KH105 Multi Channel Process Indicator Manual: Xiamen Kehao Automation Co., LTD
KH105 Multi Channel Process Indicator Manual: Xiamen Kehao Automation Co., LTD
KH105 Multi Channel Process Indicator Manual: Xiamen Kehao Automation Co., LTD
COM/EN
Version 1.0
1
WWW.KEHAOAUTO.COM/EN
1. Feature--------------------------------------------------------------------------------------------------------------------------- ------3
2. Specification--------------------------------------------------------------------------------------------------------------------- ------4
3. Order Code-------------------------------------------------------------------------------------------------------------- --------------5
4. Installation &Connection
4.1. Installation Condition ------------------------------------------------------------------------------------------------------------- -7
4.2. Installation Dimension -------------------------------------------------------------------------------------------------------------7
4.3. Connection ------------------------------------------------------------------------------------------------------- -------------------8
5. Front Panel &Operation
5.1 Front Panel--------------------------------------------------------------------------------------------------------------------------10
5.2. Operation---------------------------------------------------------------------------------------------------------------------------11
6. Parameter List----------------------------------------------------------------------------------------------------------------------12
6.1. Channel Parameters---------------------------------------------------------------------------------------------------------------13
6.2. Public Parameters-----------------------------------------------------------------------------------------------------------------15
7. Print Function-----------------------------------------------------------------------------------------------------------------------16
8. Retransmission Output -----------------------------------------------------------------------------------------------------------16
9. Alarm Output------------------------------------------------------------------------------------------------------------------------17
10. Communication--------------------------------------------------------------------------------------------------------------------17
Unit Table---------------------------------------------------------------------------------------------------------------------------17
2
WWW.KEHAOAUTO.COM/EN
NOTICE
Thanks for your purchasing Kehao instruments. Please read the manual carefully before using the instruments.
Please check whether your meter is ok after opening the package. Please contact us if any damage or broken.
Please check whether the goods and parts are same as packing list offered. Please contact us if any difference.
Please use dry cloth to clean your instruments. Please should not use alcohol, gasoline or other solvents to clean
instruments in order to avoid to the water splashed the instruments. If any water to instrument, please stop
instruments working immediately. Otherwise, there maybe leakage, electric shock or fire hazard caused.
Please shall know the connections and operations of your meter first before testing and installing the meter.
Please use your instruments in its required conditions. Please do not disassemble the instruments arbitrarily in order
to avoid danger. Please contact us and disassemble the instruments under our technical approval and guide if any
error in instruments.
Please calibrate your instruments one time every year. If the instrument error is beyond its range, usually caused by
moisture, dust and corrosive gas, please clean and dry the inner part of your instruments. Please contact us if any
problem still cannot be solved.
Please maintain your instruments in a period in order to keep your instruments and part lifespan.
Kehao instruments are being improved in quality and function. If there is any difference between the ordered
instruments and manual, please make the ordered instruments as final standard or contact our technicals
Copyright 2012, owned by Xiamen Kehao Automation Co., Ltd.
KH105’s display is 7 segments LED, so there are some differences in some characters display contrast to the one
you usually know. Please see the table as follows:
LED Means LED Means LED Means LED Means
0 8 G o
1 9 H P
2 A i q
3 b J r
4 C K S
5 d L t
6 E M u
7 F n y
1. Features
◆ High accuracy: +-(0.2%FS+1)
◆ Automatic and manual regular inspection and indicating can be shift flexibly.
◆ Programmable universal analog input signals: T.C. RTD, mA DC, mV DC. Suitable for measuring and displaying
temperature, pressure, humidity, flow level, vibration etc.
◆ Dual windows, four digit, 7 segment LED display, easy to set parameter and alarm value.
◆ SMT technology, design more concise; adopts advanced modular structure, flexible configuration.
◆ Universal 85-240VAC or 24VDC power supply option, with thunderbolt proof and 10second protection from
connecting to 380VAC by mistake.
◆ Automatically channel scanning with interval time and manual channel selection..
3
WWW.KEHAOAUTO.COM/EN
◆ Supporting digit filtering, digital offsetting and thermocouple cold junction auto compensation, flexible
maintenance and easy operation.
