MAIN PRODUCTS
Digital Temperature Controller - DIGITAL : Temperature Controller, Counter, Timer,Speedmeter,

ED6
Tachometer, Panel Meter, Recorder
- SENSOR : Proximity Sensor/Photo Electric Sensor,
Rotary Encoder, Optical Fiber Sensor,
Pressure Sensor
INSTRUCTION MANUAL - ANALOG : Timer, Temperature Controller
We appreciate you for purchasing HanYoung NUX Co.,Ltd
product. Before using the product you have purchased, HEAD OFFICE
check to make sure that it is exactly what you ordered. Then, 1381-3, Juan-Dong, Nam-Gu Incheon, Korea
please use it following the instructions below. TEL: (82-32)876-4697 FAX : (82-32)876-4696

11. When attaching this product to a panel, use an


Safety information approved switch or circuit breaker from IEC947-1 or
Before you use, read safety precautions carefully, and use IEC947-3.
this product properly. The precautions described in this 12. The warranty period for this product including parts is
manual contain important contents related with safety; one year if this product is properly used.
therefore, please follow the instructions accordingly. The 13. When the power is on, the preparation period of contact
precautions are composed of DANGER, WARNING and output is required. In case of using for signals of
CAUTION. external interlock circuit, use with a delay relay.

DANGER
There is a danger of occurring electric shock in the
Model and Suffix code
input/output terminals so please never let your body or MODEL Suffix code Description
conductive substance is touched. ED6 Aspect 77 x 35 mm

WARNING Control F ON/OFF Operation


Operation P Proportional Operation (P control)
1. To prevent defection or malfunction of this product, K K(CA) Range : -80.0 ~ 999.9
apply a proper power voltage in accordance with the P Pt100(Din) Range : -100.0 ~ 400.0
rating. Input Sensor
1 ~ 5 V DC Range : -1000 ~ 5000
2. Since this product is not designed with explosion- C
4 ~ 20 mA DC
( attach 250 ( 0.1 %) resistor in
input terminal)
protective structure, do not use it any place with Relay Contact Point
M
flammable or explosive gas. Output Control
SSR Output (Voltage Pulse 5 V DC)
S
3. Reassemble this product while the power is OFF.
A Alarm & Defrost
Otherwise, it may be a cause of malfunction or electric Options
N None
shock.
P3 10 ~ 24 V DC, AC
4. There is a possibility of occurring electric shock so Power Supply
P4 100 ~ 240 V AC
please use this product after installing it to a panel while
it is operating.
CAUTION
Ratings
1. The contents of this manual may be changed without
prior notification. Power Supply Refer to “Power Supply” in “Model and Suffix Code”
2. Make sure that there is no damage or abnormality of the Power Consumption Below 5 VA
product during delivery. Input Sensor Refer to “Input Sensor” in “Model and Suffix Code”
3. Do not use this product at any place with direct vibration Display Accuracy Max range (FS 0.5 % +1 Digit)
or impact. Output Control Relay Output 250 V AC 5 A (resistive load)
4. Do not use this product at any place with liquid, oil, (Main Output) SSR Output 5 V DC 50 mA (max)
medical substances, dust, salt or iron contents.(Use at Alarm & Defrost Relay Output 250 V AC 5 A (resistive load)
Pollution level 1 or 2) Two Position Operation (ON/OFF)
Control Operation
5. Do not use this product at any place with a large Proportional Operation (P)
inductive difficulty or occurring static electricity or Setting Method Digital method by setting, up and down keys
magnetic noise. Auxiliary output(Alarm & Defrosting Timer)
6. In case of inputting thermocouple, use a compensating Other Functions
Heating/cooling
cable. (If using a normal wire, there is a possibility of Thermocouple type (CA) Below 100 for each wire
occurring temperature error.) Resistance Below 10 for each wire
7. For R.T.D input, use a cable which is a lead wire has between wires Resistive type (Pt 100 ) (Resistance of 3 wires
small resistance and resistances of three wires shall be
should be the same.)
the same. (If the three wires have different resistances
Operating Ambient
then there will be a temperature error.) 0 ~ 50 / below 35 ~ 85 % R.H (no condensation)
Temperature/Humidity
8. Separate an input signal cable from an output signal
cable. If separating is not possible, please use the input
signal cable after shielding it.
9. Use non-earth sensor with thermocouple. (In case of
using earth sensor, there is a possibility of occurring Wiring Diagram
malfunction caused by a short circuit.)
10. If there is excessive noise from the power supply, using ALM
(Alarm)
OUT
(Main)
insulating transformer or noise filter is recommended.
T.C
The noise filter must be attached to a panel which is
already connected to a ground and the wire between the
filter output and power supply terminal must be short as
possible.
Heating Control (ON/OFF)
Dimension & Panel Cutout PV=Present Temperature, SV=Setting Temperature
Unit : mm PV < SV Main Output Relay ‘ON’
77 PV > SV Main Output Relay ‘OFF’

