Accurate: User and Maintenance Manual
Accurate: User and Maintenance Manual
Accurate: User and Maintenance Manual
precision air-conditioners
ACCURATE
Direct expansion
Direct expansion
AXO air outlet from the top
AXU air outlet from the bottom
Water-cooled
AWO air outlet from the top
AWU air outlet from the bottom
GB
frame 1: 07-10
frame 2: 15-18
frame 3: 20-26-29
frame 4: 39-30-40-50
frame 5: 55-60-70
U I A Calibrating the control and safety devices 11 U I A Terminal and board configuration 19
The following symbols are used in this publication and inside the unit:
U User Important
I Installer Prohibition
A Assistance
AX* AW*
AXO - AWO
fig. 1 fig. 2
1 OVER units with intake from the front and outlet plenum 2 OVER units with intake from the front and outlet from the
top
fig. 3 fig. 4
3 OVER units with intake from under the floor and outlet from 4 OVER units with intake from the rear and outlet from the top
the top
The versions defined as UNDER with air outlet from under the
floor have the air intake through the top of the unit directly from
the environment, or via ducts and/or intake plenums.
AXU - AWU
fig. 5
fig. 6
5 UNDER units with intake from the top and front outlet 6 UNDER units with intake from the top and outlet under the
plenum. floor
- Power input of the unit and the individual components; COOLING CAPACITY
POTENZA TERMICA
kW
kW
PRESSIONE MASSIM bar
- Current input of the unit and the individual components: OA ALIMENTAZIONE ELETTRICA DI POTENZ V - ~ - Hz
ALIMENTAZIONE ELETTRICA AUSILIARI V - ~ - Hz
(Operating current), FLA (Full load current) and LRA (Locked POTENZA ELETTRICA MAX. ASSORBIT kW
CORRENTE MAX. ASSORBIT A
rotor current); CORRENTE DI SPUNT A
GRADO DI PROTEZIONE IP X 4
- Settings of the pressure switches in the refrigerant circuit (HP SCHEMA ELETTRIC
PESO IN FUNZIONAMENT
N°
kg
and LP); ANNO DI FABBRICAZIONE
Total cooling capacity (1) kW 39,4 30,2 40,5 50,4 55,8 61,6 70,6
Sensible cooling capacity (1) kW 39,4 30,2 40,5 48,4 55,8 61,6 65
SHR (1) 1 1 1 0,97 1 1 0,92
Total cooling capacity (2) kW 35,8 27,5 36,8 45,4 50,8 56 63,6
Sensible cooling capacity (2) kW 35,8 27,5 36,8 45 50,8 56 60,4
SHR (2) 1 1 1 0,99 1 1 0,95
No. of compressors n° 1 2 2 2 2 2 2
Total power input kW 9,75 7,66 10,1 13,5 13,1 15,6 19,6
N° circuits n° 1 2 2 2 2 2 2
Air flow-rate mc/h 13500 10500 13500 13500 19000 19000 19000
No. of fans n° 2 2 2 2 3 3 3
Total power input kW 4 3,2 4 4 6 6 6
ESP (3) Pa 20 20 20 20 20 20 20
Noise level (5) 57 54 56 56 57 57 57
Standard power supply V/ph/Hz 400/3+N/50
Width mm 1550 2100
Depth mm 790
Height mm 1980
ARC outdoor condenser 052m 042b 051b 077b 077b 088b 93b
1 - 24°C-50%, 35°C ext 3 - Standard centrifugal fans
2 - 20°C-50%, 35°C ext 5 - measured at 1,5 m haight and 2 m front in free field
R22 R407C
Open any valves in the unit or in the system to ensure that all the components are involved in the emptying operation;
Connect a high efficiency vacuum pump to the Schrader fittings or to the 1/4” SAE fittings on the compressor suction and discharge side;
Wait 100 seconds and check that the absolute pressure does not rise above 200 Pa.
Break the vacuum by pre-charging from the cylinder of R22 Break the vacuum by pre-charging from the cylinder of R407C
refrigerant. refrigerant in the liquid phase.
