Installation Manual of Room Air Conditioner: Necessary Tools For Installation

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Installation Manual of Room Air Conditioner

Read this manual before installation


Explain sufficiently the operating means to the user
according to this manual.

Necessary Tools for Installation


1.Driver 5.Torque wrench(17mm,22mm,26mm) 9.Nipper 12.Reamer
2.Hacksaw 6.Pipe cutter 10.Gas leakage detector or
3.Hole core drill 7.Flaring tool soap-and-water solution
4.Spanner(17,19 and 26mm) 8.Knife 11.Measuring tape

Drawing for the installation of indoor and outdoor units


The models adopt HFC free refrigerant R410A

Accessory parts
Number
No. Accessory parts of

more than 5cm


articles

1 Remote controller 1
mo
re th
an
2 2
10c
m
R-03 dry battery

3 1 Optional parts for piping G

Mounting plate Mark Parts name


A Non-adhesive tape
4 1
Drain hose B Adhesive tape mo
re tha
n1
0cm
C Saddle(L.S) with screws
5 4X25 Plastic cap
4
Screw D Connecting electric cable
for indoor and outdoor F
Attention must be paid to
E Drain hose the rising up of drain hose A
6 Drain-elbow 1
F Heating insulating material

G Piping hole cover


7 Cushion 4

C
mo
Arrangement of piping directions re
tha m
n1 10c
0c an
Rear left m re th
mo

Left Rear
right

Right
Below

60cm
than
more more
than
15c
m

The marks from A to G in the figure are the parts numbers.


The distance between the indoor unit and the floor should be
No.0010 more than 2m.
HSU-07HV03/R2(DB) HSU-18HV03/R2(DB)
HSU-07HVA103/R2(DB) HSU-22HV03/R2(DB)
HSU-09HV03/R2(DB)
HSU-12HV03/R2(DB) HSU-09HVA103/R2(DB) HSU-22HVA103/R2(DB)
HSU-12HVB03/R2(DB) HSU-12HVA103/R2(DB)
HSU-18HVA103/R2(DB)

319.5
256
140 500 140 113.5 583 113.5

Floor fixing dimensions Floor fixing dimensions


of the outdoor unit of the outdoor unit
(Unit:mm) (Unit:mm)

Fixing of outdoor unit Fix the unit to concrete or block with bolts( 10mm) and nuts firmly and horizontally.
When fitting the unit to wall surface, roof or rooftop, fix a supporter surely with nails
or wires in consideration of earthquake and strong wind.
If vibration may affect the house, fix the unit by attaching a vibration-proof mat.

Indoor Unit Selection of Installation Place Outdoor Unit

Place, robust not causing vibration, where the body can be supported Place, which is less affected by rain or direct sunlight and is
sufficiently. sufficiently ventilated.
Place, not affected by heat or steam generated in the vicinity, where Place, possible to bear the unit, where vibration and noise are
inlet and outlet of the unit are not disturbed. not increased.
Place, possible to drain easily, where piping can be connected with the Place, where discharged wind and noise do not cause a
outdoor unit. nuisance to the neighbors.
Place, where cold air can be spread in a room entirely. Place, where a distance marked is available as illustrated
Place, nearby a power receptacle, with enough space around. (Refer in the above figure.
to drawings).
Place where the distance of more than lm from televisions, radios,
wireless apparatuses and fluorescent lamps can be left.
In the case of fixing the remote controller on a wall, place where the
indoor unit can receive signals when the fluorescent lamps in the room
are lightened.

Power Source
Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate.
Install an exclusive branch circuit of the power.
A receptacle shall be set up in a distance where the power cable can be reached. Do not extend the cable by cutting it.

Selection of pipe
HSU-07HV03/R2(DB) HSU-12HV03/R2(DB)
To this unit, both liquid and gas pipes shall be insulated HSU-09HV03/R2(DB) HSU-18HV03/R2(DB)
HSU-12HVB03/R2(DB)
HSU-22HV03/R2(DB)
as they become Iow temperature in operation. HSU-07HVA103/R2(DB)
HSU-18HVA103/R2(DB)
HSU-09HVA103/R2(DB)
Use optional parts for piping set or pipes covered with HSU-12HVA103/R2(DB) HSU-22HVA103/R2(DB)

equivalent insulation material. Liquid pipe( ) 6.35mm(1/4") 6.35mm(1/4")


The thickness of the pipe must be 0.8 mm at least.
Gas pipe( ) 9.52mm(3/8") 12.7mm(1/2")

2
Indoor unit
1.Fitting of the Mounting Plate and Positioning of the wall Hole
When the mounting plate is first fixed
1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be
fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a weight from
the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Find the wall hole location A using a measuring tape

35
A=80mm

Fit the level line

When the mounting plate is fixed side bar and lintel


Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten
the plate to the fixed mounting bar.
Refer to the previous article, " When the mounting plate is first fixed ", for the
position of wall hole.

