RC9 Instruction Manual For Refrigeration Compressors
RC9 Instruction Manual For Refrigeration Compressors
RC9 Instruction Manual For Refrigeration Compressors
00.89.221 v003.99.06.en
Grasso
Refrigeration Division
All rights reserved. No part of this publication may be copied or published by means of printing,
photocopying, microfilm or otherwise without prior written consent of Grasso. This restriction also
applies to the corresponding drawings and diagrams.
For extra information as to adjustments, maintenance and repair, contact the Technical Department of
your supplier.
This publication has been written with great care. However, Grasso cannot be held responsible, neither
for any errors occurring in this publication nor for their consequences.
The range of RC9 refrigeration compressors includes 3-single-stage and 2 two-stage compressor types. All
these types are suitable for the usual refrigerants. The single-stage compressors can also used as booster.
**For further lubrication data, refer to Chapter 3 and 9 and to lubrication oil table 3.1.
Piston stroke mm 85
Max. allowable difference between suction and discharge pres- max. bar 17.5
sure
All dimensions in mm
All dimensions in mm
All dimensions in mm
All dimensions in mm
All dimensions in mm
All compressors are provided with an oil pump. The Application of other oils is not permitted without
crankcase oil level must reach about the middle of the written consent of Grasso.
sight glass. The amount of oil charge is shown in table The choice of the viscosity of the lubricating oils
3.1. depends on the operating conditions of the
compressor. In general, a viscosity of 4 to 4.5 E at 50
The lubrication pressure (i.e. the difference between
°C will satisfy.
the oil pressure, measured at the end of the
However, a higher viscosity should be chosen when a
lubricating circuit and the suction pressure) at
high oil temperature is expected, due to arduous
operating temperature is pre-set at a value of 1.5 bar.
operating conditions, such as:
The maximum permissable oil temperature is 70 °C,
• a high ambient temperature of the compressor
which best can be measured at the suction line to the
(high engine room temperature)
oil suction filter with a contact thermometer.
• a more than normal superheat of the refrigerant
The compressor should not be started with an oil
suction vapour;
temperature below 40 °C.
• prolonged part load operation with a large num-
OIL TYPES
ber of cylinders cut out
For lubrication of refrigeration compressors, several For less arduous operating conditions a lower viscosity
brands and types of specially developed lubricating may be used. For strongly varying conditions (e.g. in
oils are on the market. The choice of oil depends not summer & winter), a viscosity of 4.5 E is recommended.
only on its good lubrication properties (viscosity) and To ensure proper lubrication of the compressor moving
chemical stability at the operating conditions of the parts, the actual oil viscosity under all operating
compressor, but also on kind and operating conditions should never be less than 10 to 15 cSt
conditions of the refrigerating plant (solidifying and (= 1.85 to 2.35 °E).
floc point, solvability). As far as the lubrication
IMPORTANT REMARK!
properties are concerned, Grasso has tested and
approved for use in RC9- compressors the brands and All viscosities mentioned relate to pure oil only and it
types of oil as listed in the table on page 3.4. Some of should be kept in mind that the actual viscosity in the
the oil types listed in the table may be marketed crankcase of an operating compressor, which is decisive
under other names and/or designations; these oils for the lubrication, is always lower due to dilution by
can also be used, provided their identity can be dissolved refrigerant. The magnitude of the viscosity
proved beyond any doubt. decrease is not only determined by the type of oil and
refrigerant, but also and essentially by the pressure and
temperature prevailing in the crankcase.
Table 3.1 Oil to be used for lubrication
VISCOSITY
BRAND TYPE at 40 oC at 50 oC
o
cSt mPa.s Engler
Energol LPT-F46 54 29 4.4
BP
* Energol LPT-F 68 68 36 5.5
* Zerice 46 43 25 3.8
ESSO * Zerice 68 63 34 5.0
* Zerice S 46 48 27 4.1
FINA Purfrigol MP 68 54 29 4.4
KUWAIT Stravinsky C 55 29 4.4
MOBILOIL Gargoyle Arctic 300 55 30 4.6
* Clavus Oil G 46 46 26 3.9
* Clavus Oil G 68 68 35 5.4
SHELL
* Clavus Oil 46 46 26 3.9
* Clavus Oil 68 68 35 5.4
TEXACO Capella WF 68 61 31 4.7
Suniso 4 GS 1) 54 29 4.4
SUN-OIL
Suniso 5 GS 95 48 7.1
Oil types marked with an asterisk (*) have a viscosity grade number designation according to ISO Standard 3448.
1. Crankcase
2. Cylinder jacket
3. Suction manifold
4. Discharge manifold
5. Cylinder liner with valve-lifting mechanism
6. Cylinder head cover
7. Cooling water jacket
8. Bearing cover
9. Oil pump
10. Rotary shaft seal
11. Oil sight glass
12. Sleeve for heating element
13. Non-return valve
14. Service cover
15. Piston
16. Connecting rod
17. Crankshaft
18. Thrust bearing
19. Cast-on counterweight
20. Suction connection
21. Discharge connection
22. Gas suction strainer
23. Oil discharge filter
24. Oil suction filter
25. Oil charge and drain valve
26. Valve lifting control piston
27. Suction and discharge valve assembly
28. Buffer spring
29. Crankcase pressure equalizing line
is at the bottom of the crankcase. To determine gudgeon pin, a bronze bush or, in the case of
the oil level, a sight glass is located on the HP-cylinders of two stage compressors, a needle
crankcase. To heat the oil, if necessary, all bearing is pressed into the small end.
compressors have a sleeve welded on to the
The crankshaft is mounted in slide bearings
crankcase bottom, into which a heating element
consisting of interchangeable white metal lined
(available as an accessory) can be inserted.
steel bushes pressed into the bearing covers. The
The oil which is separated in the suction chamber
crankshaft, furnished with cast-on counterweights,
from the refrigerant vapour can flow back to the
is dynamically balanced. The tapered shaft end
crankcase via a non-return valve. This valve is
with key for taking up flywheel or coupling, is
fitted between suction chamber and crankcase in
carried gastight through the bearing cover (see
the lower supporting ring of the cylinder liners
par. 4.3, Rotary shaft seal).
