Substation Capacity Guillaume

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 5

Substation Capacity

TOTAL RATED LOAD 7010 kVA


EFFICIENCY OF DISTRIBUTION TRANSFORMER 90%
EFFICIENCY OF PRIMARY DISTRIBUTION LINE 95%
DIVERSITY FACTOR 1.2
EFFICIENCY OF SUBSTATION 90%
EFFICIENCY OF TRANSMISSION LINE 95%

Total connected load


Maximum Feeder Load =
efficiency of distribution transformer x diversity factor
7010
=
0.90 ( 1.2 )
= 6490.74 kVA
Maximum Feeder Load
Maximum Demand =
Efficiency of primary distribution line
6490.74
=
0.95
= 6832.36 kVA
Maximum demand
Substation Capacity =
Efficiency of distribution and transmission lines
6832.36
=
0.9(.95)
= 7991.06 kVA

USE: One 10 MVA Substation Transformer, 2 – 5 MVA Standby Generator.

Feeder from Primary Busbar


2(5,000) kVA
I =
√ 3 (13.2 kV)
=437.4 A
At 125 % for size of wire
= 437.4 x 1.25
=546.73 A
1
Use: 600 Busbar ( in x 1 1/2 in)
8

Protective Device:

Fuse Link (primary) = 300 % of Full load current


= 3 x 437.4 A
= 1312.2 A
Use: 3- 400 Amp Fuse link
DP1 CIRCUITS AN BN CN
20 circuits 5.22(7) 5.22(8) 5.22(5)
15 circuits 6.52(5) 6.52(5) 6.52(5)
5 freezer 2hp 12(1) 12(2) 12(2)
5 refrigerator 1hp 8(2) 8(1) 8(2)
5 chiller 1hp 8(2) 8(1) 8(2)
Sub Total 113.14 114.36 114.7

1Phase Loading
LOAD DESCRIPTION 3 Phase
AN BN CN
Dp-1   113.14 114.36 114.7
Dp-2 34      
TOTAL 34 113.14 114.36 114.7

DP1 CIRCUITS AN BN CN
20 circuits 5.22(7) 5.22(7) 5.22(6)
15 circuits 6.52(5) 6.52(5) 6.52(5)
Sub Total 69.14 69.14 63.92

1Phase Loading
LOAD DESCRIPTION 3 Phase
AN BN CN
Dp-1   69.14 69.14 63.92
Dp-2 34      
TOTAL 34 69.14 69.14 63.92

FITNESS GYM (1, 2)


a.) General Lighting Loads
450 sq.m * 16VA/sq.m 7200VA

b.) Small Appliances Load


4-20A @ 1500VA 6000VA

c.) Other Loads


10-900W Treadmill
(9kW) (0.8) = 7200VA 7200VA
2-1Hp ACU
8*230*2 = 3680VA 3680VA

2-1Hp Refrigerator
2*8*230 = 3680VA 3680VA

________
27760VA

Demand Factor @ 80% Total Computed Load: 22208VA

BARBER SHOP (1, 2)


a.) General Lighting Loads
225 sq.m * 24VA/sq.m 5400VA

b.) Small Appliances Load


2-20A @ 1500VA 3000VA

c.) Other Loads


1-1.5Hp ACU
10*230 = 2300VA 4600VA
1-1Hp Refrigerator
8*230 = 1840VA 1840VA
________
12540VA
Demand Factor @ 80% Total Computed Load: 10032VA
MD/ kVA rating

Single phase
TOTAL 3phase
AN BN CN
110 2310 2310 2280

MD OF FEEDER = (MD1' + MD2' + MD3')/Div. Factor among Transformer


= (2310KVA + 2310 KVA + 2280 KVA + 110)/ 1.3
= 5.3923 MVA

MD of Substation = (SIMD FEEDER) / Div. Factor among Feeder


=( 2287.5 KVA + 2300 KVA + 2350 KVA + 300 KVA) /1.2
= 5.8417 MVA

MD FEEDER 5392.3 kVA


MD SUBSTATION 5.8417 kVA