Chapter 6: Electrical and Instrumentation Facilities
Chapter 6: Electrical and Instrumentation Facilities
Chapter 6: Electrical and Instrumentation Facilities
6.1 INTRODUCTION
Electrical systems that are to supply electrical power for an entire STP consist of power receiving
and transforming equipment, power distributing equipment, cables, drives and standby generators.
Instrumentation facilities are also installed for the purpose of measuring and collecting process data
such as flow rate, pressure, water qualities, and so on, at all times. These are utilized to monitor and
control treatment processes at optimal conditions for a stable treatment. The instrumentation facilities
consist of sensors for processes, signal converters, operating devices (actuators), controllers (PLC:
Programmable Logic Controller), monitoring devices (PC: personal computer), etc.
A typical single line diagram (SLD) depicts the entire electrical power flow system of an STP. The
single line diagram not only presents the type and number of equipment but also the electrical
specifications. This is an important document for an O&M person who would like to refer to it in case
of any operational or maintenance need. Every STP should have:
• A SLD kept for record and displayed properly in the STP facility particularly near the
electrical sub-station
• All those personnel involved in the electrical and instrumentation work should understand
the SLD
• Reduce the voltage to the specified level (Typical voltage level is 415 volt for STPs) suitable
for connection to local loads
• Protect the entire network by identifying and isolating electrical faults selectively
6-1
CHAPTER 6:
Part B: Operation and Maintenance ELECTRICAL AND INSTRUMENTATION FACILITIES
Figure 6.1 Typical Electrical Single Line Diagram of 11 KV Yard and Master Switch Board
6-2
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
If the STP facility receives the electrical supply at high voltage i.e., 66kV, 11kV, 6.6 kV, or 3.3 kV, it
has to be reduced to the operating voltage level, which is usually 415V. A substation, which is used
to step-down high voltage to low voltage, consists of the following equipment or devices:
Disconnecting switches are devices to open/close a high voltage circuit when high-voltage
equipment are inspected, tested or cleaned. The devices are capable of safely breaking no-load
current but not load current. For safe O&M work, be sure to open/close the disconnecting switch
only after opening a circuit breaker, which is located on the secondary side, just downstream of
the disconnecting switch.
Circuit breakers are switches that open/close electric-circuits in normal and abnormal conditions
(especially in short circuit). Therefore, the circuit breakers must be capable of tripping the circuits
in conjunction with protective relays and by cutting off the short-circuit current definitely and safely,
avoiding accidents due to high current.
Circuit breakers for high voltage are categorised into the following types according to their techniques
of eliminating arcs:
The function of a power fuse is to sense and prevent flow of excess current in electrical devices and
electrical wire by melting the fuse element and thereby breaking the electric circuit when subjected
to a short-circuit. Power fuses are typically used for smaller electrical systems because they have the
capability and speed for breaking the circuit as compared with circuit breakers.
A proper O&M, practice is that even if only one fuse melts due to an accident such as a short-circuit
in a three phase switch, all power fuses including the melted one should be replaced.
Voltage transformers are used mainly in high-voltage distribution equipment to step-down voltage in
measurement circuit for safe measurement; single-phase and three-phase types are manufactured.
6-3
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
The typical secondary voltage of the voltage transformer is 110 volt (Phase-to-Phase). They are also
applied to protective relays.
• If once short circuit occurs on the secondary side of a VT, excess current flows into the primary
side and that may cause the fuse on the primary side to blow. The primary fuse has also to be
checked when there is a fault trip or metering mismatch.
Current transformers are used for stepping down current to be measured safely. It is also applied to
protective relays.
• If the secondary side of CT is open-circuited, all the current flowing to primary side is excited by
magnetic saturation and causes damages to the CT by over-heating. Therefore, the secondary
side should never be left open-circuited. Even when the downstream instrument is removed for
any repair, the secondary should be shorted.
Protective relays should detect electrical faults promptly, isolate the faults from system and activate
alarms when there is a faulty condition sensed in the electrical supply to the circuits or electrical
equipment (short circuit, earth fault, single-phase, reverse power flow etc.)
A. Certainty: The relay should always be sensing the parameters for action when there is a
fault or specified abnormality.
B. Selectivity: The relay should obey a selection of the limits beyond which a fault will be judged.
C. Promptness: The relay should sense and operate within the shortest possible time.
A. Over current relay (OCR): Monitor and protect against over load and short-circuit.
B. Under voltage relay (UVR) and over voltage relay (OVR): Detect and protect under voltage
(power failure) or over voltage.
6-4
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
An electrochemical protective relay converts the voltages and currents to magnetic and electric
forces and torques that press against spring tensions in the relay. The tension of the spring and
taps on the electromagnetic coils in the relay are the main processes by which a user sets a relay.
In a Solid State relay, the incoming voltage and current waveforms are monitored by analog
circuits, not recorded or digitized. The analog values are compared to settings made by the user
by a potentiometer in the relay.
A Digital Relay converts all measured analog quantities into digital signals. Compared to
static relays, digital relays introduce Analogue to Digital Converter (A/D conversion) of all
measured analogue quantities and use a microprocessor to implement the protection algorithm.
The microprocessor may use some kind of counting technique, or use the Discrete Fourier Transform
(DFT) to implement the algorithm. Since late 1990s most of the protective relays are of digital type.
• Functional flexibility
• Capable of working under a wide range of temperatures. Internal power requirement is very low.
• They can implement more complex functions and are generally more accurate
• Economical because can be produced in required numbers and can be set at site
• More accurate
6-5
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
The devices have short lifetime due to the continuous development of new technologies.
• As digital systems become increasingly more complex they require specially trained staff
for operation
6.2.1.2 Transformer
A transformer is the most important component in substations. Transformers receive electrical power
at high voltage and transform it to lower service voltage. They also provide isolation between high
voltage and low voltage supply.
Cooling system for oil-immersed transformer: Oil serves as direct cooling medium to disperse the
heat that is generated from windings and core. The oil is in turn cooled by indirect cooling medium
such as air at the oil radiator.
Cooling system for dry transformer: Utilize surrounding air or SF6 as cooling medium.
Transformer Efficiency: The efficiency of a transformer varies between 96% and 99%. It not only
depends on design, but also on operating load. The transformer losses are mainly attributed to:
• Constant Loss: This is also called iron loss or core loss, which mainly depends upon the
material of the core and magnetic circuit of the flux path. Hysteresis and eddy current loss are
two components of constant loss.
