Aptomat (MCCB, MCB), Contactor LS (LG)
Aptomat (MCCB, MCB), Contactor LS (LG)
Aptomat (MCCB, MCB), Contactor LS (LG)
Electric Equipment
Page 4
● 1, 2, 3 and 4 pole series up to 125AF
● B, C and D Characteristics
Page 6
● 2 and 4 pole series up to 63AF
● Sensitivity up to 300mA
Page 8
Metasol/Meta-MEC series
● 3 and 4 pole series up to 800AF Mini-contactors available
● AC/DC common use coil from 100AF
Page 18
Page 20
Susol /Meta-MEC series
● 2, 3 and 4 pole series up to 1600AF
● Rated ambient temperature at 40℃ calibrated for 50℃ available
Page 26
Susol/Metasol series
● 65, 85 and 150kA breaking capacity
● High functional digital trip relays
● CE marked and Marine classiflcation
Page 32
Susol series
Miniature circuit breakers
1, 2, 3 and 4 pole series up to 125AF
Lug terminal
cable capacity 2.5㎟
9mm wide
(17)
63
45
82
37
82
60
45
37
(22)
(14)
5 45 5 45 17.8
8.9
60 60
68 17.8 68
4
BKN-b BKH
Overload and short circuit Overload and short circuit
1,2,3,4,6,10,20,25,32,40,50,63A 63, 80, 100, 125A
B, C, D curve C, D curve
1p, 1p+N, 2p, 3p, 3p+N, 4p 1p, 1p+N, 2p, 3p, 3p+N, 4p
1 pole 2~4 pole 1 pole 2~4 pole
10kA at 10kA at
400VAC 400VAC
10kA at 10kA at
230/400VAC 400VAC
82
45
65
5 43.8
60
17.8
68
5
Residual current circuit breakers
2 and 4 pole series up to 63AF
(22)
22
(17)
1 3 5 N 1 N
36
45
68
68
82
82
45
37
60
82
(22)
2 4 6 N 2 N
(13)
5 45 5 45 72 36
8.9
60 61
68 35.6 74
70
45
60
82
23
(10)
17.8
5 45
18
60
70 18
6
32KGRa 32KGRb Type BKD
Ground fault and overcurrent Rated current, In 40, 50, 63, 80, 100, 125A
15, 20, 30A Number of poles 1p, 2p, 3p, 4p
Rated voltage 230/400VAC
15, 30mA(non-adjustable) Standard IEC 60947-3
0.5I△n Electrical 40, 50, 63A 20000 operations
2 pole endurance 80, 100, 125A 10000 operations
110/220VAC Mount On 35mm DIN rail
≤ 0.03 sec. Width 17.8mm per pole
KS, JIS *(IEC61009) Terminal Lug type(cable up to 50㎟)
Dimension See drawing 4
Electronic
Bimetallic
1.5kA 2.5kA
6000 operations
On 35mm DIN rail
35mm
Screw clamp type(cable up to 25㎟)
See drawing 3
See curve 1
Note) * IEC61009 standard is applicable for 32KGRa only.
7
Contactors & Overload relays
Metasol MC 18 to 100A
MC type
Magnetic Contactors
MT type
Thermal Overload Relays
* The safety cover of magnetic contactor and thermal overload relay is optional.
