Power System Protection Part - 1 DR - Prof.Mohammed Tawfeeq

Download as pdf or txt
Download as pdf or txt
You are on page 1of 59

Power System Protection Part – 1 Dr.Prof.

Mohammed Tawfeeq

Power System protection


Introduction

· Protection is the art or science of continuously monitoring the


power system, detecting the presence of a fault and initiating the
correct tripping of the circuit breaker.

· The objectives of power system protection are to :


— Limit the extent and duration of service interruption
whenever equipment failure, human error, or adverse natural
events occur on any portion of the system
— Minimize damage to the system components involved in
the failure and Prevention of human injury

· Protection engineering concerned with the design and operation


of "protection schemes".

· Protection schemes are specialized control systems that monitor


the power system, detecting faults or abnormal conditions and
then initiate correct action.

· In this course the power system is considered as all the plant and
equipment necessary to generate, transmit, distribute and utilize
the electric power.

2
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Secondary systems in a Power system


· Protection

· Auto control for voltage, frequency, reactive power compensation, power flow,
network configuration and stability

· Metering for billing, operational control and statistical data

· Local manual control (plant status, voltage level reactive power support,
network configuration)

· Remote manual control via communications links (SCADA)

· Plant condition monitoring and alarming (temperature,


malfunction, maintenance need, operating duty)

· Communications infrastructure

· Instrument transformers - current and voltage transformers

3
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Protection against faults and abnormalities

Faults :
The principal electrical system faults are short circuits and overloads.
Short circuits may be caused in many ways, including failure of insulation
due to excessive heat or moisture, mechanical damage to electrical
distribution equipment, and failure of utilization equipment as a result of
overloading or other abuse.
Short circuits may occur between two-phase conductors, between all phases
of a poly-phase system, or between one or more phase conductors and
ground. The short circuit may be solid (or bolted) or welded, in which case
the short circuit is permanent and has relatively low impedance. The main
types of faults in a power system are:

■ Short-cir cuit faults (3Ф, 2 Ф, Ф g, 2 Ф g)

■ Open -cir cuit faults (open condu ct or)

■ Complex faults (inter -circuit, broken conducto r, cross -country etc)

■ Inter -turn faults in windings

Abnormalities:

■ Real power deficit - underfrequency


■ Power swings
■ Overload and excessive operating temperature
■ Power frequency overvoltage or undervoltage
■ Underexcitation of synchronous machines
■ Overfluxing of power transformers
■ Asynchronous operation of synchronous machines
■ Overfrequency
■ Mechanical defects i.e. leaking oil, tap changer mechanism faults .

4
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Types of Faults

· Short circuit type faults (solidly earth fault)

5
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

· Faults in Windings

6
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

· Single-Phase-Ground: 70 – 80 %
· Phase-Phase-Ground: 17 – 10 %
· Phase-Phase: 10 – 8 %
· Three-Phase: 3 – 2 %

Causes of Short-Circuit Faults

· Insulation breakdown due to inherent weakness Lightning

· Birds and animals bridging insulators

· Dig-ups for underground cables

· Poles collapsing

· Conductors breaking

· Vehicle impact

· Wind borne debris

· Incorrect operation by personnel

· Etc

7
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Effects of Short- Circuit Type Faults

■ Large or very large currents can flow through parts of the


network - thousands or tens of thousands of Amps can be
involved

■ These large currents can only be allowed to flow for a very


short time otherwise equipment and generators would be
damaged, most likely terminally - allowable short-circuit
current flow duration could range from as short as 10
milliseconds up to say 3 seconds.