• Variable Loss: This is also called load loss or copper loss, which varies with the square of the
load current.
The best efficiency of a transformer occurs at a load when constant loss and variable
loss are equal.
For distribution transformers, installed in an STP, the best efficiency would occur around 50% load.
O&M checks to be made are as follows:
6-6
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
They typically consist of moulded case circuit breakers (MCCBs), power contactors (PCs), protective
relays (PRs), meters, indication lamps, control switches, etc.
A. MCCB
An MCCB is designed to “open/close” low voltage feeder circuit or branch circuit at normal
condition. It also breaks the circuit automatically in case of abnormal condition such as overload,
short circuit, etc.
B. Power Contactor
A power contactor is typically used for “on / off” control of motors. A relay can be installed on the
circuit for overload protection. Electromagnetic force works to “open /close” the contacts.
• Check for abnormal noise or overheating of exciting coils, abnormal noise and discolouration of
contacts (carbonized or worn contact surfaces by arcing)
• Check for the proper working of all display indicators like voltmeters, ammeters,
energy meters and indicator lamps
• Check whether the name of the panel is written on it and it is correct as per the SLD
6-7
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
6.2.1.4 Bus-bar
Bus-bars are conductors to carry power among the various components in the power circuit in
an outdoor station or distribution board. They are to be rated to carry the maximum rated current
continuously and short-circuit current for a short time without damage.
• Check connections for looseness and overheating, and check the bus bar for discolouration
• Check bus bars are properly colour coded (Red, Yellow or Blue) to represent the phases
Correcting power factor is a typical power control technique. Power factor correction is described in
this section.
Active power, measured in kilowatt (kW), is the real power (shaft power, true power) used by a load
to perform a certain task. However, there are certain loads like motors, which require another form
of power called reactive power (kvar) to establish the magnetic field. Although reactive power is
virtual, it actually determines the load (demand) on an electrical system. Electrical capacity required
for some electrical equipment is referred to as “apparent power (kVA)”, that is, the vector sum of
“active power” and “reactive power (lagging / leading)”.
Most of the power machineries in STPs are driven by three-phase induction motors, which are
inductive loads. When an inductive load is driven, the sine wave of the load current flows at the
same frequency as the sine wave of the voltage, but lags the voltage wave cycle slightly. When both
current and voltage source waves cross zero and maximum value at the same time, the power factor
is said to be unity, and the entire power can be utilised as real power. The ‘Apparent Power-kVA’ is
equal to ‘the real Power-kW”. When the current wave is slightly lagging the voltage wave, the power
factor is said to be lagging and is less than unity. The real power is less than the apparent power due
to this lag.
A lagging power factor is not beneficial to a power consumer as the billing is includes
charges towards the kVA used, while the actual utilisation is less.
It is also not beneficial for the power supplier whose system power factor is also affected.
Equipment used in most industries such as drives, controllers, etc., are inductive loads, which
lower the power factor. The power factor is the ratio between active power (kW) and total
power (kVA), or the cosine of the angle between active and total power. A high reactive power will
increase this angle and as a result the power factor will be lower. A vector diagram of power factor is
shown in Figure 6.4 overleaf.
6-8
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
In a typical STP since a large number of induction motors are used, the power factor will be low and
needs to be improved or corrected. The power factor can be improved by installing power factor
correction capacitors to the plant’s power distribution system.
They act as advancing reactive power generators and therefore reduce the amount of lagging
reactive power, and thus the total power, generated by the utilities.
To improve or correct the power factor, apparent electrical capacity required for the electrical
equipment should be decreased by canceling the lagging reactive power by the use of leading
reactive power unit that can also reduce energy loss in cables, transformers, etc., before reaching to
load equipment.
Rating of capacitor to be required for power factor correction can be calculated by the following
vector equation.
(6.2)
Capacitor panels consist of some equipment such as condensers for power factor correction, series
reactors meters, relays, etc.
6-9
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
Induction motors, which are inductive loads, generate lagged-phase reactive power.
Phase-advanced condensers (capacitor) have the function of compensating the lagged-phase
reactive power to improve power factor.
The effects gained from the condensers vary according to the points to be installed. For
example, it is effective to install a condenser on the secondary side of a transformer if reduction in
load and loss of the transformer is targeted.
With regard to O&M, the capacitor’s reactive power acts during light load (when power equipment
has stopped), and when the current leads the voltage in the circuit so that leading power factor
occurs, and the terminal voltage of the load increases causing adverse effects on the equipment.
To prevent this phenomenon, the capacitor may need to be isolated, or an automatic power factor
regulator may need to be installed.
Normally, a capacitor unit comprises of individual capacitor elements arranged in parallel/ series
connected groups within a steel enclosure. An internal discharge device is a resistor that reduces the
unit residual voltage to 50V or less in 5 minutes. Capacitor units are available in a variety of voltage
ratings from 240 V – 66,000 V and sizes (2.5 kvar – about 1,000 kvar).
6 - 10
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
The capacitors can be with external fuses or internal fuses, or both. An internal fuse is a small fuse
wire connected to each capacitor element, encapsulated in a wrapper. When a fault occurs in a
particular element, the particular fuse melts, disconnecting the affected element only, and
permitting the other elements to function without interruption. An external fuse unit typically protects
each capacitor unit in a bank. In an oil-impregnated capacitor, the internal pressure may increase
resulting in expansion due to excessive current because of the failure of internal elements. This leads
to leakage of oil from the capacitor unit and failure of the capacitor. Care should be taken to select
capacitors with sufficient cooling volume.
When a capacitor circuit is switched on, there is an inrush current, which is likely to damage the
capacitor. A choke or series reactor is used to control the inrush current.
The major functions of a series reactor are to protect the capacitor by means of the following:
Power factor can be increased by installing low voltage capacitor in parallel with the motor. This
enables the current to be reduced. Moreover, distortion waveform can also be stabilized by
connecting a series reactor.
Power interruption is classified into two types: a scheduled power interruption and an unscheduled
power interruption.
The former requires specific operational procedure before interrupting the power supply, which is
to “open” the switches from the load side (power distribution panel) to the power source (power
receiving panel) sequentially. To restart the power supply, “close” the switches from the power source
(power receiving panel) to the load side (power distribution panel) one by one.
Make sure that the personnel in charge of the interruption/ restart operation thoroughly knows the
configuration of the machinery, the operational characteristics, the operational procedures, the place
or position of switches installed, the electrical scheme diagram and the load circuit diagram to avoid
incorrect procedures.
