Syllabus:: Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Syllabus:: Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Syllabus:: Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Omar Alazzawi
Syllabus:
1. Introduction of Power System.
2. Power System Representation.
3. Per Unit System.
4. Balanced Faults.
5. Symmetrical Fault Calculations.
6. Symmetrical Components.
7. Unsymmetrical Faults.
8. Synchronous Machine in Power System.
9. Power System Load Flow Problems.
10. Direct Methods Involving Inversion of The Nodal Admittance Matrix.
11. Iterative Methods Gauss-Seidal Method.
12. Newton Raphson Method.
References
1- power system analysis John J.Grainger , William D. Stevenson , JR.
2- power system analysis Hadi Saadat .
3- power system analysis and Design J. Duncan Glover
1
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
2
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
All devices are protected by oil circuit breakers (OCBs). We notice that the
diagram indicates the type of connection for each machine and transformer,
and also the points in the system connected to the ground.
The ground connections are important since they affect the current flowing
in nonsymmetrical faults. These connection can be direct or through a
resistor or inductor (they help reducing the fault current that flows in
unsymmetrical faults, while having no impact on the steady-state operation
of the system since the current through them will be zero). Machine ratings,
impedances, and/or consumed (or supplied) powers are usually included in
the diagrams.
3
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
In power systems there are four base quantities required to define a per unit
system. These are: power Sb, voltage Vb, current Ib, and impedance Zb. In
single phase systems, the relationships among these quantities are:
𝑆𝑆𝑏𝑏 = 𝑉𝑉𝑏𝑏 𝐼𝐼𝑏𝑏
𝑉𝑉𝑏𝑏 = 𝐼𝐼𝑏𝑏 𝑍𝑍𝑏𝑏
It is necessary to specify two base values (usually power and voltage). The
other two bases value (current and impedance) are computed from the above
equations. as follows.
𝑆𝑆𝑏𝑏
𝐼𝐼𝑏𝑏 =
𝑉𝑉𝑏𝑏
2
𝑉𝑉𝑏𝑏 𝑖𝑖𝑖𝑖 𝑉𝑉𝐿𝐿𝐿𝐿 (𝑉𝑉𝑏𝑏 𝑖𝑖𝑖𝑖 𝐾𝐾𝐾𝐾𝐿𝐿𝐿𝐿 )2 × 1000 �𝐾𝐾𝐾𝐾𝑏𝑏(𝐿𝐿𝐿𝐿) �
𝑍𝑍𝑏𝑏 = = =
𝐼𝐼𝑏𝑏 𝑖𝑖𝑖𝑖 𝐴𝐴𝐴𝐴𝐴𝐴 𝑆𝑆𝑏𝑏 (𝐾𝐾𝐾𝐾𝐾𝐾1𝜙𝜙 ) 𝑀𝑀𝑀𝑀𝑀𝑀𝑏𝑏(1𝜙𝜙)
The formulas above relate the various quantities in a single phase system and
3-ph system where the current is line current, voltage is voltage to neutral and
S is S per phase.
But normally we select a three-phase power base ( Sb or MVAb ) and a line-
to-line voltage base ( Vb or kVb ). From these two the other bases can be
computed using circuit laws thus:
Sb−3ϕ √3 Sb−3ϕ (KVA)
Ib−Line = =
3 Vb−LL √3Vb−LL (KV)
The specified power base is applicable to all parts of the power system. The
voltage base varies across a transformer and so do the current base and
impedance base. The pu electrical quantities are calculated as follows:
4
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
S 𝑃𝑃 + 𝑗𝑗𝑗𝑗 P + jQ
S pu = = = = Ppu + jQ pu pu
Sb 𝑆𝑆𝑏𝑏 Sb
𝑉𝑉
𝑉𝑉𝑝𝑝𝑝𝑝 = 𝑝𝑝𝑝𝑝
𝑉𝑉𝑏𝑏
𝐼𝐼
𝐼𝐼𝑝𝑝𝑝𝑝 = 𝑝𝑝𝑝𝑝
𝐼𝐼𝑏𝑏
𝑍𝑍
𝑍𝑍𝑝𝑝𝑝𝑝 = 𝑝𝑝𝑝𝑝
𝑍𝑍𝑏𝑏
𝑀𝑀𝑀𝑀𝑀𝑀𝑏𝑏
𝑍𝑍𝑝𝑝𝑝𝑝 = 𝑍𝑍𝑜𝑜ℎ𝑚𝑚
(𝐾𝐾𝐾𝐾𝑏𝑏 )2
It’s clear that the base voltage change as the voltage level of the system is
changed by transformers, but the voltage and impedance expressed in pu
remain unaffected on both sides of transformers.
Different parts of a system may have different base values under such
conditions the conversion of pu impedance from one base to another is
perform as:
2
𝑀𝑀𝑀𝑀𝑀𝑀𝑏𝑏2(𝑛𝑛𝑛𝑛𝑛𝑛) 𝐾𝐾𝐾𝐾𝑏𝑏1(𝑜𝑜𝑜𝑜𝑜𝑜)
𝑍𝑍𝑝𝑝𝑝𝑝2(𝑛𝑛𝑛𝑛𝑛𝑛) = 𝑍𝑍𝑝𝑝𝑝𝑝1(𝑜𝑜𝑜𝑜𝑜𝑜) × ×� �
𝑀𝑀𝑀𝑀𝑀𝑀𝑏𝑏1(𝑜𝑜𝑜𝑜𝑜𝑜) 𝐾𝐾𝐾𝐾𝑏𝑏2(𝑛𝑛𝑛𝑛𝑛𝑛)
Note
It can be seen by inspection of any power system diagram that:
a. Several voltage levels exist in a system
b. It is common practice to refer to plant MVA in terms of per unit or
percentage values
c. Transmission line and cable constants are given in ohms/km.
5
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
4) Convert from per unit back to actual MW, MVAR, MVA, and KV.
Example 2:
A one-line diagram of a three-phase power system is shown. Draw the
impedance diagram of the power system, and mark all impedances in per unit.
Use a base of 100 MVA and 138 kV for the transmission lines. All
transformers are connected to step up the voltage of the generators to the
transmission line voltages. Calculate the terminal voltage of G2 (in pu) if G1
is out of service and the motor draws 50 MW of power with 1 pu voltage at
its terminals.
Equipment Ratings:
item MVA kV Xpu item MVA kV
G1 45 13.2 0.15 T3 70 138 / 11.6 0.10
G2 55 18 0.12 Line 1 ZTL = j40 Ω
6
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Voltage zones:
Zone 1: Vb= 13.8 Kv, Sb= 100 MVA
Zone 2: Vb= 19.05 Kv, Sb= 100 MVA
Zone 3: Vb= 11.6 Kv, Sb= 100 MVA
Zone 4: Vb= 138 Kv, Sb= 100 MVA
Impedances:
100 𝑀𝑀𝑀𝑀𝑀𝑀 13.2 𝐾𝐾𝐾𝐾 2
𝑍𝑍𝐺𝐺1 = 𝑗𝑗0.15 � �� � = 𝑗𝑗0.305 𝑝𝑝𝑝𝑝
45 𝑀𝑀𝑀𝑀𝑀𝑀 13.8 𝐾𝐾𝐾𝐾
100 𝑀𝑀𝑀𝑀𝑀𝑀 18 𝐾𝐾𝐾𝐾 2
𝑍𝑍𝐺𝐺2 = 𝑗𝑗0.12 � �� � = 𝑗𝑗0.195 𝑝𝑝𝑝𝑝
55 𝑀𝑀𝑀𝑀𝑀𝑀 19.05 𝐾𝐾𝐾𝐾
100 𝑀𝑀𝑀𝑀𝑀𝑀 11.6 𝐾𝐾𝐾𝐾 2
𝑍𝑍𝑀𝑀 = 𝑗𝑗0.23 � �� � = 𝑗𝑗0.307 𝑝𝑝𝑝𝑝
75 𝑀𝑀𝑀𝑀𝑀𝑀 11.6 𝐾𝐾𝐾𝐾
100 𝑀𝑀𝑀𝑀𝑀𝑀 138 𝐾𝐾𝐾𝐾 2
𝑍𝑍𝑇𝑇1 = 𝑗𝑗0.1 � �� � = 𝑗𝑗0.2 𝑝𝑝𝑝𝑝
50 𝑀𝑀𝑀𝑀𝑀𝑀 138 𝐾𝐾𝐾𝐾
7
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
8
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
𝑗𝑗0.315 . 𝑗𝑗0.0788
𝑍𝑍𝐿𝐿 = = 𝑗𝑗0.063
𝑗𝑗0.315 + 𝑗𝑗0.0788
Example 3: The three-phase power and line-line ratings of the electric power system
shown in Figure are given below.
