User's Manual: EJX Series BRAIN Communication Type
User's Manual: EJX Series BRAIN Communication Type
User's Manual: EJX Series BRAIN Communication Type
Manual
BRAIN Communication Type
IM 01C25T03-01E
IM 01C25T03-01E
3rd Edition
Yokogawa Electric Corporation
CONTENTS
CONTENTS
FD No. IM 01C25T03-01E
3rd Edition: Aug. 2009 (KP) i IM 01C25T03-01E
All Rights Reserved, Copyright © 2004, Yokogawa Electric Corporation
CONTENTS
REVISION RECORD
ii IM 01C25T03-01E
1. INTRODUCTION
1. INTRODUCTION
Thank you for purchasing the DPharp EJX electronic • Please note that changes in the specifications,
pressure transmitter. construction, or component parts of the instrument
may not immediately be reflected in this manual at
EJX pressure transmitters are precisely calibrated at the
the time of change, provided that postponement of
factory before shipment. To ensure both safety and
revisions will not cause difficulty to the user from a
efficiency, please read this manual carefully before
functional or performance standpoint.
operating the instrument.
This manual describes the BRAIN protocol communi- • The following safety symbols are used in this
cation functions of the EJX series and explains how to manual:
set the parameters for EJX series pressure transmitters
using the BT200 handheld terminal. For information on
the installation, wiring, and maintenance of EJX series WARNING
pressure transmitters, please refer to the user’s manual Indicates a potentially hazardous situation which,
of each model. if not avoided, could result in death or serious
injury.
WARNING
1-1 IM 01C25T03-01E
1. INTRODUCTION
1-2 IM 01C25T03-01E
1. INTRODUCTION
1-3 IM 01C25T03-01E
1. INTRODUCTION
SK PL
CZ
SLO
LT H
BG
LV
EST RO
1-4 IM 01C25T03-01E
2. CONDITIONS OF COMMUNICATION LINE
2. CONDITIONS OF COMMUNICATION
LINE
The BRAIN communication signal is superimposed 2.3 Power Supply Voltage and
onto the 4 to 20 mA DC analog signal. Since the
modulated wave is a communication signal, superim- Load Resistance
posing it on the normal signal will, from basic prin- When configuring the loop, make sure that the external
ciples, cause no error in the DC component of the load resistance is within the range in the figure below.
analog signal. Thus, monitoring can be performed via
(Note) With an intrinsically safe transmitter, external load resistance
the BT200 while the transmitter is on-line. includes safety barrier resistance.
SUPP
LY
CHECK
ALARM
Control room
Relaying
terminals Terminal board
0 10.5 16.6 25.2 42
Power supply voltage E (V DC)
F0203.EPS
Distributor
Figure 2.3 Relationship between Power Supply Voltage
and External Load Resistance
F0201.EPS
Cable resistance Rc
Power
cc
supply
2-1 IM 01C25T03-01E
3. OPERATION
3. OPERATION
The DPharp is equipped with BRAIN communications MENU SCREEN
Messages
MENU BATTERY
capabilities, so that range changes, Tag No. setup, A:DISPLAY
B:SENSOR TYPE
monitoring of self-diagnostic results, and zero point C:BASIC SETUP
Menu choices
D:AUX SET1
adjustment can be handled remotely via the BT200 Screen title E:AUX SET2
G:ALARM SET
BRAIN TERMINAL or the CENTUM CS console. HOME SET ADJ ESC
LCD
(21 characters × 8 lines)
Function keys
Movement keys
ENTER key
Alphanumeric keys
Shift keys
F0301.EPS
3-1 IM 01C25T03-01E
3. OPERATION
3.1.2 Operating Key Functions Use the function key [F1] CODE to enter symbols. The
following symbols will appear in sequence, one at a
(1) Alphanumeric Keys and Shift Keys time, at the cursor each time [F1] CODE is pressed:
Use the alphanumeric keys in conjunction with the
/ . – , + * ) ( ’ & % $ # ” !
shift keys to enter numbers, symbols, and alphabetic
To enter characters next to these symbols, press [ > ] to
characters.
move the cursor.
symbol command
Alphanumeric keys l/m
(I) (/) (m)
T0303.EPS
Letter on left side of Letter on right side of CAPS/caps Selects uppercase or lowercase
the alphanumeric key the alphanumeric key CODE Selects symbols
CLR Erases input data or deletes all data
F0304 .EPS
DATA Updates parameter data
Entry Key-in sequence DEL Deletes one character
W DIAG Calls the self-check panel
ESC Returns to the most recent display
IC
HOME Displays the menu panel
J. B
NO Quits setup and returns to the previous display
T0302.EPS
Use the function key [F2] CAPS to select uppercase OK Proceeds to the next panel
and lowercase (for alphabetic characters only). The PARM Enters the parameter number setup mode
case toggles between uppercase and lowercase each SET Displays the SET menu
time [F2] CAPS is pressed. SLOT Returns to the slot selection panel
UTIL Calls the utility panel
3-2 IM 01C25T03-01E
3. OPERATION
UTILITY SCREEN
––WELCOME–– UTILITY The utility screen contains the
BRAIN TERMINAL 1.ID following items.
ID: BT200 2.SECURITY CODE
STARTUP 3.LANGUAGE SELECT 1. BT200 ID settings
SCREEN check connection 4.LCD CONTRAST 2. Security code settings
push ENTER key 5.PRINTER ADJUST
3. Switching language of messages
UTIL FEED esc (Japanese or English)
4. LCD contrast setting
5. Adjusting printout tone
(UTIL)
(BT200-P00 only)
PARAM
01:MODEL
EJX110A-DM FUNCTION SCREEN
INITIAL 02:TAG NO. FUNC
DATA YOKOGAWA 1.MENU
SCREEN 03:SELF CHECK (ESC) 2.UPLOAD TO HHT
GOOD 3.DOWNLOAD TO INST
OK 4.PRINT ALL DATA
(SET) (ADJ)
(HOME MENU SCREEN) (SET MENU SCREEN) (ADJ MENU SCREEN)
MENU MENU MENU
A:DISPLAY C:BASIC SETUP J:ADJUST
B:SENSOR TYPE D:AUX SET 1 K:TEST
MENU C:BASIC SETUP E:AUX SET 2 M:DEVICE INFO
SCREEN D:AUX SET1 G:ALARM SET P:RECORD
E:AUX SET2 H:AUTO SET T:CHARACTERIZR
G:ALARM SET I:DISP SET
HOME SET ADJ ESC HOME SET ADJ ESC HOME SET ADJ ESC
SET See the BT200 user’s manual for details concerning uploading
C10:TAG NO. and downloading parameters and printouts (BT200-P00).
SETUP YOKOGAWA
SCREEN YOKOGAWA
3.1.4 Printout (for BT200 printer option) (2) Printout by Menu Item
To printout the parameters for a specific screen, push
(1) Printout of All Parameters the function key corresponding to screen’s PRINT.
Select 4. PRINT ALL DATA from the function screen
to output a list of all parameters. It takes about
10 minutes to complete the printout.
