F600 Frame 3 To 11 Step by Step Guide Issue 3
F600 Frame 3 To 11 Step by Step Guide Issue 3
F600 Frame 3 To 11 Step by Step Guide Issue 3
Frame sizes 3 to 11
www.controltechniques.com/support
Diese Anleitung
This guide bietet
provides Informationen
a fast and simplefür eine schnelle
start-up Inbetriebnahme
procedure eines
for a basic drive andeinfachen Umrichter-Motor-Systems.
motor installation.
Bei
For aufwendigeren
help with more Systemen: UmfassendeComprehensive
Betriebsanleitungen, Online-Videos und Hilfsmittel
and helpfinden Sie be
unter
Seite
Page 22
advanced installations: user guides, online videos tools can
unserer Webadresse oder über den vorstehenden QR-Code.
accessed using the web address or QR code above.
EN
DE Bitte lesen Sie die dem Umrichter beiliegende Sicherheitsdokumentation, bevor Sie den Umrichter montieren oder
Please
in read
Betrieb the safety information booklet supplied with the drive before installation or set-up.
nehmen.
It is essential
Beim M300 istto read Section
unbedingt 4.4 in the4.2
der Abschnitt F600 User
in der Guide using
Steuerung the web address
– Kurzanleitung überor
dieQR code abovebzw.
Webadresse priorden
to using the Safe
vorstehenden QR-Code Torquehinzuzuziehen,
Off function inumsafety systems.
die Safe Torque Off-Funktion in Sicherheitssystemen zu verwenden.
control pod 10 13 13 13
8
7
16
9 16 16
15 13 16 15 14 16 14 15 15 14
16
15
15
16 15
16 16
12 13 12 13
15
16
12 13
16
12
14
16
12
14
12
16
14
16 12
14
Key
1. Keypad connection 9. Communications port
2. Rating label 10. NV media card slot
3. Identification label 11. Internal EMC filter
4. Option module slot 1 12. DC bus +
5. Option module slot 2 13. DC bus -
6. Option module slot 3 14. Motor connections
7. Relay connections 15. AC supply connections
8. Control connections 16. Ground connections
11 12
10
8
7
11 13
14
Key
1. Keypad connection 8. Control connections
2. Rating label 9. Communications port
3. Identification label 10. NV media card slot
4. Option module slot 1 11. Ground connections
5. Option module slot 2 12. AC supply connections*
6. Option module slot 3 13. DC bus +
7. Relay connections 14. Motor connections
*Common AC Supply connections are internally linked on the 11E 6 pulse drive
1
F600-034 00123 A
SAFETY
KIT BOX*
INFORMATION
STEP BY STEP
GUIDE
* With frame size 7 to 11, surface mounting brackets are also supplied with the drive.
F600 - 05 4 00270 A
The voltage rating of fuses must be greater than or equal to the highest supply voltage of the system.
Fuses: The AC supply to the drive must be installed with suitable protection against overload. Failure
to observe this requirement will cause risk of fire.
WARNING
NOTE The product is UL listed for use on a circuit up to 100 kA maximum supply symmetrical fault current,
when protected by fuses.
NOTE IEC cable sizes assume Copper conductor, PVC insulation, Installation method B2 and ambient
temperature of 40 °C (104 °F). UL cable sizes assume Copper conductor with insulation rated at 75 °C
(167 °F).
Table 4-1 200 V drive ratings, cable sizes and fuse ratings (200 V to 240 V ±10 %)
Max. Nominal cable size
cont. Fuse Normal Duty
European USA
input
current IEC UL Max.
Model Nom Motor
count.
