SAMIL POWER Expert For PV Grid-Tied Inverters. SolarLake Grid Connected Inverter. Product Manual SP SL V5.3 EN. English
SAMIL POWER Expert For PV Grid-Tied Inverters. SolarLake Grid Connected Inverter. Product Manual SP SL V5.3 EN. English
SAMIL POWER Expert For PV Grid-Tied Inverters. SolarLake Grid Connected Inverter. Product Manual SP SL V5.3 EN. English
SAMIL POWER
Expert for PV Grid-tied Inverters
01
02
Contents
1 Basic safety information 7
1.1 Preface 7
1.2 General information 7
1.3 Safety instruction 7
1.4 Pre installation checks 8
1.5 Transport 8
1.6 Electric connection 8
1.7 Operation 8
1.8 Maintenance and repair 9
1.9 EMC / noise level of inverter 9
2 Product description 10
2.1 Function 10
2.2 Electrical block diagram 10
2.3 Dimension 11
2.4 Product label 11
3 Protection devices 12
3.1 Auto shut down 12
3.2 Additional protection devices 12
4 Installation 12
4.1 Packing list 12
4.2 Safety instruction 13
4.3 Precaution 14
4.4 Preparation 15
4.5 Installation Steps 15
4.6 Connecting PV array to inveter 16
4.6.1 Notes 16
4.6.2 PV array connection types 16
4.6.3 Assembly steps of DC connectors 17
4.6.4 Assembly steps of AC connector 19
4.6.5 Grounding 20
4.7 Safety inspection before commissioning 20
5 Commissioning of inverter 21
5.1 Start inverter 21
5.2 Check country setting and PV array connection type 21
5.2.1 Checking Country setting 21
5.2.2 Programming PV array connection type 23
6 Operation 24
6.1 Control and display panel 24
6.2 LCD Settings 25
6.2.1 Standard interface 25
6.2.2 Main menu 25
6.2.3 Instantaneous data 25
6.2.4 Historical data 25
6.2.5 Event list 26
6.2.6 Restore factory settings 26
6.3 LCD function 30
6.4 CEI 0-21 30
6.5 BDEW 37
03
7 Communication and monitoring 43
7.1 Communication interface 43
7.2 Communication mode 43
7.2.1 RS232 communication for single inverter 43
7.2.2 RS485 communication 43
7.2.3 Ethernet communication 44
8 Troubleshooting 45
8.1 Troubleshooting 45
8.2 Daily maintenance 50
9 Decommissioning 50
9.1 Decommissioning steps 50
9.2 Package 50
9.3 Storage 50
9.4 Disposal 50
10 Technical data 51
10.1 Input (DC) 51
10.2 Output (AC) 51
10.3 Efficiency, Safety and Protection 52
10.4 General data 52
04
● Notes on this Manual
This manual is an integral part of the inverter. Please read the manual carefully before installation, operation
or maintenance. Keep this product manual for future reference. Please note that all pictures are edited by
Samil Power.
● Scope of Validity
This product manual describes the assembly, installation, commissioning, and maintenance of the following
Samil Power SolarLake Series inverters.
SolarLake 10000TL SolarLake 12000TL
SolarLake 15000TL SolarLake 17000TL
Keep this manual where it shall be accessible at all times.
● Target Group
This manual is for qualified persons installing and operating the inverters. The tasks described in this manual
must only be performed by qualified persons.
● Symbols Used
This manual provides safety and operation information and uses symbols in order to ensure personal
and property security and efficient operation of inverters. User must understand and observe instructions
in the manual to avoid personal injury and property loss. Please read and understand the following
symbols which are used in this manual.
Danger
Danger indicates a hazardous situation which. if not avoided, will result in death
or serious injury.
Warning
Warning indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
Caution
Caution indicates a hazardous situation, if not avoided, could result in minor or
moderate injury.
Note
Note provides tips that are valuable for the optimal operation of the product.
Attention
Attention indicates potential risks, if ignored prevent may lead to equipment
malfunction or damage.
05
● Symbols on the Inverter
These are some symbols which are related to safety and security. Please read and fully understand
these symbols before installing the equipment.
Symbol Explaination
In the event of any property destruction or personal injury due to failure to follow instructions in this
manual, Samil Power Co., Ltd does not take any responsibility for the same.
06
Basic safety information
Note!
If you have any questions or concerns when reading this manual, please contact Samil
Power Co., Ltd.
1.1 Preface
Installation of SolarLake inverter must completely meet with national and local grid connection standards
and regulations.
● Please contact Samil Power authorized repair center if you have any maintenance or repair services for
the inverter. Your dealer should be able to provide details of your nearest authorized service centre.