3-3 IM 01C25T03-01E
3. OPERATION
3-4 IM 01C25T03-01E
3. OPERATION
SET
C: BASIC SETUP D: AUX SET 1 E: AUX SET2 G: ALARM SET H: AUTO SET I: DISP SET
C10: TAG NO. D10: LOW CUT E10: T. ZERO CMP G10: P AL MODE H10: AUTO P LRV I10: DISP OUT1
C20: PRES UNIT D11: LOW CUT MODE E11: TEMP ZERO G11: P HI. AL VAL H11: AUTO P URV I11: DISP OUT2
C21: PRES LRV D15: H/L SWAP*1 E30: BI DIRE MODE G12: P LO. AL VAL H20: AUTO SP LRV*1 I12: DISP OUT3
C22: PRES URV D16: H2O UNIT SEL E50: DO SELECT G20: SP AL MODE*1 H21: AUTO SP URV*1 I13: DISP OUT4
C23: PRES POINT D20: OUT LIMIT(L) E51: DO SIG.TYPE G21: SP HI. AL VAL*1 H60: SELF CHECK I20: P DISP MODE
C30: AMP DAMPING D21: OUT LIMIT(H) E52: D OUTPUT G22: SP LO. AL VAL*1 I21: PRES % RESO
C40: OUTPUT MODE D22: REV OUTPUT E60: SELF CHECK G30: T AL MODE I30: ENGR. UNIT
C60: SELF CHECK D25: BURNOUT G31: T HI. AL VAL I31: EASY EU SET
D26: ERROR OUT G32: T LO.AL VAL I32: ENGR. EXP
D30: SP UNIT*1 G50: AUTO RECOVER I33: ENGR. LRV
D31: SP A/G SLCT*1 G60: SELF CHECK I34: ENGR. URV
D32: ATM. PRESS*1 I35: ENGR. POINT
D33: SP LRV*1 I40: BAR INDICATR
D34: SP URV*1 I60: SELF CHECK
D35: SP POINT*1
D36: SP DAMPING*1
D37: SP SELECT*1
D40: TEMP UNIT
D50: QUICK RESP
D55: WRT PROTECT
D56: WRT ENABLE
D57: NEW PASSWORD
D58: SOFTWR SEAL
D60: SELF CHECK
ADJ
J09: ADJ UNIT K10: OUTPUT X % M10: SERIAL NO. P10: ERROR REC 1 T10: S. C. ENABLE
J10: ADJ PRES K40: DO TEST M11: MFTR. DATE P12: ERROR REC 2 T11: NUM OF POINT
J11: P ZERO ADJ K50: TEST KEY1 M12: EXTRA NO. P14: ERROR REC 3 T20: X START (FIX)
J12: P SPAN ADJ K51: TEST KEY2 M15: SOFT REV P16: ERROR REC 4 T21: Y START (FIX)
J15: P ZERO DEV K52: TEST KEY3 M16: BRAIN REV P50: REC CLEAR T22: X1
J16: P SPAN DEV K53: TEST KEY4 M17: MEMO1 P60: SELF CHECK T23: Y1
J20: ADJ SP*1 K60: SELF CHECK M18: MEMO2 T24: X2
J21: SP ZERO ADJ*1 M19: MEMO3 T25: Y2
J22: SP SPAN ADJ*1 M20: ISOL MATL T26: X3
J25: SP ZERO DEV*1 M21: FILL FLUID T27: Y3
J26: SP SPAN DEV*1 M22: GASKET MATL T28: X4
J40: OUTPUT 4mA M23: PRO CON MATL T29: Y4
J41: OUTPUT 20mA M24: D-VENT MATL T30: X5
J45: AMP TEMP M25: PRO CON TYPE T31: Y5
J50: ADJ WHO M26: RS ISOL MATL T32: X6
J51: ADJ DATE M27: PRO CON SIZE T33: Y6
J52: ADJ LOC M28: NUM RS T34: X7
J53: ADJ DESC M29: RS FILL FLID T35: Y7
J55: EXT ZERO ADJ M30: RS TYPE T36: X8
J56: CLEAR ADJ M50: MS CODE 1 T37: Y8
J60: SELF CHECK M51: MS CODE 2 T38: X9
M52: MS CODE 3 T39: Y9
M53: MS CODE 4 T40: X END (FIX)
M54: MS CODE 5 T41: Y END (FIX)
M55: MS CODE 6 T60: SELF CHECK
M60: SELF CHECK
F0300.EPS
*1: Available for differential pressure transmitter.
3-5 IM 01C25T03-01E
3. OPERATION
F0309.EPS
––WELCOME––
BRAIN TERMINAL
Connect DPharp and BT200 using (2) Calibration Range Setup
ID: BT200 a communication cable and press
check connection the key. a. Setting Calibration Range Unit
push ENTER key
(C20: PRES UNIT)
UTIL FEED
The unit parameter is set at the factory before shipment
PARAM Displays the name of connected
01:MODEL
EJX110 M DPharp model, TAG NO. and
if specified at the time of order. Follow the procedure
02:TAG NO.
YOKOGAWA diagnostics information. Press the below to change the unit parameter.
03:SELF CHECK
GOOD (OK) key after confirmation.
OK
MENU Press the (SET) key to • Example: Change the unit from mmH2O to kPa.
A:DISPLAY
B:SENSOR TYPE display the SET menu panel.
C:BASIC SETUP
D:AUX SET1 SET Use the or
E:AUX SET2 C20:PRES UNIT
mmH2O
G:ALARM SET
< mmWG > key to select kPa.
HOME SET ADJ ESC < mmHg >
< Torr > Press the key twice
MENU Select C: BASIC SETUP and press < kPa >
C:BASIC SETUP ESC to enter the setting.
D:AUX SET 1 the key.
E:AUX SET 2
G:ALARM SET SET
H:AUTO SET C20:PRES UNIT Press the (OK) key.
I:DISP SET kPa
HOME SET ADJ ESC
MENU
C10:TAG NO.
Select C10: TAG NO. and press
FEED NO OK
YOKOGAWA the key.
C20:PRES UNIT
kPa
C21:PRES LRV F0310.EPS
0.00000 kPa
DATA DIAG PRNT ESC
Note that the Yokogawa default setting for the standard
SET Set the new TAG NO. (FI1-1a). temperature is 4C (39.2F). For the units of mmH2O,
C10:TAG NO.
YOKOGAWA FOKOGAWA
YOKOGAWA mmAq, mmWG, inH2O, and ftH2O, the pressure varies
FIKOGAWA
according to the standard temperature definition. When
FI1OGAWA
CODE CAPS CLR ESC
a standard temperature of 20C (68F) is required,
FI1-GAWA
select @20degC (68.0F) at the parameter of D16:H2O
FI1-1AWA
UNIT SEL.
FI1-1aWA
FI1-1a
Available pressure units are shown below.
SET Set TAG NO. and press the
C10:TAG NO.
YOKOGAWA key. mmH2O MPa inHg
FI1-1a _
mmAq mbar ftH2O
mmWG bar psi
CODE caps CLR ESC
mmHg gf/cm2 atm
Torr kgf/cm2 Pa
When you have made an entry mistake, return kPa inH2O hPa
the cursor using the key, then reenter. FX0301.EPS
F0308.EPS
3-6 IM 01C25T03-01E
3. OPERATION
Span = Upper range value – Lower range value • Example: Change from 2.00 sec to 4.00 sec.
F0311.EPS SET
C30:AMP DAMPING Enter 4.