◆ Supporting up to 8 relay alarm outputs, each alarm can be configured up to HA, HHA, LA,LLA for limits alarms.
◆ Supporting auxiliary power supply; 5VDC, 12VDC, 24VDC for external sensor and transmitters.
◆ Supporting current retransmission output for signal further transmission.
◆ Supporting RS485, RS232 communication based on standard MODBUS-RTU protocol, configurable with SCADA,
OPC servers etc for remote place communication.
2. Specification
● Input Signal
Thermocouple: K, S, E, J, T, B, N,R
RTD: Cu50, Pt100
Linear voltage: 0-5VDC, 1-5VDC, 0-10VDC
Linear current: 0-10mA, 4-20mA (should connect external precision resistor, 500Ω for 0-10mA or 250Ω for 4-20mA)
Extended signal: one input signal can be customized (Please advise the signal index no. when non-linear input)
●Measure range:
Thermocouple: K ( 0~ 1300℃ ), S ( 0 ~ 1700℃ ), T ( 0 ~ 350℃ ) , E ( 0 ~ 800℃ ), J ( 0 ~ 1000℃ ),
B ( 300 ~ 1800℃ ), N ( 0 ~ 1300℃ )
RTD: Cu50 ( -50 ~ 150℃ ) , Pt100 ( -200 ~ 600℃ )
Linear input:-999 to +9999 defined by user.
●Measure accuracy:
0.2 grade when RTD, linear voltage, linear current, T.C input with free points cold junction compensation or copper
resistance compensation)
0.2%FS±2.0℃ when T.C input with temperature compensation on cold-junction inside the meter
● Respond time:
≤0.5s when the filtering parameter FiL=0
● Output Specification:
Relay alarm outputs: 220VAC/2A, 220VAC/2A
Auxiliary power supply: 5VDC, 12VDC, 24VDC
Linear current retransmission output: 4-20mA default or 0-10mA or customized
Communication output: RS485, RS232 serial interface
Printing output: RS232 serial interface.
● Alarm Function
Each channel alarm can be configurable flexibly as high limit, higher limit, low limit, lower limit, up to 4 alarm output
● Power Supply:
85-240VAC, -15%, +10%/50-60HZ; 24VDC,-15%,+10%.
●Power Consumption: ≤5W
● Ambient Temperature:0-50 deg C
●Ambient Humidity: <85%RH
● Front Panel Dimension
96x96mm, 160x80mm, 72x72mm
●Panel Cutout Dimension
92+0.5x 92+0.5mm, 152+0.5 x76+0.5mm,68+0.5 x 68+0.5mm
●Depth Mounting Surface: ≤100mm.
4
WWW.KEHAOAUTO.COM/EN
3. Order Code
KH105-F Order Code (72x72x105mm)
5
WWW.KEHAOAUTO.COM/EN
KH105-DOrder Code (160X80X105mm)
6
WWW.KEHAOAUTO.COM/EN
4、Installation and Connection
4.1、Installation Condition
4.2、Installation Dimension(mm)
●Size: F:72X72x105mm
●Size: D: 160x80x105mm
7
WWW.KEHAOAUTO.COM/EN
4.3 Connection
8
WWW.KEHAOAUTO.COM/EN
Size D: 160X80X105mm (CH17-CH48)
Note:
When analog linear input listed, please connect a external 250hohm resistor in terminal: T, G when 4-20mA input,;
a external 500ohm resistor connected when 0-10mA input.
Pin “+, - “: code:U1,U2, U3 auxiliary 5VDC,12DC, 24VDC power supply output terminal
Pin “A, B”: code S1, RS485 communication output terminal
Pin “TXD,RXD,COM/GND”: code S2, P, RS232 communication or printing output terminal
Pin “NO,. NC, COM” : R1A,R1B,R2A,R2B,R2C, relay alarm output terminal
●Connection with sensors and transmitter
●Diagram for connnection bulit in aux. 5VDC, 12VDC, 24VDC with sensors and trnasmitter
9
WWW.KEHAOAUTO.COM/EN
5、Front Panel and Operation
5.1、Front Panel
10
WWW.KEHAOAUTO.COM/EN
5.2. Operation
5.2.1. Normal Display Statues
Print current PV
value via RS232
printing port
11
WWW.KEHAOAUTO.COM/EN
upper window (PV) and lower window (SV), press or to modify the value or code of parameter in SV or go to
next or preceding parameter in PV, press key to move the flashing point in SV to digit expected to modify.
