HI 800 013 E H41qH51q Safety Manual PDF
HI 800 013 E H41qH51q Safety Manual PDF
HI 800 013 E H41qH51q Safety Manual PDF
Safety-Related Controller
All HIMA products mentioned in this manual are protected by the HIMA trademark. Unless not-
ed otherwise, this also applies to other manufacturers and their respective products referred to
herein.
All of the instructions and technical specifications in this manual have been written with great
care and effective quality assurance measures have been implemented to ensure their validity.
However, we cannot fully preclude flaws or typesetting errors in this manual.
For this reason, HIMA offers no warranties and assumes no legal responsibilities or liabilities
for the potential consequences of any errors in this manual. HIMA appreciates any information
concerning possible errors.
Contact
HIMA Address:
© HIMA Paul Hildebrandt GmbH + Co KG
P.O. Box 1261
68777 Brühl
Telephone +49 06202 709-0
Fax +49 06202 709-107
E-mail [email protected]
Internet http://www.hima.com
Table of Contents
1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.1 Validity and Current Version. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Formatting Conventions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2.1 Safety Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2.2 Operating Tips. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3 Target Audience. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 Intended Use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1 Application Area. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.1 Application in Accordance with the 'De-Energize to Trip Principle'. . . . . . . . . . . 9
2.1.2 Application in Accordance with the Energize to Trip Principle. . . . . . . . . . . . . . 9
2.1.3 Explosion Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1.4 Use in Fire Alarm Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Non-Intended Use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3 Operating Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3.1 Environmental Requirements and Specifications. . . . . . . . . . . . . . . . . . . . . . . 10
2.3.2 Climatic Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.3.3 Mechanical Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3.4 EMC Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3.5 Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.3.6 ESD Protective Measures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.4 Personnel Qualifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.5 Requirements to be met by the operator and the machine and system manufac-
turers.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3 Safety Philosophy and Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1 Certification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 Safety and Availability. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.1 Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.2 Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3 Safety Times. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.4 Proof Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.4.1 Proof Test Execution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.4.2 Frequency of Proof Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.5 Safety Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.5.1 Hardware Project Planning: Product-Independent Requirements. . . . . . . . . . 19
3.5.2 Hardware Project Planning: Product-Dependent Requirements. . . . . . . . . . . . 19
3.5.3 Programming: Product-Independent Requirements. . . . . . . . . . . . . . . . . . . . . 19
3.5.4 Programming: Product-Dependent Requirements. . . . . . . . . . . . . . . . . . . . . . 19
3.5.5 Communication: Product-Dependent Requirements. . . . . . . . . . . . . . . . . . . . . 20
3.5.6 Special Modes of Operation: Product-Independent Requirements. . . . . . . . . . 20
4 Central Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.1 Central Modules and Kits for the H41q and H41qc Systems. . . . . . . . . . . . . . 21
4.2 Central Modules and Kits for the H51q System. . . . . . . . . . . . . . . . . . . . . . . . 21
4.3 Additional Central Modules for the H41q, H41qc and H51q Systems. . . . . . . . 22
4.4 General Notes on the Safety and Availability of Safety-Related Central Modules.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.4.1 Power Supply Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.4.2 Functional Description of the Safety-Related F 8652 X / F 8650 X Central Modu-
les. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
4.5 Principles of Function of Safety-Related Central Modules. . . . . . . . . . . . . . . . 24
4.5.1 Self-Test Routines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.5.2 Response to Faults Detected in Central Modules. . . . . . . . . . . . . . . . . . . . . . . 25
4.5.3 Diagnostic Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Appendix
1 Standard Software Function Blocks for the Central Area. . . . . . . . . . . . . . 67
1.1 HK-AGM-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
1.2 HK-COM-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
1.3 HK-MMT-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
1.4 H8-UHR-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
2 Standard Software Function Blocks for the I/O Area. . . . . . . . . . . . . . . . . . 68
2.1 H8-STA-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
2.1.1 Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
2.2 HA-LIN-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
2.3 HA-PID-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
2.3.1 Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
2.3.2 Outputs:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
2.4 HA-PMU-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
2.5 HA-RTE-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
2.5.1 Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
2.5.2 Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
2.6 HB-BLD-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
2.6.1 Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
2.6.2 Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
2.7 HB-BLD-4 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
2.7.1 Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
2.7.2 Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
2.8 HB-RTE-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
2.8.1 Inputs:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
2.8.2 Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
2.9 HF-AIX-3 Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
2.10 HF-CNT-3 Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
2.11 HF-CNT-4 Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
2.12 HF-TMP-3 Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
2.13 HK-LGP-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
2.14 HZ-DOS-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
2.15 HZ-FAN-3 Function Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
2.15.1 Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
2.15.2 Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Index of Figures
Index of Tables
1 Introduction
This manual contains information on how to operate the H41q and H51q safety-related
automation devices from HIMA in the intended manner.
The following conditions must be met to safely install and start up the H41q/H51q automation
devices, and to ensure safety during their operation and maintenance:
• Knowledge of regulations.
• Proper technical implementation of the safety instructions detailed in this manual
performed by qualified personnel.
HIMA will not be held liable for severe personal injuries, damage to property or the
environment caused by any of the following:
• Unqualified personnel working on or with the devices.
• De-activation or bypassing of safety functions.
• Failure to comply with the instructions detailed in this manual.
HIMA develops, manufactures and tests the H41q/H51q automation devices in compliance
with the pertinent safety standards and regulations. The use of the devices is only allowed if
the following conditions are met:
• They are used for the intended applications.
• They are operated under the specified environmental conditions.
• They are only connected to the approved external devices.
To provide a clearer exposition, this manual does not specify all details of all versions of the
H41q/H51q automation devices.
Chapter 1.2.3 Cross references are hyperlinks even though they are not particularly
marked. When the cursor hovers over a hyperlink, it changes its shape.
Click the hyperlink to jump to the corresponding position.
These notes must absolutely be observed to reduce the risk to a minimum. The content is
structured as follows:
• Signal word: danger, warning, caution, notice
• Type and source of danger
• Consequences arising from the danger
• Danger prevention
SIGNAL WORD
Signal Word! Type and source of danger.