■ Arcs, sparking and the heating effect of short-circuit


currents can start fires involving non-electrical assets /
property

■ Very large mechanical forces can be caused by short -


circuit currents which have potential to break or damage
equipment

■ Electric current can "escape" from the network conductors


and flow through paths where they could create a hazard to
people or livestock and cause damage to non-electrical
assets/property

8
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

· between load (normal) and fault


(abnormal) conditions

· Not be confused by non-damaging transient


conditions

· Be - coordinate with other protection


systems

· enough to prevent damage and hazards - but


not too fast

· Have no " " i.e. unprotected zones


· High degree of and

· Secure against incorrect operation

· Should not restrict rating of primary plant and


equipment

· Should be

9
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

The isolation of faults and abnormalities requires the application of


protective equipment that senses when an abnormal current flow exists and
then removes the affected portion from the system. The primary protective
equipment components are shown in the following figure:

PR Protection Relay
CB Circuit Breaker
Equip Protected Item
CT Current Transformer
VT Voltage Transformer
DC Aux DC Auxiliary supply
HMI Man-machine interface
PCL Communications Link
Tr CB trip coil

The two primary protective equipment components used in the isolation of


faults and abnormalities are circuit breakers, and protective relays.

1
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Elements of a Protection System

1 4

2.1
5
2 A D

2.2
2.4 mP
F.A.
2.3
3

1 – CT or VT , 2- Relay 3- TC 4- CB 5- DC supply

F.A. = Fault Alarm


Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Elements of a Protection System


1

n The function of transducers (usually CT and VT) is to


provide current and voltage signals to the relays, to
detect deviations of the parameters watched over .

2.1

2 A D

n Relays are the logic 2.2


elements which 2.4 mP
initiate the tripping F.A.
and closing 2.3
operations. 3

2
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Elements of a Protection System


1 4

2 n Circuit breakers
isolate the fault by
interrupting the
current.

n Tripping power, as
well as power 1 4
required by the
relays, is usually
provided by the
station battery
because is safer 2.1
than the ac faulted
system.
2 A D
5
2.2
2.4 mP
F.A.
2.3
3

3
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Protective Relays

What is a Relay?
· Device which receives a signal from the power system and
determines whether conditions are "normal" or "abnormal"
(measuring function)-

· If an abnormal condition is present, relay signals circuit breaker


to disconnect equipment that could be damaged (Switching or
signaling function)

· "Relays" signal from system to circuit breaker.

What is the Purpose of the Relay?

The purpose of the protective relaying systems is to isolate only the faulty
component of power system.
Relaying equipments are classified into two groups:
1. Primary relaying equipment.
2. Back-up relaying equipment.
Primary relaying is - the first line of defense for protecting the equipments.
Back-up protection relaying works only when the primary relaying
equipment fails (they are slow in action).

4
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Functional Diagram of Relaying

5
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Desirable Relay Characteristics

■ Speed (1/60 sec)


* Minimizes damage from current
* Maximizes power transfer during normal conditions,
stability

■ Security
* Relay should not cause circuit breaker to open during
normal conditions

■ Dependability
* Relay should cause circuit breaker to open
during abnormal conditions

■ Sensitivity
n Ability of a relay to detect all faults for the expected
limiting system and fault conditions

■ Selectivity
nAbility of a relay system to discriminate between

faults internal and external to its intended


protective zones.

6
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

7
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Classifications of Relays

Classification of Relays
Protection relays can be classified in accordance with the function which they
carry out, their construction, the incoming signal and the type of protection.

1. General function:
Auxiliary.
Protection.
Monitoring.
Control.

2. Construction:
· Electromagnetic.
· Solid state.
· Microprocessor.
· Computerized.
· Nonelectric (thermal, pressure ......etc.).

3. Incoming signal:
· Current.
· Voltage.
· Frequency.
· Temperature.
· Pressure.
· Velocity.
· Others.
4. Type of protection
· Over current.
· Directional over current.
· Distance.
· Over voltage.
· Differential.
· Reverse power.
· Other.

8
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Definitions:

■ Normally open contact ( N/O): is one which is open when the relay is not
energized.
■ Normally closed contact (N/C): is one which is closed when the relay is not
energized.
■ Operating force or torque: that which tends to close the contacts of the relay.

■ Restrain force or torque: that which opposes the operating force or torque
and tend to prevent the closure of the relay contacts.

■ Pick-up level: the value of the actuating quantity (current or voltage), which is
on the border above which the relay operates.

