Determine El Volumen Del Tanque de Almacenamiento para 189,248 Hanitantes. Dotación de 189 L/hab-Día (Caso de Tanque Q Suministra Todo El Tiempo)

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 10

DETERMINE EL VOLUMEN DEL TANQUE DE ALMACENAMIENTO PARA 189,248 HANITANTES.

Dotación
de 189 L/hab-día (Caso de tanque q suministra todo el tiempo)

Consumo Suministro
Tiempo Δ(S-C) ∑Δ(S-C)
horario ∑(acomulado) horario ∑(acomulado)
Hora % % % %
0–1 1 1 0.00 0.00 -1.00 -1.00
1–2 1 2 0.00 0.00 -1.00 -2.00
2–3 1 3 0.00 0.00 -1.00 -3.00
3–4 1 4 0.00 0.00 -1.00 -4.00
4–5 2 6 0.00 0.00 -2.00 -6.00
5–6 4 10 0.00 0.00 -4.00 -10.00
6–7 9.5 19.5 0.00 0.00 -9.50 -19.50
7–8 8 27.5 8.33 8.33 0.33 -19.17
8–9 7 34.5 8.33 16.67 1.33 -17.83
9 – 10 4 38.5 8.33 25.00 4.33 -13.50
10 – 11 3 41.5 8.33 33.33 5.33 -8.17
11 – 12 5.5 47 8.33 41.67 2.83 -5.33
12 – 13 9 56 8.33 50.00 -0.67 -6.00
13 – 14 5 61 8.33 58.33 3.33 -2.67
14 - 15 3 64 8.33 66.67 5.33 2.67
15 – 16 2.5 66.5 8.33 75.00 5.83 8.50
16 – 17 3 69.5 8.33 83.33 5.33 13.83
17 - 18 3.5 73 8.33 91.67 4.83 18.67
18 – 19 5 78 8.33 100.00 3.33 22.00
19 – 20 9 87 8.33 108.33 -0.67 21.33
20 – 21 8.5 95.5 0.00 108.33 -8.50 12.83
21 – 22 2 97.5 0.00 108.33 -2.00 10.83
22 - 23 1.5 99 0.00 108.33 -1.50 9.33
23 – 24 1 100 0.00 108.33 -1.00 8.33
Dotación Habiitantes
HANITANTES. Dotación 170 189248
po)

Q prom_dia Vol. Compensación Vol. Emergencia Vol. Contra


Volumen Vol máx (%)
(m^3/día) (m^3) (m^3) Incendios (m^3)
% 41.50 32172.16 13351.45 4825.82 345.60
18.50
17.50
16.50
15.50
13.50
9.50
0.00
0.33
1.67
6.00
11.33
14.17 Dimensiones del tanque
13.50 Diámetro Altura Curva Integral
16.83 28.68 28.68 120.00
22.17
28.00 100.00
33.33
38.17 80.00
41.50
60.00
40.83
32.33
40.00
30.33
28.83 20.00
27.83
0.00
0 5 10 15
Vol. Total
(m^3)
18522.87

Curva Integral

10 15 20 25 30
DETERMINE EL VOLUMEN DEL TANQUE ELEVADO SUMINISTRADO POR BOMBEO (8 HRS) PARA UN
CAUDAL DE 13 Lps.

Consumo Suministro
Tiempo Δ(S-C) ∑Δ(S-C)
horario ∑(acomulado) horario ∑(acomulado)
Hora % % % %
0–1 1 1 0.00 0.00 -1.00 -1.00
1–2 1 2 0.00 0.00 -1.00 -2.00
2–3 1 3 0.00 0.00 -1.00 -3.00
3–4 1 4 0.00 0.00 -1.00 -4.00
4–5 2 6 0.00 0.00 -2.00 -6.00
5–6 4 10 0.00 0.00 -4.00 -10.00
6–7 9.5 19.5 0.00 0.00 -9.50 -19.50
7–8 8 27.5 12.50 12.50 4.50 -15.00
8–9 7 34.5 12.50 25.00 5.50 -9.50
9 – 10 4 38.5 12.50 37.50 8.50 -1.00
10 – 11 3 41.5 12.50 50.00 9.50 8.50
11 – 12 5.5 47 12.50 62.50 7.00 15.50
12 – 13 9 56 12.50 75.00 3.50 19.00
13 – 14 5 61 12.50 87.50 7.50 26.50
14 - 15 3 64 12.50 100.00 9.50 36.00
15 – 16 2.5 66.5 0.00 100.00 -2.50 33.50
16 – 17 3 69.5 0.00 100.00 -3.00 30.50
17 - 18 3.5 73 0.00 100.00 -3.50 27.00
18 – 19 5 78 0.00 100.00 -5.00 22.00
19 – 20 9 87 0.00 100.00 -9.00 13.00
20 – 21 8.5 95.5 0.00 100.00 -8.50 4.50
21 – 22 2 97.5 0.00 100.00 -2.00 2.50
22 - 23 1.5 99 0.00 100.00 -1.50 1.00
23 – 24 1 100 0.00 100.00 -1.00 0.00
Caudal de diseño
EO (8 HRS) PARA UN 13