Consequences arising from the danger
Danger prevention
NOTE
2 Intended Use
Standard Content
IEC/EN 61131-2: Programmable controllers, Part 2:
2006 Equipment requirements and tests
IEC/EN 61000-6-2: EMC
2005 Generic standard, Part 6-2
Immunity for industrial environments
IEC/EN 61000-6-4: Electromagnetic compatibility (EMC)
2006 Generic emission standard, industrial environments
All modules of the H41q and H51q systems meet the requirements of the EMC Directive of
the European Union and are labeled with the CE mark.
The systems react safely to interferences exceeding the specified limits.
Electrostatic discharge can damage the electronic components within the systems.
• Touch a grounded object to discharge any static in your body.
• When performing the work, make sure that the workspace is free of static, and wear an
ESD wrist strap.
• If not used, ensure that the device is protected from electrostatic discharge, e.g., by stor-
ing it in its packaging.
Only personnel with knowledge of ESD protective measures may modify or extend the sys-
tem wiring.
2.5 Requirements to be met by the operator and the machine and system
manufacturers.
The operator and the machine and system manufacturers are responsible for ensuring that
3.1 Certification
The safety-related automation devices (PES = programmable electronic system) of the H41q,
H41qc and H51q system families are certified as follows:
The safety-related automation devices of the H41q, H41qc and H51q system families are
tested and certified in accordance with the following relevant functional safety standards:
IEC 61508: Parts 1-7: 1998-2000 up to SIL 3
IEC 61511: Part 1-3: 2004 up to SIL 3
EN/ISO 13849-1: 2008 Category 4, Performance Level e
EN 50156-1: 2004
EN 12067-2: 2004, EN 298: 2003, EN 230: 2005
NFPA 85: 2007, NFPA 86: 2007
EN 61131-2: 2007
EN 61000-6-2: 2005, EN 61000-6-4: 2007
EN 54-2:1997, A1: 2006, NFPA 72: 2010
EN 50130-4: 1998 + A1: 1998 + A2: 2003 + Corr. 2003
Chapter 2.3 contains a detailed list of all environmental and EMC tests performed.
3.2.1 Safety
The PFD (probability of failure on demand) and PFH (probability of failure per hour) values
were calculated for the safety-related H41q, H41qc and H51q systems in accordance with
IEC 61508.
IEC 61508-1 prescribes for SIL 3:
• A PFD value of 10-4...10-3
• A PFH value of 10-8...10-7 per hour
15 % of the limit value for PFD and PFH specified in the standard is assumed for the
controller. The resulting limit values for the controller's proportion:
• PFD = 1.5 ∗ 10-4
• PFH = 1.5 ∗ 10-8 per hour
A proof test interval of 10 years1) has been defined for the safety-related systems H41q,
H41qc and H51q.
The safety functions, consisting of a safety-related loop (an input, a processing unit and an
output), meet the requirements described above in all combinations.
3.2.2 Overview
The following table presents an overview of the system designations, safety, availability and
configurations
the peripherals (sensors and actuators within the plant) as redundant modules. Experience
shows that these components have higher failure rates than the PES modules.
1)
Refer to Chapter 6.5 for further information on the F 3430 relay module.
When redundant modules are used for increasing availability, three essential points must be
considered:
• Faulty modules must be detected and shut down to prevent the system from being
blocked.
• If a fault occurs, the operator must receive a message indicating that the module must
be replaced.
• Once the module has been replaced, it must automatically start operation.
The HIMA automation systems with the corresponding configuration meets these
requirements.
To program the devices, a PADT (programming and debugging tool, PC) is used with the
following programming tool
ELOP II
In accordance with IEC 61131-3 is used. It supports the user while operating the automation
devices and creating safety-related programs.
Failures, which can only have a dangerous impact on safety if combined with additional faults
are detected by background tests within the multiple fault occurrence time (MOT). The
multiple fault occurrence time is defined when the safety time is set and is defined in the
operating system as 3600 times that value.
Example of response time: a maximum of two times the cycle time. If a fault tolerance time
(safety time) of 1s is required for the process, the cycle time may not exceed 500 ms.
For operating system versions prior to (07.14), the safety time must not be set to 255 s!
i Only values within 1...254 are allowed!
HIMA safety systems must be subjected to a proof test in intervals of 10 years1). It is often
possible to extend this interval using the a calculation tool to analyze the implemented safety
loops.
With relay modules, the proof test must be performed in the intervals defined for the plant.
According to IEC 61508 1-7, IEC 61511 1-3 and VDI/VDE 2180 sheets 1 to 4, the operator of
the safety-related systems is responsible for performing the proof tests.
In practice, shorter proof test intervals are required for the input and output field devices (e.g.,
every 6 or 12 months) than for the HIMA controller. Testing the entire safety loop together
with a field device automatically includes the test of the HIMA controller. There is therefore
no need to perform additional proof tests of the HIMA controller.
If the proof test of the field devices does not include the HIMA controller, the HIMA controller
must be tested at least once every 10 years. This can be achieved by restarting the HIMA
controller.
1)
Exception: The F 3430 module must be tested for SIL 3 in intervals of 5 years.
Additional proof test requirements for specific devices are described in the corresponding
data sheets.
i The operating company is responsible for operating a plant safely in accordance with the
relevant application standards.
4 Central Modules
The central components required for the different types of HIMA automation devices are
assembled in kits. The kit of a funcitoning central module is composed of the following
elements:
• Central subrack
• Central modules
• Power supply units
• Accessories
The detailed scope of delivery, the supply voltage wiring and the connection of the I/O level
are described in the data sheets of the catalog Programmable Systems, System Families
H41q/H51q (HI 800 263).
4.1 Central Modules and Kits for the H41q and H41qc Systems
4.3 Additional Central Modules for the H41q, H41qc and H51q Systems
Table 5: Safety and availability, differences between H41q, H41qc and H51q
Test Description
CPU test The following is tested:
• Command and Addressing Types
• The writability of the flags and the commands related to the
flags.