8
40AF 65AF 100AF
MC-32a MC-40a MC-50a MC-65a MC-75a MC-85a MC-100a
● ● ● ● ● ● ●
3pole 3pole 3pole
690V 690V 690V
1000V 1000V 1000V
50/60Hz 50/60Hz 50/60Hz
8kV 8kV 8kV
1800 operations per hour 1800 operations per hour 1800 operations per hour
12 mil. operations 12 mil. operations 12 mil. operations
2 mil. operations 2 mil. operations 2 mil. operations
50 60 70 100 110 135 160
7.5 11 15 18.5 22 25 30
32 40 55 65 75 85 105
15 18.5 22 30 37 45 55
32 40 50 65 75 85 105
18.5 22 30 33 37 45 55
28 32 43 60 64 75 85
18.5 22 30 33 37 45 45
20 23 28 35 42 45 65
4.5 5.5 7.5 11 13 15 19
20 25 35 50 55 65 80
7.5 11 15 22 25 30 37
17 24 32 47 52 62 75
0.55 1.05 1.93
69×83×93 79×106×122 94×140×137
0.77 1.3 2.8
69×83×120 79×106×149 94×140×174
2a2b 2a2b 2a2b
UA-1 UA-1 UA-1
AU-2, AU-4 AU-2, AU-4 AU-2, AU-4
9
Contactors & Overload relays
Metasol MC 150 to 800A
MC type
Magnetic Contactors
MT type
Thermal Overload Relays
10
400AF 800AF
MC-265a MC-330a MC-400a MC-500a MC-630a MC-800a
● ● ● ● ● ●
3pole 3pole
690V 690V
1000V 1000V
50/60Hz 50/60Hz
8kV 8kV
1200 operations per hour 1200 operations per hour
5 mil. operations 2.5 mil. operations 2.5 mil. operations
1 mil. operations 0.5 mil. operations 0.5 mil. operations
300 350 450 580 660 900
80 90 125 147 190 220
265 330 400 500 630 800
132 150 200 250 300 400
265 330 400 500 630 800
140 160 200 250 300 400
225 280 350 400 500 720
160 200 250 300 400 500
185 225 300 380 420 630
50 55 75 90 110 160
200 220 300 350 400 630
102 110 150 176 200 300
200 220 300 350 400 630
9.2 22.4
163×243×198 285×312×242
MT-400/� MT-800/�
● ●
690V 690V
690V 690V
6kV 6kV
10A, 20 10A, 20
85~400A 200~800A
2.6 11.5
151×171×198 360×530×212
11
Contactors & Overload relays
9 to 85A
3-pole Contactors
4-pole Contactors
Overload Relays
Setting 0.1 - 0.16 4-6
ranges (A) 0.16 - 0.25 5-8
0.25 - 0.4 6-9
Bimetallic style 0.4 - 0.63 7 - 10
0.63 - 1 9 - 13
Type GT 1 - 1.6 12 - 16 Base for
1.6 - 2.5 16 - 22 separate mount
GT-22 2.5 - 4
Differential GTK-22
Class10A Non-differential (3-heater) GTH-22/3
Non-differential (2-heater) GTH-22
Class 20 Differential GTK-22/L
Setting ranges (A)
Electronic style 0.1 - 1.5
1-5
Type GMP 4.4 - 22
12
32A 40A 50A 65A 75A 85A
GTK-40 GTK-85
GTH-40/3 GTH-85/3
GTH-40 GTH-85
GTK-40/L GTK-85/L
Setting ranges (A) Setting ranges(A) : 16 ~ 80A Setting ranges(A) : 5 ~ 60A
4 - 20
8 - 40
3-pole Contactors
Types AC/DC
GMC-100 GMC-125 GMC-150
common coil
Ratings / IEC60947-4 kW A kW A kW A
AC1 160 160 210
AC3 200/240V 30 105 37 125 45 150
380/440V 55 105 60 120 75 150
500/550V 55 85 60 90 90 140
690V 55 65 60 70 90 100
Ratings / UL508 hp A hp A hp A
continuous current 160 160 210
single phase 115V 7.5 10 15
230V 15 20 25
three phase 200V 30 40 40
230V 30 40 50
460V 60 75 100
575V 60 75 100
NEMA size 3 3 4
Additional auxiliary contacts
AU-100
1NO+1NC, Side mount
4-pole Contactors
Types AC/DC
GMC-100/4 GMC-125/4 GMC-150/4
common coil
AC1(A) 160 160 210
Overload Relays
14
180A 220A 300A 400A 600A 800A
kW A kW A kW A kW A kW A kW A
230 275 350 450 660 900
55 180 75 250 90 300 125 400 190 630 220 800
90 180 132 250 160 300 220 400 330 630 440 800
110 180 132 200 160 250 225 350 330 500 550 720
110 120 132 150 200 220 250 300 330 420 500 630
hp A hp A hp A hp A hp A hp A
230 275 350 450 660 900
15 15
30 40
60 60 100 125 150 250
60 75 100 150 200 300
125 150 200 300 400 600
125 150 200 300 400 600
4 4 5 5 6 7
AU-100
1NO+1NC, Side mount
15
Mini contactors
6 to 16A
Mini contactors
Overload Relays
Differential GTK-12M
Non-differential (3-heater) GTH-12M/3
Non-differential (2-heater) GTH-12M
16
Digital motor protection relay
DMP�-S/Sa DMP�-T/Ta
Operation time Select either reverse time characteristics or definite time characteristics
Protection Over current According to the setting time
Phase failure 3 sec.