2.Making a Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of 70 mm in diameter, Indoor side Outdoor side
slightly descending to outside the wall.
Wall hole Thickness
Install piping hole cover and seal it
of wall
off with putty after installation 70mm

(Section of wall hole) G Piping hole pipe

3.Installation of the Indoor Unit


Drawing of pipe
[ Rear piping ]
Draw pipes and the drain hose, then fasten them with the adhesive tape
[ Left Left-rear piping ]
In case of left side piping, cut away, with a nipper, the lid for left piping.
In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear
piping which is marked on heat insulation materials.

3
Indoor unit
1. Insert the drain hose into the dent of heat insulation materials of indoor unit.
2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then
connect them.
3. Coat the flaring seal face with refrigerant oil and connect pipes.
Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape

Heat insulation Piping


material

Lid for right piping Pipe supporting plate


Lid for left piping
Lid for under piping Drain hose Indoor/outdoor
electric cable

Fix with adhesive tape

Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape.

[Other direction piping]


Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according
to the position of wall hole. When bending, be careful not to crash pipes.
Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation
of connecting part specially.

Fixing the indoor unit body


Hang surely the unit body onto the upper notches of the
mounting plate. Move the body from side to side to verify
its secure fixing.
In order to fix the body onto the mounting plate,hold up
the body aslant from the underside and then put it down
perpendicularly.

4.Connecting the indoor/outdoor Electric Cable


Removing the wiring cover
Remove terminal cover at right bottom corner of indoor unit, then
take off wiring cover by removing its screws.

When connecting the cable after installing the indoor unit


1. Insert from outside the room cable into left side of the wall hole, in which
the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable making a loop.

4
Indoor unit
When connecting the cable before installing the indoor unit
Insert the cable from the back side of the unit, then pull it out on the front side.
Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.
Pull the cable slightly to make sure the cables have been properly inserted and tightened.
After the cable connection, never fail to fasten the connected cable with the wiring cover.
Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully.
If wiring is not correct, proper operation can not be carried out and will cause defect.

L
Indoor unit
HSU-07HV03/R2(DB)
Outdoor unit Indoor unit
HSU-22HV03/R2(DB)
POWER PLUG

{ N
HSU-09HV03/R2(DB) Outdoor unit
HSU-22HVA103/R2(DB)
HSU-12HV03/R2(DB)
HSU-18HV03/R2(DB)
HSU-12HVB03/R2(DB) Power cable:
HSU-07HVA103/R2(DB) -mod 07-09-12: 3G1.5mm2
HSU-09HVA103/R2(DB) -mod 18-22: 3G2.5mm2
HSU-12HVA103/R2(DB)
HSU-18HVA103/R2(DB)
claw of the clip

5.Easily-demount cleaning of indoor unit


1.Top inlet can be taken down
Open the inlet grille, press the claw of the clip on the unit,then
Figure 1
take down the top inlet.(according to figure 1)
Figure 2
2.Vertical flap can be taken down
Overturn the vertical flap, press the claw of the clip ,then take
down vertical flap.(according to figure 2)
3.Horizontal louvers can be taken down Figure 2
Daff
After taking down vertical flap.Horizontal louvers are appeared,draw
the middle louver,and take down the horizontal louvers .
(according to figure 3)

Figure 3
5
Outdoor unit
1.Installation of Outdoor Unit
Install according to Drawing for the installation of indoor and outdoor units

2.Connection of pipes
To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius
should be 30 to 40 mm or longer.
Connecting the pipe of gas side first makes working easier.
The connection pipe is specialized for R410A.
Half union Flare nut Forced fastening without careful centering
may damage the threads and cause a
leakage of gas.