• The writability and crosstalk of the registers.
• Arithmetic logic unit (ALU)
Memory areas test The operating system, user program, constants and parameters
as well as the variable data are stored in each central module
directly and inversely and are checked for antivalence by a
hardware comparator.
Fixed memory areas The operating system, user program and parameter area are
each stored in a flash EPROM and are protected by a CRC test.
RAM test A write and read test is performed to check the RAM areas, in
particular for crosstalk.
Watchdog test The watchdog signal is switched off unless it is triggered within a
determined period by both the CPUs with antivalent bit patterns
or if the hardware comparator detects a difference between the
two memories (directly and inversely). An additional test deter-
mines the watchdog signal’s switch-off ability.
Test of the connection to If the central modules in the H41q-HS / H41qc-HS / H51q-HS
the I/O level within the systems are used redundantly with a single-channel I/O bus, the
central module reciprocal interlocking of the I/O access to the central modules
is ensured. Self-tests check the interlocking circuit used to this
end.
With a two-channel I/O level, HR or HRS system, the I/O access
rights are read back and checked.
With a single-channel I/O level, M or MS system (single-channel
I/O modules and single-channel CPU), the I/O access rights are
read back and checked.
Test of the connection The addressing is tested cyclically after the safety-related I/O
module in the I/O sub- module has been processed.
racks The addresses of all agreed I/O module positions are read back
and tested. The safety switches of the F 7553 module are
tested.
If the defective central module of a redundant system is replaced by a functional one with the
same user program and operating system, the new central module receives the current data
from the running central module and the system restarts redundant operation.
Uder certain conditions, such as the same operating system version which must be at least
7.0-8 (05.21), the running central module can load the user program in the new "empty"
central module (self-education). For more details, refer to the Chapter Self-Education of the
operating system manual (HI 800 105 E).
If faults occur in the central module, the CPU LED is lit. STOP appears on 4-digit display. It
is possible to intervene to show the error code. The operating system manual (HI 800 105 E)
provides a list of the error codes.
If faults occur in the safety-related modules at I/O level, the IO LED is lit. The 4-digit display
shows the module position and possibly the faulty channel.
The diagnostic system provides all error codes to be visualized in the process control system.
The diagnostic system maintains an error history. The error history can be displayed in the
PADT and is of help for detecting problems within the plant.
If a fault in the I/O bus area only occurs within an I/O subrack, the connection module
switches off the output module in the affected I/O subrack.
If faults occur or during maintenance, the following steps are required for replacing the
modules:
The diagnostic indicator on the central module displays BATI to signalize that the internal
battery is empty.
Refer to the data sheet for recommendations on how to replace the battery on the modules.
If the battery fails simultaneously to a voltage drop, the RETAIN variables lose the values
i previously stored. In such a case, the system initializes the values during start-up.
5 Input Modules
Table 7: Input modules for the H41q, H41qc and H51q systems
The safety-related input modules allows one to display a diagnosis and therefore to identify
and locate the faults.
In safety-related systems, both safety-related and non-reactive input modules can be used
i with mixed component configurations.
During operation, safety-related input modules automatically perform high-quality, cyclic self-
tests within the H41q, H41qc and H51 systems. The input modules include wiring elements
ensuring that the input module function is tested with special test routines integrated in the
operating system. These test routines are TÜV tested and ensure the safe functioning of the
corresponding module. If faults are detected, error messages are displayed. Detected faults
automatically trigger a safety-related reaction of the system. The error messages are
diagnostic information for the operator. It is thus possible to flexibly create a diagnostic
system when planning and implementing the system.
To increase availability, the safety related input module can also be used redundantly.
Using redundant input modules does not affect the system safety.
Safety-related input modules can be used for both safety-related signals and non-safety-
related signals.
The following conditions must be observed when using the slots permitted for input modules
within the system subracks, and the H41q, H41qc and H51q systems within the I/O subracks:
The wiring of the sensors can improve their safety and availability. Chapter 7.8 provides a
detailed description of how to implement the various sensor wiring options taking the aspects
of safety and availability into account. The user program must be designed accordingly.
Based on the IEC 61508 standard, proof test intervals are defined and allow one to provide
various proofs of safety. The detailed definitions of proof tests depend on the application.
The modules for proximity switches and contact makers with line monitoring additionally test
the line up to the sensor. A safety-related proximity switch can be connected to these
modules. Self-tests ensure that all requirements to the detection of thresholds for safety-
related proximity switches are met.
The sensor current monitoring for a contact maker requires wiring with two resistors in
accordance with the data sheet.
If the gate time is modified, the correct measured value is only available on the output after
i three gate times.
Table 10: Reaction to faults detected in the safety-related F 5220 counter module
Table 11: Reaction to faults detected in safety-related analog F 6213, F 6214 input
modules
Table 12: Reaction to faults detected in safety-related analog F 6217 input modules
The module has its own 1oo2 microprocessor system that automatically performs safety-
related online tests and provides the safe data to the safe processing unit. Each channel has
an analog value and a corresponding channel fault bit.
WARNING
Warning! Physical injury due to incorrect measured values possible!
If the channel fault bit is set, a safety-related reaction must be programmed for each
safety-related analog input.
Table 13: Reaction to faults detected in the safety-related F 6220 thermocouple input
module
The Underflow Threshold and Overflow Threshold inputs of the HF-TMP-3 function block are
used to define the limit values for underflow and overflow, respectively. If the measured value
for the configured threshold values is exceeded, the corresponding signal is set to TRUE,
even if no fault occurred in the module.
Table 14: Reaction to faults detected in the safety-related analog F 6221 input module
The Underflow Threshold and Overflow Threshold inputs of the HF-AIX-3 function block are
used to define the limit values for underflow and overflow, respectively. If the measured value
for the configured threshold values is exceeded, the corresponding signal is set to TRUE,
even if no fault occurred in the module.
