PDF Alarms

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 38

FOPX Separation System

Alarms and Fault Finding

Product No. 1762661-45


1762764-06
1762765-06
1762766-05

1763054-05
1763056-06
1763057-06
1763058-05

Printed Jan 1995


Book No. 1810034-02 V1

Alfa Laval Marine & Power


Alfa Laval reserve the right to make changes at any time without
prior notice.
Any comments regarding possible errors and omissions or
suggestions for improvement of this publication would be
gratefully appreciated.
Copies of this publication can be ordered from your local Alfa
Laval company.

Published by: Alfa Laval Separation AB


Marine & Power Oil Treatment Division
S - 147 80 Tumba
Sweden

© Copyright Alfa Laval Separation AB 1995. Printed in Sweden.


Contents

1 Scope 1 4 Alarm Tests 25

2 EPC Signs 3 5 Test Program 27

3 Alarms 5 5.1 How to Start the Test


3.1 Alarm Functions 5
Program 27

3.2 Alarm Reset 6 5.2 Lamp Test 28

3.3 Alarm Survey 7 5.3 How to Activate Different


Parts of the Test Program 28
3.4 LED Alarms and Fault
Finding 8 5.4 Functions in the Test
Program 29
3.4.1 High Oil Pressure 8
3.4.2 Low Oil Pressure
(Low Flow) 9
3.4.3 Sludge Discharge Failure 10
3.4.4 Water Transducer Fault 11
3.4.5 Emergency Stop 12
3.4.6 Vibrations (Option) 13
3.4.7 Heater Fault 14

3.5 LED and Display Alarms and Fault


Finding 15
3.5.1 High or Low Oil Tempera-
ture (Option) 15
3.5.2 Temperature Sensor Error
(Option) 16

3.6 Display Alarms and Fault Finding 17


3.6.1 Communication Error 17
3.6.2 Processor Fault 18
3.6.3 Programming Error 19
3.6.4 Power Failure 20
3.6.5 Temperature Deviation 21
3.6.6 ALCAP Alarms 22
3.6.7 Other Alarms 23
1 Scope

The alarms, alarm tests and the test program


are valid for the following separation systems:
FOPX 605
FOPX 609
FOPX 610
FOPX 613

1
2 EPC Signs

The signs to the control unit for the FOPX


separation systems are shown in this chapter.

P000881A
Monitoring functions

P000891A

Monitoring functions (Options)

3
P000991A
Output signals

P000641A

Operating symbols
3 Alarms

3.1 Alarm Functions


The alarm system is designed to ensure that
the separation system always remains in a safe
state. There are two different types of alarm
functions:
 Sensor-related alarm functions are
indicated by light emitting diodes (LEDs)
on the EPC-400.
 Display-related alarm functions are
indicated on the EPC-400 display. When
any of the displayed alarm functions are
activated the left digits start flashing and
the right digits are steadily lit.
If there is more than one alarm at the same
time, the EPC-400 will display the alarm with
the highest priority first and then the next
alarm, and so on in priority order.

G0442011

An activated alarm condition is identified either by an alarm LED (to the left in
the picture) or an alarm code on the display together with the main alarm LED
(to the right in the picture).

5
3.2 Alarm Reset
1. Acknowledge the alarm signal by
pressing the alarm push-button.
The flashing light then changes to steady.

G001645A
2. Remedy the cause.
3. Reset the alarm function by pressing the
alarm push-button a second time.
The LED will turn off.

G001647A
It is possible to reset the system without
remedying the cause, but the alarm signal will
be repeated.

NOTE

Never return to the EPC-400 control


unit to acknowledge or reset an alarm
if it by any means can be hazardous.
FOPX Alarms and Fault Finding 3 Alarms

3.3 Alarm Survey


LED
alarms Display Alarm function Page
alarms

"High Oil Pressure" 8

"Low Oil Pressure (Low Flow)" 9

"Sludge Discharge Failure" 10

"Water Transducer Fault" 11

"Emergency Stop" 12

“Vibrations” (Option) 13

"Heater Fault" 14

“High or Low Oil Temperature”


15
(Option)

“Temperature Sensor Error”


16
(Option)

"Communication Error" 17

"Processor Fault" 18

"Programming Error" 19

"Power Failure" 20

"Temperature Deviation" 21

"ALCAP Alarms" 22

“Other Alarms” 23

7
3.4 LED Alarms and Fault
Finding

3.4.1 High Oil Pressure

S001801A

Cause Corrective action

Regulating valve, RV4, or other valves, downstream Open or regulate RV4, or other valves, to correct
throttled or closed. back pressure, normally about 1.5 bar (150 kPa).