Pipe Diameter ( ) Fastening torque


Liquid side 6.35mm(1/4") 18N.m
Gas side 9.52mm(3/8") 40N.m
Torque wrench Gas side 12.7mm(1/2") 55N.m
Spanner
Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
The standard pipe length is 5m. If it is over 5m, the function of the unit will be affected. If the pipe has
to be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerant
must be conducted by professional air conditioner engineer. Before adding additional refrigerant,
perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge
additional refrigerant.

Outdoor unit Outdoor unit


Max. Length:
A=20m(for: 07k 09k 12k)
A=25m(for:18k 22k)
A
Oil trap

Indoor unit

Indoor unit

Max.Elevation: CAUTION
In case more than 5m
10m (for: 07k 09k 12k) Oil trap shoud be installed every 5~7m
15m(for:18k 22k)
no more gas if the length of connecting pipe is less than10m

3.Connection
Use the same method on indoor unit. Loosen the screws on terminal block and insert the plugs fully into
terminal block, then tighten the screws.
Insert the cable according to terminal number in the same manner as the indoor unit.
If wiring is not correct, proper operation can not be carried out and controller may be damaged.
Fix the cable with a clamp.

4.Attaching Drain-Elbow
If the drain-elbow is used, please attach it as
figure. (Note: Only for heat pump unit.)
Outdoor unit
2-way valve
Liquid Side
6.Purging Method:To use vacuum pump 3-way valve
Gas Side

1
Detach the service port's cap of 3-way valve, the
Gaugemanifold(for R410A)
valve rod's cap for 2-way valve and 3-way's, connect
Anti countercurrent joint
the service port into the projection of charge hose
(Iow) for gaugemanifold. Then connect the projection
of charge hose (center) for gaugemanifold into
Vacuum pump(for R410A)
vacuum pump. Tube(for R410A)

2
Open the handle at Iow in gaugemanifold, operate
vacuum pump. If the scale-moves of gause (Iow) Open
reach vacuum condition in a moment, check 1 again.

3
Vacuumize for over 15min. And check the level gauge
which should read -0.1 MPa (-76 cm Hg) at Iow
pressure side. After the completion of vacuumizing,
close the handle 'Lo' in gaugemanifold and stop the
operation of the vacuum pump. Close
Check the condition of the scale and hold it for 1-2min.
If the scale-moves back in spite of tightening, make
flaring work again, the return to the beginning of 3 .

2-way valve
4
Open the valve rod for the 2-way valve to an angle of 2-way valve
anticlockwise 90 degrees. Open 3-way valve
O

After 6 seconds, close the 2-way valve and make 90


3-way valve
the inspection of gas leakage.

If it does not stop gas leakage, discharge


5 HSU-22HV03/R2(DB)
In case of gas leakage, tighten whole refrigerants from the service port.
After flaring work again and vacuumize, HSU-22HVA103/R2(DB)
parts of pipe connection. If
No gas leakage? fill up prescribed refrigerant from the gas
leakage stops, then proceed 6
cylinder.
steps. 2-way valve 3-way valve
2-way valve
6
Detach the charge hose from the service port, open
3-way valve
2-way valve and 3-way. Turn the valve rod anticlockwise 6
until hitting lightly.
6

7 HSU-07HV03/R2(DB)
2-way valve HSU-09HV03/R2(DB)
To prevent the gas leakage, turn the service port's
HSU-12HV03/R2(DB)
cap, the valve rod's cap for 2-way valve and 3-way's HSU-18HV03/R2(DB)
a little more than the point where the torque increases 3-way valve HSU-12HVB03/R2(DB)
HSU-07HVA103/R2(DB)
suddenly.
HSU-09HVA103/R2(DB)
HSU-12HVA103/R2(DB)
8 7 Valve rod cap HSU-18HVA103/R2(DB)
After attaching the each caps, check the gas leakage 7 Valve rod cap
around the caps. 7 Service port cap

CAUTION:
1.If the refrigerant of the air conditioner leaks, it is necessary to 2.Please do not let other cooling medium, except specified one (R410A),
discharge all the refrigerant. Vacuumize first, then charge the liquid or air enter into the cooling circulation system. Otherwise, there will be
refrigerant into air conditioner according to the amount marked on abnormal high pressure in the system to make it crack and lead to
the name plate. personal injuries.

7
1.Power Source Installation
The power source must be exclusively used for air conditioner. (Over I0A)
In the case of installing an air conditioner in a moist place, please install an
earth leakage breaker.
For installation in other places, use a circuit breaker as far as possible.