2.00 sec
Press the key twice to
• Entering the range values as LRV>URV reverses the + 004.00
enter the setting.
direction of the output signal of 4-20 mA to 20-4 mA
CLR ESC
corresponding to the calibration range of 0 to 100%.
• Calibration range can be specified with range value SET
C30:AMP DAMPING Press the (OK) key.
4.00 sec
specifications up to 5 digits (excluding any decimal
point) for lower or upper range limits within the
range of –32000 to 32000. FEED NO OK
Note 2: When the damping time constant is set to less than 0.5
second, communication may occasionally be unavailble
during the operation, especially while output changes
dynamically.
3-7 IM 01C25T03-01E
3. OPERATION
(4) Output Mode and Integral Indicator Dis- (5) Output Signal Low Cut Mode Setup
play Mode Setup (C40: OUTPUT MODE, (D10: LOW CUT, D11: LOW CUT MODE)
I20: P DISP MODE) Low cut mode can be used to stabilize the output
The mode setting for the output signal and the integral signal near the zero point. The low cut point can be set
indicator can be performed independently. in a range from 0 to 20%, the direct ratio correspond-
This mode is set as specified in the order when the ing to the output signal of 4 to 20 mA. (Hysteresis:
instrument is shipped. Follow the procedure below to ±10% of the cut point)
change the mode. Either LINEAR or ZERO can be selected as the low
If the instrument is equipped with an integral indicator cut mode. Unless otherwise specified, the cut mode is
and the display mode is SQUARE ROOT, “ ” is set to LINEAR at the factory.
displayed on the integral indicator. Note that when the output modes of the output signal
• Output mode for 4-20 mA output and the integral indicator are selected as SQUARE
ROOT and LINEAR accordingly, the low cut function
is not available for the integral indicator display.
• Example: Set output mode from Linear to
Square root.
SET Use the or key • Example: Change the low cut setting range
C40:OUTPUT MODE
LINEAR
to select SQUARE ROOT. from 10% to 20%, and the low
< LINEAR >
< SQUARE ROOT >
Press the key twice to
cut mode from LINEAR to ZERO in
the SQUARE ROOT output mode.
ESC enter the setting.
SET Low cut mode “LINEAR” Low cut mode “ZERO”
C40:OUTPUT MODE Press the (OK) key.
SQUARE ROOT
(%) (%)
50 50
FEED NO OK
Output
F0314.EPS
FEED NO OK
PARAM
D10:LOW CUT
20.0 %
D11:LOW CUT MODE
ZERO
D15:H/L SWAP
NORMAL
DATA DIAG PRNT ESC
F0317.EPS
3-8 IM 01C25T03-01E
3. OPERATION
The low cut point has hysteresis so that the output (6) Integral Indicator Scale Setup
around the point is behaved as below figure. The following five displays are available for integral
indicators: input pressure*1, % of range, user set scale,
<Example>
input static pressure, and % of static pressure range*1.
Output mode: Linear
A cycle of up to four displays can be shown by
Low cut mode: Zero
assigning variables to the parameters I10 to I13: DISP
Low cut: 20.00%
OUT1 to DISP OUT4.
Output Low cut point
7.2mA Description
Available displays
(20%) and related parameters
Input pressure Indicates values of input pressure
4mA (PRES) with the indication limits 32000 to
Input 2% 2%
32000.
Setting range: 0 to 20% A11:PRES
Hysteresis
456 kPa
fixed at 10%
of the cut point
F0317-02.EPS
T0306.EPS
*1: Available for differential pressure transmitter.
3-9 IM 01C25T03-01E
3. OPERATION
b. Cyclic Display
(I11: DISP OUT2, I12: DISP OUT3, and I13: • Example: Set lower range value (LRV) to –50
DISP OUT4) and upper range value (URV) to 50.
In addition to the display set at I10: DISP OUT1,
Setting LRV
displays can be set at I11: DISP OUT2, I12: DISP SET Set –50.
I33:ENGR.LRV
OUT3, and I13: DISP OUT4 for cyclic display in the 0.00 M
- 50 Press the key twice to
order of the parameter number.
enter the setting.
DEL CLR ESC
c. User Setting of Engineering Unit and Scale
(I30: ENGR.UNIT, I31: EASY EU SET, I33: SET Press the (OK) key.
I33:ENGR.LRV
ENGR.LRV, and I34: ENGR.URV) - 50 M
mmWG l/h mm
F0320.EPS
Torr l/min in
inH2O kl/h ft
inHg kl/min kg/m3
inHgA Nl/h g/cm3
FX0302.EPS
3-10 IM 01C25T03-01E
3. OPERATION
d. Setting Static Pressure Unit and Scale (9) Impulse Line Connection Orientation
(D30: SP UNIT, D33: SP LRV, and D34: SP Setup (D15: H/L SWAP)
URV) This function reverses the impulse line orientation.
Static pressure can be displayed in measured input Follow the procedure below to make this change.
static pressure or in %, independent from the 4-20 mA
output signal of measured pressure or differential
pressure. These parameters allow the entry of the static • Example: Assign the high pressure impulse
pressure unit and scale to be displayed. line connection to the L side of
the transmitter.
Note that the parameter D37: SP SELECT can be used
SET Use the or key
to select either the high or low pressure side of the D15:H/L SWAP
NORMAL
to select REVERSE.
capsule to monitor the static pressure. < NORMAL >
< REVERSE>
Press the key twice to
(7) Unit Setup for Displayed Temperature ESC
enter the setting.
(D40: TEMP UNIT) Then press the (OK) key.
When the instrument is shipped, the temperature units
are set to degC. Follow the procedure below to F0323.EPS
3-11 IM 01C25T03-01E
3. OPERATION
SET
D57:NEW PASSWORD Press the (OK) key.
• Example: Standard specifications 1234ABCD
Then status of parameter D55:
D25: BURNOUT Slide switch position: H WRT PROTECT becomes YES.
HIGH
FEED NO OK
(11) Software Write Protect (D55: WRT PRO- • Example: Enter the password of 1234ABCD.
TECT, D56: WRT ENABLE, D57: NEW
SET Enter the password.
PASSWORD) D56:WRT ENABLE
Press the key twice
EJX configured data can be saved by the write protect 1234ABCD
to enter the setting.
function. Write protect status (D55: WRT PROTECT)
CODE CAPS CLR ESC
is set from NO to YES when eight alphanumerics are
SET
entered in the parameter of D57: NEW PASSWORD. D56:WRT ENABLE Press the (OK) key.
PASS
Accordingly, the transmitter does not accept any Parameter changes are available
parameter changes. When the eight alphanumeric for 10 minutes.
FEED NO OK
password is entered in the parameter of D56: WRT
ENABLE, the transmitter accepts parameter changes F0341.EPS
during a 10 minute period.
To cancel the transmitter for the software write c. Releasing Password
(D57: NEW PASSWORD)
protection completely, use D56: WRT ENABLE to
first release the write protect function and then enter To release the password, enter eight spaces at D57:
eight spaces in the D57: NEW PASSWORD field. NEW PASSWORD during the period that the param-
eter change is possible.
