Abb Reg 630 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 72
At a glance
Powered by AI
The document provides an overview of the REG630 generator protection and control relay including its applications, components, protection functions, and communication capabilities.

The REG630 includes preconfigurations, protection functions, control, measurement, disturbance recording, event logging, circuit breaker monitoring, and communication capabilities.

The REG630 provides several standard protection functions including overcurrent, over/under voltage, over/under frequency, differential, thermal overload protection, and circuit breaker failure protection.

RELION® 630 SERIES

Generator Protection and Control


REG630
Product Guide
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Contents

1. Description..................................................................... 3 15. Access control............................................................ 14


2. Application..................................................................... 3 16. Inputs and outputs...................................................... 14
3. Preconfigurations........................................................... 7 17. Communication...........................................................15
4. Protection functions......................................................12 18. Technical data.............................................................17
5. Control......................................................................... 13 19. Front panel user interface............................................ 55
6. Measurement............................................................... 13 20. Mounting methods...................................................... 55
7. Disturbance recorder....................................................13 21. Selection and ordering data.........................................57
8. Event log...................................................................... 13 22. Accessories.................................................................59
9. Disturbance report........................................................13 24. Tools........................................................................... 60
10. Circuit-breaker monitoring........................................... 13 25. Supported ABB solutions............................................ 61
11. Trip-circuit supervision.................................................14 26. Terminal diagrams.......................................................63
12. Self-supervision...........................................................14 27. References..................................................................65
13. Fuse failure supervision............................................... 14 28. Functions, codes and symbols.................................... 66
14. Current circuit supervision........................................... 14 29. Document revision history........................................... 69

Disclaimer

The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors
that may appear in this document.
© Copyright 2019 ABB.
All rights reserved.
Trademarks

ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks
of their respective holders.
2 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3 Issued: 2019-02-25
Revision: C

1. Description diesel, gas, hydroelectric, combined heat and power (CHP),


REG630 is a comprehensive generator management relay for and steam power plants.
protection, control, measuring and supervision of small and
medium size generators. REG630 is a member of ABB’s The pre-defined configuration developed for REG630 can be
used as such or easily customized or extended with add-on
Relion ® product family and a part of its 630 series characterized
functions, by means of which the generator management
by functional scalability and flexible configurability.
protection relay can be fine-tuned to exactly satisfy the specific
The supported communication protocols including IEC 61850 requirements of your present application.
offer seamless connectivity to industrial automation systems.

2. Application
REG630 provides main protection for generator and generator-
transformer units in, for example, small– and medium–power

ABB 3
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

RET630
Preconf. n
3U ANSI IEC

87T 3ΔI>T
3I
HV 27 3U<
Io side 46 I2>
49T 3I >T REF630
50P/51P 3I>>> Preconf. n
51BF/51NBF 3I>/Io>BF ANSI IEC
51N-1/51N-2 Io>/Io>> 25 SYNC
51P-1/51P-2 3I>/3I>> 27 3U<
59 3U> 50P/51P 3I>>>
Io 87NL dIoLo> 51BF/51NBF 3I>/Io>BF
LV 46 I2> 51N-1/51N-2 Io>/Io>>
side 50P/51P 3I>>> 51P-1/51P-2 3I>/3I>> U12
3U 51P-1/51P-2 3I>/3I>> 59 3U>

3I
3I

3I 3I

3U 3U

3U Uo

Io Io

3I 3I

Io Io

REG630 REG630
Preconf. A Preconf. A
REU615
ANSI IEC ANSI IEC
Std. conf. A
27 3U< 27 3U<
ANSI IEC
32R/32O P>→ 32R/32O P> →
47O-/59 U2>/3U>
32U P<→ 32U P< →
47U+/27 U1</3U<
40 X< 40 X<
59G Uo>
46G/46M I2>G/M 46G/46M I2>G/M
81 f</f>,df/dt
49T/G 3Ith>T/G 49T/G 3Ith>T/G
81LSH UFLS/R
51BF/51NBF 3I>/Io>BF 51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>> 51P-1/51P-2 3I>/3I>>
51V I(U)> 51V I(U)>
59 3U> 59 3U>
59G Uo> 59G Uo>
60 FUSEF 60 FUSEF
67N-1/67N-2 Io>→/Io>>→ 67N-1/67N-2 Io>→/Io>>→
81U/81O/81R f</f>/Δf/Δt 81U/81O/81R f</f>/Δf/Δt
87G/87M 3dl>G/M 87G/87M 3dl>G/M

GUID-95FFD0DD-9A1E-422D-A6F2-0603158D0DBA V1 EN

Figure 1. Application example for Diesel/Gas generator application with preconfiguration A

Several generator units connected in parallel, where each unit is


individually earthed. Earth-fault current is small, typically 3-5 A.

4 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

3I

3U RET630
Preconf. n
ANSI IEC

46 I2>
Io
51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>>
59 3U>
59G Uo>
67N-1 Io>→
87T 3ΔI>T

3U
REG630
Preconf. n
ANSI IEC

EXC. 21GT Z<GT


AVR
3I 24 U/f>
27 3U<
REK510 3I
27/59THD ΔU03f>/Uo>
Ufn
32R/32O P>→
Io 40 X<
Io 49T/G 3Ith>T/G
Uo 51BF/51NBF 3I>/Io>BF
51N-1 Io>
51P-1/51P-2 3I>/3I>>
59 3U>
59G Uo>
60 FUSEF
64R Io>R
81U/81R f</df/dt

GUID-C93D2D3A-8C8E-40CB-9242-FA76FA0E3C3D V1 EN

Figure 2. Generator in block connection with a transformer

The protection is implemented with REG630 covering


generator part, and RET630 covering transformer and feeder
part of this application.

ABB 5
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

REF630
U12 Preconf. n
ANSI IEC

25 SYNC
3I 27/47U+ 3U</U1<
3I 46 I2>
50N/51N Io>>>
3U 50P/51P 3I>>>
51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>>
59/47O- 3U>/U2>
Io 59G Uo>
60 FUSEF
67N-1/67N-2 Io>→/Io>>→
68 3I2f>

Uo
REG630
Preconf. n
ANSI IEC

32R/32O P>→
40 X<
46G/46M I2>G/M
3U 51BF/51NBF 3I>/Io>BF
51N-1/51N-2 Io>/Io>>
51P-1/51P-2 3I>/3I>>
59 3U>
59G Uo>
EXC. 81U/81R f</df/dt
AVR 87T 3ΔI>T
3I
REK510 3I
Ufn
REG630
Io Preconf. n
Io ANSI IEC
Uo
21GT Z<GT
24 U/f>
27 3U<
27/59THD ΔU03f>/Uo>
32R/32O P>→
49T/G 3Ith>T/G
51BF/51NBF 3I>/Io>BF
51P-1/51P-2 3I>/3I>>
59 3U>
59G Uo>
60 FUSEF
64R Io>R

GUID-42A3A43D-4F62-4541-AB39-D662B21769AB V1 EN

Figure 3. Medium-sized generator in block connection with a transformer

The protection is implemented with two REG630 generator available transformer differential protection function and
protection relays and one REF630 feeder terminal. One REF630 is protecting and controlling the feeder part of this
REG630 is taking care of protecting the generator itself, the application.
second REG630 is protecting the power transformer with

6 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

3. Preconfigurations settings including the texts shown in the HMI, configuration of


The 630 series protection relays are offered with optional the LEDs and function buttons, and adaptation of the default
factory-made preconfigurations for various applications. The single-line diagram.
preconfigurations contribute to faster commissioning and less
engineering of the protection relay. The preconfigurations In addition, the adaptation of the preconfiguration always
include default functionality typically needed for a specific includes communication engineering to configure the
application. Each preconfiguration is adaptable using the communication according to the functionality of the protection
Protection and Control IED Manager PCM600. By adapting the relay. The communication engineering is done using the
preconfiguration the protection relay can be configured to suit communication configuration function of PCM600.
the particular application.
If none of the offered preconfigurations fulfill the needs of the
The adaptation of the preconfiguration may include adding or intended area of application, 630 series protection relays can
removing of protection, control and other functions according also be ordered without any preconfiguration. In this case the
to the specific application, changing of the default parameter protection relay needs to be configured from the ground up.
settings, configuration of the default alarms and event recorder

ABB 7
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

REG630 GENERATOR PROTECTION AND CONTROL IED


For directly connected generator set
PRE-
CONFIGURATION
A

PROTECTION LOCAL HMI *) ALSO AVAILABLE

- 5 × prog. push buttons on LHMI


1× 1× - Disturbance and fault recorders
I→O - IED self-supervision
94 - Local/Remote push button on LHMI
- Sequence event recorder
- User management
- WebHMI
2× 1× 2× 1× 2×
P> P< X<
3I 32R/32O 32U 40 AND
OR
*) Fixed or detached LHMI is available.