■ Drop-out or reset level: the value of current or voltage below which a relay
opens its contacts and comes to original position..
■ Operating time: the time which elapses between the instant when the
actuating quantity exceeds the pick-up value to the instant when the relay
contacts close.
■ Reset time: the time which elapses between the instant when the actuating
quantity becomes less than the reset value to the instant when the relay contact
returns to its normal position.
■ Primary relays: the relays which are connected directly in the circuit to be
protected.
■ Secondary relays: the relays which are connected in the circuit to be
protected through CTs and V.Ts.
■ Auxiliary relays: relays which operate in response to the opening or closing of
its operating circuit to assist another relay in the performance of its function. This
relay may be instantaneous or may have a time delay.
■ Reach: a distance relay operates whenever the impedance seen by the relay
is less than a prescribed value, this impedance or rt]ic corresponding distance is
known as the reach of the relay.
■ Instantaneous relay: One which has no intentional time-delay and operates in
less than 0.1 second.
■ Blocking: preventing the protective relay from tripping cither due to its own
characteristics or to an additional relay.

■ Time delay relay : One which is designed with a delaying means .

9
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Types of Relays
The main types of protective relays are summaries in the following diagram:

Types of Relay

Solid Electromagnetic Computerized


State

Others:
Temperature
Pressure

Magnetic Magnetic Digital Numerical


Induction Attraction Relays Relays

Attracted Plunger
Armature Type

Wattmetric Induction Shaded Pole


Type Cup

21
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Electromagnetic Relays

1. Electromagnetic relays

Electromechanical Relays
Research Began at the End of the 19th
Century
The Relay Family Was Completed in
the 1930’s
They Are Still in Use

These relays were the earliest forms of relay used for the protection of power
systems, and they date back nearly 100 years. They work on the principle of
a mechanical force causing operation of a relay contact in response to a
stimulus. The mechanical force is generated through current flow in one or
more windings on a magnetic core or cores, hence the term
electromechanical relay. The principle advantage of such relays is that they
provide galvanic isolation between the inputs and outputs in a simple, cheap
and reliable form – therefore for simple on/off switching functions where the
output contacts have to carry substantial currents, they are still used.
Electromechanical relays can be classified into several different types as
follows:

a. magnetic attracted armature relays


b. magnetic induction relays
c. moving coil
d. thermal

However, only attracted armature and induction types have significant


application at this time, all other types having been superseded by more
modern equivalents. Electromagnetic relays are constructed with
electrical, magnetic and mechanical components, have an operating coil
and various contacts and are very robust, inexpensive and reliable.
However they required maintenance by skilled personnel.

2
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

1.1 . Magnetic attraction relays

Magnetic attraction relays can be supplied by AC or DC, and operate by


the movement of a piece of metal when it is attracted by the magnetic
field produced by a coil. There are two main types of relay in this class.
› Attracted armature type (clapper type)
› Plunger type

1.1.1 The attracted armature relays: which are shown in Fig.1,


consists of a bar or plate of metal which pivots when it is attracted
towards the coil.

(a) (b)

(c)

Fig. 1 Attracted armature-type relays

22
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

· The armature is attracted to the electromagnet when the current


reaches a certain predetermined value (iop – operating current). The
force of the armature will trip the link mechanism of the circuit
breaker, or it may operate as a relay and close the contacts of a
separate tripping circuit. The armature is attracted against gravity or a
spring. By adjusting the distance of the armature from the
electromagnet, or the tension of the spring, the current at which the
trip operates can be varied to suit the circuit conditions.
· The armature carries the moving part of the contact, which is
closed or opened according to the design when the armature is
attracted to the coil.

1.1.2 Plunger type relay: The other type is the piston or solenoid relay,
illustrated in Figure 2, in which α bar or piston is attracted axially within the
field of the solenoid. In this case, the piston also carries the operating
contacts. This called plunger type relay.