The software write protection does not affect the
function of external zero adjustment screw. d. Software Seal
(D58: SOFTWR SEAL)
To disable the external zero adjustment screw, set the
When you lose the password that has been registered, it
parameter of J15: EXT ZERO ADJ to INHIBIT before
is possible to release the write protect function by
activating the software write protection.
using general password, “YOKOGAWA.” When the
password is used, the status shown in the parameter of
D58: SOFTWR SEAL is changed from KEEP to
BREAK. The status returns to KEEP by entering a
newly set password at D56: WRT ENABLE.
3-12 IM 01C25T03-01E
3. OPERATION
F0329.EPS
a. Zero Trim
(J11: P ZERO ADJ, J15: P ZERO DEV,
J55: EXT ZERO ADJ)
The DPharp supports several adjustment methods.
Select the method best suited for the conditions of your
application.
3-14 IM 01C25T03-01E
3. OPERATION
A11:PRES Transmitter measures pressure of Note that the parameter of J55: EXT ZERO ADJ must
0.03585 kPa
0.03585 kPa. be ENABLE to perform this adjustment.
SET
A pressure of 0 kPa is applied. Follow the procedure below to enable or inhibit zero
J11:P ZERO ADJ
+
0.00000 kPa
0 Press the key twice
point adjustment from the zero-adjustment screw on
the transmitter.
after the pressure has become
DEL CLR ESC stable.
This is set to ENABLE when the instrument is
SET
shipped.
J11:P ZERO ADJ Zero adjustment is completed.
0.00000 kPa
Press the (OK) key.
• Example: Inhibiting zero adjustment by the
FEED NO OK external zero-adjustment screw.
A11:PRES Transmitter measures pressure of SET Use the or key to
0.00000 kPa J55:EXT ZERO ADJ
0.00000 kPa. ENABLE
< ENABLE > select INHIBIT.
< INHIBIT>
Press the key twice to
F0331.EPS
ESC
enter the setting.
Then press the (OK) key.
a-2. Level Adjustment
The zero adjustment by the parameter of J11: P ZERO F0335.EPS
• Example: For the range of 10 to 30 kPa. • Example: For the range of 10 to 30 kPa.
Setting a lower point
J15: P ZERO DEV = 0.04 kPa
SET Transmitter indicates 9.94 kPa as J16: P SPAN DEV = 0.03 kPa
J10:ADJ PRES
9.94000 kPa
its output when applying a standard
Suppose that a standard pressure of 10 kPa is applied and
pressure of 10 kPa. the value of the parameter of J10: ADJ PRES is 9.94 kPa.
ESC Correct for this output error of 0.06 kPa by adding 0.06 to
J15: P ZERO DEV.
SET Set 10.
J11:P ZERO ADJ
+
9.94000 kPa
10 After obtaining a stable pressure of 0.040.06=0.02
FEED NO OK
ESC
FEED NO OK
SET
J16:P SPAN DEV
Set 0.13.
SET
J10:ADJ PRES
Check the output becomes 30 kPa. -0.03000 kPa
30.0000 kPa - 0.13 Press key twice.
FEED NO OK
F0352.EPS
3-16 IM 01C25T03-01E
3. OPERATION
c. Sensor Trim for Static Pressure (16) Test Output Setup (K10: OUTPUT X %)
(J21: SP ZERO ADJ, J22: SP SPAN ADJ, This feature can be used to output a fixed current for
J25: SP ZERO DEV, J26: SP SPAN DEV)
loop checks. The available range for test output
For the EJX differential transmitters (Except for
depends on the setting at parameters of D20 OUT
EJX120A), zeroing and full sensor trim of the static
LIMIT (L) and D21 OUT LIMIT (H), whose limit is
pressure is performed in the same way as with the
from 3.6 mA (–2.5%) to 21.6 mA (110%).
primary process variable (PV). Note that the static
pressure sensor trim should be done only after trim-
ming the PV. • Example: Output 12 mA (50%) fixed current.
F0336.EPS
• Example: Reset the trim adjustment of pressure
to factory set characterization curve.
SET Use the or key IMPORTANT
J56:CLEAR ADJ
---
to select PRES.
< ---
< PRES
>
>
1. Test output continues for approximately 10
< SP > Press the key twice to minutes, then is released automatically. Even if
< 4-20mA >
ESC enter the setting. the BT200 power supply is turned off or the
SET Press the (OK) key. communication cable is disconnected, test
J56:CLEAR ADJ
--- output will continue for approximately 10
minutes.
FEED NO OK
2. Press the (OK) key to release test output
immediately.
F0353.EPS
3-17 IM 01C25T03-01E
3. OPERATION
PARAM
T21:Y
0.00%
(19) Status Output (option code AL)
T22:X1
12.00% This feature is used for a transistor output (open
T23:Y1
14.00% collector) of an on/off signal according to the status of
DATA DIAG PRNT ESC
high and low alarm limits, which are user-configurable
F0345.EPS
values as shown in (18) Process Alarm. The status
output can be assigned as any combination of the high
or low limits of the input pressure, input static pres-
• Example: Set the signal characterizer ENABLE.
sure, or capsule temperature.
SET Use the or key
T10:S.C.ENABLE
INHIBIT
< INHIBIT> to select ENABLE.
< ENABLE >
Press the key twice to CAUTION
ESC activate the function.
Execute DO testing by the parameter "K40 DO
SET
T10:S.C.ENABLE
ENABLE
Press the (OK) key. test" whenever turning on the transmitter or
detecting the short interruption in order to check
that the alarm contact output is correctly config-
FEED NO OK
ured.
F0343.EPS
3-18 IM 01C25T03-01E
3. OPERATION
No status output signal has been defined for a Status output for higher alert value
CPU failure or hardware error. Use a 4-20 mA Output
5%* of hysteresis
signal to indicate a transmitter’s failure. (%)
(5C for heat)
Setting
value
Setting
FEED NO OK value
5%* of hysteresis
SET Use the or key (5C for heat)
E51:DO SIG.TYPE
ON WHEN ALARM
< ON WHEN ALARM > to select OFF WHEN ALARM.
< OFF WHEN ALARM >
Press the key twice to On Time (t)
ESC enter the setting.
SET
Status output
E51:DO SIG.TYPE Press the (OK) key. On Off
OFF WHEN ALARM F0350.EPS
F0354.EPS
3-19 IM 01C25T03-01E
3. OPERATION
SET
(2) Zero Shift Compensation Setup E11:TEMP ZERO Press the (OK) key.
-0.149 %/degC
(E11: TEMP ZERO)
Obtain the K compensating value from the equa-
tion(1) below. FEED NO OK
Span
Note 1: The function is performed using in a built-in temperature
where, sensor in the transmitter body. The temperature deviation
B: Constant value of fill fluid (See Table A.) between the transmitter body and capillaries should be
minimized to achieve optimal performance of the function.
span: |URV–LRV| Note 2: When the span changes, reenter the newly obtained value of
K to E11: TEMP ZERO.
h: Distance from high pressure side to low
pressure side (m)
Table A. Constant value [B] of fill fluid
EJX118A: Distance from high side of Fill fluid A, C B D E
diaphragm seal to low side of diaphragm seal. code
mmH2O 0.76 0.87 1.45 0.75
Constant value [B]
EJX438A: Distance from diaphragm seal (high kgf/cm2 0.000076 0.000087 0.000145 0.000075
kPa 0.00745 0.00853 0.01422 0.00736
side) to position of transmitter (low side).
mBar 0.07453 0.08532 0.14220 0.07355
atm 0.000074 0.000084 0.000140 0.000073
inH2O 0.02992 0.03425 0.05709 0.02953
psi 0.00108 0.00124 0.00206 0.00167
mmHg 0.05592 0.06401 0.10669 0.05518
T0308.EPS
Note 3: Select the unit of constant value of [B] from the actual unit
used for the transmitter in operation.
