User's Manual H240

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

User's Manual

TempTron 607AC

Program version: H240


Contents
Document Information ___________________________________________ 3
Front Panel ___________________________________________ 4
Reading Function Set Points ___________________________________________ 5
Shortcut keys ___________________________________________ 5
Recall Function Settings ___________________________________________ 5
Programming Function Settings _________________________________________ 6
Function List ___________________________________________ 6
01. Current Time __________________________________________________ 6
02. Required Temperature ___________________________________________ 6
03. Heat _________________________________________________________ 6
Variable Speed Fan Control _______________________________________________ 7
04. SP Fan On Temperature (SP) ______________________________________ 7
05. SP Temperature Band Width (BW) _________________________________ 7
06. SP Minimum Speed % ___________________________________________ 7
07. SP Maximum Speed % ___________________________________________ 7
08. SP Current Speed _______________________________________________ 8
09. Fan 1 _________________________________________________________ 8
10. Fan 2 _________________________________________________________ 8
11. Fan 3 _________________________________________________________ 8
12. Fan 4 _________________________________________________________ 8
13. Fan 5 _________________________________________________________ 8
14. Fan On Time___________________________________________________ 8
15. Fan Off Time __________________________________________________ 8
16. Humidity Set Point _____________________________________________ 10
17. Cool Temperature ______________________________________________ 10
18.Cool On Time: mm:ss ___________________________________________ 10
19.Cool Off Time: mm:ss___________________________________________ 10
20. Low alarm ___________________________________________________ 10
21. High alarm ___________________________________________________ 11
22. Alarm Type __________________________________________________ 11
23. Alarm Disable ________________________________________________ 11
24. Minimum temperature __________________________________________ 11
25. Minimum temperature time ______________________________________ 11
26. Maximum temperature __________________________________________ 11
27. Maximum temperature time ______________________________________ 11
28. Minimum Humidity ____________________________________________ 11
29. Minimum humidity time ________________________________________ 11
30. Maximum Humidity ____________________________________________ 11
31. Maximum humidity time ________________________________________ 11
31. Maximum humidity time ________________________________________ 12
34. Water Meter __________________________________________________ 12
35. Feed Multiply _________________________________________________ 12
36. Daily Feed Consumption ________________________________________ 12
37. Total Feed Consumption ________________________________________ 12
38. Temperature Day 1. ____________________________________________ 12
User's Manual Page 2 of 18
www.agrologic.com
39 – 47 automatic reduction table ____________________________________ 12
48. Grow Day ____________________________________________________ 13
49. Reset Time ___________________________________________________ 13
Hidden Set up functions __________________________________________ 13
50. Lock Code ___________________________________________________ 13
51. Sensor Average _______________________________________________ 14
52. Net Name ____________________________________________________ 14
53. Digital Input Readout ___________________________________________ 14
54. Feed Mode ___________________________________________________ 14
55. Fan Mode ____________________________________________________ 14
56. SP Fan Humidity Set Speed % ____________________________________ 14
57. SP / Fan Mode ________________________________________________ 14
58. Communication Protocol; _______________________________________ 15
59. Version ______________________________________________________ 15
TROUBLE-SHOOTING __________________________________________ 16
Default settings __________________________________________ 16
Wiring Diagram __________________________________________ 18

Document Information

Revision History
Document version Program version Date Description
Ver. 1.0 H240 June 20, 2016 First edition

Attention!!
1. This manual may contain mistakes and or printing errors. We accept no liability for
technical mistakes or printing errors, or their consequences.
2. This control unit is supplied with default settings. These setting are only general
settings and should not be seen as final settings. We accept no liability for any
consequences that may occur because of these settings.

User's Manual Page 3 of 18


www.agrologic.com
Front Panel
Display screen Function number

Function list

Keyboard
Relay functions

Enter key Program key Data key

Display screen: The entered values for each function are displayed here.

Function number: The current function number is shown here.

Function list: Shown here is the list of functions for the 607 program.

Relay functions: Each relay operates a particular output. When an output is in use
the corresponding led goes on.

Enter key: Press on the enter button to store entered values into the 608 memory.

Program key: Press on the PROG button to enter the programming mode for a
chosen function.

Data key: Use this button to go forward in the function list.

Keyboard: A numeric keyboard for entering the set point values for each function.

User's Manual Page 4 of 18


www.agrologic.com
When the power is turned on the program version number will appear on the display.
After approximately 20 Seconds, the average temperature will appear on the front
display screen.

Reading Function Set Points


It is possible to recall and read all the programmed information on the TempTron
607 display screen. The right display indicates the function number. The left display
shows the set point values for each function.

