Air System Sizing Summary for TORRE B-OF_ADMINIS

Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019


Prepared by: anonimo 04:55p.m.

Air System Information


Air System Name TORRE B-OF_ADMINIS Number of zones 1
Equipment Class UNDEF Floor Area 14247.0 ft²
Air System Type SZCAV Location Lima, Peru

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 88.2 Tons Load occurs at Jan 1500
Total coil load 1058.6 MBH OA DB / WB 85.7 / 74.9 °F
Sensible coil load 841.0 MBH Entering DB / WB 77.1 / 66.3 °F
Coil CFM at Jan 1500 44695 CFM Leaving DB / WB 59.7 / 58.7 °F
Max block CFM 44695 CFM Coil ADP 57.8 °F
Sum of peak zone CFM 44695 CFM Bypass Factor 0.100
Sensible heat ratio 0.794 Resulting RH 56 %
ft²/Ton 161.5 Design supply temp. 58.0 °F
BTU/(hr-ft²) 74.3 Zone T-stat Check 0 of 1 OK
Water flow @ 10.0 °F rise 211.83 gpm Max zone temperature deviation 0.1 °F

Central Heating Coil Sizing Data


Max coil load 111.7 MBH Load occurs at Des Htg
Coil CFM at Des Htg 44695 CFM BTU/(hr-ft²) 7.8
Max coil CFM 44695 CFM Ent. DB / Lvg DB 68.9 / 71.2 °F
Water flow @ 20.0 °F drop 11.17 gpm

Supply Fan Sizing Data


Actual max CFM 44695 CFM Fan motor BHP 0.00 BHP
Standard CFM 44627 CFM Fan motor kW 0.00 kW
Actual max CFM/ft² 3.14 CFM/ft² Fan static 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM 2898 CFM CFM/person 7.85 CFM/person
CFM/ft² 0.20 CFM/ft²

Hourly Analysis Program v4.91 Page 1 of 17


Zone Sizing Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

Air System Information


Air System Name TORRE B-OF_ADMINIS Number of zones 1
Equipment Class UNDEF Floor Area 14247.0 ft²
Air System Type SZCAV Location Lima, Peru

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20.0 °F (MBH) @ 20.0 °F (CFM)
Zone 1 44695 44695 3.14 0.0 0.00 0.0 0.00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 814.6 Jan 1500 80.0 14247.0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
P2_POOL6_POOL4_JEF4-TB 4 26.6 Feb 1500 1449 2.0 462.0 3.14
P2_POOL5_POOL3_JEF3-TB 4 29.5 Jan 1500 1607 3.4 462.0 3.48
P2_POOL2_JEF2_TB 5 18.9 Feb 1500 1032 1.6 355.0 2.91
P2_DATA CENTER_TB 4 13.2 Dec 1500 718 1.7 75.0 9.58
P2_POOL1-PLAN_JEF1_TB 4 19.2 Dec 1500 1045 1.7 355.0 2.94
P2_JEF1_POOL1_TB 4 17.8 Feb 1400 972 1.6 355.0 2.74
P2_JEF3_POOL3_TB 4 17.8 Feb 1400 972 1.6 355.0 2.74
P2_POOL2-JEF2-POOL4_TB 4 31.4 Dec 1500 1716 3.2 581.0 2.95
P2_JEF2_POOL2_GALE DI 4 25.8 Mar 1500 1406 2.8 473.0 2.97

Hourly Analysis Program v4.91 Page 2 of 17


Ventilation Sizing Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/20
Prepared by: anonimo 04:55p

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 2898 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Zone 1
P2_POOL6_POOL4_JEF4-TB 4 462.0 12.0 1448.8 5.00 0.06 0.0 0.0 87.7
P2_POOL5_POOL3_JEF3-TB 4 462.0 11.0 1606.5 5.00 0.06 0.0 0.0 82.7
P2_POOL2_JEF2_TB 5 355.0 9.0 1032.0 5.00 0.06 0.0 0.0 66.3
P2_DATA CENTER_TB 4 75.0 9.0 718.3 10.00 0.12 0.0 0.0 99.0
P2_POOL1-PLAN_JEF1_TB 4 355.0 9.0 1045.4 5.00 0.06 0.0 0.0 66.3
P2_JEF1_POOL1_TB 4 355.0 9.0 971.6 5.00 0.06 0.0 0.0 66.3
P2_JEF3_POOL3_TB 4 355.0 9.0 971.6 5.00 0.06 0.0 0.0 66.3
P2_POOL2-JEF2-POOL4_TB 4 581.0 13.0 1715.6 5.00 0.06 0.0 0.0 99.9
P2_JEF2_POOL2_GALE DI 4 473.0 9.0 1406.0 5.00 0.06 0.0 0.0 73.4
Totals (incl. Space Multipliers) 44695.2 2897.8