Please do not attempt any maintenance yourself as it may cause property destruction and personal injury.
● Read and understand the instruction in this manual and familiarize with the relevant safety symbols before
installing or maintaining the equipment.
● National and State regulations may require prior approval before connecting on site power generation systems
to the local grid.
● Before installing or maintaining the inverter, PV array and grid supply must be disconnected to avoid injury.
Danger!
Danger to life due to high voltages in the inverter!
• All work on the inverter must be carried out by qualified person only;
• The appliance is not to be used by children or persons with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge.
• Children should be supervised to ensure that they do not play with the appliance.
Caution!
Danger of burn injuries due to hot parts!
During inverter operation, should only touch the display and keys on the inverter.
Attention!
PV array should be connected to the ground in accordance with requirements
of local regulations
To protect system and avoid personnel injury, Samil Power suggests that PV array
frame and inverter should be properly grounded.
Warning!
Ensure that the input DC voltage is less than the Max.DC voltage rating of the
inverter under all operating conditions. Over voltage may cause permanent damage
to the inverter or lead to other losses, which are not covered by product warranty.
07
Basic safety information
Warning!
Disconnect both AC and DC power from the inverter before opening the inverter. All
maintenance work should only be carried out by qualified and trained Electrical
Engineers.
1.5 Transport
All SolarLake inverters leaving the factory are thoroughly are tested and inspected to ensure the high
quality of our products. Our products are packed safely to ensure that these are not damage during
transportation. However, damage in transport do happen and in such cases the responsibility lies with the
transportation company.
While taking delivery of the goods, please check inverter and if packing or transit damages are found,
please inform transportation company immediately. If you need assistance please contact your supplier
or Samil Power Co. Ltd.
If the inverter is to be returned the original packing materials or suitable alternative must be used to avoid
damage during transport.
Danger!
Before making electrical connection, use opaque materials to cover the PV modules
or disconnect PV panel DC switch. Beware that PV modules produce dangerously
high voltages when exposed to sun.
Warning!
All installation work must be done only professional electrical engineer.
● Must be trained;
● Read and understand the User manual.
Attention!
If necessary obtain prior permission from the local energy supplier before connecting
the inverter to the grid.
1.7 Operation
Attention!
Some internal components will be very hot when the inverter is working. Please
wear protective gloves.
08
Basic safety information
Danger!
Touching the power grid or electrical terminals may lead to electric shock or fire and
may lead to death or serious injury.
● Don’t touch the terminals or conductor When live.
Danger!
Disconnect the PV array and electricity grid before undertaking any work on the
inverter.
Wait about 5 minutes after turning off AC and DC switches to discharge capacitors
before opening the inverter cover.
Attention!
In case of any problem with the inverter, please contact your local authorized
service center.
Attention!
There are no user serviceable parts inside the inverters, hence do not open the inverter.
Samil Power Co., Ltd does not take any responsibility if this advice is ignored.
Warning!
Electromagnetic radiation from inverter may be harmful to health.
• Please do not stay close to the inverter for long periods when operating.
Keep minimum distance of 20 cm.
09
Product description
2 Product description
2.1 Function
The SolarLake Series PV inverters converts the DC power of a PV generator to grid compatible AC power
and feed it into the public grid.
SolarLake inverters are manufactured using the latest technology and under strict safety standards. Even
then in correct installation or operation will cause property destruction and personal injury.
The SolarLake series inverters are not designed for mobile application.
The SolarLake series inverters should not be used for anyother purpose than grid tied PV systems. The
manufacturer/supplier does not take any responsibility if used for any other purpose.
Control Board
Output to grid
Solar input
10
Product description
ON
1 2
OFF
AC GRID
Note: For safety reasons, use of a DC switch is recommended between the PV modules and the inverter’s
power modules. DC switch, when opted, is built into the SolarLake inverters.
2.3 Dimension
● Dimension for SolarLake 10000TL, 12000TL, 15000TL and 17000TL inverters. 716mm
520mm 230mm
Note: The AC output terminal projects out the most in these inverters, hence care should be taken to avoid
any damage to the terminal. Avoid resting the inverter on the floor with the terminal touching the floor.
11
Protection devices
3 Protection Devices
3.1 Auto shut down
SolarLake Inverters will be disconnected within a fraction of a second if grid power is lost or switched off to
protect any person working on the grid supply. This facility corresponds with current national standards and
regulations. SolarLake inverter is also equipped with automatic disconnection protection system to avoid
any possible island operation.
Attention!
To learn details on possible malfunction of the inverter, please refer to section 8 of
this manual.
