Transient Stability of Power Systems With Embedded VSC HVDC Links Stability Margins Analysis and Control Juan Carlos GONZALEZ
Transient Stability of Power Systems With Embedded VSC HVDC Links Stability Margins Analysis and Control Juan Carlos GONZALEZ
Transient Stability of Power Systems With Embedded VSC HVDC Links Stability Margins Analysis and Control Juan Carlos GONZALEZ
Abstract: This paper investigates the impact of embedded Voltage Source Converter-based High Voltage Direct Current (VSC-
HVDC) links on AC grids transient stability. Firstly, using Transient Energy Functions (TEF), it is demonstrated that VSC-HVDC
links controlled to track constant power references, do not inherently improve transient stability of the surrounding AC grid as an
AC line naturally does. Then, a control law using the feedback linearization technique on a simple but representative power system
is derived. The control law highlights and combines the three main actions the VSC-HVDC link can offer to enhance rotor angle
stability: fast power reallocation, injection of synchronising power and injection of damping power. The control law is implemented
and validated in EMT simulation. It is then shown that an HVDC link can assure the synchronisation of different AC areas even if no
AC transmission lines interconnect them. Through another case study, it is shown how the HVDC link can help to share dynamic
frequency reserves in order to not jeopardise the stability of the system. A last example investigates the effect of a DC fault on AC
transient stability and how the control can help improving the system response.
−1 −1 δ = [δ1 . . . δn ]T , ω = [ω1 . . . ωn ]T
with YSN = (YA − YB YD YC ) and Khvdc = YB YD . Matrix
YSN is the matrix relating all generators voltages and currents, u = [∆Phvdc,1 . . . ∆Phvdc,k ∆Qhvdc,1 . . . ∆Qhvdc,k ]T
Khvdc describes the effect of HVDC injected currents on the
generator. Elements of YSN and Khvdc are:
ω1
.
..
hvdc hvdc
ωn
ȲSNij = Gij + jBij K̄hvdc,ik = Dik
and + jFik
(5) f (δ, ω) = 1 P
− K ω − P (δ)
M
1 m,1 D,1 i gg,1
Gij and Bij are the equivalent conductance and susceptance
..
between generators i and j. Dik hvdc hvdc
and Fik are the real and
.
1
imaginary parts of the element Khvdc,ik which denote the effect Mn Pm,n − KD,n ωn − P gg,n (δ)
of the injected current of the k − th converter on the i − th genera-
0n×k 0n×k
tor. Then, the expression of the active power supplied by the i − th ahvdc ahvdc bhvdc bhvdc
machine Pe,i in Equation (1), is developed as: 11
M1
··· 1k
M1
11
M1
··· 1k
M1
Bp = , B =
.. .. .. Q .. .. ..
. . . . . .
n m
∗ ahvdc ahvdc bhvdc bhvdc
0 ∗ 0 ∗
I¯∗
n1 nk n1 nk
··· ···
X X
Pei = < Ēdi ȲSNij
Ē 0 dj − Ēdi K̄hvdc ik hvdck
(6) Mn Mn Mn Mn
j=1 k=1
Pe,1 (δ1 ) For more general conclusions, the transient stability of both systems
z }| { can be compared by means of the Transient Energy Functions (TEF).
M1 ω̇1 + kD,1 ω1 = Pm,1 − Pmax sin δ1 + Phvdc,1 (13) These functions represent the sum of the kinetic and potential energy
of the system [35]. For a SMIB system represented by Equation (11),
0 the TEF can be found by computing the first integral of motion, as
with Pmax = Ed,1 V2 /X12 .
follows:
WKE WP E
3.1 The Equal Area Criterion z }| { z }| {
1 δ1
2
W (ω1 , δ1 ) = M1 ω1 + ∫ − [Pm,1 − Pe,1 (δ1 )] dδ1 (14)
The power-angle (P-δ) curve of both systems is depicted in Figure 3. 2 δs
This curve represents the power delivered by the generator as func-
tion of the rotor angle. By means of the Equal Area Criterion (EAC), where the total energy W is the sum of the kinetic and potential
the stability margins of both cases can be analysed [34]. energy noted WKE and WP E respectively. From Equation (14),
it must be noted that there is a relation between the Equal Area
Criterion and the potential energy function WP E . Indeed, WP E
represents the surface 1-6-7 on the equal area criterion in Figure 3.