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode (PS41) flashes. Alarm diode off.

Change over valve (V1) is set for oil recirculation. V1 is set for oil feed to separator.
3.4.2 Low Oil Pressure (Low Flow)

S001802A
Causes Corrective actions

Too low oil feed. Check the oil feed pump.


Adjust the oil flow.

Strainer before the oil feed pump is clogged. Clean the strainer.

Oil feed pump has stopped. Check the oil feed pump.

Change over valve (V1) is in recirculation position. 1. Check the air supply to the solenoid valve block
air (MV1).
2. Check MV1.
3. Check V1.

Too low back pressure. Increase the back pressure with regulating valve
RV4. The correct back pressure is normally about
1.5 bar (150 kPa).

Bowl opened accidentally during operation. Check the opening water valve (MV15) for leakage.
See “Separator Manual”.

Leakage from bowl. See “Separator Manual”.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode (PS42) flashes. Alarm diode off.

V1 is set for oil recirculation. V1 is set for oil feed to separator.


3.4.3 Sludge Discharge Failure

I000682A
Causes Corrective actions

No or very low opening water supply. Check the water supply system.

Opening water valve (MV15) broken. Check MV15.

No signal from low oil pressure switch (PS42) at dis- Check PS42.
charge.

Separator operating water system not working. 1. Check the separator by manually open MV15.
2. Dismantle and check the operating water
system. See “Separator Manual”.

N.B. This alarm is activated after two attempts to discharge, within the same discharge cycle, have
failed.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode flashes. Alarm diode off.

The stop sequence is initiated. 1. If the power has been off during more than
approximately 10 minutes the separator bowl
must be stopped and manually cleaned before
restart.
2. The separator and the EPC program has to be
restarted.
3.4.4 Water Transducer Fault

S000261A
Causes Corrective actions

Loose connection between transducer test circuit Check connections.


board and oscillator.

Faulty oscillator unit or faulty EPC control module. Check supply voltage in the MT4 on terminal 3 - 4
(20 V DC).
About every 5:th second the voltage at terminal 4 - 5
(20 VDC) will drop for approx. 0.5 second:
 If voltage drop: replace the oscillator unit.
 If no voltage drop: replace the EPC control
module.
For more information about the interconnections, see
“System Reference”.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode flashes. Alarm diode off.

Change over valve (V1) is set for oil recirculation. V1 is set for oil feed to separator.
3.4.5 Emergency Stop

S003911A
Cause Corrective actions

Emergency stop button has been pushed. 1. Remedy the cause why the emergency stop
button was pushed and then reset it.

Automatic actions at alarm Automatic action after alarm reset

Main alarm flashes. The alarm function can not be reset by pushing the
Alarm diode flashes. alarm reset button.
The separator is stopped and the heater is off.
Oil feed is on for further 3 minutes through the heater 1. Reset the alarm by switching the power off and
and separator. on.
Bowl closing water supplied for 3 minutes. 2. Restart the separator.
3. Restart the EPC program.

NOTE

The separator bowl must be manually


cleaned before starting up again.
3.4.6 Vibrations (Option)

S000111A
Cause Corrective actions

Vibration switch activated. Remedy the cause. See “Separator Manual”.


Separator bowl out of balance. Check the vibration switch setting.

Automatic actions at alarm Automatic action after alarm reset

Main alarm flashes. The alarm function can not be reset by pushing the
Alarm diode flashes. alarm reset button.
Separator is stopped.
Oil feed is on for a further 3 minutes through the 1. Reset the alarm by switching the power off and
heat- er and separator. on.
Bowl closing water supplied for 3 minutes. 2. Restart the separator.
3. Restart the EPC program.

NOTE

The separator bowl must be manually


cleaned before starting up again.
3.4.7 Heater Fault

I000221A
N.B. Heater fault is only activated if the heater is controlled by the EPC-400.