(except in the HP-cylinders in two-stage
compressors). The valve, normally open, closes 4.3 ROTARY SHAFT SEAL
when the crankcase pressure exceeds the suction
pressure. In order to pass the crankshaft (2) gastight
The crankcase interior is accessible via one or two outwards, the compressor is provided with a
service covers provided on both sides of the special rotary shaft seal, the construction of which
crankcase. is shown in fig. 4.2.
The sealing between rotating and stationary parts
4.2 CYLINDERS AND MOVING PARTS (see fig. 4.1) is effected on the sliding surface between a
carbon slip ring (7.1) rotating with the crankshaft
The cylinders are formed by interchangeable
and a stationary counterslip ring (6) fitted in the
cylinder liners pressed into the supporting rings in
shaft seal housing (4). For this purpose the sliding
the cylinder jackets. The collar on top of the
surface of both slip rings is ground to extreme
cylinder liners is provided with openings and acts
finish and lapped.
as a seat for the suction valve ring. In the cylinder
liners, light metal pistons are located, on which The carbon slip ring is carried by the slip ring
three compression rings and one oil scraper ring holder and forms an integral part of the rotary
are fitted. seal assembly (7). This assembly consists of the
The connecting rods have a split-type big end, in afore mentioned slip ring holder with carbon
which white metal lined steel precision bearing insert, a metal bellows (7.2) and a drive collar
shells are positioned. To provide bearing for the (7.3). The drive collar in turn is locked on the
1. Bearing cover
2. Drive pin
3. Rotary shaft seal assembly:
3a. Drive collar
3b. Metal bellows
3c. Slip ring holder with
carbon insert
4. O-ring
5. Grub screw
6. Shaft seal housing
7. Stationary counter-slip ring
8. Crankshaft
crankshaft by means of three grub screws (7.4) with four sinusoidal springs is placed
and a drive pin (3) . The slip ring holder with concentrically. The discharge valve seat and the
carbon insert can slide axially over the crankshaft suction valve stroke limitor are one and the same.
and is pressed on to the counter-slip ring by The whole assembly is pressed on to the collar of
means of the metal bellows. the cylinder liner by a powerful buffer spring. For
O-rings (5 and 7.5) are provided to ensure the the function of this buffer spring, see Chapter 6,
sealing between rotary seal assembly and par. 6.3, Liquid Hammer.
crankshaft and between counter-slip ring and
Fig. 4.3 only shows schematically the construction
shaft seal housing.
and operation of the suction and discharge valves.
To remove sufficiently the frictional heat
For the real construction, reference is made to
developed by the slip rings, the shaft seal is
Chapter 9, Compressor Maintenance.
incorporated in the lubricating oil circuit (see
further Paragraph 4.10, “Lubrication system”). 4.5 VALVE LIFTING MECHANISM (see fig. 4.4)
4.4 SUCTION AND DISCHARGE VALVES In order to enable the compressor to start
(see fig. 4.3) unloaded, all cylinders have be put out of action
mechanically by suction valve ring lifting during
The suction and discharge valves of the
compressor standstill. For this purpose a lifting
compressor are of the ring type. They contain
bush is provided in each cylinder, which can move
steel valve rings pressed, under spring tension, on
up and down around the cylinder liner. The lifting
to a seat and shutting off the openings provided
bush is provided at the top with push pins capable
in it. The lift of the valve rings is limited by a
of lifting the suction valve ring from its seat via
stroke limitor. The suction valve only has one valve
openings in the collar of the cylinder liner. The
ring retained, together with one sinusoidal spring,
lifting bush is connected with an oil pressure
between the valve seat type collar of the cylinder
controlled spring-loaded piston, located in a
liner and a stroke limitor.
housing on the outside of the cylinder jacket, by
The stroke limitor of the suction valve is centred
means of a lever. The piston can be moved
by the collar of the cylinder liner.
upward by control oil pressure from the oil pump.
The discharge valve consists of a valve seat and a At compressor standstill there is no oil pressure,
stroke limitor, fixed together by means of bolts, the piston is forced down by the spring causing
and between which the one valve ring, together the lifting bush with push pins to move upwards
1. Buffer spring
A Discharge
B Suction
FIG. 4.3 SCHEMATIC CONSTRUCTION AND OPERATION OF SUCTION AND DISCHARGE VALVE
1. Lever
2. Piston housing
3. Spring
4. Control piston
6. Push pin
7. Lifting bush
Crankcase pressure = suction pressure for both pump consisting of three gears with the centre
single- and two-stage compressors gear driven by the crankshaft.