Reverse phase Within 0.1 sec.
Asymmetry 5 sec.
Stall 5 sec.
Lock Within 0.5 sec.
Under current 3 sec.
Ground fault Within 0.05~1 sec. Selectable (0.05~1.0sec)
Short circuit Note2) Within 50ms
Alarm Variable (60~110% of the setting current)
Current setting range (A) 0.5~6 5~60 0.5~6 5~60
Motor capacity 220~240V 0.09~0.75 1.1~11 0.09~0.75 1.1~11
(kW) 380~440V 0.12~1.5 2.2~22 0.09~1.5 2.2~22
Time setting Definite Delay in starting 0~60sec
range (sec) time Delay in operating 0~30sec
Inverse time 0~60sec
Reset Manual reset
Tolerance Current ±5%
Time ±5% (or±0.5sec)
Operating power Voltage AC 190~250V
Note3) Frequency 60Hz (50Hz)
Aux. contact OL 2-SPST 3A/250Vac Resistive load
AL SPST 3A/250Vac Resistive load
Insulation resistance Over DC500V 100㏁
Surge impulse voltage(IEC1000-4-5) 1.2×50㎲ 6kV (Apply standard wave form)
Fast transient burst(IEC1000-4-4) 2.5kV/5min
Environment Temperature Operation -25~70℃
Storage -30~80℃
Humidity 30~90% RH (No freezing)
Display 7-Segment 3 phase current, cause of a fault
Bar-Graph 60~110% of real load current
Mounting type 35mm Din-rail/Panel
Note1) In extension type, the digital EMPR is calibrated with combining the display past and main body so,
please cautious not to combine the display part and main body with different part No.
Note2) Instantaneous short circuit protection is optional
Note3) Operational voltage of AC 110V and 50Hz is optional
17
Manual motor starters
Quick selection table ... IEC rating
Frame 32AF
Current adjustable type MMS-32S MMS-32H
Type
Instantaneous type - MMS-32HI
Breaking capacity Standard High breaking
Handle Type Toggle Rotary
Number of poles 3 3
Rated operational voltage (Ue) Up to 690V Up to 690V
Rated frequency 50/60 Hz 50/60 Hz
Rated insulation voltage (Ui) 690V 690V
Rated impulse voltage (Uimp) 6kV 6kV
Utilization category IEC 60 947-2 (Breaker) Cat. A Cat. A
IEC 60 947-4 (Motor starter) AC 3 AC 3
Mechanical endurance (Operating) 100,000 100,000
Electrical endurance (Cycles) 100,000 100,000
Max operating frequency per hour (Ope./h) 25 25
Temperature compensation (Operation) -20 ~ +60℃ -20 ~ +60℃
Instantaneous short circuit release 13 × Ie max. 13 × Ie max.