3-20 IM 01C25T03-01E
3. OPERATION
(21) Adjustment Information and User Memo 3.3 Displaying Data Using the
Fields (J50: ADJ WHO, J51: ADJ DATE,
J52: ADJ LOC, J53: ADJ DESC, M17 to BT200
M19: MEMO1 to MEMO3)
This feature provides four fields for instrument 3.3.1 Displaying Measured Data
adjustment information at maintenance: inspection
date, inspector, location, and description. Also three The BT200 can be used to display measured data.
user memo fields are provided, each holding up to 16 The measured data is updated automatically every
alphanumeric characters. seven seconds. In addition, the display can be updated
to the present data value at any time by pressing the
(DATA) key. For parameters associated with the
• Example: Save an inspection date of October
display of measured data, see chapter 5 Parameter
21, 2003.
Summary.
PARAM
J50:ADJ WHO
Set “10-21-2003” in the order of
J51:ADJ DATE month, day, and year. • Example: Display output.
J52:ADJ LOC Press the key twice to
MENU
DATA DIAG PRNT ESC A:DISPLAY
enter the setting. B:SENSOR TYPE
SET C:BASIC SETUP
J51:ADJ DATE D:AUX SET1
MM-DD-YYYY E:AUX SET2
10-21-2003 G:ALARM SET
HOME SET ADJ ESC
F0338.EPS
PARAM
B10:MODEL For the associated
EJX110 M parameters, see Chapter 5,
B11:STYLE NO. Parameter Summary.
1.00
B20:PRES LRL
– 98.07 kPa
DATA DIAG PRNT ESC
F0339.EPS
3-21 IM 01C25T03-01E
4. SELF-DIAGNOSTICS
4. SELF-DIAGNOSTICS
4.1 Checking for Problems • Example 3: Checking the history of the errors
• Example 1: Connection errors P10: “ERROR REC 1” displays the last error.
P12: “ERROR REC 2” displays the error one time before
––WELCOME––
BRAIN TERMINAL
Press the key.
ID: BT200 the last error occurred.
When the panel shown on the left
check connection P14: “ERROR REC 3” displays the error two times before
push ENTER key appears, press the key. the last error occurred.
UTIL FEED
P16: “ERROR REC 4” displays the error three times before
Since communications will be the last error occurred.
communication error unsuccessful if there is a problem The history of up to four errors can be stored. When the 5th
in the connection to the BT200, the error has occurred, it is stored in “P10.” The error stored in
ESC display at the left will appear. “P16” will be deleted, and then, the error in “P14” will be
Recheck the connection. copied to “P16.” In this sequence, the history of the most
previously occurred error will be removed from memory.
Press the (OK) key.
“GOOD” will be displayed if there was no previous error.
4-1 IM 01C25T03-01E
4. SELF-DIAGNOSTICS
NOTE
F0403.EPS
4-2 IM 01C25T03-01E
4. SELF-DIAGNOSTICS
AL. 10 10: P OVER SPEC Input is outside measurement Outputs upper range limit (URL) Check input or replace
PRESS range limit of capsule. or lower range limit (LRL). capsule when necessary.
AL. 11 11: SP OVER SPEC Static pressure exceeds Continues to operate and
ST. PRSS limit. output.
AL. 12 12: CT OVER SPEC Capsule temperature is outside Use heat insulation or
CAP. TMP range (–50 to 130°C). make lagging to keep
temperature within
AL. 13 13: AT OVER SPEC Amplifier temperature is outside range.
AMP. TMP range (–50 to 95°C).
AL. 30 30: P OVER RANGE Output is outside upper or lower Outputs upper range value Check input and range
RANGE range limit value. (URV) or lower range value setting, and change
(LRV). them as needed.
AL. 31 31: SP OVER RANGE Static pressure exceeds Continues to operate and
SP. RNG specified range. output.
AL. 35 35: P HIGH ALARM Input pressure exceeds specified Check input.
P. HI threshold.
AL. 36 36: P LOW ALARM
P. LO
AL. 37 37: SP HIGH ALARM Input static pressure exceeds
SP. HI specified threshold.
AL. 38 38: SP LOW ALARM
SP. LO
AL. 39 39: CT HIGH ALARM Detected temperature exceeds Check capsule
TMP. HI specified threshold. temperature.
AL. 40 40: CT LOW ALARM
TMP. LO
AL. 50 50: P ILLEG LRV Specified value is outside of Holds output immediately Check settings and change
P. LRV setting range. before error occurred. them as needed.
AL. 51 51: P ILLEG URV
P. URV
AL. 52 52: P ILLEG SPAN
P. SPN
AL. 53 53: P SPAN ADJ Continues to operate and Adjust settings and
P. ADJ output. change them as needed.
53: P ZERO ADJ
AL. 54 54: SP ILLEG LRV Continues to operate and Check settings and change
SP. RNG output holding static them as needed.
54: SP ILLEG URV
pressure in %.
54: SP ILLEG SPAN
AL. 55 55: SP SPAN ADJ Continues to operate and Adjust settings and
SP. ADJ output. change them as needed.
55: SP ZERO ADJ
AL. 60 60: SC CONFIG ERR Specified values or settings do Continues to operate and Check settings and change
SC. CFG not meet the conditions. output without signal them as needed.
characterizing.
AL. 79 Displayed value exceeds Continues to operate and
OV. DISP limit. output.