In order to prevent excessive discharge pressures
The oil suction and oil discharge filters are fitted
in the compressor, one or more overflow safety
to the pump. The oil suction filter contains a metal
valves (number depends on the type of
gauze filter element; the oil discharge filter is
compressor) are provided. These valves act on the
provided with a paper filter element retaining the
difference between suction and discharge
fine (metal) particles suspended in the oil.
pressure and moreover, in the case of two-stage
compressors, between suction and intermediate The oil is drawn from the crankcase via the oil
pressure. suction filter. The pressures dilevered by the gear
The spring-loaded overflow safety valves are pump are a lubricating pressure and a control
adjusted at the works; they blow the gas off to pressure to operate the valvelifting mechanisms
suction when there is an excessive pressure (capacity control). The pressurized lubricating oil is
difference. delivered to the discharge filter, led back to the
The overflow safety valves are fitted externally pump housing and into the lubricating system via
between the suction manifold and the HP and/or the crankshaft. The lubricating oil pressure
LP discharge manifold. depends on the setting of the lubricating oil
pressure regulator built into the lubrication system
4.9 OIL PUMP, FILTERS AND CONTROL OIL of the compressor (see also par. 4.10, Lubrication
SYSTEM (see fig. 4.5) system). The control oil pressure delivered by the
The oil pump is fitted on the bearing cover pump is regulated by a built-in relief valve
opposite the compressor driving end and is connected to the lubrication system. Excess of
directly driven by the crankshaft. control oil is thus used for lubrication. The control
The pump housing accomodates a double gear pressure has been set at 13 - 15 bar above suction
pressure.
1. Oil suction filter 4. Gear pump B Control oil pressure to valve lifting mechanisms
2. Oil discharge filter 5. Hydraulic time delay for unloaded starting and capacity control
3. Relief valve valve
C Oil suction from crankcase
FIG. 4.5 OIL PUMP, FILTERS AND CONTROL OIL SYSTEM
The accessories of the compressor include those The gauges indicate the pressure in bars; at a pressure
devices and systems with which the efficient lower than the atmospheric, the pressure gauge
operation of the compressor in the installation can indicates a negative value. The scale of suction,
be promoted and checked and those which, in the discharge and intermediate pressure gauges is
event of failures prevent the compressor from adjusted to the refrigerant in the plant, as besides the
being damaged. pressure scale also the saturation temperatures
The accessories should be distinguished as follows: corresponding to te overpressures are given.
A) Accessories the use of which has been
prescribed by the compressor 5.2 PRESSURE SAFETY SWITCHES
manufacturer,among which: In order to protect compressor and plant, safety
• Pressure gauges for suction pressure, discharge switches for discharge pressure, suction pressure
pressure and oil pressure; in the case of two stage and lubricating oil pressure are provided. They are
compressors also for the intermediate pressure; mounted on a panel and connected to the
pressure connections of the compressor via the
• Pressure safety switches for discharge pressure pressure gauge valves. The switch contacts are
and lubricating oil pressure; incorporated in the control current circuit for the
• For two-stage compressors: Electrically operated ca- drive motor of the compressor.
pacity control (also to be used as run-in control with The discharge pressure safety switch (Danfoss
which the compressor can proceed as favourably as pressure control type RT 5 for halocarbon
possible to two-stage compression during the time refrigerants, type RT 5A for NH3) protects the
the installation attains the operating conditions). compressor against excessive discharge pressure.
B) Accessories the use of which is deemed In case the preset pressure is exceeded, the
necessary by the installation engineer, control current circuit is interrupted and the
amongwhich: compressor stops.
• Suction pressure safety switch; The suction pressure safety switch (Danfoss
pressure control type RT 1 for R12, R22, etc. type
• Cylinder head temperature safety device; RT 1A for NH3) protects compressor and plant
• Crankcase heating; against too low suction pressure. In case the
pressure drops below the preset value, the
• For single-stage compressors: Manually or compressor is switched off.
electically operated capacity control.
The choice of the accessories depends on the type The switching pressure of both switches can be
of plant, the refrigerant used and the operating adjusted by turning the main spindle after
conditions; therefore, this choice will be removing a cap on the top side of the housing.
determined by the installation engineer. The adjustment can be read on a scale behind the
window in the front cover. Between the cut-out
In this chapter only those accessories are described pressure and the pressure at which the switch
that can be supplied by the manufacturer of the makes circuit again, there is a fixed difference of
compressor. If other accessories have been approx. 0.4 bar in the suction pressure safety
provided by the installation engineer, their switch and of approx. 1 bar in the discharge
description can be found in the plant manual. pressure safety switch.
5.1 PRESSURE GAUGES Both pressure safety switches are provided with a
locking device when cut out, so that, on return of
The pressure gauges necessary for checking the the original pressures, the compressor does not
correct operation of compresssor and installation become operative automatically again. The
are mounted on a panel, each of them being switches can be unlocked by pushing a green
connected to the compressor via a shut-off valve. button on the side; however, this may be done
For single-stage compressors three pressure only after the cause of the switching off of the
gauges have been provided, viz. a suction pressure compressor has been investigated and the failure
gauge, a discharge pressure gauge and an oil has been remedied. In both switches an auxiliary
pressure gauge; moreover, for two-stage contact is provided for connection a pilot lamp or
compressors, there still is an intermediate pressure a klaxon.
gauge.
The lubricating oil pressure safety switch protects the or by a push button switch in the control
compressor against too low lubricating oil pressure. current circuit for the drive motor.