2.Cutting and Flaring Work of Piping


Pipe cutting is carried out with a pipe cutter and burs must be removed.
After inserting the flare nut, flaring work is carried out.
A

Flare tool for R410A Conventional flare tool


Flare tooling die
Clutch-type clutch-type(Rigid-type) Wing-nut type (Imperial-type)
1.Cut pipe 2.Remove burs A 0~0.5mm 1.0~1.5mm 1.5~2.0mm

3.Insert the flare nut


Correct Incorrect

4.Flare pipe
Lean Damage of flare Crack Partial Too outside

3.On Drainage
Please install the drain hose so as to be downward slope without fail.
Please don't do the drainage as shown below.

Less than 5cm

It becomes high midway. The end is immersed It waves. The gap with the ground There is the bad smell
in water. is too small from a ditch

Please pour water in the drain pan of the indoor unit, and confirm that drainage is
carried out surely to outdoor.
In case that the attached drain hose is in a room, please apply heat insulation
to it without fail.
Check for Installation and Test Run
Please kindly explain to our customers how to operate through the instruction manual.
Check Items for Test Run Put check mark in boxes
Gas leak from pipe connecting? Is drainage securely carried out? Is the lamp normally lighting?
Heat insulation of pipe connecting? Is the earth line securely Are cooling and heating (when
Are the connecting wirings of connected? in heat pump) performed normally?
indoor and outdoor firmly inserted Is the indoor unit securely fixed? Is the operation of room temperature
to the terminal block? Is power source voltage abided regulator normal?
Is the connecting wiring of indoor by the code?
and outdoor firmly fixed? Is there any noise?

8
Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.China

IT CONFORMITÀ ALLE DIRETTIVE EUROPEE PER I MODELLI:

CE SPECIFICHE DI SMALTIMENTO:
Tutti i prodotti sono conformi alle seguenti normative europee: Il climatizzatore è contrassegnato con questo simbolo,
- Direttiva 73/23/EEC Basso Voltaggio ciò significa che i prodotti elettrici ed elettronici non
- Direttiva 2006/95/EC Basso Voltaggio possono essere smaltiti insieme ai rifiuti domestici non
- Direttiva 89/336/EEC Compatibilità elettromagnetica differenziati. Non cercare di demolire il sistema da soli:
- Direttiva 2004/108/EC Compatibilità elettromagnetica la demolizioni dei sistemi di condizionamento, nonché il
recupero del refrigerante, dell’olio e di qualsiasi altra
ROHS parte devono essere eseguiti da un installatore qualifi-
Il prodotto è conforme alla normativa 2002/95/EEC sulla restrizione d’uso di cato in conformità alla legislazione locale e nazionale
sostanze inquinanti negli apparecchi elettrici ed elettronici. vigente in materia.I climatizzatori devo essere trattati presso una struttura spe-
cializzata nel riutilizzo, riciclaggio e recupero dei materiali. Il corretto smaltimen-
WEEE to del prodotto eviterà le possibili conseguenze negative all’ambiente e alla
Informativa al consumatore come previsto dalla normativa europea salute dell’uomo. Per maggiori informazioni contattare l’installatore o le autori-
2002/96/CE riguardante i rifiuti di apparecchiature elettriche ed elettroniche. tà locali. Le batterie devono essere tolte dal telecomando e smaltite separata-
mente conformemente alla legislazione locale e nazionale vigente in materia.

EN EUROPEAN REGULATIONS CONFORMITY FOR THE MODELS:

CE DISPOSAL REQUIREMENTS:
All the products are in conformity with the following European provision: Your air conditioning product is marked with this sym-
- Low Voltage Directive 73/23/EEC bol. This means that electrical and electronic products
- Low Voltage Directive 2006/95/EC shall not be mixed with unsorted household waste.
- Electromagnetic CompatibilitY 89/336/EEC Do not try to dismantle the system yourself: the dis-
- Electromagnetic CompatibilitY 2004/108/EC mantling of the air conditioning system, treatment of
the refrigerant, of oil and of other part must be done
ROHS
by a qualified installer in accordance with relevant
The products are fulfilled with the requirements in the directive 2002/95/EEC of the
local and national legislation. Air conditioners must be
European parliament and of the council on the Restriction of the use of Certain Haz-
treated at a specialized treatment facility for re-use, recycling and recovery.
ardous Substances in Electrical and Electronic Equipment (EU RoHS Directive).
By ensuring this product is disposed of correctly, you will help to prevent
WEEE potential negative consequences for the environment and human health.
In accordance with the directive 2002/96/CE of the European parliament, Please contact the installer or local authority for more information. Battery
herewith we inform the consumer about the disposal requirements of the must be removed from the remote controller and disposed of separately in
electrical and electronic products. accordance with relevant local and national legislation.