Shortcut keys
To display temperature sensor 1 readout, press on keyboard number 1.
To display temperature sensor 2 readout, press on keyboard number 2.
To display temperature sensor 3 readout, press on keyboard number 3.
To display temperature sensor 4 readout, press on keyboard number 4.
To display temperature sensor 5 readout, press on keyboard number 5.
To display the current humidity readout, press on keyboard number 6.
To display the minimum ventilation cycle time, press on keyboard number 7.
To display current flap position, press on keyboard number 8.

Recall Function Settings

Each set point has a Function number (see Function list on the front panel). It is
possible to call up and program the functions in two ways:
1. Press once on the DATA key, the function number display on the right side of
the panel will increase by one. The programmed information for each function
will appear on the data display screen on the left side of the panel.
2. Press once on the 0 key, two lines will appear on the function display and
FUNC on the data display. Next enter the required function number using the
keyboard and then press Enter.

Example:
If you would like to recall function 8 follow these steps:
Press once on the 0 key. Two lines will appear on the right display (function display).
Press on the 0 key, then on the 8 key.
The function display will display 08. The data display will show the current
programed setting for this function.

If a function number is larger than 10, press on key 0, then the function number.
Example:
If you would like to recall function 12;
Press on the 0 key.
Press on the 1 and 2 keys.
The function display will display 12. The data display will show the current
programed setting for this function.

User's Manual Page 5 of 18


www.agrologic.com
You can scroll through the function list by pressing on the DATA key. Each time you
press on the function key the function number will increase by one.

Programming Function Settings

It is possible to change each set point.


1. Go into the desired code as explained above.
2. Push on “PROG” button. The code display will start to flash.
3. Use the keyboard to enter the desired data. The new data will appear on the data
display.
4. Check the display to see if the information is correct. If yes, push on the “Enter”
button. The code display will stop flashing to indicate that the new information has
been stored into the unit’s memory.

Function List

01. Current Time


Displays the current time.

02. Required Temperature


The required temperature is the requested temperature for the house. All set points
(except the cool temperature set point) are set as a differential above or below the
required temperature.

03. Heat
Heat set point is the temperature differential below the requested room temperature
that the heating system will turn on.
Example: Heat set point = 1.0
If the room temperature should drop 1.0° below the Room temperature (function 02)
setting, the heating system will start to run.

User's Manual Page 6 of 18


www.agrologic.com
Variable Speed Fan Control
If you are using variable speed fans in your house, Hidden function 57, 57. SP
/ Fan Mode on page 14 must be set to 1.

The variable speed fans (SP fans) will be used for minimum ventilation and run at the
speed set in SP Minimum Speed % as long as the house average temperature is less
than the Required Temperature plus SP Fan On Temperature.
Once the house average temperature reaches the Required Temperature plus SP
Fan On Temperature setting, the SP fans will start to increase in speed. The SP fans
will increase in speed from SP Minimum to SP Maximum over the temperature
range set in SP Temperature Band Width.
Once the average house temperature reaches Required Temperature plus Fan 1
offset, fan 1 will start to operate. At this point, the SP fans will run at 100%.
Fan 2, 3, 4 and 5 will come into operation as their offset temperatures are reached.
See Photo 1 on page 9.

If SP fans are not being used in your house, enter 0 (zero) in Hidden function
57, 57. SP / Fan Mode on page 14. Fan 1-5 will be used as minimum
ventilation as setup in function 55, 57. SP / Fan Mode on page 14.

04. SP Fan On Temperature (SP)


Temperature differential above the Required temperature. At this temperature the SP
fans start to increase in speed according to the set Band Width (BW) Function 05
below. Up to this temperature, the SP fans run at the set minimum speed percentage
(function 06 below).

05. SP Temperature Band Width (BW)


This starts at the SP fan temperature differential ON temperature (see above). Over
this set number of digress, the SP fans will increase in speed from minimum to
maximum speed (see SP Minimum Speed % and SP Maximum Speed % below).

06. SP Minimum Speed %


This is the minimum speed percentage that the SP fans will run.
Example:
Fan Min Out = 20
The minimum speed percentage that the SP fan will run at is 20%

07. SP Maximum Speed %


This is the maximum speed that the SP fans will run.
Example:
Fan Min Out = 90%
The maximum speed that the SP fan will run at is 90%

User's Manual Page 7 of 18


www.agrologic.com
08. SP Current Speed
Displays the SP fan current speed in percentage

09. Fan 1
Fan 1 set point is the temperature differential above the required temperature at which
time fan 1 will operate nonstop. Fan group 1 alone may be used as a minimum
ventilation fan group or it may be used together in a rotating manner together with the
other 4 fan groups (see Hidden function 55, 55. Fan Mode on page 14).