T0401.EPS
4-3 IM 01C25T03-01E
5. PARAMETER SUMMARY
5. PARAMETER SUMMARY
Instruments to which applicable:
F: Differential pressure transmitters
P: Absolute and gauge pressure transmitters
L: Flange mounted differential pressure transmitters
Applicable model
Upload
*1
data
No. Parameter name Item R/W Content Default value
F P L
01 MODEL Model R EJX ● ● ● -
02 TAG No. Tag number R As specified ● ● ● -
03 SELF CHECK Self-diagnostics R GOOD ● ● ● -
A DISPLAY Measured data display
A10 OUTPUT Output (in %) R 2.5 to 110% ● ● ● -
A11 PRES Measured pressure after zero R Unit specified in C20 ● ● ● -
adjustment
A15 OUTPUT mA Output current R 3.6000 to 21.600 mA ● ● ● -
A16 ENGR. OUTPUT User scaled value R Unit specified in I30 ● ● ● -
A17 ENGR. EXP Exponents R Unit specified in I32 ● ● ● -
A20 SP % Static pressure (in %) R 10 to 110% ● - ● -
A21 SP Static pressure after zero R Unit specified in D30 ● - ● -
adjustment
A30 CAPSULE TEMP Capsule temperature R Unit specified in D40 ● ● ● -
A60 SELF CHECK Self-diagnostics R Refer to Table 4.2 Alarm Message Summary ● ● ● -
B SENSOR TYPE Sensor type
B10 MODEL Model and capsule type R Model and capsule type ● ● ● -
B11 STYLE NO. Style number R Style number of product ● ● ● -
B20 PRES LRL Lower range limit R Unit specified in C20 ● ● ● -
B21 PRES URL Upper range limit R Unit specified in C20 ● ● ● -
B22 P MIN SPAN Minimum span R Unit specified in C20 ● ● ● -
B30 SP LRL Lower range limit for static pressure R Unit specified in D30 ● - ● -
B31 SP URL Upper range limit for static pressure R Unit specified in D30 ● - ● -
B32 SP MIN SPAN Minimum span for static pressure R Unit specified in D30 ● - ● -
B60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
C BASIC SETUP Setting data
C10 TAG NO. Tag number W 16 alphanumeric characters As specified ● ● ● ●
C20 PRES UNIT Measurement range unit W mmH2O, mmAq, mmWG, mmHg, Torr, kPa, kPa ● ● ● ●
MPa, mbar, bar, gf/cm2, kgf/cm2, inH2O,
inHg, ftH2O, psi, atm, Pa, hPa
C21 PRES LRV Lower range value W 32000 to 32000 within measurement range As specified ● ● ● ●
C22 PRES URV Upper range value W 32000 to 32000 within measurement range As specified ● ● ● ●
C23 PRES POINT Decimal place W 0 to 4 2 ● ● ● ●
C30 AMP DAMPING Damping time constant at amplifier W 0.50 (0.00) to 100.00 sec, see D50 2.00 sec or as specified ● ● ● ●
C40 OUTPUT MODE Output mode W LINEAR or SUQARE ROOT LINEAR or as specified ● ● ● ●
C60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
D AUX SET 1 Auxiliary setting data 1
D10 LOW CUT Low cut W 0.00 to 20.00% 10.00% ● ● ● ●
D11 LOW CUT MODE Low cut mode W LINEAR or ZERO LINEAR ● ● ● ●
D15 H/L SWAP Impulse piping accessing direction W NORMAL or REVERSE NORMAL ● - ● ●
D16 H2O UNIT SEL H2O unit select W @4degC or @20degC (68.0F) @4degC ● ● ● ●
D20 OUT LIMIT (L) Low side output limiter W 2.50 to 110.00% 2.50% ● ● ● ●
D21 OUT LIMIT (H) High side output limiter W 2.50 to 110.00% 110% ● ● ● ●
D22 REV OUTPUT Output reversal W NORMAL or REVERSE NORMAL ● ● ● ●
D25 BURNOUT CPU error R HIGH or LOW ● ● ● -
D26 ERROR OUT Hardware error W BURNOUT DIR or HOLD BURNOUT DIR ● ● ● ●
D30 SP UNIT Static pressure unit W See C20 MPa ● - ● ●
D31 SP A/G SLCT Gauge/Abs select for static pressure W GAUGE or ABSOLUTE ABSOLUTE ● - ● ●
D32 ATM. PRESS Coefficient for given gauge pressure W Unit specified in D30 0.10133 MPa ● - ● ●
D33 SP LRV Lower limit of static pressure W 32000 to 32000 within measurement range 0.0 MPa ● - ● ●
D34 SP URV Upper limit of static pressure*2 W 32000 to 32000 within measurement range ● - ● ●
5-1 IM 01C25T03-01E
5. PARAMETER SUMMARY
Applicable model
Upload
*1
data
No. Parameter name Item R/W Content Default value
F P L
D AUX SET 1 Auxiliary setting data 1
D35 SP POINT Decimal place of static pressure W 0 to 4 1 ● - ● ●
D36 SP DAMPING Damping time constant of SP W 0.00 to 100.00 sec 2.00 sec ● - ● ●
D37 SP SELECT H/L select for static pressure W HIGH or LOW HIGH ● - ● ●
D40 TEMP UNIT Temperature setting unit W degC, degF, or K degC ● ● ● ●
D50 QUICK RESP Quick response W OFF or ON (enable 0.00 to 0.50 sec at C30) OFF ● ● ● ●
D55 WRT PROTECT Write protect indicator R NO or YES NO ● ● ● -
D56 WRT ENABLE Write protect release W 8 alphanumeric characters None ● ● ● -
D57 NEW PASSWORD User set password for write protect W 8 alphanumeric characters None ● ● ● -
D58 SOFTWR SEAL Software seal R BREAK or KEEP KEEP ● ● ● -
D60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
E AUX SET 2 Auxiliary setting data 2
E10 T. ZERO CMP Temperature compensation mode W OFF or ON OFF ● ● ● -
E11 TEMP ZERO Zero shift compensation W 99.999 to 99.999%/degC 0.000%/degC ● ● ● -
E30 BI DIRE MODE Bidirectional mode W OFF or ON OFF ● ● ● -
E50 DO SELECT Contact output select W INHIBIT, PRES, SP, TEMP, PRES/SP, INHIBIT ● ● ● -
PRES/TEMP, SP/TEMP, or PRES/SP/TEMP
E51 DO SIG. TYPE Signal type select W OFF WHEN ALARM or ON WHEN ALARM ON WHEN ALARM ● ● ● -
E52 D OUTPUT Contact output R OFF or ON OFF ● ● ● -
E60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
G ALARM SET Alarm setting
G10 P AL MODE Alert mode W INHIBIT, HI. AL DETECT, LO. AL DETECT, INHIBIT ● ● ● -
or HI/LO. AL DETECT
G11 P HI. AL VAL High side alert value W 32000 to 32000, unit specified in C20 100.000 kPa ● ● ● -
G12 P LO. AL VAL Low side alert value W 32000 to 32000, unit specified in C20 100.000 kPa ● ● ● -
G20 SP AL MODE Static pressure alert mode W INHIBIT, HI. AL DETECT, LO. AL DETECT, INHIBIT ● - ● -
or HI/LO. AL DETECT
G21 SP HI. AL VAL High side alert value of SP*2 W 32000 to 32000, unit specified in D30 ● - ● -
G22 SP LO. AL VAL Low side alert value of SP W 32000 to 32000, unit specified in D30 0.00000 MPa ● - ● -
G30 T AL MODE Temperature alert mode W INHIBIT, HI. AL DETECT, LO. AL DETECT, INHIBIT ● ● ● -
or HI/LO. AL DETECT
G31 T HI. AL VAL High side alert value of temperature W 50 to 130 120 degC ● ● ● -
G32 T LO. AL VAL Low side alert value of temperature W 50 to 130 40 degC ● ● ● -
G50 AUTO RECOVER Auto-recover from sensor error W OFF or ON ON ● ● ● -
G60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
H AUTO SET Automatic setup
H10 AUTO P LRV Lower range value auto setup W 32000 to 32000, unit specified in C20 As specified ● ● ● -
H11 AUTO P URV Upper range value auto setup W 32000 to 32000, unit specified in C20 As specified ● ● ● -
H20 AUTO SP LRV SP lower range value auto setup W 32000 to 32000, unit specified in D30 0.00000 MPa ● - ● -
H21 AUTO SP URV SP upper range value auto setup*2 W 32000 to 32000, unit specified in D30 ● - ● -
H60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
I DISP SET Display setting
I10 DISP OUT1 LCD output 1 W PRES, PRES %, ENGR. PRES, SP, or SP % PRES % ● ● ● ●
I11 DISP OUT2 LCD output 2 W PRES, PRES %, ENGR. PRES, SP, SP %, or --- ● ● ● ●
--- ● ● ● ●
I12 DISP OUT3 LCD output 3 W See I11 --- ● ● ● ●
I13 DISP OUT4 LCD output 4 W See I11 --- ● ● ● ●
I20 P DISP MODE % display mode W LINEAR or SQUARE ROOT LINEAR ● ● ● ●
I21 PRES % RESO % display resolution W NORMAL or HIGH RESOLUTION NORMAL ● ● ● ●
I30 ENGR. UNIT User set engineering unit W 8 alphanumeric characters ● ● ● ●
I31 EASY EU SET Engineering unit select W ● ● ● -
I32 ENGR. EXP Exponents W ---, 10, 100, 1000 --- ● ● ● ●
I33 ENGR. LRV User set lower range limit W 32000 to 32000, unit specified in I30 0.00 ● ● ● ●
I34 ENGR. URV User set upper range limit W 32000 to 32000, unit specified in I30 100.00 ● ● ● ●
I35 ENGR. POINT Decimal place of user set W 0 to 4 1 ● ● ● ●
I40 BAR INDICATR Bar indicator W OFF or ON ON ● ● ● ●
I60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
*1: R/W: R = Read only, W = Read & Write
*2: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.