FR CONFORMITÉ AUX DIRECTIVES EUROPÉENNES POUR LES MODÈLES:

CE SPECIFICATIONS POUR L'ELIMINATION:


Tous les produits sont conformes aux directives européennes suivantes: Ce pictogramme, apposé sur le climatiseur, signifie
- Directive 73/23/CEE Basse tension que les équipements électriques et électroniques ne
- Directive 2006/95/CE Basse tension peuvent pas être éliminés avec les déchets ménagers
- Directive 89/336/CEE Compatibilité électromagnétique non triés. Ne pas essayer de démanteler l'équipement
- Directive 2004/108/CE Compatibilité électromagnétique soi-même: le démantèlement des systèmes de clima-
tisation, ainsi que la récupération du frigorigène, de
ROHS l'huile et de toute autre partie doivent être effectués
L'appareil est conforme à la directive 2002/95/CEE relative à la limitation de par un installateur qualifié conformément à la législa-
l'utilisation de certains substances dangereuses dans les équipements élec- tion locale et nationale en vigueur en la matière. Les climatiseurs doivent être
triques et électroniques. traités dans un centre spécialisé dans la réutilisation, le recyclage et la valo-
risation des matériaux. L'élimination correcte de ces appareils permet d'évi-
DEEE (WEEE) ter les effets nocifs sur l'environnement et la santé humaine. Pour plus de
Information au consommateur comme le prévoit la directive européenne renseignements contacter l'installateur ou les autorités locales. Les piles doi-
2002/96/CE relative aux déchets d'équipements électriques et électro- vent être retirées de la télécommande et éliminées séparément, conformé-
niques. ment à la législation locale et nationale en vigueur en la matière.
Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.China

ES CONFORMIDAD EUROPEA DE LAS REGULACIONES PARA LOS MODELOS:

CE REQUISITOS PARA LA ELIMINACIÓN:


Todos los productos están en conformidad con las siguientes Normativas Su acondicionador de aire está marcado con este
Europeas: símbolo. Esto significa que los productos eléctricos y
- Bajo Voltaje directiva 73/23/EEC electrónicos no deben mezclarse con el resto de resi-
- Bajo Voltaje directiva 2006/95/EC duos domésticos no clasificados.
- Compatibilidad electromagnética 89/336/EEC No intente desmontar el sistema usted mismo: El des-
- Compatibilidad electromagnética 2004/108/EC mantelamiento del acondicionador de aire, así como
el tratamiento del refrigerante, aceite y otros compo-
ROHS nentes, debe ser efectuado por un instalador compe-
Los productos cumplen los requisitos de la directiva 2002/95/EEC del parla- tente de acuerdo con las normas locales y nacionales aplicables. Los acon-
mento Europeo y el consejo regulador Del uso de materiales peligrosos en dicionadores de aire deben ser tratados en instalaciones especializadas para
equipamientos eléctricos Y electrónicos. (EU RoHS Directiva). su reutilización, reciclaje y recuperación. Al asegurarse de desechar este pro-
ducto de la forma correcta, està contribuyendo a evitar posibles consecuen-
WEEE cias negativas para el entorno y para la salud de las personas. Contacte, por
De acuerdo con la directiva 2002/96/CE del parlamento Europeo, Informa- favor, con el instalador o con las autoridades locales para obtener más infor-
mos al consumidor acerca del reciclage de los productos Electrónicos y mación. Las pilas del control remoto deben extraerse y eliminarse por sepa-
eléctricos. rado y de acuerdo con la normativa local y nacional aplicable.
Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.China