10. Fan 2
Fan 2 set point is the temperature differential above the required temperature at which
time fan 2 will operate nonstop. Fan group 2 may be programmed to work as a
minimum ventilation fan group (see Hidden function 55, 55. Fan Mode on page 14).

11. Fan 3
Fan 3 set point is the temperature differential above the required temperature at which
time fan 3 will operate nonstop. Fan group 3 may be programmed to work as a
minimum ventilation fan group (see Hidden function 55, 55. Fan Mode on page 14).

12. Fan 4
Fan 4 set point is the temperature differential above the required temperature at which
time fan 4 will operate nonstop. Fan group 4 may be programmed to work as a
minimum ventilation fan group (see Hidden function 55, 55. Fan Mode on page 14).

13. Fan 5
Fan 5 set point is the temperature differential above the required temperature at which
time fan 3 will operate nonstop. Fan group 5 may be programmed to work as a
minimum ventilation fan group (see Hidden function 55, 55. Fan Mode on page 14).

14. Fan On Time


Fan on time is set in minutes. This is the length of time the minimum ventilation fans
will run during minimum ventilation cycle.

15. Fan Off Time


Fan off time is set in minutes. This is the length of time the minimum ventilation
fans will be off during minimum ventilation cycle.

User's Manual Page 8 of 18


www.agrologic.com
Photo 1: SP fan with 5 regular On Off fans

Fan 2 On

Fan 1 On
SP fan max%

SP fan min%
Required Temp.
BW
SP Fan Temp

Regular On Off Fans1

SP Fan Temp

Required Temp.

Fan 2 On

Fan 1 On

Required Temp.
Min vent On

Min vent Off


Min vent Off

User's Manual Page 9 of 18


www.agrologic.com
16. Humidity Set Point
Humidity set is set in percentage. If the humidity reading in the house rises to this
level, the unit will automatically bring into operation the next fan group.
If the Humidity Set Point is reached and the SP fans are running at a speed that is
less than the speed set in SP Fan Humidity Set Point % (on page 14) the SP fans
will increase to the speed as set in SP Fan Humidity Set Point %

This setting is also used for the cooling system. If the cooling system is
running and the humidity reading in the house rises to this level, the cooling
system will not be allowed to operate.

17. Cool Temperature


Enter here the average house temperature that when reached will turn on the
cooling system. Once on, the system will run in its cycle mode according to the
Cool On and Cool Off times.

18.Cool On Time: mm:ss


This is the ON time period, set in minutes and seconds, which the cooling
system will run.

19.Cool Off Time: mm:ss


This is the OFF time period, set in minutes and seconds, which the cooling
system will be off during the cooling system cycle.

Example:
Function: Value:
12. Cool Temperature 27.0°
13. Cool On Time mm:ss 02:00
14. Cool Off Time mm:ss 05:00

If the average house temperature reaches 27°, the cooling system will start to
operate.
The cooling system will run for 2 minutes, and be off for 5 minutes

Humidity Set Point (function 16) is also used for the cooling system. If the
cooling system is running and the humidity reading in the house reaches the
humidity set point, the cooling system will turn off.

20. Low alarm


Low alarm set point is the temperature differential below the requested room
temperature. This alarm is represented by the number 1 in function 22, Alarm type
(on page 11).
Example: If 5.0° is entered in the alarm low function, if the average house
temperature
falls 5.0° below the required room temperature (function 01), the alarm relay will
be activated.

User's Manual Page 10 of 18


www.agrologic.com
21. High alarm
High alarm set point is the temperature differential above the requested room
temperature. This alarm is represented by the number 2 in function 22, Alarm type
(below).
Example: If 5.0° is entered in the alarm high function, if the average house
temperature raises 5.0° above the required room temperature (function 02), the
alarm relay will be activated.

22. Alarm Type


Shown here is the current alarm in digital form.
The unit has 6 alarms:
1. Low – average temperature has dropped below Low alarm setting.
2. High – average temperature has risen above the High alarm setting.
3. Memory- represents a problem with the unit’s memory.
4. Sensors- all temperature malfunctioning.
5. Sensor- one sensor is malfunctioning.

23. Alarm Disable


It is possible to disable only alarms 5&6.
To disable an alarm, enter the corresponding number.
Example: In order to disable alarm number 5 (bad sensor) enter the value 5.

24. Minimum temperature


Shown here is the minimum inside temperature reading over the last 24 hours.

