VM-5U Dual Seismic Monitor
VM-5U Dual Seismic Monitor
VM-5U Dual Seismic Monitor
■ Main Functions
1. Display function 5. Monitor output
Vibration measured value and alarm level setting value are normally Vibration waveform signal is output from BNC connectors (on the front
displayed on individual LCD for each channel. panel) and terminal board (on the rear panel) via a buffer amplifier for
vibration analysis.
2. Alarm function
ALERT alarm, DANGER alarm and input abnormal alarm are contact- 6. Recorder output
output and displayed on LED. An analog signal proportional to the vibration is output from the terminal
block on the rear panel.
3. Alarm delay time variable function
Alarm delay time can be adjusted from 0 to 6 sec. to prevent false alarm 7. Sequence function
output caused by noise, etc. Internal gain is changed by inputting an external contact signal when
rotating machinery is started, and thus no alarm signal is temporarily
4. Self-diagnostic function output.
Any failures in the input system, such as sensor break or imperfect
connections are detected, then an input abnormal alarm is contact-output 8. DANGER bypass function
and simultaneously, ALERT and DANGER alarm circuits are cut off. When the alarm setpoint is changed during operation, alarm output is
disconnected so that no alarm is output by mistake.
■ Specifications
Input Alarm
Transducer input ■ CV-85, CV-86, CV-87 Alarm set point ■ 4 points (DANGER 1, ALERT 1, DANGER 2, ALERT 2)
■ Number of input points : 2 points Alarm set range ■ 0 to 110% of monitor range
Input impedance ■ Approx. 10kΩ Alarm set accuracy ■ ±1.0% of F.S. or less
External contact input ■ Contact type: Dry contact Alarm set repeatability ■ ±0.1% of F.S. or less
(from rear panel) ■ Contact for external reset Alarm output ■ 5 points (DANGER 1, ALERT 1, DANGER 2, ALERT 2, OK)
■ Contact for sequence or 6points (DANGER 1, ALERT1, DANGER 2, ALERT 2,
OK1, OK2)
I/O conversion
Recorder output conversion accuracy Display
■ ±0.5% of F.S. at calibration frequency at 25°C (77°F), Measured value
±2.0% of F.S. at calibration frequency at 0 to 65°C (32 to ■ LCD digital meter with 5 digits (7 segments with back light)
149°F) (the calibration frequency is determined by the cut-off LCD bar graph meter (40 segments with back light)
frequency range.) * Measurment value and alarm set value are indicated on the
Bar graph meter ■ Recorder output conversion accuracy ±2.5% of F.S. digital meter and bar graph meter simultaneously.
Diqital meter ■ Recorder output conversion accuracy ±1.0% of F.S. Alarm indicator ■ DANGER : (red LED) ALERT : (yellow LED)
ABNOR. alarm indicator
Output ■ OK : (green LED)
Recorder output ■ Voltage or current output proportional to monitor range Bypass indicator ■ BYPASS: (red LED)
(from rear panel) 1 to 5VDC (output impedance : 250Ω)
4 to 20mADC (max. load resistance : 500Ω) Others
0 to −10VDC*, 0 to10VDC*, 0 to −5VDC*, Temperature range ■ Operating temperature : 0 to 65°C (32 to 149°F)
0 to 5VDC* (output impedance:100Ω) ( * option) Storage temperature : −30 to +85°C (−22 to +185°F)
Number of output points : 2 points Relative humidity : 20 to 95% RH (noncondensing)
Monitor output ■ Input signal is output via a buffer amplifier. Material and finish ■ Face plate : Aluminum Munsell N-4.0 (equiv.)
(from front, rear panel) Signal level : ±15V Output impedance : 100Ω Mass ■ Monitor: max. 0.7kg
(including single unit instrument rack: max. 2.5kg)
■ Model Code No.
Outline Drawing