Hourly Analysis Program v4.91 Page 3 o


Air System Design Load Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.7 °F / 74.9 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 480 ft² 14236 - 480 ft² - -
Wall Transmission 11618 ft² 40067 - 11618 ft² 34045 -
Roof Transmission 15224 ft² 148041 - 15224 ft² 23861 -
Window Transmission 480 ft² 2418 - 480 ft² 3669 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 21498 ft² 0 - 21498 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 22950 W 64444 - 0 0 -
Task Lighting 18051 W 55535 - 0 0 -
Electric Equipment 56988 W 194442 - 0 0 -
People 369 70417 75645 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 37000 37000 - 0 0
Safety Factor 30% / 30% 187980 33794 30% 18473 0
>> Total Zone Loads - 814581 146439 - 80048 0
Zone Conditioning - 812510 146439 - 71889 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 44695 CFM 0 - 44695 CFM 0 -
Ventilation Load 2898 CFM 28442 71294 2898 CFM 39793 0
Supply Fan Load 44695 CFM 0 - 44695 CFM 0 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 840952 217733 - 111683 0
Central Cooling Coil - 840952 217640 - 0 0
Central Heating Coil - 0 - - 111682 -
>> Total Conditioning - 840952 217640 - 111682 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.91 Page 4 of 17


Zone Design Load Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.7 °F / 74.9 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 480 ft² 14236 - 480 ft² - -
Wall Transmission 11618 ft² 40067 - 11618 ft² 34045 -
Roof Transmission 15224 ft² 148041 - 15224 ft² 23861 -
Window Transmission 480 ft² 2418 - 480 ft² 3669 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 21498 ft² 0 - 21498 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 22950 W 64444 - 0 0 -
Task Lighting 18051 W 55535 - 0 0 -
Electric Equipment 56988 W 194442 - 0 0 -
People 369 70417 75645 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 37000 37000 - 0 0
Safety Factor 30% / 30% 187980 33794 30% 18473 0
>> Total Zone Loads - 814581 146439 - 80048 0

Hourly Analysis Program v4.91 Page 5 of 17


Space Design Load Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' P2_POOL6_POOL4_JEF4-TB '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.7 °F / 74.9 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 290 ft² 732 - 290 ft² 850 -
Roof Transmission 462 ft² 4507 - 462 ft² 724 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 700 ft² 0 - 700 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 1183 W 3321 - 0 0 -
Task Lighting 739 W 2274 - 0 0 -
Electric Equipment 1848 W 6305 - 0 0 -
People 12 2290 2460 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 1000 - 0 0
Safety Factor 30% / 30% 6129 1038 30% 472 0
>> Total Zone Loads - 26559 4498 - 2046 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' P2_POOL6_POOL4_JEF4-TB '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 290 0.225 - 732 - 850
N EXPOSURE
ROOF 462 0.121 - 4507 - 724

Hourly Analysis Program v4.91 Page 6 of 17


Space Design Load Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' P2_POOL5_POOL3_JEF3-TB '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.7 °F / 74.9 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 45 ft² 904 - 45 ft² - -
Wall Transmission 535 ft² 2031 - 535 ft² 1568 -
Roof Transmission 462 ft² 4493 - 462 ft² 724 -
Window Transmission 45 ft² 227 - 45 ft² 344 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 700 ft² 0 - 700 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 1183 W 3321 - 0 0 -
Task Lighting 739 W 2274 - 0 0 -
Electric Equipment 1848 W 6305 - 0 0 -
People 11 2099 2255 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 1000 - 0 0
Safety Factor 30% / 30% 6796 977 30% 791 0
>> Total Zone Loads - 29451 4232 - 3427 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' P2_POOL5_POOL3_JEF3-TB '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 290 0.225 - 1417 - 850
N EXPOSURE
WALL 245 0.225 - 614 - 718
WINDOW 1 45 0.588 0.811 227 904 344
N EXPOSURE
ROOF 462 0.121 - 4493 - 724