3Ith>T/G I(U)>
49T/G 51V

CONDITION MONITORING COMMUNICATION


3U 3I AND SUPERVISION
3dl>G/M Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
87G/87M 1× 1× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
1 0 1 1 0 1 1 0 1 1 0 1 0 0
60 CBCM E DNP3 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0 1 0 0
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
2× 2× 1×
2× 1× 1× Ethernet: TX (RJ45),1 0 1(LC)
FX 1 0 1 1 0 1 1 0 1 0 0
MCS 3I OPTS TCS
Io I2>G/M 3I>/Io>BF Serial: Serial glass fiber (ST),
MCS 3I OPTM TCM
46G/46M 51BF/51NBF Serial plastic fiber
(snap-in connector)

1× 1× U<>
3I> 3I>> U<>
51P-1 51P-2

CONTROL AND INDICATION 1) MEASUREMENT

∆Io 1× 1×
Io>→ Io>→ Object Ctrl 2) - I, U, Io, Uo, P, Q, E, pf, f
67N-1 67N-2 - Sequence current/voltage measurement
3I CB 2 - Limit value supervision
Uo DC - RTD/mA measurement (optional)
8
ES Analog interface types B
1)
Check availability of binary inputs/outputs Current transformer 7
2× 2× 2× 1× 2× 2×
from technical documentation
3U< 3U> Uo> f> 2)
Control and indication function for Voltage transformer 3
27 59 59G 81O primary object

Io 2× 2× 2× 2×
df/dt> f< SYNC
81R 81U 25

2× 2×
Z<GT U/f> dUo(3H)>/Uo(3H)<
21GT 24 27/59THD

3× 2× 2×
U<RT Q>→, 3U< U2>
27RT 32Q, 27 47O-

2× 2×
U1> U1< Io>>> 3I>>>
47O+ 47U+ 50N/51N 50P/51P


Io> Io>> Io>R 3I>→
51N-1 51N-2 64R 67-1

3I>>→ 3I2f> VS
67-2 68 78V
REMARKS

Optional 2× No. of instances Calculated


3dlHi>G/M dIoHi> 3dI>T function enabled by default
Io/Uo value
87GH/87MH 87NH 87T

16× Function(s) not enabled by 1× No. of instances not enabled


MAP default in preconfiguration, by default in preconfiguration,
MAP can be enabled afterwards can be enabled afterwards

GUID-73E671D3-F46A-4778-8A7E-03AAED8AAACA V1 EN

Figure 4. Functionality overview for preconfiguration A

8 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

REG630 GENERATOR PROTECTION AND CONTROL IED


Empty configuration
PRE-
CONFIGURATION
n

PROTECTION LOCAL HMI *) ALSO AVAILABLE

- 5 × prog. push buttons on LHMI


2× - Disturbance and fault recorders
I→O - IED self-supervision
94 - Local/Remote push button on LHMI
- Sequence event recorder
2× 2× 2× - User management
Z<GT U/f> 3U< dUo(3H)>/Uo(3H)< - WebHMI
21GT 24 27 27/59THD

3× 2× 3× 3× AND
3I
U<RT Q>→, 3U< P> P< OR
27RT 32Q, 27 32R/32O 32U *) Fixed or detached LHMI is available.

2× 2× 2× 2×
X< I2>G/M U2> U1>
CONDITION MONITORING COMMUNICATION
40 46G/46M 47O- 47O+
3U AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1 0 0 1 1 0 0
2× 2× IEC 61850-8-1 1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Uo U1< 3Ith>T/G Io>>> 3I>>> FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0 1 1 0 1 0
1 0 1 1 0 1 1 0 1 1 0 1 0 0
47U+ 49T/G 50N/51N 50P/51P 60 CBCM E DNP3 1 0 1 0 0 0 1 1 0 0 1 1 0 0 1 0
1 0 1 1 0 0 1 0 1 1 1 0 0 1 0
Interfaces: 1 1 0 0 1 1 1 0 1 1 0 1 0
2× 2× 3×
Ethernet: TX (RJ45),1 0 1(LC)
FX 1 0 1 1 0 1 1 0 1 0 0
3I>/Io>BF Io> Io>> 3I> MCS 3I OPTS TCS
Io Serial: Serial glass fiber (ST),
51BF/51NBF 51N-1 51N-2 51P-1 MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
2× 2× 2× 3×
3I>> I(U)> 3U> Uo> Io>R U<>
51P-2 51V 59 59G 64R U<>

2× 2×
3I>→ 3I>>→ Io>→ Io>→ 3I2f>
67-1 67-2 67N-1 67N-2 68 CONTROL AND INDICATION 1) MEASUREMENT

∆Io 4× 4× 4×
Object Ctrl 2) - I, U, Io, Uo, P, Q, E, pf, f
VS f> df/dt> f< - Sequence current/voltage measurement
3I 78V 81O 81R 81U CB 2 - Limit value supervision
DC - RTD/mA measurement (optional)
8
ES Analog interface types A B C
3dl>G/M 3dlHi>G/M dIoHi>
87G/87M 87GH/87MH 87NH 1)
Check availability of binary inputs/outputs Current transformer 51) 7 8
from technical documentation
2)
Control and indication function for Voltage transformer 4 3 2
16× primary object 1)
One of available current transformer
3dI>T MAP inputs is sensitive (0.1 / 0.5 A)
Io 87T MAP

SYNC
25

REMARKS
Optional 3× Total nr. of
function instances

GUID-21213F0B-B9FF-4310-9561-24A39E51157B V1 EN

Figure 5. Functionality overview for preconfiguration n

Table 1. REG630 preconfiguration ordering options

Description Preconfiguration

Preconfiguration A for generator A

Number of instances available n

ABB 9
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 2. Functions used in preconfigurations

Description A n

Protection

Three-phase non-directional overcurrent protection, low stage 1 1

Three-phase non-directional overcurrent protection, high stage 1 2

Three-phase non-directional overcurrent protection, instantaneous stage - 1

Voltage dependent overcurrent protection 2 2

Three-phase directional overcurrent protection, low stage - 2

Three-phase directional overcurrent protection, high stage - 1

Non-directional earth-fault protection, low stage - 1

Non-directional earth-fault protection, high stage - 1

Non-directional earth-fault protection, instantaneous stage - 1

Directional earth-fault protection, low stage 1 2

Directional earth-fault protection, high stage 1 1

Third harmonic based stator earth-fault protection - 1

High-impedance based restricted earth-fault protection - 1

Rotor earth-fault protection - 1

Negative-sequence overcurrent protection for machines 2 2

Three-phase thermal overload protection, two time constants 1 1

Three-phase current inrush detection - 1

Transformer differential protection for two-winding transformers - 1

High-impedance or flux-balance based differential protection for machines - 1

Stabilized differential protection for machines 1 1

Three-phase overvoltage protection 2 2

Three-phase undervoltage protection 2 2

Positive-sequence overvoltage protection - 2

Positive-sequence undervoltage protection - 2

Negative-sequence overvoltage protection - 2

Residual overvoltage protection 2 3

Directional reactive power undervoltage protection - 2

Reverse power/directional overpower protection 2 3

Underpower protection 2 3

Frequency gradient protection 2 4

Overfrequency protection 2 4

Underfrequency protection 2 4

Low voltage ride through protection function - 3

Overexcitation protection - 2

Voltage vector shift protection - 1

Three-phase underexcitation protection 2 2

10 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 2. Functions used in preconfigurations, continued


Description A n

Three-phase underimpedance protection - 2

Circuit breaker failure protection 1 2

Tripping logic 1 2

Multipurpose analog protection - 16

Control

Bay control 1 1

Interlocking interface 3 10

Circuit breaker/disconnector control 3 10

Circuit breaker 1 2

Disconnector 2 8

Local/remote switch interface - 1

Synchrocheck - 1

Generic process I/O

Single point control (8 signals) - 5

Double point indication - 15

Single point indication - 64

Generic measured value - 15

Logic Rotating Switch for function selection and LHMI presentation - 10

Selector mini switch - 10

Pulse counter for energy metering - 4

Event counter - 1

Supervision and monitoring

Runtime counter for machines and devices - 1

Circuit breaker condition monitoring 1 2

Fuse failure supervision 1 1

Current circuit supervision - 2

Trip-circuit supervision 2 3

Station battery supervision - 1

Energy monitoring 1 1

Measured value limit supervision - 40

Measurement

Three-phase current measurement 1 2

Three-phase voltage measurement (phase-to-earth) - 2

Three-phase voltage measurement (phase-to-phase) 1 2

Residual current measurement 1 1

Residual voltage measurement 1 1

Power monitoring with P, Q, S, power factor, frequency 1 1

Sequence current measurement 1 1

ABB 11
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 2. Functions used in preconfigurations, continued


Description A n

Sequence voltage measurement 1 1

Disturbance recorder function

Analog channels 1-10 (samples) 1 1

Analog channels 11-20 (samples) - 1

Analog channels 21-30 (calc. val.) - 1

Analog channels 31-40 (calc. val.) - 1

Binary channels 1-16 1 1

Binary channels 17-32 1 1

Binary channels 33-48 1 1

Binary channels 49-64 1 1

Station communication (GOOSE)

Binary receive - 10

Double point receive - 32

Interlock receive - 59

Integer receive - 32

Measured value receive - 60

Single point receive - 64

n = total number of available function instances regardless of the preconfiguration selected


1, 2, ... = number of included instances

4. Protection functions stability and reliability, and thus avoid grid collapse. The low-
REG630 offers wide protection functionality for synchronous voltage ride-through protection allows monitoring of distributed
generators against internal faults and abnormal conditions of generation during low-voltage or fault ride-through, in order to
external systems. The generator management protection relay determine whether and when to disconnect from the grid. A
features non-directional and directional overcurrent and earth- reactive power undervoltage protection (QU) can be used at
fault protection functions, over- and undervoltage protection grid connection point of distributed power generation units. The
functions and specific functions for the protection of voltage vector shift protection detects islanding from the grid. It
generators, for example, voltage-controlled overcurrent measures continuously the duration of voltage cycle. At the
protection, reverse/directional overpower protection, instance of islanding, the duration of measured voltage cycle
differential protection, underexcitation protection, becomes shorter or longer than the previous one, i.e. the
overexcitation protection, high-impedance-based restricted measured voltage cycle shifts with time.
earth-fault protection, underimpedance protection (line back-
up protection), thermal overload protection, negative-phase
sequence protection, frequency protection and underpower
protection. Rotor earth-fault protection function to be used with
a separate fundamental frequency voltage injection device is
also included.

