Installation & Operation Manual Energy Storage System (ESS) Storion-T50/T100 (Off-Grid, Indoor) V01
Installation & Operation Manual Energy Storage System (ESS) Storion-T50/T100 (Off-Grid, Indoor) V01
Installation & Operation Manual Energy Storage System (ESS) Storion-T50/T100 (Off-Grid, Indoor) V01
V01
IMPRINT Your Smart Energy
IMPRINT
www.alpha-ess.cn
Jiu Hua Road 888, Nantong High-Tech Industrial Development Zone, Nantong City, China,
226300
www.alpha-ess.de
www.alpha-ess.it
www.alpha-ess.com
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 1 of 58
Your Smart Energy Copyright Statement
Copyright Statement
This manual is under the copyright of Alpha ESS Co., Ltd, with all rights reserved. Please
keep the manual properly and operate in strict accordance with all safety and operating
instructions in this manual. Please do not operate the system before reading through the
manual.
Version Information
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 2 of 58
Content Your Smart Energy
Content
IMPRINT .......................................................................................................... 1
Copyright Statement ...................................................................................... 2
Version Information ....................................................................................... 2
Content ........................................................................................................... 3
1. Introduction.............................................................................................. 5
Brief Introduction............................................................................... 5
Explanation of Terms ........................................................................ 5
2. Safety Instructions .................................................................................. 7
Manual Keeping ................................................................................. 7
Operator Requirements ..................................................................... 7
Protection of Warning Sign............................................................... 7
Setting of Warning Sign for Safety ................................................... 7
Live Line Measurement ..................................................................... 7
Measuring Equipment ....................................................................... 8
Electrostatic Prevention.................................................................... 8
Moisture Prevention .......................................................................... 8
Operation After Power Failure .......................................................... 8
Minimum Personal Protective Equipment ..................................... 8
3. Product Description .............................................................................. 10
Appearance of the Product ............................................................. 10
Product Characteristics .................................................................. 11
Parameters of Components ............................................................ 11
PCS ........................................................................................................... 11
Battery System .......................................................................................... 14
4. Installation.............................................................................................. 21
Installation Precautions .................................................................. 21
Parts List .......................................................................................... 21
Installation ........................................................................................ 23
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 3 of 58
Your Smart Energy Content
Wiring ............................................................................................... 30
Battery Side Wiring ................................................................................... 30
Inverter Side-Wiring .................................................................................. 34
Dry Contact Description ............................................................................ 36
5. Operation................................................................................................ 37
Switch on.......................................................................................... 37
Check Before Operation ........................................................................... 37
Power-on Procedures ............................................................................... 37
Notes................................................................................................. 53
7. Troubleshooting .................................................................................... 55
Battery and BMS Troubleshooting ................................................. 55
Error Type ................................................................................................. 55
Emergency Handling Plan ........................................................................ 56
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 4 of 58
Introduction Your Smart Energy
1. Introduction
Brief Introduction
This manual applies for Storion-T50/T100 Li-ion battery energy storage system, mainly
includes:
Introduces the product use, operating notes and qualification of operators of T50/T100 Li-ion
battery energy storage system.
(4) Operation
Introduces items in maintenance of T50/T100 kWh Li-ion battery energy storage system,
including attentions.
(6) Trouble-shooting
Introduces the faults of T50/T100 Li-ion battery energy storage system, causes to faults, and
processing method.
Explanation of Terms
(1) Lithium iron phosphate cell (LiFePO4)
Basic unit constituted by electric poles and electrolytes; Each cell is independent and closed.
Notes: For packs from same company, all the details such as physical size,
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 5 of 58
Your Smart Energy Introduction
working performance and interface specification should be consistent so that all the
packs are compatible and interchangeable.
Electronic equipment collection for monitoring the operating information of cells, packs and
system units (such as voltage, current, temperature, protective parameter of batteries),
evaluating the state of charge (SOC), the state of health (SOH) and cumulative processed
energy and protecting batteries for safety, etc.
A combination of a bidirectional converter and a battery system unit, which can be used as an
independent load or be controlled directly by monitoring system.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 6 of 58
Safety Instructions Your Smart Energy
2. Safety Instructions
Manual Keeping
This manual contains important information about operating the system. Before operating,
please read it very carefully.