The transient energy functions of the described systems under
comparison are the following:
• a) AC SMIB system:
1
W ac = M1 ω12
2
WPacE (δ1 ) (15)
z }| {
− Pm,1 (δ1 − δ s ) − 2Pmax (cos δ1 − cos δ s )
Fig. 3: Equal area criterion comparison • b) AC/DC SMIB system:
1
In this comparison, every transmission line (HVAC or HVDC) W dc = M1 ω12
2
in both systems transmits the same amount of power in the pre-fault (16)
steady-state situation. Therefore, the constant active power reference WPdcE (δ1 )
z }| {
for the HVDC link is set to be equal to the active power for one − (Pm,1 − Phvdc,1 ) (δ1 − δ s ) − Pmax (cos δ1 − cos δ s )
AC line in steady state (i.e. Phvdc1 = Pmax sin δ s ). This assump-
tion allows to have the same equilibrium points in both systems (the
same angle in steady state). In the plotted region systems have two where WPacE and WPdcE stand for the potential energy of the AC
equilibrium points, one being stable and the other unstable [1]. It SMIB and the AC/DC SMIB respectively. The evaluation of the time
is possible to note that, the stable equilibrium point (SEP) of both derivative of the total energy (W ac and W dc ) gives an estimation
systems is the same (δ1 = δ s ), as well as their unstable equilibrium on how the total energy decays when the system is subjected to a
point (UEP) (δ1 = δ u ). disturbance. The computation of the time derivative of Equations
Let us assume that a temporary three-phase fault occurs in bus 1. (15) and (16) yields (see [12] for more details):
When the fault occurs, the power delivered by the generator suddenly
changes from point 1 to 2 in Figure 3 (it goes to zero). During the Ẇ ac = Ẇ dc = −kD,1 ω12 (17)
fault, both systems accelerate following the same trajectory as the
machine’s delivered power is zero until the fault disappears. Due to This equation shows that the energy decays at a rate proportional
this acceleration, the angle increases from δs to δcl . During the time- to the damping coefficient (kD,1 > 0 ) and the square of the speed
span between fault occurrence and fault disappearance, the system deviation. It is also found that the rate of change of energy in both
acquires a kinetic energy proportional to surface 1-2-3-4. For the systems is the same. Therefore, for a more convenient comparison it
described fault, the acquired energy of both systems is the same (i.e. is proposed to analyse the potential energy on both systems. For this
AAC1 = ADC 1 ).
purpose, the potential energy functions WPacE and WPdcE are plotted
When the fault is cleared, the systems get back to their pre-fault alongside the power-angle curve of each system in Figure 4.
power-angle curve (trajectories go from points 3 to 5 in Figure 3).
The angle continues to deviate until the kinetic energy absorbed
during the fault is expended by transferring it to the grid [1]. The
systems move from 5 to 6, such that area AAC 2 (ADC
2 ) is equal
to area AAC1 (A DC
1 ). For the studied fault, it can be observed that
the maximum angle reached during the first swing in the AC/DC
DC AC
SMIB is larger than the one in the AC SMIB (i.e. δmax < δmax ).
This shows that the AC/DC SMIB is closer to instability for the
same fault. Furthermore, after fault clearing, the available energy for
decelerating the system is proportional to the surface 4-5-8, it can
be easily observed that in the AC/DC SMIB, this surface is smaller
than the surface in the AC SMIB case. This means that transient sta-
bility margins are larger in the AC SMIB than in the AC/DC SMIB.