REG630 incorporates third harmonic-based stator earth-fault


protection as an optional function. Transformer differential
protection for two-winding transformers is another optional
function applicable for generator-transformer blocks.

Low-voltage ride-through, reactive power undervoltage and


voltage vector shift protection can be used to ensure grid
12 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

5. Control trigger the recording. In addition, the disturbance recorder


The protection relay incorporates local and remote control settings include pre- and post triggering times.
functions. The protection relay offers a number of freely
assignable binary inputs/outputs and logic circuits for The disturbance recorder can store up to 100 recordings. The
establishing bay control and interlocking functions for circuit number of recordings may vary depending on the length of the
breakers and motor operated switch-disconnectors. The recording and the number of signals included. The disturbance
protection relay supports both single and double busbar recorder controls the Start and Trip LEDs on the front-panel
substation busbar layouts. The number of controllable primary user interface. The operation of the LEDs is fully configurable
apparatuses depends on the number of available inputs and enabling activation when one or several criteria, that is,
outputs in the selected configuration. Besides conventional protection function starting or tripping, are fulfilled.
hardwired signaling also GOOSE messaging according to IEC
The recorded information is stored in a nonvolatile memory and
61850-8-1 can be used for signal interchange between
can be uploaded for subsequent fault analysis.
protection relays to obtain required interlockings.

Further, the protection relay incorporates a synchro-check 8. Event log


function to ensure that the voltage, phase angle and frequency The protection relay features an event log which enables
on either side of an open circuit breaker satisfy the conditions logging of event information. The event log can be configured to
for safe generator connection to the network. log information according to user predefined criteria including
relay signals. To collect sequence-of-events (SoE) information,
6. Measurement the protection relay incorporates a nonvolatile memory with a
The protection relay continuously measures the phase currents, capacity of storing 1000 events with associated time stamps
the symmetrical components of the currents and the residual and user definable event texts. The nonvolatile memory retains
current. The protection relay also measures phase and phase- its data also in case the protection relay temporarily loses its
to-phase voltages, symmetrical components of the voltages auxiliary supply. The event log facilitates detailed pre- and post-
and the residual voltage. In addition, the protection relay fault analyses of faults and disturbances.
monitors active and reactive power, power demand value over
The SoE information can be accessed locally via the user
a user-selectable pre-set time frames as well as cumulative
interface on the protection relay's front panel or remotely via the
active and reactive energy of both directions. Line frequency,
communication interface of the protection relay. The
the thermal overload of the protected object, and the phase
information can further be accessed, either locally or remotely,
unbalance value based on the ratio between the negative
using the web-browser based user interface.
sequence and positive sequence current are also calculated.
Cumulative and averaging calculations utilize the non-volatile The logging of communication events is determined by the used
memory available in the protection relay. Calculated values are communication protocol and the communication engineering.
also obtained from the protection and condition monitoring The communication events are automatically sent to station
functions of the protection relay. automation and SCADA systems once the required
communication engineering has been done.
The values measured are accessed locally via the front-panel
user interface of the protection relay or remotely via the
communication interface of the protection relay. The values are 9. Disturbance report
also accessed locally or remotely using the Web-browser The disturbance report includes information collected during
based user interface. the fault situation. The report includes general information such
as recording time, pre-fault time and post fault time. Further,
the report includes pre-fault magnitude, pre-fault angle, fault
7. Disturbance recorder
magnitude and fault angle trip values. By default, the
The protection relay is provided with a disturbance recorder
disturbance reports are stored in a nonvolatile memory. The
featuring up to 40 analog and 64 binary signal channels. The
numerical disturbance report can be accessed via the local
analog channels can be set to record the waveform of the
front panel user interface. A more comprehensive disturbance
currents and voltage measured. The analog channels can be
report with waveforms is available using PCM600.
set to trigger the recording when the measured value falls below
or exceeds the set values. The binary signal channels can be
set to start a recording on the rising or the falling edge of the 10. Circuit-breaker monitoring
binary signal. The binary channels are set to record external or The condition monitoring functions of the protection relay
internal relay signals, for example the start or operate signals of constantly monitors the performance and the condition of the
the protection functions, or external blocking or control signals. circuit breaker. The monitoring comprises the spring charging
Binary relay signals such as a protection start or trip signal, or time, SF6 gas pressure, the travel-time, operation counter,
an external relay control signal over a binary input can be set to accumulated energy calculator, circuit-breaker life estimator
and the inactivity time of the circuit breaker.

ABB 13
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

The monitoring functions provide operational circuit breaker Engineer and User Administrator. The user group association
history data, which can be used for scheduling preventive for each individual user enables the use of theprotection relay
circuit-breaker maintenance. according to the profile of the user group.

11. Trip-circuit supervision 16. Inputs and outputs


The trip-circuit supervision continuously monitors the The protection relay can be equipped with three different
availability and operability of the trip circuit. It provides open- combinations of current and voltage inputs. The available
circuit monitoring both when the circuit breaker is in its closed options are five current and four voltage inputs, seven current
and in its open position. It also detects loss of circuit-breaker and three voltage inputs, and eight current and two voltage
control voltage. inputs.

The phase-current inputs are rated 1/5 A. The option with five
12. Self-supervision current and four voltage inputs has one input rated to 0.1/0.5 A.
The relay’s built-in self-supervision system continuously The 0.1/0.5 A input can be used for example for stator earth-
monitors the state of the relay hardware and the operation of fault protection.
the relay software. Any fault or malfunction detected is used for
alerting the operator. The voltage inputs, for either phase-to-phase voltages or
phase-to-earth voltages, and the residual-voltage input cover
Self-supervision events are saved into an internal event list the rated voltages 100 V, 110 V, 115 V and 120 V. The rated
which can be accessed locally via the user interface on the values of the current and voltage inputs are selected in the relay
protection relay's front panel. The event list can also be software.
accessed using the Web HMI or PCM600.
The optional RTD/mA module facilitates the measurement of up
to eight analog signals via the RTD/mA inputs and provides four
13. Fuse failure supervision
mA outputs. With RTD sensors the RTD/mA inputs can for
The fuse failure supervision detects failures between the
instance be used for temperature measurement stator
voltage measurement circuit and the relay. The failures are
windings, thus extending the functionality of the thermal
detected either by the negative sequence-based algorithm or
overload protection and preventing premature aging of the
by the delta voltage and delta current algorithm. Upon the
windings. Furthermore, the RTD/mA inputs can be used for
detection of a failure, the fuse failure supervision function
measuring the ambient air or cooling media temperature, or
activates an alarm and blocks voltage-dependent protection
bearing temperatures. The RTD/mA inputs can be used for
functions from unintended operation.
supervision of analog mA signals provided by external
transducers. The RTD/mA inputs can be alternatively used also
14. Current circuit supervision as resistance input or as an input for voltage transducer. The
Current circuit supervision is used for detecting faults in the RTD/mA module enables the use of the multipurpose analog
current transformer secondary circuits. On detecting of a fault protection functions. These protection functions can be used
the current circuit supervision function can also activate an for tripping and alarm purposes based on RTD/mA measuring
alarm LED and block certain protection functions to avoid data, or analog values communicated via GOOSE messaging.
unintended operation. The current circuit supervision function The mA outputs can be used for transferring freely selectable
calculates the sum of the phase currents and compares the measured or calculated analog values to devices provided with
sum with the measured single reference current from a core mA input capabilities.
balance current transformer or from another set of phase
current transformers. The enhanced scalability of the 6U variant protection relays are
intended for optimized medium voltage metal-clad switchgear
applications where additional binary inputs and outputs are
15. Access control often required.
To protect the protection relay from unauthorized access and to
maintain information integrity, the protection relay is provided All binary input and output contacts are freely configurable
with an authentication system including user management. using the signal matrix of the application configuration function
Using the IED User Management tool in the Protection and in PCM600.
Control IED Manager PCM600, an individual password is
See the Input/output overview tables, the selection and
assigned to each user by the administrator. Further, the user
ordering data and the terminal diagrams for more information
name is associated to one or more of the four available user
about the inputs and outputs.
groups: System Operator, Protection Engineer, Design

14 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 3. Analog input configuration

Analog input configuration CT (1/5 A) CT sensitive (0.1/0.5 A) VT RTD/mA mA outputs


inputs

AA 4 1 4 - -

AB 7 - 3 - -

AC 8 - 2 - -

BA 4 1 4 8 4

BB 7 - 3 8 4

BC 8 - 2 8 4

Table 4. Binary input/output options for 4U variants

Binary I/O options Binary input configuration BI BO

Default AA 14 9

With one optional binary I/O module AB 23 18

With two optional binary I/O modules1) AC 32 27

1) Not possible if RTD/mA module is selected.

