Digitrip 1150 with Effective July 2006

Maintenance Mode I.S. 70C1486


Supplement to I.L. 70C1036

FIGURE 1. Digitrip with ARMs in Magnum Circuit Breaker

Table of Contents Diagrams and Appendix

1.0 General ................................................................... 2 Wiring Diagram ............................................................... 4


2.0 Maintenance Mode Settings .................................... 2 Display Matrix for Program Settings Menu ...................... 5
3.0 Arming Maintenance Mode ...................................... 2 Display Matrix for Program Aux Relays Menu ................. 6
4.0 Remote Indicator ..................................................... 3 Display Matrix for Program Accessory Bus ..................... 7
5.0 Choosing the Reduction Setting .............................. 3 Display Matrix for Possible Events TRIP .......................... 8
6.0 Tripping and Testing ................................................ 3 Display Matrix for View Settings Menu ............................ 9
Manufacturer’s Statement ............................................. 10
EATON CORPORATION Cutler-Hammer InformationSheets 70C1486H01 1
2.0 Maintenance Mode Settings
WARNING
The Maintenance Mode Settings provide the Arc Flash
ONLY CERTIFIED AND COMPETENT PERSONNEL Reduction setting. 2.5 x Rating Plug Value is the Maxi-
SHOULD ATTEMPT TO INSTALL OR MAINTAIN mum reduction setting which correlates to the lowest
POTENTIALLY HAZARDOUS EQUIPMENT. pickup value.

DO NOT ATTEMPT TO INSTALL OR PERFORM Available Trip current of Maintenance Mode Settings:
MAINTENANCE ON EQUIPMENT WHILE IT IS
ENERGIZED. DEATH OR SEVERE PERSONAL INJURY 2.5 x Rating Plug Amperes
CAN RESULT FROM CONTACT WITH ENERGIZED
EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS 4.0 x Rating Plug Amperes
PRESENT BEFORE PROCEEDING. ALWAYS FOLLOW
SAFETY PROCEDURES. 6.0 x Rating Plug Amperes

EATON IS NOT LIABLE FOR THE MISAPPLICATION OR 8.0 x Rating Plug Amperes
MISINSTALLATION OF ITS PRODUCTS.
10.0 x Rating Plug Amperes

1.0 General
3.0 Arming Maintenance Mode
Per the above WARNING, it is highly recommended that
maintenance be conducted on electrical equipment
including circuit breakers with the system de-energized. There are three ways to arm the Maintenance Mode Arc
Flash Reduction setting. One method is via the local
keypad located on the trip unit. The setting is located in
For situations that arise where this is not possible, the
Maintenance Mode function of the Digitrip 1150ARM family the “SYSTEM” submenu of programmable settings (PGM
(cat. 11ARMLSI, 11ARMLSIG, 11ARMLSIA) can reduce SET). When the Mainternance Mode Arc Flash reduction
Arc Flash incident energy that is generated on a fault setting is enabled, the message “Maintenance Mode
condition. This is accomplished by an analog trip circuit Enabled” is displayed to confirm that the function is on. If
which, when armed, provides a fast acting response to the any key is pressed, the Maintenance Mode message is
fault. The reduced arc condition will occur only in devices removed and replaced by normal display messages. If no
downstream of the trip unit in Maintenance Mode.This is keys are pressed, the Maintenance Mode message will
separate from the normal system protection setting of reappear after 10 seconds.
Instantaneous. The Maintenance Mode is located in the
“SYSTEM” submenu of the programmable settings menu For the second method, a remote switch wired through the
(PGM SET). (See Appendix for screen details.)
breaker secondary contacts can remotely arm the
Maintenace Mode setting. A high quality, gold plated or
palladium contact is required in this application.The
CAUTION Maintenance Mode Enabled message will verify that the
function is armed. (See wiring diagram on adjacent page.)