G: 60 MVA 20 kV X = 9%
T1 : 50 MVA 20/200 kV X = 10%
T2 : 50 MVA 200/20 kV X = 10%
M : 43.2 MVA 18 kV X = 8%
Line: 200 kV Z = 120 + j200 Ω
Draw an impedance diagram showing all impedances in per unit on a 100-MVAbase.
Choose 20 kV as the voltage base for generator.
Solution:
The base voltage VBG1on the LV side of T1is 20 kV. Hence the base on its HV side
is:
200
𝑉𝑉𝐵𝐵1 = 20 � � = 200 𝐾𝐾𝐾𝐾
20
9
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
This fixes the base on the HV side of T2at VB2= 200 kV, and on its LV side at
20
𝑉𝑉𝐵𝐵𝐵𝐵 = 200 � � = 20 𝐾𝐾𝐾𝐾
200
The generator and transformer reactances in per unit on a 100 MVA base,
100
𝐺𝐺: 𝑋𝑋 = 0.09 � � = 0.15 𝑝𝑝𝑝𝑝
60
100
𝑇𝑇1 : 𝑋𝑋 = 0.1 � � = 0.2 𝑝𝑝𝑝𝑝
50
100
𝑇𝑇2 : 𝑋𝑋 = 0.1 � � = 0.2 𝑝𝑝𝑝𝑝
50
100 18 2
𝑀𝑀: 𝑋𝑋 = 0.08 � � � � = 0.15 𝑝𝑝𝑝𝑝
43.2 20
The base impedance for the transmission line is
(200)2
𝑍𝑍𝐵𝐵𝐵𝐵 = = 400Ω
100
The per unit line impedance is
120 + 𝑗𝑗200
𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙: 𝑍𝑍𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙 = � � = 0.3 + 𝑗𝑗0.5 𝑝𝑝𝑝𝑝
400
The per unit equivalent circuit is shown in Figure
10
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Example 4: Draw an impedance diagram for the electric power system shown in Figure
showing all impedances in per unit on a 100-MVA base. Choose 20 kV as the voltage
base for generator. The three-phase power and line-line ratings are given below
G1 :90 MVA 20 kV X = 9%
T1 :80 MVA 20/200 kV X = 16%
T2 :80 MVA 200/20 kV X = 20%
G2 :90 MVA 18 kV X = 9%
Line: 200 kV X = 120 Ω
Load: 200kv Z = 300 + j400 Ω
Solution:
The base voltage VBG1on the LV side of T1is 20 kV. Hence the base on its HV side
is:
200
𝑉𝑉𝐵𝐵1 = 20 � � = 200 𝐾𝐾𝐾𝐾
20
This fixes the base on the HV side of T2at VB2= 200 kV, and on its LV side at
20
𝑉𝑉𝐵𝐵𝐵𝐵2 = 200 � � = 20 𝐾𝐾𝐾𝐾
200
The generator and transformer reactance in per unit on a 100 MVA base,
100
𝐺𝐺1 : 𝑋𝑋 = 0.09 � � = 0.1 𝑝𝑝𝑝𝑝
90
100
𝑇𝑇1 : 𝑋𝑋 = 0.16 � � = 0.2 𝑝𝑝𝑝𝑝
80
100
𝑇𝑇2 : 𝑋𝑋 = 0.2 � � = 0.25 𝑝𝑝𝑝𝑝
80
100 18 2
𝐺𝐺2 : 𝑋𝑋 = 0.09 � � � � = 0.081 𝑝𝑝𝑝𝑝
90 20
The base impedance for the transmission line is
(200)2
𝑍𝑍𝐵𝐵𝐵𝐵 = = 400Ω
100
11
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Example 5: Draw an impedance diagram for the electric power system shown in
Figureshowing all impedances in per unit on a 30MVA base. Choose 6.9 kV as
thevoltage base for generator. The three-phase power and line-line ratings are
givenbelow
Solution:
6.9 2 30
𝐺𝐺1 : 𝑋𝑋 = 0.15 � � � � = 0.225 𝑝𝑝𝑝𝑝
6.9 20
115
Base voltage in L1-2=6.9 � � = 115 𝐾𝐾𝐾𝐾
6.9
(115)2
Base impedance = = 440Ω
30
100
L1-2𝑋𝑋 = = 0.2268 𝑝𝑝𝑝𝑝
440
80
L2-3𝑋𝑋 = = 0.1814 𝑝𝑝𝑝𝑝
440
12
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
6.9 2 30
𝑇𝑇1 : 𝑋𝑋 = 0.1 � � � � = 0.12 𝑝𝑝𝑝𝑝
6.9 25
6.9
Base KV in G2 = 115 � � = 6.9 𝐾𝐾𝐾𝐾
115
30 6.9 2
𝐺𝐺2 : 𝑋𝑋 = 0.15 � � � � = 0.45 𝑝𝑝𝑝𝑝
10 6.9
30 115 2
𝑇𝑇2 : 𝑋𝑋 = 0.1 � �� � = 0.25 𝑝𝑝𝑝𝑝
12.5 115
7.5
Base voltage =115 � � = 11.5 𝐾𝐾𝐾𝐾
75
13.8 2 30
𝐺𝐺3 : 𝑋𝑋 = 0.15 � � � � = 0.216 𝑝𝑝𝑝𝑝
11.5 30
30 75 2
𝑇𝑇3 : 𝑋𝑋 = 0.1 � � � � = 0.127 𝑝𝑝𝑝𝑝
10 115
HW.
Q1/ A 100 MVA, 13.8 KV, 3-phase generator has a reactance of 20%. The
generator is connected to a 3-phase transformer T I rated 100 MVA 12.5 KV 1110
KV with 10% reactance. The h.v. side of the transformer is connected to a
transmission line of reactance 100 ohm. The far end of the line is connected to a
step down transformer T 2' made of three single-phase transformers each rated 30
MVA, 60 KV / 10 KV with 10% reactance the generator supplies two motors
connected on the l.v. side T2 as shown in Fig. E.6.2. The motors are rated at 25
MVA and 50 MVA both at 10 KV with 15% reactance. Draw the reactance
diagram showing all the values in per unit. Take generator rating as base.
Q2/ Figure below shows single-line diagram of a power system. The ratings
of the generators and transformers are given below:
G1: 25 MVA, 6.6 kV, xg1=0.20 pu
13
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
T3 : Single-phase unit each rated 10 MVA, 6.9/69 kV, xT3 = 0.10 pu.
Draw per-unit circuit diagram using base values of 30 MVA and 6.6 kV in
the circuit of generator-1.
Q3: A 100 MVA, 33 kV, three phase generator has a reactance of 15%. The
generator is connected to the motors through a transmission line and transformers
as shown in Fig. below. Motors have rated inputs of 40 MVA, 30 MVA and 20
MVA at 30 kV with 20% reactance-each. Draw the per-unit circuit diagram.
Example: Draw the per-unit impedance diagram of the system shown in Fig.
14
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
4- Nodal Analysis
where Ya = 1 /Za ' Thus, the emf Es and its series impedance Za can be
interchanged with the current source Is and its shunt admittance Ya ,
provided
Figure 1Circuits illustrating the equivalenc of sources when Is = Es/Za and Ya = 1 /Za
15
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
𝐼𝐼1 = 𝑉𝑉1 �𝑌𝑌𝑎𝑎 + 𝑌𝑌𝑓𝑓 + 𝑌𝑌𝑑𝑑 � − 𝑉𝑉3 𝑌𝑌𝑓𝑓 − 𝑉𝑉4 𝑌𝑌𝑑𝑑 ………………….1
0 = −𝑉𝑉1 𝑌𝑌𝑑𝑑 − 𝑉𝑉2 𝑌𝑌ℎ − 𝑉𝑉3 𝑌𝑌𝑒𝑒 + 𝑉𝑉4 (𝑌𝑌𝑑𝑑 + 𝑌𝑌𝑒𝑒 + 𝑌𝑌ℎ ) …………..2
The (Y) matrix is designated (Ybus) and called (the bus admittance matrix)
1- Each diagonal element in the nodal admittance matrix ( Y11 Y22 Y33
Y44) is called self admittance and it is the sum of the admittances of the
branches terminating in each node.
2- Each off-diagonal element of the nodal admittance matrix (all the other
admittances) called the mutual admittances and each equal the negative
16
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Example:
Write in matrix form the node equations necessary to solve for the
voltages of the numbered buses of the figure below.
Solution:
1.5∠0
I1 = I3 = = 1.2∠ − 90 = −j1.2 p. u
j1.25
1.5∠−36.87
I2 = = 1.2∠ − 126.87 = −0.72 − j0.96 p. u
j1.25
Self admittances
Mutual admittances
17
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
-j1.2 -j9.8 j0 j4 V1
j5
-0.72- = V2
j0.96 j0 -j8.3 j2.5
V3
j5
-j1.2
V4
j4 j2.5 -j15.3
0
j8
j5 j5 j8
-j18
5- Fault
5-1 Introduction
A fault is any abnormal condition in a power system. The steady state
operating mode of a power system is balanced 3-phase a.c. .However, due to
sudden external or internal changes in the system, this condition is disrupted.