After having started the compressor, complete the charge slowly, until the pressure stabilises in the lines and the gas bubbles disappear
from the flow indicator;
The charge must be checked at the environmental design conditions and with a discharge pressure of around 18 bar (equal to a dew
and with a discharge pressure of around 18 bar (equal to a saturated point of 48°C and boiling point of 43°C); for units with on-off con-
temperature of 48°C); for units with on-off condenser control, par- denser control, partially close the intake to stop the condenser fan
tially close the intake to stop the condenser fan from repeatedly from repeatedly starting-stopping.
starting-stopping. Make sure that the subcooling of the liquid at the thermostatic valve
Make sure that the subcooling of the liquid at the thermostatic valve intake is between 3 and 5°C less than the condensing temperature
intake is between 3 and 5°C less than the condensing temperature read on the pressure gauge and that the superheating of the vapour
read on the pressure gauge and that the superheating of the vapour at the evaporator outlet is around 5 °C.
at the evaporator outlet is around 5 °C.
The charge must be checked at the environmental design conditions
COMMISSIONING PROCEDURE trap (both inside and outside of the air-conditioner) have been filled
Arm the cutout in the auxiliary circuits; with water during installation.
Arm all the cutouts on the electrical panel;
Power up the air-conditioner electrical panel and close the main
disconnecting switch on the unit (position 'I'); AT LEAST 12 HOURS AFTER POWER UP:
Check that the control board is powered; Check that both the Start the air-conditioner using the buttons on the user terminal;
LEDs relating to the phase sequence relay (RSF) are on; the yellow If an alarm is activated refer to the controller instruction manual.
LED indicates power, the green LED indicates that the sequence of
phases is correct.
If the green LED is off, disconnect power supply from the units, rever-
se two phases of the power cable and restart the commissioning pro-
cedure.
(In the units with sump heaters)
After having powered up the air-conditioner, wait at least 12 hours
before starting so as to suitably heat the oil in the compressors.
During extended shutdown there may be spontaneous migration of
refrigerant to the compressor sump, which at the start may cause the
oil to foam and consequent damage due to insufficient lubrication.
As a result, do not disconnect power during weekly pauses;
Open the on-off valves in the refrigerant circuits and check that the
air-cooled remote condensers are connected (air-cooled models);
Check that the external radiators are connected and make sure there
is water flow for cooling (water-cooled models);
Check that the sections of corrugated pipe with the function of drain
1 main board
2 disconnecting switch
3 electric heaters
4 radial fan and inverter 3
5 compressor
6 dewatering filter
7 liquid valve 4
8 flow indicator
9 thermostatic valve
10 humidifier
11 dehumidification valve
2
1
12 hot water coil valve
13 temperature-humidity probe
8 13
9 7
11
10 5
6
12
The pressure test points for the air flow (F3) and dirty filter (F4)
differential pressure switches are connected in parallel; (on OVER
units) Pressure
test point Pressure Q.E.
- the positive pressure test point is located on the right-hand test point
Pressure
test point
RIGHT-HAND SIDE
RIGHT-HAND SIDE
Symbol Description
+ - A D
B
3
mbar mbar
2
B C D
A D
C
80
OUT
OUT
M
H
T
+
126 mm Shielded cable Fastening
inlet holes
Electric heaters
Modelli V/ph/Hz n° kW OA FLA
07 - 10 230/1/50 2 4 17,5 -
15 - 18 230/1/50 2 8 35 -
20 - 26 - 29 400/3N/50 3 9 13 -
39 - 30 - 40 - 50 400/3N/50 5 15 22 -
55 - 60 - 70 400/3N/50 6 18 26 -
Compressors
models V/ph/Hz n° kW OA FLA LRA
MAINTENANCE U I A
This section, aimed above all for the end user, is extremely impor- depends on the amount of dust in the environment.
tant for the correct operation of the appliance. In any case, the following are recommended:
Just a few operations completed scrupulously and regularly will - Every week check that the filters are clean
avoid serious damage to the components and expensive repairs - Every two weeks clean the filters with a vacuum cleaner
by specialist personnel. - Every month wash the filters with soapy water
The maintenance instructions are simple and do not require spe- - Every 6 months replace the filters.
cific technical knowledge of air-conditioning. It is clear that the recommended times are purely indicative, and
The purpose of this chapter is to assist and guide the user and in some cases it may be necessary to increase the frequency of
avoid having to unnecessarily call out specialist personnel. the checks and maintenance operations.
These operations must be carried out with the unit off and after
The maintenance operations can be summarised as follows: having made sure that the appliance is disconnected from the
- Clean the air filter. power supply.