During the work of starting, operating and stopping the load equipment, pay attention to meter
readings, vibration, heat, and sound of equipment. If some abnormal state is found, report to the
related person in charge immediately, investigate the causes and take appropriate measures.
6 - 11
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
In the latter case, investigate the cause of the power failure first. Power failures can be caused by
the following: some failure attributed to the power company (outside power suppliers) and some
local fault in the STP. To identify the causes, read indicated values or signs on the incoming supply
voltmeter, under-voltage relay, earth fault relay, over current relay, etc.
• If the receiving voltmeter indicates “0” and the under voltage relay is “tripped,” it implies that
power is interrupted on the power source side (attributed to power company). After confirming
that the receiving circuit breaker is “opened,” the contact person or authority prescribed by the
power company should be asked about the causes and the estimated recovery time. However,
the related substation should try to restore power at the earliest.
• If the reading of the receiving voltmeter is within a specified range, the under voltage relay is
“untripped” and the earth fault relay or the over current relay is “tripped,” that implies some
failure (overload, short, earth fault, etc., in equipment or lines) has occurred in the STP and the
circuit breaker for receiving power is “opened.” By studying the protective relay, circuit breakers,
etc., which were tripped or opened, identify the line with fault and isolate the broken down point
immediately before recovering from the failure.
Generally, digester gas is used as fuel in boilers for heating sludge digestion tanks; surplus gas is
incinerated in biogas combustion units or flared and discharged to the atmosphere. An example of
flow of power generated from digester gas is shown in Figure 6.6.
A sewage gas generator uses the sewage gas as fuel to a gas engine and generates electricity, which
is supplied to equipment within a STP. The digester gas engine consumes gas as fuel and employs
spark-ignition method, which is the same as the one used in petrol car engines.
6 - 12
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
• Typical concentration of NOx in exhausted gas from digestion gas engines is about 2,000 ppm.
NOx should be reduced to prevent air pollution
• Replace the ignition plugs in the spark-ignition system periodically
• Periodic opening up, cleaning and inspection of a digestion gas engine is extremely important
because siloxane compound gets deposited in the combustion chamber of such an engine, which
causes faults in engine parts
Dual-fuel (gas-diesel) engines are compression-ignition, not spark-ignition engines. To ignite, they
simultaneously burn gas and a small amount of diesel fuel as pilot fuel. Their controls also allow
automatic switchover to 100 % diesel fuel operation without changing load if the digestion gas supply
is inadequate or is interrupted. This capability is a beneficial feature for standby units because they
can start and operate even during power failures.
Dual-fuel engines typically use 1 to 5 % diesel fuel oil, but many can, if necessary, operate on
1 to 100 % diesel fuel. Such fuel flexibility is an excellent advantage, especially if the digester gas
supply is disrupted. This option includes storage and handling equipment for diesel fuel, along with
gas compressors to supply digester gas to these engines. The same O&M checks should be made
for the diesel engine and the gas engine. Please refer to 6.3.2 and 6.2.4.
Standby or emergency power can be supplied through AC(alternating current) generator and diesel
engine. Most generators of STPs are installed for the purpose of standby power supply.
Therefore, they should be highly reliable because the STPs have to keep functioning without
hindrance even in the event of unexpected power cut from the power company.
6.3.1 AC Generator
Frequency of the synchronous generator is determined according to the rate of rotation, and
accordingly, the frequency decreases as the rate of rotation becomes lower than the
synchronous rate.
Therefore, the rate of the engine for the synchronous generator should be regulated to maintain
the level of synchronous rate.The O&M issues to be taken care of are mentioned overleaf:
6 - 13
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
• Winding
• Oil or dust on windings or air vent sleeves obstructs air ventilation and leads to overheating of
the generator and deterioration of insulators, which may cause short circuit and ground fault.
The dust should be blown-off by a compressed air and the oil and grease should be removed
with cloth, cleansing oil, etc.
• In the case of severe accumulation of oil and dust, it is recommended to have the winding
cleaned and varnished with insulation paint after drying thoroughly, by a professional
cleaning company.
• Bearing
• Pay full attention to any abnormal noise from bearings during running to detect any defect at early
stage. It is the simplest way to check bearing conditions.
• Grease should be supplied through the openings periodically while the generator is running.
If a drain valve is provided to the grease chamber, always open the valve during filling grease to
purge out old grease.
• Worn brush reduces brush pressure and causes sparks that may make the surface of a slip
ring rough. To prevent it, always check for abrasion, unsymmetrical wear or damage to brush,
and pressure of the brush holder. The brush-lifting device should be inspected to ensure
that it works properly.
• Brushes should be replaced with new ones when the wear level reaches the designated value.
The newly installed brushes should preferably be of the same material and shape as the
currently used ones.
• Exciter (brushless)
• Exciters hate moisture and dust. Dust should be blown-off by low-pressure compressor and
wiped with dry cloth.
• Check bolts and nuts on terminal area and terminal block for looseness, wires for discolouration
and conditions of earthing and installation.
Diesel engines are generally used as drives for back-up power generators.
The diesel engine works by the action of high-speed diesel combustion, which pushes out pistons
by the expansion based on self-ignition. The compressed air is hot enough to self-ignite when diesel
fuel is injected. Piston action caused by the energy is converted in the crank-shaft to rotating energy,
which drives the generator. High-speed diesel is typically used as fuel.
6 - 14
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
• During inspection and maintenance, take care not to allow dust contamination especially into fuel
or lubrication system
• Check wiring for loose connection and check piping for leakage
• Where it is necessary to store diesel for such engines, mandatory precautions regarding
storage-area fire protection, clearances, etc., should be followed. Appropriate clearance from the
jurisdictional authorities on pollution control and inflammable fuel storage should be obtained.
6.3.3 UPS
UPS stands for Uninterruptible Power Supply and is a power supply device, which works when the
usual power source is interrupted. UPS is used to keep critical systems like monitoring, SCADA,
communication and alarm systems running even when power is not available form main
source. A typical UPS circuit is shown in Figure 6.7.
In the normal condition, commercial AC (alternating current) power is sourced and converted to
DC (direct current), which is then supplied to an inverter, and charges a battery.
6 - 15
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
When the commercial power source is interrupted, power charged in the battery is converted to AC
and supplied to the load.
The UPS has a rectifier to convert AC supply to DC for charging the battery, a DC to AC inverter to
convert the battery output to AC voltage, and a battery to act as a source of power during normal
power interruption. Other components like protection, fuses, indication, surge controlling circuit etc.,
are also built into the unit.
