Cuttler-Hammer Digitrip 1150
Cuttler-Hammer Digitrip 1150
Cuttler-Hammer Digitrip 1150
DO NOT ATTEMPT TO INSTALL OR PERFORM Available Trip current of Maintenance Mode Settings:
MAINTENANCE ON EQUIPMENT WHILE IT IS
ENERGIZED. DEATH OR SEVERE PERSONAL INJURY 2.5 x Rating Plug Amperes
CAN RESULT FROM CONTACT WITH ENERGIZED
EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS 4.0 x Rating Plug Amperes
PRESENT BEFORE PROCEEDING. ALWAYS FOLLOW
SAFETY PROCEDURES. 6.0 x Rating Plug Amperes
EATON IS NOT LIABLE FOR THE MISAPPLICATION OR 8.0 x Rating Plug Amperes
MISINSTALLATION OF ITS PRODUCTS.
10.0 x Rating Plug Amperes
1.0 General
3.0 Arming Maintenance Mode
Per the above WARNING, it is highly recommended that
maintenance be conducted on electrical equipment
including circuit breakers with the system de-energized. There are three ways to arm the Maintenance Mode Arc
Flash Reduction setting. One method is via the local
keypad located on the trip unit. The setting is located in
For situations that arise where this is not possible, the
Maintenance Mode function of the Digitrip 1150ARM family the “SYSTEM” submenu of programmable settings (PGM
(cat. 11ARMLSI, 11ARMLSIG, 11ARMLSIA) can reduce SET). When the Mainternance Mode Arc Flash reduction
Arc Flash incident energy that is generated on a fault setting is enabled, the message “Maintenance Mode
condition. This is accomplished by an analog trip circuit Enabled” is displayed to confirm that the function is on. If
which, when armed, provides a fast acting response to the any key is pressed, the Maintenance Mode message is
fault. The reduced arc condition will occur only in devices removed and replaced by normal display messages. If no
downstream of the trip unit in Maintenance Mode.This is keys are pressed, the Maintenance Mode message will
separate from the normal system protection setting of reappear after 10 seconds.
Instantaneous. The Maintenance Mode is located in the
“SYSTEM” submenu of the programmable settings menu For the second method, a remote switch wired through the
(PGM SET). (See Appendix for screen details.)
breaker secondary contacts can remotely arm the
Maintenace Mode setting. A high quality, gold plated or
palladium contact is required in this application.The
CAUTION Maintenance Mode Enabled message will verify that the
function is armed. (See wiring diagram on adjacent page.)
OBSERVE ALL RECOMMENDATIONS, NOTES, CAU- A third method to arm the maintenance setting is via a
TIONS, AND WARNINGS RELATING TO THE SAFETY communication device. A Palm Pilot along with an IR Mint
OF PERSONNEL AND EQUIPMENT. OBSERVE AND
device can be employed to arm the setting. By initiating
COMPLY WITH ALL GENERAL AND LOCAL HEALTH
AND SAFETY LAWS, CODES, AND PROCEDURES. the ENABLE setting, the Maintenance Mode selection in
the control screen of the Palm, Maintenance Mode is set.
There is a confirmation screen that verifies the arming. A
BIM (Breaker Interface Module) is another communcation
method to arm the setting. When Maintenance Setting is
A FLASH HAZARD ANALYSIS SHOULD BE DONE TO
DETERMINE PERSONAL PROTECTIVE EQUIPMENT enabled via device communications, this setting must be
REQUIREMENTS. disabled by device communications.
Circuit breakers built after July 2006 will be wired with experienced in power system analysis.
secondary contacts A12 which is reassigned to
Maintenance Mode Enable. (MM_E) - (See label on This setting choice normally does not change unless there
secondary contacts) A normally open contact (A10, A11) is are future system modifications that could increase or
available for customer use via programming of RelayA. This decrease fault levels at the circuit breaker location.
contact can be used to indicate remotely that the
Maintenance setting is armed. Refer to diagram on page For time/current curve information, refer to drawing
three for a wiring of this remote (blue light) indicator. # 70C1498.