The lubricating oil pressure is the difference between
oil pressure and crankase pressure (=suction pressure) 5.3 CRANKCASE HEATING
indicated by pressure gauges. The lubricating oil
pressure safety switch reacts to this difference, which During standstill of the compressor at low
should be at least 1 bar to ensure proper lubrication. ambient temperatures
• condensation of the refrigerant in the crankcase
Two types of lubricating oil pressure safety may occur;
switches may be used:
a) with locking device and built-in thermal time • the refrigerant may dissolve in the oil to a
delay relay (Danfoss differential pressure control higher extent;
type MP 55A for NH3). • the viscosity of the oil may become so high that
With this switch, a differential pressure between 0.3 too much delay occurs during starting
- 4.5 bar can be adjusted by means of a set disc These phenomena can be prevented by maintaining
under the upper pressure bellows inside the switch. the crankcase at a certain temperature. This is
The effected by a heating element which is screwed into a
setting value should be at least 1 bar. If the sleeve provided under the crankcase. The electrical
differential pressure decreases, the control current connection should be designed so that the element
circuit of the motor wil be interrupted with a delay can only operate during compressor standstill.
of 60 secs. A pilot lamp or klaxon can be connected
via an 5.4 CYLINDER HEAD TEMPERATURE SAFETY
auxiliary contact. When in “break” position, the DEVICE (see fig. 5.1)
switch is locked. This lock should be released only The compressor discharge temperature, measured on
after 3 mins. by pressing the reset button on the the outside of the discharge line upstream the
switch. The permanently set contact differential discharge valve, must not exceed 140 °C. It is
amounts to 0.2 bar, so that the lubricating oil nevertheless possible that, due to a failure, the
pressure must be at least 1.2 bar to operate the temperature in one or more cylinder heads suddenly
switch again. In order yet to re-start the compressor rises, in which event danger of damage arises. In
and to allow it to build up a sufficient lubricating oil order to protect the compressor against such danger,
pressure, a thermal time delay relay is provided, it can be equipped with an electronic temperature
which leaves the contacts closed during 60 seconds. safety device with sensing elements on all cylinders or
In order to check the safety switch for proper on some of them. This safety device interrupts the
operation, a test device is provided inside at the left control current circuit at a local temperature of
side of the switch. When this device is depressed approx. 170 °C after which the compressor stops. The
and kept in this position, the compressor should relay to which the temperature sensing elements are
stop after 60 seconds. connected, is locked when cut out. A pilot lamp or
b) without locking device and without thermal
time delay relay (Danfoss differential pressure Î
control type RC 260A).
Ì
With this safety switch, the lubricating oil pressure
Í
can be adjusted between 0.5 and 4 bar by means Ê Ê Ë
of a set disc which is accessible after removing the
front cover. The setting value should here, too, be M
at least 1 bar. An auxiliary contact is provided for
connecting a pilot lamp or a klaxon. The
permanently set contact differential is 0.3 bar, so
that the lubricating oil pressure should be at least
1.3 bar to cause the switch to make circuit again. 1. Temperature sensing element in cylinder head
2. Relay unit
In order to start the compressor and to allow it to 3. Motor overload protector
build up lubricating oil pressure, the contact of the 4. Control current circuit
safety switch must have been shunted with the aid 5. Reset button
of a separate time delay relay with locking device FIG. 5.1 CYLINDER HEAD TEMPERATURE
SAFETY DEVICE
klaxon can be connected via auxiliary contacts (see This control system enables the compressor to be
the plant manual). controlled in maximum four steps from minimum
up to maximum capacity. After stopping the
5.5 CAPACITY CONTROL compressor it is desirable to set the oil distributor
In order to adapt the compressor capacity of the again to position 1 (also refer to chapter 7).
cooling load of the moment, a number of cylinders A survey of the operating cylinders in the various
can be put in or out of action either individually of
collectively. In this case use is made of the valve
lifting mechanism fitted on each cylinder (see
chapter 4) and operated by the pump control oil
pressure.
The capacity control may be of two-fold disign:
a) with a manually operated oil distributor
(single-stage compressors only);
b) with one up to four three-way solenoid valves
which are operated electrically and thus enable
automatic control.
Regardless of the control system applied, one or
more cylinders are connected direct to the control
oil pressure; these cylinders become automatically
operative after the unloaded starting of the
comrpessor. The other cylinders can be cut in or out
in one or more stages.
Especially in the case of two-stage compressors the
use of these switching possibilities can be limited by
the operating conditions of the installation (refer to
the plant manual). Moreover, the number of
switchings per unit of time of one individual
cylinder, as well as of the whole compressor, is tied FIG. 5.2 SCHEMATIC DIAGRAM OF
to a maximum (see chapter 8, Supervision during THE MANUALLY OPERATED
compressor operation). CAPACITY CONTROL
positions of the oil distributor is indicated in table
5.5.1 MANUALLY OPERATED CAPACITY 5.1, overleaf.
CONTROL (single-stage compressors only)
(see fig. 5.2) 5.5.2 ELECTRICALLY OPERATED CAPACITY
CONTROL (see fig. 5.3)
In this control system the compressor is fitted with
an oil distributor which can be set by hand to For distributing the control pressure to the valve
serveral positions. The distributor has six ports: lifting mechanisms of the cylinders or cylinder
one for the control pressure connection, one for groups, use is made in this system of one up to
the oil return connection and four for the four electrically operated three-way solenoid
connection of the valve lifting mechanisms of the valves; their number depends on the size of the
cylinders or cylinder groups. Depeding on the compressor. The solenoid valves fitted on the
compressor size, one or more of the last-named compressor each have three connections: one for
ports may be out of use. the control pressure (2), one for the oil return (0)
The distributor has five positions. In position 1 the and one for the valve lifting mechanism (1).
control pressure is blocked and the valve lifting When the valve is not energized, the control
mechanisms are connected to the oil return. Only pressure connection in each valve is blocked, and
the cylinders directconnected to the control the valve lifting mechanism is connected to the oil
pressure are then in operation. In the positions 2, return, so that the cylinder or cylinder group is out
3, 4 and 5 the control pressure is admitted step by of action. As soon as the valve is energized, the oil
step to the valve lifting mechanisms of the return is shut off and the control pressure is
connected cylinders or cylinder groups, which then admitted to the valve lifting mechanism, causing
become operative.