Input Output Input Output power power
3ph Nom Nom output
@ 230 V @ 230 V
Class Class current
A A A mm² mm² AWG AWG A kW hp
03200066 10.4 16 20 1.5 1.5 14 14 6.6 1.1 1.5
03200080 12.6 20 20 CC, J 1.5 1.5 14 14 8 1.5 2
gG
03200110 17 20 25 or T* 4 4 12 12 11 2.2 3
03200127 20 25 25 4 4 12 12 12.7 3 3
04200180 20 25 25 CC, J 6 6 10 10 18 4 5
gG
04200250 28 32 30 or T* 8 8 8 8 25 5.5 7.5
CC, J
05200300 31 40 gG 40 10 10 8 8 30 7.5 10
or T*
06200500 48 63 60 CC, J 16 16 4 4 50 11 15
gG
06200580 56 63 70 or T* 25 25 3 3 58 15 20
07200750 67 80 80 35 35 2 2 75 18.5 25
CC, J
07200940 84 100 gG 100 35 35 1 1 94 22 30
or T*
07201170 105 125 125 70 70 1/0 1/0 117 30 40
08201490 137 200 200 6 95 3/0 3/0 149 37 50
gR HSJ
08201800 166 200 225 2 x 70 2 x 70 2x1 2x1 180 45 60
2 x 70 2 x 95
09202160 205 250 250 2 x 2/0 216 55 75
(B1) (B2)
gR HSJ
2 x 95 2 x 120
09202660 260 315 300 2 x 4/0 266 75 100
(B1) (B2)
2 x 120
10203250 305 400 400 2 x 250 325 90 125
(B1) 2 x 120
gR HSJ
2 x 150 (B2)
10203600 361 450 450 2 x 300 360 110 150
(C)
A 1 2
A: Size 3 to 11
1 2 B: Size 5 only
B
C: Size 6 only
D: Size 7 to 11
1 2 Place finger-guard on a flat solid surface and hit
relevant break-outs with hammer as shown (1).
For sizes 7 to 9 pliers can be used to remove the
break-outs, grasp the relevant break-out with the
pliers and twist it as shown (3). Continue until all
1 2
required break-outs are removed (2). Remove any
C
flash / sharp edges once the break-outs
are removed.
Finger guard grommets are supplied in the kitbox for
size 5 and 6.
D
3
2
DC Connections
+DC
-DC
Additional ground
connection
1
Ground connection
AC Connections studs
PE L1 L2 L3 U V W
Optional
EMC filter
Optional
line reactor
Fuses
Motor
L1 L2 L3
Mains Optional ground
Supply
supply connection
ground
The drive must be connected to the system ground of the AC supply. The ground wiring must
conform to local regulations and codes of practice.
The ground loop impedance must conform to the requirements of local safety regulations.
The drive must be grounded by a connection capable of carrying the prospective fault
current until the protective device (fuse, etc.) disconnects the AC supply.
WARNING The ground connections must be inspected and tested at appropriate intervals.
Main process
PID Feedback
4-20 mA input
Drive active
Relay 1
Drive Healthy
(240 Vac, installation
over-voltage category II)
Unassigned Relay 2
(240 Vac, installation
over-voltage category II)
1 2 3
To install, align the KI-485 Adaptor and press gently in the direction shown until it clicks into position.
To remove, reverse the installation instructions.
NOTE IEC cable sizes assume Copper conductor, PVC insulation, Installation method B2 and ambient
temperature of 40 °C (104 °F). UL cable sizes assume Copper conductor with insulation rated at 75 °C
(167 °F).
When using the Control Techniques converters or any other suitable converter with the drive, it is
recommended that no terminating resistors be connected on the network. It may be necessary to
disconnect the terminating resistor within the converter depending on which type is used.
1. Escape button
2. Auto Inhibit
3. Hand Inhibit STO
4. Navigation keys (x4) 0.0Hz
5. OFF/ Reset
6. Enter button
Parameter
Mode Then returning
to Parameter
Mode use the
Temporary
Parameter
Mode
To select parameter
Press
keys to select
another parameter
to change, if required
Edit Mode
( is displayed)
(Character to be edited in lower line of display flashing)
The default status display shows the drive status, the Pump software status and the motor Frequency or Speed.
Inhibit
Inhibit STO
0.0Hz
Select “Induction” Set Motor Type Pr 0.004 to Induction and press the red OFF / Reset button to change the
motor. mode. This selects open-loop (OL) control for an induction motor.
Motor Type
OFF
Induction Reset
If “Induction” is already shown, then skip this step.
Configure the motor • Set Rated Current Pr 0.006 to the motor rated current in Amps.
name plate details. • Set Rated Speed Pr 0.007, the motor rated speed in rpm.
