DOBLE TDR9000 - Spec
DOBLE TDR9000 - Spec
DOBLE TDR9000 - Spec
TDR9000
Circuit Breaker
Test System
Benefits
• Accurate measurement of grading capacitors capacitance values, and
insertion resistor resistance values – built-in, precision measurements
for grading capacitors and insertion resistors testing eliminates the need
for separate measuring instruments. No other product on the market can
match the TDR9000 in this capability.
• Immune to Interference – accuracy of test results is unaffected
Identification by severe conditions of electrostatic and electromagnetic inter-
ference, present in harsh substation environments.
Breaker Performance Report
TDR9000 Version: RE 4.01 • Modular Design – customize the system to match present
Manufacturer :A.B.C. Electric Location : Webster Circuit testing requirements; field upgrade the system as required,
Model Number: 1234-GW-10000 Circuit : 45678
Serial Number : 1-38Y1740
Instr Book # : 33-123-C3
Operator : You to protect the capital investment.
Mechanism # :
Mech Instr # :
Special ID : 02472 Operation Counter : 696
• High Accuracy Motion Recording – a patented digital rotary
Test Type
:
: TRIP Test Plan Name :
:
and linear transducer provides early diagnosis of mechanical
problems, auxiliary switch and main contact timing errors.
Test was performed on 03/30/2004 at 13:09:10.
• Rugged and Reliable – the TDR9000 is a single box solution,
Motion Channels 1-3 Transfer Function
1.000 in Travel at the contacts is 1.000 in Travel at the transducer. providing the accuracy of a laboratory instrument with
Command Parameters Trip Pulse 4.00 cy Close Pulse 95.50 cy durability for field use.
Delay 1 0.50 cy (Standing)
Command Currents Trip Current 16.55 A pk Close Current 0.72 A pk • Self-Diagnostics – self-diagnostics on demand ensures accurate
and valid test results.
• User-friendly PC interface – an intuitive control panel on
your PC provides quick, efficient and simple testing of circuit
Test Tabulation breakers.
OCB Contact Timing
Reclose Operation • Comprehensive Testing – accurately measures all essential
Reclose Dead Time Within a Phase parameters of a circuit breaker in a single test for accurate
Specifications Test Results Compare
diagnostics of the circuit breaker operation.
Maximum 16.50 cy Phase A 16.92 cy Fail
Minimum Phase B 16.81 Fail
Phase C 16.72 Fail
TRX™ Software
The Windows based TRX software controls the TDR9000 and stores test results and
test plans. TRX Software uses an industry standard SQL compliant client server
database architecture.
For ease of analysis, TRX displays test data and test results in tabular or graphical
form. Time-related information such as travel, velocity, contact transition, trip
and/or close coil currents, analog and auxiliary contact channels are displayed
graphically. TRX Software organizes Circuit Breaker Test Plans and test types by
user-defined regions, locations, substations, manufacturers, models and serial
numbers along with the historical results. Both the reliability of the system and
productivity of test personnel is improved.
TRXField, an independent component of TRX Software, quickly allows Test Plan
creation, switching device Testing and Test Result analysis. The operator can specify
expected results. The software compares the actual test results with the user
defined expected test results to make a pass or fail determination.
TDR9000
TDR9000 Control Panel Operations
Efficient operational Circuit Breaker TDR control circuit breaker trip and
verification is accomplished with the close commands allow the user to per-
TDR9000 Control Panel. This user- form these operations:
friendly PC interface allows an Trip (O)
operator to configure the TDR9000 Close (C)
for testing via a simple point and click Reclose (O-C)
mouse operation. The TDR9000 Tripfree (O-C)
Control Panel’s intuitive controls allow O-C-O
circuit breaker testing without the need First Trip (O)
for an elaborate test plan. Test results First Close (C)
such as contact timing and instanta- Slow Close (C)
neous velocity and displacement, can Continuity
be displayed graphically for instant Capacitance
analysis, while an optional 8.5 inch Self Diagnostics
thermal printer, provided with the
Identify your selection in a test plan
TDR9000, prints out the test results
by using the control panel.
for a paper record. A test created in the
TDR9000 Control Panel can be saved
for future use on the PC.
Knowledge Is Power SM
MKT-SL-TDR9000B 12/05