- Check and clean the condenser coils
- Check the water-cooled condensers for fouling.
- Check and clean the drains.
- Check the drive belts.
- Check the humidification system.
- General examination of the overall operation of the appliance.
- Visual check of the condition of the pressurised containers.
DRIVE PULLEYS
Below is a description of how to assemble and dismantle the pul-
leys if these require replacement or repair.
Dismantling
Take out the 2 safety screws and remove the pulley from the
elastic ring
See Fig.A
A B
Assembly
Slide the elastic ring onto the motor pin. Insert the pulley on top,
then tighten the fastening screws
See Fig. B
KM4
2. TA1
3
4
7 1. A3
9. B1
5
6.
7. YV1 8. YV2
10. BH1
8
- completely drain the water from the boiler using the MANUAL
CONTROLS on the controller A1;
- disconnect the power supply by opening the main switch on the
electrical panel;
- remove the fill pipe from the 3/4 GAS fitting on the fill solenoid
valve;
- remove and clean the filter located inside the solenoid valve fit-
ting;
- dismantle the drain assembly (shown in Figure 13), clean the pipes
and remove any flakes of scale from the cup-drain trap.
TROUBLESHOOTING U I A
Troubleshooting is simplified by the information provided by the If required, contact the nearest service centre, indicating the
microprocessor controller: if an alarm is signalled, refer to the probable causes of the fault.
control panel instruction manual.
THE AIR-CONDITIO-
The electrical panel is not powered Check for voltage; close the main switch.
NER DOESN'T START
The air flow-rate is too low or null. See “LOW OR NO AIR FLOW”.
High temperature of the chilled water. Check the operation of the water chiller.
The power of the heaters is not sufficient or Check that the heater thermal cutout is armed.
the heaters aren't working. Check the power supply to the electric heaters.
If the heater safety thermostat is activated,
resolve the causes and reset the alarm.
The hot gas post-heating system isn't working Check the operation of the hot gas three-way
during the dehumidification plus post-heating valve;
phase Check the operation of the compressor used
for post-heating: in this case, see “THE
COMPRESSOR/COMPRESSORS DON'T
START”.
The three-way valve in the chilled water Close the valve using the manual control knob
circuit is stuck in the open position. and replace the servomotor.
Latent load higher than expected Check and calculate the latent load; check the
flow-rate and the conditions of the outside air;
check the inflow of outside air.
AMBIENT HUMIDITY The parameter settings on the microprocessor Check the room temperature setting (see the
TOO LOW controller are not correct. control panel manual).
Latent load lower than expected. Verificare la consistenza del carico latente.
LOW OR NO AIR
The fans are not powered. Check the power supply to the fans.
FLOW
Excessive pressure drop in the air distribution Check the sizing of the air distribution system
system. (ducting, false-ceiling, underfloor plenum, grills)
HEATER SAFETY
Insufficient air flow-rate See “LOW OR NO AIR FLOW”.
THERMOSTAT
ACTIVATED
Check the continuity of the connection from
Thermostat connection wire cut or broken
the safety thermostat to the control system.
B) Insufficient air flow-rate to the remote heat Check the operation and the correct direction
exchanger or air too hot of rotation of the fans on the outdoor heat
exchanger.
Check that the exchanger is not dirty and
remove any material that may be blocking it
(leaves, paper, seeds, dust, etc.) with a jet of
compressed air or with a brush;
Check the outdoor unit for any obstacles to
the flow of air and any recirculation of the coo-
ling air;
Check that the temperature of the cooling air
does not exceed the design value.
Too much refrigerant in the circuit. Remove refrigerant from the circuit
LOW COMPRESSOR Room temperature too low See “ROOM TEMPERATURE TOO LOW”.
SUCTION PRESSURE
(and possible defrosting
of the coil)
The air flow-rate is too low or null See “LOW OR NO AIR FLOW”.
Thermostatic valve not correctly calibrated Check that the thermostatic valve superheating
LOW PRESSURE
or faulty value is correct (around 5°C).
SWITCH ACTIVATED
(low compressor suction
pressure) Check and if necessary replace the dewatering
Dewatering filter cartridge dirty filter cartridge; the temperature difference
measured upstream and downstream of the
filter must be less than 2°C.