Three-phase induction motor is widely used as a general-purpose motor due to high reliability and
low price among driving forces for general industrial machinery. Most prime movers used for pumps
or blowers in STPs are three-phase induction motors.
A three-phase induction motor rotates the rotor by a rotating electromagnetic field, which is generated
in the stator core by AC current flowing in the stator winding.
(6.3)
Rotating speed of the revolving magnetic field is referred to as “synchronous speed” and expressed
as Ns (rpm). The speed of the rotor itself is slightly lower which is expressed as N (rpm). The ratio of
Ns to the differential speed (Ns/N) is referred to as “slip”.
6.4.2 Starters
An extremely large current of about five to eight times the rated current flows when a motor is started.
The power factor is at an extremely low value of about 0.2 at the start. The duration of the starting
current is short, but the motor winding coil is subjected to thermal stress load as Joule heat. Voltage
fluctuation occurs in the power system and its effect becomes more pronounced.
6 - 16
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
The starting method of three-phase induction motor includes a method of restricting current at start
as mentioned above, and other methods described below.
A. Direct-on-line Starter
Power supply voltage is applied as-is, and a starting current which is several times the rated
current flows. This starter is used in motors requiring comparatively small starting currents.
1/√3 of power supply voltage is applied on the Y (star) connection winding at start, while Δ (delta)
connection is used during operation. Compared to the full voltage starter, the starting current is
one third and the starting torque is also one third.
C. Reactor Starter
The voltage to be applied to the motor at start is reduced by the reactor and full voltage is applied
after the motor picks up speed, and is operated. The starting current can be restricted to a smaller
value compared to the Y-Δ starting method.
The circuit diagram of some of the starting methods are shown in Figure 6.8.
6 - 17
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
Theoretical analysis should be carried out to study torque characteristics and overheating of
three-phase induction motor due to fluctuation in frequency and variation in voltage of the motor.
According to the equation for induced electromotive force, the frequency is constant, therefore
the maximum magnetic flux Φm increases and the over-excitation phenomenon occurs. Heat is
generated because of this excitation current. In a submersible pump, when a thermal protector is
built-in in the internal coil for protection, it may activate.
According to the torque equation, when the frequency is constant, the power supply voltage V
reduces, so the torque reduces.
When the power supply voltage is unbalanced, reverse phase current flows and the temperature
increases because of load loss in the coil resistance.
According to the torque equation, when power supply voltage is constant, the torque reduces.
When the power supply voltage is constant, the maximum magnetic flux φm increases, and heat
is generated because of the excitation current. According to the torque equation, when the power
supply voltage is constant, the torque increases.
6 - 18
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
The efficiency of a motor is determined by intrinsic losses that can be reduced only by changes in
motor design and operating condition. Losses can vary from approximately 2 to 20 %.
Table 6.1 shows the types of losses and their typical shares for an induction motor.
The efficiency of a motor can be defined as “the ratio of a motor’s useful power output to its total
power output”. Factors that influence motor efficiency include:
• Capacity - As with most equipment, motor efficiency increases with the rated capacity
• Type - For example, squirrel cage motors are normally more efficient than slip-ring motors
• Temperature - Totally-enclosed fan-cooled (TEFC) motors are more efficient than screen
protected drip-proof (SPDP) motors
There is a clear link between the motor’s efficiency and the load. Manufacturers design motors to
operate at a 50–100% load and to be most efficient at a 75% load. But, once the load drops below
50% the efficiency decreases rapidly as shown in Figure 6.9 overleaf. Operating motors below 50%
of rated loads has a similar, but less significant, impact on the power factor. High motor efficiencies
and power factor close to 1 are desirable for efficient operation and for reducing costs down of the
entire plant and not just the motor.
Because the efficiency of a motor is difficult to assess under normal operating conditions, the motor
load can be measured as an indicator of the motor’s efficiency. As loading increases, the power factor
and the motor efficiency increase to an optimum value at around full load. It is necessary to see the
percentage loading of the motor. If the motor runs at more than 70% load, then the power factor and
efficiency will be good.
6 - 19
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
Apart from operational point of view, the motors should be seen from energy efficiency opportunities
also. The following points may be considered:
The vibration in rotating machinery is caused by many reasons like unbalance, misalignment, loose
foundation, mechanical looseness, bearing damage etc.
Vibration monitoring is the most common, versatile and powerful condition monitoring technique
adopted in rotating machinery to identify problem areas. The severity of the vibration is
specified by IS 2372, which is measured with reference to class of machine.
The criteria for class of machine are given in Table 6.2 overleaf. For the above class of machine,
the vibration severity can be judged by the guidelines shown in Table 6.3 overleaf.
6 - 20
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
The guidelines for vibration frequencies and likely causes are mentioned in Table 6.4 overleaf.
6 - 21
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
If the measured vibration level is more than the acceptable level, then it calls for vibration analysis,
which is a captured time waveform plotted as amplitude versus time, or data can be transformed
using a Fast Fourier Transform (FFT) and expressed as amplitude versus frequency. Any random
vibration signal can be represented by a series (a Fourier series) of individual sine and cosine
functions that can be summed to yield an overall vibration level. The amplitude of this vibration
signal defines the severity of the problem. Plotting the amplitude versus the frequency (the Fourier
spectrum) allows for identification of discrete frequencies contributing most to the overall
vibration signal, commonly referred to as a “signature analysis” or a “frequency spectrum”, Machine
looseness, misalignment, imbalance, and soft foot conditions are all fairly easily identified in the
frequency spectrum generated by an analyser. The vibration monitoring and analysis should be done
periodically, typically once in 6 months for all rotating equipment.
6 - 22
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
Commonly identified with electrical equipment monitoring, thermography is also a useful tool for
monitoring plant machinery.
This technique can be used very well for seeing the loose contact, corrosive contact of all types of
electrical joints, body temperature of motor and transformers, panels, etc.
The criteria shown in Table 6.5 may be used to know the severity of the problem.
6 - 23
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
The following five types of ASDs (Adjustable Speed Device) are available.
• VFD: Electronic devices to control the speed of the motor by controlling the frequency of the
voltage at the motor.
• Direct current ASDs: Electronic devices to control direct-current motors by changing the voltage
applied to the motor.
• Eddy-current drives: Electrical devices that use an electro-magnetic coil on one side of coupling
to induce a magnetic field across a gap, creating an adjustable coupling.
• Hydraulic Drives: Devices that operate much like an automotive hydraulic transmission.