The checklists associated with this safety manual are available as MS Word files (*.doc) on
the HIMA DVD or can be downloaded from the corresponding Internet page at
www.hima.com.
6 Output Modules
6.1 Overview of All Output Modules for the H41q, H41qc and H51q Systems
Table 15: Output modules for the H41q, H41qc and H51q systems
Additionally, a walking bit test is performed through all outputs within the multiple fault
occurrence time (MOT); during the test, the test signal is present for no longer than 200 µs.
This ensures that the switchability of the outputs is verified without affecting the function of
the connected actuators. As a result, the freezing of each output is detected, even if the
output signal is static.
Safety-related output modules with line monitoring can detect faults in the input lead to the
load. The line monitoring function meets the safety requirements up to SIL 1. This is only
relevant if line monitoring is used in safety-related circuits. The output signal can be used in
all applications for safety requirements up to SIL 3.
Table 16: Slots for output modules in the H41q, H41qc and H51q systems
Additionally, the H8-STA-3 function block can be used to define one or multiple shutdown
groups. An output module fault causes then all remaining output modules of the shutdown
group to be shut down.
Depending on the system safety requirements, the I/O parameters in the resource settings
can be used to configure a complete shutdown of the controller.
In current source mode, if a fault occurs, the integrated safety shutdown ensures the safe
state (output current 0 mA).
In current sink mode, the safe state can only be achieved taking additional measures. The
user program must safely shut down the supply voltage for the current loop. The faults are
evaluated using the HZ-FAN-3 function block.
IO Bus
Figure 1: Principle of the output module circuit with integrated safety shutdown (here with
4 output channels)
• All faults detected in the modules cause the affected module to enter the safe, de-
energized state, i.e., the module is shut down.
• External short-circuits cause the fuse for the relevant channel to trigger. No error
message is generated.
At nominal operating conditions, the service life is approx. 300 000 switching operations at
30 VDC and 4 A.
To meet the requirements in accordance with IEC 61508 (PFD/PFH, see Chapter 3.2.1), the
proof-test interval is of 5 years for use in SIL 3 and 20 years for use in SIL 2.
An external open-circuit cannot be distinguished from internal faults and cause the module to
be shut down.
In current sink mode, the module can only enter the safe, de-energized state via an external
shutdown. The user program must shut down the voltage supply for the current loop safely.
Therefore, the HZ-FAN-3 function block must be used for evaluating the faults.
The checklists associated with this safety manual are available as MS Word files (*.doc) on
the HIMA DVD or can be downloaded from the corresponding Internet page at
www.hima.com.
7 Software
The software for the safety-related HIMA automation devices of the H41q/H41qc and H51q
system families is divided into three blocks:
• Operating system
• User program
• Programming tool in accordance with IEC 61131-3 (ELOP II with intergated safety
tool).
The operating system must be used in the current version certified by TÜV for safety-related
applications. This version can be found in the version list maintained together with the test
authority (Revision List of Devices and Firmware of H41q/H51q Systems). This document is
created by the joint modification service from TÜV Rheinland Industrie Service GmbH and
HIMA.
The user program is created using the ELOP II programming tool and contains the
application-specific functions to be performed by the automation device. ELOP II is also used
to set the parameters for operating system functions. A code generator translates the user
program into a machine code. ELOP II uses a serial interface or the Ethernet interface to
transfer this machine code to the flash EPROM of the automation device central module.
The main functions of the operating system and the resulting specifications for the user
program are described in the table Operating System Functions of the operating system
manual (HI 800 104 D).
A cycle is processed in seven phases. Refer to the operating system manual (HI 800 105 E)
for more details on these phases.
Terms
Load This term indicates the procedure for loading a program into the controller,
either by performing a download or a reload.
Download If a download is performed to load a program into the controller, the controller
is stopped and all its outputs are reset.
Reload If a reload is performed to load a user program into a redundant controller, the
modified user program can be loaded into the central modules one after the
other. In the process, a central module is always operating in MONO mode.
The controller is not stopped.
If the PES only equipped with one central module, the outputs are held for the
duration of the loading process.
A reload can only be performed if a reloadable code was generated befor-
hand.
The automation concept of the system must include an analysis of the field circuits, i.e., the
type of sensors and actuators:
• Sensors (digital or analog)
• Signals during normal operation (de-energize-to-trip principle with digital sensors, life-
zero with analog sensors)
• Signals in the event of a fault:
• Definition of required safety-related redundancies (1oo2, 2oo3)
• Discrepancy monitoring and reaction.
• Actuators
• Positioning and activation during normal operation
• Safe reaction/positioning at shutdown or after power loss.
When starting up a safety-related controller for the first time, a comprehensive functional test
is performed to verify the safety of the entire system. So far, to ensure safety, if the user
program changed, a complete functional test was required.
The safety tool included in ELOP II is in accordance with IEC 61131-3 and ensures that only
the changes must be verified, if the user program is modified. This safety tool is used to detect
user mistakes and programming tool failures.
The ELOP II safety tool is composed of three function blocks essential for safety:
• C code comparator
• Target code comparator
• Proven GNU C compiler.
The C code comparator identifies changes performed to the user program. The target code
comparator compares two target codes generated consecutively by the GNU C compiler
(GNU CC). This action prevents faults due to an unsafe PC.
DANGER
Danger! Physical injury due to malfunction possible!
A cross-reference list must be generated for the user program and checked for cor-
rect use of the variables. It must be verified that all variables are only used in the posi-
tions indicated in the specification.
3. The proven compiler (GNU CC) translates the C code and the comparison file, points
(6) and (13). The target code and the comparison code are generated.
DANGER
Danger! Physical injury due to malfunction possible!
The target code comparator must be activated, point (14). It compares the target code
and the comparison code. It also detects and reports faults caused by the not safe PC.
4. Load the resulting operational program into the H41q or H51q system, point (7). Then,
the program must be completely tested and accepted, point (8).