OBSERVE ALL RECOMMENDATIONS, NOTES, CAU- A third method to arm the maintenance setting is via a
TIONS, AND WARNINGS RELATING TO THE SAFETY communication device. A Palm Pilot along with an IR Mint
OF PERSONNEL AND EQUIPMENT. OBSERVE AND
device can be employed to arm the setting. By initiating
COMPLY WITH ALL GENERAL AND LOCAL HEALTH
AND SAFETY LAWS, CODES, AND PROCEDURES. the ENABLE setting, the Maintenance Mode selection in
the control screen of the Palm, Maintenance Mode is set.
There is a confirmation screen that verifies the arming. A
BIM (Breaker Interface Module) is another communcation
method to arm the setting. When Maintenance Setting is
A FLASH HAZARD ANALYSIS SHOULD BE DONE TO
DETERMINE PERSONAL PROTECTIVE EQUIPMENT enabled via device communications, this setting must be
REQUIREMENTS. disabled by device communications.

2 EATON CORPORATION Cutler-Hammer Information Sheets 70C1486H01


FIGURE 2. Digitrip 1150 with ARMs

4.0 Remote Indicator

Circuit breakers built after July 2006 will be wired with experienced in power system analysis.
secondary contacts A12 which is reassigned to
Maintenance Mode Enable. (MM_E) - (See label on This setting choice normally does not change unless there
secondary contacts) A normally open contact (A10, A11) is are future system modifications that could increase or
available for customer use via programming of RelayA. This decrease fault levels at the circuit breaker location.
contact can be used to indicate remotely that the
Maintenance setting is armed. Refer to diagram on page For time/current curve information, refer to drawing
three for a wiring of this remote (blue light) indicator. # 70C1498.

5.0 Choosing the Reduction Setting 6.0 Tripping and Testing

The Arc Flash Maintenance Switch has five unique The Maintenance Mode function will provide fast tripping
settings. From the factory, the Magnum circuit breaker is even when the regular Instantaneous is set to OFF. The
shipped with the Digitrip unit set to the 2.5x setting and Instantaneous LED position is also used to indicate a trip
with its Maintenance Mode disabled. The “Maintenance initiated by the Maintenance Mode setting. The message
Mode Enabled” message provides an indication that the “Maintenance Mode Trip” will be displayed after a trip.
Maintenance Mode setting is armed per one of the three
methods described in section 3.0. The Maintenance setting, external wiring (if any) and
tripping functionality should all be periodically verified by
In general, the selection of one of the Reduction Settings primary or secondary injection current testing.
should be determined and selected by a person who is
EATON CORPORATION Cutler-Hammer InformationSheets 70C1486H01 3
A11

Maintenance Mode Wiring


Digitrip 1150 with ARMs

NOTES:
The Digitrip 1150 (Cat #11ARMxxx) can locally be placed in Maintenance Mode via front panel programming
of the Trip Unit. The function can also be armed via a remote switch as shown. In addition, the function can
be activated via communications. The display will indicate “Maintenance Mode In Use” when in this special
mode.

The recommended selector switch for this low voltage application is Cutler Hammer part number
# 10250T1333-2E which includes a contact block rated for Logic Level and Corrosive Use.

The maximum length of this wiring to the remote ARM switch (or alternate relay contact) is three meters
(9.78 feet). Use #20 AWG wire or larger.

Control voltage is 120 VAC or 230 VAC or 24-48 VDC or 125 VDC as ordered. Check Magnum circuit breaker
front cover for Trip Unit Power requirements.

A remote Stack Light, Annunciator Panel or other remote indication device can be connected to remotely verify
that the Digitrip is in Maintenance Mode.

RelayA contact changes state when Digitrip is in Maintenance Mode. This action requires pre-assigning RelayA
to Maintenance Mode function. RelayC contacts (A9, A10) are also available to be programmed to provide an
indication of a trip in Maintenance Mode. Contact is rated 1A @ 120 VAC or 0.5A @ 230 VAC or 1A @ 24-48
VDC or 0.35A @ 125 VDC.