• Set Rated Voltage Pr 0.008, the motor rated voltage in Volts.
• Set Rated Power Factor Pr 0.009, the motor rated power factor, (cos phi or cos φ).
Configure motor If a normally closed motor thermal protection switch has been connected, (contacts closed =
thermal protection. temperature OK, contacts open = temperature fault), set Motor Thermal Protection Enable
Pr 0.017 to On. Otherwise leave Pr 0.017 set to Off.
Motor Thermal Pr
otection Enable
Off
50.0Hz
50.0
It may be required when running to reduce this value if pump cavitation is suspected during
operation.
Set the Hand Mode Set Hand Mode Reference Pr 0.026 to configure the frequency reference used in Hand
Reference mode. By default, this is half of the motor rated frequency
frequency. Hand Mode
Reference
25.0Hz
25.0
Enable the drive. Close the Enable or Safe Torque Off input switch to the drive. The pump software status
changes to Off (Ready).
Inhibit
O f f (R e a d y)
0.0Hz
Start the motor in Make sure it is safe to run the motor. Press and hold the green Hand button for 2 s or close
Hand mode. the Hand switch. The motor will turn at the Hand mode speed reference and the pump
software status changes to Hand Run.
Run
Hand Run
25.0Hz HAND
If the application requires more starting torque to get the motor turning, e.g. a waste water
pump, increase Low Frequency Voltage Boost Pr 0.011, in 1 % steps. If 5 % is reached and
the motor still does not turn, stop the Motor by pressing the red OFF / Reset button or by
opening the Hand switch. The pump software status changes to Off (Ready).
Inhibit
O f f (R e a d y) OFF
0.0Hz
Reset
When safe to do so, check the application for physical items that may be preventing the
motor from rotating.
25.0Hz
25.0
If the motor appears to be running in the wrong direction, reverse two motor phases
electrically when safe to do so. Alternatively, set Reverse Output Phase Sequence Pr 0.018
to On to do this in software, and Set Pr 0.000 to Save Parameters and press the red OFF /
Reset button.
Reverse Output
Phase Sequence
On
Parameter mm.000
OFF
Save parameters Reset
Stop the motor. Stop the motor by pressing the red OFF / Reset button or by opening the Hand switch. The
pump software status in changes to Off (Ready).
Inhibit
O f f (R e a d y) OFF
0.0Hz
Reset
Inhibit
I n h i b i t STO
0.0 r p m
Select Permanent- Set parameter Pr 0.004 to Permanent-magnet and press the red OFF / Reset button to
magnet motor. change the mode. This selects closed-loop sensorless (RFC-S) control for a permanent-
magnet motor.
Motor Type
OFF
Permanent-magnet Reset
If Permanent-magnet is already shown, then skip this step.
Configure If a normally closed motor thermal protection switch has been connected, (contacts closed =
Motor Thermal temperature OK, contacts open = temperature fault), set Motor Thermal Protection Enable
Protection. Pr 0.017 to On. Otherwise leave Pr 0.017 set to Off.
Motor Thermal Pr
otection Enable
Off
Set the Maximum The Maximum Reference Clamp, Pr 0.022 normally matches the motor name plate speed as
Reference Clamp. entered in Pr 0.007.
Maximum
Reference Clamp
1500.0 rpm
It may be required when running to reduce this value if pump cavitation is suspected during
operation.
Set the Hand Set the Hand mode digital frequency speed reference Pr 0.026. By default, this is half of the
Reference Speed. motor rated speed.
Hand Mode
Reference
750.0rpm
Select the auto-tune Set Pr 0.013 to Stationary to select a stationary auto-tune. The motor shaft will not rotate as
mode. a part of this test, however, as a precaution it should be treated as if will rotate.
Auto-tune
Stationary
Enable the drive. Close the Enable or Safe Torque Off input switch to the drive. The pump software status
changes to Off (Ready).
Inhibit
O f f (R e a d y)
0.0rpm
Auto-tune
Hand Run
0.0rpm HAND
The drive will run the auto-tune to measure the electrical properties of the motor.
The autotune process takes approximately 30 s.
When the Autotune is completed the pump software status changes to Inhibit STO.
The drive sequencer prevents the drive running in an unexpected way after the auto-tune.