Table 5. Binary input/output options for 6U variants

Binary I/O options Binary input configuration BI BO

Default AA 14 9

With one optional binary I/O module AB 23 18

With two optional binary I/O modules AC 32 27

With three optional binary I/O modules AD 41 36

With four optional binary I/O modules1) AE 50 45

1) Not possible if RTD/mA module is selected.

17. Communication values using GOOSE messaging. Analog GOOSE messaging


The protection relay supports the IEC 61850 substation enables fast transfer of analog measurement values over the
automation standard including horizontal GOOSE station bus, thus facilitating for example sharing of RTD input
communication as well as the well-established DNP3 (TCP/IP) values, such as surrounding temperature values, to other relay
and IEC 60870-5-103 protocols. All operational information applications. The protection relay interoperates with other IEC
and controls are available through these protocols. 61850 compliant devices, tools and systems and
simultaneously reports events to five different clients on the IEC
Disturbance files are accessed using the IEC 61850 or IEC 61850 station bus. For a system using DNP3 over TCP/IP,
60870-5-103 protocols. Disturbance files are also available to events can be sent to four different masters. For systems using
any Ethernet based application in the standard COMTRADE IEC 60870-5-103, the protection relay can be connected to one
format. The protection relay can send binary signals to other master in a station bus with star-topology.
protection relays (so called horizontal communication) using the
IEC 61850-8-1 GOOSE (Generic Object Oriented Substation All communication connectors, except for the front port
Event) profile. Binary GOOSE messaging can, for example, be connector, are placed on integrated communication modules.
employed for protection and interlocking-based protection The protection relay is connected to Ethernet-based
schemes. The protection relay meets the GOOSE performance communication systems via the RJ-45 connector
requirements for tripping applications in distribution (10/100BASE-TX) or the fibre-optic multimode LC connector
substations, as defined by the IEC 61850 standard. Further, the (100BASE-FX).
protection relay supports the sending and receiving of analog

ABB 15
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

IEC 60870-5-103 is available from optical serial port where it is With special time synchronization wiring
possible to use serial glass fibre (ST connector) or serial plastic • IRIG-B (Inter-Range Instrumentation Group - Time Code
fibre (snap-in connector). Format B)

The protection relay supports the following time


synchronization methods with a timestamping resolution of 1 IEC 60870-5-103 serial communication has a time-stamping
ms. resolution of 10 ms.

Ethernet communication based


• SNTP (simple network time protocol)
• DNP3

Table 6. Supported communication interface and protocol alternatives

Interfaces/protocols1) Ethernet Ethernet Serial snap-in Serial ST


100BASE-TX RJ-45 100BASE-FX LC

IEC 61850 ● ●

DNP3 ● ●

IEC 60870-5-103 ● ●
● = Supported
1) Please refer to the Selection and ordering data chapter for more information

16 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

18. Technical data

Table 7. Dimensions

Description Value

Width 220 mm

Height 177 mm (4U)


265.9 mm (6U)

Depth 249.5 mm

Weight box 6.2 kg (4U)


5.5 kg (6U)1)

Weight LHMI 1.0 kg (4U)

1) Without LHMI

Table 8. Power supply

Description 600PSM03 600PSM02

Uauxnominal 100, 110, 120, 220, 240 V AC, 50 and 60 Hz 48, 60, 110, 125 V DC

110, 125, 220, 250 V DC

Uauxvariation 85...110% of Un (85...264 V AC) 80...120% of Un (38.4...150 V DC)

80...120% of Un (88...300 V DC)

Maximum load of auxiliary voltage supply 35 W

Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)

Maximum interruption time in the auxiliary DC 50 ms at Uaux


voltage without resetting the protection relay

Power supply input must be protected by an For example, type S282 UC-K.
external miniature circuit breaker The rated maximum load of aux voltage which is given as 35 watts. Depending on the voltage
used, select a suitable MCB based on the respective current. Type S282 UC-K has a rated
current of 0.75 A at 400 V AC.

ABB 17
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 9. Energizing inputs

Description Value

Rated frequency 50/60 Hz

Operating range Rated frequency ±5 Hz

Current inputs Rated current, In 0.1/0.5 A1) 1/5 A2)

Thermal withstand capability:

• Continuously 4A 20 A

• For 1 s 100 A 500 A

• For 10 s 25 A 100 A

Dynamic current withstand:

• Half-wave value 250 A 1250 A

Input impedance <100 mΩ <20 mΩ

Voltage inputs Rated voltage, Un 100 V AC/ 110 V AC/ 115 V AC/ 120 V AC

Voltage withstand:

• Continuous 425 V AC

• For 10 s 450 V AC

Burden at rated voltage <0.05 VA

1) Residual current
2) Phase currents or residual current

Table 10. Binary inputs

Description Value

Operating range Maximum input voltage 300 V DC

Rated voltage 24...250 V DC

Current drain 1.6...1.8 mA

Power consumption/input <0.3 W

Threshold voltage 15...221 V DC (parametrizable in the range in steps of 1% of the rated


voltage)

Threshold voltage accuracy ±3.0%

Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)

18 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 11. RTD inputs

Description Value

RTD inputs Supported RTD sensor 100 Ω platinum TCR 0.00385 (DIN 43760)

250 Ω platinum TCR 0.00385

100 Ω nickel TCR 0.00618 (DIN 43760)

120 Ω nickel TCR 0.00618

10 Ω copper TCR 0.00427

Supported resistance range 0…10 kΩ

Maximum leadresistance (three-wire 100 Ω platinum 25 Ω per lead


measurement)
250 Ω platinum 25 Ω per lead

100 Ω nickel 25 Ω per lead

120 Ω nickel 25 Ω per lead

10 Ω copper 2.5 Ω per lead

Resistance 25 Ω per lead

Isolation 4 kV Inputs to all outputs and


protective earth

RTD / resistance sensing current Maximum 0.275 mA rms

Operation accuracy / temperature • ±1°C Pt and Ni sensors for


measuring range -40°C...
200°C and -40°C...70°C
ambient temperature

• ±2°C CU sensor for measuring


range -40°C...200°C in room
temperature

• ±4°C CU sensors -40°C...70°C


ambient temperature

• ±5°C From -40°C...-100ºC of


measurement range

Operation accuracy / Resistance ±2.5 Ω 0...400 Ω range

±1.25% 400 Ω...10KΩ ohms range

Response time < Filter time +350 ms

mA inputs Supported current range -20…+20 mA

Current input impedance 100 Ω ±0.1%

Operation accuracy ±0.1% ±20 ppm per °C of full-scale Ambient temperature -40°C...
70°C

Voltage inputs Supported voltage range -10 V DC...+10 V DC

Operation accuracy ±0.1% ±40 ppm per °C of full-scale Ambient temperature -40°C...
70°C

ABB 19
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 12. Signal output and IRF output

IRF relay change over - type signal output relay

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 5A

Make and carry for 3.0 s 10 A

Make and carry 0.5 s 15 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at U ≤0.5 A/≤0.1 A/≤0.04 A
< 48/110/220 V DC

Minimum contact load 100 mA at 24 V AC/DC

Table 13. Power output relays without TCS function

Description Value

Rated voltage 250 V AC/DC

Continuous contact carry 8A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at ≤1 A/≤0.3 A/≤0.1 A
U< 48/110/220 V DC

Minimum contact load 100 mA at 24 V AC/DC

Table 14. Power output relays with TCS function

Description Value

Rated voltage 250 V DC

Continuous contact carry 8A

Make and carry for 3.0 s 15 A

Make and carry for 0.5 s 30 A

Breaking capacity when the control-circuit time constant L/R<40 ms, at U ≤1 A/≤0.3 A/≤0.1 A
< 48/110/220 V DC

Minimum contact load 100 mA at 24 V DC

Control voltage range 20...250 V DC

Current drain through the supervision circuit ~1.0 mA

Minimum voltage over the TCS contact 20 V DC

Table 15. mA outputs

Description Value

mA outputs Output range -20 mA…+20 mA

Operation accuracy ±0.2 mA

Maximum load (including wiring resistance) 700 Ω

Hardware response time ~80 ms

Isolation level 4 kV

20 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 16. Ethernet interfaces

Ethernet interface Protocol Cable Data transfer rate

LAN1 (X1) TCP/IP protocol Fibre-optic cable with LC 100 MBits/s


connector or shielded twisted pair
CAT 5e cable or better

Table 17. LAN (X1) fibre-optic communication link

Wave length Fibre type Connector Permitted path attenuation1) Distance

1300 nm MM 62.5/125 μm or LC <7.5 dB 2 km


MM 50/125 μm glass
fibre core

1) Maximum allowed attenuation caused by connectors and cable together

Table 18. X4/IRIG-B interface

Type Protocol Cable

Screw terminal, pin row header IRIG-B Shielded twisted pair cable
Recommended: CAT 5, Belden RS-485 (9841- 9844) or Alpha Wire
(Alpha 6222-6230)