Figure 2 Solenoid-type (plunger) relay

· It can be shown that the force of attraction is equal to K 1I2 - K2, where
Κ1 depends upon the number of turns on the operating solenoid, the
air gap, the effective area and the reluctance of the magnetic circuit,
among other factors. K2 is the restraining force, usually produced by a
spring. When the relay is balanced, the resultant force is zero and
therefore Κ112 = K2, so that :
I = K 2 / K1 =constant.

23
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

This equation can be proved as follows:

Atracted armature relay analysis

In general, the mechanical force produced by an electric magnet is


propotional to φ2; i.e:
F (t )aj 2
mmf N
j= = i where
R R
lg
R = al = reluctance
mo A g
Ni N 2i 2
So ja or j 2a
lg l g2

Hence F (t ) = kj j
2
Where k j is constant
N 2i 2 N2
= kj 2 = k1i 2 , k1 = kj l 2
lg g

The net force is


Fn (t ) = F (t ) - k 2 = k1i 2 - k 2
Where k 2 = restraining force produced by the spring
When the relay is balanced Fn (t ) = 0
0 = k1I 2 - k2
So k1I 2 = k2
k2
or I = = constant
k1

I = RMS value of i

24
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

· In order to control the value at which the relay starts to operate, the
restraining tension of the spring or the resistance of the solenoid
circuit can be varied, thus modifying the restricting force. Attraction
relays effectively have no time delay and, for that reason, are widely
used when instantaneous operations are required.

Example :
An electromagnetic relay of attracted armature type has constants
k1 = 0.6 and k 2 = 10 find whether the relay will operate or not
when:
(a) A current of 4A flows through the relay winding.
(b) A current of 5A flows through the relay winding.
(c) Find the minimum current required to operate the relay.
Solution:
(a) For 4A current:

Fn (t ) = k1 I 2 - k 2 = 0.6(4) 2 - 10 = -0.4 N

So the relay will not operate. Since, the restrain force


> operating force.

(b) For 5A current:

Fn (t ) = k1 I 2 - k 2 = 0.6(5) 2 - 10 = 15 - 10 = 5N

Hence, the relay will operate, since, the operating


force > restrain force
(c) The minimum current required to operate the relay
is when the relay becomes at balanced condition, i.e
Fn (t ) = 0

25
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

k2 10
or I= = = 4.08 A
k1 0.6

1. 2. M ag ne ti c induction relays
An induction relay works only with alternating current. Induction relays can
be grouped into three classes as set out below.

1.2.1. Wattmetric-type relay

It consists of an electromagnetic system consists of two electromagnets


constructed as shown in Fig.4, which operates on a moving conductor, in the
form of a disc.

Fig.4. Induction type overload relay

Electromagnetic Induction Principle


· Induction type relay: General operating principle:

The two magnets of the induction type relay produce two alternating
magnetic fields j1 & j 2 :

26
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

j1 = j1m sin wt
j 2 = j 2m sin(wt + q )
where j 2 leads j1 by an angle q .
j1 & j 2 produce eddy currents in the rotating disc which are iφ1 and iφ2

dj 1
ij 1a
dt
dj 2
ij 2a
dt

or

ij1aj1m cos wt
ij 2aj2 m cos(wt + q )

F1 is the force produced by intersection of j1 and ij 2 .

27
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

F2 is the force produced by intersection of j 2 and ij1 .


The net force is
F = F2 - F1a[j 2 ij1 - j1ij 2 ]
Thus Faj1mj 2m [sin(wt + q ) cos wt - sin wt cos(wt + q )]
Now sin(wt + q ) cos wt = sin wt cos wt cos q + sin q cos 2 wt

- sin wt cos(wt + q )= - sin wt cos wt cos q + sin 2 wt sin q

= sin q (cos 2 wt + sin 2 wt ) = sin q

Hence Faj1mj 2 m sin q

The net torque produced

T = Fr aF
or
T = K1j1mj 2m sin q

Let Φ1 is the R.M.S value of j1 , Φ2 is the R.M.S value of j 2


So
FaF1F 2 sin q
or

TaF1F 2 sin q

In terms of currents:

TaI 1 I 2 sin q
or
T = K t I 1 I 2 sin q

28
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

· Induction Type Relay with plug settings

Fig.6 Induction type relay with

Plug settings

1.2.2. Induction-Cup relay

The operation is similar to the induction disc; here, two fluxes at right angles
induce eddy currents in a bell-shaped cup which rotates and carries the
moving contacts. A four-pole relay is shown in Figure 7.