When the insulation of the system fails at one or more points or a conducting
object comes into contact with a live point, a short circuit or a fault occurs.
Causes of Power System Faults
The causes of faults are numerous, e.g.
· Lightning
· Heavy winds
· Trees falling across lines
· Vehicles colliding with towers or poles
· Birds shorting lines
· Aircraft colliding with lines
· Vandalism
· Small animals entering switchgear
· Line breaks due to excessive loading
18
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Fault studies form an important part of power system analysis. The problem
consists of determining bus voltages and line currents during various type of
19
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
faults. Faults in power systems are divided into three-phase balanced faults and
unbalanced faults. The information gained from fault studies are used for proper
relay setting and coordination, and used to obtain the rating of the protective
switchgears.
The magnitude of the fault currents depends on the internal impedance of the
generators plus the impedance of the intervening circuit.
In course of power system stability, it was shown that the reactance of a generator
under short circuit condition is not constant (is a time-varying quantity) and for
network analysis three reactances were defined. The sub transient reactance X d′′
, for the first few cycles of the short circuit current, transient reactance X d′ , for
the next (say) 30 cycles, and the synchronous reactance X d , thereafter. Since the
duration of the short circuit depends on the time of operation of the protective
system, it is not always easy to decide which reactance to use. Generally, the sub
transient reactance is used for determining the interrupting capacity of the circuit
breakers. Transient reactance is used for relay setting and coordination, and for
transient stability studies.
If the fault impedance is zero, the fault is referred to as the bolted fault or the
solid fault. The faulted network can be solved by the Thevenin's method. The
procedure is demonstrated in the following example.
In the power system shown in fig. All impedance in per unit on a common
100MVA, the resistances and shunt capacitances are neglected. The system is
considered on no-load and the generators are running at their rated voltage and
frequency with their emfs in phase. Find the fault current, the bus voltages, and
20
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
the line currents during the fault when a balanced three-phase fault with a fault
impedance Z f = 0.16 per unit, occurs on bus 3.
21
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Vth = V3 (0) = pre fault bus voltage (obtain from the results of
the power flow solution)
Z th = Z 33
V3 (0)
I3 (F ) =
Z 33 + Z f
22
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Z ∆ → ZY
( j 0.4)( j 0.8)
Z1 = Z 2 = = j 0.2
j 0.16
( j 0.4)( j 0.4)
Z3 = = j 0.1
j 0.16
( j 0.4)( j 0.6)
= + j 0.1 = j 0.24 + j 0.1 = j 0.34
j 0.4 + j 0.6
The load are neglected, and the generators emfs are assumed equal to the rated
value, therefore all the pre-fault bus voltages are equal to 1.0 pu, i.e.:
V1 (0) = V2 (0) = V3 (0) = 1.0 pu
V3 ( F ) 1.0
∴ I3 (F ) = = = − j 2.0 pu
Z 33 + Z f j 0.34 + j 0.16
j 0.6
I g1 = I 3 ( F ) = − j1.2 pu
j 0.4 + j 0.6
j 0.4
Ig2 = I 3 ( F ) = − j 0.8 pu
j 0.4 + j 0.6
For the bus voltage changes:
The bus voltages during the fault are obtained by superposition of the pre-fault
bus voltages and the changes in the bus voltages caused by the equivalent emf
connected to the faulted bus V3 ( F ) .
V1 ( F ) − V2 ( F ) 0.76 − 0.68
I12 ( F ) = = = − j 0.1 pu
Z12 j 0.8
V1 ( F ) − V3 ( F ) 0.76 − 0.32
I13 ( F ) = = = − j1.1 pu
Z13 j 0.4
V2 ( F ) − V3 ( F ) 0.68 − 0.32
I 23 ( F ) = = = − j 0.9 pu
Z 23 j 0.4
1- The pre-fault bus voltages are obtained from the results of the power
flow solution.
2- In order to preserve the linearity feature of the network, loads are
converted to constant admittances using the pre-fault bus voltages.
3- The faulted network is reduced into a Thevenin's equivalent circuit as
viewed from the faulted bus. Applying Thevenin's theorem, changes in the
bus voltages are obtained.
4- Bus voltages during the fault are obtained by superposition of the pre-fault
bus voltages and the changes in the bus voltages computed in the previous
step.
5- The current during the fault in all branches of the network are then obtained.
24
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
VK (0)
I K ( F ) pu = .............................. ( 2)
X KK
S B × 103
IB = ..................................... (3)
3 VB
25
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
I K ( F ) in amp. = I K ( F ) pu × I B
VK (0) S B × 103
= ................... ( 4)
X KK 3 VB
V K(0) S B VL
SCC = ............................ (5)
X KK VB
V K(0) S B
∴ SCC = . ......................... (6)
X KK
SB
∴ SCC (short − circuit MVA) = MVA .... (7)
X KK
26
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
The pre fault bus voltages are obtained from the power flow solution and are
represented by the column vector.
V1 (0)
Vbus (0) = Vk (0) ........................................(8)
Vn (0)
The bus load by a constant impedance evaluated at the pre fault bus voltage,
i.e.:
27
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
2
Vi (0)
Z iL = ∗
................................(9)
S L
The bus voltage changes caused by the fault in this circuit are represented by
the column vector :
∆V1
∆Vbus = ∆Vk
........................................(10)
∆Vn
By applying Thevenin's theorem, bus voltages during the fault are obtained by
superposition of the pre fault bus voltages and the changes in the bus voltages
i.e.:
28
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Also , we know :
m
Yii = ∑ yij j ≠ i , and Yij = Y ji = − yij ....... (13)
j =0
In the Thevenin's circuit of fig. above, current entering every bus is zero except at
the faulted bus. Since the current at faulted bus is leaving the bus, it is taken as a
negative current entering bus k.
Thus the nodal equation applied to the Thevenin's circuit in fig. above becomes:
The above matrix equation, can be writing in terms of its elements as shown:
29
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Since we have only one single nonzero element in the current vector , the kth
equation in eq. 15 becomes :
Vk ( F ) = Z f I k ( F ) .............................. (17)
From eq. (16) and eq. (17) , the fault current becomes :
Vk (0)
Ik (F ) = ................................ (18)
Z kk + Z f
Vk (0)
Ik (F ) =
Z kk
Thus, for a fault at bus k we need only the Z kk element of the bus impedance
matrix. This element is indeed the Thevenin's impedance as viewed from the
faulted bus.
30
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Z ik
Vi ( F ) = Vi (0) − Vk (0) ...................... ( 20)
Z kk + Z f
Vi ( F ) − V j ( F )
I ij ( F ) = .................................. ( 21)
zij
For previous example, to compute the fault current, the bus voltages , and the line
currents during the fault at bus 3 , by using the bus impedance matrix method , the
Thevenin's equivalent network is redraw with impedances converted to
admittances as shown in fig. below , in order to find the bus admittance matrix .
31
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
From eq. (18), for a fault at bus 3 with fault impedance Z f = 0.16 pu:
V3 (0) 1.0
I3 (F ) = = − j 2.0 pu
Z 33 + Z f j 0.34 + j 0.16
From eq. (21), the short circuit currents in the lines are:
V1 ( F ) − V2 ( F ) 0.76 − 0.68
I12 ( F ) = = = − j 0.1 pu
z12 j 0.8
V1 ( F ) − V3 ( F ) 0.76 − 0.32
I13 ( F ) = = = − j1.1 pu
z13 j 0.4
V2 ( F ) − V3 ( F ) 0.68 − 0.32
I 23 ( F ) = = = − j 0.9 pu
z23 j 0.4
The results are exactly the same as the values found previously.
32
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
The values of the diagonal elements in the bus impedance matrix are equal to
the thevenin's impedances for other fault locations , i.e. if the fault occurs at
bus2 , the thevenin's impedance is j 0.24 , and equal to j 0.16 if the fault occurs
at bus1, then can be used eq. (18) to find directly the fault current at buses 1
and 2 , as following :
V1 (0) 1.0
I1 ( F ) = = − j 3.125 pu
Z11 + Z f j 0.16 + j 0.16
V2 (0) 1.0
I2 (F ) = = − j 2.5 pu
Z 22 + Z f j 0.24 + j 0.16
Furthermore, the 0ff-diagonal elements are utilized in eq. (20) to obtain bus
voltages during the fault.
Therefore, the bus impedance matrix method is an indispensable tool for fault
studies.
The matrix inversion for a large power system with a large number of buses is not
feasible. A computationally attractive and efficient method for finding Z bus
matrix is (building) or (assembling) the impedance matrix by adding one network
element at a time. In effect, this is an indirect matrix inversion of the bus
admittance matrix.
Sotution
Choose a system base of 25 MVA.