5 5 5 5 5
4 4 4 4 4
3 3 3 3 3
POSITION 2 2 2 2 2
OF OIL 1 1 1 1 1
DISTRIBUTOR
starting
and
APPLICATION control up to maximum capacity
minImum
capacity
Each figure between
brackets refers to the
COMPRESSOR TYPE OPERATING CYLINDERS swept volume expressed as
a percentage of the full
load swept volume
1 1 Typical numbering of
RC29 • 2 cylinders
(50) (100)
• 2 12 12
RC49 3• 3• 34
(50) (75) (100)
1•3 1•3 123 1•3 123
RC69 ••• •5• •5• 45• 456
(33) (50) (67) (83) (100)
TABLE 5.1 STANDARD STEPS OF THE MANUALLY OPERATED CAPACITY CONTROL
(SINGLE—STAGE COMPRESSORS ONLY)
VALVE NO.
❍ non-
energized
● energized
starting
APPLICATION and
control up to maximum capacity
min.
capacity
Each figure between brackets
refers to the swept volume
COMPRESSOR TYPE OPERATING CYLINDERS expressed as a percentage of the
full load swept volume
VALVE NO.
m non-
energized
l energized
minimum
APPLICATION starting control up to maximum capacity
capacity
Each figure between brackets refers to
COMPRESSOR TYPE OPERATING CYLINDERS the swept volume expressed as a
percentage of the full load swept volume
Cylinder no.1 •2
omitted •• Typical
RC219 34
3• numbering
(100) of cylinders
1•• 1•• 12• 123
RC429
••• •56 •56 456
“energized”. However, in this case, the valve can externally against the HP-suction line of the
no more be operated electrically in the usual way. compressor (see fig. 5.4, overleaf). At compressor
standstill the supply of liquid is cut off by a
5.6 INJECTION INTERSTAGE GAS COOLER (only solenoid valve located upstream the expansion
in two-stage comressors) valve. This solenoid valve should be connected
In two-stage compressors, an injection interstage electrically so that it opens only when the
gas cooler may have been provided between the compressor has come up to speed and LP- as well
LP-discharge connection and the HP-suction as HP-cylinders are in operation (see the chapter
connection. This cooler cools the gas compressed “Capacity control”).
by the LP-cylinders down to 5 to 6 K above the
saturation temperature corresponding to the
intermediate pressure.
The interstage cooler consists of an amply
dimensioned connecting tube, into which, on the
LP-discharge side, liquid refrigerant is injected.
This injection takes place either direct on the
interstage gas cooler or via a separate injection
liquid cooler. Due to the evaporation of this
liquids, the temperature of the gas to be sucked
by the HP-cylinders is reduced. The amount of
liquid is controlled by a thermostatic expansion
valve, whose temperature bulb must be clamped
C LP-Discharge
D HP-Suction
This chapter deals with the starting and stopping d) Check whether the discharge stop valve, the
of the compressor in a plant which, after the test pressure gauge valves and (in the case of
run, has been delivered completely ready for two-stage compressors) the stop valves in the
operation by the installation engineer. If further intermediate pressure line are open.
contains instructions for resetting the lubricating
e) In the case of a compressor provided with a
oil pressure regulator and pressure safety
manually operated capacity control: set the oil
switches, if this should be necessary.
distributor to position 1:
It is recommended to start and stop the In the case of a compressor provided with an
compressor according to a fixed procedure in electrically operated capacity control: Check
order to prevent errors and possible damage. whether the manual control lever of all solenoid
Especially in the case of plants with manual valves is in its lowest horizontal position.
control, the sequence of the necessary operations
has to come up to certain requirements. f) (not within 3 minutes after the compressor was
Therefore, in the instructions given below, stopped) Start the compressor and check
reference is made, wherever necessary, to the whether the oil pressure increases.
plant manual. If at some point the plant manual g) Slowly open the suction stop valve, thereby
differs form this instruction manual, the watching the suction pressure which may not
installation engineer should be consulted. exceed 6 bar (on gauge). Also be careful that
no liquid hammer occurs, especially in plants
7.1 STARTING THE COMPRESSOR with lower suction lines.
When starting the compressor, distinction should h) In the case of single-stage compressors with
be made between: capacity control: After the compressor has
1) Starting the compressor for the first time after started up and one or more cylinders have
the plant has been out of operation for a long automatically become operative, cut in the
period of time (for example, on account of other cylinders as and when required, thereby
seasonal standstill or maintenance operations). watching the maximum allowable amperage (it
for manually controlled plants as well as for those must not be higher than the amperage stated
operating automatically the starting procedure on the motor).
given below should be followed exactly. In the case of two-stage compressors with
2) Restarting the compressor in an already capcity control: 3-4 minutes after the
operational plant. compressor has started and one HP-cylinder
In the case of manually operated plants only the becomes operative automatically, cut in the other
instructions mentioned under b, e, f, h and j need cylinders stepwise, thereby watching the
to be followed, as well as those included in the discharge temperture on both the HP- and LP-side
plant manual. In the case of automatically (max. 140 °C), the intermediate pressure (max.
operating plants, this starting procedure is saturation intermediate temp. +10 °C) and the max.
incorporated in the control system and therefore allowable amperage (not to be higher than the
does not generally require any special care. amperage stated on the motor nameplate).
The starting procedure is as follows: j) (if cylinder jacket cooling is applied). Check the
a) Consult the plant manual. cooling water flow.
b) Make sure that the oil level in the crankcase is k) Adjust the opening of the pressure gauge stop
correct (see Chapter 8) and check whether the valves so that the gauge pointers do not
shaft seal housing and both oil filter housings vibrate any longer.
are filled with oil (especially after maintenace
work). l) (not during the running-in period of the plant).