Fig 7.Four-pole induction-cup relay.

29
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

1.2.3. Shaded-pole relay

In this case operation of the electromagnetic section is short-circuited by


means of a copper ring or coil. This creates a flux in the area influenced
by the short circuited section (the so-called shaded section) which lags the
flux in the nonshaded section, see Figure 8.

Fig.8 Shaded – pole Relay

Ø Note that the main coils has TAPS, this means that the
number of turns is actually adjustable.
In the electromagnetic induction principle, the relay element has a non-
magnetic rotor (an aluminum or copper disc or cylinder) in which coils
create magnetic fluxes that induce circulating currents. The interaction
between the fluxes and the circulating currents generates torque. This is the
operation principle of induction motors.
If the current is sinusoidal and the iron core is assumed to have a linear
behavior, the magnetic field and the magnetic flux in the iron core are
sinusoidal too. Note that the flux is divided in two parts. One flows through
the normal (‘pole”) and the other flows through the shaded pole. These two
fluxes are similar in magnitude but different in angle.
Features of the Induction Principle
Suitable for AC Systems
The Torque Does Not Vary With Time: No Vibration
Inherent Rejection of DC Offset: Low Overreach

31
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Solid State Relays

2. Solid State Relays


Research Began in the 1940’s
First Commercial Products in the Late
1950’s
Full Development in the 1960’s
Advantages Over Electromechanical
Relays
A solid state relay (SSR) is a solid state electronic component that provides
a similar function to an electromechanical relay but does not have any
moving components, increasing long-term reliability. Introduction of static
relays began in the early 1960’s. Their design is based on the use of
analogue electronic devices instead of coils and magnets to create the relay
characteristic. Early versions used discrete devices such as transistors and
diodes in conjunction with resistors, capacitors, inductors, etc., but advances
in electronics enabled the use of linear and digital integrated circuits in later
versions for signal processing and implementation of logic functions.. Figure
9 shows a small overcurrent relay and the circuit board for a simple static
relay.

Fig.9 . Small overcurrent relay and the circuit board for a simple static relay.

3
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Solid State Relay Principle of Operation


Solid state relays (static relays) are extremely fast in their operation. They
have no moving parts and have very quick response time and they are very
reliable.
Figure 1 shows the elements used in a single – phase time lag overcurrent
relay.

R
Relay
CT
Rectifier
C

Fig.1

· The AC input from the current transformer CT is rectified and


converted to DC voltage Vin through shunt resistance.
· A delay time circuit (RC) is used to produce the required time delay.
· If Vin < VR, the base – emitter of transistor TR1 is reversed bias
forcing the transistor to be in the cut off state.
· When Vin > VR, transistor TR1 will be in the ON state and in turn will
turn on TR2 and the output relay is activated.
· VR is set by R1 and R2.

32
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Computerized Relays

3. Computerized Relay
3.1. Digital relays
Research Began in the 1960’s
Basic Developments: Early 1970’s
A Technical and Economic Solution:
the Microprocessor
Commercial Relays: Early 1980
A digital protective relay is a microcomputer controlled relay. The data
acquisition system collects the transducers information and converts it to the
proper form for use by the microcomputer. Information from CT and PT and
other systems is amplified and sampled at several kHz. The sampled signals
are digitized with A/D converter and fed to registers in microprocessor
system. The microprocessor may use some kind of counting technique, or
use the Discrete Fourier Transform (DFT) to compare the information with
preset limits for overcurrent , over/under voltage…etc, and then send
command through D/A converter to alarm or trip signals to the circuit
breakers.