Overload protection � �
Phase failure function � �
Trip indicating function × ×
Test function � �
Weight (g) 320 360
Rated Thermal release 220V 220V
Rated 415V 460V 525V 690V 415V 460V 525V 690V
breaking Adjustment 240V 400V 440V 500V 600V 240V 400V 440V 500V 600V
operational 230V 230V
capacity range
current (Ie) Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
(kA) (A)
0.16 0.1~0.16 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
0.25 0.16~0.25 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
0.4 0.25~0.4 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
0.63 0.4~0.63 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
1 0.63~1 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
1.6 1~1.6 100 100 100 100 100 100 100 100 3 3 100 100 100 100 100 100 100 100 100 100
2.5 1.6~2.5 100 100 100 100 100 100 50 38 3 3 100 100 100 100 100 100 100 100 8 8
4 2.5~4 100 100 100 100 50 38 15 11 3 3 100 100 100 100 100 100 100 100 8 8
6 4~6 100 100 100 100 15 11 10 8 3 3 100 100 100 100 100 100 100 100 6 6
8 5~8 100 100 100 100 15 11 10 8 3 3 100 100 100 100 50 38 50 38 6 6
10 6~10 100 100 50 38 15 11 6 5 3 3 100 100 100 100 50 38 50 38 6 6
13 9~13 100 100 50 38 10 8 6 5 3 3 100 100 100 100 50 38 42 32 6 6
17 11~17 50 38 20 15 10 8 6 5 3 3 100 100 50 38 20 15 10 8 4 4
22 14~22 40 30 15 11 8 6 6 5 3 3 100 100 50 38 20 15 10 8 4 4
26 18~26 40 30 15 11 8 6 6 5 3 3 100 100 50 38 20 15 10 8 4 4
32 22~32 30 22 15 11 6 4 5 4 3 3 100 100 50 38 20 15 10 8 4 4
40 28~40 - - - - - - - - - - - - - - - - - - - -
50 34~50 - - - - - - - - - - - - - - - - - - - -
63 45~63 - - - - - - - - - - - - - - - - - - - -
75 55~75 - - - - - - - - - - - - - - - - - - - -
90 70~90 - - - - - - - - - - - - - - - - - - - -
100 80~100 - - - - - - - - - - - - - - - - - - - -
18
63AF 100AF
MMS-63S MMS-63H MMS-100S MMS-100H
- MMS-63HI - MMS-100HI
Standard High breaking Standard High breaking
Rotary Rotary Rotary Rotary
3 3 3 3
Up to 690V Up to 690V Up to 690V Up to 690V
50/60 Hz 50/60 Hz 50/60 Hz 50/60 Hz
1,000V 1,000V 1,000V 1,000V
8kV 8kV 8kV 8kV
Cat. A Cat. A Cat. A Cat. A
AC 3 AC 3 AC 3 AC 3
50,000 50,000 50,000 50,000
25,000 25,000 25,000 25,000
25 25 25 25
-20 ~ +60℃ -20 ~ +60℃ -20 ~ +60℃ -20 ~ +60℃
13 × Ie max. 13 × Ie max. 13 × Ie max. 13 × Ie max.
� � � �
� � � �
× × � �
� � � �
1,000 1,000 2,200 2,200
220V 220V 220V 415V 460V 525V 690V 220V 415V 460V 525V 690V
415V 460V 525V 690V 415V 460V 525V 690V
240V 240V 240V 400V 440V 500V 600V 240V 400V 440V 500V 600V
400V 440V 500V 600V 400V 440V 500V 600V
230V 230V 230V 230V
Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
100 100 100 100 15 12 10 8 4 3 100 100 100 100 50 38 50 38 6 5 - - - - - - - - - - - - - - - - - - - -
100 100 50 38 10 8 6 5 4 3 100 100 100 100 50 38 42 32 6 5 - - - - - - - - - - - - - - - - - - - -
100 100 25 19 10 8 6 5 4 3 100 100 50 50 50 38 12 9 5 5 100 100 50 38 40 30 25 19 10 8 100 100 100 100 50 38 35 27 12 9
50 38 25 19 10 8 6 5 4 3 100 100 50 50 50 38 12 9 5 5 100 100 50 38 40 30 25 19 10 8 100 100 100 50 50 38 35 27 12 9
50 38 25 19 10 8 6 5 4 3 100 100 50 50 35 27 12 9 5 5 100 100 50 38 40 30 25 19 10 8 100 100 100 50 50 38 35 27 12 9