Open the stop valve in the return line of the oil
c) Check whether the suction stop valve and the separator.
stop valve in the return line of the oil separator CAUTION! In case of reduced cooling load it is
are closed. not allowed to cut out so many cylinders of a
compressor already operating in two stages that
only the HP-cylinder is still operating. At least
two LP-cylinders should remain operative.
3
3
2
2
1 Main spindle
2 Graduated scale
3 Setting scale
FIG. 7.2 SETTING OF PRESSURE SAFETY SWITCHES
FREQUENCY
CHECK POINTS REMARKS
monthly
weekly
daily
Oil level in crankcase The oil level must be between 1 and 3 quarters
• height of the sight glass. For topping up oil, refer to
Chapter 9, Compressor Maintenance.
Colour of the oil The oil should be transparently clear. A disappearing
• white colour points to dissolved refrigerant.
Lubricating oil pressure The indication of the oil pressure gauge should be
• 1.5 bar higher than the value shown by the suction
pressure gauge.
Oil temperature The maximum allowable temperature is 70 °C,
• measured on the suction line to the oil suction filter.
Return from oil separator To be checked only when a sight glass is provided in
• the oil return line.
Oil leakage • Remedy visible oil leakage.
Suction pressure • Refer to plant manual.
Discharge pressure Refer to plant manual. For the max. allowable
• discharge pressure refer to Chapter 3, Technical data
of compressor.
Suction temperature The suction temperature should indicate at least 5 K
• superheat.
Discharge temperature The maximum allowable discharge temperature is
• 170 °C.
Cooling water temperature (if Water temperature must be higher than condensing
water cooling is applied) • temperature.
Crankcase heating (if provided) During compressor standstill the crankcase bottom
• side must remain warmer than the surroundings.
Condition of V-belts Check belts for: 1) wear (fraying, cuts etc.) and
ensure that they do not touch the groove bottom; 2)
Tension. Too low a tension gives rise to excessive
•
flapping or oscillation in operation. For correct
tension consult the instructions given by the V-belt
supplier.
Adjustment and operation of pressure Refer to Chapter 7 and to the plant manual.
safety switches •
Switching frequency of the The time interval between stopping and starting
compressor •should be at least 10 minutes.
Capacity control (if provided) The time lag between the unloading and loading of
• one cylinder or cylinder group should generally be at
least 3 minutes.
Number of operating hours Check the number of operating hours in view of any
• maintenance operations to be carried out.
Apart from the above check points, the sound produced by the compressor provides a proper standard
for its mechanical condition. If abnormal sounds are audible, their cause should be traced and removed
immediately in order to prevent serious breakdowns at inconvenient times.
Major inspection to be
installation engineer
carried out by
1
) time dependent on pollution.
2
) Only for NH3-compressors
3
) In the case of a possible rapid pollution of the oil, it should be drained and renewed sooner than at the times given
above.
For most of the maintenance operations the compressor must be evacuated before in order to remove
the refrigerant gas. after completion of the operations the compressor has to be purged. Both compres-
sor evacuation and purging are dealt within this chapter.
of a separate oil pump. This pump enables the oil h) Fix a hose to this connection point and put its
to be forced into the crankcase via the oil open end at some safe place in the free air.
charging valve, against suction pressure. If this oil
j) Slowly open the pressure gauge stop valve so
pump is not available, oil can be charged by
that the discharge gas still present in the
reducing the crankcase pressure to below
compressor can escape via the hose.
atmospheric pressure. the procedure is as follows:
a) Connect a hose to the oil charging valve after k) Remove the hose.
removing the cap nut with gasket. NOTE:
Connecting the line to the lower side of the
b) Fill the hose with oil and emerge its loose end in
discharge pressure safety switch and removing the
a reservoir containing a sufficient amount of oil.
shunting of the contacts in the suction pressure
c) Close the suction stop valve to such an extent safety switch should be effected only during
that the suction pressure falls below the compressor purging after the maintenance
atmospheric pressure. operations have been completed.
d) Keep the oil charge valve open as long as the 9.5 DRAINING AND CHANGE OF OIL
oil in the crankcase has attained the equired
level again. Take care that no air is being drawn Small impurities in the refrigerant gas that are not
into the crankcase. retained by the suction strainer (for example, fly
rust, especially in the case of NH3 installations)
e) Slowly open the suction stop valve in order to eventually find their way in the lubricating oil
prevent liquid hammer. which thus becomes dirty. Therefor, in the case of
f) Remove the hose and replace the cap nut with a new installation (or after extension or alteration
gasket onto the oil charging valve. of an exisisting installation) the oil should be
renewed twice during the first 100 operating
hours of the compressor (refer to the
9.4 EVACUATION OF COMPRESSOR maintenance schedule on page 9.1).
Draining and change of oil must be carried out
a) Close the suction stop valve and check whether
with the compressor being at operating
the discharge stop valve is open.
temperature. Proceed as follows:
b) Close the stop valve in the oil return line of the a) Evacuate the compressor (refer to par. 9.4).
oil separator. b) Drain the oil via the oil charging valve. remove
c) In the case of two-stage compressors with the cover and sealing ring of one or more
injection interstage gas cooler: shut off the service openings on the compressor side.
liquid lines of the interstage cooler. c) Clean the inside of the crankcase with a
In the case of two-stage compressors with flash non-fibrous cloth (don’t use cotton waste!);
interstage cooler: refer to the plant manual. also mind the sight glass. At the same time
d) Shunt the electric contacts of the suction clean the oil filters (refer to par. 9.6, point b)
pressure safety switch. up to and including g).
e) Start the compressor and wait until the suction d) Fill the crankcase with fresh oil as far as possible
pressure is below the atmospheric pressure. via the service opening(s).