25. Minimum temperature time


Shown here is the time that the minimum temperature reading occurred.

26. Maximum temperature


Shown here is the maximum inside temperature reading over the last 24 hours.

27. Maximum temperature time


Shown here is the time that the maximum temperature reading occurred.

28. Minimum Humidity


Shown here is the minimum house humidity reading over the last 24 hours.

29. Minimum humidity time


Shown here is the time that the minimum humidity reading occurred.

30. Maximum Humidity


Shown here is the maximum house humidity reading over the last 24 hours.

31. Maximum humidity time


Shown here is the time that the maximum humidity reading occurred

User's Manual Page 11 of 18


www.agrologic.com
31. Maximum humidity time
Shown here is the time that the maximum humidity reading occurred.

34. Water Meter


If a water meter is attached to the unit, it is possible to see here the amount of
water consumed in liters.

35. Feed Multiply


The feed multiply is the total feed in Kg. that is brought into the house over one
minute when the auger motor is on. This is needed in order to calculate the
amount of feed being used. Example: Enter 25. The unit will assume that 25 kilos
of feed pass through the auger each minute. After 10 minutes the feed
consumption will be 250 kilos.

36. Daily Feed Consumption


A display of the current total feed consumption over the last 24 hours (from reset
time to reset time).

37. Total Feed Consumption


A display of the total feed consumption since the start of the flock.

38. Temperature Day 1.


Temperature day 1 is the required room temperature (code 02) for the first day of
the flock. It is the temperature that will appear as the required room temperature
(code 02) when Grow Day (Function 48 on page 13) is equal to 1. The room
temperature will be reduced according to the temperature table as explained
below.

39 – 47 automatic reduction table


It is possible to set a temperature table to reduce automatically the room
temperature each day during the raising period. It is possible to set up to 9 Groups.
Length of each group can be up to 9 days. Each Group can be reduced up to
9.9C.

Example: Day 1 temperature = 31C. (code 21)


Grow day = 1 (code 31)
Required house temperature = 31C. (code 02)
Group 1- 7 days reducing of 2C.

Each day the room temperature will be reduced by 0.3C. At day 7 - the room temp.
will be 29C.
Group 2-3 days reducing of 1.5C. Each day the room temperature will be reduced by
0.5C. At day 10 the room temperature will be 27.5C. This will continue for the 9
possible settings.

User's Manual Page 12 of 18


www.agrologic.com
Example:
To Enter temperature reduction of 2C over 7 days, enter function 39, press on the
program button, press on 7, then 2, then 0, then on Enter. On the display will appear:
7 2.0 G1
Push on data key, next group will appear. 32
To enter temperature reduction of 1.5C in 3 days, push on 3, T 30
e
then on 1, then on 5, then on Enter. m
28
On the display will appear: 3 1.5 G2. p 26
24
G1 G2
It is important to enter data in all 9 groups. If a group is not in
use than put one day and 0C. as a reduction temp.

48. Grow Day


This is the current grow day of the flock. At the beginning of the flock enter here
1. The room temperature (code 02) will automatically receive the value as entered
in Grow day1 temp. (function 38 on page 12 ).

49. Reset Time


The Temptron T-607 collects all its information on a 24-hour basis. It is possible to
set the reset time. The grow day also changes after this time is passed. All
information, temperature, humidity, water count and feed consumption will reset at
this time.

Hidden Set up functions


Functions 50-59 are hidden functions and cannot be accessed unless the hidden
function code is entered:
A. Go to the time function (function 01)
B. Push on “PROG”
C. Enter “3331”, then press "Enter".
Now the hidden functions may be accessed.

50. Lock Code


It is possible to enter a 4-digit function, which will lock the Temptron T-607.
Enter a 4-digit function and press enter. This will be the code necessary in order to
enter information into the Temptron T-607.
Once the code has been entered, after a ten-minute period, if no information has
been entered the unit will lock. It is possible to see all the information in the unit,
but not possible to make any changes.
In order to unlock the unit, first enter the 4-digit code, then continue in the usual
manner to enter information.
Example:
A. Enter 4-digit function
B. Push the Prog.
C. Enter function number and press enter.
D. Enter desired value and press enter.

If no lock code is desired enter in 0000 as the lock code.

User's Manual Page 13 of 18


www.agrologic.com
51. Sensor Average
It is necessary to define the number of temperature sensors that will be used for
the average temperature reading.
Enter the number of sensors. If two sensors are used enter the value 2.
It is possible to enter up to 4 sensors for the average temperature

52. Net Name


It is possible to connect the Temptron-607 to a PC computer with the help
of the "WebChick" software package (optional).
Each unit needs a net name.
Set the net name 1 for house one, 2 for house 2 and so on.