Cause Corrective action

Oil flow stopped or temperature switch tripped in an If oil flow stopped, investigate the cause. See correc-
installed Heatpac heater. tive actions for PS42.
Check the flow switch on the Heatpac heater.
If temperature switch tripped, investigate the temper-
ature switch setting. If OK check the heater for clean-
liness.

Clogged heater. Clean heater.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode flashes. Alarm diode off.

Change over valve (V1) is set for oil recirculation. V1 is set for oil feed to separator.

Heater switched off. Heater switched on.


3.5 LED and Display
Alarms and Fault
Finding

3.5.1 High or Low Oil


Temperature (Option)
S000121A

S000141A
N.B. Also applicable to TT2 temperature sensor, if fitted.

Causes Corrective actions

Low temperature alarm when: Investigate the reason and remedy it.
- clogged heater
- insufficient steam supply
- faulty steam trap
- faulty steam supply valve
- electric fault (tripped fuse)

High temperature alarm when: Investigate the reason and remedy it.
- faulty steam supply valve
- electrical control system out of function

Set point (P7) changed or the alarm limits are too 1. Adjust the parameters.
close to the set point. P5 = max. temp
P6 = min. temp
P7 = set point.
See “Parameter List”.
2. Check the temperature control loop.

Steam control valve (SRV1) too far open or closed. 1. Check and adjust the SRV1 function.
2. Check the EPC output functions.

Low temperature alarm when the temperature in- Check the heater and parameter P41, See “Parame-
creases too slowly, during the start. ter List”.

Pt 100 temperature signal faulty. Check the Pt 100 temperature sensor.

N.B. The current temperature is indicated when the alarm is acknowledged. To find the appropriate
temperature sensor reading, push the alarm reset button twice 1C (1F) = TT1, 2C (2F) = TT2. For
more information, see “Operating Instructions”.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode and displayed value flashes. Alarm diode off and display returned to normal.

Change over valve (V1) is set for oil recirculation. V1 is set for oil feed to separator.

Heater is switched off at high temperature (if heater Heater is switched on (if heater is controlled by EPC-
is controlled by EPC-400). 400).
3.5.2 Temperature Sensor Error
(Option)
S000121A

S000131A
N.B. Also applicable to TT2 temperature sensor, if fitted.

Causes Corrective actions

Temperature sensor is incorrectly connected. Check the temperature sensor by the test program,
see ‘‘Analog inputs’’ on page 32 in the chapter "Test
Program".

Temperature sensor loop is open or short-circuit. Check the connections.

Temperature sensor cables are too close to power Check the cables between the temperature sensor
ca- bles. and EPC-400.

N.B. Push the alarm reset button to find appropriate process value reading.
1C (1F) = TT1, 2C (2F) = TT2. If both temperature sensors are fitted, alarm A6 is also activated.

Automatic actions at alarm Automatic actions after alarm reset

Main alarm flashes. Main alarm off.

Alarm diode and displayed value flashes. Alarm diode off and display returned to normal.

Change over valve (V1) is set for oil recirculation. V1 is set for oil feed to separator.
3.6 Display Alarms and
Fault Finding

3.6.1 Communication Error

S000151A

Alarm code Cause Corrective actions

Communication error between front 1. Check by measurement the


and rear circuit board. fuses A1:F2 (front board),
A2:F2 and A2:F3 (rear board).
(See “Component Description,
EPC-400 Control Unit”).
2. Replace the control module.
I001105A

Automatic action at alarm Automatic actions after alarm


reset

Main alarm flashes. Main alarm off.


Display flashes. Display normal.
3.6.2 Processor Fault

S000161A
Alarm codes Causes Corrective actions

Internal RAM error. Replace control module.


I001091A

External RAM error. Replace control module.


I001092AI001106A

E2 RAM error. Replace control module.

Program error. Replace control module.


I001093A

Mode switch error. Check that the mode selector is in the correct position.
I001096A

A / D (Analog / Digital)
Check
conversion
the fuseerror.
A1:F2 (front board) If the fuse is correct, replace the control modu
I001094A

Calibration error. Ask for service or replace the con- trol module.
I001095A

Automatic actions at alarm Automatic actions after alarm


reset

Main alarm flashes. Main alarm off.