5-2 IM 01C25T03-01E
5. PARAMETER SUMMARY
Applicable model
Upload
*1
data
No. Parameter name Item R/W Content Default value
F P L
J ADJUST Adjusting data
J09 ADJ UNIT Pressure adjusting unit select W % or PRES UNIT PRES UNIT ● ● ● -
J10 ADJ PRES Adjustment reference pressure R Unit specified in J09 ● ● ● -
J11 P ZERO ADJ Automatic zero adjustment W 32000 to 32000, unit specified in J09 0.00000 kPa ● ● ● -
J12 P SPAN ADJ Automatic span adjustment W 32000 to 32000, unit specified in J09 100.000 kPa ● ● ● -
J15 P ZERO DEV Manual zero adjustment W 32000 to 32000, unit specified in J09 100.000 kPa ● ● ● -
J16 P SPAN DEV Manual span adjustment W 32000 to 32000, unit specified in J09 100.000 kPa ● ● ● -
J20 ADJ SP Adjustment reference pressure of SP R Unit specified in J09 ● - ● -
J21 SP ZERO ADJ Automatic SP zero adjustment W 32000 to 32000, unit specified in J09 0.00000 MPa ● - ● -
J22 SP SPAN ADJ Automatic SP span adjustment*2 W 32000 to 32000, unit specified in J09 ● - ● -
J25 SP ZERO DEV Manual SP zero adjustment W 32000 to 32000, unit specified in J09 0.00000 MPa ● - ● -
J26 SP SPAN DEV Manual SP span adjustment W 32000 to 32000, unit specified in J09 0.00000 MPa ● - ● -
J40 OUTPUT 4mA 4 mA adjustment W 10.000 to 10.000% 0.000% ● ● ● -
J41 OUTPUT 20mA 20 mA adjustment W 10.000 to 10.000% 0.000% ● ● ● -
J45 AMP TEMP Amplifier temperature R Unit specified D40 0 degC ● ● ● -
J50 ADJ WHO Adjustment information W 8 alphanumeric characters ● ● ● -
J51 ADJ DATE Adjustment information W 16 alphanumeric characters ● ● ● -
J52 ADJ LOC Adjustment information W 8 alphanumeric characters ● ● ● -
J53 ADJ DESC Adjustment information W 16 alphanumeric characters ● ● ● -
J55 EXT ZERO ADJ External zeroing permission W INHIBIT or ENABLE ENABLE ● ● ● -
J56 CLEAR ADJ Clear adjustment W ---, PRES, SP, 4-20mA, or ALL --- ● ● ● -
J60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
K TEST Test parameters
K10 OUTPUT X % Test output % setting W Within a range between D20 and D21 0.00% ● ● ● -
K40 DO TEST Test contact output W OFF or ON OFF ● ● ● -
K50 TEST KEY1 Special maintenance parameter W ● ● ● -
K51 TEST KEY2 Special maintenance parameter W ● ● ● -
K52 TEST KEY3 Special maintenance parameter W ● ● ● -
K53 TEST KEY4 Special maintenance parameter W ● ● ● -
K60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
M DEVICE INFO Device information
M10 SERIAL NO. Serial number R ● ● ● -
M11 MFTR. DATE Manufactured date R ● ● ● -
M12 EXTRA NO. Customization number R ● ● ● -
M15 SOFT REV Software revision R ● ● ● -
M16 BRAIN REV BRAIN protocol revision R ● ● ● -
M17 MEMO1 Memo W 16 alphanumeric characters ● ● ● -
M18 MEMO2 Memo W 16 alphanumeric characters ● ● ● -
M19 MEMO3 Memo W 16 alphanumeric characters ● ● ● -
M20 ISOL MATL Capsule material W ● ● ● -
M21 FILL FLUID Fill fluid W ● ● ● -
M22 GASKET MATL Gasket material W ● ● ● -
M23 PRO CON MATL Flange material W ● ● ● -
M24 D-VENT MATL Vent plug material W ● ● ● -
M25 PRO CON TYPE Process connection type W ● ● ● -
M26 RS ISOL MATL Remote seal material W ● ● ● -
M27 PRO CON SIZE Flange size W ● ● ● -
M28 NUM RS Number of remote seal W ● ● ● -
M29 RS FILL FLUID Fill fluid of remote seal W ● ● ● -
M30 RS TYPE Remote seal type W ● ● ● -
M50 MS CODE 1 Model and suffix code 1 W ● ● ● -
M51 MS CODE 2 Model and suffix code 2 W ● ● ● -
M52 MS CODE 3 Model and suffix code 3 W ● ● ● -
M53 MS CODE 4 Model and suffix code 4 W ● ● ● -
M54 MS CODE 5 Model and suffix code 5 W ● ● ● -
M55 MS CODE 6 Model and suffix code 6 W ● ● ● -
M60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
*1: R/W: R = Read only, W = Read & Write
*2: The default value shows MWP (Maximum working pressure) of the capsule.
Since the working pressure limit varies according to the Model, refer to the General Specifications section in each user’s manual.