For a generator voltage base of 11 kV, line voltage base is 66 kV and motor
voltage base is 6.6 kV.
(a) For each motor
34
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Example 2/ Consider the 4-bus system of Fig. Buses1 and 2 are generator
buses and 3 and 4 are load buses. The generators are rated 11kv, 100 MVA,
with transient reactance of l0% each. Both the transformers are 11/110 kV,
100 MVA with a leakage reactance of 5%. The reactances of the lines to a
base of 100 MVA, 110 kv are indicated on the figure. obtain the short circuit
solution for a three-phase solid fault on bus 4 (load bus).
Assume pre-fault voltages to be 1 pu and pre-fault currents to be zero.
Solution
Changes in voltages and currents caused by a short circuit can be
calculated from the circuit model of Fig.1. Fault current If is calculated by
systematic network reduction as in Fig.2,
35
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Fig. 1
Fig 2
36
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
37
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Q2/ The one-line diagram of a simple power system is shown in Figure. Each
generator is represented by an emf behind the transient reactance. All
impedances are expressed in per unit on a common MVA base. All resistances
and shunt capacitances are neglected. The generators are operating on no load
at their rated voltage with their emfs in phase. A three-phase fault occurs at
bus 1 through a fault impedance of Zf = j0:08 per unit.
(a) Using Thevenin's theorem obtain the impedance to the point of fault and
the fault current in per unit.
(b) Determine the bus voltages and line currents during fault.
Q3/ Equipment ratings for the four-bus power system shown in Figure are as
follows:
Generator G1: 500 MVA, 13.8 kV, X"= 0:20 per unit
Generator G2: 750 MVA, 18 kV, X"= 0.18 per unit
Generator G3: 1000 MVA, 20 kV, X"=0.17 per unit
Transformer T1: 500 MVA, 13.8 ∆/500Y kV, X =0.12 per unit
Transformer T2: 750 MVA, 18 ∆/500Y kV, X =0.10 per unit
Transformer T3: 1000 MVA, 20 ∆/500Y kV, X =0.10 per unit
Each 500-kV line: X1 =50 Ω
38
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
A three-phase short circuit occurs at bus 1, where the pre fault voltage is 525 kV.
Pre fault load current is neglected. Draw the positive-sequence reactance diagram
in per-unit on a 1000-MVA, 20-kV base in the zone of generator G3. Determine (a)
the Thevenin reactance in per-unit at the fault, (b) the sub transient fault current in
per unit and in kA rms, and (c) contributions to the fault current from generator G1
and from line 1–2.
Q4/A three-phase short circuit occurs at the generator bus (bus 1) for the
system shown in Figure. Neglecting pre fault currents and assuming that the
generator is operating at its rated voltage, determine the subtransient fault
current using superposition.
39
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
40
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
41
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
If the machine short circuit takes place from unloaded conditions, the
Terminal voltages constitutes the positive sequence voltage; on the other
hand. If the short circuit occurs from loaded condition the voltage behind an
appropriate reactance (sub transient, transient or synchronous) constitutes
the positive sequence voltage.
42
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
43
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Zero sequence network models on a three- and single-phase basis are shown
in Figs. A and b. In Fig. a, the current flowing in the impedance Zn
between neutral and ground is In = 3Iao. The zero-sequence voltage of terminal
a with respect to ground, the reference bus. is therefore
Vao= - 3Zn Iao – Zog Iao = - (3Zn + Zog)Iao
Where Zo, is the zero-sequence impedance per phase of the machine.
Since the single-phase zero sequence network of Fig. b carries only per
Phase zero sequence current, its total zero sequence impedance must be
Zo=3Zn+Zog
44
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
in order for it to have the same voltage from a to reference bus. The reference
bus here is, of course at ground potential. From Fig. b zero sequence voltage
of point a with respect to the reference bus is
Vao = -Zo Iao
Order of Values of Sequence Impedances of a Synchronous Generator:
Typical values of sequence impedances of a turbo-generator rated 5 MVA,
6.6 kV, 3;000 rpm are:
Z1 = 12% (sub transient)
Z1 = 20% (transient)
Z1 = 110% (synchronous)
Z2= 12%
Zo= 5%
45
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
46
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
The zero sequence currents are in phase and flow through the line conductors
only if a return conductor is provided. The zero-sequence impedance is
different from positive and negative sequence impedances.
It is well known that almost all present day installations have three-phase
transformers since they entail lower initial cost, have smaller space
requirements and higher efficiency.
The positive sequence series impedance of a transformer equals its leakage
impedance. Since a transformer is a static device, the leakage impedance does
not change with alteration of phase sequence of balanced applied voltages.
The transformer negative sequence impedance is also therefore equal to its
leakage reactance. Thus. for a transformer
Z1= Z2= Z leakage
Assuming such transformer connections that zero sequence currents can flow
on both sides, a transformer offers a zero-sequence impedance which may
differ slightly from the corresponding positive and negative sequence values.
It is, however, normal practice to assume that the series impedances of all
sequences are equal regardless of the type of transformer.
The zero-sequence magnetizing current is somewhat higher in a core type
than in a shell type transformer. This difference does not matter as the
magnetizing current of a transformer is always neglected in short circuit
analysis.
47
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
48
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Fig. Y-Y transformer bank with one neutral grounded and its zero
Sequence network
Case 2: Y-Y Transformer Bank Both Neutrals Grounded
When both the neutrals of a Y-Y transformer are grounded, a path through the
transformer exists for zero sequence currents in both windings via the two
grounded neutrals. Hence, in the zero sequence network H and L are
connected by the zero sequence impedance of the transformer as shown in
Fig.
Fig. Y-Y transformer bank with sequence network neutrals grounded and its zero
If the neutral of stars ide is grounded, zero sequence currents can flow in star
Because a path is available to ground and the balancing zero sequence currents
can flow in delta. Of course, no zero sequence currents can flow in the line on
the delta side. The zero-sequence network must therefore have a path from the
line H on the star side through the zero sequence impedance of the transformer
to the reference bus, while an open circuit must exist on the line L side of delta
49
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
(see Fig.). If the star neutral is grounded through Zn an impedance 3Zn appears
in series with Zo in the sequence network
Fig. Y-∆ transformer bank with ungrounded star and its zero sequence network
50
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
SUMMARY
51
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
EX1. For the power system whose one-line diagram is shown in Fig. sketch
the zero sequence network
Sol.:
121
Transmission line voltage base= 11𝑥𝑥 = 11𝑘𝑘𝑘𝑘
10.8
10.8
Motor voltage base= 123.2𝑥𝑥 = 11𝑘𝑘𝑘𝑘
121
The reactances of transformers line and motors are converted to pu values
on appropriate bases a s follows
25 10.8 2
Transformer reactance= 0.1𝑥𝑥 𝑥𝑥 � � = 0.0805𝑝𝑝𝑝𝑝
30 11
100𝑥𝑥25
Line reactance =(123.2)2
52
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
25 10 2
Reactance of motor 1=0.25𝑥𝑥 𝑥𝑥 � � = 0.345𝑝𝑝𝑝𝑝
15 11
25 10 2
Reactance of motor 2=0.25𝑥𝑥 𝑥𝑥 � � = 0.69𝑝𝑝𝑝𝑝
7.5 11
Ex3. Draw the zero-sequence network for the system described in Example2
Assume zero sequence reactance for the generator and motors of 0.06 per unit.
Current limiting reactors of 2.5 ohms each are connected in the neutral of the
generator and motor No. 2. The zero-sequence reactance of the transmission
line is 300 ohms.
Sol.:
Solution The zero sequence reactance of the transformer is equal to its
positive sequence reactance. Hence
Transformer zero sequence reactance: 0.0805 pu
Generator zero sequence reactance : 0.06 pu
25 10 2
Zero sequence reactance of motor 1=0.06𝑥𝑥 𝑥𝑥 � � = 0.082𝑝𝑝𝑝𝑝
15 11
25 10 2
Zero sequence reactance of motor 2=0.06𝑥𝑥 𝑥𝑥 � � = 0.164𝑝𝑝𝑝𝑝
7.5 11
2.5𝑥𝑥25
Reactance of current limiting reactors= = 0.516
112
53
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Q1/ Draw the positive, negative and zero sequence impedance networks for
the power system of Fig. Choose a base of 50 MVA, 220 kV in the 50Ω
transmission lines, and mark all reactance in pu. The ratings of the
generators and transformers are:
G1: 25 MVA, 11 kV, X" = 20%
G2: 25 MVA, 11 kV, X" = 20%
Three-phase transformer (each): 20 MVA, 11Y /220Y kV, X = I5%
The negative sequence reactance of each synchronous machine is equal to its
sub transient reactance. The zero-sequence reactance of each machine is 8%.
Assume that the zero-sequence reactance of lines are 250% of their positive
sequence reactance.