MIND: Stop the compressor immediately as soon e) Close the service opening(s) again by placing
as the lubricating oil pressure (i.e. the difference the cover(s). Especially check the condition of
between oil pressure and suction pressure) the sealing rings so as to prevent leakage
becomes lower than 1 bar. afterwards.
f) Stop the compressor and close the discharge f) Fill the crankcase further with oil by means of a
stop valve. separate oil pump via the oil charging valve
until the oil has reached the required level.
g) Close the stop valve of the discharge pressure If no separate oil pump is available, proceed
gauge and disconnect the line at the lower side with point g.
of the discharge pressure safety switch.
REMARK!
All valve parts can be obtained separately.
h) Carefully clean all valve parts and slightly oil
them with compressor oil; then reassemble the
discharge valve.
head. Make sure that the buffer spring is f) Open the discharge valve and watch the
centred by the cover. Pull the cover with the discharge and suction pressure gauges,
nuts on the long studs so far down that the particularly if maintenance operations have
other studs been effected on the valves. Only the discharge
sufficiently project beyond the cover. pressure gauge may rise; if also the suction
pressure gauge rises distinctly, this is indicative
n) Screw the nuts onto the other studs and firmly
of leaking valves due, for instance, to their
tighten them.
incorrect assembly.
p) Purge the compressor (refer to par. 9.9). If necessary, remedy this defect.
g) Start the compressor and slowly open the
REMARK!
suction stop valve (mind liquid hammer!).
In order to reduce the downtime involved in this
valve inspection, it is recommended to have as h) Open the shut-off valve in the return line of the
many complete valve assemblies in stock as there oil separator.
are cylinders on the compressor.
j) For two stage compressors: open the shut-off
The valves can then be exchanged with the valves
valves in the liquid lines of the interstage cooler.
to be checked; the original valves can then be
inspected at leisure and, if necessary, repaired or k) Keep the compressor running for some minutes.
replaced.
l) Purge the refrigerating installation (refer to
9.9 COMPRESSOR PURGING plant manual).
When the compressor has been opened for
carrying out maintenance operations, it must be
purged before being put into operation again.
Purging can be effected by means of the
compressor itself, whereby the situation after
compressor evacuation is taken as a starting point.
The procedure is as follows :
a) For compressors equipped with capacity control:
Cut out as many cylinders as possible.
b) Start the compressor; the air in it is now blown
off via the line disconnected during evacuation
at the lower side of the discharge pressure
safety switch.
c) Cut in the other cylinders step-wise as soon as
the suction pressure has dropped considerably,
and wait until the suction pressure ceases to fall
or the oil lubricating pressure safety switch
becomes operative.
The fault-finding table below may be helpful to failure must often be sought in the refrigeration
quickly trace and remedy failures that interfere installation itself. Therefore, it is necessary, in
with the proper operation of the compressor. It is addition to this fault-finding table, also to consult
emphatically pointed out that the cause of a the plant manual.
A Discharge pressure too 1. Discharge stop valve not wide open enough 1. Open fully
high, according to plant 2. Discharge pressure gauge defective 2. Repair or replace
manual (discharge 3. Condenser capacity too small due to:
pressure safety switch
may possibly become op- 3a. Pollution 3a. Clean
erative) 3b. Hardly or no supply of water 3b. Increase water supply
3c. Fans do not operate 3c. Switch on fans
4. Air in the system 4. Purge system
C Suction pressure too high 1. Capacity control does not operate 1. Repair*
2. Compressor capacity too small 2. Consult installation engineer
3. Suction pressure gauge defective 3. Repair or renew
4. One or more suction valves defective 4. Repair or renew
5. One or more discharge valves defective 5. Repair or renew
6. By-pass safety valve is leaking 6. Repair or renew*
D Suction pressure too low 1. Suction stop valve not wide open enough 1. Open fully
(suction pressure safety 2. Suction gas strainer poluted 2. Clean
switch may possibly be- 3. Injection control not adjusted correctly 3. Re-adjust control
come operative)
4. Too little refrigerant in installation 4. Top-up with refrigerant
5. Suction pressure gauge defective 5. Repair or renew
E Crankcase frosted or wet 1. Liquid refrigerant in crankcase due to: In the case of big amount of
just after starting, refrigerant: stop compressor and
possibly also during op- contact installation engineer
eration 1a. Room temperature too low 1a. Provide for crankcase heating or, if
provided, check it for proper
operation
1b. Return from oil separator mainly consists 1b. Contact installation engineer
of liquid refrigerant
1c. Installation operates too wet 1c. Re-adjust installation and provide
for superheat
1d. Liquid separator too small 1d. Contact installation engineer
F All cylinders out of 1. Control pressure for valve lifting mechanism 1. See K
action while compressor too low
is operating
G Too high oil 1. Type of oil not according to lubrication oil 1. Consult installation engineer
consumption table 3.1 (too thin oil)
2. Compressor operates onloaded too 2. Consult installation engineer
frequently
3. No return from oil separator 3. Check the operation of float valve
in oil separator
4. O-rings around control piston of valve lifting 4. Replace O-rings
mechanism worn or defective
5. Non-return valve at the bottom of suction 5. Replace valve*
chamber in cylinder defective
6. Worn out oil scraper rings 6. Replace rings*
7. Loss of oil due to leakage 7. Repair
H Too high oil pressure 1. Lubricating oil pressure regulator not 1. Re-adjust or repair
during normal adjusted properly or defective
operation at working 2. Defective oil pressure and/or suction 2. Repair or replace
temperature pressure gauge
J Too low oil pressure 1. Tool little amount of oil in crankcase 1. Top up oil
2. Oil suction and/or discharge filter is dirty 2. Clean or renew
3. Lubricating oil pressure regulator not 3. Re-adjust or repair
adjusted properly or defective
4. Liquid refrigerant in crankcase 4. See E
5. Defective oil pressure and/or suction 5. Repair or replace
pressure gauge
6. Too large bearing clearance 6. Renew bearings*
K Too low or no control 1. Hydraulic time delay valve in oil pump is 1. Dismantle and repair oil pump*
pressure jammed
2. Relief valve in oil pump leaks 2. Disassemble and repair valve
The operation marked with an * in the column "Remedy" should be carried out by the installation engineer
The standard illustrated parts list on the following pages is meant for identification and accurate specification of current
spare parts. Refer to the Monitron CR instruction manual, Chapter 8, Par. 8.7, if equipped with a Monitron CR-Control.