53. Digital Input Readout


This is a display of the current digital inputs being used in a bin format

54. Feed Mode


The unit can measure feed consumption in two ways. One is as explained in function
18, by converting time into kilos.
The second way is for the unit to receive a dry contact pulse from a weighing
machine. Each pulse represents a preset amount of feed.
Enter 0(zero) to measure by time.
Enter 1(one) to measure by pulse.

55. Fan Mode


Set the required fan order for minimum ventilation as explained below.
It is possible to program which group or groups will run in the minimum ventilation
mode. It is possible to choose fan group 1 only or fan group 1 alternating with other
fan groups. Example: If you enter here the value 1 then only fan group 1 will run in
the minimum ventilation cycle. If you enter 2 then in the first minimum ventilation
cycle fan group 1 will run. In the second cycle fan group 2 will run. The two fans
groups will run alternately during the minimum ventilation cycle.
If you enter 3 then fan groups 1, 2 and 3 will run alternately during the minimum
ventilation cycle.
If you enter 4 then fan groups 1, 2, 3 and 4 will run alternately during the minimum
ventilation cycle.
If you enter 5 then fan groups 1, 2, 3, 4 and 5 will run alternately during the minimum
ventilation cycle.

56. SP Fan Humidity Set Speed %


Enter here the SP fan speed that will be used if the humidity is higher than that set in
function 16, Humidity Set Point on page 10. If the SP fan is already running at a speed
higher than that set here, there will be no change in speed.

57. SP / Fan Mode


Enter here 0 (zero) if there are no SP fans. The minimum ventilation will be done with
fan groups 1-5 as explained earlier.

User's Manual Page 14 of 18


www.agrologic.com
Enter 1 if you are using SP fans. The minimum ventilation will be don’t with the SP
fans as explained earlier.

58. Communication Protocol;


Enter 0 for text 2400 bps
Enter 1 for text 9600 bps
Enter 2 for binary 2400 bps
Enter 3 for binary 96000 bps
Factory default is “0”

59. Version
The number shown is the program version number for your unit.

User's Manual Page 15 of 18


www.agrologic.com
TROUBLE-SHOOTING

1. If a temperature sensor or its cable is disconnected, the sensor reading will


show OPEN.

2. If a temperature sensor or its cable is shorted, the sensor reading will show
SHORT

3. If both sensors are disconnected, the unit will show open as average and
activate the alarm.

If one sensor is disconnected, the system will automatically work on the remaining
sensor.

Default settings

Function # Description Default setting


01 Time
02 Required temperature 25.0
03 Heat 2.0
04 SP fan Temperature 0
05 SP temperature BW 3.0
06 SP minimum speed 3.0
07 SP maximum speed 100
08 SP speed ---
09 Fan 1 3.0
10 Fan 2 4.0
11 Fan 3 6.0
12 Fan 4 7.0
13 Fan 5 8.0
14 Fan On time 01:00
15 Fan off time 10:00
16 Humidity Set point 80
17 Cool on temperature 32.0
18 Cool on time 01:00
19 Cool off time 05:00
20 Cold alarm 10.0
21 Hot alarm 10.0
22 Alarm Type 0
23 Disable alarm 0
24 Minimum temperature ---
25 Minimum temperature time ---
26 Maximum temperature ---
27 Maximum temperature time ---
28 Minimum humidity ---
29 Minimum humidity time ---
30 Maximum humidity ---

User's Manual Page 16 of 18


www.agrologic.com
Function # Description Default
setting
31 Maximum humidity time ---
32 Cool timer ---
33 Fan timer ---
34 Water meter ---
35 Feed multiply 15.0
36 Feed meter ---
37 Total feed ---
38 Day 1 temperature 32.0
39 Temperature reduction 1 7.2.0
40 Temperature reduction 2 7.2.0
41 Temperature reduction 3 7.2.0
42 Temperature reduction 4 7.2.0
43 Temperature reduction 5 7.2.0
44 Temperature reduction 6 0
45 Temperature reduction 7 0
46 Temperature reduction 8 0
47 Temperature reduction 9 0
48 Grow day 2
49 Reset time 0
50 Lock code 0
51 Sensor average 2
52 Net name 1
53 Digital input readout ---
54 Feed mode 0
55 Fan mode 0
56 SP fan humidity set speed % 80
57 SP/ Fan mode 0
58 Communication protocol 0
59 Version number H240

User's Manual Page 17 of 18


www.agrologic.com
Wiring Diagram

User's Manual Page 18 of 18


www.agrologic.com