Q2/ For the power system of Fig. draw the positive, negative and zero
sequence networks. The generators and transformers are rated as follows:
Generator1 : 25 MVA, 11 kV, X" =0.2, X2 = 0.15, Xo = 0.03 pu
Generator2 : 15 MVA, 11 kV, X" =0.2, X2= 0.15, Xo = 0.05 pu
Synchronous Motor 3: 25 MVA, 11 kV, X" = 0.2, X2= 002, Xo = 0.1 pu
Transformer l: 25 MVA, 11∆/120 Y kV, X = 10%
Transformer 2: 12.5 MVA, 11∆/120 Y kV, X = 10%
54
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
7- Unbalanced Faults
Most of the faults that occur on power systems are unsymmetrical faults,
which may consist of unsymmetrical short circuits, unsymmetrical faults
through impedances, or open conductors. Unsymmetrical faults occur as
single line--‐to--‐ground faults, line--‐to--‐ line faults, or double line--‐to--‐
ground faults.
The path of the fault current from line to line or line to ground may or may
not contain impedance.
One or two open conductors result in unsymmetrical faults, through either the
breaking of one or two conductors or the action of fuses and other devices that
may not open The three phases simultaneously.
Since any unsymmetrical fault causes unbalanced currents to flow in the
system, the method of symmetrical components is very used in the analysis
to determine the currents and voltages in all parts of the system after the
occurrence of the fault.
We will consider faults on a power system by applying Thévenin's theorem,
which allows us to find the current in the fault by replacing the entire
system by a single generator and series impedance, and we will show how
the bus impedance matrix is applied to the analysis of unsymmetrical faults.
The common types of asymmetrical faults occurring in a Power System are
single line to ground faults and line to line faults, with and without fault
impedance.
55
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
The single line to ground fault can occur in any of the three phases.
However, it is sufficient to analyze only one of the cases. Looking at the
symmetry of the symmetrical component matrix, it is seen that the simplest
to analyze would be the phase a. Consider an L-G fault with zero fault
impedance as shown in figure. Since the fault impedance is 0, at the fault
Va = 0, Ib = 0, Ic = 0
56
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
at the fault
Va = IaZf , Ib = 0 , Ic = 0
These can be converted to equivalent conditions in symmetrical components
as
57
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
follows.
Va0 + Va1 + Va2 = (Ia0 + Ia1 + Ia2).Zf
And
The line to line fault takes place on phases ‘b’ and ‘c’
The boundary conditions are
58
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Which means for a line to line fault the zero sequence component of current
is absent and positive sequence component of current is equal in magnitude
but opposite in phase to negative sequence component of current, i.e.,
Transform equation 1 in terms of symmetrical components we have
59
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
NOTE:
1. The connection of sequence currents are connected in parallel.
2. The phase difference between Ia1 and Ia2 for line – to – line fault should be
180° (Ia1 = Ia2).
Line to Line fault with Zf
−𝐽𝐽√3 𝐸𝐸𝑎𝑎1
If=
𝑍𝑍1 +(𝑍𝑍2 +𝑍𝑍𝑓𝑓 )
60
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
𝑉𝑉𝑎𝑎0 = 0 − 𝑍𝑍 0 𝐼𝐼𝑎𝑎0
We have � 𝑉𝑉𝑎𝑎1 = 𝐸𝐸𝑎𝑎 − 𝑍𝑍1 𝐼𝐼𝑎𝑎1 � ………………8
𝑉𝑉𝑎𝑎2 = 0 − 𝑍𝑍 2 𝐼𝐼𝑎𝑎2
Substitute 8 in 7
𝐸𝐸𝑎𝑎 −𝑍𝑍 1 𝐼𝐼𝑎𝑎1
𝐼𝐼𝑎𝑎0 = − ………………………………….9
𝑍𝑍 0 +3Zf
Using 8 in 5
𝐸𝐸𝑎𝑎 −𝑍𝑍 1 𝐼𝐼𝑎𝑎1
𝐼𝐼𝑎𝑎2 = − ……………………………….10
𝑍𝑍 2
61
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Example:
The one-line diagram of a simple power system is shown in the figure. The
neutral of each generator is grounded through a current-limiting reactor of
0.25 per unit on a 100-MVA base. The system data is tabulated below. The
generators are running on no-load at their rated voltage and rated frequency
with their emfs in phase. Determine the fault current for the following faults:
(a) A balanced three-phase fault at bus3 through fault impedance Zf = j0.1 per
unit.
(b) A single line-to-ground fault at bus 3 through fault impedance Zf = j0.1
per unit
(c) A line-to-line fault at bus 3 through fault impedance Zf = j0.1 per unit
(d) A double line-to-ground fault at bus 3 through fault impedance Zf = j0.1
per unit
62
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Solution:
Find the Thevenin impedance viewed from bus 3
(faulted bus). The delta transforms to a Y as in the
figure below
The positive- and negative-sequence networks are shown to the right. The only difference
between them in this case is that the source is missing in the negative-sequence network.
Hence we have:
Now, the zero-sequence network is constructed based on the transformer connections and
is shown in the figures to the right. Find the equivalent zero sequence circuit. The result
is the simple circuit shown below.
63
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
𝑉𝑉3𝑎𝑎 (0)
𝐼𝐼𝑎𝑎1 = 𝑍𝑍 2 (𝑍𝑍 0 +3Zf )
𝑍𝑍1 +
𝑍𝑍 2 +𝑍𝑍 0 +3Zf
64
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
1
= 𝑗𝑗0.22(𝑗𝑗0.35+0.3)
𝑗𝑗0.22 +
𝑗𝑗0.22+𝑗𝑗0.35+0.3
= −𝑗𝑗2.6017 𝑝𝑝. 𝑢𝑢
HW
Q1/ The reactance data for the power system shown in Figur in per unit on a
common base is as follows:
Obtain the Th´evenin sequence impedances for the fault at bus 1 and compute
the fault current in per unit for the following faults:
(a) A bolted three-phase fault at bus 1.
(b) A bolted single line-to-ground fault at bus 1.
65
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
66
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
The inductor connected to Generator 3 neutral has a reactance of 0.05 per unit
using generator 3 ratings as a base. Draw the zero-, positive-, and negative-
sequence reactance diagrams using a 1000-MVA, 765-kV base in the zone of
line 1–2.
Q4/ Equipment ratings for the four-bus power system shown in Figure are
given as follows:
67
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
68
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
INTRODUCTION
Network equations can be formulated systematically in a variety forms.
However, the node-voltage method, which is the most suitable form for many
power system analysis, is commonly used.
The formulation of the network equations in the nodal admittance form result in
complex linear simultaneous algebraic equations in terms of node currents.
When node currents are specified, the set of linear equations can be solved for
the nod voltages. However, in a power system, powers are known rather than
currents. Thus, the resulting equations in terms of power, known as the power
flow equations, become nonlinear and must be solved by iterative techniques.
Power flow studies, commonly referred to as load flow. They are necessary for
planning, operation, economic scheduling, exchange of power between utilities,
transient stability and contingency studies.
Load flow or power flow is the solution obtained for the power system under
static (steady state) conditions of operation.
The phase angles of load bus voltages , reactive power at generator bus .
69
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
For the purpose of Load flow studies, a single phase representation of the
power network is used since the system is generally balanced. The generators
are provided with voltage magnitude and phase angle controls. The loads are
represented by constant impedances. Meters are provided on the panel board
for measuring voltages, currents, and powers. The load flow solution is
obtained directly from measurements for any system simulated on the
analyzer. With the advent of the modern digital computer processing large
storage and high speed, the mode of Load flow studies have changed from
analogue to digital simulation. A large number of algorithms are developed to
digital power flow solution. In the network at each bus or node there are four
variables:
Out of these four quantities, two of them are specified at each bus and
the remaining two are determined from the load flow solution.
The system buses are generally classified into three types :
70
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Slack bus (swing bus): Is taken as reference where the magnitude and phase angle
of the voltage ( V , δ ) are specified. This bus makes up the difference between
the scheduled loads and generated power that are caused by losses in the network.
Load buses (P - Q buses): At these buses the P and Q are specified. The magnitude
and the phase angle ( V , δ ) of the bus voltages are unknown.
Regulated buses (P – V buses): These buses are the generator buses ( voltage
controlled buses ) . At these buses V and P are specified. The δ and Q are to be
determined. The limits on the value of the Q are also specified.
71
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
admittances on a common
MVA base .
n n
or I i = Vi ∑y −∑y V
j =0
ij
j =1
ij j j ≠ i …….(10)
72
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Pi + jQi = Vi I i∗
∗
P + jQi P + jQi
∗
I = i
i ; I i = i
Vi Vi
P − jQ
= i ∗ i
Vi
Pi − jQi n n
Vi ∗
= Vi ∑y
j =0
ij − ∑ yijV j
j =1
j≠i .....(11)
The above equation is algebraic nonlinear equation which must be solved by iterative
techniques .