This phenomenon is due to the nature of the AC lines, their synchro- Fig. 4: Potential energy and power-angle curve comparison.
nizing power injections (AC lines transmit power as function of the
transport angle) contribute to decrease the separation of areas. In the
AC/DC SMIB case, as the HVDC link is set in constant power mode, The evolution of the potential energy as function of the angle
its contribution against angle deviations is nonexistent. deviation shows that there is a local minimum in the SEP. Besides,
which is true for all stable equilibrium points of interest (i.e. 0 < • a) SMIB AC system
δ s < π/2). Consequently it can be stated that, in all the stable equi-
librium points (0 < δ s < π/2), the critical energy of the AC SMIB Ks = KsAC = 2Pmax cos δ s (22)
system is higher than the critical energy of the AC/DC SMIB. Fur-
ther analysis can show that, for a given equilibrium point (0, δ s ), • b) SMIB AC/DC system (the power reference of the HVDC is
all positive values of Phvdc1 will result in lower values of critical constant and equal to Phvdc,1 = Pmax sin δ s )
energy than its equivalent AC SMIB system.
Ks = KsDC = Pmax cos δ s (23)
The synchronising power constant from case (a) KsAC is bigger than
the one in case (b) KsDC for all the stable values of δ s . Conse-
quently, the damping coefficient is higher for the hybrid AC/DC case
than in the pure AC system.
It is possible to conclude, that HVDC links with constant ref-
erences can damp power oscillations in a mixed AC/DC system,
with respect to their equivalent AC system; as it has been actually
observed by power system operators (e.g. [36]). However it doesn’t
mean that transient stability is enhanced, as it was previously shown
in this Section.
(a) AC SMIB
4 Linearizing feedback control
In order to enhance the stability margins of the AC network, the
active power references of the VSC-HVDC are modulated based on
feedback linearization techniques, such as to actively support the
AC grid. The idea behind the feedback linearisation technique is
to compensate the nonlinearities of the system by a control signal,
produced by feedback of measured variables and knowledge of the
system [37]. The obtained system, with reduced nonlinearities is fur-
ther controlled applying linear control techniques for deciding the
dynamic behaviour of the system. The proposed control is used to
(b) AC/DC SMIB derive a supplementary control scheme which computes the neces-
sary active power modulation for the power-mode converter allowing
Fig. 5: Comparison of the regions of attraction. Characteristics
to improve the rotor angle stability of the surrounding AC grid, damp
of the system: δ s = 30, Pm,1 = 1pu , Pmax = 1pu, Phvdc,1 =
the electro-mechanical oscillations and to ensure the synchronisation
0.5pu, kD,1 = 0, M = 0.12MW s2 /MVA rad (i.e. H1 = 4s ). of two AC interconnected networks.
2Xac
L L L L
a a a a
+ PMm1 − PMm2
1 2
− ( M111 − M212 )PL1 + ( M121 − M222 )PL2 − v
(28)
Pload,1 + jQload,1 Pload,2 + jQload,2 Note that if the internal reactance of the machines and the trans-
0
former are small compared to the AC line (Xd1 << Xac ), then
1
Fig. 6: 2-Area 2-Machines AC/DC power system L L hvdc hvdc
a21 = a12 = 0 and a2 = a2 = 1, and the system is found
to be described by:
Pm1 −PL1
Following the procedure described in Section 2, and neglect- δ̈12 = M1 − Pm2M−P
2
L1