Table 19. X9 Optical serial interface characteristics

Wave length Fibre type Connector Permitted path attenuation Distance

820 nm MM 62.5/125 ST 4 dB/km 1000 m

820 mm MM 50/125 ST 4 dB/km 400 m

660 mm 1 mm Snap-in 10 m

Table 20. Degree of protection of flush-mounted protection relay

Description Value

Front side IP 40

Rear side, connection terminals IP 20

Table 21. Degree of protection of the LHMI

Description Value

Front and side IP 42

Table 22. Environmental conditions

Description Value

Operating temperature range -25...+55ºC (continuous)

Short-time service temperature range -40...+70ºC (<16h)


Note: Degradation in MTBF and HMI performance outside the
temperature range of -25...+55ºC

Relative humidity <93%, non-condensing

Atmospheric pressure 86...106 kPa

Altitude up to 2000 m

Transport and storage temperature range -40...+85ºC

ABB 21
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 23. Environmental tests

Description Type test value Reference

Dry heat test (humidity <50%) • 96 h at +55ºC IEC 60068-2-2


• 16 h at +85ºC

Cold test • 96 h at -25ºC IEC 60068-2-1


• 16 h at -40ºC

Damp heat test, cyclic • 6 cycles at +25…55°C, Rh >93% IEC 60068-2-30

Storage test • 96 h at -40ºC IEC 60068-2-1


• 96 h at +85ºC IEC 60068-2-2

22 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 24. Electromagnetic compatibility tests

Description Type test value Reference

100 kHz and 1 MHz burst disturbance test IEC 61000-4-18, level 3
IEC 60255-22-1

• Common mode 2.5 kV

• Differential mode 1.0 kV

3 MHz, 10 MHz and 30 MHz burst disturbance IEC 61000-4-18


test IEC 60255-22-1, class III

• Common mode 2.5 kV

Electrostatic discharge test IEC 61000-4-2, level 4


IEC 60255-22-2
IEEE C37.90.3.2001

• Contact discharge 8 kV

• Air discharge 15 kV

Radio frequency interference tests

• Conducted, common mode 10 V (rms), f=150 kHz...80 MHz IEC 61000-4-6 , level 3
IEC 60255-22-6

• Radiated, pulse-modulated 10 V/m (rms), f=900 MHz ENV 50204


IEC 60255-22-3

• Radiated, amplitude-modulated 10 V/m (rms), f=80...2700 MHz IEC 61000-4-3, level 3


IEC 60255-22-3

Fast transient disturbance tests IEC 61000-4-4


IEC 60255-22-4, class A

• All ports 4 kV

Surge immunity test IEC 61000-4-5, level 3/2


IEC 60255-22-5

• Communication 1 kV line-to-earth

• Binary inputs, voltage inputs 2 kV line-to-earth


1 kV line-to-line

• Other ports 4 kV line-to-earth, 2 kV line-to-line

Power frequency (50 Hz) magnetic field IEC 61000-4-8

• 1...3 s 1000 A/m

• Continuous 300 A/m

Pulse magnetic field immunity test 1000 A/m IEC 61000-4-9


6.4/16 µs

Damped oscillatory magnetic field immunity IEC 61000-4-10


test

• 2s 100 A/m

• 1 MHz 400 transients/s

Power frequency immunity test Binary inputs only IEC 60255-22-7, class A
IEC 61000-4-16

• Common mode 300 V rms

• Differential mode 150 V rms

Conducted common mode disturbances 15 Hz...150 kHz IEC 61000-4-16


Test level 3 (10/1/10 V rms)

ABB 23
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 24. Electromagnetic compatibility tests, continued


Description Type test value Reference

Voltage dips and short interruptions 30%/10 ms IEC 61000-4-11


60%/100 ms
60%/1000 ms
>95%/5000 ms

Electromagnetic emission tests EN 55011, class A


IEC 60255-25

• Conducted, RF-emission (mains terminal)

0.15...0.50 MHz <79 dB(µV) quasi peak


<66 dB(µV) average

0.5...30 MHz <73 dB(µV) quasi peak


<60 dB(µV) average

• Radiated RF-emission

30...230 MHz <40 dB(µV/m) quasi peak, measured at 10 m


distance

230...1000 MHz <47 dB(µV/m) quasi peak, measured at 10 m


distance

Table 25. Insulation tests

Description Type test value Reference

Dielectric tests IEC 60255-5


IEC 60255-27

• Test voltage 2 kV, 50 Hz, 1 min


500 V, 50 Hz, 1 min, communication

Impulse voltage test IEC 60255-5


IEC 60255-27

• Test voltage 5 kV, 1.2/50 μs, 0.5 J


1 kV, 1.2/50 μs, 0.5 J, communication

Insulation resistance measurements IEC 60255-5


IEC 60255-27

• Isolation resistance >100 MΩ, 500 V DC

Protective bonding resistance IEC 60255-27

• Resistance <0.1Ω, 4 A, 60 s

Table 26. Mechanical tests

Description Reference Requirement

Vibration tests (sinusoidal) IEC 60068-2-6 (test Fc) Class 1


IEC 60255-21-1

Shock and bump test IEC 60068-2-27 (test Ea shock) Class 1


IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2

Seismic test IEC 60255-21-3 (method A) Class 1

24 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 27. Product safety

Description Reference

LV directive 2006/95/EC

Standard EN 60255-27 (2005)


EN 60255-1 (2009)

Table 28. EMC compliance

Description Reference

EMC directive 2004/108/EC

Standard EN 50263 (2000)


EN 60255-26 (2007)

Table 29. RoHS compliance

Description

Complies with RoHS directive 2002/95/EC

ABB 25
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Protection functions

Table 30. Three-phase non-directional overcurrent protection (PHxPTOC)

Characteristic Value

Operation accuracy At the frequency f = fn

PHLPTOC ±1.5% of the set value or ±0.002 × In

PHHPTOC ±1.5% of set value or ±0.002 × In


and (at currents in the range of 0.1…10 × In)
PHIPTOC ±5.0% of the set value
(at currents in the range of 10…40 × In)

Start time 1)2) PHIPTOC:


IFault = 2 × set Start value Typically 17 ms (±5 ms)
IFault = 10 × set Start value
Typically 10 ms (±5 ms)

PHHPTOC:
IFault = 2 × set Start value Typically 19 ms (±5 ms)

PHLPTOC:
IFault = 2 × set Start value Typically 23 ms (±15 ms)

Reset time <45 ms

Reset ratio Typically 0.96

Retardation time <30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)

Suppression of harmonics RMS: No suppression


DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression

1) Set Operate delay time = 0.02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In , fn = 50 Hz, fault current in one phase
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Includes the delay of the heavy-duty output contact

26 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 31. Three-phase non-directional overcurrent protection (PHxPTOC) main settings

Parameter Function Value (Range) Step

Start Value PHLPTOC 0.05...5.00 pu 0.01

PHHPTOC 0.10...40.00 pu 0.01

PHIPTOC 0.10...40.00 pu 0.01

Time multiplier PHLPTOC 0.05...15.00 0.01

PHHPTOC 0.05...15.00 0.01

Operate delay time PHLPTOC 0.04…200.00 s 0.01

PHHPTOC 0.02…200.00 s 0.01

PHIPTOC 0.02…200.00 s 0.01

Operating curve type1) PHLPTOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

PHHPTOC Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

PHIPTOC Definite time

1) For further reference, see the Operation characteristics table

Table 32. Voltage dependent overcurrent protection (PHPVOC)

Characteristic Value

Operation accuracy At the frequency f = fn

Current: ±1.5% of the set value or ±0.002 × In

Voltage: ±1.5% of the set value or ±0.002 × Un

Start time 1)2) Typically 20 ms (±10 ms)

Reset time <45 ms

Reset ratio Typically 0.96

Operate time accuracy in definite time mode ±1.0% of the set value of ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the set value of ±20 ms

Suppression of harmonics -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Measurement mode = default, current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements.
2) Includes the delay of the signal output contact.

ABB 27
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 33. Voltage dependent overcurrent protection (PHPVOC) main settings

Parameter Function Value (Range) Step

Start value PHPVOC 0.05...5.00 pu 0.01

Start value low PHPVOC 0.05...1.00 pu 0.01

Start value Mult PHPVOC 0.8...10.0 0.1

Voltage high limit PHPVOC 0.01...1.00 pu 0.01

Voltage low limit PHPVOC 0.01...1.00 pu 0.01

Time multiplier PHPVOC 0.05...15.00 0.01

Operate delay time PHPVOC 0.04...200.00 s 0.01

Operating curve type1) PHPVOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

1) For further reference, see the Operation characteristics table

Table 34. Three-phase directional overcurrent protection (DPHxPDOC)

Characteristic Value

Operation accuracy At the frequency f = fn

DPHLPDOC Current:
±1.5% of the set value or ±0.002 × In
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°

DPHHPDOC Current:
±1.5% of the set value or ±0.002 × In (at currents in the range of 0.1…10
× In)
±5.0% of the set value (at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle:
±2°

Start time1)2) IFault = 2.0 × set Start value Typically 24 ms (±15 ms)

Reset time <40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)

Suppression of harmonics RMS: No suppression


DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression

1) Measurement mode = default (depends of stage), current before fault = 0.0 × In, fn = 50 Hz, fault current in one phase with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20

28 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 35. Three-phase directional overcurrent protection (DPHxPDOC) main settings