Display flashes. Display normal.
3.6.3 Programming Error

S000171A
Alarm code Cause Corrective action

Programming mode too long Change the mode selector to the


(more than 30 minutes without “L” (Local) position and when
programming during this time). appropriate, return to the
“P” (Programming) position and
continue with programming.
I001108A

Automatic actions at alarm Automatic actions after alarm


reset

Main alarm flashes. Main alarm off.


Display flashes. Display normal.
3.6.4 Power Failure

Alarm codes S000181A Causes Corrective actions

Check the power


Power supply.
failure.
I001103A

If the power has been off during more than approximately 10 minutes the separator bowl must be stopped and
Restart the heater, separator and EPC program.

CheckPower
the supply
power supply.
frequency too high (more than + 5%).1
I001104A

If the power has been off during more than approximately 10 minutes the separator bowl must be stopped and
Restart the heater, separator and EPC program.

Automatic actions at alarm Automatic actions after alarm


reset

All outputs are off.

Only valid for alarm A4-1: Only valid for alarm A4-1:
Main alarm diode and display start Main alarm off.
to flash when power returns. Display indicates “OFF”.

Only valid for alarm A4-2: Only valid for alarm A4-2:
Main alarm flashes. Main alarm off.
Display flashes. Display normal.

1. The frequency deviation must be repeated or be continuous during the alarm delay time before an alarm is
activated.
3.6.5 Temperature Deviation

S000191A
Alarm code Cause Corrective actions

Temperature deviation alarm At commissioning


(difference between TT1 and TT2 Check if the distance between sen-
is more than 30 °C/54 °F). sors is too great.
System in operation
Check the temperature sensors.
I001109A

Automatic actions at alarm Automatic actions after alarm


reset

Main alarm flashes. Main alarm off.


Display flashes. Display normal.

N.B. Push the alarm reset button to find the appropriate process value reading 1C (1F) = TT1,
2C (2F) = TT2. For more information, see “Operating Instructions”.
3.6.6 ALCAP Alarms

S000211A
Alarm codes Causes Corrective actions

High water transducer (MT4) value (above 400):


I001111A

High water content in oil. Check the oil system for water leak- age.

WaterClean
transducer
the liquid-wetted
dirty inside.surfaces of water transducer. See “Component Description, Water

Low water transducer (MT4) value (below 100):


I001112A

Open circuit in the MT4. Check connections in control unit and transducer.
Check cables for damage.

Check the cable connection.


Bad connection between oscillator unit and electrode.
Tighten oscillator unit to the electrode.

ALCAP stand-by more than 24 hours. The reason for stand-by mode must be checked!
I001113A

Try then to operate the system nor- mally.

PROM and/or RAM fault. Replace control module.


I001115A

No triggering by water transducer signal at twoCheck


sludgethe displacement
discharges water supply, including parts in separator.
in a row.
I001181A

Check for bowl leakage.

Automatic actions at alarm Automatic actions after alarm


reset

Main alarm flashes. Main alarm off.


Display flashes. Display normal.
3.6.7 Other Alarms

S000201A
Alarm codes Causes Corrective actions

Extra alarm. 1. Check the connected external


function.
2. Check the jumper at terminal
XC-X7:1 (when extra alarm
not used).
I001121A

Low pressure signal (PS42) faulty Check the pressure switch.


at start. Circuit should be open.
I001122A

Automatic actions at alarm Automatic actions after alarm re-


set

Main alarm flashes. Main alarm off.


Display flashes. Display normal.

The start of the timer sequences is


blocked (is only valid for alarm
A9-2).
4 Alarm Tests

Use the following guide for testing alarm


functions by activating them. Alarms are
provoked by one or more actions (A, B and so
on) as shown in the right column, however,
certain alarm functions can not be tested
without being disconnected.
N.B. If the alarm functions are to be
disconnected in the control unit, be
careful to avoid a short-circuit.
The recommendation is to test the alarms
every 3 months.
LED alarm Display alarm Function Sensor Actions to provoke an alarm

High oil pressure PS41 Increase back pressure.

Low oil pressure (low PS42 A. Stop oil feed pump.


flow)
B. Change V1 position by
reducing air pressure.
C. Reduce the back pressure.

Sludge discharge failure PS42 1. Disconnect hose for opening


water (MV15).
2. Initiate a sludge discharge.