4 Installation
4.1 Packing list
Please ensure that the box contains all the materials mentioned in the packing list. If any item is missing
or damaged please contact supplier immediately.
12
Installation
1 2 3 4 5
6 7 8 9
TM
Sami
Expert l Powe
for PV
Grid-ti
ed Inverte
r
rs
Sola
rRiv
Prod er PV Grid-tied
uct
Manu rter
SP-SR Inve
-V5-E
N
al
479 mm
39.2 mm
440 mm
152 mm
407.2 mm
302 mm
511 mm
13
Installation
Must strictly observe the following standard and specifications when installing, operating and maintaining
SolarLake inverter.
1. Get permission from the local electricity supplier before connecting inverter to the grid.
2. All installation work must comply with local installation standards and regulations.
3. High voltage will be present when the inverter is working. Switch off AC/DC power and wait for at least 5
minutes before undertaking any maintenance work.
4. Some areas of the inverter could be very hot even after turning the inverter off.
Warning!
Pay attention to the rated voltage and current when design the system.
4.3 Precaution
Before starting installation please check the site to ensure the following.
● Temperature at the site is likely to be within permitted range of -20°C to +60°C.
● Site altitude is less than 2,000m above sea level.
● Inverter not likely to be exposed to by sea water.
● Inverter is not close to corrosive gas or liquid (for example, avoid locations where chemicals are processed
or poultry farm).
● Inverter is not exposed to direct sunlight.
● Not likely to be flooded or snowed in.
● Good ventilation .
● Not exposed to steam, vapor, or water.
● Not close to television antenna or antenna cable.
If the installation does not meet the above conditions, the product warranty may become void.
Please provide the clearance shown in the drawing below as a minimum. Minimum clearance is essential
for servicing product warranty.
50cm
Side 50cm
Bottom 50cm
Standard 11-04-03 10:12:17
Today
14.6 kwh
5 hours 1 minutes
Total
52.7 kwh
5 hours
Esc OK
Normal
15.21 kw 14.60 kw
49.99 Hz
Front 50cm
50cm
max 15
14
Installation
4.4 Preparation
Following tools may be needed for correct inverter installation.
Tools: Crimping pliers, Screw drivers and Manual wrench and drill machine, and rubber hammer.
Step 1 Step 2
Step 3 Step 4
15
Installation
Warning!
Ensure that the DC side is not powered at the time of connecting. Note that the
capacitors could be charged even after turning the inverter off, hence wait at least
5 minutes before opening the inverter lid.
Attention!
Only qualified and trained electrical engineers should install inverters.
Danger!
Before the electrical connection, make sure to use opaque material to cover the
PV array or disconnect PV panels. While exposed to sun light, PV array will produce
dangerous voltage.
Note!
There are 2 independent MPP trackers in Solar Lake inverters. PV arrays connected
to each MPP tracker must be of the same make and model and receive the same
solar radiation at all times.
There are 2 independent MPP trackers in the SolarLake inverters. While common-string or multi-strings
input connections can be used we suggest multi-strings to harvest max. PV energy.
Output Output
Figure 11 Multi-string input connection (Left) and common-string input connection (Right)
16
Installation
Note: Make sure to select the right PV string connection setting while commissioning. Please refer to
parts 5.3 and 6.2 for details.
Please use good quality PV modules with Samil Power Inverters. Ensure that the open-circuit voltage of
array is less than the Max. Input DC input voltage of the inverter. Also the operating voltage should be
within the MPPT range of the inverter.
MPPT voltage range 320~800 Vdc 380~800 Vdc 380~800 Vdc 430~800 Vdc
Please use standard PV cable to connect modules to inverter. Use fast action string fuses meeting Country
regulations. Suggest the inverter is installed close PV module in order to reduce PV cables as well as
reduce DC side losses.
Note!
Please don’t connect the PV panel positive or negative to ground except for thin
film panels.
4.6.3.1 Procedure
Step 2: Strip about 8mm length of insulation from the string cables, and then insert the bare wire core
into core tube of connectors and crimp the connection using crimping tool.
Step 3: Insert the cable with the tube core into the fastening nut.
Step 4: Insert the core tube into slot of connection until clicked into place.
Step 5: Tight the nuts to complete the connection.
17
Installation
Use string fuses and external DC switches on the string cables as per Country regulations.
Step 1: Check DC open circuit voltage of the strings to make sure that the voltages are within the
inverter range. Do note that the voltage is subject to solar radiation.
Step 2: Connect the positive and negative string cables to the DC connectors on the inverter.