To allow the motor to run after the auto-tune, do one of the following:
• Open the Enable or Safe Torque Off switch.
• Or press the red OFF / Reset button.
• Or open the Hand switch.
The pump software status changes to Off (Ready).
Inhibit
O f f (R e a d y)
0.0rpm
OFF
Reset
Does the motor If the motor has a pump attached or RFC Low Speed Mode Pr 0.014 = Injection, move to the
have a load? next step to Save the drive parameters.
RFC Low Speed
Mode
Injection
If the motor has no load attached e.g. for a basic bench test, and RFC Low Speed Mode
Pr 0.014 = Current, reduce the Low Speed Sensorless Mode Current Pr 0.015 to 50.0 %.
RFC Low Speed
Mode
Current
When the load is attached, increase Pr 0.015 back to 100.0%.
Save the drive Set Pr 0.000 to Save Parameters and press the red OFF / Reset button.
parameters.
Parameter mm.000
OFF
Save parameters Reset
Run
Hand Run
25.0Hz HAND
If instability is noted at high speed and load, additional filtering of the estimated speed
feedback may be required. Stop the motor by pressing the red OFF / Reset button or by
opening the Hand switch. The pump software status changes to Off (Ready).
Inhibit
Ready
0.0rpm
OFF
Reset
Increase the Sensorless Mode Filter value Pr 0.019 in single steps until the required
performance is reached. Stop and start the motor making sure it starts and runs at high
speed properly.
If the motor doesn’t start properly and there is significant starting torque required to turn the
load, check if the RFC Low Speed Mode Pr 0.014 = Injection. If it is set to “Injection” please
try setting Pr 0.014 to “Current” instead and Increase the Low Speed Sensorless Current
Pr 0.015 to 100 %.
Check the motor is All pumps have a direction to turn in for their main operation. Use the manufacturers data or
turning in the labels on the apparatus and compare to the direction of rotation of the cooling fan or motor
correct direction. output shaft. The Hand Mode Reference Pr 0.026 may need to be lowered to see the
direction.
Hand Mode
Reference
750.0rpm
If the motor appears to be running in the wrong direction, either reverse two motor phases
electrically, when safe to do so. Alternatively, set Reverse Output Phase Sequence Pr 0.018
to “On”.
Reverse Output
Phase Sequence
On
Parameter mm.000
OFF
Save parameters Reset
Stop the motor. Stop the Motor by pressing the red OFF / Reset button or by opening the Hand switch. The
pump software status changes to Off (Ready).
Inhibit
O f f (R e a d y) OFF
0.0rpm Reset
0.00 UU 100.00 UU
Note that all setpoints and feedback related parameters will use this scaling. The units of the
feedback and setpoint may be scaled into any unit type e.g. percent but on the display the
unit type will be shown as UU or User Unit.
Test the feedback Make sure it is safe to run the motor. Press and hold the green Hand button for 2 s or close
device. the Hand switch. The motor will turn at the Hand mode speed reference and the pump
software status changes to Hand Run.
Run
Hand Run
25.0Hz HAND
Observe the PID1 Feedback Pr 0.067 and vary the Hand Mode Reference Pr 0.026. The
PID1 Feedback Pr 0.067 should increase with an increase in Hand Mode Reference
Pr 0.026.
PID1 F e e d b a c k
43.21 %
If the feedback does not respond in proportion to the speed e.g. remains at 0. Please check
the configuration of the feedback device and wiring.
Find the frequency Observe the output of the application. Increase the Hand Mode Reference Pr 0.026 and
or speed where flow note the value when output flow is detected.
starts. Hand Mode
Reference
25.0Hz
25.0
The resulting value should be entered as the Positive Minimum Reference Clamp Pr 0.023.
Po siti ve M ini mum
Re fere nce Cla mp
22.00 Hz
Stop the motor. Stop the Motor by pressing the red OFF / Reset button or by opening the Hand switch. The
pump software status changes to Off (Ready).
Inhibit
O f f (R e a d y) OFF
0.0Hz
Reset
50.00 UU
Set the wake The wake threshold determines the feedback value, below which, the drive will start
threshold. operating and the minimum working feedback level, e.g. if the setpoint pressure is 50.00 %
and the wake threshold is 40.00 % the drive try to maintain its output between these values.