The PCS should be operated in strict accordance with the description in the manual, in case
that it causes damage or loss to equipment, personnel and property.
Operator Requirements
The operators should get a professional qualification, or trained.
The operators should be familiar with the whole storage system, including compositions and
working principles of the system.
While carrying out maintenance work it has to be at least two operators in the filed all the time.
They can not operate on any equipment until they are all powered off and fully discharged.
It is strictly prohibited for any maintenance to be carried out when equipments are on or charged.
Obvious signs should be set at front switch and rear-level switch in case of accidents caused
by false switching.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 7 of 58
Your Smart Energy Safety Instructions
Equipment protection must be taken in live line measurements (e.g.: insulation gloves).
The measuring equipment should be connected and used correctly to ensure personnel safety.
When measuring, at least two workers are needed.
Measuring Equipment
To ensure the electrical parameters to match requirements, related measuring equipment are
required when the system is being connected or tested.
Ensure that the connection and use matches specification in case of electric arc or shock.
Electrostatic Prevention
Contact or improper operation of the printed circuit board or other ESD sensitive components
may result in damage to the device. Unnecessary contact should be avoided.
Moisture Prevention
It is very likely that moisture may cause damages to the system.
Do not open the container door if the humidity is larger than 95%.
The PCS maintains fatal voltage even when both the DC or AC side are disconnected, so it
must be tested by the multimeter for safety before operation.
When doing maintenance works such as checking cables or wires, measuring voltage,
replacing small electrical parts or cleaning modules and brackets, as minimum the following
protective equipments are required:
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 8 of 58
Safety Instructions Your Smart Energy
Note: When replacing modules, the stacking machine should be used carefully in
case that the modules may fall down. All workmen are suggested to wear high-safety
and high strength protective shoes to protect their feet.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 9 of 58
Your Smart Energy Product Description
3. Product Description
The AlphaESS Storion-T50/T100 energy storage system is an off-grid system. The excessive
energy generated by the PV will be stored in the batteries. The stored energy can be used when
the PV is not generating enough energy. When connected with a generator, if there is neither
enough PV supply nor enough stored energy, the loads will be automatically powered by
generator through STS (Smart Transform Switch).The overall system connection diagram is as
follows:
6
1
5
2
3 4
Item Components
1 Storion-T50/100-INV
2 M48112-S
3 Junction Box
4 HV900112 Box
5 Battery Rack
6 TOP BMU Box
Product Characteristics
LiFePO4 batteries produced by AlphaESS have longer lifespan and higher reliability, which is
able to satisfy the application of energy storage systems.
The system is highly modular designed, and it is easier to assemble, transport and maintain.
The system has a three-level BMS and is allowed for system expansion.
The system adopts all time balancing technology so that the consistency of batteries and
modules can be well ensured.
The system has current balance technology between strings in case of circulating current or
unbalanced power.
The system has relatively developed thermal management technology so that the consistency
of the system environment can be ensured.
The system has both remote monitor function and local control function.
The system realizes flexible scheduling of electric power system through communication
among BMS, PCS and monitoring system.
The system realizes emergency fire protection by using the automatic alarming and fire
extinguishing system
Parameters of Components
PCS
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 11 of 58
Your Smart Energy Product Description
module can charge batteries by using the electricity generated by PV panels. The DC/AC
module is bidirectional so that the battery can also be charged by the grid through the inverter.
105%~115% 10min;
10 Overload Capability 115%~125% 1min;
125%~150% 200ms
DC Data (Battery Side)
11 DC Voltage Range 250 – 520 V
12 One-Way Maximum Input
150 A 300 A
Current
13 Max. DC Power 50 kW 100 kW
PV Side Data
14 PV Voltage Range 520 – 900 V (MPPT: 520~800 V)
15 PV DC Max. Current (in case
192 A 384 A
of completely consumption)
17 Max. PV Power 100 kW 200 kW
General Data
18 Max Efficiency 95.5%
19 Dimensions (W x H x L) 800 x 2160 x 800 mm
20 Weight 520 kg 750 kg
21 Altitude 3000 m
22 Ingress Protection IP20
23 Noise 70 dB
If you want to restart the converter, please proceed in the following order:
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 13 of 58
Your Smart Energy Product Description
a) Conduct counter clockwise rotation on the emergency stop switch and then loosen the
locking status.
b) Push the AC breaker into “OFF” position, pull up the emergence button and then turn
the AC breaker “ON”.
c) Launch the machine and operate it as required
Battery System
DC side
3 Continuous discharge current 1C (continuous)
4 Direct voltage 250 ~ 520 V
5 Communication interface RS485, CAN2.0
3.3.2.1 M48112-S
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 14 of 58
Product Description Your Smart Energy
The dip switch of M48112-s defines the serial number. Please see the detailed description in
the following table.