Water transducer fault MT4 Disconnect cable to XE:4 (the test


signal to MT4).

Emergency stop XS2 Press the emergency stop button.

Vibrations (option) XS1 Tap on the vibration switch three


times within one second.

Heater fault - 1. Start the heater.


2. Disconnect cable to X9:3.

25
LED alarm Display alarm Function Sensor Actions to provoke an alarm

High or low oil tempera- TT1 A. Remove sensor from pipe and
ture (option) put into hot/cool liquid.
B. Change alarm limit parameters
(P5 = max temp., P6 = min.
temp.) in relation to actual
temperature. For more
information see “Parameter
List”.
N.B. Reset the parameter values
after test.

Communication error - Remove fuse A2:F3 (rear board).

A / D conversion error - Remove fuse A1:F2 (front board).

Programming error - Leave the mode selector switch in


position P for 30 minutes.

Power failure - Switch the power to the EPC off and


on when it is in operation.

Temperature deviation TT1 - TT2 Remove one sensor from pipe to


cool off or be heated up (temp. diff.
more than 30 °C/54 °F).

High water transducer MT4 Touch the central screw in the MT4
(MT4) value (above connection box.
400).

Low water transducer MT4 Disconnect cable to XE:3 in EPC.


(MT4) value (below
100).

Insufficient amount of MT4 A. Change parameter 70 to a low


displacement water value (e.g. 5 seconds) and
initiate discharge cycle twice.
B. Close displacement water
supply and wait 2 discharge
cycles.
The amount of displacement water
supply is checked every 2nd dis-
charge.

Extra alarm - A. Activate appropriate sensor.


B. Disconnect cable X7:1.

PS42 faulty at start PS42 With the EPC in off mode put a jump-
(Circuit should be open) er between XC- X7:4 and push the
start button.
5 Test Program

The EPC-400 control unit has a test program,


for testing of input and output functions,
memory etc.
This test program should be run when the
installation is made and whenever there is a
need for it, for instance, during fault finding.

5.1 How to Start the Test


Program
N.B. The test program is only to be used
when the separation system is out of
operation.
To run the test program, do as follows:
1. Open the control unit door.
2. Switch the power off and the mode
selector in any position (R, L or P).
3. Press simultaneously the discharge and
the alarm push-buttons, and keep them
pressed.
4. Switch the power on.
5. Release the discharge and alarm push-
buttons when the test program has started.
P000191A

27
5.2 Lamp Test
The test program starts with a lamp test.
1. The display lit with power on.
2. There are two ways to check the lamps:
• Each LED and display segment
individually lit (see the picture).
• Each group of LED:s and display

G001142A
segments lit.

Push the button 2 (see the figures in the


picture below) to switch between the two
modes.

5.3 How to Activate


Different Parts of the
Test Program TT2

Use the push-buttons to activate different TT1MT4 FS4

parts of the test program (see the figures 1, 2


and 3 in the picture). XT1

1. Push button 1 to step from function 1 to


function 2 etc. in the test program. XS1
FOPX

It is not possible to step backwards.


Wait until the function is activated before
pushing the button again.
2. Push button 2 to step forward within each
function in the test program, for instance
from function 1.1 to 1.2.
P000181A

3. Push button 3 to activate or deactivate


output terminal (function 5 and 6). V1 MV10

V5

MV16
MV15

EPC-400
FOPX
FOPX Alarms and Fault Finding 5 Test Program

5.4 Functions in the Test


Program
1. Memory

I000941A
Function

1.1 PROM

1.2 Internal RAM


Memory correct
1.3 External RAM
I000951A

1.4 EEPROM

Memory fault

2. Digital inputs

Function Terminal Unit Correct


value

2.1 Low flow X7:4-XC PS42 0


I000941A

2.2 High pressure X7:3-XC PS41 1

2.3 Not in use


Circuit open
2.4 Not in use

2.5 Emergency stop or Vibration X8:4-XC XS2 or 1


I000961A

switch XS1
Circuit closed 2.6 Not in use - -

2.7 Start or stop EPC X8:2-XC Remote 0


switch

2.8 Start or stop heater X8:1-XC Remote 0


switch

29
3. Digital inputs

Function Terminal Unit Correct


value

3.1 Alarm acknowledge or Reset X9:4-XC Remote 0


switch
I000941A

3.2 Heater fault X9:3-XC 1


Circuit open 3.3 Sludge discharge X9:2-XC Remote 0
switch
I000961A

Circuit closed

4. Mode selector

Function

4.1 Remote (R) position


I000971A

4.2 Local (L) position

4.3 Program (P) position


Remote position
I000981A

Local position
I000991A

Program position
5. Digital outputs

Use push-button 3 to activate or deactivate


each output (see ‘‘How to Activate Different
Parts of the Test Program’’ on page 28).
N.B. Corresponding green LED is not lit.
Function Terminal Unit