50 38 25 19 10 8 6 5 4 3 100 100 50 50 35 27 10 8 5 5 100 100 50 38 40 30 15 11 10 8 100 100 100 50 50 38 25 19 12 9
50 38 25 19 10 8 6 5 4 3 100 100 50 50 35 27 10 8 5 5 100 100 50 38 40 30 15 11 6 5 100 100 100 50 50 38 20 15 12 9
50 38 25 19 10 8 6 5 4 3 100 100 50 50 35 27 10 8 5 5 100 100 50 38 40 30 12 9 6 5 100 100 100 50 50 38 15 11 10 8
50 38 25 19 10 8 6 5 4 3 100 100 50 50 35 27 10 8 5 5 100 100 50 38 40 30 12 9 6 5 100 100 100 50 50 38 15 11 8 6
- - - - - - - - - - - - - - - - - - - - 100 100 50 38 40 30 8 6 5 4 100 100 75 50 50 38 12 9 6 6
- - - - - - - - - - - - - - - - - - - - 100 100 50 38 40 30 8 6 5 4 100 100 75 50 50 38 12 9 6 6
- - - - - - - - - - - - - - - - - - - - 100 100 50 38 40 30 8 6 5 4 100 100 75 50 50 38 12 9 6 6
19
Mold case circuit breakers
Susol MCCB Series
(100)※, 125, 160 125, 160, 200, 250 300, 400 500, 630 700★★, 800
100 120 200 100 120 200 100 120 200 100 120 200 100 120 200
220 264 440 220 264 440 220 264 440 220 264 440 220 264 440
105 187 330 105 187 330 143 187 330 143 187 330 143 220 330
105 154 286 105 154 286 143 187 286 143 187 286 143 220 286
88 143 187 88 143 187 88 143 187 88 143 187 88 187 220
17 30 40 17 30 40 17 40 74 17 40 74 17 40 74
A A A A A
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
- - ● ● ●
- - ● ● ●
- - ● ● ●
- - ● ● ●
- - ● ● ●
- - ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
● ● ● ● ●
25000 25000 20000 20000 10000
10000 10000 6000 6000 3000
- - - - -
105×160×86 105×160×86 140×260×110 140×260×110 210×320×135
140×160×86 140×160×86 186.5×260×110 186.5×260×110 280×320×135
- - - - -
2 2 5.4 5.4 15.1
2.6 2.6 7.2 7.2 19.6
IEC60947-2 IEC60947-2 IEC60947-2 IEC60947-2 IEC60947-2
1. The breakers with electronic trip units are available only at 3-pole version. (Only for AC supply)
※ The trip unit ATU is available from 125A
21
Molded case circuit breakers
Meta-MEC 30AF to 225AF Series
Frame Size(AF) 30 50
Frame Type ABS ABH ABE ABS ABH
Breaking capacity(kA), Icu at 415VAC 5 10 5 10 25
Number of poles 2, 3 2, 3 2, 3 2, 3, 4 2, 3, 4
Type 2 pole ABS32b ABH32b ABE52b ABS52b ABH52b
3 pole ABS33b ABH33b ABE53b ABS53b ABH53b
4 pole ABS54b
Rated current (A) (3), 5, 10, 15, 20, 30 5, 10, 15, 20, 30 5, 10, 15, 20, 30, 40, 50 15, 20, 30, 40, 50
22
60 100 225
ABE ABS ABE ABS ABH ABE ABS ABH
5 10 10 25 35 18 25 35
2, 3 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4 2, 3, 4
ABE62b ABS62b ABE102b ABS102b ABH102b ABE202b ABS202b ABH202b
ABE63b ABS63b ABE103b ABS103b ABH103b ABE203b ABS203b ABH203b
ABH54b ABS64b ABE104b ABS104b ABH104b ABE204b ABS204b ABH204b
60 5, 10, 15, 20, 30, 15, 20, 30, 40, 50 100, 125, 150, 175, 200, 225
40, 50, 60, 60, 75, 100
75, 100
See table 1 See table 1 See table 2
10 25 25 50 65 35 50 65
7.5 14 14 25 35 18 25 35
5 10 10 25 35 18 25 35
5 10 10 25 35 18 25 35
2.5 7.5 7.5 14 25 10 14 25
2.5 5 5 10 18 7.5 10 18
5 10 10 20 25 15 20 25
2.5 5 5 14 18 10 14 18
50 50 50 50 50 50 50 50
A A A A A A A A
8500 8500 8500 8500 8500 7000 7000 7000
1500 1500 1500 1500 1500 1000 1000 1000
▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
- - - - - - - -
- - - - - - - -
- - - - - - - -
75×130×60 90×155×60 105×165×60
0.45 0.45 0.45 0.7 0.7 1.1 1.1 1.1
0.65 0.65 0.65 1.1 1.1 1.2 1.2 1.2
- 0.85 0.85 1.2 1.2 1.5 1.5 1.5
Table 2.