Note: There are 4 pairs of DC terminals on SolarLake inverters. Left two are DC input terminals for
MPPT 1 and marked PV1. The two on the right DC input terminals for MPPT 2 and marked PV2. Grounding
of PV1 and PV2 should not be connected together, failure will result in fault message. Check the string
cable polarity and voltage range before connection.
Warning!
DC string voltage is likely to be very high. Avoid contact with live cables and
comply with all electric safety rules.
If any problem or concern is found with the String power, those need to be
sorted out before connecting to the Inverter.
18
Installation
SolarLake series inverters are designed for three phases grid connection only. Voltage across phase can
be 230±20%, but these need to be set to Country regulations. Typical grid frequency is 50Hz.
Note: For safety reasons, suitable cables should be used. Unsuitable cable may lead to cable getting
heated which could result in fire and serious risks.
Esc OK
Input
Output
19
Installation
4.6.5 Grounding
Attention!
As SolarLake inverters are Transformer less units, DC Positive or Negative terminals
should be grounded. Failure will result in inverter damage.
PV String
Inverter AC Switchboard
L1
L2
L3
N
PE
Earth
Link
PV module frame
20
Commissioning of inverter
5 Commissioning of inverter
5.1 Start inverter
Attention!
Ensure that DC and AC voltages are within the range permitted by the inverter.
Note!
If the inverter shows faults, please refer to part 8——error messages.
Inverter should enter standard interface automatically after startup (If not , press “ESC” to go to standard
interface) shown in figure 17.
Total
52.7 kwh
5 hours
Normal
15.21 kw 14.60 kw
49.99 Hz
21
Commissioning of inverter
In the standard interface display press “ESC” button to enter the main menu shown in figure 18.
Instantaneous
History
Event List
Settings
System Info
Press the “down arrow key” to move the cursor to Settings and press “OK” key to enter setup interface,
shown in figure 19.
Language Calibration
Time Update
Country LCD
AutoTest Ita. Clear Prod.
Click on " Country" and OK to enter the local country setting interface shown in figure 20.
Commissioning Country
Germany GreeceContin.
Italy GreeceIslands
Australia Netherland
Spain Belgium
Czech Bulgaria
Germany
VDE0126-1-1
Current:Germany
Select the correct Country setting and OK it. The inverter may ask for a password which is 000111. Enter
the password and press “OK” to confirm the selection. The display should return to standard interface.
Note!
When setting Country, PV array connection type and Factory reset , please use
password 000111.
22
Commissioning of inverter
Total
52.7 kwh
5 hours
Normal
15.21 kw 14.60 kw
49.99 Hz
Instantaneous
History
Event List
Settings
System Info
Language Calibration
Time Update
Country LCD
AutoTest Ita. Clear Prod.
Commissioning Input
Common-String
Multi-String
Current : Common-String
Please refer to section 4.6.2" PV array connection types " for information on PV array connection options.
6 Operation
6.1 Control and display panel
Red LED
Green LED
Buttons
LCD
There are 6 buttons next to the display for programming the inverter.
OK: to confirm selection.
ESC: to exit current screen or selection
Up: to move up or increase value
DOWN: to move down or decrease value.
RIGHT: to move right or increase the backlight.
LEFT: to move cursor left or decrease the backlight.
Total
52.7 kwh
5 hours
Normal
15.21 kw 14.60 kw
49.99 Hz
There are two LEDS on the front panel of the inverter to indicate inverter operation status.
24
Operation
Wait State: Inverter is waiting to Check State at the end of reconnection time. In this state, the PV voltage
is more than 250V and grid voltage value is between the max and min limits; If not, Inverter will go to Fault
State or Permanent State.
Check State: Inverter is checking isolation resistor, relays, and other safety requirements. It also does
self-test to ensure inverter software and hardware are functional. Inverter will go to Fault State or Permanent
State if any error or fault occurs.
Normal State: Inverter is feeding power to the grid.
Fault State: Inverter has encountered recoverable error. It should recover if the errors disappear. If Fault
State coninues check the inverter according error code in table 6,7,8, and 9.
Permanent State: Inverter has encountered unrecoverable error. It will stay in the Permenent State till
corrective action is taken.
Total
52.7 kwh
5 hours
Normal
15.21 kw 14.60 kw
49.99 Hz
In the standard interface press “ESC” button to enter the main menu shown in figure 28.
Instantaneous
History
Event List
Settings
System Info
Enter " Instantaneous" to see input and output voltages, current, power, temperature, and other real-time
information.
Enter " History" to see the power generation histogram of every hour. By pressing the left or right arrow
one can see the DC input power curve, the AC output power curve, daily energy production for a month
and also total output data.