Set the Wake Detection Feedback Threshold Pr 0.040.
Wake Detect Fbck
Threshold
40.00 UU
Set the sleep The sleep threshold determines the frequency or speed below which the drive will stop
threshold. during normal operation. Set the Sleep Detect Speed Threshold Pr 0.042 to a value in the
order of 1 % to 5 % of motor rated frequency or speed above the Positive Minimum
Reference Clamp Pr 0.023 value.
Sleep Detect
Speed Threshold
25.00 Hz
Setting the sleep threshold less than the Positive Minimum Reference Clamp Pr 0.023 value
disables the sleep threshold.
Run in Auto mode. When it is safe to do so, run the system in Auto mode. To do this, press and hold the blue
Auto button for 2 s or close the Auto switch. The display will change to Auto Run.
Run
Auto Run
25.9 Hz AUTO
The application motor should run at a speed that controls the system output at the process
PID Setpoint 0 Pr 0.029.
If the system remains in the sleeping state, the process PID Final Feedback Pr 0.075 has
not fallen below the Wake Detection Feedback Threshold Pr 0.040.
Ready
Sleeping
0.0 Hz
43.21 UU 40.00 UU
Move to the next step when the drive is running in Auto mode.
Verify the sleep If the application has a discharge valve, slowly close it and make sure that the drive enters
threshold. the Sleeping state. If the sleeping state is not entered with a fully closed discharge valve,
note the frequency or speed while in this condition, and increase the Sleep Detect Speed
Threshold Pr 0.042 to 1 % to 5 % above the noted value.
Sleep Detect
Speed Threshold
27.00 Hz
Inhibit
O f f (R e a d y) OFF
0.0Hz
Reset
Save the drive Set Pr 0.000 to “Save Parameters” and press the red OFF / Reset button.
parameters.
Parameter mm.000
OFF
Save parameters Reset
Choose the Set Pump Control Mode Pr 0.021 to match the system. The options available are Single
operating mode and Pump, Cascade and Multi-leader.
additional features.
Pump & Fan
Control Mode
Single Pump
Configure the Pump system features required. See the user guide functional description
section or the Basic Features section for more details on the on the control modes and
features available.
Pipe Filling
In a pump application, when starting the drive in Auto mode but prior to automatic running, the drive
may optionally run a fixed reference pipe filling routine. The routine has a time limit, (maximum time),
to run which can be superseded by either reaching a PID feedback threshold or if flow is indicated
from a hardware flow switch. When the routine completes, the system moves to Auto Run where the
PID controls the motor speed.
Parameter Description
Pipe Fill Mode. Disabled (0), pipe filling is disabled. Feedback Level (1), pipe filling is
Pr 0.046 stopped when the main process PID level is reached. Flow Switch (2), pipe filling is
stopped when Flow Switch Input Pr 29.066 = On(1) indicating flow.
Pr 0.047 Pipe Fill Reference. The frequency or speed used while pipe filling.
Pipe Fill Maximum Time. The maximum time in seconds that the pipe fill routine will run for.
Pr 0.048 If the feedback level or flow switch indicates liquid in the pipe, the drive switches to auto
run.
Pipe Fill Threshold. This is the PID feedback level that must be reached to terminate the
Pr 0.049
pipe fill routine and not wait for Pipe Fill Maximum Time Pr 0.048 to elapse.
No Flow
The no flow by software detection scheme is intended to detect when there is no liquid flow due to a
closed pump discharge valve e.g. a closed tap. This is intended to be used in a pump system where
the main process PID feedback is a pressure transducer and not a flow transducer.
Parameter Description
No Flow Detect Threshold. This is a frequency or speed threshold below which No flow is
detected. This must be set higher than the Positive Minimum Reference Clamp Pr 0.023
Pr 0.055 or the Sleep Detect Speed Threshold Pr 0.042. When a pump discharge valve is closed,
the PID output will reduce to maintain pressure. No Flow Detect Threshold must be
greater than 0 to enable the feature.
No Flow Detection Band. This is a band above and below the No Flow Detect Threshold
Pr 0.056
Pr 0.045.