• Mechanical speed-control products including gearing, mechanical transmissions, and belt drivers
with variable-pitch pulleys can be used.
VFD varies the revolving speed of an induction motor freely by changing the power supply
frequency and the power supply voltage. A power transistor is used for the main circuit and IC, and a
microcomputer is used for the control circuit of VFD.
6 - 24
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
Further advanced controlling technology has been applied due to improved semiconductor devices
in recent years.
Moreover, generally, VFD is also called inverter control equipment or variable voltage variable
frequency (VVVF) equipment. The fundamental configuration is shown in Figure 6.11.
After changing an alternating power source into direct current in a converter part and
making it smooth, transform the direct current inversely to variable frequency alternating current
at an inverter part
Advantages:
Disadvantages:
• Harmonic protection measures are necessary since high frequency current is generated
• Generation of leakage current and noise due to high frequencies need to be restricted
• Noise prevention for other equipment (especially measuring instruments) is necessary
One of the pump characteristics is that its load torque is proportional to the square of its revolving
speed, and this torque is called square reduction torque load.
6 - 25
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
• Circuit breaker
The former is a thermal function and has on-delay characteristics, while the latter is an
electromagnetic function and has instantaneous characteristics.
• Thermal relay
Changes bimetal with Joule heat of overload current, opens or closes the contact, and performs
on-delay operation.
This unit measures the current from all the three phases and checks for single-phase,
unbalance and overload. The measurement and comparison of these three factors
provide protections against short circuit, single-phase, earth fault, phase sequence and thermal
protection to the motors.
Temperature sensing thermistors are also embedded in the stator winding of HT motors
during manufacture and connected to relays to monitor winding temperature and raise alarm
when needed
• Dry-run protection
In addition, dry-run protection is also provided by water level sensors in the sump, which
sense any low level of water and prevent dry running, thereby protecting the pump and motor.
6 - 26
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
6.5.2.1 Float
A float device measures a liquid level from above. Floats, one of the oldest and simplest methods
of level measurement, are used extensively in wet-wells or sludge sumps that require a discrete
high or low level indication. They are also used for local indication of level in tanks and open
channels as in Figure 6.12 and Figure 6.13.
Source: WEF,2008
Figure 6.12 Counter weighted float-level indicator
Source: WEF,2008
Figure 6.13 Float switches
A float level meter shown in Figure 6.12 senses water level through a slide rheostat as
resistance and converts the changed resistance into current. It transmits analog output signal (DC
4 mA to 20 mA) proportional to the water level and sends the signal representing the water level
continuously to the monitoring room.
• Clean inside the stilling well regularly and keep it free from floating matter or scum to
prevent malfunctions
6 - 27
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
• Check moving parts such as a counter weight, pulley and wires for corrosion or damage
The level switch shown in Figure 6.13 is used to control the pump and to issue alarms according
to water level. The signals from the level switch are “on/off” digital signals, which compromise a
sequence circuit. Float switches should be located away from the tank walls to prevent the floats
from banging against the concrete wall and internal contacts from failures.
6.5.2.2 Ultrasonic
The ultrasonic level measuring device is installed above the liquid surface and measures the level
by generating a pulse of ultrasonic waves that bounce off the liquid surface below. The instrument
detects the echo, calculates the echo’s travel time and converts it to a level measurement as shown
in Figure 6.14.
Source: WEF,2008
Figure 6.14 Acoustic level-sensor installation
Specifically, the relation between distance from sonic transmitter/ receiver to the liquid surface and
the reaching time is expressed in the following formula:
• Ultrasonic level meters require little daily maintenance because they have no moving parts
and work without contacting the measuring objects. However, the junction boxes have to be
regularly checked for any water ingress
6 - 28
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
6.5.2.3 Head-Pressure
The head pressure level measuring devices, bubbler tubes and diaphragm bulbs measure the
head pressure at the liquid level and are often used in open-channels or non-pressurized tank
applications.
The bubbler tube system uses a small, regulated airflow that constantly bubbles into the liquid.
Because the airflow is small, the system produces a backpressure equal to the static head of the
liquid. A conventional pressure gauge or transmitter measures this back pressure as the height
of an equivalent water column. A schematic of bubbler tube system is shown in Figure 6.15.
Source: WEF,2008
Figure 6.15 Schematic of bubbler-level system
Corrections are required when the liquid’s specific gravity differs significantly from water. Because
air is constantly bubbling out of the bubbler tube, the system is typically self-purging. Valves may be
arranged to isolate the pressure-measuring device while providing high purge flow through the tube
for preventive maintenance blow-down if fouling occurs.
Stilling wells are often used to protect the bubbler tube from turbulence and damage. To protect
pneumatic instruments and regulators, operators should clean the air supply of excessive
moisture and oils.
When bubbles are discharged into the liquid from the front end of pipe, the pressure within the
pipe becomes equal to the static pressure of liquid at the front end of the pipe. This pressure is
proportional to the liquid height h.
6 - 29
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
The bubble type liquid level gauge does not have moving parts or mechanisms, so it has
comparatively high accuracy. Moreover, it is suited to level gauges for corrosive liquids. However,
daily maintenance of air sources such as compressor, purging set and air piping is very important.
The diaphragm bulb system operates on the principle that air sealed between the dry side of the
diaphragm (in the capillary tube) and the receiver compresses or expands with the movement
of the diaphragm.
A change in the static head of the liquid being measured moves the diaphragm, so the pressure
of the trapped air is the same as the head pressure. Temperature changes because of
sunlight or heat build-up, particularly along the capillary tube, can cause measurement
errors as a result of expansion of the trapped air. To reduce the effect of temperature, the
capillary can be filled with a fluid unaffected by operating temperature; however, this often affects
the measurement response time.
The differential pressure from the diaphragm is detected by a piezoelectric semiconductor element.
The output signal (4 mA – 20 mA DC) generated by the converter is changed to analog data in the
central monitor and transmitted.
The following precautions should be taken related to the use of differential pressure type
level gauge:
• The installed position of differential pressure transmitter should be lower than the minimum
liquid level
• When the density of the liquid changes, correction is necessary (Span adjustment on the
converter side is required)
• If the liquid has pulsing motion, the output of the differential pressure transmitter may become
unstable
6 - 30
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
6.5.3.1 pH
A glass electrode, which is sensitive to hydrogen ion activity, measures the pH of an aqueous
solution. The electrode produces a voltage related to hydrogen ion activity and to pH. The pH is
determined by measuring the voltage against a reference electrode. While it is generally
assumed that no other ions seriously affect the pH electrode in an aqueous system, sodium ions
can have an effect. Temperature corrections are also necessary, but are typically done automatically
by the meter. A typical pH sensor is shown in Figure 6.16.
