WDG 12 - Technical Data Sheet LV 804 T
WDG 12 - Technical Data Sheet LV 804 T
WDG 12 - Technical Data Sheet LV 804 T
FRAME LV 804 T
SPECIFICATIONS & OPTIONS
STANDARDS WINDINGS & ELECTRICAL PERFORMANCE
Cummins Generator Technologies industrial generators All generator stators are wound to 2/3 pitch. This
meet the requirements of BS EN 60034 and the relevant eliminates triplen (3rd, 9th, 15th …) harmonics on the
sections of other national and international standards such voltage waveform and is found to be the optimum design
as BS5000, VDE 0530, NEMA MG1-32, IEC60034, CSA for trouble-free supply of non-linear loads. The 2/3 pitch
C22.2-100, AS1359. design avoids excessive neutral currents sometimes seen
Other standards and certifications can be considered on with higher winding pitches. A fully connected damper
request. winding reduces oscillations during paralleling. This
winding, with the 2/3 pitch and carefully selected pole and
DESCRIPTION tooth designs, ensures very low levels of voltage waveform
distortion.
The STAMFORD PI range of synchronous ac generators
are brushless with a rotating field. They are separately TERMINALS & TERMINAL BOX
excited by the STAMFORD Permanent Magnet Generator
(PMG). This is a shaft mounted, high frequency, pilot Standard generators feature a main stator with 6 ends
exciter which provides a constant supply of clean power brought out to the terminals, which are mounted on the
via the Automatic Voltage Regulator (AVR) to the main frame at the non-drive end of the generator. A sheet steel
exciter. The main exciter output is fed to the main rotor, terminal box contains the AVR and provides ample space
through a full wave bridge rectifier, protected by surge for the customers' wiring and gland arrangements. It has
suppression. removable panels for easy access.
The P range generators complete with a PMG are All generator rotors are dynamically balanced to better than
available with an analogue AVR as standard. The AVR BS6861:Part 1 Grade 2.5 for minimum vibration in
has soft start voltage build up and built in protection operation. Two bearing generators are balanced with a half
against sustained over-excitation, which will de-excite the key.
generator after a minimum of 8 seconds.
Underspeed protection (UFRO) is also provided on both INSULATION/IMPREGNATION
AVRs. The UFRO will reduce the generator output voltage
proportional to the speed of the generator below a pre- The insulation system is class 'H'.
settable level. All wound components are impregnated with materials and
processes designed specifically to provide the high build
The MA330 AVR is full wave rectified, 3 phase rms required for static windings and the high mechanical
sensed with a voltage regulation of 0.5% rms (see the note strength required for rotating components.
on regulation). The UFRO circuit has adjustable slope and
dwell for controlled recovery from step loads. An over QUALITY ASSURANCE
voltage protection circuit will shutdown the output device of
the AVR, it can also trip an optional excitation circuit Generators are manufactured using production procedures
breaker if required. As an option, short circuit current having a quality assurance level to
limiting is available with the addition of current BS EN ISO 9001.
transformers.
NOTE ON REGULATION
The MA330 AVR needs a generator mounted current The stated voltage regulation may not be maintained in the
transformer to provide quadrature droop characteristics for presence of certain radio transmitted signals. Any change
load sharing during parallel operation. in performance will fall within the limits of Criteria 'B' of EN
Provision is also made for the connection of the 61000-6-2:2001. At no time will the steady-state voltage
STAMFORD power factor controller, for embedded regulation exceed 2%.
applications, and a remote voltage trimmer.
NB Continuous development of our products entitles us to change
specification details without notice, therefore they must not be
regarded as binding.
2
FRAME LV 804 T
WINDING 12
RATINGS REFER TO SALES AND SERVICE BRIEFING
MAXIMUM ALTITUDE 1000 METRES ABOVE SEA LEVEL
MAXIMUM AMBIENT TEMPERATURE 40º C
Continuous development of our products entitles us to change specification details without notice,
therefore they must not be regarded as binding.
3
FRAME LV 804 T WDG 12 50 Hz
380 V
98.0
97.5
97.0 1.0
96.5 0.9
96.0
0.8
95.5
% 95.0 P.F.
94.5
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2895.0 kVA
2895 kVA
400 V 98.0
97.5
97.0 1.0
96.5 0.9
96.0 0.8
95.5
% 95.0 P.F.
94.5
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
3050 kVA
415 V
98.0
97.5
97.0 1.0
96.5 0.9
96.0 0.8
95.5
% 95.0 P.F.
94.5
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
3050 kVA
440 V 98.0
97.5
1.0
97.0
0.9
96.5
0.8
96.0
95.5
% 95.0 P.F.