Parameter Function Value (Range) Step

Start value DPHLPDOC 0.05...5.00 pu 0.01

DPHHPDOC 0.05...5.00 pu 0.01

Time multiplier DPHxPDOC 0.05...15.00 0.01

Operate delay time DPHxPDOC 0.04...200.00 s 0.01

Directional mode DPHxPDOC 1 = Non-directional


2 = Forward
3 = Reverse

Characteristic angle DPHxPDOC -179...180° 1

Operating curve type1) DPHLPDOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

DPHHPDOC Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

1) For further reference, refer to the Operation characteristics table

Table 36. Non-directional earth-fault protection (EFxPTOC)

Characteristic Value

Operation accuracy At the frequency f = fn

EFLPTOC ±1.5% of the set value or ±0.001 × In

EFHPTOC ±1.5% of set value or ±0.002 × In


and (at currents in the range of 0.1…10 × In)
EFIPTOC ±5.0% of the set value
(at currents in the range of 10…40 × In)

Start time 1)2) EFIPTOC: Typically 12 ms (±5 ms)


IFault = 2 × set Start value

EFHPTOC: Typically 19 ms (±5 ms)


IFault = 2 × set Start value

EFLPTOC: Typically 23 ms (±15 ms)


IFault = 2 × set Start value

Reset time <45 ms

Reset ratio Typically 0.96

Retardation time <30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)

Suppression of harmonics RMS: No suppression


DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression

1) Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In, fn = 50 Hz, earth-fault current with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In, Start value multiples in range of 1.5...20

ABB 29
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 37. Non-directional earth-fault protection (EFxPTOC) main settings

Parameter Function Value (Range) Step

Start value EFLPTOC 0.010...5.000 pu 0.005

EFHPTOC 0.10...40.00 pu 0.01

EFIPTOC 0.10...40.00 pu 0.01

Time multiplier EFLPTOC 0.05...15.00 0.01

EFHPTOC 0.05...15.00 0.01

Operate delay time EFLPTOC 0.04...200.00 s 0.01

EFHPTOC 0.02...200.00 s 0.01

EFIPTOC 0.02...200.00 s 0.01

Operating curve type1) EFLPTOC Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

EFHPTOC Definite or inverse time


Curve type: 1, 3, 5, 9, 10, 12, 15, 17

EFIPTOC Definite time

1) For further reference, see the Operation characteristics table

Table 38. Directional earth-fault protection (DEFxPDEF)

Characteristic Value

Operation accuracy At the frequency f = fn

DEFLPDEF Current:
±1.5% of the set value or ±0.002 × In
Voltage
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°

DEFHPDEF Current:
±1.5% of the set value or ±0.002 × In
(at currents in the range of 0.1…10 × In)
±5.0% of the set value
(at currents in the range of 10…40 × In)
Voltage:
±1.5% of the set value or ±0.002 × Un
Phase angle: ±2°

Start time 1)2) DEFHPDEF and DEFLPTDEF: Typically 54 ms (±15 ms)


IFault = 2 × set Start value

Reset time Typically 40 ms

Reset ratio Typically 0.96

Retardation time <30 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms 3)

Suppression of harmonics RMS: No suppression


DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression

1) Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 × In , fn = 50 Hz, earth-fault current with
nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × In, Start value multiples in range of 1.5 to 20

30 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 39. Directional earth-fault protection (DEFxPDEF) main settings

Parameter Function Value (Range) Step

Start Value DEFLPDEF 0.010...5.000 pu 0.005

DEFHPDEF 0.10...40.00 pu 0.01

Directional mode DEFLPDEF and DEFHPDEF 1=Non-directional


2=Forward
3=Reverse

Time multiplier DEFLPDEF 0.05...15.00 0.01

DEFHPDEF 0.05...15.00 0.01

Operate delay time DEFLPDEF 0.06...200.00 s 0.01

DEFHPDEF 0.06...200.00 s 0.01

Operating curve type1) DEFLPDEF Definite or inverse time


Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15, 17, 18, 19

DEFHPDEF Definite or inverse time


Curve type: 1, 3, 5, 15, 17

Operation mode DEFLPDEF and DEFHPDEF 1=Phase angle


2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88

1) For further reference, refer to the Operation characteristics table

Table 40. Third harmonic based stator earth-fault protection (H3EFPSEF)

Characteristic Value

Operation accuracy At the frequency f = fn


±5% of the set value or ±0.004 × Un

Start time 1)2) Typically 23 ms (±15 ms)

Reset time <45 ms

Reset ratio Typically 0.96

Operate time accuracy in definite time mode ±1.0% of the set value of ±20 ms

1) fn= 50 Hz, results based on statistical distribution of 1000 measurements


2) Includes the delay of the signal output contact

Table 41. Third harmonic based stator earth-fault protection (H3EFPSEF) main settings

Parameter Function Value (Range) Step

Beta H3EFPSEF 0.50...10.00 0.01

Voltage N 3.H Lim H3EFPSEF 0.005...0.200 0.001

Operate delay time H3EFPSEF 0.08...300.00 s 0.01

Voltage selection H3EFPSEF No Voltage -


Measured ResU
Calculated ResU
Phase A
Phase B
Phase C

CB open factor H3EFPSEF 1.00...10.00 0.01

ABB 31
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 42. High-impedance based restricted earth-fault protection (HREFPDIF)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × In

Start time1)2) IFault = 2.0 × set Operate value Typically 22 ms (±5 ms)
IFault = 10.0 × set Operate value Typically 15 ms (±5 ms)

Reset time <60 ms

Reset ratio Typically 0.96

Retardation time <60 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

1) Current before fault = 0.0 × In , fn = 50 Hz


2) Includes the delay of the signal output contact

Table 43. High-impedance based restricted earth-fault protection (HREFPDIF) main settings

Parameter Function Value (Range) Step

Operate value HREFPDIF 0.5...50.0% 0.1

Minimum operate time HREFPDIF 0.020...300.000 s 0.001

Table 44. Rotor earth-fault protection (MREFPTOC)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × In

Start time1)2) Typically 25 ms (±15 ms)

Reset time <50 ms

Reset ratio Typically 0.96

Retardation time <50 ms

Operate time accuracy ±1.0% of the set value of ±20 ms

Suppression of harmonics -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Current before fault = 0.0 × In , fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact

Table 45. Rotor earth-fault protection (MREFPTOC) main settings

Parameter Function Value (Range) Step

Alarm start value MREFPTOC 0.010...2.000 pu 0.001

Operate start value MREFPTOC 0.010...2.000 pu 0.001

Alarm delay time MREFPTOC 0.04...200.00 s 0.01

Operate delay time MREFPTOC 0.04...200.00 s 0.01

32 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 46. Negative-sequence overcurrent protection for machines (MNSPTOC)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × In

Start time1)2) IFault = 5.0 × set Start value Typically 43 ms (±15 ms)

Reset time <70 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±35 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±30 ms 3)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Negative-sequence current before = 0.0 × In, fn = 50 Hz


2) Includes the delay of the signal output contact
3) Start value multiples in range of 1.10...5.00

Table 47. Negative-sequence overcurrent protection for machines (MNSPTOC) main settings

Parameter Function Value (Range) Step

Start value MNSPTOC 0.01...0.50 pu 0.01

Operating curve type MNSPTOC ANSI Def. Time -


IEC Def. Time
Inv. Curve A
Inv. Curve B

Operate delay time MNSPTOC 0.10...120.00 s 0.01

Cooling time MNSPTOC 5...7200 s 1

Table 48. Three-phase thermal overload protection, two time constants (T2PTTR)

Characteristic Value

Operation accuracy At the frequency f = fn

Current measurement: ±1.5% of the set value or ±0.002 × In (at currents


in the range of 0.01...4.00 × In)

Operate time accuracy1) ±2.0% or ±1000 ms

1) Overload current > 1.2 × Operate level temperature, Current reference > 0.50 pu

Table 49. Three-phase thermal overload protection, two time constants (T2PTTR) main settings

Parameter Function Value (Range) Step

Temperature rise T2PTTR 0.0...200.0° 0.1

Max temperature T2PTTR 0.0...200.0° 0.1

Operate temperature T2PTTR 80.0...120.0% 0.1

Weighting factor p T2PTTR 0.00...1.00 0.01

Short time constant T2PTTR 60...60000 s 1

Current reference T2PTTR 0.05...4.00 pu 0.01

ABB 33
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 50. Three-phase current inrush detection (INRPHAR)

Characteristic Value

Operation accuracy At the frequency f = fn

Current measurement:
±1.5% of the set value or ±0.002 × In
Ratio I2f/I1f measurement:
±5.0% of the set value

Reset time +35 ms / -0 ms

Reset ratio Typically 0.96

Operate time accuracy +30 ms / -0 ms

Table 51. Three-phase current inrush detection (INRPHAR) main settings

Parameter Function Value (Range) Step

Start value INRPHAR 5...100% 1

Operate delay time INRPHAR 0.02...60.00 s 0.001

Table 52. Transformer differential protection for two-winding transformers (TR2PTDF)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × In

Operate time1)2) Biased low stage Typically 35 ms (±5 ms)


Instantaneous high stage Typically 17 ms (±5 ms)

Reset time <30 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Differential current before fault = 0.0 × In , fn = 50 Hz. Injected differential current = 2.0 × set operate value
2) Includes the delay of the output contact value and fn = 50 Hz