5. Generate a backup of the target code.
6. The PES starts safe operation.
7.2.2.2 Usíng the ELOP II Safety Tool when Modifying the Program
1. Modification of a user program in accordance with a binding specification (e.g., based
upon IEC 61508, DIN V VDE 0801 or a corresponding user standard); points (1)
through (4) in the flow diagram.
The modification is based on the backup of the running user program. This backup in-
cludes:
• Comparison file
• Target code
• Input data
2. The C code generator compiles the modified user program in the C codenew, point (5).
3. The C code comparator must be activated, point (12). It compares the C codenew with
the C codeold of the previous program version, point (11). The backup must be
indicated as comparison file (old C code).
4. The result of the comparison is documented, point (15).
5. Check whether the C code comparator displays the changes performed to the user
program. Only code-relevant changes are indicated.
Symbolic names are also used for physical inputs and outputs and may include up to 256
characters.
The user has two essential advantages when using symbolic names instead of physical
addresses:
• The system denominations of inputs and outputs are used in the user program.
• The modification of how the signals are assigned to the input and output channels
does not affect the user program.
7.2.3.1 Assigning PCS Names to Variable Names
PCS names should be assigned to variable names in accordance with the measuring points
list or a list of sensors and actuators.
Variable names are assigned to the used hardware in the dialog box for the resource, under
Process cabinet. The following information is entered: Required subrack type and position (1-
1 through 1-8 or 2-1 through 2-8), the slot and type of the required module and the PCS names
to be assigned to the variable names.
TIP For practical reasons, the variable name and the PCS name should be identical.
The number of channels (names) per module depends on the type of module used. The
required test routines for safety-related I/O modules are automatically executed by the
operating system.
HIMA recommends grouping the input and output modules used in the I/O subracks into
functional units.
The functional units may be grouped in accordance with the following aspects:
• Grouping in accordance with the plant parts
Homogenuous arrangement of the modules such as:
• Digital/analog system components
• Safety-related/non safety-related I/O modules
• Redundant grouping into various I/O subracks in the same order
• Spare modules or channels for later reload (reloadable code)
power supply.
For most analog safety-related and non safety-related I/O modules, HIMA function blocks
must be used in the user program, see Annex.
7.2.3.5 Imported or Exported Variables
The data of the variables to be imported or exported are either forwarded for HIMA
communication via HIPRO (PES master) or to third-party systems via the serial interfaces.
Protocols available for third-party systems are Modbus, Modbus TCP, PROFIBUS DP and
3964R. The data can also be transmitted to an OPC server via an Ethernet protocol. The
import and export variables are processed in the user program like normal input and output
variables. They are defined in the variable declaration of the program instance.
Boolean variables may be assigned the Event attribute. Events are signal changes of
Boolean variables with additional information about the time (date and time). The timestamp
Changes of the basic addresses for external/Modbus coupling may result in a change of the
code version number. With all other changes, the code version number changes as well.
7.2.4.2 Run Version Number
The controller generates the run version number during operation. Its comparison with a
currently valid and documented run version number shows whether the program loaded into
the controller has changed (which is also displayed on the diagnostic indicators).
The run version number changes in the following cases:
• A different code version number is in use (does not apply to all changes)
• Modules were added or deleted
• Other system parameters are in use
• VAR_CONST have been added or deleted
• VAR_CONST values have changed
• The resource type has changed
• Setting have been changed online
• I/O variables have been forced in the online test field
• The position of the force main switch has changed
7.2.4.3 Data Version Number
The data version number refers to the definition of non-safety-related imported or exported
variables and changes in the following case:
• If the name of a variable with attributes for HIPRO-N (non safety-related) changes.
• If these variables were compressed when generating a non-reloadable code (if
memory gaps exist).
7.2.4.4 Area Version Number
The area version number records all the variables defined in a project and changes in the
following cases:
• If modules are deleted or added modules within the control cabinet.
• If the generation of reloadable code is set and more variables are associated with the
attributes of the following types than are deleted:
HIPRO N, HIPRO S, BUSCOM, event, 3964R
• If the generation of non-reloadable code is set and variables are added or deleted and
are associated with the attributes of the following types:
HIPRO N, HIPRO S, BUSCOM, event, 3964R.
• If the memory must be reorganized because the memory limit was achieved.
Changes of the basic addresses for external/Modbus coupling may result in a change of the
area version number.
Table 18: Standard function blocks, not depending on the I/O level
1)
In the TÜV test column, the symbol • indicates that a TÜV safety certificate exists for the corre-
sponding function block. For the safety-related application of the function blocks, refer to the doc-
umentation of these function blocks.
Refer to the HIMA website at www.hima.com and the HIMA DVD for further details.
For operating system versions prior to (07.14), the safety time must not be set to 255 s!
i Only values within 1...254 s are allowed!
Parameters that may be defined for safety-related operation are not firmly bound to any spe-
i cific safety integrity levels. Instead, each of these must be agreed upon together with the
responsible test authority for each separate implementation of the automation device.
Setting Description
Display only Shutdown via safety shutdown integrated in the output amplifier. If not
possible, the watchdog signal within the I/O subrack is switched off via the
connection module (systems H51q only).
The watchdog signal in the corresponding central module is not switched
off.
The user program and communication continue to run.
Only allowed up to SIL 1!
Emergency The watchdog signal of the corresponding central module is switched off,
stop which also results in the shutdown of the output channels.
The user program and communication are stopped.
Normal oper- Reaction as described in Display only; additionally, the watchdog signal in
ation the corresponding grouping is switched off if a group was configured
beforehand using the H8-STA-3 function block Chapter 2.1 in the Annex.
The watchdog signal in the corresponding central module is switched off
(error stop) if no group was configured beforehand or the groupe relay is
faulty. In this scenario, the user program and communication are stopped.
Required with SIL 2 and beyond.
Usual and recommended setting.
Table 21: Setting for the Behavior in Case of Output Faults parameter
When a fault occurs, communication with the PADT does not depend on the setting of the
Behavior in Case of Output Fault parameter.