In the Gauss-Seidel method , the equation (11) is solved for Vi and the iterative
sequence becomes :
Pi sch − jQisch n
∗( k )
+ ∑ yijV j( k )
( k +1) Vi j =1
Vi = n
j ≠ i ..........(12)
∑y
j =0
ij
73
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
sch
Pi sch and Qi are the net real and reactive power expressed in per unit .
n n
Pi ( k +1)
= Re{Vi ∗( K )
[Vi (k )
∑ y −∑ y V
j =0
ij
j =1
ij j
(k )
]} j≠i
n n
Q i
( k +1)
= − Im{Vi ∗( K )
[Vi (k )
∑ y −∑ y V
j =0
ij
j =1
ij j
(k )
]} j≠i …(13)
The power flow equation is usually expressed in terms of the elements of the bus
admittance matrix ( Ybus ) . Since the off-diagonal elements of Ybus shown by Yij ( i.e.
Yij = − yij ) and the
n
diagonal elements are Yii = ∑ yij , since equation (11) becomes :
j =0
Pi − jQi n
∗
= Vi Yii + ∑ YijV j j≠i ........(14)
Vi j =1
74
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Pi sch − jQisch n
∗( k )
− ∑ YijV j( k )
Vi j =1
( k +1) j ≠i
Vi = .........................(15)
Yii
n
Pi ( k +1)
= Re{Vi ∗( K )
[Vi (k )
Yii + ∑ Yij V j( k ) ]} j≠i
j =1
j ≠i
n
Q ( k +1)
= − Im{Vi ∗( K )
[Vi (k )
Yii + ∑ Yij V j( k ) ]} j ≠ i
i ..(16)
j =1
j ≠i
Yii includes the admittance to ground of line charging susceptance and any other fixed
admittance to ground . Also which includes the effect of transformer tap setting .
For the Gauss-Seidel method , an initial voltage estimate of 1.0 + j 0.0 for unknown
voltage is satisfactory , and the converged solution correlates with the actual operation
states .
sch sch
For P-Q buses , the real and reactive powers Pi and Qi are known . Starting with
an initial estimate , eq. (15) is solved for the real and imaginary components of voltage .
sch ( k +1)
For P-V buses where Pi and Vi are specified , first eq.(16) is solved for Qi ,
( k +1)
and then is used in eq (15) to solve for Vi . However , since Vi is specified , only
( k +1)
the imaginary part of Vi
Where ei( k +1) and f i ( k +1) are the real and imaginary components of the voltage
Vi ( k +1) in the iterative sequence .
Where α is the acceleration factor , the range of its value is ( 1.3 to 1.7 ) .
The process is continued until changes in the real and imaginary components of bus
voltages between successive iterations are with a specified accuracy , i.e. :
76
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
After a solution is converged , the real and reactive powers at the slack bus are computed
from eq (16)
Complex power
Si = Pi + jQi = Vi I i* 3
77
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Hence, from the equations (4) and (5), for an n-bus system:
Pi − jQi n
Ii = *
= Yii .Vi + ∑ yik .Vk
Vi k =1
k ≠i
8
1 Pi − jQi n
Vi = [ *
− ∑ Yik .Vk ]
Yii Vi k =1
k ≠i
9
n
Pi + jQi = Vi ∑ Yik .Vk
Further, k =1
10
k ≠i
i =1,2,…,n
So that
n
Pi = ∑ Vi .Vk .Yik cos(δ i − δ k − θ ik )
k =1 12
And
n
Qi = ∑ Vi .Vk .Yik sin(δ i − δ k − θ ik )
k =1 13
i =1,2,…,n
i ≠ slack bus
78
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
The power flow equations (10) are nonlinear. Finally, the powers at the slack
bus may be computed from which the losses and all other line flows can be
ascertained. Y-matrix interactive methods are based on solution to power flow
relations using either current mismatch at a bus given by
n
∆I i = I i − ∑ Yik .Vk 14
k =1
∆I i
∆Vi = 15
Yii
1 Pi − jQi n
Vi = [ *
− ∑ Yik .Vk ]
Yii Vi k =1
k ≠i
16
1 Pi − jQi n n
Vi ( m +1)
= [ ( m )* − ∑ Yik .Vk( m +1)
− ∑ YikVk( m ) ]
Yii Vi k =1 k =i +1
k ≠i
17
79
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
∆Si*
∆Vi = α *
Vi Yii 18
Vi ( m ) ∠δ i = α Vi ( m ) ∠δ i
19
take a function and rearrange it into the form x = g(x). {there are several
possible arrangements}
make an an initial estimate of the variable x: x[0] = initial value
find an iterative improvement of x[m], that is: x[m+1] = g( x[m] )
a solution is reached when the difference between two iterations is
less than a specified accuracy factor: x[m+1] - x[m] ≤ ε
acceleration factors: can improve the rate of convergence. the improvement is
found as
𝑚𝑚+1 𝑚𝑚
𝑥𝑥𝑎𝑎𝑎𝑎𝑎𝑎 = 𝑥𝑥𝑎𝑎𝑎𝑎𝑎𝑎 +∝ [𝑔𝑔(𝑥𝑥)𝑚𝑚 − 𝑥𝑥𝑎𝑎𝑎𝑎𝑎𝑎
𝑚𝑚 ]
80
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Example
are performed.
1 6 4
𝑥𝑥 [1] = 𝑔𝑔�𝑥𝑥 [0] = 2� = − (2)3 + (2)2 + = 2.222
9 9 9
1 6 4
𝑥𝑥 [2] = 𝑔𝑔�𝑥𝑥 [1] = 2.2222� = − (2.2222)3 + (2.2222)2 + = 2.5173
9 9 9
1 6 4
𝑥𝑥 [3] = 𝑔𝑔�𝑥𝑥 [2] = 2.5173� = − (2.5173)3 + (2.5173)2 + = 2.8966
9 9 9
𝑥𝑥 [4] = 3.3376
𝑥𝑥 [5] = 3.7398
𝑥𝑥 [6] = 3.9568
𝑥𝑥 [7] = 3.9988
𝑥𝑥 [8] = 4
81
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Example
𝑥𝑥 [0] = 2
1 6 4
𝑔𝑔(2) = − (2)3 + (2)2 + = 2.2222
9 9 9
1 6 4
𝑔𝑔(2.2778) = − (2.2778)3 + (2.2778)2 + = 2.5902
9 9 9
𝑥𝑥 [2] = 2.2778 + 1.25[2.5902 − 2.2778] = 2.6683
𝑥𝑥 [3] = 3.0801
𝑥𝑥 [4] = 3.1831
𝑥𝑥 [5] = 3.7238
𝑥𝑥 [6] = 4.0084
𝑥𝑥 [7] = 3.9978
𝑥𝑥 [8] = 4.0005
82
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
|V1|=1.0, δ=0.0
n n
(𝑚𝑚+1) 1 𝑃𝑃𝑖𝑖 − 𝑗𝑗𝑗𝑗𝑖𝑖 β (m)
𝑉𝑉𝑖𝑖 = � (𝑚𝑚)∗ − � Yik . Vk − � Yik . Vk �
𝑌𝑌𝑖𝑖𝑖𝑖 𝑉𝑉
𝑖𝑖 k=1 k=i+1
k≠i
where, m = iteration number. For generator bus, find using (11) and (17)
together. That is, find Qi first.
n
Q i
( m+1)
= − Im ag[Vi *( m )
{Vi Yii + ∑ YikVk( m )
( m)
k =1
k ≠i
Then
n n
(𝑚𝑚+1) 1 𝑃𝑃𝑖𝑖 − 𝑗𝑗𝑗𝑗𝑖𝑖 β (m)
𝑉𝑉𝑖𝑖 = � (𝑚𝑚)∗ − � Yik . Vk − � Yik . Vk �
𝑌𝑌𝑖𝑖𝑖𝑖 𝑉𝑉
𝑖𝑖 k=1 k=i+1
k≠i
83
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
So, for example, if there are five busses in the system being studied, and one
has determined new values of bus voltages at busses 1–3, then during the
determination of bus voltage at bus 4, one should use these newly calculated
values of bus voltages at 1, 2, and 3; busses 4 and 5 will have the values from
the previous iteration.
Step 2b: for faster convergence, apply acceleration factor to load buses
m +1)
Vi ,(acc = Vi ,(acc
m)
+ α (Vi ( m ) − Vi ,(acc
m)
)
That is, the absolute value of the difference of the real part of the voltage
between successive iterations should be less than a tolerance value ε .
Typically, ε ≤ 10 −4
, and also,
That is, the absolute value of the difference of the imaginary value of the
voltage should be less than a tolerance value ε,
84
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Step 4: Find slack bus power Pg and Qg from equations (5) and (6).
Step 5: Find all line flows as described in the next section computing line
flows. As the last step in any power-flow solution, one has to find the line
flows. This is illustrated by the two-bus system shown in above Fig. Line
current, Iij, at bus i is defined positive in the direction i to j.
