Project : MEGHALAYA POWER DISTRIBUTION CORPORATION LIMITED Rev.

: 0
Title : FOUNDATION DESIGN FOR 33KV LIGHTING ARRESTER Date: 14.01.2019

0.55m
Y FOOTING PARAMETER:
0.30m G.L. Depth of footing, D = 1.50m
Pedestal Overall depth of pedestal, d1 = 1.55m
1.55m Depth of pedestal from GL,d2 = 1.25m
1.25m CL Pedestal length, Lp = 0.55m
1.50m Pedestal width, Bp = 0.55m
Length of the Base Slab, Ls = 1.00m
0.25m Footing Slab Width of the Base Slab, Bs = 0.80m
Thickness of the slab, t = 0.25m
1.00m
LOADS ON FOOTING:
Operating Load uplift (Fvu) = 1.75 kN
Operating Load downward (Fvd) = 1.75 kN
Weight of Struc fitted., W = 0.50 kN
0.55m X Horizontal Load (Fhy) = 0.00 kN
(0,0) 0.80m distance of acting from GL = 1.45m
X Pedestal Wind load at Y direction, Fwy = 1.69 kN
Acting distance from GL = 1.45m
Tensile Load at terminal, Ftx = 0.00 kN
Acting distance from GL = 1.45m
Wind load at X direction, Fwx = 1.69 kN
Acting distance from GL = 1.45m
Y Weight of Foundation, Sw = 16.72 kN
2
Bearing Capacity of Soil, SBC = 180 N/mm

Grade of concrete fck = M 20 Grade of steel used, fy = 415 MPa

Overburden soil weight above footing = 11.19375 kN acts at centre of footing (dry condition)
Overburden soil weight above footing = 5.596875 kN acts at centre of footing (wet condition)

1. CHECK FOR OVERTURNING:


Taking point on extreme end under footing slab

Overturning Moment Stabilizing Moment


due to horizontal load (Fh) = 0 kN-m due to self-weight of footing = 8.3609375 kN-m
due to Wind Load (Fw) = 4.9855 kN-m due to self-weight of structure = 0.875 kN-m
due to Tensile Load (Ftx) = 0 kN-m due to overburden soil above = 2.7984375 kN-m
Total overturing Moment = 4.9855 kN-m Total stabilizing moment = 12.034375 kN-m

Factor of safety in overturing = 2.41


Required factor of safety = 1.5 SAFE

2. CHECK FOR SLIDING:

Horizontal forces caused to sliding Resisting Forces


due to horizontal force (Fh) = 0.00 kN due weight of footing, μW = 5.5796875 kN
due to wind load (Fw) = 1.690 kN due to passive pressure at slab = 1.6875 kN
Total sliding forces = 1.69 kN Total resisting forces = 7.2671875 kN

Factor of safety in overturing = 4.30


Required factor of safety = 1.5 SAFE
Project : MEGHALAYA POWER DISTRIBUTION CORPORATION LIMITED Rev. : 0
Title : FOUNDATION DESIGN FOR 33KV LIGHTING ARRESTER Date: 14.01.2019
3. CHECK FOR BEARING CAPACITY:

Moment in X-direction at the bottom of foundation


due to horizontal load (Fh) = 0 kN-m CCW
due to wind load (Fwx) = 4.9855 kN-m CCW
Total, Mx = 4.9855 kN-m CCW

Moment in Y-direction at the bottom of foundation


due to wind load (Fwy) = 4.9855 kN-m CCW

Total, My = 4.9855 kN-m CCW

4
Moment of inertia of the footing slab along XX, Ix = 0.0427 cm
4
Moment of inertia of the footing slab along YY, Iy = 0.0667 cm

Bearing Pressure ( q ) = [( P / A ) + / - {( MX / Iy ) ( x )} + / - {( MY / Ix ) ( z )}]


Total Vertical Load, P = 30.17 kN

2
Base pressure at point (0.5,0)= 75.098 kN/m Safe in SBC No Tension
2
Base pressure at point (-0.5,0)= 0.316 kN/m Safe in SBC No Tension
2
Base pressure at point (0,0.4)= 84.446 kN/m Safe in SBC No Tension
2
Base pressure at point (0,-0.4)= 9.032 kN/m Safe in SBC No Tension

4. PUNCHING SHEAR ZONE & PERMISSIBLE SHEAR STRESS

Effective depth of the slab (d) = 188 mm


Longer side length of punching shear zone = 738 mm
Shorter side length of punching shear zone = 738 mm
Loads on the area due to soil pressure = 40901.828 N
Effective shear force on the area = 38651.828 N
Shear force per meter of the perimeter = 13.093438 kN per meter
2
Developed shear stress τv = 0.0696459 N/mm
According to clause 31.6.3.1 of IS:456 - 2000 permissible shear stress =ksτc
βc = ( Short Side of Column / Long Side of Column ) 1
ks = 1
2
τc =0.25 sqrt(fck) = 1.118 N/mm SAFE

TWO-WAY SHEAR
Two way shear resistance, Vc1 = 17784.51 N
Thikness of the slab in two way shear, d = 139.7503 mm
Hence one way shear is more critical.

9. REINFORCEMENT OF SHAFT
d'/D = 0.116 Pu/fckbD = 0.0003719
2
Mu/fckbD = 0.0014983
Use 12 tor bars 4 Nos
As per SP:16 1980 and chart No. 44 , reinforcement are negligible and provide reinforcement, pt = 0.15%
2
Area of the longitudinal reinforcement, Asc = 453.75 mm

10. SLAB REINFORCEMENT:


2
Ultimate moment at shaft face = 17.411486 kN-m/m Mu/bd = 0.0575586
from table 2 of SP:16 1980 we get the minimum value of pt = 0.075 %
Area of reinforcement = 412.5 sqmm
Use 10 tor bars 5 Nos spacing = 235 mm C/C