ing damping effects, the dynamic equations of the power system M1 +M2 E 0 d1 E 0 d2
depicted in Figure 6 are given by: − M1 M2 (Phvdc0,1 + Xac sin(δ12 ) + ∆Phvdc1 )
(29)
0
E 0 d2
Then the linearizing control law is:
1
M1
Pm1 − E d1 Xeq
sin(δ1 − δ2 )
E 0 d1 E 0 d2
L aL hvdc
+ ahvdc u = −Phvdc0,1 − sin(δ12 )
−a11 PL1 − 12 PL2 − (a11
12 )Phvdc0,1
Xeq (30)
ω̇1 M1 M2 Pm1 −PL1
+M ( M1 − Pm2 −PL1
)− M M1 M2
v
0
E 0 d2 1 +M2 M2 1 +M2
ω̇2 1
Pm2 − E d1 sin(δ2 − δ1 )
= M2 Xeq
δ̇1 L The first part of the control law compensates the nonlinearities of
−a21 PL1 − aL hvdc
22 PL2 + (a21 + ahvdc
22 )Phvdc0,1
δ̇2
the original system, while the term v is used to define the desired
ω1
closed loop dynamics. Then using linear control techniques, v can
be designed to impose the electromechanical mode between two
ω2 regions [39]:
hvdc δ̄12 − δ12
1
+ ahvdc
M1 (a11 12 )
v = −Kδ −Kω (31)
− 1 (ahvdc + ahvdc ) ω12
+
M2
21 22 ∆Phvdc
1
0
where Kδ and Kω are control gains. Injecting the linear control law
0 (31) and the feedback linearizing control law (28) into the system
(24) (25), the dynamics of the closed-loop are found to be:
where ∆Phvdc1 stands for the control input and it represents the
supplementary power injection of the VSC-HVDC link and coef- δ̈12 = −Kω δ̇12 − Kδ (δ̄12 − δ12 ) (32)
ficients aL
il are the distribution factors expressing the impact of
the l − th load on the i − th generator. The equivalent reactance with δ̇12 = ω12 . The control gains can be designed using the pole
is the sum of the reactances between generator G1 and G2 (i.e. placement technique. For this case, the gains can be chosen as func-
0 0
Xeq = Xd1 + XT 1 + Xac + XT 2 + Xd2 ). Generators are said to tion of the desired natural frequency (ωn ) and damping coefficient
be in synchronous equilibrium if all angular distances δi − δj are (ξ) of the controlled system, as follows:
bounded and all frequencies are identical ωi = ωj , therefore the
objective of the control is to make ω1 − ω2 = 0. The error between 2
Kδ = ωn and Kω = 2ξωn (33)
the two regions can be modelled following the change of variables
ω1 − ω2 = ω12 and δ1 − δ2 = δ12 as: Since the system has been linearized by the control action, it can
be concluded that the region of attraction of the controlled system is
M1 + M2 E 0 d1 E 0 d2 theoretically determined only by the power limits (rated power) of
δ̈12 = − sin(δ12 ) the VSC-HVDC link.
M1 M2 Xeq
1 1
+ Pm1 − Pm2 4.1 Physical interpretation of the control actions
M1 M2
aL
11 aL aL aL The control law in (30) is composed of three main actions:
−( − 21 )PL1 + ( 12 − 22 )PL2 (25)
M1 M2 M1 M2
• The first action (noted ulf in Equation (27)) allows to compensate
ahvdc
1 ahvdc for nonlinearities of the system. This action can also work as a feed-
+( + 2 )Phvdc0,1
M1 M2 forward action that compensates disturbances, especially if some of
ahvdc ahvdc those values are measured (e.g. the power flowing through the par-
1
+( + 2 )∆Phvdc0,1 allel AC transmission line). Indeed, from the control law (27) it can
M1 M2 be remarked that the term f (δ12 ) corresponds to the actual power
with δ̇12 = ω12 . It can be observed that using Equation (25), the flowing through the AC corridor, therefore the term c corresponds to
system is now written in strict-feedback form (see [38]), where: the scheduled power to flow through such AC corridor. This prop-
erty can highly simplify the practical implementation of this control
action.