50 70
45 65
35

ON OFF ON OFF OFF ON OFF ON

Main output Alarm Output (High Limit Alarm)


ED6
[setting=50 , dlf=5, dLy=0, tyP=HEt] [AtS=70, AdF=5, AdL=0, SAo=0]

6.5
60.5 10 Proportional Control
Proportional Control is that an output capacity regarding a setting value
(SV) is proportionally operated by a deviation. The width which the
output is varied within 0 ~ 100 % is called Proportional Band (PB).
Therefore, if PV=Present Temperature, PB=Proportional Band

28.5
PV < PB Output capacity 100 %
35

PV > PB Output capacity 0 %


PV = PB Output capacity 50 %

Temperature PV

71 0.3
PB
SV

Time
0.3

PC
ON
PANEL CUT OUT
29

OFF

SV PV: Present Temperature


SV: Setting Value
PB: Proportional Band
PC: Proportional Cycle
Parts Name
Main output indicator Delay Timer Setting
At present temperature,
Auxiliary output indicator 1. Press [ ] key for more than 3 sec
Indicator window 2. Go to by pressing [ ] key
3. Change the setting by using [ ]/[ ] key
4. Save it by pressing [ ] key
[ ] [ ] [ ] (0 ~ 240 sec.)

Operation Description of Delay Relay OFF Relay ON


Timer
Delay Time ‘dLy’ = 0
0 S 5 S 10 S 15 S 20 S

ED6 Delay Time ‘dLy’ = 5 Relay OFF Relay ON

Setting Down Up In case of Delay Time=0, Relay is immediately ON when output


signal is generating. In case of Delay Time=5, Relay is ON after 5
sec. when output signal is generating. In the interval of 5 sec, the
output indicator is flickering during Delay Timer Operation. After the
delay time, the output indicator lights as the relay is on.

Controlling Temperature Method


Auxiliary Output (Timer Mode) Setting and
Cooling/Heating Control Setting
Operation Description
: Heating Control When using as a freezer, Timer Mode can be used as Defrosting
: Cooling Control Function.
min. : minute
Cooling Control (ON/OFF) 0 : Alarm Mode
PV=Present Temperature, SV=Setting Temperature 1 : Timer Mode (Setting)
PV > SV Main Output Relay ‘ON’
PV < SV Main Output Relay ‘OFF’
15 min OFF 5 min 15 min OFF 5 min
ON ON
ton = 5 min, tof = Timer Output at 15 min
-20 -35
-25 -40
0 : Main Output Control Cancellation

1 : Main Output Control


ON OFF ON OFF OFF ON OFF ON
If MOC is 1 then Timer is ON as Main Output is automatically OFF.
Main output Alarm Output (Low Limit Alarm) When using MOC function, you can effectively use Timer Output as
[setting=-25 , dlf=5, dLy=0, tyP=CoL] [AtS=-40, AdF=5, AdL=0, SAo=0] Defrosting Function.
Setting Menu
Setting of SV Lock function, Decimal Point function & Adjusting Operation Setting
Item SV Description SV : Setting Value
0 Lock cancellation, User Setting is possible P.B : Proportional Band
Lock M.R : Offset Elimination
1 Lock and User Setting are not possible
0 Decimal point function (0.1 )
trSL (Pt100, CA)
1 No Decimal point function (1 )
trSL (1 ~ 5 V DC) 0~2 Decimal point function (Ex. 0:200, 1:20.0, 2:2.00)
Proportional Control
0
PorF (P.B value/ M.R value setting is possible)
1 ON/OFF Control

※Input : 1 ~ 5 V DC
※Input : Pt100, CA
Present
Temperature Decimal Point Function
Decimal Point Function
Change a position
To Enter Setting Mode
of decimal point (0 ~ 2)
Press it for more than 3 sec. ※Default : 0
0: 200 1: 20.0
2: 2.00
0.1 ℃ Resolution 1 ℃ Resolution ※Default : 0
Control Method Setting •Save SV

At the same time, High Scale


+ press them for more -1000(L-Sc)~H-Sc
than 3 sec. ※Default : 200
•Save SV •Save SV
SV Lock Function

※Default : 0
Cancellation Lock Adjusting Operation Low Scale
Setting
L-Sc ~ 5000(H-Sc)
※Default : -200

P (Proportional) Control ON/OFF Control

•Save SV

•Save SV/ Return to the initial menu.