33
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Operation :

· The relay applies A/D (analog/digital) conversion processes to the


incoming the voltages and currents.
· The relay analyzes the A/D converter output to extract the magnitude
of the incoming quantity (RMS value) using Fourier transform
concept. Further, the Fourier transform is commonly used to extract
the signal's phase angle relative to some reference.
· The digital relay is capable of analyzing whether the relay should trip
or restrain from tripping based on current and/or voltage magnitude
(and angle in some applications).

Examples of digital relays are shown in Figure 10.

Fig.10 Digital relays

Signal Path for Microprocessor Relays


The signal path for voltage and current input signals are shown in Fig.11.

Fig.11

34
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

· After the currents and voltages are reduced to acceptable levels by the
instrument transformers, the signals are filtered with an analog filter
· The signal then digitized and re-filtered with a digital filter.
· Numerical operating quantities are then calculated from the processed
waveforms.

Digital Relay Construction

Analog Input Subsystem


Discrete Input Subsystem
A/D Converter
Microprocessor
Discrete output Subsystem
Operating signaling and communication subsystems

Fig.12

35
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Discrete Input Subsystem


Surge Suppression
Signal Conditioning
!

·
·
·
·
·
·
·
·
·

36
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Sampling frequency is the inverse of sampling rate.

37
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

The digital filter smoothes the signal by eliminating DC and frequencies


components those are different than the fundamental (when required).

38
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

39
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

These routines implement the protection function:


overcurrent, directional, distance,differential, etc.

Other Features :
· The relay has some form of advanced event recording. The event
recording would include some means for the user to see the timing of
key logic decisions, relay I/O (input/output) changes, and see in an
oscillographic fashion at least the fundamental frequency component
of the incoming AC waveform.
· The relay has an extensive collection of settings, beyond what can be
entered via front panel knobs and dials, and these settings are
transferred to the relay via an interface with a PC (personal computer),
and this same PC interface is used to collect event reports from the
relay.
· The more modern versions of the digital relay will contain advanced
metering and communication protocol ports, allowing the relay to
become a focal point in a SCADA system.

41
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Advantages of Digital Relays

Low Cost
Multifunctionality
Protection and control
Measurement
Fault recording
Communications capability
Compatibility with Digital Integrated Systems
High Reliability
Relays (integration, self-testing)
Protection system (supervised by the relays)
Sensitivity and Selectivity
New Protection Principles
New Relay Operating Characteristics
Maintenance-Free
Reduced Burden on CTs and VTs
Adaptive Protection

4
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Numerical Relays

3.2. NUMERICAL RELAYS

The distinction between digital and numerical relay rests on points of fine
technical detail, and is rarely found in areas other than Protection. They can
be viewed as natural developments of digital relays as a result of advances in
technology. Typically, they use a specialized digital signal processor (DSP)
as the computational hardware, together with the associated software tools.

Numerical measurement treatment

I1 U
1 numerically the measurement
value is converted into a
D
000101001001
A logical digit and then
compared with another digit
setting value stored 000101001011
in EEPROM stored in a memory
meas. current 1,05 A
no pick-up
setting value 1,10 A

meas. current 1,15 A pick-up


setting value 1,10 A

42
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Mode of operation
Analog Inputs

Analog-Digital-Conversion

yes Fault detection no

Protection program Routine program

Command and information output

Advantages of numerical technolo gy

· Comprehensive information supply

· clear representation of the fault sequence

Fault sequence of event and disturbance recording indicate

q What actually happened ?

q What did the current and voltage signals look like (CT
saturation) ?

q When did the protection issue a trip signal ?

q How long did the circuit breaker need to operate ?

q What was the magnitude of the interrupted current ?

q How did the system behave after the circuit breaker


tripped ?

43
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Electromagnetic vs Computerized

44
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

ANSI Device Numbers


The ANSI Standard Device Numbers denote what features a protective device supports
(such as a relay or circuit breaker). These types of devices protect electrical systems and
components from damage when an unwanted event occurs, such as a electrical fault.