δ̈12 = f (δ12 ) + c + b u (26)
• An action injecting power proportionally to the speed deviation of
both regions (see Equation (31)), contributing to the damping torque
with u the control input, f (δ12 ) is the nonlinear function of the angle of the system.
difference, and c is a constant making its derivative equal to zero in • An action injecting power proportionally to the transport angle
steady state (i.e. δ̈12 = δ̇12 = 0). The linearizing feedback control between both regions (see Equation (31)), contributing to the syn-
law can be computed as follows: chronising torque. As it will be shown in the examples, this action
allows to synchronise both regions even if the parallel AC lines are
u = ulf + v = −b−1 (f (δ12 ) + c + v) (27) tripped.
the power flowing through the tripped AC line before the fault, is
reallocated on the remaining AC line. This is reflected in the incre-
ment of the angle in the post-fault steady-state compared with the
pre-fault value (35o before the fault against 58o after the fault). The
NFL control, by taking into account the disturbance in the system,
will rapidly compensate the power imbalance due to the fault. This
rapid action will limit the angle deviation between regions during
Fig. 7: Control implementation the first swing. After the fault, if power is available, the power of
the tripped AC line is reallocated to the HVDC link. This action will
take the transport angle near its initial condition. As a consequence,
stability margins of the post-fault configuration are similar as in the
initial configuration.
5.1 3-phase fault and trip of the faulted line
In order to quantify the transient stability margins for each strat-
The first case study corresponds to a 250ms 3-phase fault occur- egy, the Critical Clearing Time for two different fault locations are
ring in the middle of the AC line at t = 1s. Three different control computed by iterative simulations and are summarised in Table 1.
strategies are compared: In every case, the fault is cleared by the tripping of the faulty line. It
can be observed that both supplementary controllers (POD and NLF)
• CR (Constant references): The power reference of the converter is increase the stability limits with respect to the CR strategy. Besides,
maintained constant. it is also shown that the stability margins are higher when the NLF
• POD (Power oscillation damping): The control proposed in [13] strategy is implemented.
is implemented. This controller modulates the power reference as a
function of the frequency deviation in both PCCs of the HVDC link Table 1 Critical clearing times for different fault locations
(∆Phvdc = K(ω1 − ω2 )).
• NLF (Nonlinear Feedback): The proposed control is implemented CCT(ms)
Case
and tuned to obtain an inter-area oscillation with a natural frequency CR POD NLF
of ωn = 0.5Hz and a damping factor of ξ = 0.5. The gains are Kδ
= 1.7MW/deg and Kω = 197MW/Hz Fault in the Middle of the line 3-4 290 355 460
Fault near bus 3 120 220 335
In Figure 8, it is seen that in the CR case, angle deviations dur-
ing the first swing are higher compared with the other strategies.
This means that the AC system is closer to lose transient stability (or
power system split). With the CR strategy, it is also clearly observed 5.2 Synchronisation in case of the disconnection of the AC
that inter-area oscillations are poorly damped. When the POD strat- parallel lines
egy is implemented, it can be seen that the VSC-HVDC link is able
to damp power oscillations via the modulation of the active power. In this scenario, the disconnection of the whole group of AC trans-
It is also observed that the angle deviation during the first swing has mission lines connecting both areas after a fault is studied. Let us
been decreased. In the post-fault equilibrium point, the power refer- consider that after a fault on the AC transmission lines, both of them
ence of the HVDC goes back to its initial reference. In other words, are tripped, then no AC lines are interconnecting both areas. In order
1 3
6
10
9
10km 11 10km
25km 25km
20/230kV
2 4
P=967MW P=2400MW
Q=-287MW Q=-437MW
Slack 700MW
p p
1 X 1 X
δCOIq = Mi δi , ωCOIq = Mi ω i
MT MT
i=1 i=1
p
(35)
X
(c) Power transferred through the HVDC link MT = Mi
i=1
Fig. 9: Comparison of different control schemes when the AC
transmission line is disconnected. where p is the number of generators of synchronous generators in
the Area q of interest.