No Flow Detect Delay. When the process PID output is in the No flow detection band it
Pr 0.057 must remain there for No Flow Detect Delay to filter intermittent no flow frequency or
speed detection.
No Flow Setpoint Settling Delay. After the PID output is in the No flow detection band for
No Flow Detect Delay seconds, the main process PID setpoint is lowered by a small value
Pr 0.058 defined by No Flow Setpoint Reduction Pr 0.059. If after the reduction is applied the PID
output is still in the No Flow Detection Band, the system will be stopped due to no flow
where the drive will enter the “Sleeping” state.
No Flow Setpoint Reduction. This is the amount that the main process PID setpoint will be
Pr 0.059
reduced by in order to test to see if there is liquid flow.
Over-cycle protection
Over-cycle protection handles when the drive wakes and sleeps too many times in an hour.
Parameter Description
Over-cycle Mode. Disabled (0), over-cycle detection is disabled. Alarm Only (1), Pr 29.131
indicates when the over-cycle threshold has been reached this hour. Trip (2), the drive
Pr 0.059 trips Over-cycle when the Over-cycle Starts Per Hour Pr 0.061 is reached. Inc Setpoint (3)
the main process PID setpoint is automatically increased to prevent the system from going
to Sleep when the over-cycle limit is reached.
Over-cycle Starts Per Hour. The Over-cycle Mode Pr 0.060 is actioned when the number
Pr 0.060
of starts per hour threshold is reached.
Diagnostics –
The last 3 trips are stored in Pr 00.077 to Pr 00.080, with Pr 00.077 being the most recent trip.
Refer to the F600 User guide for a complete list of trips and their meaning.
00.014
Injection (0), Current (1), Current (2),
(RFC-S RFC low
5.064 Current No Test (3), Current Step (4), Current (2)
mode speed mode
Current Only (5)
only)
00.015
Low speed
(RFC-S
sensor-less 5.071 0.0 to 1000.0 % 100.0 %
mode
mode current
only)
Symmetrical VM_MOTOR1_CURRENT_LIMIT[MIN] to
00.016 4.007 110.0 %
current limit VM_MOTOR1_CURRENT_LIMIT[MAX] %
Table B-1 575 V drive ratings, cable sizes and fuse ratings (500 V to 575 V ±10 %)
Max. Nominal cable size
cont. Fuse Normal Duty
European USA
input
current IEC UL Max.
Model Nom Motor
count.
Input Output Input Output power power
3ph Nom Nom output
@ 575 V @ 575 V
Class Class current
A A A mm² mm² AWG AWG A kW hp
05500039 4 10 10 0.75 0.75 16 16 3.9 2.2 3
CC, J
05500061 7 10 gG 10 1 1 14 14 6.1 4 5
or T*
05500100 11 20 20 1.5 1.5 14 14 10 5.5 7.5
06500120 13 20 20 2.5 2.5 14 14 12 7.5 10
06500170 19 32 25 4 4 10 10 17 11 15
06500220 24 40 30 CC, J 6 6 10 10 22 15 20
gG
06500270 29 50 35 or T* 10 10 8 8 27 18.5 25
06500340 37 50 40 10 10 6 6 34 22 30
06500430 47 63 50 16 10 6 6 43 30 40
07500530 45 50 50 CC, J 16 16 4 4 53 45 50
gG
07500730 62 80 80 or T* 25 25 3 3 73 55 60
08500860 83 125 100 35 35 1 1 86 75 75
gR HSJ
08501080 104 160 150 50 50 1 1 108 90 100
2 x 35
09501250 166 150 150 2x3 125 110 125
2 x 70 (B2)
gR HSJ 2x1
(B2) 2 x 50
09501500 166 200 175 2x1 150 110 150
(B2)
10502000 197 250 gR 250 HSJ 2 x 70 (B2) 2 x 2/0 200 150 200
11502480 265 2 x 70 (C) 2 x 3/0 248 185 250
11502880 310 400 gR 400 HSJ 2 x 95 (C) 2 x 4/0 288** 225 300
11503150 338 2 x 120 (C) 2 x 250 315** 250 350
0478-0621-03