Source: WEF,2008
Figure 6.16 Typical pH sensor
• Dirt on the electrode surface should be periodically removed and the surface cleaned
• Since the electrodes of the pH meter are made of glass, care is necessary to ensure that
they do not break
• Due to long period use of glass electrodes, dirt sticks on them gradually, the zero point changes,
and the electromotive force by pH reduces and it stops responding to changes in pH, making
replacement necessary
• Standard liquid should be used in the pH meter and it should be calibrated. Calibration
should include zero adjustment (standard liquid with pH7) and span adjustment (standard
liquid of pH4 or pH9)
6 - 31
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
• Precautions against breaking an ORP electrode, which is made of glass and is fragile
A dissolved oxygen meter is an electronic device that converts signals from a probe placed in the
water into units of DO in mg/L. Most meters and probes also measure temperature. The probe is
filled with a salt solution and has a selectively permeable membrane that allows DO to pass from the
stream water into the salt solution. The DO that has diffused into the salt solution changes its electric
potential. This change is sent by electric cable to the meter, which converts the signal to mg/L on a
scale that anyone can read.
If it is determined that the DO membrane needs to be replaced, consult the manufacturer’s manual
on conditioning the new membrane before use. It is also possible that other maintenance will need to
be performed on the DO meter or the zero DO solution may need to be replaced. Other factors that
affect the accuracy of DO measurements include–improper calibration, not verifying calibration after
use and not correcting for ambient barometric pressure/altitude and instrument drift. A typical hand
held DO meter with probe for field use is shown in Figure 6.17 overleaf.
6 - 32
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
6.5.3.4 Temperature
Even though most of the major sewage treatment processes are not temperature-controlled, many
temperature measurements are required. Obvious applications for temperature measurement are
anaerobic digesters, chlorine evaporators, incinerators, and equipment protection. Less obvious
are temperature controls for analyzers and flow meters. Temperature measurement devices include
liquid thermometers, bimetal thermometers, pressure on liquid or gas expansion bulbs, thermistors,
resistance temperature detectors (RTDs), infrared detectors, and crystal window tapes. The RTD is
typically used on lower, ambient-range temperatures, while thermocouples provide better reliability in
higher ranges. In addition, gas- and liquid-filled temperature sensors and thermistors are frequently
used for equipment-protection and cooling systems.
For continued accurate service, operators should periodically calibrate the instruments using a
standard temperature measurement device with high accuracy.
6.5.3.4.1 Thermocouple
The thermocouple operates on the principle that current flows in a circuit made of two different
metals when the two electrical junctions between the metals are at different temperatures. The various
combinations of metals used are tabulated in most engineering handbooks, and the selection of
metals is based on the maximum temperature to be measured. Thermocouples measure as high as
980°C, with an accuracy of 1% of the full scale.
6 - 33
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
All solids concentration meters use indirect methods (such as optical, ultrasonic and nuclear).
Indirect methods correlate the solids concentration with a measurable factor. The limitation of not
relating perfectly to the quantity of suspended matter does not seriously affect the analysers ability to
produce a repeatable signal of great value in process control.
When a light beam is directed on to liquid containing suspended particulates, the suspended
particulates scatter some of the light. The nephelometer helps observe and measure the amount of
light that the particulate matter scatters as shown in Figure 6.18.
Source: WEF,2008
Figure 6.18 Nephlometer
The amount of scattered light relates approximately to the amount of particulate matter, particle
size and surface optical properties. This is a photoelectric device that uses an incandescent light
source (lamp), which produces light in wavelengths from blue to red. The light is directed to a
liquid and if the liquid contains particles, some of the light strikes the particles and scatters. By
placing a photocell or light detector at an angle to the light beam rather than directly in front of it, the
detector receives only light scattered by the suspended particulate matter. Most nephelometers have
the photo detector placed at a 90-degree angle to the incandescent light source.
SCADA is an acronym for Supervisory Control and Data Acquisition. This presents the data as
a viewable and controllable system on the screen of a computer. The data thus collected can be
stored and analysed for optimization of the process and for better real time process control. It assists
plant-operating personnel by monitoring and announcing abnormal conditions and failure of
equipment. It allows the operators to perform calculations based on the sensor inputs. Daily, weekly,
monthly reports can be prepared using the stored data. It also allows the operator to know the state
of a process by an alarm associated with it. A typical SCADA is shown in Figure 6.19 overleaf.
6 - 34
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
Source: Kruger
Figure 6.19 Typical SCADA communication overview
For maximum use and effectiveness, signals generated by various sensors and instruments are
transmitted from the sensor to a receiver installed at another location. Often, the sensor output is
transmitted to a control panel or computer system, which allows operators to inspect many process
variables simultaneously.
The three components of a signal-transmission system are the transmitter, receiver and
transmission medium (the connection between the transmitter and receiver). The transmitter
converts a mechanical or electrical signal from the sensor into a form that the transmission medium
can use. The transmission medium contains the signal and transfers it to the receiver. The receiver
subsequently converts it into a form that the receiving system can use.
6.6.1.1 Signal
“Analog input signal” means continuous signal such as process data, which is transmitted from a
local transmitter to a central control unit (CCU).
For instance, process variables expressed in physical amount such as opening degree of a
sluice gate (0–100%), sewage flow rate (0– ***m3/hr), and water level in tanks (0–***m) are
converted into electrical signals and are transmitted to CCU. Standard electronic transmission
systems use 4 – 20 mA DC.
6 - 35
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
There are several transmission systems. One is to connect directly with the CCU I/O (Input/Output)
device via shielded cables. Another is the so-called link system with PLC, in which analog signal is
converted to digital signal and is transmitted via coaxial cables or optical fibres.
“Analog output signal” means signals continuously transmitted from CCU to local control panels or
equipment to direct operational amount.
Electric operated valves and regulating valves for controlling pressure of pipe, and VFD for
controlling frequency of aerators or pumps, etc., are typical examples, which are controlled by
analog output signals. More specifically, there are electromagnetic valves and regulating valves used
to control pressure in the piping.
There are also aeration blowers or VFD (inverter) equipment used to control pump rpm.
One of the transmission systems for analog output signal connects directly to the I/O device of CCU
via shielded cables.