List of Device Numbers


· 1 - Master Element
· 2 - Time Delay Starting or Closing Relay
· 3 - Checking or Interlocking Relay
· 4 - Master Contactor
· 5 - Stopping Device
· 6 - Starting Circuit Breaker
· 7 - Anode Circuit Breaker
· 8 - Control Power Disconnecting Device
· 9 - Reversing Device
· 10 - Unit Sequence Switch
· 12 - Overspeed Device
· 13 - Synchronous-speed Device
· 14 - Underspeed Device
· 15 - Speed - or Frequency-Matching Device
· 20 - Elect. operated valve (solenoid valve)
· 21 - Distance Relay
· 23 - Temperature Control Device
· 25 - Synchronizing or Synchronism-Check Device
· 26 - Apparatus Thermal Device
· 27 - Undervoltage Relay
· 29 - Isolating Contactor
· 30 - Annunciator Relay
· 32 - Directional Power Relay
· 36 - Polarity or Polarizing Voltage Devices
· 37 - Undercurrent or Underpower Relay
· 38 - Bearing Protective Device
· 39 - Mechanical Conduction Monitor
· 40 - Field Relay
· 41 - Field Circuit Breaker
· 42 - Running Circuit Breaker
· 43 - Manual Transfer or Selector Device
· 46 - Reverse-phase or Phase-Balance Relay
· 47 - Phase-Sequence Voltage Relay
· 48 - Incomplete-Sequence Relay
· 49 - Machine or Transformer Thermal Relay
· 50 - Instantaneous Overcurrent
· 51 - AC Time Overcurrent Relay

45
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

· 52 - AC Circuit Breaker
· 53 - Exciter or DC Generator Relay
· 54 - High-Speed DC Circuit Breaker
· 55 - Power Factor Relay
· 56 - Field Application Relay
· 59 - Overvoltage Relay
· 60 - Voltage or Current Balance Relay
· 61 - Machine Split Phase Current Balance
· 62 - Time-Delay Stopping or Opening Relay
· 63 - Pressure Switch
· 64 - Ground Detector Relay
· 65 - Governor
· 66 - Starts per Hour
· 67 - AC Directional Overcurrent Relay
· 68 - Blocking Relay
· 69 - Permissive Control Device
· 71 - Level Switch
· 72 - DC Circuit Breaker
· 74 - Alarm Relay
· 75 - Position Changing Mechanism
· 76 - DC Overcurrent Relay
· 78 - Phase-Angle Measuring or Out-of-Step Protective Relay
· 79 - AC-Reclosing Relay
· 81 - Frequency Relay
· 83 - Automatic Selective Control or Transfer Relay
· 84 - Operating Mechanism
· 85 - Carrier or Pilot-Wire Receiver Relay
· 86 - Lockout Relay
· 87 - Differential Protective Relay
· 89 - Line Switch
· 90 - Regulating Device
· 91 - Voltage Directional Relay
· 92 - Voltage and Power Directional Relay
· 94 - Tripping or Trip-Free Relay
· 95 - Reluctance Torque Synchrocheck
· 96 - Autoloading Relay

46
Power System Protection Part – 1 Dr.Prof.Mohammed Tawfeeq

Methods of Fault Detections


q Magnitude of current – Overcurrent protection

q Magnitude of current in earth and neutral – Earth fault

protection

q Magnitude and angle of Impedance (Ratio V/I)

Impedance protection

q Difference between two currents – Differential

protection

q Difference between phase angles of two currents –

phase comparison protection

q Magnitude of negative sequence current

q Magnitude of voltage – Overvoltage or undervoltage

protection

q Magnitude of frequency – Overvoltage or

underfrequency protection

q Temperature – Thermal protection

q Specials i.e. transformer gas protection

47
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Zones of Protection

Zones of protection
Zone of protection of a relay is the place or the distance that the relay can protect
easily.Fig.1 shows an example of protection zones for three circuit breakers.It is to be
noted that the protection zones are overlapped.