25
Operation
Enter " Event List" to see the list of events recorded by the inverter. Up to 100 recent events recorded
can be viewed by pressing “OK” one can see detailed information, including the occurrence time and error
code.
It is possible to reset the inverter to factory set if that is necessary. A password will be required for this
operation.
Date and time settings
Date and time settings interface as shown in figure 29, set according to the local date and time. Then,
press “OK” key to enter the next step.
Commissioning Time
YYYY MM DD
2011 - 04 - 03
hh mm ss
10 : 04 : 47
Germany
Common-String
26
Operation
Language Calibration
Time Update
Country LCD
AutoTest Ita. Clear Prod.
Operate a new AutoTest according to “ GUIDA PER LE CONNESSIONI ALLA RETE ELETTRICA DI
ENEL DISTRIBUZIONE, Ed. 2.2, Dicembre 2011”
1. Before performing the AutoTest, confirm that the country setting “Italy” and that the inverter is running
in normal state.
2. On the display Main Menu find Settings → AutoTest Ita. as per fig.35 and press OK. Then select “New
Autotest”, press OK, and after few seconds, you can see “(OK) to start Grid R V_max” on the LCD.
3. Press OK button to start grid R V_max test, or press ESC button to exit from “New Autotest”. If there
is no button operation within 5 seconds, the test will start automatically. If the test has started, key
operation is invalid until test is over.
4. After grid R V_max test is over, the LCD will show the result and “(OK) to start V_min”. The inverter will
reconnect automatically.
5. Press OK button to start grid R V_min test. Alternatively press ESC button to exit from “New Autotest”.
If there is no button operation within 5 seconds, the test will start automatically. If the test has started,
key operation is invalid until test is over.
6. After grid R V_min test is over, the LCD will show the result and “(OK) to start F_max”. The inverter
will reconnect automatically.
7. Press OK button to start grid R F_max test. Alternatively press ESC button to exit from “New Autotest”.
If there is no button operation within 5 seconds, the test will start automatically. If the test has started,
key operation is invalid untill this test is over.
8. After grid R F_max test is over, the LCD will show the result and “(OK) to start F_min”. The inverter
will reconnect automatically.
9. Press OK button to start grid R F_min test. Alternatively press ESC button to exit from “New Autotest”.
If there is no button operation within 5 seconds, the test will start automatically. If the test has started,
key operation is invalid untill this test is over.
10. After grid R F_min test is over, the LCD will show the result and “(OK) to start Grid S V_max”.The
inverter will reconnect automatically.
11. Press OK button to start grid S V_max test. Alternatively press ESC button to exit from “New Autotest”.
If there is no button operation within 5 seconds, the test will start automatically. If the test has started,
key operation is invalid untill this test is over.
12. After grid S V_max test is over, the LCD will show the result and “(OK) to start V_min”. The inverter
will reconnect automatically.
13. Press OK button to start grid S V_min test. Alternatively press ESC button to exit from “New Autotest”.
If there is no button operation within 5 seconds, the test will start automatically. If the test has started,
key operation is invalid untill this test is over.
14. After grid S V_min test is over, the LCD will show the result and “(OK) to start F_max”. The inverter
will reconnect automatically.
15. Press OK button to start grid S F_max test. Alternatively press ESC button to exit from “New Autotest”.
If there is no button operation within 5 seconds, the test will start automatically. If the test has started,
key operation is invalid untill this test is over.
27
Operation
16. After grid S F_max test is over, the LCD will show the result and “(OK) to start F_min”. The inverter
will reconnect automatically.
17. Press OK button to start grid S F_min test. Alternatively press ESC button to exit from “New Autotest”.
If there is no button operation within 5 seconds, the test will start automatically. If the test has started,
key operation is invalid untill this test is over.
18. After grid S F_min test is over, the LCD will show the result and “(OK) to start Grid T V_max”, The
inverter will reconnect automatically.
19. Press OK button to start grid T V_max test. Alternatively press ESC button to exit from “New Autotest”.
If there is no button operation within 5 seconds, the test will start automatically. If the test has started,
key operation is invalid untill this test is over.
20. After grid T V_max test is over, the LCD will show the result and “(OK) to start V_min”.The inverter
will reconnect automatically.
21. Press OK button to start grid T V_min test. Alternatively press ESC button to exit from “New Autotest”.
If there is no button operation within 5 seconds, the test will start automatically. If the test has started,
key operation is invalid untill this test is over.
22. After grid T V_min test is over, the LCD will show the result and “(OK) to start F_max”.The inverter
will reconnect automatically.