※To enter menu press key
for more than 3 sec.

Present
Temperature

SV : Setting Value

Normal User Setting Mode

※PorF='0' when setting P (Proportional Control)


Present
Temperature
Proportional Band Setting(P.B)

•Function Selection Setting Range : 1~100 ℃


※Default : 20 ℃

•Save SV
Temperature Setting (SV)

※Default : 25 ℃ Offset Elimination (M.R)


Setting Range : 1~100 %
※Default : 50 %

•Save SV
Present
Temperature
Present
Temperature

SV : Setting Value
Confirmation mode of Output Capacity & Setting Value

When operating Proportional Control, display Present Output


Capacity (0 ~ 100 %).
Present -In case of occurring Offset, eliminate M.R value by decreasing as
※PorF='0' when setting P referring Present Output Capacity.
Temperature
(Proportional Control)
Heating Control MODE Cooling Control MODE
•Output Capacity (%) •Setting Value (SV) PV < SV: Increase M.R value PV > SV: Increase M.R value
Flickering Display for 1 sec Flickering Display for 1 sec PV > SV: Decrease M.R value PV < SV: Decrease M.R value

Present
Temperature PV : Present Value
SV : Setting Value
M.R : Offset Elimination

Setting MODE

Present 4.High Limit of Setting Range


Temperature
Ex) Pt100
A: -100 ℃ ~ TSH(High Limit)
B: -100.0 ℃ ~ TSH(High Limit)
(Press for more than 3 sec) ※Default : Pt100(400.0 ℃)
CA(999.9 ℃)
1 ~ 5 V DC (5000)
0. Control Method Setting •Save SV
5.Low Limit of Setting Range
Ex) Pt100
Default SV display A: TSL(Low Limit) ~ -400 ℃(TSH)
B: TSL(Low Limit) ~ -400.0 ℃(TSH)
※Default : Pt100(-100.0 ℃)
CA(-80.0 ℃)
1 ~ 5 V DC (-1000)

•Save SV

Cooling Control Heating Control 6.Auxiliary Output Selection


※Default : 0

※Default : Heat

•Save SV

Alarm Setting Timer Setting


Menu Menu
1.Deviation Setting

7.ON Time Setting


•Deviation Setting 7.Alarm Temperature Setting
A: 1 ~ 50 ℃ A: -100 ~ 400 ℃
B: 1.0 ~ 50.0 ℃ B: -100.0 ~ 400.0 ℃
•Setting Range: 0 ~ 999 minute
※Default : 2.0 ℃ ※Default : Pt100(400.0 ℃) ※Default : 1 minute
•Save SV CA(999.9 ℃)
1 ~ 5 V DC (5000) •Save SV

•Save SV

2.Delay Time Setting 8.Deviation Setting for Alarm 8.OFF Time Setting

•Setting Range: 0~ 240 sec A: 1 ~ 50 ℃


B: 1.0 ~ 50.0 ℃
※Default : 1 sec. •Setting Range: 0 ~ 999 minute
※Default : 2.0 ℃ ※Default : 3 minute
•Save SV
•Save SV
•Save SV

3.Input Compensation
9.Delay Time Setting for Alarm 9.Main Output Control
A: -30 ~ 30℃
B: -30 ~ 30.0℃
•Setting Range
※Compensating for 0: Output Control Cancellation
: 0 ~ 240 sec.
Sensor Line Length 1: Output Control
or error occurrance ※Default : 1 sec.
※Default : 0.0 ℃ •Save SV •Save SV
•Save SV
※ A : 1℃ Display Mode(trSL=1) ※Only it can be used when PorF=1 (ON/OFF Control)
B : 0.1℃ Display Mode (trSL=0)

SV : Setting Value