5-3 IM 01C25T03-01E
5. PARAMETER SUMMARY
Applicable model
Upload
*1
data
No. Parameter name Item R/W Content Default value
F P L
P Record History of errors
P10 ERROR REC 1 Last error W See A60 GOOD ● ● ● -
P12 ERROR REC 2 Second recent error W See A60 GOOD ● ● ● -
P14 ERROR REC 3 Third recent error W See A60 GOOD ● ● ● -
P16 ERROR REC 4 Forth recent error W See A60 GOOD ● ● ● -
P60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
T CHARACTERIZR Signal characterizer setting
T10 S. C. ENABLE Signal characterizer permission W INHIBIT or ENABLE INHIBIT ● ● ● -
T11 NUM OF POINT Number of coordinates W 0 to 9 0 ● ● ● -
T20 X START (FIX) Start point of X R 0.00% ● ● ● -
T21 Y START (FIX) Start point of Y R 0.00% ● ● ● -
T22 X1 Coordinate 1 of X W 0.00 to 100.00% 10.00 ● ● ● -
T23 Y1 Coordinate 1 of Y W 0.00 to 100.00% 10.00 ● ● ● -
T24 X2 Coordinate 2 of X W 0.00 to 100.00% 20.00 ● ● ● -
T25 Y2 Coordinate 2 of Y W 0.00 to 100.00% 20.00 ● ● ● -
T26 X3 Coordinate 3 of X W 0.00 to 100.00% 30.00 ● ● ● -
T27 Y3 Coordinate 3 of Y W 0.00 to 100.00% 30.00 ● ● ● -
T28 X4 Coordinate 4 of X W 0.00 to 100.00% 40.00 ● ● ● -
T29 Y4 Coordinate 4 of Y W 0.00 to 100.00% 40.00 ● ● ● -
T30 X5 Coordinate 5 of X W 0.00 to 100.00% 50.00 ● ● ● -
T31 Y5 Coordinate 5 of Y W 0.00 to 100.00% 50.00 ● ● ● -
T32 X6 Coordinate 6 of X W 0.00 to 100.00% 60.00 ● ● ● -
T33 Y6 Coordinate 6 of Y W 0.00 to 100.00% 60.00 ● ● ● -
T34 X7 Coordinate 7 of X W 0.00 to 100.00% 70.00 ● ● ● -
T35 Y7 Coordinate 7 of Y W 0.00 to 100.00% 70.00 ● ● ● -
T36 X8 Coordinate 8 of X W 0.00 to 100.00% 80.00 ● ● ● -
T37 Y8 Coordinate 8 of Y W 0.00 to 100.00% 80.00 ● ● ● -
T38 X9 Coordinate 9 of X W 0.00 to 100.00% 90.00 ● ● ● -
T39 Y9 Coordinate 9 of Y W 0.00 to 100.00% 90.00 ● ● ● -
T40 X END (FIX) End point of X R 100.00% ● ● ● -
T41 Y END (FIX) End point of Y R 100.00% ● ● ● -
T60 SELF CHECK Self-diagnostics R See A60 ● ● ● -
5-4 IM 01C25T03-01E
APPENDIX 1. SAFETY INSTRUMENTED SYSTEMS INSTALLATION
This section provides an overview of the user responsi- A1.2.5 Proof Testing
bilities for installation and operation of the EJX in
order to maintain the designed safety level for Safety The objective of proof testing is to detect failures
Instrumented Systems (SIS) applications. Items that within the transmitter that are not detected by the
will be addressed are proof testing, repair and replace- diagnostics of the transmitter. Of main concern are
ment of the transmitter, reliability data, lifetime, undetected failures that prevent the safety instrumented
environmental and application limits, and parameter function from performing its intended function. See
settings. table A1.2.5 for proof testing method.
The frequency of the proof tests (or the proof test
A1.2 Using the EJX for an SIS interval) is to be determined in the reliability calcula-
tions for the safety instrumented functions for which
Application the EJX is applied. The actual proof tests must be
performed more frequently or as frequently as specified
A1.2.1 Safety Accuracy
in the calculation in order to maintain required safety
The EJX has a specified safety accuracy of 2%. This integrity of the safety instrumented function.
means that the internal component failures are listed in
The following tests need to be specifically executed
the device failure rate if they will cause an error of 2%
when a proof test is performed. The results of the proof
or greater.
test need to be documented and this documentation
should be part of a plant safety management system.
A1.2.2 Diagnostic Response Time
Failures that are detected should be reported to
The EJX will report an internal failure within 5 Yokogawa.
seconds of the fault occurrence.
The personnel performing the proof test of the trans-
A1.2.3 Setup mitter should be trained in SIS operations including
bypass procedures, EJX transmitter maintenance, and
During installation the transmitter must be setup with company management of change procedures.
engineering units parameters. This is typically done
with a handheld terminal. These parameters must be
verified during the installation to insure that the correct
parameters are in the transmitter. Engineering range
parameters can be verified by reading these parameters
from the optional local display or by checking actual
calibration of the transmitter.
A-1 IM 01C25T03-01E
APPENDIX 1. SAFETY INSTRUMENTED SYSTEMS INSTALLATION
Functional test: Handheld terminal Proof Test Coverage The output needs to
1. Follow all Management of =52% be monitored to assure
Change procedures to bypass that the transmitter
logic solvers if necessary. communicates the
correct signal.
2. Execute HART/BRAIN command
to send value to high alarm (21.5
mA) and verify that current has
reached this level.
Perform three point calibration along Handheld terminal Proof Test Coverage
with the functional test listed above. =99%
Calibrated pressure
source
TA0102.EPS
A1.2.6 Repair and Replacement The EJX is certified up to SIL2 for use in a simplex
(1oo1) configuration, depending on the PFDavg
If repair is to be performed with the process online the
calculation of the entire Safety Instrumented Function.
EJX will need to be bypassed during the repair. The
user should setup appropriate bypass procedures. The development process of the EJX is certified up to
SIL3, allowing redundant use of the transmitter up to
In the unlikely event that the EJX has a failure, the
this Safety Integrity Level, depending the PFDavg
failures that are detected should be reported to
calculation of the entire Safety Instrumented Function.
Yokogawa.
When using the transmitter in a redundant configura-
When replacing the EJX, the procedure in the installa-
tion, the use of a common cause factor ("-factor) of
tion manual should be followed.
2% is suggested. (However, if the redundant transmit-
The personnel performing the repair or replacement of ters share an impulse line or if clogging of the separate
the EJX should have a sufficient skill level. impulse lines is likely, a common cause factor of 10%
is suggested.)
A1.2.7 Startup Time
Note that the failure rates of the impulse lines need to
The EJX generates a valid signal within 1 second of be accounted for in the PFDavg calculation.
power-on startup.
A1.2.10 Lifetime Limits
A1.2.8 Firmware Update
The expected lifetime of the EJX is 50 years. The
In case firmware updates are required, they will be reliability data listed the FMEDA report is only valid
performed at factory. The replacement responsibilities for this period. The failure rates of the EJX may
are then in place. The user will not be required to increase sometime after this period. Reliability calcula-
perform any firmware updates. tions based on the data listed in the FMEDA report for
EJX lifetimes beyond 50 years may yield results that
A1.2.9 Reliability Data are too optimistic, i.e. the calculated Safety Integrity
A detailed Failure Mode, Effects, and Diagnostics Level will not be achieved.
Analysis (FMEDA) report is available from Yokogawa
with all failure rates and failure modes.
A-2 IM 01C25T03-01E
APPENDIX 1. SAFETY INSTRUMENTED SYSTEMS INSTALLATION
A-3 IM 01C25T03-01E
REVISION RECORD
Title: EJX Series BRAIN Communication Type
Manual No.: IM 01C25T03-01E
Edition Date Page Revised Item
1st Apr. 2004 – New publication
2st Oct. 2004 3-19 3.2.3 (20) Add capillary fill fluid density compensation setting procedure.
3rd Aug. 2009 3-8 3.2.3 (5) Add example for hysteresis.
3-14 3.2.3 (15) Correct misprint.
3-18 3.2.3 (19) Add CAUTION. Add note for hysteresis.
REVISION RECORD.EPS
IM 01C25T03-01E