23. Press OK button to start grid T F_max test. Alternatively press ESC button to exit from “New Autotest”.
If there is no button operation within 5 seconds, the test will start automatically. If the test has started,
key operation is invalid untill this test is over.
24. After grid T F_max test is over, the LCD will show the result and “(OK) to start F_min”. The inverter
will reconnect automatically.
25. Press OK button to start grid T F_min test. Alternatively press ESC button to exit from “New Autotest”.
If there is no button operation within 5 seconds, the test will start automatically. If the test has started,
key operation is invalid untill this test is over.
26. After grid T F_min test is over, the LCD will show the result and “(Esc) to exit”. The inverter will
reconnect automatically.
27. The autotest function is considered successful once all the previous 12 tests have been performed.
When LCD shows “(Esc) to exit”, press ESC button to exit from “New Autotest” .
Note: If an unexpected grid disconnection occurs during the autotest, the autotest is interrupted. The
LCD will show "AutoTest break! (OK) to exit". Press OK button or ESC button to exit from “New Autotest”.
Disconnect the AC breaker from all 3 phases and prevent it from being reactivated, disconnect the DC
switch for 5 minutes and connect it again. The inverter is now initializing and the autotest procedure can
be restarted.
Note: If user exits from “New Autotest” when any of the previous 12 tests haven’t been performed yet,
the inverter will not record any of the test results.
Procedure of viewing AutoTest results from the inverter’s LCD
Enter Main Menu, then enter Settings sub-menu, select “AutoTest.”, then select “Last Results” , press OK
button, the LCD will show the latest results’ time in terms of a list. The latest result shows on the top.
Press DOWN or UP button to select a result and press OK to view the detail. When entering the detail
screen, test results of grid R are shown, press RIGHT or LEFT button to view other phases’ results. Press
ESC button to exit from detail screen.
Procedure of viewing AutoTest results from PC
Note: After a new AutoTest is finished, the results’ data can be sent to a PC through the RS-232 port
between the inverter and PC, a “txt” format report can be automatically created. The detailed operation
procedures are as follows:
28. Open the “Enel.exe” file shown in figure 31 in PC(User can request “Enel.exe” application software at
[email protected]), a "Report" folder will created in the same “Enel.exe“ file directory, and each “txt”
report generated will be stored into the "Report" folder, as shown in Figure 32.
28
Operation
Figure 32
Figure 33
29. Select the corresponding models and communication port (PC and the inverter connection port: com1
~ com9), as shown in figure 34 and figure 35.
Figure 34 Figure 35
30. By clicking "OK" button, the “software Enel.exe” automatically reads the inverter’s LATEST test data,
and generates a “txt” format report, as shown in figure 36 and figure 37.
Figure 36
29
Operation
Figure 37
31. If you click “OK” button, a warning message as shown in figure 38 appears, please check the RS-232
communication connection between the Inverter and PC.
Figure 38
In figure 38, press any arrow key to move the cursor to the" System Info" and then press “OK”, you will
see the machine serial number, software version and so on. Press “ESC” and will return to the superior
interface progressively.
30
Operation
6. LVRT: Low voltage ride through enabled and low voltage ride through parameter setting.
7. Active power derating settings
8. Safety parameters setting
Figure 39
B: Click the serial number, the interface is shown as following figure, set the safety parameters of this
inverter. Detailed settings refer to step 3.
Figure 40
31
Operation
Setp 2: Click “CEI0-21/A70” on the top of navigation bar, configure parameters conforming to standard of
CEI 0-21
Figure 41
A: Fixed cosphi setting, as the following figure. Click on the drop-down menu, select Overexcited or
Underexcited, fill in the cosphi value which range from 0.9 to 1.
Figure 42
B: Fixed reactive power settings, as the following figure. Click on the drop-down menu, select Overexcited
or Underexcited, fill in the reactive power which unit is Var.
Figure 43
32
Operation
C: cosphi=f(P), as the following figure. Click on the drop-down menu, select Overexcited or Underexcited,
fill in cosphi value, ratio of P and Pn. Lock-in Voltage、Lock-out Voltage correspond to the voltage value of
the reactive power production or not.
Figure 44
Cos-phi
P1 P2 P3
1
0.2 0.5 1 P/Pn
0.95
Figure 45
D: Q=f(V), as the following picture. Parameters displayed are default parameters. U1s、U2s、U1i、U2i are
the settable four points of Q value which range from 0.90-1.10, Lock-in Power、Lock-out Power correspond
to the active power value of the reactive power production or not. Mode A and mode B refer to the following
figures.
Figure 46
33
Operation
Figure 47
E: Low voltage ride through setting, as the following picture. Parameters displayed are default parameters .