“Digital input signal” refers to a contact output signal generated and transmitted from local
equipment. For example, answer-back signal to express equipment conditions, alarm signal for
abnormal conditions and “remote / local” switch signal of local control panels are examples of
digital input signal. Contact signals are electronically converted to an appropriate series of zeros
and ones. Link systems with PLC are widely used for transmitting the signal, with which analog
signal is converted to digital signal and is transmitted via coaxial cables or optical fibres.
Digital output signal means contact output signal expressed “1 / 0” transmitted from CCU to an
auxiliary relay on the control center panel. For example, “on/off” signal for equipment is regarded as
digital output signal. Link systems with PLC are widely applied for transmitting the signal, with which
analog signal is converted to digital signal and is transmitted via coaxial cables or optical fibres.
The PLC is a blind device. It does not have any provision of displaying the plant status to the
operator, or to enter certain data like set points, or manual mode operation. An additional device is
needed for these provisions, to communicate with PLC, which will have a display to show the status
and also the means to enter set points. Such a unit is called Human Machine Interface (HMI).
• PC based system in which the computer acts as HMI as in Figure 6.21 overleaf.
6 - 36
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
A PLC is electronic equipment that senses inputs and takes the decision to change outputs
according to the set rules stored in the memory. It is primarily an electronic controller, housed in
industrial housing, which has logic programming function and can be an interface to
industrial devices.
6 - 37
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
Instrumentation facilities are established mainly based on feedback control in combination with feed
forward control in most STPs for controlling process variables such as temperature, water level,
pressure, flow rate, etc.
6.7 CABLES
The flow of power from transformer to switchgear and from there to starter and to motor and other
related equipment like capacitors are through power cables.
The size of the cable should be so selected that the total drop in voltage, when calculated as the
product of current and the resistance of the cable should not exceed 3%.
The following points should be considered when selecting the size of the cable:
• The current carrying capacity should be appropriate for the lowest voltage, the lowest power
factor and the worst condition of installation that is, duct-condition.
• The cable should also be suitable for carrying the short circuit current for the duration of the fault.
The duration of the fault should preferably be restricted to 0.1 sec. by proper relay setting.
• Appropriate rating factors should be applied when cables are laid in- group (parallel) and/or laid
below ground.
6 - 38
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
Among all the power consuming components, pumping installations consume a large amount
of energy in STPs. Need for conservation of energy, therefore cannot be over emphasized. All
possible steps need to be identified and adopted to conserve energy and reduce energy cost so that
sewerage charges can be kept as low as possible and gap between high cost of sewage treatment
and affordable charge to users can be reduced.
Some adverse scenarios in energy aspects are quite common in pumping installations as herein:
• Energy consumption is higher than optimum value due to reduction in efficiency of pumps.
• Operating point of the pump is away from best efficiency point (b.e.p.).
• Energy is wasted due to increase in head loss in pumping system, for instance, clogging of
strainer, encrustation in column pipes and encrustation in pumping main.
• Selection of uneconomical diameter of sluice valve, butterfly valve, reflux valve, column pipe, and
drop pipe, etc., in pumping installations.
• Energy wastage due to operation of electrical equipment at low voltage and/or low power factor.
Such inefficient operation and wastage of energy should be avoided to cut down energy cost. It
is therefore, necessary to identify all such shortcomings and causes, which can be achieved by
conducting methodical energy audit.
• Conduct thorough and in-depth energy audit covering analysis and evaluation of all equipment,
operations and system components, which have bearing on energy consumption, and identify the
scope for reduction in energy cost.
• Implement measures for conservation of energy. Energy audit as implied is auditing of billed
energy consumption and how the energy is consumed by various units, and sub-units in the
installation and whether there is any wastage due to poor efficiency, higher hydraulic or power
losses etc. and identification of actions for remedy and correction.
Scope of energy audit and suggested methodology includes the following, steps and processes:
6 - 39
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
• Calculated energy consumption taking into account rated efficiency and power losses in all
energy utilising equipment and power transmission system, such as conductor, cable,
panels, etc.
B. Conducting performance tests of pumps and electrical equipment if the difference between
actual energy consumption and calculated energy consumption is significant and taking follow up
action on conclusions drawn from the tests.
C. Taking up discharge test at rated head if test in B. above is not being taken.
D. Identifying the equipment, operational aspects and characteristics of power supply causing
inefficient operation, wastage of energy, increase in hydraulic or power losses etc. and evaluating
the increase in energy cost or wastage of energy.
E. Identifying solutions and actions necessary to correct shortcomings and lacunae in D. above and
evaluating cost of the solutions.
F. Carrying out economic analysis of costs involved in D. and E. above and drawing conclusions on
whether rectification is economical or otherwise.
G. Checking whether operating point is near the best efficiency point and whether any improvement
is possible.
H. Verification of penalties if any, levied by power supply authorities, such as penalty for poor power
factor, penalty for exceeding contract demand, and so on.
I. Broad review of the following points for future guidance or long-term measure:
• Suitability of pump for the duty conditions and situation in general and specifically from
efficiency aspects
• Suitability of ratings and sizes of motor, cable, transformer and other electrical appliances
for the load
Records are the key to an effective maintenance programme. Records can remind the operator when
routine O&M is necessary. They help ensure that schedules are maintained and needed O&M are not
overlooked or forgotten.
6 - 40
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
Records must be permanent, complete and accurate. Write entries clearly and neatly on data
sheets in ink. A pencil should never be used because notations can smudge or they can be
altered or erased.
Minimum record keeping that may be required for operations is listed below and shown in
Appendix C.6.1:
Review of operating records can indicate the efficiency of the plant, performance of its treatment
units, past problems, and potential problems.
Records can be used to determine the financial health of the utility, provide the basic data on the
system’s property and prepare monthly and annual reports.
Scheduled activities to ensure that an item of equipment is operating correctly and thereby avoid
any unscheduled breakdown and downtime.
Activities performed after one or more indicators show that the equipment is going to fail or that
equipment performance is deteriorating.
The vast majority of electrical maintenance should be predictive or preventive. This section
focuses exclusively on these activities. There are four cardinal rules to follow in any maintenance
programme:
• Keep it clean
Dirt build-up on moving parts will cause slow operation, arcing and subsequent burning.
Moreover, coils can short-circuit. Dirt will always impede airflow and result in elevated
operating temperatures.
6 - 41
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
• Keep it dry
• Keep it tight
• Keep it frictionless
Any piece of equipment or machinery is designed to operate with minimum friction. Dirt,
corrosion or excessive torque will often cause excessive friction.