4) After finish required parameter configuration, then press key and hold and do not release, then can access
“Public parameter” table for parameter configuration. Then press key and hold and do not release again, can exit
from the parameter
5.2.3.2 Character Parameter Setting
E.g. Please set parameter “ CS01” as “CLoS” from “oPEn” ,then set it as “ oPEn” again:
Enter into parameter configuration Move cursor to required position Modify the value
Confirm
12
WWW.KEHAOAUTO.COM/EN
6.Parameters List
6.1 Channel Parameters
13
WWW.KEHAOAUTO.COM/EN
value can be increased gradually thus to make momentary
fluctuation of the measuring value less than 2-5 digits.
Please set “Fil” as 0 to shorten the response speed when
the instrument is metrological verified.
1AXX 9 Alarm 1 -999 to 9999 A1 alarm setting value
2AXX 10 Alarm 2 -999 to 9999 A2 alarm setting value
3AXX 11 Alarm 3 -999 to 9999 A3 alarm setting value
4AXX 12 Alarm 4 -999 to 9999 A4 alarm setting value
“Hy” is the buffer of alarm output, used for avoiding
frequent alarm on-off action because of the fluctuation of
HyXX 13 Hysteresis 0 -2000
the measuring value. When thermocouple and RTD input,
decimal point----. Fixed.
Alarm mode, can be configurable flexibly.
LA: Low limit alarm: alarm on when PV<LA, alarm off
1MXX 14 A1 alarm mode
when PV >LA+Hy. When this alarm output is as public
alarm with others, their public alarm principle is “or”.
E.g.:A1=30,A2=40,A1-M=LA, A2-M=LA, A1-O=OUT1,
A2-O=OUT1, so when PV =35 or 25, OUT1 alarm.
2MXX 15 A2 alarm mode -LA: Low limit alarm: alarm on when PV<LA, alarm off
when PV >LA+ Hy. When this alarm output is as public
alarm with others, their public alarm principle is “and”
LA, -LA, HA, -HA
E.g.:A1=30,A2=40,A1-M=-LA,A2-M=LA,A1-O=OUT1,
A2-O=OUT1, so when PV =35, OUT1 not alarm, just
3MXX 16 A3 alarm mode
when PV<30, OUT1 alarm.
HA: High limit alarm: alarm on when PV >LA, alarm
off when PV <LA +Hy. When this alarm output is as
public alarm with others, their public alarm mode is “or”.
4MXX 17 A4 alarm mode -HA: High limit alarm: alarm on when PV >LA, alarm
off when PV <LA +Hy. When this alarm output is as
public alarm with others, their public alarm mode is “and”
1OXX 18 A1 alarm output nuLL
A1, A2, A3, A4 Alarm output position.
2OXX 19 A2 alarm output OUT1, OUT2,
Null: None output
3OXX 20 A3 alarm output OUT3, OUT4,
When there is open circuit when thermocouple or RTD
OUT5, OUT6,
4OXX 21 A4 alarm output input, all output is invalid.
OU7, OUT8
0: ℃1: ℉ please see the unit table below for other units,
unXX 22 Engineer unit 0-53 which will be printed in stick when ex-work for your
sticking unit required to front panel.
Used for modify the measured value slope. Modified
KXX 23 Slop coefficient -0.999-2.000 measured value=non-modified measured value x “K”
value.
Used to cut out the invalid small signal. When the
C1XX 24 Small signal cut -999 to 9999
measured value is lower than “Cut” setting value, PV
14
WWW.KEHAOAUTO.COM/EN
display the setting value of parameter “C-to”. When
“Cut”=0, means none.
Means PV display value when the measured value is
lower than “Cut” setting value. For example, the
C2XX 25 Cut replace -999 to 9999
measured value is 0.3, when “Cut”=0.5, “C-to”=0, so PV
display value=0.