7.2.8 Checking the Created User Program for Compliance with the Specified
Safety Function
A number of suitable test cases covering the specification must be created for the verification.
It is not necessary to perform 220 test cases for 20-fold AND gates. The independent test of
each input and of the most important logic connections is usually sufficient. This series of
tests is sufficient since ELOP II and the measures defined in this safety manual make it
sufficiently improbable that a code generated properly from a semantic and syntactic view
point can still contain undetected systematic faults resulting from the code generation
process.
An appropriate series of tests must also be generated for numerically evaluating formulas.
Equivalence class tests are convenient which are tests within defined ranges of values, at the
limits of and within invalid ranges of values. The test cases must be selected such that the
calculation can be proven to be correct. The required number of test cases depends on the
formula used and must include critical value pairs.
To this end, the online test can be useful, e.g., for presetting values and read intermediate
values. However, the active simulation with sources must be performed since it is the only
way to verify the proper wiring of the sensors and actuators. This is also the only way to verify
the system configuration.
A reload is only permitted after receiving consent from the test authority responsible for the
i final system acceptance test. When performing the reload, the person in charge must take
further technical and organizational measures to ensure that the process is sufficiently mon-
itored in terms of safety.
WARNING
Warning! Physical injury due to malfunction possible!
• Prior to performing the reload, use the C code comparator integrated in the safety
tool of ELOP II to determine the changes performed to the user program compared
to the user program still running.
• The changes caused by the reload must be carefully tested on simulators prior to
transferring them to the PES.
If a reload may be performed to load the user program into the central module(s), the
message Reloadable Code appears while the code generator is compiling the code.
Reloadability is lost if the following changes are performed to the user program:
• Modules located in the control cabinet are deleted or added.
• More variables are associated with the attributes of the following types than are
deleted:
HIPRO N, HIPRO S, BUSCOM, event, 3964R
• The basic addresses for BUSCOM are modified, see Chapter 7.2.4.4.
• Assignments to system variables are added or modified.
This does not apply to all system variables; refer to the operating system manual
(HI 800 105 E) for further details.
• Names of HIPRO S variables are modified.
While the user program is being loaded, the controller interfaces are not processed by the
user program and imported or exported variables are not routed via the interfaces.
7.6 Forcing
Forcing is only permitted after receiving consent from the test authority responsible for the
final system acceptance test. When forcing values, the person in charge must take further
technical and organizational measures to ensure that the process is sufficiently monitored in
terms of safety.
Forcing in safety-related controllers must be performed in accordance with the current ver-
i sion of the document Maintenance Override published by TÜV Rheinland Industrie Service.
The document may be downloaded from the Internet at www.tuvasi.com.
For further details on the forcing procedure refer to the operating system manual
(HI 800 105 E) and the ELOP II online help.
DANGER
Danger! Physical injury due to malfunction possible!
All force markers must be removed from the user program prior to starting safety-
related operation or before an acceptance test is performed by a test institute!
Refer to the ELOP II online help for details on the force markers.
All requirements about protection against manipulation specified in the safety and applica-
i tion standards must be met. The operator is responsible for authorizing employees and
implementing the required protective actions.
Together with the responsible test authority, the operator must define which measures
should be implemented to protect the system against manipulation.
If an error occurs in a safety-related digital I/O module, the input is set to the safe value 0 and
the digital output module is switched off by the integrated safety shutdown. Refer to the
description of the software function blocks provided in the Annex for details.
Compared to hard-wired controllers, programmable logic controllers are provided with a more
extensive range of functions, in particular with respect to byte and word processing.
Analog Analog
F 6213 HA-RTE-3 F 6705 HZ-FAN-3
F 6214 HA-RTE-3
F 6220 HF-TMP-3
F 6221 HF-AIX-3
For safety-related I/O modules, the corresponding software function blocks must be added to
the user program. Refer to the annex or the description of the software function block
provided in the ELOP II online help for further details.
Programming
Safety considerations
The output is switched off if one of the two sensors is triggered or a components fails within
the system.
The relevant standards, e.g., IEC 61511, must be observed used for sensor applications.
Availability considerations
No availability since each component failure causes a shutdown.
Wiring, hardware
1) e.g., 50
2) e.g., 50
3) 7777, if the physical size increases in dangerous situations (every four module channels),
0000, if the physical size decreases in dangerous situations (every four module channels)
4) Values 0...1066
Figure 7: Use of the HA-RTE-3 function block with the F 6213 or F 6214 module
Comparator element for alarming or shutting down upon achievement of the allowed
threshold
Figure 8: Comparator element for alarming or shutting down upon achievement of the al-
lowed threshold
Safety Considerations
The output A has a high level if one of the two sensors is triggered or a components fails
within the system.
The relevant standards, e.g., IEC 61511, must be observed for sensor applications.
Availability Considerations
No availability since a shutdown occurs whenever a component fails or a sensor is triggered.
This documentation is required for the acceptance test of a system subjected to approval by
a test authority (e.g., TÜV). This acceptance test only applies to the user functionality, but not
to the safety-related HIMA automation devices H41q-MS, H51q-MS, H41q-HS, H51q-HS,
H41q-HRS, H51q-HRS that have already been approved.
HIMA recommends involving the test authority as soon as possible when designing systems
i that are subject to approval.
The monitoring time to be set depends on the process and must be agreed upon together with
the responsible test authority.
Safety-related communication can also occur via the TÜV-certified safeethernet protocol
using the F 8627 X or F 8628 X Ethernet communication modules.
The data transmission time TT resulting from the moment in which a sensor changes on a
PES to the moment in which an output on another PES responds to the change, is:
Digital connectors
Analog connectors
For the application, the REOL, RL and RShunt resistors must be calculated as dictated by the
sensors in use and the number of sensors per detection loop. The data sheets provided by
The alarm outputs for controlling lamps, siren, horns etc. are operated in accordance with the
energize to trip principle, which means that output modules with line monitoring must be used
(e.g., the F 3331 or F 3334 modules).
A user program appropriately adjusted, can be used to control visual display systems,
indicator light panels, LED indicators, alphanumeric displays, audible alarms, etc.