Vol. Vol. Vol. Contra


Q prom_dia Vol. Total
Volumen Vol máx (%) Compensaci Emergencia Incendios
(m^3/día) (m^3)
ón (m^3) (m^3) (m^3)
% 55.50 1123.20 623.38 168.48 230.40 1022.26
18.50
17.50
16.50
15.50
13.50
9.50
0.00
4.50
10.00
18.50
28.00
35.00 Dimensiones del tanque
38.50 Diámetro Altura Curva Integral
46.00 10.92 10.92
120
55.50
53.00 100
50.00
80
46.50
41.50 60
32.50
40
24.00
22.00 20
20.50
0
19.50 0 5 10 15 20 25

Horas vs Consumo Acum Horas Vs Suministro Acum


Integral

15 20 25 30

Horas Vs Suministro Acum


SUMINISTRE HORAS DE FUNCIONAMIENTO Y CAUDAL DE DISEÑO O HABITANTES Y DOTACIÓN EN LAS
CASILLAS DE LA DERECHA

Consumo Suministro
Tiempo Δ(S-C) ∑Δ(S-C)
horario ∑(acomulado) horario ∑(acomulado)
Hora % % % %
0–1 1 1 4.17 4.17 3.17 3.17
1–2 1 2 4.17 8.33 3.17 6.33
2–3 1 3 4.17 12.50 3.17 9.50
3–4 1 4 4.17 16.67 3.17 12.67
4–5 2 6 4.17 20.83 2.17 14.83
5–6 4 10 4.17 25.00 0.17 15.00
6–7 9.5 19.5 4.17 29.17 -5.33 9.67
7–8 8 27.5 4.17 33.33 -3.83 5.83
8–9 7 34.5 4.17 37.50 -2.83 3.00
9 – 10 4 38.5 4.17 41.67 0.17 3.17
10 – 11 3 41.5 4.17 45.83 1.17 4.33
11 – 12 5.5 47 4.17 50.00 -1.33 3.00
12 – 13 9 56 4.17 54.17 -4.83 -1.83
13 – 14 5 61 4.17 58.33 -0.83 -2.67
14 - 15 3 64 4.17 62.50 1.17 -1.50
15 – 16 2.5 66.5 4.17 66.67 1.67 0.17
16 – 17 3 69.5 4.17 70.83 1.17 1.33
17 - 18 3.5 73 4.17 75.00 0.67 2.00
18 – 19 5 78 4.17 79.17 -0.83 1.17
19 – 20 9 87 4.17 83.33 -4.83 -3.67
20 – 21 8.5 95.5 4.17 87.50 -4.33 -8.00
21 – 22 2 97.5 4.17 91.67 2.17 -5.83
22 - 23 1.5 99 4.17 95.83 2.67 -3.17
23 – 24 1 100 4.17 100.00 3.17 0.00
Caudal de diseño(lts/dias). Dotación(L/h.d) Habiitantes Horas
793800 378 2100 24
Caudal de diseño(^3m/dias).
S Y DOTACIÓN EN LAS 793.8

Vol. Compensación Vol. Emergencia


Volumen Vol máx (%) Q prom_dia (m^3/día)
(m^3) (m^3)
% 25.00 793.80 198.45 119.07
11.17
14.33
17.50
20.67
22.83
23.00
17.67
13.83
11.00
11.17
12.33
11.00 Dimensiones del tanque dostanques
6.17 Diámetro Altura Diámetro
5.33 7.39 7.39 3.70
6.50 4.89
8.17
9.33
10.00
9.17
4.33
0.00 En la area de estudio elegida por nuestro
2.17 diametro es muy alto .Por tal razon es neces
4.83
8.00 area en 2 tanques.

4
Vol. Contra
Incendios (m^3)
Vol. Total (m^3) Curva Integral
0.00 317.52 120

100

80

60
Altura
3.70
2.5 para tanques de concreto
40

20
da por nuestro grupo, el
razon es necesario dividir la
tanques. 0
0 5 10 15

Horas vs Consumo Acum


Curva Integral

10 15 20 25 30

Horas vs Consumo Acum Horas Vs Suministro Acum