E1 Operator Para. 1 Parameters of field parameter table for operator
nuLL、 CS、Sn、
modification, which can be set by engineer flexibly
E2 Operator Para. 2 CC、Pn、iL、iH、
among table parameter table.
E3 Operator Para. 3 Au、Fi、1A、2A、
Eg, If setting E1=tyPE, E2=AdJu, E3/E4/E5=LocK, so
E4 Operator Para. 4 3A、4A、Hy、1M、
filed parameters for operator modification is only three
2M、3M、4M、1O、
parameter “type”, “AdJu”, “LocK” .If operator needing
E5 Operator Para. 5 2O、3O、4O、unxx、
more parameter modified, will ask engineer to set more
Kxx、C1xx、C2xx
for them.
15
WWW.KEHAOAUTO.COM/EN
6: Input error and alarm output is not valid , the
measured value is maximum (32751)
4: Input error and alarm output is not valid, the
measured value keeps same.
5: Input error and alarm output is not valid, the
measuring value is minimum(-20000)
Setting channel no. required with 4-20mA
trCH Retransmission output 1-16 retransmission output.. Eg.: Tran.CH=2, CH2 is with
4-20mA retransmission output.
Used when communication.
Null: None
CHEC Even and odd check Null, EvEn, odd
EvEn: Even check/parity when communication
Odd: :Odd check parity when communication
yEAr Year 00-99
Mon Month 1-12
dAtE Date 1-31 System real time date setting, please calibrate it when
Hour Hour 0-23 first using.
Min Minute 0-59
SEC Second 0-59
7、Print Function
There are two printing type: automatic fixed printing and manual printing. Please see attached details:
Fixed time printing: please set parameter “Pr-t” ≠0 required, thus, the mini printer will print the data every setting
value of “Pr-t”
Manual Printing: When the meter is working normally and power on, please press "MOVE" key, then the mini
printer print all data in current real time immediately.
Note:
The connection between meter and mini printer adopts RS232 interface. Thus, the printing and communication
function can not be working in a meter at the same time, just can be used by turn.
Please ensure the baudrate between meter and mini printer keep same, default is 9600b/s.
8、Retransmission output
The retransmission functions is according to PV(measured value) and ‘ tyPE’, ‘trAn’, ‘tr-H’,’ tr-L’ and “Poin” to
transmit the linear current ,used for transmission in long distance or as the external setting of the other control devices.
The retransmission current output value can be calculated by the below format;
16
WWW.KEHAOAUTO.COM/EN
9、Alarm output
The diagram of the alarm output as follows:
Low and Lower alarm limit diagram High and higher alarm limit diagram
Alarm off Low Limit alarm Alarm off High Limit alarm
PV PV
LA+Hy HHA
LA HHA-Hy
LLA+Hy HA
LLA HA-Hy
10、Communication
KH105 have serial communication function, which can communicate with computer through RS232 or RS485 interface
(should connecting RS485/RS232 converter with PC when RS485 interface), read and write to the instrument to achieve
DCS control. Standard MODBUS communication protocol is available, with strong universality, good compatibility and
high communication stability etc. There is up to 255 meters in a field bus when RS485 communication, which needing
repeater working together. The user can program its software for its system based on MODBUS-RTU free offered, also
purchase KH-DCS software from KEHAO.
Enclose 1
0 ℃ 10 m3/s 20 g 30 PH 40 KWh 50 m/s
1 F 11 Kg/h 21 kg 31 % 41 ppm 51 m/min
2 t/h 12 Kg/min 22 t 32 Hz 42 mg/m3 52 m/h
3 t/min 13 Kg/s 23 Pa 33 KHz 43 lel 53 None
4 t/s 14 mV 24 KPa 34 MHz 44 mm/s
5 L/h 15 V 25 MPa 35 r/s 45 mm/min
6 L/min 16 KV 26 mm 36 r/min 46 mm/h
7 L/s 17 mA 27 cm 37 r/h 47 cm/s
8 m3/h 18 A 28 m 38 W 48 cm/min
9 m3/min 19 KA 29 Km 39 KW 49 cm/h
17