Of the four cardinal rules, none is essentially electrical in nature. The failure of a bearing in a motor
can lead to an ultimate motor winding failure that is electrical, but the root cause of the failure could
have been mechanical.
The goal of any electrical preventive maintenance programme is to minimize electrical outages and
ensure continuity of operation.
Maintenance works can be classified as follows according to their inspection intervals. The results of
maintenance can be utilized for preventing possible faults or breakdowns of equipment in future.
• Routine maintenance
Routine maintenance consists of observation for signs of overheating, dirt, loose parts, noise and
any other signs of abnormalities. It will help grasping the state of electrical equipment.
• Periodic maintenance
• Detailed examination
A wide, variety of instruments are used to maintain electrical systems. These instruments
measure current, voltage and resistance. They are used not only for troubleshooting, but also for
preventive maintenance as well.
These instruments may have either an analog readout, which uses a pointer and scale, or a digital
readout, which gives a numerical reading of the measured value.
6 - 42
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
* Details of the maintenance tasks of the marked equipment above are given in Appendix B.6.2.
(Legend)
6.10.2.1 Multimeter
A multimeter is used to measure voltage and low levels of current in a live system and continuity in a
switched-off system. There are several types available in the market. A digital multimeter and an analog
multimeter are shown in Figure 6.23. They are designed to be used on energized circuits and care
must be exercised when testing.
6 - 43
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
By holding one lead on ground and the other on a power lead, a user can determine if power is
available, and also can tell if it is AC or DC, the intensity or voltage (1, 10, 220, 480, and so on) by
testing the different leads. A clamp-on multimeter can measure larger currents typical in a motor.
• Use a multimeter or other circuit tester to determine if the circuit is energized, or if voltage is off.
This should be done after the main switch is turned off to ensure that it is safe to work inside the
electrical panel. Always be aware of the possibility that even if the unit is off, the control circuit
may still be energized if the circuit originates at a different distribution panel.
• Check with a multimeter before and during the time the main switch is turned-off as a double
check. This procedure ensures that the multimeter is working and that the users have good
continuity to the tester.
• Use a circuit tester to measure voltage or current characteristics to a given piece of equipment for
checking whether the circuit is “alive” or not. Switches can fail and the only way to find out that a
circuit is dead is to test the circuit.
• In addition to checking for power, a multimeter can be used to test for open circuits, blown fuses,
single phasing of motors, grounds and many other uses.
The clamp-on meter measures the current or amps in the circuit as shown in Figure 6.24.
It is used by clamping the meter over only one of the power leads to the motor or other apparatus and
taking a direct reading.
Therefore, the measurement by the clamp-on meter is a safe method in a high-current circuit.
Each lead in a three-phase motor must be checked.
A megger or megohmmeter is used for checking the insulation resistance of motors, generators,
feeders, bus bar systems, grounds, and branch circuit wiring. This device actually applies a DC test
voltage, which can be as high as 5,000 volts, depending on the megohmmeter selected.
6 - 44
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
Figure 6.25 shows a hand-held that applies 500 volts DC and is particularly useful for
testing low-tension motor insulation.
Battery-operated and instrument style meggers are also available in both analog and digital
models. If a low reading is obtained, disconnect motor leads from power or line leads.
A low reading in the megger for motor generally indicates that the motor winding insulation has
broken down. If this reading is low, the wiring to the motor is defective.
Motors and wiring should be subjected to megger test at least once a year or preferably, twice a year.
The readings taken should be recorded and plotted to determine the deterioration of insulation and
predict its breakdown.
When the electrical equipment is installed in housings, they may be charged against the ground.
Therefore, they should be connected with earth (referred to as “earth”) to reduce the potential
difference between the terminal and the earth to as low a value as possible (ideally 0 volt).
A. Prevent electric shock: Discharge any electricity charged in equipment housing due to electrical
insulation failure or a transformer breakdown to prevent shock; and
B. Prevent breakdown of loaded equipment: Connect a neutral line on the load side of transformer
with earth and prevent high voltage on the power source side from intruding into the load side in
case of transformer fails so as to protect the loaded equipment
Value of ground resistance is depends considerably on the soil to be earthed, and the smaller the
resistance, the better. Ground resistance testers are devices to measure the stated resistance when
the circuit is earthed. Testers with measurable range from 0 to 1,000 ohms are widely used.
6 - 45
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
• Always refer to manufacturers manual for O&M and drawings for frequency of testing, lubrication,
replacement of any component and follow all these.
• When operating electrical equipment, follow the operational procedures, confirm the purposes of
the operation, and predict the result of the operation
• When overheat, abnormal noise, or vibration, etc, is detected during inspection, report the
condition to the person in charge of electrical work
• When overheat, abnormal noise, or vibration, etc, is detected during inspection, stop the
equipment and investigate the causes if necessary.
• Always keep the surrounding of electrical equipment tidy and clean. Never allow outsiders to
enter the electrical equipment site.
6.10.4 Rehabilitation
If the equipment in the electrical facility is old, frequent outages and high maintenance and repair
costs are likely to occur. If some of the equipment is beyond repair, breakdowns lead to long and
extensive power outages in the STP.
To prevent such occurrences, functional degradation of electric equipment and causes for
breakdown and stoppages should be tracked at an early stage and repaired. Causes of fault also
follow a certain trend. Training should be imparted on predicting faults beforehand, so that measures
and repairs can be implemented.
Spare parts and tools should be kept ready on site so that repairs can be carried out. Inventory of
spare parts and tools should be confirmed and the required number should be stored.
6 - 46
CHAPTER 6: ELECTRICAL AND
Part B: Operation and Maintenance INSTRUMENTATION FACILITIES
For reconstruction of electric facilities, plans should be formulated; therefore, scheduled O&M should
have been implemented.
Items to be studied for planned reconstruction are whether abnormalities exist from routine
inspection records, data, periodic inspections and repair records and a judgement of the condition
of equipment.
Analyse collected and accumulated data, and understand the long-term deterioration trend of
equipment.
6.11 TROUBLESHOOTING
6.12 SUMMARY
The primary function of electrical system in sewerage is to receive power from outside, transform
it and distribute it stably to each facility. The instrumentation system also plays an important role in
indicating operating conditions.
For realizing these functions properly, the electrical system requires periodic inspection and
maintenance for early detection of abnormal conditions. The instrumentation system should be
inspected and adjusted regularly so that it can provide correct readings at all times.
6 - 47