Contains fluorinated greenhouse gases


covered by the Kyoto Protocol A

R410A 1= kg
B
2 2= kg
C
1
1+2= kg
D

F E

IT INFORMAZIONI IMPORTANTI SUL REFRIGERANTE UTILIZZATO


Questo prodotto contiene gas fluorurati ad effetto serra inclusi nel Protocollo L’etichetta compilata deve essere collocata in prossimità della portata di cari-
di Kyoto. Non liberare tali gas nell’atmosfera. ca del prodotto (ad esempio, nell’interno del coperchio della valvola d’inter-
cettazione).
Tipo di refrigerante: R410A
Valore GWP*: 1975 A contiene gas fluorurati ad effetto serra inclusi nel protocollo di Kyoto
*GWP = potenziale di riscaldamento globale B carica di refrigerante di fabbrica del prodotto: vedi targhetta con il nome
dell’unità
Compilare con inchiostro indelebile, C quantità di refrigerante aggiuntiva nel campo
•1 la carica di refrigerante di fabbrica del prodotto D carica di refrigerante totale
•2 la quantità di refrigerante aggiuntiva nel campo e E unità esterna
• 1+2 la carica di refrigerante totale F cilindro del refrigerante e collettore di carica
sull’etichetta di carica del refrigerante fornita con il prodotto

EN IMPORTANT INFORMATION REGARDING THE REFRIGERANT USED


This product contains fluorinated greenhouse gases covered by the Kyoto The filled out label must be adhered in the proximity of the product charging
Protocol. Do not vent into the atmosphere. port (e.g. onto the inside of the stop valve cover).

Refrigerant type: R410A A contains fluorinated greenhouse gases covered by the Kyoto Protocol
GWP* value: 1975 B factory refrigerant charge of the product: see unit name plate
*GWP = global warming potential C additional refrigerant amount charged in the field
D total refrigerant charge
Please fill in with indelible ink, E outdoor unit
•1 the factory refrigerant charge of the product F refrigerant cylinder and manifold for charging
•2 the additional refrigerant amount charged in the field and
• 1+2 the total refrigerant charge
on the refrigerant charge label supplied with the product.

FR INFORMATION IMPORTANTE RELATIVE AU RÉFRIGÉRANT UTILISÉ


Ce produit contient des gaz à effet de serre fluorés encadrés par le protoco- L’étiquette complétée doit être apposée à proximité de l’orifice de recharge
le de Kyoto. Ne pas laisser les gaz s’échapper dans l’atmosphère. du produit (par ex. à l’intérieur du couvercle de la vanne d’arrêt).

Type de réfrigérant: R410A A contient des gaz à effet de serre fluorés encadrés par le protocole de
Valeur GWP*: 1975 Kyoto
*GWP = potentiel de réchauffement global B charge de réfrigérant d’usine du produit: voir plaquette signalétique de
l’unité
Prière de compléter à l’encre indélébile, C quantité de réfrigérant supplémentaire chargée sur place
•1 la charge de réfrigérant d’usine du produit D charge de réfrigérant totale
•2 la quantité de réfrigérant supplémentaire chargée sur place et E unité extérieure
• 1+2 la charge de réfrigérant totale F cylindre de réfrigérant et collecteur de recharge
sur l’étiquette de charge de réfrigérant fournie avec le produit.
Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.China

Contains fluorinated greenhouse gases


covered by the Kyoto Protocol A

R410A 1= kg
B
2 2= kg
C
1
1+2= kg
D

F E

ES INFORMACIÓN IMPORTANTE EN RELACIÓN AL REFRIGERANTE UTILIZADO


Este producto contiene los gases fluorados de efecto invernadora regulados La etiqueta rellenada debe pegarse cerca de la conexión de carga del pro-
por el Protocolo de Kioto. No vierta gases a la atmósfera. ducto (p.ej. en el interior de la cubierta de la válvula de tope).

Tipo de refrigerante: R410A A Contiene los gases fluorados de efecto invernadora regulados por el
Valor GWP*: 1975 Protocolo de Kioto
*GWP = Potencial de calentamiento global B Carga de refrigerante de fábrica del producto: véase placa de especifi-
caciones técnicas de la unidad
Rellene con tinta indeleble, C Cantidad adicional de refrigerante cargado en campo
•1 la carga de refrigerante de fábrica del producto D Carga total de refrigerante
•2 la cantidad adicional de refrigerante cargado en campo y E Unidad exterior
• 1+2 la carga total de refrigerante F Cilindro del refrigerante y dosificador de carga
En la etiqueta de carga de refrigerante suministrada con el producto.

You might also like