5.1 Oil feed X4:4-XD MV1/V1


I000941A

5.2 Water drain X5:1-XD MV5

5.3 Displacement or sealing water X5:2-XD MV10


Circuit deactive supply

5.4 Opening water X5:3-XD MV15


I000961A

5.5 Closing water X5:4-XD MV16


Circuit active 5.6 Steam shut-off valve or Heatpac X6:1-XD -
fixed load

5.7 Steam valve decrease or X6:2-XD -


Heatpac fixed load

5.8 Steam valve increase or Heatpac X6:3-XD


fixed load

6. Digital outputs

Use button 3 to activate or deactivate each


output. (See ‘‘How to Activate Different
Parts of the Test Program’’ on page 28.)
N.B. Corresponding green LED is not lit.
Function Terminal Unit

6.1 Heatpac variable load X6:4-XD


I000941A

6.2 Heatpac alarm blocking during X4:2-XD K15 in


start power
Circuit deactive unit

6.3 Not in use


I000961A

6.4 Separator stop X1:1-2

Circuit active 6.5 Not in use

6.6 Remote/common alarm X2:1-2

6.7 Blocking vibration switch X2:3-4 XS1

7. Not in use
8. Analog inputs

To simulate the temperature sensor elements


(Pt 100) in 8.1 and 8.2, a resistor can be used.

P000111A
Separate plug connectors with appropriate
resistors are included in the test module kit.
Resistor Ref.temp Display
reading
110  25 °C/77 °F 60
140  104 C/219 °F 215

The normal value on the display for function


8.1 and 8.2 should be 60 – 215. Outside the
range 42 – 233 indicates a fault. Value 000
(or a very low value) or 255 indicates a
serious fault.
A normal value for function 8.3, Reference
4 V should be 195 – 215.
The table below shows how to find the fault.
Causes to the alarm “Temperature sensor error”
(the display shows the alarm code “EEE”)

Function Terminal Unit Fuse A1:F2 A/D conver- Input open Input short
blown sion faulty circuit

8.1 Temperature sensor X10:1-2-3 TT2 000 000 255 000


for control

8.2 Temperature sensor X11:1-2-3 TT1 000 000 255 000


for alarm

8.3 Reference 4 V 000 000 195 – 215 195 – 215

8.4 Not in use

For instance, if the display shows “000” for


function 8.1, 8.2 and 8.3, it must be either a
blown fuse or A/D converter fault. Check it in
this order:

1. If the fuse is blown, replace it.


2. If the fuse is correct, replace the control
module.
9. Serial communication

Function Terminal Unit

I000941A
9.1 Not applicable X14:1-3
(The display will show an E).
Circuit correct
9.2 RS 232 C X14:1-3
Measure -10 to -12V DC
on X14:1-3 (Circuit correct).
I000951A

Circuit fault

N.B. Disconnect the communication cable


and put a jumper between X14:3-4
before the test is carried out.

P000121A
N.B. After the test, remove the terminal
jumpers and connect communication
cables.
10. Test of EPROM (rear circuit board)

I000941A
11. Test of internal RAM in CPU
(rear circuit board Circuit correct

12. Test of external RAM in CPU (rear


circuit board)

I000951A
13. Test of IC 8255 I/O port (rear circuit
board) Circuit fault

14. Low reference analog input


(internal)

A value between 42 and 66 is displayed,


when it is correct.

15. High reference analog input


(internal)

A value between 220 and 310 is displayed,


when it is correct.

16. Transducer signal (internal)

The display shows 100 ±  with oil in WT


200 and 55 ± 10 with air, when it is correct.

17. Not in use

18. Not in use

You might also like