34 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 53. Transformer differential protection for two-winding transformers (TR2PTDF) main settings

Parameter Function Value (Range) Step

Restraint mode TR2PTDF 2.h & 5.h & wav -


Waveform
2.h & waveform
5.h & waveform

High operate value TR2PTDF 500...3000% 10

Low operate value TR2PTDF 5...50% 1

Slope section 2 TR2PTDF 10...50% 1

End section 2 TR2PTDF 100...500% 1

Start value 2.H TR2PTDF 7...20% 1

Start value 5.H TR2PTDF 10...50% 1

Winding 1 type TR2PTDF Y -


YN
D
Z
ZN

Winding 2 type TR2PTDF Y -


YN
D
Z
ZN

Zro A elimination TR2PTDF Not eliminated -


Winding 1
Winding 2
Winding 1 and 2

Clock number TR2PTDF Clk Num 0 -


Clk Num 1
Clk Num 2
Clk Num 4
Clk Num 5
Clk Num 6
Clk Num 7
Clk Num 8
Clk Num 10
Clk Num 11

Table 54. High-impedance or flux-balance based differential protection for machines (MHZPDIF)

Characteristic Value

Operation accuracy ±1.5% of the set value or 0.002 × In

Start time 1)2) Typically 15 ms (±10 ms)

Reset time <65 ms

Reset ratio Typically 0.96

Retardation time <50 ms

Operate time accuracy in definite time mode ±1.0% of the set value of ±20 ms

1) Fn = 50 Hz, results based on statistical distribution of 1000 measurements


2) Includes the delay of the signal output contact

ABB 35
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 55. High-impedance or flux-balance based differential protection for machines (MHZPDIF) main settings

Parameter Function Value (Range) Step

Operate value MHZPDIF 0.5...50.0% 0.1

Minimum operate time MHZPDIF 0.02...300.00 s 0.01

Table 56. Stabilized differential protection for machines (MPDIF)

Characteristic Value

Operation accuracy At the frequency f = fn

±3% of the set value or ±0.002 × In

Operate time 1)2) Biased low stage Typically 40 ms (±10 ms)


Instantaneous high Typically 15 ms (±10 ms)
stage3)

Reset time <40 ms

Reset ratio Typically 0.96

Retardation time <20 ms

1) Fn = 50 Hz, results based on statistical distribution of 1000 measurements


2) Includes the delay of the high speed power output contact
3) Ifault = 2 × High operate value

Table 57. Stabilized differential protection for machines (MPDIF) main settings

Parameter Function Value (Range) Step

CT connection type MPDIF 1...2 1

High operate value MPDIF 100...1000% 1

Low operate value MPDIF 5...30% 1

Slope section 2 MPDIF 10.0...50.0% 0.1

End section 1 MPDIF 0...100% 1

End section 2 MPDIF 100...300% 1

Table 58. Three-phase overvoltage protection (PHPTOV)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × Un

Start time1)2) UFault = 2.0 × set Start value Typically 17 ms (±15 ms)

Reset time <40 ms

Reset ratio Depends of the set Relative hysteresis

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Start value = 1.0 × Un, Voltage before fault = 0.9 × Un, fn = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
3) Maximum Start value = 1.20 × Un, Start value multiples in range of 1.10...2.00

36 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 59. Three-phase overvoltage protection (PHPTOV) main settings

Parameter Function Value (Range) Step

Start value PHPTOV 0.05...1.60 pu 0.01

Time multiplier PHPTOV 0.05...15.00 0.01

Operate delay time PHPTOV 0.40...300.000 s 0.10

Operating curve type1) PHPTOV Definite or inverse time


Curve type: 5, 15, 17, 18, 19, 20

1) For further reference, see the Operation characteristics table

Table 60. Three-phase undervoltage protection (PHPTUV)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × Un

Start time1)2) UFault = 0.9 × set Start value Typically 24 ms (±15 ms)

Reset time <40 ms

Reset ratio Depends of the set Relative hysteresis

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse time mode ±5.0% of the theoretical value or ±20 ms3)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Start value = 1.0 × Un, Voltage before fault = 1.1 × Un, fn = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
3) Minimum Start value = 0.50 × Un, Start value multiples in range of 0.90...0.20

Table 61. Three-phase undervoltage protection (PHPTUV) main settings

Parameter Function Value (Range) Step

Start value PHPTUV 0.05...1.20 pu 0.01

Time multiplier PHPTUV 0.05...15.00 0.01

Operate delay time PHPTUV 0.040...300.000 s 0.010

Operating curve type1) PHPTUV Definite or inverse time


Curve type: 5, 15, 21, 22, 23

1) For further reference, see the Operation characteristics table

ABB 37
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 62. Positive-sequence overvoltage protection (PSPTOV)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × Un

Start time1)2) UFault = 1.1 × set Start value


UFault = 2.0 × set Start value Typically 29 ms (±15 ms)

Typically 24 ms (±15 ms)

Reset time <40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Positive-sequence voltage before fault = 0.0 × Un, fn = 50 Hz, positive-sequence overvoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact

Table 63. Positive-sequence overvoltage protection (PSPTOV) main settings

Parameter Function Value (Range) Step

Start value PSPTOV 0.800...1.600 pu 0.001

Operate delay time PSPTOV 0.040...120.000 s 0.001

Table 64. Positive-sequence undervoltage protection (PSPTUV)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × Un

Start time1)2) UFault = 0.9 × set Start value Typically 28 ms (±15 ms)

Reset time <40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Positive-sequence voltage before fault = 1.1 × Un, fn = 50 Hz, positive-sequence undervoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact

Table 65. Positive-sequence undervoltage protection (PSPTUV) main settings

Parameter Function Value (Range) Step

Start value PSPTUV 0.010...1.200 pu 0.001

Operate delay time PSPTUV 0.040...120.000 s 0.001

Voltage block value PSPTUV 0.01...1.0 pu 0.01

38 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 66. Negative-sequence overvoltage protection (NSPTOV)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × Un

Start time1)2) UFault = 1.1 × set Start value Typically 29 ms (± 15ms)


UFault = 2.0 × set Start value Typically 24 ms (± 15ms)

Reset time <40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Negative-sequence voltage before fault = 0.0 × Un, fn = 50 Hz, negative-sequence overvoltage of nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact

Table 67. Negative-sequence overvoltage protection (NSPTOV) main settings

Parameter Function Value (Range) Step

Start value NSPTOV 0.010...1.000 pu 0.001

Operate delay time NSPTOV 0.040...120.000 s 0.001

Table 68. Residual overvoltage protection (ROVPTOV)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × Un

Start time1)2) UFault = 1.1 × set Start value Typically 27 ms (± 15 ms)

Reset time <40 ms

Reset ratio Typically 0.96

Retardation time <35 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Residual voltage before fault = 0.0 × Un , fn = 50 Hz, residual voltage with nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact

Table 69. Residual overvoltage protection (ROVPTOV) main settings

Parameter Function Value (Range) Step

Start value ROVPTOV 0.010...1.000 pu 0.001

Operate delay time ROVPTOV 0.040...300.000 s 0.001

ABB 39
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 70. Directional reactive power undervoltage protection (DQPTUV)

Characteristic Value

Operation accuracy At the frequency f = fn


Power:
1.5% or 0.002 × Qn (±1.5%) for power, PF -0.71...0.71
Voltage:
±1.5% of the set value or ±0.002 × Un

Start time 1) Typically 22 ms

Reset time <40 ms

Reset ratio Typically 0.96

Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5 and so on

1) Start value = 0.05 × Sn, Reactive power before fault = 0.8 × Start value. Reactive power overshoot 2 times. Results based on statistical distribution of 1000 measurement.

Table 71. Directional reactive power undervoltage protection (DQPTUV) main settings

Parameter Function Value (Range) Step

Voltage start value DQPTUV 0.20...1.20 pu 0.01

Operate delay time DQPTUV 0.1...300.00 s 0.01

Min reactive power DQPTUV 0.01...0.50 pu 0.01

Min PS current DQPTUV 0.02...0.20 pu 0.01

Pwr sector reduction DQPTUV 0.0...10.0° 1.0

Table 72. Reverse power/directional overpower protection (DOPPDPR)

Characteristic Value

Operation accuracy At the frequency f = fn

±3% of the set value or ±0.002 × Sn

Start time1)2) Typically 20 ms (±15 ms)

Reset time <40 ms

Reset ratio Typically 0.94

Retardation time <45 ms

Operate time accuracy ±1.0% of the set value of ±20 ms

1) U = Un , F n = 50 Hz, results based on statistical distribution of 1000 measurements.


2) Includes the delay of the signal output contact.

Table 73. Reverse power/directional overpower protection (DOPPDPR) main settings

Parameter Function Value (Range) Step

Directional mode DOPPDPR Forward -


Reverse

Start value DOPPDPR 0.01...2.00 pu 0.01

Power angle DOPPDPR -90.00...90.00° 0.01

Operate delay time DOPPDPR 0.04...300.00 s 0.01

40 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 74. Underpower protection (DUPPDPR)

Characteristic Value

Operation accuracy At the frequency f = fn


±3% of the set value or ±0.002 × Sn

Start time 1)2) Typically 20 ms (±15 ms)

Reset time <40 ms

Reset ratio Typically 0.94

Retardation time <45 ms

Operate time accuracy ±1.0% of the set value of ±20 ms

1) U = U n , f n = 50 Hz, results based on statistical distribution of 1000 measurements.