The Arc Flash Maintenance Switch has five unique The Maintenance Mode function will provide fast tripping
settings. From the factory, the Magnum circuit breaker is even when the regular Instantaneous is set to OFF. The
shipped with the Digitrip unit set to the 2.5x setting and Instantaneous LED position is also used to indicate a trip
with its Maintenance Mode disabled. The “Maintenance initiated by the Maintenance Mode setting. The message
Mode Enabled” message provides an indication that the “Maintenance Mode Trip” will be displayed after a trip.
Maintenance Mode setting is armed per one of the three
methods described in section 3.0. The Maintenance setting, external wiring (if any) and
tripping functionality should all be periodically verified by
In general, the selection of one of the Reduction Settings primary or secondary injection current testing.
should be determined and selected by a person who is
EATON CORPORATION Cutler-Hammer InformationSheets 70C1486H01 3
A11
NOTES:
The Digitrip 1150 (Cat #11ARMxxx) can locally be placed in Maintenance Mode via front panel programming
of the Trip Unit. The function can also be armed via a remote switch as shown. In addition, the function can
be activated via communications. The display will indicate “Maintenance Mode In Use” when in this special
mode.
The recommended selector switch for this low voltage application is Cutler Hammer part number
# 10250T1333-2E which includes a contact block rated for Logic Level and Corrosive Use.
The maximum length of this wiring to the remote ARM switch (or alternate relay contact) is three meters
(9.78 feet). Use #20 AWG wire or larger.
Control voltage is 120 VAC or 230 VAC or 24-48 VDC or 125 VDC as ordered. Check Magnum circuit breaker
front cover for Trip Unit Power requirements.
A remote Stack Light, Annunciator Panel or other remote indication device can be connected to remotely verify
that the Digitrip is in Maintenance Mode.
RelayA contact changes state when Digitrip is in Maintenance Mode. This action requires pre-assigning RelayA
to Maintenance Mode function. RelayC contacts (A9, A10) are also available to be programmed to provide an
indication of a trip in Maintenance Mode. Contact is rated 1A @ 120 VAC or 0.5A @ 230 VAC or 1A @ 24-48
VDC or 0.35A @ 125 VDC.
The Digitrip 1150 can also be placed remotely in its Maintenance Mode via a General Purpose Relay
(ice cube type with Logic Level contacts) activated by a remote control switch. A recommended type is
IDEC Relay Ry22. Choose voltage as desired.
SLIDING OFF,
DISPLAY DEMAND max kW,
INCOM max kVA
AUXRLY
INCOM
001-FFE
ADDRESS in hex
INCOM WAVEFORM
Program Auxiliary ENABLED
AUXRLY Relays
CAPTURE DISABLED
ALARMS
INCOM
AUXRLY 9600
Program BAUD 1200
ALARMS RevPower
Alarms ENABLED
ACCBUS SENSING DISABLED
RELAY
Only
ADDR 01
XXXXXXXX
XXXXXXXX OFF
AUX
VIEW
RLY FUNC BELL
1 DEAD
2 XXXX ALARM
ADDR 02 WATCH
XXXXXXXX LDT
XXXXXXXX SDT
RLY FUNC
INST
SEL 2 GndT
3 XXXX GFAlm
HLAlm
MAINT
ADDR 03 RLY FUNC
XXXXXXXX 3
XXXXXXXX 4 XXXX
RLY FUNC
ADDR 04 4
XXXXXXXX 1 XXXX
XXXXXXXX
NOTE: The "MAINT" Relay Function will act as an indicator that the
"Maintenance Mode" is enabled and in use.
SLIDING OFF,
DISPLAY DEMAND max kW,
INCOM max kVA
AUXRLY
INCOM
001-FFE
ADDRESS in hex
INCOM WAVEFORM
Program ENABLED
AUXRLY Auxiliary Relays
CAPTURE DISABLED
ALARMS
INCOM
AUXRLY 9600
Program BAUD 1200
ALARMS RevPower
Alarms ENABLED
ACCBUS SENSING DISABLED
TIME Program
VOLTAGE VOLTAGE,FREQ NOTE: Throughout Program Settings
CURRENT Settings sub-menus with blocks ( ) represent
DT 910 variable information that can be directly
ENABLED changed with the EDIT buttons, while
NOTE: Screen shown for
COMM
DISABLED X's represent variable information that
Digitrip 1150 - Cat. # 1 1ARMxxxx. is viewable.
Cutler-Hammer is a federally
registered trademark of Eaton
Corporation. Digitrip is a trade-
mark of Eaton Corporation.