The routing of fault signals via the input and output modules or to transmission equipment for
fault signals must occur in accordance with the de-energize to trip principle.
The transmission of fire alarms among HIMA systems can be realized using the available
communication standards such as Modbus, HIPRO S, or OPC (Ethernet). The
communication monitoring is an essential part of the user program. HIMA recommends
configuring communication redundantly to ensure communication even if a transmission
component (line, hardware fault, etc.) fails. The component failure must be reported and the
replacement or repair of the faulty component during operation should be ensured.
H41q, H41qc or H51q systems that are used as fire alarm systems must have a redundant
power supply. Precautionary measures must also be taken against power supply drops, e.g.,
the use of a battery-powered horn. Switching from the main power supply to the back-up
power supply must be performed as fast as possible to ensure uninterrupted operation.
Voltage drops of up to 10 ms are permitted.
If a fault occurs in the system, the operating system writes to the system variables that can
be evaluated in the user program. This allows the user to program fault signaling for faults
detected by the system. If a fault occurs, the safety-related inputs and outputs are switched
off, i.e., low levels are applied to all the channels of faulty input modules and all the channels
of faulty output modules are switched off.
Earth fault monitoring is required if fire detection and fire alarm systems in accordance with
EN 54-2 and NFPA 72 are used.
Appendix
The function block is not safety-relevant. The function block's outputs serve informative
purposes only, and no safety-related actions may be derived for the user program.
The function block is not safety-relevant. The function block's outputs serve informative
purposes only, and no safety-related actions may be derived for the user program.
The function block is not safety-relevant. The function block's outputs serve informative
purposes only, and no safety-related actions may be derived for the user program.
The function block's outputs serve informative purposes only, and no safety-related actions
may be derived for the user program.
For details on the behavior in the event of output channel faults, refer to Chapter 7.2.6.2.
2.1.1 Inputs
The positions of the modules belonging to the shot-down group are input as four place
decimals in accordance with the values defined in the selected resource.
If modules with integrated safety shut-down are used, either the Bus No. Rack Pos. Group
Amplif. or Bus No. Rack Pos. red. Group Amplif. input must be used. To do so, specify an
existing but currently unoccupied slot.
Output modules with integrated safety shut-down need no group shut-down. A group shut-
i down, however, can also be preset for this type of modules. If this is done, an output mod-
ule's failure causes all modules belonging to a specific group to shut down (in accordance
with the specifications on the H8-STA-3 function block).
2.3.1 Inputs
True=Manual (PID=0), If the control function block is safely operating, these inputs must
True=Manual, Compen- not be used. Divergences must be approved by the test authority
sating responsible for the final inspection.
Parameters and constants in the function block inputs may only be
changed during operation if approved by the responsible test
authority and during monitored operation.
The function block inputs may not be assigned with non-safety-
related imported variables.
2.3.2 Outputs:
Safety shut-downs are only allowed using the following parameters:
Maximum Value Reached and Diff Maximum Reached
Divergences must be approved by the test authority responsible for the final inspection.
The control algorithm of the function block is not able alone to ensure the safe state in all
i cases. Additional measures could be necessary on an individual basis.
2.5.1 Inputs
Bus No. Rack Pos. (e.g., 1305) Position of the safety-related analog input module and, if
Bus No. Rack Pos. red. Mod. existing, of the redundant module as four-digit decimal num-
ber.
Example: 1305 means:
Cabinet 1, subrack 3, module position 05 (for redundant
operation, the redundant module must have a different posi-
tion)
0 = No Damping; 1 = Damping 1 for redundant operation only. The difference between the
current value and the value from the previous cycle is added
to the allowed difference in ‰ (Tolerated Differ. red. Values
in 0,1 %).
Maximum Test Time in min Limitation of the test time expressed in minutes. Upon com-
pletion of the test time, the actual value is once again pro-
cessed in the user logic. See also the document
Maintenance Override available on the TÜV Rheinland's
website: www.tuvasi.com.
2.5.2 Outputs
Value 1...4 The use of values must be verified if the values are
employed for shutting down safety-related circuits.
Error Value 1...4 The outputs must be in use to trigger a shut-down with their
Boolean values if faults occur.
The remaining outputs serve informative purposes only, and no safety-related actions may
be derived for the user program.
2.6.1 Inputs
Bus No. Rack Pos. (e.g., 1305)“ Position of the safety-related digital output module as four-
digit decimal number,
Example: 1305 means:
Cabinet 1, subrack 3, module position 05
Mode Channel n (0/1/2) Assign- Description
ment
1 Normal operation, detected errors are reported at
the corresponding Error Channel n with high
level, the output circuit of the module is closed
0 Fault evaluation, error messages are suppressed
2 Only plant-specific allowed, inverse operation,
i.e., the output circuit should be open
>2 Range of values exceeded: The channel is con-
sidered as faulty (output is TRUE) and a channel-
related error is output.
Usually the de-energized to trip principle applies for safety-
related control circuits.
Max. Time Inrush Current in ms Definition of the waiting time for detecting open-circuits or
the tolerance time for current limiting. No faults are displayed
during this time period. Increasing the waiting time causes
also the cycle time to rise.
2.6.2 Outputs
The Pulse on Error (2x), Error and Error Code outputs serve informative purposes only, and
no safety-related actions may be derived for the user program.
The remaining outputs may be used for safety-related actions.
2.7.1 Inputs
Bus No. Rack Pos. (e.g., 1305) Position of the safety-related digital output module and, if
Bus No. Rack Pos. red. Mod. existing, of the redundant module as four-digit decimal
number.
Example: 1305 means:
Cabinet 1, subrack 3, module position 05
Mode Channel n (0/1/2) Assign- Description
ment
1 Normal operation, detected errors are reported
at the corresponding Error Channel n with high
level, the output circuit of the module is closed
0 Fault evaluation, error messages are sup-
pressed
2 Only plant-specific allowed, inverse operation,
i.e. the output circuit should be open.