5.3.1 Poorly coordinated frequency response: A result of
In this case study, two strategies are compared: POD and NFL. the increase in the penetration of renewable energies in a grid is the
Figure 9 shows that, after a few seconds, the POD control is able to loss of inertia. The lack of inertia in the grid will lead to a more
ensure the right power exchange between regions and takes the value volatile power system. Controllable devices such as HVDC trans-
of the speed difference ω12 to a stable value different from zero. This mission and Power electronics interface sources must take part in the
means that synchronism of both areas is not achieved. If the system stabilisation of the grid. As reported in [44], one possibility to do so,
are not synchronised it is not possible to reconnect the AC lines (a is to make the renewable sources participate into frequency control
reconnection attempt is shown at t=10s). by supplying fast frequency response. While the primary response of
The implementation of the NFL control shows that synchroni- synchronous machines acts some seconds after the disturbance, the
sation of both areas can be achieved even if no physical AC line power electronics interfaced sources can supply a faster response.
is connected. The proposed control scheme allows to automatically However, as mentioned in [44], this fast power injections can jeop-
replace the disconnected group of lines while damping power oscil- ardise system transient stability. In the case presented in this section,
lations, assuring power exchange and maintaining synchronism by it is shown how those fast power injections may lead to system loss
emulating the behaviour of a modifiable transmission line connect- of synchronism.
ing both areas. Besides, it can be seen that if the AC group of lines The evaluated contingency in this case study is the loss of gen-
is reconnected later, at t=10s, the system remains stable and goes erator G5 in Fig. 10. In order to describe the phenomena, two cases
back to its initial equilibrium point. Synchronisation is achieved are compared. In both cases, the point to point VSC-HVDC system
when ω12 = 0. If both areas are synchronised, the AC transmission is controlled to track constant power references.
line can be reconnected, even if the frequency of each region is not Stable case: No fast frequency response is injected by the
stabilised at 1pu. renewable sources after generator tripping, only the primary reserve
of the generators participates on frequency control. In Figure 11a, the
5.3 Split of the system due to uncoordinated Frequency frequency of the COI of each region as well as the COI of the whole
Response system are represented. It can be seen that after generator tripping
the global frequency drops, and frequency of each areas oscillates
The system used in the last two cases correspond to a modified ver- around the global frequency. The system remains in synchronism
sion of the Klein-Rogers-Kundur’s two-area power system [1]. In and some seconds after the contingency, frequencies reach the same
this modified version the two areas are interconnected by a group steady state value.
of AC transmission lines and a VSC-HVDC link in bipolar con- Unstable case: Fast frequency response is injected. While gen-
figuration. In addition, power electronics interfaced power sources erator tripping occurs in zone two the fast frequency response is
(c) Pos. pole reactive power (d) Neg. pole reactive power
Fig. 13: Active and reactive power injections during execution of the converter breaker strategy triggered by a DC fault[45]
When the fault occurs (t0 ), the current flowing through the sta-
tion increases until the fault is detected and the DC circuit breakers
(DCCB) disconnect the faulted cable, and hence suppress the cur-
rent contribution to the fault. It should be noted that after fault and
before DCCB breaker opening, MMC converters are rapidly blocked
and the AC contribution to the fault passes through the freewheeling
diodes [47]. When the converter is blocked it exhibits the behaviour
of an uncontrolled rectifier. When the faulted cable is isolated, the
MMC can be deblocked (t1 ), therefore the faulted pole can operate
in STATCOM mode. As it can be seen in Figure 13d, while the MMC
is blocked (between t0 and t1 ), reactive power is zero, while after
deblocking the reactive power control is recovered. Before reconnec-
tion, the overhead line requires deionization, which in this simulation
(a) Speed deviation between zones
lasts 350ms (t2 ) after DC circuit breaker opening [46]. After this
time, the cable can be reconnected and the control of the DC voltage
is recovered. Then, the system is ready to return to operation (t3 )
and power is smoothly restored to its initial value.
For this example power references are set to 300 MW for the
VSC-HVDC link and the total exchanged power between 2 regions
is 500 MW. Figures 13 and 14 show the response of the DC and AC
systems respectively, in case of a DC fault. Three control strategies
are compare:
When no supplementary control is implemented, the temporary action of the controller includes the information about the power
power interruption in one pole leads to the loss of transient stabil- references (Phvdc0 ), thus it is possible to update the value of the
ity. In the case where NFL is implemented, the linearizing feedback static references including the loss of power of the faulted pole with