Amb. Temp. -5℃ 0℃ 10℃ 20℃ 25℃ 30℃ 35℃ 40℃ 45℃ 50℃
Calibrated for 40℃ In=100 to 225A 114.3% 113.2% 110.6% 107.5% 105.8% 140.0% 102.0% 100.0% 97.9% 95.6%
Calibrated for 50℃ In=100 to 225A 116.3% 115.4% 113.2% 110.6% 109.1% 107.5% 105.8% 104.0% 102.0% 100.0%
23
Mold case circuit breakers
Meta-MEC 250AF to 1600AF Series
24
800 1200 1600
ABE ABS ABL GBN(E) GBH(E) ABS ABS(electronic trip) GBN(E)
35 50 85 35 50 65 65 65
2, 3, 4 2, 3, 4 2, 3, 4 3 3 3, 4 3 3
ABE802b ABS802b ABL802b
ABE803b ABS803b ABL803b GBN803E GBH803E ABS1003 ABS1203 ABS1203E GBN1603E
ABE804b ABS804b ABL804b ABS1004 ABS1204
500, 600, 630, 700, 800 800 1000 1200 1200 1600
Interchangeable via rating plug between Electronically adjustable : Electronically adjustable :
500 and 600, 500 and 630, 700 and 800 (0.5-0.6-0.7-0.8-0.9-1.0)×In (0.5-0.6-0.7-0.8-0.9-1.0)×In
See table 3
▲
▲ ▲ ▲ ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● - - ●
- - - - - - - ●
● ● ● ● ● - - ●
● ● ● ● ● ● ● ●
● ● ● ● ● ● ● ●
● ● ● ● ● - - -
- - - - - - - ●
- - - - - - - ●
140×257×113 210×280×113 210×400×105 210×350×142.5
11 11 11 - - - -
11.5 11.5 11.5 11.5 19.4 19.4 23
18.2 18.2 18.2 - 27 - -
25
Air circuit breakers
Susol ACB Series
D
Fixed type 3P 300×300×295
W
4P 300×385×295
Trip relay N, A, P, S type
Certificate & Approval KS / KEMA / KERI / GOST
Marine classiflcation LR, ABS, DNV, KR, BV, GL, RINA, NK
* Refer to trip relay specification. ** �: Standard, �: Option
26
AH-06E AH-08E AH-10E AH-13E AH-16E AH-20E AH-25E AH-32E AH-40E AH-40G AH-50G AH-63G
630 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
630 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
630 800 1000 1250 1600 2000 2500 3200 4000 4000 5000 6300
1,000 1,000
690 690
12 12
50/60 50/60
3, 4 3, 4
100 150
100 150
85 100
100% 100%
220 330
220 330
187 220
85 100
75 100
65 100
40 40
80 80
15,000 10,000
20,000 15,000
5,000 2,000
10,000 5,000
� � �
� � �
� - -
� - -
87/103 104/147 181/223 186/230
85/101 102/145 179/221 184/228
44/55 58/70 97/117 102/124
44/55 63/100 98/123 103/130
42/53 61/98 96/121 101/128
430×412×375 460×785×375
430×527×375 460×1015×375
300×378×295 300×751×295
300×493×295 300×981×295
N, A, P, S type N, A, P, S type
KS / KEMA / KERI / GOST KS / KEMA / KERI / GOST
LR, ABS, DNV, KR, BV, GL, RINA, NK LR, ABS, DNV, KR, BV, GL, RINA, NK
27
Air circuit breakers
Metasol ACB Series
29
Trip relay(OCR)
The trip relay of Susol ACB provides the additional protection functions for voltage, frequency, unbalance, and
others in addition to main protection functions for over current, short-circuit, ground fault. It supports the
advanced measurement functions for voltage, current, power, electric energy, harmonics, communication
function, and others.
Analog trip function interlocked with mechanism enhanced a durability of devices as well as the breaking
capacity of ACB.
Zone selective interlocking function makes the protective coordination more simple and thermal memory can
be applied to various loads.
Trip relay types
Externals
31
Vacuum Circuit Breakers
Susol VCB Series
32
Accessories
Dimensions Main Cradle
E type F type
• No Shutter • Insulation Shutter
• For MESG • For MESG
G type H type
• Bushing • Bushing
34
� For your safety, please read user's manual thoroughly before operating.
� Contact the nearest authorized service facility for examination, repair, or adjustment.
� Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Safety Instructions � Any maintenance and inspection shall be performed by the personnel having expertise concerned.
www.lsis.biz
2009. 07 LOW VOLTAGE CIRCUIT BREAKERS & CONTACTORS(E) 2004. 02/(22) 2009. 07 Printed in Korea STAFF