>2 Range of values exceeded: The channel is con-
sidered as faulty (output is TRUE) and a chan-
nel-related error is output.
Usually the de-energized to trip principle applies for
safety-related control circuits.
Max. Time Inrush Current in Definition of the waiting for detecting open-circuits or the
ms, Mod. tolerance time for current limiting. No faults are displayed
Max. Time Inrush Current in during this time period. Increasing the waiting time causes
ms, red. Mod. also the cycle time to rise.
2.7.2 Outputs
The Pulse on Error (2x), Error, Error Mod. and Error Code red. Mod. outputs serve informative
purposes only, and no safety-related actions may be derived for the user program.
The remaining outputs may be used for safety-related actions.
2.8.1 Inputs:
Bus No. Rack Pos. (e.g., Position of the safety-related digital output module and, if existing,
1305) of the redundant module as four-digit decimal number
Bus No. Rack Pos. red. Example: 1305 means:
Mod. Cabinet 1, subrack 3, module position 05
2.8.2 Outputs
The Channel Error Mask, Other Error Code, Pulse (2x), Error, Error Code Mod. and Error
Code red. Mod. outputs serve informative purposes only, and no safety-related actions may
be derived for the user program.
The outputs Output 1 through Output 8 may be used for safety-related actions.
The HF-AIX-3 function block must be used in the user program one time for each channel of
the F 6221 module.
For each channel, the analog input module has a safety-related output that is controlled
independently from the central module cycle. Its state is output to the HF-AIX-3 function block
and can be further processed in the user program.
The value of the analog input module can be converted and scaled through the parameter
setting.
A value preset on the Value on Error function block input is switched to the Value output in
the following cases:
• With channel faults
• With module faults
• With violation of the measurement range
In these cases, the user program processes the value of the Value on Error input instead of
the measured value.
The HF-CNT-3 function block must be used in the user program one time for each channel
of the F 5220 module.
For each channel, the counter module has a safety-related output that is controlled
independently from the central module cycle. Its Output State is output to the HF-CNT-3
counter function block and can be further processed in the user program.
A TRUE signal on the MOS input (MOS: maintenance override switch) can be used to directly
control the counter module output during the specified test operating time, i.e., the output
drives the signal specified on the Force Value for Test Operation input. See also the
document Maintenance Override available on the TÜV Rheinland's website:
www.tuvasi.com.
If the Gate time is modified, the correct measured value is only available on the output
i after three Gate times (as currently set).
The Enable External Comparison Temperature signal is only evaluated if the Temperature
Measurement mode is set (values 2 through 8 on the Sensor Type input). If the input is TRUE,
the temperature on the External Reference Temperature input is used as comparison value.
If this input is FALSE, the temperature value of the resistance thermometer located in the
module is processed as reference temperature.
The Value function block output is set to 0 if the module or channel fails. If faults occur, the
Channel Error function block output must thus be evaluated in the user program to ensure
that the type of fault to be defined in the user program is processed.
The reference temperature for safety-related applications compliant with SIL 3 must be taken
from two different modules, the same applies to the temperature of two thermocouples.
The TRUE signal on the MOS input (MOS = maintenance override switch) is used to freeze
the value on the Value and Channel Error function block outputs, while the time for test
operation is running. See also the document Maintenance Override available on the TÜV
Rheinland's website: www.tuvasi.com.
The function block is not safety-relevant. The function block's outputs serve informative
purposes only, and no safety-related actions may be derived for the user program.
The function block is not safety-relevant. The function block's outputs serve informative
purposes only, and no safety-related actions may be derived for the user program.
All safety-related I/O modules listed on the HZ-DOS-3 function block must not be used for
safety functions!
2.15.1 Inputs
Bus No. Rack Pos. (e.g., 1306) The positions of the safety-related I/O modules are specified
as four-digit decimal numbers.
Example: 1306 means:
Cabinet 1, subrack 3, module position 06
2.15.2 Outputs
All function block's outputs serve informative purposes only, and no safety-related actions
may be derived for the user program.
Index of Figures
Figure 1: Principle of the output module circuit with integrated safety shutdown
(here with 4 output channels) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 2: Flow Diagram, Function of the Safety Tool . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 3: Redundant I/O modules used for increasing availability . . . . . . . . . . . . 58
Figure 4: Example of a 1oo2 function block and function block logic . . . . . . . . . 59
Figure 5: Use of the HB-RTE-3 function block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Figure 6: Wiring of redundant sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Figure 7: Use of the HA-RTE-3 function block with the F 6213 or F 6214 module 60
Figure 8: Comparator element for alarming or shutting down upon achievement of
the allowed threshold. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Figure 9: 2oo3 function block and function block logic . . . . . . . . . . . . . . . . . . . . . 61
Figure 10: Digital fire alarm connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Figure 11: Wiring of fire alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Figure 12: H8-STA-3 function block's connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Figure 13: HA-LIN-3 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Figure 14: HA-PID-3 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Figure 15: HA-PMU-3 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Figure 16: HA-RTE-3 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Figure 17: HB-BLD-3 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Figure 18: HB-BLD-4 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Figure 19: HB-RTE function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Figure 20: HF-AIX-3 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Figure 21: HF-CNT-3 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 22: HF-CNT-4 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Figure 23: HF-TMP-3 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Figure 24: HK-LGP-3 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Figure 25: HZ-DOS-3 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Figure 26: HZ-FAN-3 function block's connectors . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Index of Tables
Name:
Dept.
HIMA Paul Hildebrandt GmbH + Co KG Address:
Industrial Automation
Documentation
P.O. Box 1261
Telephone:
68777 Brühl, Germany Fax:
Date
Dear readers,
our manuals have been written with great care and quality measures have been implemented to
maintain them up to date and avoid mistakes. However, we cannot fully preclude flaws in this manual.
We appreciate any information concerning possible errors and any suggestions or recommendations
for improvement.
To this end, make a copy of the affected page and send or fax it to us.
(Fax: 06202 709 199)