1 6 11
2 7 12
3 8 13
4 9 14
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 15 of 58
Your Smart Energy Product Description
5 10 15
Transportation/storage
11 -20 ~ 45 ℃
temperature range
Charging work temperature
12 0~50 ℃
range
Discharging work temperature
13 -10~50 ℃
range
14 Communication mode CAN
15 Weight 70 ± 2.0 kg
494.6 x 615.3 x 162.6
16 Size (W x D x H)
(±5) mm
17 Humidity 15%~85%
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 16 of 58
Product Description Your Smart Energy
3.3.2.2 HV900112
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 17 of 58
Your Smart Energy Product Description
6 Weight 20 kg
7 Power consumption <10 W
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 18 of 58
Product Description Your Smart Energy
NOTE: TOP BMU box (with EMS) can communicate with outside device, such as PCS,
Air conditioner, PV junction box, etc.
If the communication type is CAN, you can connect from the COM port (from Port 1 to
10) in TOP BMU box to the device by using regular net cables.
If the communication type is RS485, please connect to the RS485A and RS485B port in
TOP BMU box. Besides, the two corresponding COM ports in TOP BMU box should be
connected with each other.
1 3 1 2 4 2
5 5
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 19 of 58
Your Smart Energy Product Description
2 2 x DC IN INV+ 5 Handle
3 7 x DC OUT-
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 20 of 58
Installation Your Smart Energy
4. Installation
Installation Precautions
The following sites are not allowed for installation:
- Sites which are salty and where humid air can penetrate.
- Flooded areas.
- Earthquake areas –additional security measures are required here.
- Sites that are higher than 3000 meters above the sea level.
- Sites that are in an explosive or potentially explosive atmosphere.
- Sites with extreme changes of ambient temperature.
- Sites with highly flammable materials or gases.
Parts List
Table 13 Parts List
M48112-S
Hv900112
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 21 of 58
Your Smart Energy Installation
1 X Communication Cable 4 x M6
1 X Terminal Resistance 4 x M6*16
2500 mm, TOP BMU-HV BOX Gouding Serrated Washer
Rack
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 22 of 58
Installation Your Smart Energy
Installation
PCS Installation
4.3.1.1 Removal
When removing the T50/T100-INV, a forklift can be used to remove the whole case. Users can
lift the device bottom with a forklift or remove the inverter cabinet through the lifting hole on its
top with a crane. It can be transported alone.
Don’t insert the module into the cabinet and move them together! Before the cabinet is
moved, pull out the module and move the cabinet alone.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 23 of 58
Your Smart Energy Installation
A≥1,000mm, make sure that the front door of the cabinet can be fully opened and there is
sufficient space for cold air to enter. Users can conveniently insert and extract the module and
operate the breaker.
B≥1,000mm, make sure that the rear door of the cabinet can be fully opened. Ventilation and
heat dissipation should be ensured. Users can also have sufficient space for product
maintenance.
When the cabinet needs to be fixed on the steel channel, Φ14 holes can be made in the steel
channel. Fix the cabinet to the steel channel with screws, as shown in Figure 4.4.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 24 of 58
Installation Your Smart Energy
Figure 4.4 Fix the cabinet to the steel Figure 4.5 Fix the cabinet to the
channel concrete floor
When the cabinet is fixed to the concrete floor, make holes on the floor and fix the cabinet to
the concrete floor with expansion screws, as shown in Figure 4.5.
As for cabinet grounding, the cabinet bottom is installed with grounded cooper bars. During
wiring, refer to the following table for cable diameter. The grounding resistance should be less
than 4Ω.