Hourly Analysis Program v4.91 Page 7 of 17


Space Design Load Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' P2_POOL2_JEF2_TB '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.7 °F / 74.9 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 226 ft² 571 - 226 ft² 662 -
Roof Transmission 344 ft² 3356 - 344 ft² 539 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 550 ft² 0 - 550 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 547 W 1535 - 0 0 -
Task Lighting 497 W 1529 - 0 0 -
Electric Equipment 1420 W 4845 - 0 0 -
People 9 1717 1845 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 1000 - 0 0
Safety Factor 30% / 30% 4366 854 30% 360 0
>> Total Zone Loads - 18919 3699 - 1562 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' P2_POOL2_JEF2_TB '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 226 0.225 - 571 - 662
N EXPOSURE
ROOF 344 0.121 - 3356 - 539

Hourly Analysis Program v4.91 Page 8 of 17


Space Design Load Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' P2_DATA CENTER_TB '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.7 °F / 74.9 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1333 - 30 ft² - -
Wall Transmission 196 ft² 1080 - 196 ft² 574 -
Roof Transmission 344 ft² 3194 - 344 ft² 539 -
Window Transmission 30 ft² 133 - 30 ft² 229 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 550 ft² 0 - 550 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 116 W 324 - 0 0 -
Task Lighting 105 W 323 - 0 0 -
Electric Equipment 300 W 1024 - 0 0 -
People 9 1717 1845 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 1000 - 0 0
Safety Factor 30% / 30% 3039 854 30% 403 0
>> Total Zone Loads - 13168 3699 - 1746 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' P2_DATA CENTER_TB '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 196 0.225 - 1080 - 574
WINDOW 1 30 0.588 0.811 133 1333 229
N EXPOSURE
ROOF 344 0.121 - 3194 - 539

Hourly Analysis Program v4.91 Page 9 of 17


Space Design Load Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' P2_POOL1-PLAN_JEF1_TB '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.7 °F / 74.9 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 15 ft² 666 - 15 ft² - -
Wall Transmission 211 ft² 1163 - 211 ft² 618 -
Roof Transmission 344 ft² 3194 - 344 ft² 539 -
Window Transmission 15 ft² 67 - 15 ft² 115 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 550 ft² 0 - 550 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 355 W 997 - 0 0 -
Task Lighting 355 W 1092 - 0 0 -
Electric Equipment 1420 W 4845 - 0 0 -
People 9 1717 1845 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 1000 - 0 0
Safety Factor 30% / 30% 4422 854 30% 382 0
>> Total Zone Loads - 19164 3699 - 1654 0

TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' P2_POOL1-PLAN_JEF1_TB '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 211 0.225 - 1163 - 618
WINDOW 1 15 0.588 0.811 67 666 115
N EXPOSURE
ROOF 344 0.121 - 3194 - 539

Hourly Analysis Program v4.91 Page 10 of 17


Space Design Load Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' P2_JEF1_POOL1_TB '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.7 °F / 74.7 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 226 ft² 479 - 226 ft² 662 -
Roof Transmission 355 ft² 3629 - 355 ft² 556 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 550 ft² 0 - 550 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 355 W 982 - 0 0 -
Task Lighting 355 W 1084 - 0 0 -
Electric Equipment 1420 W 4845 - 0 0 -
People 9 1683 1845 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 1000 - 0 0
Safety Factor 30% / 30% 4110 854 30% 366 0
>> Total Zone Loads - 17812 3699 - 1584 0

TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' P2_JEF1_POOL1_TB '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 226 0.225 - 479 - 662
N EXPOSURE
ROOF 355 0.121 - 3629 - 556

Hourly Analysis Program v4.91 Page 11 of 17


Space Design Load Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' P2_JEF3_POOL3_TB '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.7 °F / 74.7 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 226 ft² 479 - 226 ft² 662 -
Roof Transmission 355 ft² 3629 - 355 ft² 556 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 387 ft² 0 - 387 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 355 W 982 - 0 0 -
Task Lighting 355 W 1084 - 0 0 -
Electric Equipment 1420 W 4845 - 0 0 -
People 9 1683 1845 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 1000 - 0 0
Safety Factor 30% / 30% 4110 854 30% 366 0
>> Total Zone Loads - 17812 3699 - 1584 0

TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' P2_JEF3_POOL3_TB '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 226 0.225 - 479 - 662
N EXPOSURE
ROOF 355 0.121 - 3629 - 556

Hourly Analysis Program v4.91 Page 12 of 17


Space Design Load Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' P2_POOL2-JEF2-POOL4_TB '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.7 °F / 74.9 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1333 - 30 ft² - -
Wall Transmission 454 ft² 2503 - 454 ft² 1330 -
Roof Transmission 581 ft² 5394 - 581 ft² 911 -
Window Transmission 30 ft² 133 - 30 ft² 229 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 550 ft² 0 - 550 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 581 W 1631 - 0 0 -
Task Lighting 581 W 1787 - 0 0 -
Electric Equipment 2324 W 7929 - 0 0 -
People 13 2481 2665 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 1000 - 0 0
Safety Factor 30% / 30% 7258 1100 30% 741 0
>> Total Zone Loads - 31450 4765 - 3211 0

TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' P2_POOL2-JEF2-POOL4_TB '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 454 0.225 - 2503 - 1330
WINDOW 1 30 0.588 0.811 133 1333 229
N EXPOSURE
ROOF 581 0.121 - 5394 - 911

Hourly Analysis Program v4.91 Page 13 of 17


Space Design Load Summary for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' P2_JEF2_POOL2_GALE DI '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Mar 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 83.7 °F / 73.9 °F HEATING OA DB / WB 57.0 °F / 47.8 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 484 ft² 1763 - 484 ft² 1418 -
Roof Transmission 473 ft² 4251 - 473 ft² 741 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 700 ft² 0 - 700 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 927 W 2603 - 0 0 -
Task Lighting 662 W 2037 - 0 0 -
Electric Equipment 1892 W 6455 - 0 0 -
People 9 1717 1845 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1000 1000 - 0 0
Safety Factor 30% / 30% 5948 854 30% 648 0
>> Total Zone Loads - 25776 3699 - 2808 0

TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' P2_JEF2_POOL2_GALE DI '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 484 0.225 - 1763 - 1418
N EXPOSURE
ROOF 473 0.121 - 4251 - 741

Hourly Analysis Program v4.91 Page 14 of 17


System Psychrometrics for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

January DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 85.7 0.01618 2898 400 28442 71294
Vent - Return Mixing Outlet 77.1 0.01133 44695 1559 - -
Central Cooling Coil Outlet 59.7 0.01030 44695 1559 840952 217640
Central Heating Coil Outlet 59.7 0.01030 44695 1559 0 -
Supply Fan Outlet 59.7 0.01030 44695 1559 0 -
Cold Supply Duct Outlet 59.7 0.01030 44695 1559 - -
Zone Air - 76.6 0.01099 44695 1640 812510 146439
Return Plenum Outlet 76.6 0.01099 44695 1640 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4739.4 BTU/(hr-CFM)
Site Altitude = 42.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 814581 Cooling 812510 76.6 44695 1640 0 0

Hourly Analysis Program v4.91 Page 15 of 17


System Psychrometrics for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/2019
Prepared by: anonimo 04:55p.m.

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 57.0 0.00494 2898 400 -39793 0
Vent - Return Mixing Outlet 68.9 0.00494 44695 537 - -
Central Cooling Coil Outlet 68.9 0.00494 44695 537 0 0
Central Heating Coil Outlet 71.2 0.00494 44695 537 111682 -
Supply Fan Outlet 71.2 0.00494 44695 537 0 -
Cold Supply Duct Outlet 71.2 0.00494 44695 537 - -
Zone Air - 69.7 0.00494 44695 546 -71889 0
Return Plenum Outlet 69.7 0.00494 44695 546 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.078 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4739.4 BTU/(hr-CFM)
Site Altitude = 42.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -80048 Heating -71889 69.7 44695 546 0 0

Hourly Analysis Program v4.91 Page 16 of 17


Psychrometric Analysis for TORRE B-OF_ADMINIS
Project Name: SIST-AA- MARINA DE GUERRA 11/25/20
Prepared by: anonimo 04:55p

Location: Lima, Peru


Altitude: 42.0 ft.
Data for: January DESIGN COOLING DAY, 1500
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0.018
5. Room Air
1
0.016

Specific Humidity ( lb/lb )


0.014

2 0.012
34 5
0.010

0.008

0.006

0.004

0.002

0.000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program v4.91 Page 17 of