Data Sheet 6ES7214-1AG40-0XB0: General Information
Data Sheet 6ES7214-1AG40-0XB0: General Information
Data Sheet 6ES7214-1AG40-0XB0: General Information
General information
Product type designation CPU 1214C DC/DC/DC
Firmware version V4.4
Engineering with
● Programming package STEP 7 V16 or higher
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
Current consumption (rated value) 500 mA; CPU only
Current consumption, max. 1 500 mA; CPU with all expansion modules
Output current
for backplane bus (5 V DC), max. 1 600 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V L+ minus 4 V DC min.
Power loss
Power loss, typ. 12 W
Memory
Work memory
● integrated 100 kbyte
● expandable No
Load memory
● integrated 4 Mbyte
● Plug-in (SIMATIC Memory Card), max. with SIMATIC memory card
Backup
● present Yes
● maintenance-free Yes
● without battery Yes
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of
addressable blocks ranges from 1 to 65535. There is no
restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code
Address area
Process image
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
● Hardware clock (real-time) Yes
● Backup time 480 h; Typical
● Deviation per day, max. ±60 s/month at 25 °C
Digital inputs
Number of digital inputs 14; Integrated
● of which inputs usable for technological 6; HSC (High Speed Counting)
functions
Source/sink input Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 14
Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 V DC at 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms,
selectable in groups of four
— at "0" to "1", min. 0.2 ms
— at "0" to "1", max. 12.8 ms
for interrupt inputs
— parameterizable Yes
for technological functions
— parameterizable Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80
kHz & 3 @ 30 kHz
Cable length
● shielded, max. 500 m; 50 m for technological functions
● unshielded, max. 300 m; for technological functions: No
Digital outputs
Number of digital outputs 10
● of which high-speed outputs 4; 100 kHz Pulse Train Output
Limitation of inductive shutdown voltage to L+ (-48 V)
Switching capacity of the outputs
● with resistive load, max. 0.5 A
Analog inputs
Number of analog inputs 2
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
— Input resistance (0 to 10 V) ≥100k ohms
Cable length
● shielded, max. 100 m; twisted and shielded
Analog outputs
Number of analog outputs 0
Encoder
Connectable encoders
● 2-wire sensor Yes
1. Interface
Interface type PROFINET
Isolated Yes
Protocols
Supports protocol for PROFINET IO Yes
PROFIBUS Yes; CM 1243-5 (master) or CM 1242-5 (slave) required
AS-Interface Yes; CM 1243-2 required
Protocols (Ethernet)
● TCP/IP Yes
● DHCP No
● SNMP Yes
● DCP Yes
● LLDP Yes
Open IE communication
● TCP/IP Yes
— Data length, max. 8 kbyte
● ISO-on-TCP (RFC1006) Yes
— Data length, max. 8 kbyte
● UDP Yes
— Data length, max. 1 472 byte
Web server
● supported Yes
● User-defined websites Yes
OPC UA
● Runtime license required Yes; "Basic" license required
● OPC UA Server Yes; Data access (read, write, subscribe), runtime license
required
— Application authentication Available security policies: None, Basic128Rsa15,
Basic256Rsa15, Basic256Sha256
— User authentication "anonymous" or by user name & password
— Number of sessions, max. 5
— Number of accessible variables, max. 1 000
— Number of subscriptions per session, max. 5
— Sampling interval, min. 100 ms
— Publishing interval, min. 200 ms
— Number of monitored items, max. 500
— Number of server interfaces, max. 2
Communication functions
S7 communication
● supported Yes
● as server Yes
● as client Yes
● User data per job, max. See online help (S7 communication, user data size)
Number of connections
● overall 8 connections for open user communication (active or passive):
TSEND_C, TRCV_C, TCON, TDISCON, TSEND and TRCV, 8
CPU/CPU connections (Client or Server) for GET/PUT data, 6
connections for dynamic assignment to GET/PUT or open user
communication
Interrupts/diagnostics/status information
Diagnostics indication LED
● RUN/STOP LED Yes
● ERROR LED Yes
● MAINT LED Yes
Integrated Functions
Number of counters 6
Counting frequency (counter) max. 100 kHz
Frequency measurement Yes
controlled positioning Yes
Number of position-controlled positioning axes, max. 8
Number of positioning axes via pulse-direction 4; With integrated outputs
interface
PID controller Yes
Potential separation
Potential separation digital inputs
● Potential separation digital inputs No
● between the channels, in groups of 1
Potential separation digital outputs
● Potential separation digital outputs Yes
● between the channels No
● between the channels, in groups of 1
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of Yes
static electricity acc. to IEC 61000-4-2
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to Yes
IEC 61000-4-4
● Interference immunity on signal cables acc. to Yes
IEC 61000-4-4
Interference immunity against voltage surge
● Interference immunity on supply lines acc. to Yes
IEC 61000-4-5
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high-frequency Yes
radiation acc. to IEC 61000-4-6
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes; Group 1
● Limit class B, for use in residential areas Yes; When appropriate measures are used to ensure compliance
with the limits for Class B according to EN 55011
Configuration
Programming
Programming language
— LAD Yes
— FBD Yes
— SCL Yes
Know-how protection
● User program protection/password protection Yes
Dimensions
Width 110 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 415 g