Generators: Model: PDG20SS 20 KVA / Single Phase

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Specifications

GENERATORS Model PDG20SS


Alternator
Model: PDG20SS Make & Model Powercity TWG-224B
Frequency Hz 50 60
20 KVA / Single Phase Output Rating Prime 16 20
(KVA) Standby 17.6 22
Phase 1 - Phase (2 Wires)
Rated Voltage V 200-240 / 380-440
Power Factor 0.8 (Lagging)
Voltage
% Within +/- 1.5
Regulation
Brushless rotating exciter
Excitation with Automatic Voltage
Regulator (AVR)
Insulation Class H
Engine
Make & Model Quanchai N485D
Vertical inline; water
Type cooled; 4 stroke; direct
injected.
Output Rating Kw/rpm 15.5/1500 18/1800
Powercity generators are designed in conformance No. of cylinders-
mm 4 – 85 X 95
with European Standards certified by independent Bore X Stroke
certifying agency the Materials Industrial Research Piston
L 2.156
Displacement
and Technology Center (MIRTEC) with certificate Fuel ASTM No. 2 Diesel
number MC/TH-C-269/08. The principles in design, Fuel
safety, rating and performance are in accordance Consumption @ L/h 3.7 4.1
with European Standards EN 12601:2001, EN 60204- 75% Load
Lube Oil
1:2006, EN 60034-1:2004, EN ISO 12100-1:2003 and Capacity
L 6
EN ISO 12100-2:2003. Generators are designed and Coolant
L 14
built to provide electrical power for stand-by or Capacity
continuous use. Comes with 2 years or 2,000 run Battery Capacity V-Ah 12V-80Ah
Fuel Tank
hours limited warranty whichever comes first. L 65
Capacity
Unit
Features: Length mm 1630
Dimensions Width mm 740
 MANUAL or AUTOMATIC starting and Height mm 910
stopping capability. Dry Weight Kg 800
 Digital controller. Sound Level
dB @ 7 m 68 70
 Direct injection diesel engine for fuel
efficiency.
 Brushless rotating field generator with class Note: Due to continuous product improvement, the generator
set manufacturer reserves the right to change the design or
H insulation.
specifications without notice and without any obligation or
 NEMA 3R enclosure suitable for outdoor use. liability whatsoever.
 Integral vibration isolators.
 Silent type generator.
Engine: GENERAL GUIDELINES FOR DERATION:

Altitude: Derate 0.5% per 100 meter (328 ft.) elevation above
N485D – 4 cylinder Direct Injection Diesel
1000 meter (3279 ft.).
15.5kW@1500 rpm / 18kW@1800 rpm
Temperature: Derate 1.0% per 10°C (18°F) temperature above
40°C (104°F).

FUEL: Use clean diesel fuel only. Diesel fuel quality should
meet the specifications of ASTM D975 and the Worldwide Fuel
Charter.

SOUND LEVEL: Sound level is measured in free field


environment (acoustic test chamber) where sound may
propagate free from any form of obstruction.

dB Range:

Quiet Normal Alarm clock


Room conversation City traffic Chainsaw

40 50 60 70 80 90 100
Standards:
Moderate Vacuum Motorcycle
EN 12601:2001 – Reciprocating internal combustion rainfall cleaner Hair dryer
engine driven generating sets – Safety.
PDG20SS
EN 60204-1:2006 – Safety of machinery; electrical
equipment of machines – General requirements.
Quality Assurance:
EN 60034-1:2004 – Rotating electrical machines –
Rating and performance.
EN ISO 12100-1:2003 – Safety of machinery; basic
concepts and general principles for design Part 1.
EN ISO 12100-2:2003 – Safety of machinery; basic ISO 9001:2008
concepts and general principles for design Part 2. Certificate No. U13Q2GZ682452F1M

Applicable EGSA* Standards.


Manufactured by:
*- Electrical Generating Systems Association Powercity Electromechanical & Equipment Co Ltd
Fujian, China
Application Notes:
Distributed in the Philippines by:
STANDBY RATING: Standby ratings apply to installations served
Powercity Corporation
by a reliable utility source. This rating is applicable to varying
Km. 20, East Service Road, Muntinlupa City
loads for the duration of a power outage. There is no overload
Metro Manila, Philippines
capability for this rating. Ratings are in accordance with ISO
Tel. (+632) 869 1991, (+632) 8697520
3046-1, BS 5514, AS 2789 and DIN 6271.
Fax. (+632) 8693869
PRIME POWER RATING: Prime power ratings apply to Email: [email protected]
installations where utility power is unavailable or unreliable.
At varying load the number of generator set operating hours is Made in China
unlimited. A 10% overload capacity is available for one hour in
twelve hours. Ratings in accordance with ISO 8528-1, overload
power in accordance with ISO 3046-1, BS 5514, AS 2789, and
DIN 6271.

You might also like