In order to facilitate quick retrieval of the required parts, the list and corresponding figures is divided into the following
groups of parts:
Figures asterisk is used instead of the Ref. no., this means that the
relevant part cannot be obtained separately.
All parts shown in the figures bear an item number.
When for some part no quantity has been given, the
Assemblies are indicated by a dotted frame with separate
quantity required depends on the compressor size. When
item number around the parts included in that particular
determining the required quantity of parts, it should be
assembly; the parts themselves bear the same item number,
considered that the listed quantities relate to the
followed by a sequence number (e.g. 2.1, 2.3, 2.3, etc.).
corresponding figure and not to the compressor as a
Parts lists whole. When ordering, for example, bearings for two
connecting rods, the quantities stated in the relevant list
The parts are specified by the headings “Item”,
must be doubled, because these apply to one connecting
“Description” “Ref. no.” and “Qty” (= Quantity). If an
rod only.
I M P O R T A N T ! How to order!
It is emphatically pointed out that a prompt despatch of the correct spare parts can be guaranteed only if the following
information is given:
1. Type designation of the compressor
shown on the compressor name plate
2. Serial number of the compressor
3. Quantity, Description and Ref. No. of the required parts.
25X Set of valve parts R-NH3-12 RC9 48.27.512 1 for 12 bar-type valve
25Y Set of valve parts R-NH3-21 RC9 consisting of: 48.27.522 1 for 21 bar-type valve
25.1 Valve disc 0x23x3 09.42.230 1
25.2 Valve guide 22x75 48.40.322 1
RC9-1
RC9-2
RC9-3
4 Valve-lifting mechanism * 1
4.1 Plug G33 01.36.336 1
4.2 O-ring 3x33 09.52.300 1
4.3 Piston housing FA55M 27.10.501 1 with O-ring groove only 1)
4.4 Spring 3.2x22x9x80 11.31.322 1
4.5 Control piston 27.10.520 1
4.6 Lever FA55 27.10.550 1
4.7 O-ring 3.53x23.4 09.52.360 1
4.8 O-ring 3.5x36 09.52.348 1
4.9a Cover 060G13 05.38.013 1
4.10a Hex. head bolt M10x25 01.10.525 2 for 2- and 4-cyl. compressors
4.11a Nipple coupling 6G13 03.38.136 1
4.9b Cover KA60x85A 27.14.605 1
4.10b Socket head screw M10x20 01.04.520 2 for 6-cyl. compressors only
4.11b Nipple coupling 6G10 03.38.106 1
5 Oilit gasket 20x58x1.5 09.07.020 1 for housing (4.3) with gasket recess
O-ring 09.52.367 1 for housing (4.3) with O-ring groove1
6 Stud M8x22 01.51.422 4
7 Washer M8 11.13.401 4
8 Hex. nut M8 01.15.410 1
1
) This piston housing (Ref. Nr. 27.10.501) always includes an O-ring with Ref. Nr. 09.52.367.
RC9-4
RC9-5
RC9-6
RC9-7
5 Set of discharge valves and springs 11.34.850 1 one set per cylinder
6 Set of suction valve and springs 11.34.852 1 one set per cylinder
1
) A mounting instructions leaflet is always supplied with each complete shaft seal.
RC9-8
RC9-9
1Y Oil suction filter assy RC9 07.15.969 1 on compr. types RC69 & RC429
RC9-10
RC9-11
1.15 1.14 1.13 1.12 1.11 1.10 1.9 1.6 1.8 1.7 1.6 1.5 1.4 1.3 1.2 1.1
1.16A 1.3
1.17 1.16B
2
1.18 4
3
RC9-12
RC9-13
4
5 6 7 15 16
6
8
9
7
10
11 12 13 14
RC9-14
RC9-15
RC9-16
RC9-17
2 Clamping sleeve * 1
3 Tire clamp (coupling tool) 15.08.232 1 for coupling element 42 1)
Tire clamp (coupling tool) 15.08.244 1 for coupling element 61 1)
Tire clamp (coupling tool) 15.08.280 1 for coupling element 91 1)
Tire clamp (coupling tool) 15.08.376 1 for coupling element 182 1)
OILIT SEALING RINGS FOR SUCTION-, INTERMEDIATE- AND DISCHARGE CONNECTIONS (FIG. RC9-18)
LP DISCHARGE HP SUCTION
MODEL SIZE PART NO. SIZE PART NO. SIZE PART NO. SIZE PART NO.
RC429 84X 98X1.5 09.03.084 48X58X1.5 09.03.048 84X98X1.5 09.03.084 84X98X1.5 09.03.084
RC9-18
Grasso Products B.V. P.O. Box 343 • 5201 AH ’s-Hertogenbosch • The Netherlands
Phone: +31 (0)73 - 6203 911 • Fax: +31 (0)73 - 6231 286 • E-Mail: [email protected]