The tray is for the battery, the holder 1 is for HV900112 and the holder 2 is for junction box or
TOP BMU box as the below figures show. The locations of them can be exchanged.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 25 of 58
Your Smart Energy Installation
L Holder
Note: the location of L holder on holder 2 is flexible. The front location is for the
junction box and the rear location is for TOP BMU box.
b. If there are only one or two clusters, the junction box is not required, and the same is true of
cluster racks. Just place the rack(s) in the suitable place(s) by using a crane or forklift.
If there are more than three racks, place the first rack beside the PCS, which is different from
others as Figure 4.6 shows.
d. Fix the rack foundation(s) with hex screws and nuts if the fixing is required, which you can
find in the rack parts list. The customer shall prepaid for some materials, such as a cable to
connect your own grounding cooper bar to the grounding screws of the rack bottom by using
the grounding nut M6 from the rack parts list.
Grounding screw
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 26 of 58
Installation Your Smart Energy
b. Put all the HV900112 boxes in the right places as Figure 4.9 shows.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 27 of 58
Your Smart Energy Installation
If the junction box is not required, just put the HV900112(s) in the bottom of the rack(s).
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 28 of 58
Installation Your Smart Energy
Step 1: Open all the battery packages. Step 2: Check the Battery No. and cluster No. on the
battery cover.
BAT 1-01
BAT 1-02
BAT 1-03
BAT 1-04
BAT 1-05
BAT 1-06
BAT 1-07
BAT 1-08
BAT 1-09
Step 3: Put the same cluster of batteries on the same rack with the serial number of 01 to 09
from top to bottom as the above figure shows. The dip switch defines the serial number, see
Table 6.
NOTE: All the cluster battery group No. shall be the same.
In one cluster the dip switch of each battery should be different from ohers.
When you are installing the battery, pleasecto avoid scratches because of the heavy
battery.
Step 4: After completing one rack, please check whether the installed batteries have the same
cluster No. and the same battery group No.
Step 5: If there are more than one rack, please repeat step 3 and 4 to install the other battery
racks as Figure 4.11 shows.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 29 of 58
Your Smart Energy Installation
Wiring
c. Connect the bottom battery of each cluster to V900112 (LMU Port) by using the
communication cables from HV900112 parts list.
d Connect HV900112 (COM Port) in the nearest cluster from TOP BMU and TOP BMU box
(COM Port, Port 1 or 2) by using the communication cable from TOP BMU part list. Then
connect HV900112 (COM port) one by one by using cable from HV900112 parts list, please
see Figure 4.14.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 30 of 58
Installation Your Smart Energy
e To connect the PCS and EMS please open the PCS cabinet front door and remove the shield
of the right side. You can see the communication interface at the right bottom. Then please
connect TOP BMU box (Port 27 -485A and Port 28 - 485B) to the PCS (Port 9 - 485A and Port
10 - 485B) by using the RS485 cable from the rack parts list as Figure 4.15 shows.
Shield
TOP BMU
PCS
f. Connect the COM port 9 and COM port 20 of TOP BMU box with a regular net cable.
g. The last COM port of HV900112, which has no cable to connect, should be inserted with the
terminal residence from HV900112 parts list. You can see the detailed information Figure 4.16.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 32 of 58
Installation Your Smart Energy
If you use the junction box, place the relevant power cables to junction box at the first, as
shown in Figure 4.18. Then put the junction box in to the rack as shown in Figure 4.19.
The cover of the junction box should be taken off for wiring. The cables should be
connected vertically with the copper bars in the junction box.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 33 of 58
Your Smart Energy Installation
Inverter Side-Wiring
The connection positions are in the bottom down position of the inverter cabinet. The cables
shall be passed through the hole on the base of cabinet into the cable trench. Open the front
door and remove the inner door, you can see the wiring copper bar. In view of the requirements
of connecting cables, single or multiple cables with suitable diameter shall be selected.
For T50 the 35 mm²cable with copper core is suggested for each phase.
For T100 the 50 mm²cable with copper core is suggested for each phase.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 34 of 58
Installation Your Smart Energy
Please connect the AC side – the loads and the diesel generator as Figure 4.21 shows.
Notes: For the diesel generator selection, the rated power of the generator should
be more than the inverter rated power.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 35 of 58
Your Smart Energy Installation
Notes: The auxiliary power cable bond must be placed above the AC power cable
bond. After this please tighten the screw.