CB1
Zone of protection of CB1

CB2 CB3

Zone of protection of CB3

Zone of protection of CB2

In power systems, all power system elements must be encompassed by at


least one zone

n The more important elements must be included in at least two zones

n Zones must overlap to prevent any element from being unprotected.

n The overlap must be finite but small to minimize the likelihood of a


fault inside this region.

n A zone boundary is usually defined by a CT and a CB.

n The CT provides the ability to detect a fault inside the zone

n The CBs provide the ability to isolate the fault.

8
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Zones of Protection
CLOSED AND OPEN PROTECTION ZONES

OPEN ZONE
CLOSED ZONE
PROTECTION
PROTECTION

ZONE OF PROTECTION ZONE OF PROTECTION

Relay 87
Distance Relay 50/51
Overcurrent
Primary Zones of protection

Zone3
Zone 5
Zone 4
Zone1
Zone2

05
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Zones of Protection

Primary protection in power


systems

0
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Zones of Protection

Backup protection
n It is essential that provision be made to
clear the fault by some alternative
protection system in case of the
primary protection fails to operate.
These are referred to as backup
protection systems

n Ideally primary and backup are


independent (relay,breaker,CT,PT)

n Slower than primary

n Sometimes backup protection opens


more circuit breakers than absolutely
necessary to clear the fault

n Provide primary protection when usual


primary equipment out of service

0
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Zones of Protection

Two Types of Backup


Protection
Back up relaying may be installed
locally, in the same substation, or
remote in other substations or
places:

n Local backup : Clears fault in the


same station where the failure
has occurred

n Remote backup : Clears fault on


station away from where the
failure has occurred

0
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Zones of Protection

Primary and Back up protection


at the same location
( Local Backup)
Backup
REACH OF PROTECTION 21P Primary
REACH OF PROTECTION 21B

Fault

Transmission line

21P
21B

08
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Zones of Protection

Local backup protection at


differente locations
REACH OF PROTECTION 50/51 OF THE TRANSFORMER
REACH OF PROTECTION 50/51 OF BUS TIE BREAKER
REACH OF PROTECTION 21

21

50/51

50/51

B/B2 B/B1

00
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Power System protection Dr. Mohamad Tawfeeq


Zones of Protection

Remote back up protection

REACH OF PROTECTION 21B


REACH OF PROTECTION 21A

21 21

SUBSTATION B SUBSTATION A

n Selectivity and zones of protection


Selectivity is defined in terms of regions of a power
system (zones of protection) for which a given relay is
responsible.
n The relay will be considered secure if it responds only to
faults within its zone of protection

0
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Example : Consider the following simple power system:

A D
G1 G2
B E
G H J K

C F

L M
Q R

N P

LOAD

Discuss the local and remote backup protection for two fault
locations as follows:

0
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Case 1: Local Backup

A D
G1 G2
B E
G H J K

C F
F1
I

L M
Q R

N P

LOAD

Breaker closed Breaker opened

For fault at F1: Suppose that breaker J operate and breaker H


failed to operate.

Therefore:

04
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

G and I must operate as local backup protection


Case 2: Local Backup

A D
G1 G2
B E
G H J K

C F

L M
Q R

N P

F2

LOAD

Breaker closed Breaker opened


For fault at F2: Suppose that breakers P and Q operate and
breaker M failed to operate.
Therefore:

L must operate as local backup protection and I should tripped


by communication signal (Transfer Trip)

0
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Case 3: Remote Backup

A D
G1 G2
B E
G H J K

C F

I
F1

L M
Q R

N P

LOAD

Breaker closed Breaker opened


For fault at F1: Suppose that breaker J operate and breaker H
failed to operate.
Therefore:

E, F, L and M must operate as Remot backup protection

5
Power System Protection Part – 2 Dr.Prof. Mohammed Tawfeeq

Case 4: Remote Backup

A D
G1 G2
B E
G H J K

C F

L M
Q R

N P
F2

LOAD

Breaker closed Breaker opened


For fault at F1: Suppose that breakers P & Q operate and
breaker M failed to operate.
Therefore:

I, B, and C must operate as Remot backup protection

You might also like