U/Uc and T are 4 points of LVRT.
Figure 48
Po
100%
P3,P4
50%
P1,P2
0%
0 300
T(ms)
Figure 49
F: P=f(F), as the following picture. Slope range is 2%-5%, the default slope is 2.4%.
34 Figure 50
Operation
Pm
Slope(%/ Hz)
Figure 51
G: Active power derating settings, as the following picture. Fill in the ratio of the active power and rated
active power, the range is 0%-100%, and the default is 100%.
Figure 52
Po
100%Pn
100% 50%Pn
Active power In
50%
0%
t
Figure 53
35
Operation
Step 3: Inverter safety parameters setting, as the following picture. Before setting, click “Read” to refresh
current data then set parameters, click “save” at last. The following picture shows default parameters of
CEI 0-21.
Figure 54
Parameters explanation:
Name Explanation
36
Operation
Continued:
6.5 BDEW
The followings items can be set by Solar Browser
1. Fixed cosphi setting: Set cosphi to a fixed value.
2. Fixed reactive power setting: Set reactive power to a fixed value.
3. Cosphi=f(P): Cosphi as a function of active power generated by the inverter.
4. Q=f(V): Reactive power as a function of the grid voltage measured by the inverter.
5. P=f(F): Active power as a function of the frequency measured by the inverter.
6. LVRT: Low voltage ride through enabled and low voltage ride through parameter setting.
7. Active power derating settings
8. Safety parameters setting
Figure 55
B: Click the serial number, the interface is shown as following figure, set the safety parameters of this
inverter. Detailed settings refer to step 3.
37
Operation
Figure 56
Setp 2: Click “BDEW” on the top of navigation bar, configure parameters conforming to standard of BDEW
Figure 57
A: Fixed cosphi setting, as the following figure. Click on the drop-down menu, select Overexcited or
Underexcited, fill in the cosphi value which range from 0.9 to 1.
Figure 58
38
Operation
B: Fixed reactive power settings, as the following figure. Click on the drop-down menu, select Overexcited
or Underexcited, fill in the reactive power which unit is Var.
Figure 59
C: cosphi=f(P), as the following figure. Click on the drop-down menu, select Overexcited or Underexcited,
fill in cosphi value, ratio of P and Pn.
Figure 60
Cos-phi
P1 P2 P3
1
0.2 0.5 1 P/Pn
0.95
Figure 61
39
Operation
Figure 62
Q(%)
48%
UQ0(100%)
0%
94.2% 104.8% U(%)
-48%
Figure 63
E: Low voltage ride through setting, as the following picture. Parameters displayed are default parameters .
U/Uc and T are 4 points of LVRT.
Figure 64
40
Operation
Po
100%
P3,P4
50%
P1,P2
0%
0 0.6 2
T(s)
Figure 65
F: P=f(F), as the following picture. Slope range is 2%-5%, the default slope is 5%.
Figure 66
Figure 67
G: Active power derating settings, as the following picture. Fill in the ratio of the active power and rated
active power, the range is 0%-100%, and the default is 100%.
Figure 68
41
Operation
Po
100%Pn
100% 50%Pn
Active power In
50%
0%
t
Figure 69
Setp 3: Inverter safety parameters setting, as the following picture. Before setting, click “Read” to refresh
current data then set parameters, click “save” at last. The following picture shows default parameters of
BDEW.
Figure 70
Parameters explanation:
Name Explanation
42
Communication and monitoring
Continued:
RS232 is an optional communication interface which can transmit data between PC and one single SolarLake
inverter (figure 71).
Only one inverter can communicate with a PC through RS232 port. Hence this is normally used for service
requirements like software update and checking the inverter performance.
RS485 port can be used for communicating upto 32 inverters at the same time. The total length of the
communication cable needs to be less than 1200m. One can also use the RS485 port for communicating
with SolarLog. Please refer to SolarLog manual for more information on using SolarLog.
43
Communication and monitoring
WAN
Router
Auto IP
Static IP
IP Address
Subnet Mask
Gateway
DNS Server
<ESC> to confirm
44
Troubleshooting
Auto IP
Static IP
IP Address 192.168.000.002
Subnet Mask 255.255.255.000
Gateway 000.000.000.000
DNS Server 000.000.000.000
<ESC> to confirm
Note!
① Need to install SolarLake Inverter Monitoring software Solar Power Browser on
the PC when using RS232 or Ethernet communication.
② Can’t using RS232, RS485 and Ethernet communication mode at the same time
③ The default setting is “Auto IP”.
④ In WAN mode, router is necessary and auto IP mode should be selected.