1. Connect DO_2 to the dry contact of the diesel generator, port 2 and 3 (normally closed contact),
1 and 2 (normally open), you can connect the diesel dry contact to control the 1 and 2.
2. Connect DI_2 to the fire fighting dry contact, port 14 and 15 are respectively corresponding to
the composite fire alarm of connecting fire fighting. (if required)
3. Please connect the diesel control dry contact as the below picture shows:
Notes: normally open/closed contact which connects the Genset according to the
genset controller.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 36 of 58
Operation Your Smart Energy
5. Operation
Switch on
If no sign of damage is inspected visually outside the inverter module and all the battery switch,
PV switch and load switch, diesel engine switch are in the "OFF" position, you will
a. check whether the DC input wiring of the energy storage system and the AC output wiring
are normal and whether the earthing is good;
Power-on Procedures
The system shall be turned on in the correct sequence to avoid any damage.
A. Turn on the moulded case circuit breakers of HV900112 in each cluster respectively.
B. Turn on the AC air switch of HV900112 in each cluster respectively. If there is an AC main
switch, turn it on.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 37 of 58
Your Smart Energy Operation
C. After the power is on, the LED on the batteries and HV900112 starts flashing.
D. Two minutes later, turn on the battery and PV switches of the inverter by pushing up the
switch handles. The green indicator of the inverter starts flashing. After 10 seconds, the red
indicator is on.
E. Turn on the load switch by pushing up switch handles. If a diesel generator is connected,
turn on the generator switch.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 38 of 58
Operation Your Smart Energy
After the system is powered on, it will be switched on automatically if there are no errors and
warnings.
EMS Setting
Step 1: Enter into EMS menu and get into Step 2: Enter the password (the initial
Setting. password for installers is 1111).
Step 3: Get into the Function menu. Choose Step 4: Get into the PCS menu. Choose
PCS. AC_Tied.
Step 5: If you connect a diesel generator in Step 5: Make sure in the PCS menu the Minv
the off-grid system, please get into the is the system model, such as T50.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 39 of 58
Your Smart Energy Operation
When the diesel generator is enabled, it will supply the load first.
1. SOC mode: When the SOC drops below the lower limit of the configured SOC range, the
diesel generator will start; when it raises beyond the upper limit, the diesel generator will then
be turned off.
2. TOU mode: the generator will run during the configured GCTime (from GCTimeStart to
GCTimeEnd).
If the mode 8 - battery charging power mode is selected, the diesel generator will charge the
batteries with configured power.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 40 of 58
Operation Your Smart Energy
If the mode 9 – diesel generator output rated power mode is selected, the diesel generator will
charge batteries with the rest of the power under the condition of satisfying load.
You can also set the control mode on the website, see 5.4.3
For diesel generator control setting, please operate according to following steps:
Step 1: Please get into setting menu, then the Step 2: Please get into GeneratorEN and
function menu, after that get into generator select Enable as YES.
menu.
Step 3: Please get into GeneratorMode Step 4.1: If you choose SOC control mode,
menu. please select the mode as SOC Mode.
Step 4.1.1: Get into GCSOCStart menu. Step 4.1.2: Set the lower limit of the
configured SOC range.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 41 of 58
Your Smart Energy Operation
Step 4.1.3: Get into GCSOCEnd menu. Step 4.1.4: Set the upper limit of the
configured SOC range
Step 4.2: If you choose time control mode, Step 4.2.1: Get into GCTimeStart menu.
please select the mode as TOU Mode.
Step 4.2.2: Set the diesel generator start time Step 4.2.3: Get into GCTimeEnd menu.
Step 4.2.4: Set the diesel generator end time Step 5: Get into the GCOutputMode menu
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 42 of 58
Operation Your Smart Energy
Step 5.1: If you choose fixed charging power, Step 5.1.1: Get into the GCChargePower
please select the output mode as GCCharge. menu.
Step 5.1.2: Set the fixed charging power. Step 5.2: If you choose rated power mode,
please select the output mode as GCRated.
Step 5.2.1: Get into the GCRatedPower Step 5.2.2: Set the generator rated power.
menu.
Switch off
Step 1: Enter into EMS menu and get into Step 2: Enter the password (the initial
Setting. password for installers is 1111).