The Digitrip 1150 can also be placed remotely in its Maintenance Mode via a General Purpose Relay
(ice cube type with Logic Level contacts) activated by a remote control switch. A recommended type is
IDEC Relay Ry22. Choose voltage as desired.

4 EATON CORPORATION Cutler-Hammer Information Sheets 70C1486H01


Appendix
Program
VOLTAGE Settings
Program Current Menu
CURRENT ESC / SEL
Curve
SYSTEM
Program
2.5
CURRENT 4.0 Maint PU Mainten- FREQ BC RELAY
SYSTEM 6.0 . x In ance Mode RESET
8.0 A Hz
DISPLAY 10.0
Manual,
ENABLED 50,60
Auto
SYSTEM DISABLED
Program Display
DISPLAY Settings
INCOM

SLIDING OFF,
DISPLAY DEMAND max kW,
INCOM max kVA
AUXRLY
INCOM
001-FFE
ADDRESS in hex
INCOM WAVEFORM
Program Auxiliary ENABLED
AUXRLY Relays
CAPTURE DISABLED
ALARMS

INCOM
AUXRLY 9600
Program BAUD 1200
ALARMS RevPower
Alarms ENABLED
ACCBUS SENSING DISABLED

ALARMS EXT COMM


Program ENABLED
ACCBUS Accessory Bus OpenTrip DISABLED
TripLink
NOTE: For units built
after July 2006, this
setting replaces function
ACCBUS of secondary contact
Program EXT COMM hardware jumper.
TripLink TripLink
TIME OPEN
TRIP NOTE: TRIP uses TA device.
OPEN requires a separate
TripLink Shunt Trip wired through Aux
Program Relay C (terminals (A-9, A-
TIME Time
10)) when programmed as
EXT COMM TRIP via
VOLTAGE EXT COMM ENABLED PowerNet. Requires BC Reset
DISABLED (auto) in system.
CLOSE
TIME Program
VOLTAGE VOLTAGE,FREQ NOTE: Throughout Program Settings
CURRENT Settings sub-menus with blocks ( ) represent
DT 910 variable information that can be directly
ENABLED changed with the EDIT buttons, while
NOTE: Screen shown for
COMM X's represent variable information that
DISABLED
Digitrip 1150 - Cat. # 1 1ARMxxxx. is viewable.

EATON CORPORATION Cutler-Hammer InformationSheets 70C1486H01 5


Program Aux
" * " (asterisk) is placed beside the Relays Menu
relay letter when at least one of its
RELAY functions is ENABLED. Group 1 Group 2

RELAY C* PULSE DISABLED


RELAY
RELAY A* SEL INITIATE LDT
RELAY B*

VIEW ENABLED RELAY A


RELAY RELAY A
kW DMND
ENABLED SDT kVA DMND
RELAY A*
RELAY B* PULSE kVAh
RELAY C* kWh
RELAY RELAY A
RELAY A
INST THD ALRM
UV ALARM
Group 3
RELAY B*
RELAY C* RELAY A
RELAY RELAY RELAY A
RELAY A* PF ALARM
VolUnbal GND TRIP OV ALARM
"ENABLED"
or
"DISABLED" RELAY A
for all screens RELAY RELAY RELAY A
RevPower AmpUNBAL OP ALARM UF ALARM

Selected Relay determines Groups displayed.

