BTS 2000 The Fast Bus Transfer System: Solonics LTD
BTS 2000 The Fast Bus Transfer System: Solonics LTD
BTS 2000 The Fast Bus Transfer System: Solonics LTD
BTS 2000
THE FAST BUS TRANSFER SYSTEM
BTS 2000 Human Machine Interface
For Your High Speed Motor Bus Transfer Needs:-
Programmable LED indications Human Machine Interface
- Fast Transfer with less than 2 cycles of dead bus 20x4 Character Backlit LCD
- In Phase Transfer Mode -Transfer at first slip cycle Menu Navigation Pushbuttons
PLATFORM EDISON IDEA PLUS MANUFACTURED BY COOPER POWER SYSTEMS U.S.A. WITH 32 BIT MICROPROCESSOR BASED RISC
ARCHITECTURE
MOUNTING HORIZONTAL, FLUSH MOUNTING IN THE SWITCHGEAR CUBICLE / SIMPLEX PANEL / 19” RACK FRAME WITH A ½ 19” RACK
& WEIGHT ADAPTER WITH AN OPTIONAL DEDICATED COMPUTER INTERFACE. WEIGHT: 6KGS.
DIMENSIONS 5U HEIGHT, ½ 19” RACK EQUIPMENT [262 (W) x 222 (H) x 254 (D) mm]
TEMP. RANGE -40 DEG C TO +70 DEG C CONTINUOUS
-40 DEG C TO +85 DEG C UPTO 16 HOURS
POWER SUPPLY 250V AC/DC +/- 20%, OTHER STANDARD VOLTAGES E.G. 120/ 48/24 V AC/DC ON REQUEST.
VISUAL INTERFACE 25 PROGRAMMABLE LED INDICATIONS
20 CHARACTER, 4 LINE, WIDE ANGLE, HIGH TEMPERATURE, SUPER TWIST BACKLIT LCD FOR MENU DISPLAY
BTS OUT HIGH INTENSITY LED INDICATION
CONTROL INTERFACE 8 FIXED FUNCTION PUSHBUTTONS FOR MENU NAVIGATION
8 HOTKEYS FOR DIRECT MENU ACCESS
4 MULTI FUNCTION PROGRAMMABLE, CONTEXT SENSITIVE PUSHBUTTONS FOR MENU BASED CONTROLS
9 FIXED FUNCTION PUSHBUTTONS WITH LED INDICATIONS FOR TRANSFER DIRECTION SELECTION & TRANSFER MODE
SELECTION
1 EACH TEST AND TRANSFER ILLUMINATED PUSHBUTTONS
BTS SERVICE SELECTION IN/OUT TOGGLE SWITCH
BTS READINESS DISABLE FUSE
SYSTEM INTERFACE UPTO 17 CONTACT INPUTS, 4 TRIP RATED ELECTROMECHANICAL CONTACT OUTPUTS, 9 TRIP RATED SOLID STATE
CONTACT OUTPUTS, 4 5A CURRENT INPUTS, 6 110VAC VOLTAGE INPUTS, FRONT AND REAR RS-232 PORTS, RS-485
PORT/RJ-45 PORT, IRIG-B PORT. (INDIVIDUAL CONFIGURATIONS VARY)
SOFTWARE INTERFACE GRAPHICAL USER INTERFACE BASED SCHEME IMPLEMENTATION, VIRTUAL TEST SET SIMULATION, MODULAR OBJECT
ORIENTED PROGRAMMING, SETTINGS, ONLINE VIEWING, SCADA MIMIC APPLICATION DIAGRAM, SEQUENCE OF EVENT
RECORDING, STEP-BY-STEP REPLAY, “WHAT-IF” ANALYSIS, OSCILLOGRAPHY, DATA PROFILER, REMOTE CONTROL.
HARDWARE STANDARDS ELECTROMAGNETIC COMPATIBILITY: ENVIRONMENTAL TESTING:
IMPULSE / DIELECTRIC WITHSTAND: IEC 60255-5 COLD TEMPERATURE TEST: IEC 60068-2-1
ELECTROSTATIC DISCHARGE: EN 61000-4-2, IEC 60255-22-2 HIGH TEMPERATURE TEST: IEC 60068-2-2
RADIO FREQUENCY INTERFERENCE EN 61000-4-3 HUMIDITY TEST: IEC 60068-2-30
SURGE WITHSTAND: ANSI / IEEE C37.90.1, IEC 61000-4-5 ENVIRONMENTAL WITHSTAND: IEC 60068-2-30
CONDUCTED IMMUNITY TEST15 Hz 150 kHz: IEC 61000-4-16 VIBRATION TEST: IEC 255-21-1
CONDUCTED IMMUNITY TEST: 150 kHz 80 MHz: IEC 61000-4-6 BUMP & SHOCK TEST: IEC 60255-21-2
DC SUPPLY INTERRUPTION TEST - IEC 60255-11 PENETRATION: IEC 60259, IP3X
VOLTAGE DIP & INTERRUPTION - IEC 61000-4-11
HIGH FREQUENCY DISTURBANCE TEST - IEC 60255-22-1
ELECTRIC FAST TRANSIENT/ BURST IMMUNITY - IEC 60255-22-4
CONDUCTED EMISSION - EN 55022
RADIATED EMISSION - EN 55022
RADIATED IMMUNITY TEST: 80 MHz 1 GHz: EN 61000-4-3, IEEE C37.90.2, IEC 60255-22-3
INSULATION RESISTANCE TEST - IEC 60255-5
AC RIPPLE ON DC SUPPLY
CONTACT RATING TEST:
MAKE AND CARRY RATING: IEEE C37.90
BUS TRANSFER SCHEME MULTIPLE TRANSFER DIRECTIONS: BASED ON BREAKER CONFIGURATIONS
FEATURES MULTIPLE TRANSFER INITIATION: MANUAL, PROTECTIVE & AUTO INITIATION (U/V, U/F & |df/dt| BASED)
TRANSFER MODES: FAST, IN-PHASE, RESIDUAL VOLTAGE / SLOW, MOMENTARY PARALLELING
COMPREHENSIVE TRANSFER READINESS & BTS BLOCKING INTERLOCKS
CONTINUOUS BREAKER TRIP/CLOSE CIRCUIT MONITORING
SMART BREAKER FAILURE PROCESSING
COMPREHENSIVE ONLINE / OFFLINE TESTING MODES
ANSI C50.41 2000 COMPLIANT
NORMAL SOURCE
FAST TRANSFER VOLTAGE PHASOR
IN PHASE TRANSFER (V NORMAL)
RESIDUAL VOLTAGE OR MOTOR BUS
SLOW TRANSFER VOLTAGE PHASOR
VOLTAGE COLLAPSE
AND PHASE DECAY
CHARACTERISTICS
OF THE MOTOR BUS
For any queries, please write to [email protected] or contact us at our Registered Office