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 43 of 58
Your Smart Energy Operation
Step 3: Enter into function menu and get into Step 4: Choose ModeOff as yes
INVcmd
Power-off Procedures
The system shall be powered off according to following steps:
E. turn off the moulded case circuit breaker of HV900112 in each cluster.
Online Monitoring
Register
You have to create a new account on our webserver for the normal monitoring.
Enter the username and password, then click “Login” to jump to the home page. There will be
a prompt after a failed login.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 44 of 58
Operation Your Smart Energy
Users who haven't yet registered need to click “Register” to visit the registration page: (as
shown below)
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 45 of 58
Your Smart Energy Operation
Registering License
Input S/N, Check Code, License No., Date, Name, and Contact No. to complete the
registering process.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 46 of 58
Operation Your Smart Energy
Choose SOC control to set SOC range. If the SOC drops below the lower limit of the
configured SOC range, the diesel generator will start; when it raises beyond the upper limit,
the diesel generator will then be turned off.
If you set the battery charge power, it will charge the batteries with the configured battery
charge power.
If you set the Generator output power, it will charge the batteries with the rest of the
power under the condition of satisfying load. The rest of the power is P=Poutput – Pload.
Choose time control, the diesel generator will start during the configured working time.
Emergency Stop
When the energy storage system is abnormal, you can press the emergency stop button "EPO"
on the cabinet door, follow the step A to D in 0 to power it off.
In order to prevent personal casualty, if you want to repair or open the machine after power-off,
please measure the voltage at the input port with the multimeter first. Before any relevant
operation, please confirm that there is no grid electric supply!
The upper cover plate cannot be opened until the DC-link capacitance inside the module
discharges completely about 15 minutes (see warning label on the surface of module for details).
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 47 of 58
Your Smart Energy Routine Maintenance
6. Routine Maintenance
Maintenance Plan
check if wire connection loose
check if cables aged/damaged
check if cable insulating ribbon drop
check if cable terminal screw loose, any overheat sign
check if ground connection is well
Routine Inspection
Minimum PPE
Training/qualificat (Personal
Item Details Frequency Notes
ion requirements protection
equipment)
Check the
Once Work cloth;
Foundation foundation for tilt No tilt or sink
6 months Protective shoes
or sink
Check the
earthing bar of Once Work cloth;
Footing No rusting
the container for 6 months Protective shoes
rusting.
Check the
Lighting lighting supply;
Once All the lights should Work cloth;
power all the lights
6 months work normally Protective shoes
supply should work
normally
Check the
All emergency
emergency
lights should work
Emergency lighting Once Work cloth;
normally after
lighting equipments; all 6 months Protective shoes
power supply is
the lights should
down
work normally
Check the
Bracket Once 6 No rusting or Work cloth;
brackets for rust
surface month damage Protective shoes
or damage
Check the fixing All bolts are tight Work cloth;
of brackets Protective shoes;
Bracket between Once 6 Wrenches
fixing brackets and months
ground of the
container
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 48 of 58
Routine Maintenance Your Smart Energy
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 49 of 58
Your Smart Energy Routine Maintenance
Routine Maintenance
Maintenance Training/qualification
Item Equipment
cycle requirements
Work clothes;
Protective
Painting on
shoes; 6 months Corresponding color number
brackets
Anticorrosive
paint
Work clothes;
Fixing on Protective Fixing between brackets and
6 months
brackets shoes; container ground
Wrench
Work clothes;
Grounding Protective
3 months Use multimeter to test grounding.
of brackets shoes;
Screwdriver
Battery Work clothes;
Battery
system Protective The brackets and modules should
system 6 months
shoes; be clean
cleaning
Cloth
Work clothes;
Protective
Painting on
shoes; 6 months Corresponding color number
modules
Insulating
paint
Work clothes;
Fixing on Protective Fixing between modules and
3 months
modules shoes; brackets
Wrench
Connecting Work clothes;
3 months Serial copper bars
cooper bar Protective
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 50 of 58
Routine Maintenance Your Smart Energy
fixing shoes;
Wrench
Work clothes;
Insulation Protective
3 months Protecting cover on module poles
protection shoes;
Work clothes;
Module
Protective
tamper 3 months Tamper proof labels
shoes;
proof labels
Work clothes;
Module Protective
3 months Use multimeter to test grounding.
grounding shoes;
Wrench
Battery Work clothes;
Whole discharge-charge-
capacity Protective 6 months
discharge cycle
calibration shoes;
Work clothes;
Battery data Analyze BMS data recorded (by
Protective 6 months
analyze Alpha staff)
shoes;
Junction Work clothes;
Junction box cable Protective
6 months All bolts are tight
box terminal shoes;
fixing Wrench
Check whether the converter is
damaged or deformed or not.
