 OFF HTR-4 OFF HTR-5 OFF HTR-6 OFF
1150 R
HTR-1 TRIP HTR-2 TRIP HTR-3 TRIP HTR-4 TRIP HTR-5 TRIP HTR-6 TRIP
F Q
OVER TEMP OVER TEMP OVER TEMP OVER TEMP OVER TEMP OVER TEMP
TRIP TRIP TRIP TRIP TRIP TRIP
EMERGENCY
STOP
INCOMMER S1 S1 S1
G MCCB
100 S2 S2 S2
P
H O
LEGEND:
I N
1.PANEL : MS WITH POWDER COATING
FLOOR MOUNTING TYPE.
2. CABLE ENTRY - REMOVABLE GLAND PLATE
3. DHC : DIGITAL THUMIDITY CONTROLLER [ 48 X48].
AT BOTTOM SIDE
4. VOLT & AMMETER : [ 72 X 48]
3. PAINT - RAL 7035
5. MCCB : MOULD CASE CIRCUIT BREAKER
INDUSTRIALS HEATORS
4. PANEL THICKNESS : 1.6 MM
J 5. DOOR THICKNESS : 1.6 MM
M
TITLE:- GA DRAWING OF 8 KW HEATER CONTROL PANEL
6. MOUNTING PLATE THICKNESS : 2.0 MM
CUSTOMER:- M/S.CRESCON PROJECTS PVT LTD
NAME SIGN DRAWING NO. IH/CPL/1710/20-21
DRN P.O NO: 838/151-B/027/20-21
26 25 24 23 22 21 20 19 18 17 16 15 14
1 2 3 4 5 6 7 8 9 10 11 12 13
A R Y B N
POWER DRAWING V
INCOMING CABLE
(YOUR SCOPE) N
R
Y
B B U
4P, 16A
MCCB
R
V
Y S DIGITAL
B S VOLTMETER
ASS
C 4 SQMM COPPER S1 DA S1 S1 T
CONDUCTOR PVC CABLE S2
S2
S2
R Y B N
1X4 FDBK
R
D 1X4 FDBK S
Y
1X4 FDBK
B
N 1X4 FDBK
2.5 Sq.mm
PVC CABLE
E R
F Q
2.5 Sq.mm
PVC CABLE
4P, 25A,
4P, 25A,
G 30mA
30mA P
RCCB 4
RCCB 3
4P, 25A, 4P, 25A, 4P, 25A, 4P, 25A,
30mA 30mA 30mA 30mA
RCCB 1 RCCB 2 RCCB 5 RCCB 6
I N
INDUSTRIALS HEATORS
TO BANK 1 HEATERS TO BANK 2 HEATERS TO BANK 3 HEATERS TO BANK 4 HEATERS TO BANK 5 HEATERS TO BANK 6 HEATERS
J 1.5KW 1.5KW 1.5KW 1.5KW 1KW 1KW M
TITLE:- POWER CIRCUIT OF 8 KW HEATER CONTROL PANEL
26 25 24 23 22 21 20 19 18 17 16 15 14
1 2 3 4 5 6 7 8 9 10 11 12 13
A V
CONTROL CIRCUIT
B
CONTINUED ON PAGE 4.. U
T1
EM-PB
T2
C MCB T
T3
R 2P,6A
T4
T5
D S
T6
(CUSTOMER SCOPE)
230VAC SUPPLY
E AMMETER VOLTMETER R
F Q
T7
T8
T9
G 0 P
FAN
T10
T11
T12
H O
I NOTE: N
1. TERMINALS T1 TO T6 ARE SHORT LINKED FOR PHASE SUPPLY
2. TERMINALS T7 TO T12 ARE SHORT LINKED FOR NEUTRAL SUPPLY
INDUSTRIALS HEATORS
J M
TITLE:- CONTROL CIRCUIT
26 25 24 23 22 21 20 19 18 17 16 15 14
1 2 3 4 5 6 7 8 9 10 11 12 13
A V
CONTROL CIRCUIT OF HEATER BANK 1
CONTINUED ON PAGE 5..
T1
B R U
FUSE 1, 2A
THERMOSTAT 1
R1 BLOWER
CONTACT
R1 T1
C RCCB 1 K1 K1 T
TRIP
R2 R3 CONTACT
A M RCCB 1
DHC1 TRIP
BMS O/P CONTACT DHC1
D S
HUMIDITY
SENSOR
L1 L2 L3
L4 L5 L6
R1 R2 R3 T1 K1
E R
T7
TRIP INDICATION-1
N FUSE 2, 2A
BANK 1 HEATER
EARTH LEAKAGE
OVER TEMPERATURE
AUTO MODE ON
ON INDICATION
OFF INDICATION
MANUAL MODE
MANUAL MODE
HEATER BANK 1
HEATER BANK 1
ON INDICATION
TIMER COIL
TRIP INDICATION-1
AUTO MODE
F Q
INDICATION
G P
H O
RELAY DETAILS
RELAY
RELAY TYPE C NO NC
NO
3
I 1 2 1 1 N
CHANGEOVER
3
2 1 1 0
CHANGEOVER
3
3 1 1 0
CHANGEOVER INDUSTRIALS HEATORS
J M
TITLE:- CONTROL CIRCUIT
26 25 24 23 22 21 20 19 18 17 16 15 14
1 2 3 4 5 6 7 8 9 10 11 12 13
A V
CONTROL CIRCUIT OF HEATER BANK 2
CONTINUED ON PAGE 6..