⑤ WAN is not available currently
8 Troubleshooting
8.1 Troubleshooting
This section contains information and procedures for solving possible problems with the SolarLake series
inverters, and provides user with troubleshooting tips to identify and solve most problems that could occur.
In case of problem with inverter, check the following tips.
● Check the warning fault messages or Fault codes on the inverter information panel. Record it before doing
anything further.
● Attempt the solution indicated in Tables 6 ,7,8,9 and 10.
● If inverter information panel is not displaying any Fault, check the following to make sure that the installation
allows proper operation of the unit.
- Is the inverter located in a clean, dry, adequately ventilated place?
- Have the DC input breakers switched on?
- Are the cables adequately sized and short enough?
- Are the input and output connections and wiring in good condition?
- Are the configuration settings correct for the particular installation?
- Are the display panel and the communications cable properly connected and undamaged?
If necessary, contact Samil Power Customer Service for further assistance. Please be prepared to describe
details of the system and provide the model and serial number of the unit.
To view recorded problems if any follow the steps below.
Press “ESC” to enter the main menu in the normal interface. In the interface screen select “Event List”, then
press “OK” to enter events list like figure 76.
45
Troubleshooting
When SolarLake Inverter is at fault, the fault information is composed of “group+code”. There are three
kinds of faults related to grid, PV or inverter. The fault code indicates a like "Grid 3" indicates under voltage
L2 phase.
The events list also displays the type of event, code, occurring time and current status.
Use the right, left, up or down to move through the list and press OK to view the selected even as shown
in Figure 77.
The event details show event type, code, occurring time and rectification hints.
If further help is needed please contact Samil Power technical help line.
46
Troubleshooting
0 L1 phase over-voltage
1 L1 phase under-voltage
2 L2 phase over-voltage
3 L2 phase under-voltage
4 L3 phase over-voltage
① Check whether AC grid
5 L3 phase under-voltage
voltage and frequency are
6 Over-frequency with in permitted limits.
7 Under-frequency ② Check whether the AC
Grid
8 DC component of L1 phase is too large connection is correct;
9 DC component of L2 phase is too large ③ Contact installer for help.
10 DC component of L3 phase is too large
11 L1 phase over- frequency
12 L1 phase under- frequency
13 L2phase over- frequency
14 L2phase under- frequency
15 L3 phase over- frequency
16 L3 phase under- frequency
47
Troubleshooting
0 Start working
9~29
41 Over-current of output(RMS)
Check whether the string
42 Choose input mode error connection and setting on the
inverter.
Ask for help if still at fault after
43 Self- checking error
rebooting.
48
Troubleshooting
Continued:
57 Unrecover IAC_RMS_imbalance
58 Fan 1 error
Note: “Without any remedy” means that the event is not an error, or inverter will resume working automatically.
49
Decommissioning
9 Decommissioning
9.1 Decommissioning steps
1 Switch off the AC grid
2 Switch Off the DC switch
3 Wait for 5 minutes
4 Release the DC connectors
5 Release the AC terminals using screw drivers.
Remove inverter from the mounting carefully to avoid ingury. Please note that the SolarLake inverters
weight over 50 kgs.
9.2 Package
If possible, please pack the inverter in the original packaging. If original packing it is not available, use an
equivalent carton suitable for loads more than 50 kg, has handle and can be closed fully.
9.3 Storage
Store the inverter in a dry place where ambient temperature is between -25 and - +70 °C.
9.4 Disposal
At the end of its life, dispose inverters and packing materials at locations that can handle and or recyle
electric equipment safely.
50
Technical data
10 Technical data
10.1 Input (DC)
Min. DC voltage /
start voltage [V] 160/210 160/210 160/210 160/210
51
Technical data
Overvoltage / Undervoltage
Yes Yes Yes Yes
protection
DC isolation impedance
Yes Yes Yes Yes
monitoring
Weight [kg] 40 40 40 40
Operating temperature
-20 °C ~ +60 (Derating at 45 °C)
range [°C]
Pollution Degree II
Topology Transformerless
Standard warranty(Year) 5
52
Manufacturer’s warranty and liability clauses
53
SAMIL POWER CO., LTD.
Marketing & Sales Office Factory
Add: No.52,Huigu Innovation Park, Huishan District, Add: No.66 Taihangshan Road,
Wuxi,Jiangsu Province,P.R.China 214174 Suyu Economic Development Zone, Suqian City,
Tel: +86 510 83593131 Jiangsu Province, P.R.China 223800
Fax: +86 510 81819678 Tel: +86 527 88754666
E-mail:[email protected] Fax: +86 527 84453877
http://www.samilpower.com