94.5
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
2865 kVA
4
FRAME LV 804 T WDG 12 60 Hz
416 V
97.5
97.0
1.0
96.5
0.9
96.0
95.5 0.8
95.0
% 94.5 P.F.
94.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
3170.0 kVA
3170 kVA
440 V 97.5
97.0
1.0
96.5
0.9
96.0
0.8
95.5
95.0
94.5
% P.F.
94.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
3355 kVA
460 V
98.0
97.5
97.0 1.0
96.5 0.9
96.0 0.8
95.5
95.0
% 94.5
P.F.
94.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
3508 kVA
480 V 98.0
97.5
1.0
97.0
96.5 0.9
96.0 0.8
95.5
95.0
% 94.5
P.F.
94.0
0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1
3660 kVA
5
FRAME LV 804 T WDG 12 50Hz
FULL WAVE RECTIFIED AVR
LOCKED ROTOR MOTOR STARTING CURVE
380V 400V 415V 440V
30.0
PER CENT TRANSIENT VOLTAGE DIP
25.0
20.0
15.0
10.0
5.0
0.0
0 1000 2000 3000 4000 5000 6000
LOCKED ROTOR kVA
NOTE 1
100000 THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO ADJUST THE VALUES
FROM CURVES BETWEEN THE 0.001 SECONDS AND THE MINIMUM CURRENT POINT IN
SYMMETRIC
RESPECT OF NOMINAL OPERATING VOLTAGE
380V X 0.95
400V X 1.00
415V X 1.04
440V X1.10
CURRENT (Amps)
NOTE 2
THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO CONVERT THE
VALUES CALCULATED IN ACCORDANCE WITH NOTE 1 TO THOSE APPLICABLE
TO THE VARIOUS TYPES OF SHORT CIRCUIT
3 PHASE 2 PHASE L-L 1 PHASE L-N
INSTANTANEOUS X 1.0 X 0.87 X 1.30
MINIMUM X 1.0 X 1.80 X 3.20
SUSTAINED X 1.0 X 1.50 X 2.50
MAX SUSTAINED DURATION 10 SEC 5 SEC 2 SEC
6
FRAME LV 804 T WDG 12 60Hz
FULL WAVE RECTIFIED AVR
LOCKED ROTOR MOTOR STARTING CURVE
25.0
20.0
15.0
10.0
5.0
0.0
0 1000 2000 3000 4000 5000 6000
LOCKED ROTOR kVA
NOTE 1
100000
THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO ADJUST THE VALUES
SYMMETRIC FROM CURVES BETWEEN THE 0.001 SECONDS AND THE MINIMUM CURRENT POINT IN
RESPECT OF NOMINAL OPERATING VOLTAGE
416V X 0.87
440V X 0.92
460V X0.96
CURRENT (Amps)
480V X1.00
NOTE 2
THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO CONVERT THE
VALUES CALCULATED IN ACCORDANCE WITH NOTE 1 TO THOSE APPLICABLE
TO THE VARIOUS TYPES OF SHORT CIRCUIT
3 PHASE 2 PHASE L-L 1 PHASE L-N
INSTANTANEOUS X 1.0 X 0.87 X 1.30
MINIMUM X 1.0 X 1.80 X 3.20
SUSTAINED X 1.0 X 1.50 X 2.50
MAX SUSTAINED DURATION 10 SEC 5 SEC 2 SEC
ALL OTHER TIMES ARE UNCHANGED
1000
0.001 0.01 0.1 1 10
TIME (secs)
SUSTAINED SHORT CIRCUIT = 16509 Amps
7
FRAME LV 804 T
WINDING 12 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
kVA 2660 2800 2800 2630 2895 3050 3050 2865 3095 3260 3260 3065 3180 3350 3350 3150
kW 2128 2240 2240 2104 2316 2440 2440 2292 2476 2608 2608 2452 2544 2680 2680 2520
Efficiency (%) 96.2 96.3 96.3 96.4 96.1 96.2 96.2 96.4 95.9 96.0 96.1 96.3 95.9 96.0 96.1 96.3
kW Input 2212 2327 2325 2182 2411 2538 2535 2378 2581 2716 2713 2547 2653 2792 2789 2618
60Hz Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
kVA 2910 3080 3220 3360 3170 3355 3508 3660 3390 3590 3752 3915 3490 3690 3857 4025
kW 2328 2464 2576 2688 2536 2684 2806 2928 2712 2872 3002 3132 2792 2952 3086 3220
Efficiency (%) 95.9 96.0 96.1 96.2 95.8 95.9 96.1 96.2 95.7 95.8 95.9 96.1 95.6 95.8 95.9 96.0
kW Input 2429 2566 2680 2793 2648 2798 2922 3045 2835 2998 3129 3261 2920 3082 3217 3354
© 2009 TD_LV804T.12.GB_03.09_09_GB