T2
B R U
FUSE 3, 2A
THERMOSTAT 2
R4 BLOWER
CONTACT
T2
C R4
RCCB 2 K2 K2
T
TRIP
R5 R6 CONTACT
A M RCCB 2
DHC2 TRIP
BMS O/P CONTACT DHC2
D S
HUMIDITY
SENSOR
L7 L8 L9
L10 L11 L12
R4 R5 R6 T2 K2
E R
T8
TRIP INDICATION-2
N FUSE 4, 2A
BANK 1 HEATER
EARTH LEAKAGE
OVER TEMPERATURE
AUTO MODE ON
ON INDICATION
OFF INDICATION
MANUAL MODE
MANUAL MODE
HEATER BANK 2
HEATER BANK 2
F Q
ON INDICATION
TIMER COIL
TRIP INDICATION-2
AUTO MODE
INDICATION
G P
H O
RELAY DETAILS
RELAY
RELAY TYPE C NO NC
NO
I 3 N
1 2 1 1
CHANGEOVER
3
2 1 1 0
CHANGEOVER
3
3
CHANGEOVER
1 1 0 INDUSTRIALS HEATORS
J M
TITLE:- CONTROL CIRCUIT
26 25 24 23 22 21 20 19 18 17 16 15 14
1 2 3 4 5 6 7 8 9 10 11 12 13
A V
CONTROL CIRCUIT OF HEATER BANK 3
CONTINUED ON PAGE 7..
T3
B R U
FUSE 5, 2A
THERMOSTAT 3
R7 BLOWER
CONTACT
T3
C R7
RCCB 3 K3 K3
T
TRIP
R8 R9 CONTACT
A M RCCB 3
DHC3 TRIP
BMS O/P CONTACT DHC3
D S
HUMIDITY
SENSOR
TRIP INDICATION-3
N FUSE 6, 2A
BANK 3 HEATER
EARTH LEAKAGE
OVER TEMPERATURE
AUTO MODE ON
ON INDICATION
OFF INDICATION
MANUAL MODE
MANUAL MODE
HEATER BANK 3
HEATER BANK 3
F Q
ON INDICATION
TIMER COIL
TRIP INDICATION-3
AUTO MODE
INDICATION
G P
H O
RELAY DETAILS
RELAY
RELAY TYPE C NO NC
NO
I 3 N
1 2 1 1
CHANGEOVER
3
2 1 1 0
CHANGEOVER
3
3
CHANGEOVER
1 1 0 INDUSTRIALS HEATORS
J M
TITLE:- CONTROL CIRCUIT
26 25 24 23 22 21 20 19 18 17 16 15 14
1 2 3 4 5 6 7 8 9 10 11 12 13
A V
CONTROL CIRCUIT OF HEATER BANK 4
CONTINUED ON PAGE 8..
T4
B R U
FUSE 7, 2A
THERMOSTAT 4
R10 BLOWER
CONTACT
C R10 T4 T
RCCB 4 K4 K4
TRIP
R11 R12 CONTACT
A M RCCB 4
DHC4 TRIP
BMS O/P CONTACT DHC4
D S
HUMIDITY
SENSOR
TRIP INDICATION-4
N FUSE 8, 2A
BANK 4 HEATER
EARTH LEAKAGE
OVER TEMPERATURE
AUTO MODE ON
ON INDICATION
OFF INDICATION
MANUAL MODE
MANUAL MODE
HEATER BANK 4
HEATER BANK 4
F Q
ON INDICATION
TIMER COIL
TRIP INDICATION-4
AUTO MODE
INDICATION
G P
H O
RELAY DETAILS
RELAY
RELAY TYPE C NO NC
NO
I 3 N
1 2 1 1
CHANGEOVER
3
2 1 1 0
CHANGEOVER
3
3 1 1 0 INDUSTRIALS HEATORS
CHANGEOVER
J M
TITLE:- CONTROL CIRCUIT
26 25 24 23 22 21 20 19 18 17 16 15 14
1 2 3 4 5 6 7 8 9 10 11 12 13
A V
HUMIDITY
SENSOR
T11
TRIP INDICATION-5
N FUSE 10, 2A
BANK 5 HEATER
EARTH LEAKAGE
OVER TEMPERATURE
F AUTO MODE ON Q
ON INDICATION
OFF INDICATION
MANUAL MODE
MANUAL MODE
HEATER BANK 5
HEATER BANK 5
ON INDICATION
TIMER COIL
TRIP INDICATION-5
AUTO MODE
INDICATION
G P
H O
RELAY DETAILS
RELAY
RELAY TYPE C NO NC
I NO N
3
1 2 1 1
CHANGEOVER
3
2 1 1 0
CHANGEOVER
3 INDUSTRIALS HEATORS
3 1 1 0
J CHANGEOVER M
TITLE:- CONTROL CIRCUIT
26 25 24 23 22 21 20 19 18 17 16 15 14
1 2 3 4 5 6 7 8 9 10 11 12 13
A V
HUMIDITY
SENSOR
T12
TRIP INDICATION-6
N FUSE 12, 2A
BANK 6 HEATER
EARTH LEAKAGE
OVER TEMPERATURE
F AUTO MODE ON Q
ON INDICATION
OFF INDICATION
MANUAL MODE
MANUAL MODE
HEATER BANK 6
HEATER BANK 6
ON INDICATION
TIMER COIL
TRIP INDICATION-6
AUTO MODE
INDICATION
G P
H O
RELAY DETAILS
RELAY
RELAY TYPE C NO NC
I NO N
3
1 2 1 1
CHANGEOVER
3
2 1 1 0
CHANGEOVER
3 INDUSTRIALS HEATORS
3 1 1 0
J CHANGEOVER M
TITLE:- CONTROL CIRCUIT
26 25 24 23 22 21 20 19 18 17 16 15 14