Relay Groups Displayed RELAY RELAY RELAY A RELAY A


A (Alarming) 1, 2 PULSE INITIATE DISABLED OF TRIP PH LOSS HighLOAD OF ALARM
None PULSE INITIATE ENABLED
B (Blocking) 1, 3
C (Latching) 1, 3

RELAY RELAY RELAY A RELAY A


UF TRIP OverTEMP LDPU PhROTATE

RELAY RELAY RELAY A RELAY A


OV TRIP PlugTRIP NeutALRM V UNB AL

RELAY RELAY RELAY A RELAY A


"ENABLED" or MM InUse
"DISABLED" for
UV TRIP CommTRIP GND ALRM
all screens
Relay A

RELAY
Only

MM TRIP Relays B & C


Only

6 EATON CORPORATION Cutler-Hammer Information Sheets 70C1486H01


Program
Accessory Bus

"XXXXXXXX NO SETTINGS If no relay functions are enabled Each of the 4 addresses is


XXXXXXXX" DIGITAL OUTPUT If any relay functions are enabled Save
a separate Save group

ADDR 01
XXXXXXXX
XXXXXXXX OFF
AUX
VIEW
RLY FUNC BELL
1 DEAD
2 XXXX ALARM
ADDR 02 WATCH
XXXXXXXX LDT
XXXXXXXX SDT
RLY FUNC
INST
SEL 2 GndT
3 XXXX GFAlm
HLAlm
MAINT
ADDR 03 RLY FUNC
XXXXXXXX 3
XXXXXXXX 4 XXXX

RLY FUNC
ADDR 04 4
XXXXXXXX 1 XXXX
XXXXXXXX

NOTE: The "MAINT" Relay Function will act as an indicator that the
"Maintenance Mode" is enabled and in use.

EATON CORPORATION Cutler-Hammer InformationSheets 70C1486H01 7


Possible Events
TRIP

Data and Time Stamp


logged for each event. PlugTRIP
No data
RevPower Power kW screen
displayed displayed
LONG 1st & 2nd TRIP See Note 5
DELAY Meter screens
TRIP Note 1
MAKING VOLT UN- L-L Voltage and
No data
CURRENT displayed BALANCE FREQ screens
displayed.
SHORT TRIP TRIP See Note 5
1st & 2nd
DELAY Meter screens
TRIP PHASE
3rd Meter
LOSS screen
1st & 2nd
TRIP
INST Additional TRIP for Digitrips
Meter screens
TRIP Cat # 11ARMxxx only
Note 2
HIGH
No data
INST displayed Mainten-
1st & 2nd TRIP No data
Meter ance Mode displayed
NEUTRAL TRIP
screens
TRIP Note 3

GROUND 1st & 2nd


FAULT Meter screens Additional TRIPs for Digitrips
1. LONG DELAY TRIP term is
TRIP Note 4 Cat # 11Pxxx and
used by LSI, IEEE and IEC
11ARMxxx only
curve type indicating an
overload trip.
L-L Voltage and
OPEN BY No data UndrVOLT FREQ screens
displayed displayed. 2. INST TRIP values displayed
COMM TRIP See Note 5 could be less than actual fault
levels due to fast response of this
element.
L-L Voltage and
ACC BUS No data OverVOLT FREQ screens 3. NEUTRAL TRIP is a
displayed displayed.
TRIP TRIP See Note 5 Long Delay Trip on Neutral
or 4th pole

AMPERES L-L Voltage and 4. If IEC -EF style,


1st Meter UndrFREQ FREQ screens "EARTH" will replace
OUT OF screens displayed.
TRIP "GROUND"
BALANCE See Note 5

5. Real Time data is


OVER L-L Voltage and
shown for Voltage and
No data OverFREQ FREQ screens Frequency. View
TEMP displayed displayed. EventLog screen for
TRIP See Note 5
TRIP actual TRIP data.

8 EATON CORPORATION Cutler-Hammer Information Sheets 70C1486H01


View Settings
VOLTAGE Menu
Program Current
CURRENT ESC / SEL
Curve
SYSTEM
Program
2.5
CURRENT 4.0 Maint PU Mainten- FREQ BC RELAY
SYSTEM 6.0 . x In ance Mode RESET
8.0 A Hz
DISPLAY 10.0
Manual,
ENABLED 50,60
Auto
SYSTEM DISABLED
Program Display
DISPLAY Settings
INCOM