Listen whether abnormal sound is
available during the operation of
converter.
Check all varieties during the
operation of converter.
Operating Check whether the major parts are
Work clothes;
status and Ok or not.
Protective
PCS environmen 6 months Check the heating of converter`s
shoes;
t of the case and use thermal imager to
system monitor the heating situation of the
system.
View whether the air inlet/outlet is
normal or not.
Check the humidity and dust
around the converter and ensure
the filters in air inlet are OK.
Attention! Check the ventilation in
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 51 of 58
Your Smart Energy Routine Maintenance
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 52 of 58
Routine Maintenance Your Smart Energy
Notes
After all of the equipments are out of operation, the following notes should be paid attention to
while maintaining:
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 53 of 58
Your Smart Energy Routine Maintenance
start.
For single cell, it is better to be sank into water to block burning.
The batteries need to be charged to 30%~50%SOC rate when the whole system is static
(that is, the batteries has not been charged for two weeks or longer) for a long time, in case of
over discharge.
Please contact us in time if there are any conditions that could not be explained in the
manual.
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 54 of 58
Troubleshooting Your Smart Energy
7. Troubleshooting
Error Type
Alarm Displayed in EMS Processing method
Cell temperature different fault Cell-Temp-Diff Contact with Alpha service
Balancer fault Balancer Err Contact with Alpha service
Module charge over current
Chrg-Ov-Curr Contact with Alpha service
fault
Module discharge over current
Disch-Ov-Curr Contact with Alpha service
fault
Pole over temperature fault Pole-Ov-Temp Contact with Alpha service
Cell over volt fault Cell-Ov-Volt Contact with Alpha service
cell volt different fault Cell-Volt-Diff Contact with Alpha service
cell discharge under
Disch-Low-Temp Contact with Alpha service
temperature fault
Cell under volt fault Cell-Low-Volt Contact with Alpha service
Cut off BMS at the first, then operate
Insulation resistan fault IR_Fail in power sequence when power the
system
Check communication connection
between batteries (LMU and LMU),
LMU Communication fault Commu_fail_LMU
battery and HV900112 (LMU and
BMU)
Cell over temperature fault Cell-Ov-Temp Contact with Alpha service
Check communication cable between
HV90012s (BMU and BMU), also
BMU Communication fault Commu_fail_BMU
HV900112 and TOP BMU Box (BMU
and TOP BMU)
Cell charge under temperature
Chrg-Low-Temp Contact with Alpha service
fault
Wire beam fault Wire-Harness-Err Contact with Alpha service
Relay fault relay Err Cut off BMS
Temperature sensor fault Temp-Sen-Err Contact with Alpha service
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 55 of 58
Your Smart Energy Troubleshooting
Please record every detail related to the fault, so we can analyze and solve the fault better. Any
operation of equipments is strictly forbidden, please contact us as soon as possible.
When the batteries are on fire, do not try to put the fire out manually. That is dangerous because
the special chemical property of lithium-ion batteries (though LiFePO4 is safer, there is
possibility of danger). Water or other liquid is not recommended. Novec 1230, FM-200, or
dioxide extinguisher are recommended. ABC extinguishers are not effective when the battery
pack is on fire.
As battery cell contains little Oxygen inside and all cells have got explosion-proof valve,
explosion hardly happens.
EMS Troubleshooting
Alarm Displayed in EMS Processing method
Check communication connection
Inverter Disconnect INV Lost
between EMS and inverter
Check communication connection
Grid Meter Disconnect Meter Lost
between EMS and grid meter
Check communication connection
Battery Disconnect BMS Lost
between EMS and battery system
Check communication connection
PV Meter Disconnect PV-Meter Lost
between EMS and grid meter
SD not inserted or SD writing
SD lost Replug SD card
error
Network card error NetCard Err Contact with Alpha
______________________________________________________________________
Alpha ESS Co., Ltd.
Page 56 of 58