I ik = I s + I pi = (Vi − Vk ). y s + Vi . y pi
Let Skj, Sjk be line powers defined positive into the line at bus i and j,
respectively.
The power loss in line (i-j) is the algebraic sum of the power flows determined
from (a-1) and (a-2).
S Lij = Sij + S ji
85
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Form Y-Bus
Let m=0
Is i YES
Vi(m)=Vi(m+1)
i = i+1
NO
Is (i-n) ≤0
M=m+1
NO
Is ΔVmax-Vspecified ≥0
End
86
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Example 1:
For the 3-bus system in Fig below, the line per-unit reactances are: x12=0.75,
x13=0.25, and x23=0.50.
Bus 2 is a generator bus with voltage magnitude 𝑉𝑉2 = 1.02 𝑝𝑝𝑝𝑝. and real
injected power, P2=0.6 pu.
a) Use the Gauss-Seidel method to determine the power flow solution for
power system within a V3 tolerance of 0.01 pu. For
Solution
1
𝑌𝑌13 = − = 𝑗𝑗4 Y22=Y12+Y23 =-j3.33
𝑗𝑗𝑗𝑗13
87
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
1
𝑌𝑌23 = − = 𝑗𝑗2 Y33=Y13+Y23 =-j6
𝑗𝑗𝑗𝑗23
Known quantities:
(0) (0)
𝛿𝛿2 = 𝛿𝛿3 = 0
k =1
k ≠i
1 Pi − jQi n
Vi ( m+1)
= [ ( m )* − ∑ Yik .Vk( β ) ]
Yii Vi k =1
k ≠i
β= m k> 𝑖𝑖
β= m+1 k< 𝑖𝑖
88
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Iteration 1
1 P2 − jQ2 ( m +1)
V2(1) = [ ( 0 )*
− Y21V1 − Y23V3
m
]
Y22 V2
1 0.6 − j 0.07
= [ − ( j1.33)(1∠0) − ( j 2)1∠0]
− j 3.33 (1.02∠0)∗
= 1.04∠9.8
V2 specified ⇒ V2(1) = V2 spec ∠δ 2 calcul
= 1.02∠9.8
(1)
V2
(1)
𝑄𝑄2 = −𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼[𝑉𝑉2∗ (𝑉𝑉2 𝑌𝑌22 + 𝑌𝑌21 𝑉𝑉1 + 𝑌𝑌23 𝑉𝑉3 )]
89
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Iteration 2
1 P2 − jQ2
V2( 2 ) = [ − Y21V1 − Y23V3 ]
Y22 V2(1)*
1 0.6 − j 0.33
= [ − ( j1.33)(1∠0) − ( j 2)0.91∠ − 4.8] = 1.02∠8.2
− j 3.33 (1.02∠9.8)∗
1 P3 − jQ3
V3( 2 ) = [ − Y31V1 − Y32V2 ]
Y33 V3(1)*
1 − 0.8 + j 0.6
= [ − ( j 4)(1∠0) − ( j 2)(1.02∠8.2]
− j 6 (0.91∠ − 4.8)∗
= 0.89∠ − 5.7
(2) (2) (1)
∆𝑉𝑉3 = �∆𝑉𝑉3 − ∆𝑉𝑉3 � = 0.89 − 0.91 = 0.02
(2)
𝑄𝑄2 = −𝐼𝐼𝐼𝐼[(1.02∠8.2)∗ {(−𝑗𝑗3.33)1.02∟8.2 + (𝑗𝑗1.33) + (𝑗𝑗2)0.89∠
− 5.7}] = 0.36
Iteration 3
1 P2 − jQ2
V2( 3) = [ − Y21V1 − Y23V3 ]
Y22 V2( 2 )*
1 0.6 − j 0.36
= [ − ( j1.33)(1∠0) − ( j 2)0.89∠ − 5.7]
− j 3.33 (1.02∠8.2)∗
= 1.02∠7.7
1 P3 − jQ3
V3(3) = [ − Y31V1 − Y32V2 ]
Y33 V3( 2 )*
1 0.8 + j 0.6
= [ − ( j 4) − ( j 2)(1.02∠7.7]
− j 6 (0.89∠ − 5.7)∗
= 0.88∠ − 6
90
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
(3) (3)∗
𝑄𝑄2 = −𝐼𝐼𝐼𝐼𝐼𝐼𝐼𝐼 �𝑉𝑉2 (𝑉𝑉2 𝑌𝑌22 + 𝑌𝑌21 𝑉𝑉1 + 𝑌𝑌23 𝑉𝑉3 )� = 0.38
The N-R method has rapid convergence independent from system size.
Thus, the method usually converges in less than 10 iterations
91
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
𝑛𝑛
If these equations are linearized as before around the point δik and |𝑉𝑉𝑘𝑘 | using
the Taylor series expansion around the points we have
(𝑚𝑚) (𝑚𝑚) (𝑚𝑚) (𝑚𝑚)
⎡𝜕𝜕𝜕𝜕2 𝜕𝜕𝜕𝜕2 𝜕𝜕𝜕𝜕2 𝜕𝜕𝜕𝜕2 ⎤
⎢ 𝜕𝜕𝜕𝜕2 𝜕𝜕𝜕𝜕𝑛𝑛 𝜕𝜕|𝑉𝑉2 | 𝜕𝜕|𝑉𝑉𝑛𝑛 | ⎥ (𝑚𝑚)
(𝑚𝑚)
⎡∆𝑃𝑃2 ⎤ ⎢ . . . . ⎥ ⎡ ∆𝛿𝛿2 ⎤
.
⎢ . ⎥ ⎢ .(𝑚𝑚) . . . ⎥⎢ ⎥
⎢ . ⎥ ⎢ 𝜕𝜕𝜕𝜕𝑛𝑛 ⎥ .
(𝑚𝑚) (𝑚𝑚) (𝑚𝑚)
𝜕𝜕𝜕𝜕𝑛𝑛 𝜕𝜕𝜕𝜕𝑛𝑛 𝜕𝜕𝜕𝜕𝑛𝑛 ⎢ ⎥
⎢∆𝑃𝑃𝑛𝑛(𝑚𝑚) ⎥ ⎢ …𝜕𝜕𝜕𝜕 ⎥ (𝑚𝑚)
∆𝛿𝛿𝑛𝑛 ⎥
… …𝑛𝑛 . . …⎥ ⎢
𝜕𝜕𝜕𝜕 𝜕𝜕|𝑉𝑉 | 𝜕𝜕|𝑉𝑉 |
⎢ …..
2
… …𝑛𝑛. . … …2 . .
⎢ − ⎥= (𝑚𝑚) ⎢ − ⎥
⎢𝜕𝜕𝜕𝜕2(𝑚𝑚) 𝜕𝜕𝜕𝜕2
(𝑚𝑚)
𝜕𝜕𝜕𝜕2 𝜕𝜕𝜕𝜕2
(𝑚𝑚)
⎥
⎢ (𝑚𝑚) ⎥
⎥ ⎢∆ �𝑉𝑉2 �⎥
(𝑚𝑚)
∆𝑄𝑄 ⎢
⎢ 2 ⎥ ⎢ 𝜕𝜕𝜕𝜕2 𝜕𝜕𝜕𝜕𝑛𝑛 𝜕𝜕|𝑉𝑉2 | 𝜕𝜕|𝑉𝑉𝑛𝑛 | ⎥ ⎢ . ⎥
⎢ . ⎥ ⎢ . . . .
⎥⎢ ⎥
⎢ . ⎥ ⎢ . . . . .
(𝑚𝑚) (𝑚𝑚) (𝑚𝑚) (𝑚𝑚) (𝑚𝑚) ⎥ ⎢ (𝑚𝑚) ⎥
⎣∆𝑄𝑄𝑛𝑛 ⎦ ⎢𝜕𝜕𝜕𝜕𝑛𝑛 𝜕𝜕𝜕𝜕𝑛𝑛 𝜕𝜕𝜕𝜕𝑛𝑛 𝜕𝜕𝜕𝜕𝑛𝑛 ⎥⎣ ∆ �𝑉𝑉𝑛𝑛 �⎦
⎢ 𝜕𝜕𝜕𝜕2 𝜕𝜕𝜕𝜕𝑛𝑛 𝜕𝜕|𝑉𝑉2 | 𝜕𝜕|𝑉𝑉𝑛𝑛 | ⎥
⎣ ⎦
or
∆𝑈𝑈 = 𝐽𝐽 ∙ ∆𝑋𝑋
J: Jacobean matrix
92
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
P1, Q1:- of the slack bus can be computed since for this bus we know V1 and
δ1.
For every generator bus we know P and |𝑉𝑉| for that bus, hence the equation
in ∆𝑄𝑄 and ∆|𝑉𝑉| for that bus is not needed. Thus we can delete the
corresponding row and column from Jacobean matrix. Jacobean matrix is
evaluated at every iteration step.