SLIDING OFF,
DISPLAY DEMAND max kW,
INCOM max kVA
AUXRLY
INCOM
001-FFE
ADDRESS in hex
INCOM WAVEFORM
Program ENABLED
AUXRLY Auxiliary Relays
CAPTURE DISABLED
ALARMS

INCOM
AUXRLY 9600
Program BAUD 1200
ALARMS RevPower
Alarms ENABLED
ACCBUS SENSING DISABLED

ALARMS EXT COMM


Program ENABLED
ACCBUS Accessory Bus OpenTrip DISABLED NOTE: For units built
TripLink after July 2006, this
setting replaces
function of secondary
contact hardware
ACCBUS jumper.
Program EXT COMM
TripLink TripLink
TIME OPEN
TRIP NOTE: TRIP uses TA device.
OPEN requires a separate Shunt
Trip wired through Aux Relay C
TripLink (terminals (A-9, A-10))
Program
TIME Time
when programmed as
EXT COMM TRIP via
VOLTAGE EXT COMM ENABLED PowerNet. Requires BC Reset
(auto) in system.
CLOSE DISABLED

TIME Program
VOLTAGE VOLTAGE,FREQ NOTE: Throughout Program Settings
CURRENT Settings sub-menus with blocks ( ) represent
DT 910 variable information that can be directly
ENABLED changed with the EDIT buttons, while
NOTE: Screen shown for
COMM
DISABLED X's represent variable information that
Digitrip 1150 - Cat. # 1 1ARMxxxx. is viewable.

EATON CORPORATION Cutler-Hammer InformationSheets 70C1486H01 9


DISCLAIMER OF WARRANTIES AND
LIMITATION OF LIABILITY

The information recommendations, descriptions and safety


notations in this document are based on Eaton’s experi-
ence and judgment and may not cover all contingencies. If
further information is required an Eaton sales office should
be consulted.

Sale of the product shown in this literature is subject to the


terms and conditions outlined in appropriate Eaton Electri-
cal Inc. selling policies or other contractual agreement be-
tween Eaton and the purchaser.

THERE ARE NO UNDERSTANDINGS, AGREEMENTS,


WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF FITNESS FOR A PARTICULAR PUR-
POSE OR MERCHANTABILITY, OTHER THAN THOSE
SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT
BETWEEN THE PARTIES. ANY SUCH CONTRACT
STATES THE ENTIRE OBLIGATION OF EATON ELECTRI-
CAL INC. THE CONTENTS OF THIS DOCUMENT SHALL
NOT BECOME PART OF OR MODIFY ANY CONTRACT
BETWEEN THE PARTIES.

IN NO EVENT WILL EATON ELECTRICAL INC. BE


RESPONSIBLE TO THE PURCHASER OR USER IN
CONTRACT, IN TORT (INCLUDING NEGLIGENCE),
STRICT LIABILITY OR OTHERWISE FOR ANY SPECIAL,
INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGE
OR LOSS WHATSOEVER, INCLUDING BUT NOT
LIMITED TO DAMAGE TO OR LOSS OF USE OF
EQUIPMENT, PLANT OR POWER SYSTEM, LOSS OF
PROFITS OR REVENUES, OR CLAIMS AGAINST THE
PURCHASER OR USER BY ITS CUSTOMERS
RESULTING FROM THE USE OF THE PRODUCTS OR
INFORMATION, RECOMMENDATIONS AND
DESCRIPTIONS CONTAINED HEREIN.

Cutler-Hammer is a federally
registered trademark of Eaton
Corporation. Digitrip is a trade-
mark of Eaton Corporation.

Eaton Electrical, Inc.


1000 Cherrington Parkway © 2006 Eaton Corporation
Moon Township, PA 15108-4312 All Rights Reserved
United States Printed in USA
Tel.: 1-800-525-2000 Publication No. I.S.70C1486H01
www.EatonElectrical.com July 2006

10 EATON CORPORATION Cutler-Hammer Information Sheets 70C1486H01