Starting with some initial value for|𝑉𝑉| and δ and solve these equations for
∆𝛿𝛿 and ∆|𝑉𝑉| we can proceed to the next iteration thus:
(𝑚𝑚+1) (𝑚𝑚)
𝛿𝛿𝑖𝑖 = 𝛿𝛿𝑖𝑖𝑚𝑚 + ∆𝛿𝛿𝑖𝑖
(𝑚𝑚+1) (𝑚𝑚) (𝑚𝑚)
�𝑉𝑉𝑖𝑖 � = �𝑉𝑉𝑖𝑖 � + ∆ �𝑉𝑉𝑖𝑖 �
We can stop the iteration process when the power residual are smaller than a
pre-specified value. These are
(𝑚𝑚) (𝑚𝑚)
∆𝑃𝑃𝑖𝑖 = 𝑃𝑃𝑖𝑖(𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠) − 𝑃𝑃𝑖𝑖
(𝑚𝑚) (𝑚𝑚)
∆𝑄𝑄𝑖𝑖 = 𝑄𝑄𝑖𝑖(𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠} − 𝑄𝑄𝑖𝑖
Solution:
Step 1:
93
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
Step3:
(0)
𝑃𝑃2 = |𝑉𝑉2 ||𝑉𝑉1 ||𝑌𝑌21 | cos(𝛿𝛿1 − 𝛿𝛿2 + 𝜃𝜃21 ) + |𝑉𝑉2 ||𝑉𝑉2 ||𝑌𝑌22 | cos(𝛿𝛿2 − 𝛿𝛿2 + 𝜃𝜃22 )
+ |𝑉𝑉2 ||𝑉𝑉3 ||𝑌𝑌23 | cos(𝛿𝛿3 − 𝛿𝛿2 + 𝜃𝜃23 )
(0)
𝑄𝑄2 = −[|𝑉𝑉2 ||𝑉𝑉1 ||𝑌𝑌21 | sin(𝛿𝛿1 − 𝛿𝛿2 + 𝜃𝜃21 )
+ |𝑉𝑉2 ||𝑉𝑉2 ||𝑌𝑌22 | sin(𝛿𝛿2 − 𝛿𝛿2 + 𝜃𝜃22 )
+ |𝑉𝑉2 ||𝑉𝑉3 ||𝑌𝑌23 | sin(𝛿𝛿3 − 𝛿𝛿2 + 𝜃𝜃23 )]
(0)
𝑃𝑃3 = |𝑉𝑉1 ||𝑉𝑉3 ||𝑌𝑌31 | cos(𝛿𝛿1 − 𝛿𝛿3 + 𝜃𝜃31 ) + |𝑉𝑉2 ||𝑉𝑉3 ||𝑌𝑌32 | cos(𝛿𝛿2 − 𝛿𝛿3 + 𝜃𝜃32 )
+ |𝑉𝑉3 ||𝑉𝑉3 ||𝑌𝑌33 | cos(𝛿𝛿3 − 𝛿𝛿3 + 𝜃𝜃33 )
(0)
𝑄𝑄3 = −[|𝑉𝑉1 ||𝑉𝑉3 ||𝑌𝑌31 | sin(𝛿𝛿1 − 𝛿𝛿3 + 𝜃𝜃31 )
+ |𝑉𝑉2 ||𝑉𝑉3 ||𝑌𝑌32 | sin(𝛿𝛿2 − 𝛿𝛿3 + 𝜃𝜃32 )
+ |𝑉𝑉3 ||𝑉𝑉3 ||𝑌𝑌33 | sin(𝛿𝛿3 − 𝛿𝛿3 + 𝜃𝜃33 )]
94
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
(0)
∆𝑃𝑃2 (0) = �𝑃𝑃2(𝑠𝑠) − 𝑃𝑃2 � = 0.6
(0)
∆𝑃𝑃3 (0) = �𝑃𝑃3(𝑠𝑠) − 𝑃𝑃3 � = −0.8
(0)
∆𝑄𝑄3 (0) = �𝑄𝑄3(𝑠𝑠) − 𝑄𝑄3 � = −0.6
Step 4:
𝜕𝜕𝑃𝑃2 (0)
= 𝑉𝑉1 𝑉𝑉2 Y21 sin(𝛿𝛿1 − 𝛿𝛿2 + 𝜃𝜃21 ) + 𝑉𝑉2 𝑉𝑉3 𝑌𝑌23 sin(𝛿𝛿3 − 𝛿𝛿2 + 𝜃𝜃23 )
𝜕𝜕𝛿𝛿2
=2+4=6
𝜕𝜕𝑃𝑃2 (0)
= −𝑉𝑉2 𝑉𝑉3 𝑌𝑌23 sin(𝛿𝛿3 − 𝛿𝛿2 + 𝜃𝜃23 ) = −4
𝜕𝜕𝛿𝛿3
𝜕𝜕𝑃𝑃2 (0)
= 𝑉𝑉2 𝑌𝑌23 cos(𝛿𝛿3 − 𝛿𝛿2 + 𝜃𝜃23 ) = 0
𝜕𝜕|𝑉𝑉3 |
𝜕𝜕𝑃𝑃3 (0)
= −𝑉𝑉2 𝑉𝑉3 𝑌𝑌32 sin(𝛿𝛿2 − 𝛿𝛿3 + 𝜃𝜃32 ) = −4
𝜕𝜕𝛿𝛿2
𝜕𝜕𝑃𝑃3 (0)
= 𝑉𝑉1 𝑉𝑉3 Y31 sin(𝛿𝛿1 − 𝛿𝛿3 + 𝜃𝜃31 ) + 𝑉𝑉2 𝑉𝑉3 𝑌𝑌32 sin(𝛿𝛿2 − 𝛿𝛿3 + 𝜃𝜃32 )
𝜕𝜕𝛿𝛿3
=5+4=9
𝜕𝜕𝑃𝑃3 (0)
= 𝑉𝑉1 Y31 cos(𝛿𝛿1 − 𝛿𝛿3 + 𝜃𝜃31 ) + 𝑉𝑉2 𝑌𝑌32 cos(𝛿𝛿2 − 𝛿𝛿3 + 𝜃𝜃32 )
𝜕𝜕|𝑉𝑉3 |
+ 2𝑉𝑉3 𝑌𝑌33 cos(𝜃𝜃33 ) = 0
𝜕𝜕𝑄𝑄3 (0)
= −𝑉𝑉2 𝑉𝑉3 Y32 cos(𝛿𝛿2 − 𝛿𝛿3 + 𝜃𝜃32 ) = 0
𝜕𝜕𝛿𝛿2
95
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
𝜕𝜕𝑄𝑄3 (0)
= 𝑉𝑉1 𝑉𝑉3 Y31 cos(𝛿𝛿1 − 𝛿𝛿3 + 𝜃𝜃31 ) + 𝑉𝑉2 𝑉𝑉3 𝑌𝑌32 cos(𝛿𝛿2 − 𝛿𝛿3 + 𝜃𝜃32 ) = 0
𝜕𝜕𝛿𝛿3
𝜕𝜕𝑄𝑄3 (0)
= −𝑉𝑉1 Y31 sin(𝛿𝛿1 − 𝛿𝛿3 + 𝜃𝜃31 )
𝜕𝜕|𝑉𝑉3 |
− 𝑉𝑉2 𝑌𝑌32 sin(𝛿𝛿2 − 𝛿𝛿3 + 𝜃𝜃32 ) − 2𝑉𝑉3 𝑌𝑌33 sin(𝜃𝜃33 )
= −5 − 4 + 2(9) = 9
0.6
∆|𝑉𝑉3 |(0) = − = −0.067
9
𝛿𝛿2 = 0 + 0.058
96
Electrical Dept. Electrical Power III Dr. Omar Alazzawi
(1)
𝑃𝑃2 = 1 ∙ 1 ∙ 2 cos(0 − 0.058 + 90) + 1 ∙ 1 ∙ 6 cos(−90) + 1 ∙ 4
∙ (0.933) cos(−0.063 − 0.058 + 90) = 0.0099
(1)
𝑃𝑃3 = 1 ∙ 5 ∙ (0.933) cos(90 + 0.063) + 4
∙ (0.933) cos(90 + 0.058 + 0.063) + 9(0.933)2 cos(−90)
= −0.013
(1)
𝑄𝑄3 = −[1 ∙ 5 ∙ (0.933) sin(90 + 0.063) + 4
∙ (0.933) sin(90 + 0.058 + 0.063) + 9(0.933)2 sin(−90)]
= −0.562
(1)
∆𝑃𝑃2 = 0.6 − 0.0099 = 0.59
(1)
∆𝑃𝑃3 = −0.8 + 0.013 = −0.787
(1)
∆𝑄𝑄3 = −0.6 + 0.5625 = −0.0375
97