2) Includes the delay of the signal output contact.

Table 75. Underpower protection (DUPPDPR) main settings

Parameter Function Value (Range) Step

Start value DUPPDPR 0.01...2.00 pu 0.01

Operate delay time DUPPDPR 0.04...300.00 s 0.01

Disable time DUPPDPR 0.00...60.00 s 0.01

Pol reversal DUPPDPR No -


Yes

Table 76. Frequency gradient protection (DAPFRC)

Characteristic Value

Operation accuracy df/dt < ±10 Hz/s: ±10 mHz/s


Undervoltage blocking: ±1.5% of the set value or ±0.002 × Un

Start time1)2) Start value = 0.05 Hz/s Typically 110 ms (±15 ms)
df/dtFAULT = ±1.0 Hz/s

Reset time <150 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Frequency before fault = 1.0 × fn , fn = 50 Hz


2) Includes the delay of the signal output contact

Table 77. Frequency gradient protection (DAPFRC) main settings

Parameter Function Value (Range) Step

Start value DAPFRC -10.00...10.00 Hz/s 0.01

Operate delay time DAPFRC 0.120...60.000 s 0.001

ABB 41
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 78. Overfrequency protection (DAPTOF)

Characteristic Value

Operation accuracy At the frequency f = 35...66 Hz

±0.003 Hz

Start time1)2) fFault = 1.01 × set Start value Typically <190 ms

Reset time <190 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Frequency before fault = 0.99 × fn , fn = 50 Hz


2) Includes the delay of the signal output contact

Table 79. Overfrequency protection (DAPTOF) main settings

Parameter Function Value (Range) Step

Start value DAPTOF 35.0...64.0 Hz 0.1

Operate delay time DAPTOF 0.170...60.000 s 0.001

Table 80. Underfrequency protection (DAPTUF)

Characteristic Value

Operation accuracy At the frequency f = 35...66 Hz

±0.003 Hz

Start time1)2) fFault = 0.99 × set Start value Typically <190 ms

Reset time <190 ms

Operate time accuracy in definite time mode ±1.0% of the set value or ±30 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

1) Frequency before fault = 1.01 × fn , fn = 50 Hz


2) Includes the delay of the signal output contact

Table 81. Underfrequency protection (DAPTUF) main settings

Parameter Function Value (Range) Step

Start value DAPTUF 35.0...64.0 Hz 0.1

Operate delay time DAPTUF 0.170...60.000 s 0.001

Table 82. Low voltage ride through protection function (LVRTPTUV)

Characteristic Value

Operation accuracy At the frequency f = fn


±1.5% of the set value or ±0.002 × Un

Start time Typically 40 ms

Reset time Based on maximum value of Recovery time setting

Operate time accuracy in definite time mode ±1.0% of the set value or ±40 ms

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5 and so on

42 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 83. Low voltage ride through protection function (LVRTPTUV) main settings

Parameter Function Value (Range) Step

Voltage start value LVRTPTUV 0.05...1.20 pu 0.01

Num of start phases LVRTPTUV Exactly 1 of 3 -


Exactly 2 of 3
Exactly 3 of 3

Voltage selection LVRTPTUV Highest Ph-to-E -


Lowest Ph-to-E
Highest Ph-to-Ph
Lowest Ph-to-Ph
Positive Seq

Active coordinates LVRTPTUV 1...10 1

Voltage level 1 LVRTPTUV 0.00...1.20 pu 0.01

Recovery time 1 LVRTPTUV 0.00...300.00 s 0.01

Voltage level 2 LVRTPTUV 0.00...1.20 pu 0.01

Recovery time 2 LVRTPTUV 0.00...300.00 s 0.01

Voltage level 3 LVRTPTUV 0.00...1.20 pu 0.01

Recovery time 3 LVRTPTUV 0.00...300.00 s 0.01

Voltage level 4 LVRTPTUV 0.00...1.20 pu 0.01

Recovery time 4 LVRTPTUV 0.00...300.00 s 0.01

Voltage level 5 LVRTPTUV 0.00...1.20 pu 0.01

Recovery time 5 LVRTPTUV 0.00...300.00 s 0.01

Voltage level 6 LVRTPTUV 0.00...1.20 pu 0.01

Recovery time 6 LVRTPTUV 0.00...300.00 s 0.01

Voltage level 7 LVRTPTUV 0.00...1.20 pu 0.01

Recovery time 7 LVRTPTUV 0.00...300.00 s 0.01

Voltage level 8 LVRTPTUV 0.00...1.20 pu 0.01

Recovery time 8 LVRTPTUV 0.00...300.00 s 0.01

Voltage level 9 LVRTPTUV 0.00...1.20 pu 0.01

Recovery time 9 LVRTPTUV 0.00...300.00 s 0.01

Voltage level 10 LVRTPTUV 0.00...1.20 pu 0.01

Recovery time 10 LVRTPTUV 0.00...300.00 s 0.01

ABB 43
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 84. Overexcitation protection (OEPVPH)

Characteristic Value

Operation accuracy At the frequency f = fn

±2.5% of the set value or 0.01 × Ub/f

Start time 1)2) Frequency change Typically 200 ms (±20 ms)

Voltage change Typically 100 ms (±20 ms)

Reset time <60 ms

Reset ratio Typically 0.96

Retardation time <45 ms

Operate time accuracy in definite-time mode ±1.0% of the set value or ±20 ms

Operate time accuracy in inverse-time mode ±5.0% of the theoretical value or ±50 ms

1) Results based on statistical distribution of 1000 measurements


2) Includes the delay of the signal output contact

Table 85. Overexcitation protection (OEPVPH) main settings

Parameter Function Value (Range) Step

Leakage React OEPVPH 0.0...50.0% Zb 0.1

Start value OEPVPH 100...200% UB/f 1

Time multiplier OEPVPH 0.1...100.0 0.1

Operating curve type OEPVPH ANSI Def. Time -


IEC Def. Time
OvExt IDMT Crv1
OvExt IDMT Crv2
OvExt IDMT Crv3
OvExt IDMT Crv4

Operate delay time OEPVPH 0.10...200.00 s 0.01

Table 86. Voltage vector shift protection (VVSPPAM)

Characteristic Value

Operation accuracy At the frequency f = fn


±0.5% of the set value or ±0.01°

Operate time Typically 60 ms

Table 87. Voltage vector shift protection (VVSPPAM) main settings

Parameter Function Value (Range) Step

Start value VVSPPAM 2...30° 1

Phase supervision VVSPPAM All -


Pos sequence

Over Volt Blk value VVSPPAM 0.40...1.50 pu 0.01

Under Volt Blk value VVSPPAM 0.15...1.00 pu 0.01

Voltage selection VVSPPAM phase-to-earth -


phase-to-phase

44 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 88. Three-phase underexcitation protection (UEXPDIS)

Characteristic Value

Operation accuracy1) At the frequency f = fn

±3.0% of the set value or ±0.2% Zb

Start time2)3) Typically 45 ms (±15 ms)

Reset time <50 ms

Reset ratio Typically 1.04

Retardation time Total retardation time when the impedance returns from the operating
circle <40 ms

Operate time accuracy in definite-time mode ±1.0% of the set value of ±20 ms

1) Adaptive DFT measurement used


2) fn = 50 Hz, results based on statistical distribution of 1000 measurements
3) Includes the delay of the signal output contact

Table 89. Three-phase underexcitation protection (UEXPDIS) main settings

Parameter Function Value (Range) Step

External Los Det Ena UEXPDIS 0...1 1

Diameter UEXPDIS 1...6000 %Zb 1

Offset UEXPDIS -1000...1000 %Zb 1

Displacement UEXPDIS -1000...1000 %Zb 1

Operate delay time UEXPDIS 0.06...200.00 s 0.01

Table 90. Three-phase underimpedance protection (UZPDIS)

Characteristic Value

Operation accuracy At the frequency f = fn

±3.0% of the set value or ±0.2% × Zb

Start time Typically 25 ms (±15 ms)

Reset time <50 ms

Reset ratio Typically 1.04

Retardation time <40 ms

Operate time accuracy in definite-time mode 1)2) ±1.0% of the set value or ±20 ms

1) Fn = 50 Hz, results based on statistical distribution of 1000 measurements


2) Includes the delay of the signal output contact

Table 91. Three-phase underimpedance protection (UZPDIS) main settings

Parameter Function Value (Range) Step

Polar reach UZPDIS 1...6000% Zb 1

Operate delay time UZPDIS 0.04...200.00 s 0.01

ABB 45
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 92. Circuit breaker failure protection (CCBRBRF)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.5% of the set value or ±0.002 × In

Operate time accuracy ±1.0% of the set value or ±30 ms

Table 93. Circuit breaker failure protection (CCBRBRF) main settings

Parameter Function Value (Range) Step

Current value CCBRBRF 0.05...1.00 pu 0.01

Current value Res CCBRBRF 0.05...1.00 pu 0.01

CB failure mode CCBRBRF 1 = Current -


2 = Breaker status
3 = Both

CB fail trip mode CCBRBRF 1 = Off -


2 = Without check
3 = Current check

Retrip time CCBRBRF 0.00...60.00 s 0.01

CB failure delay CCBRBRF 0.00...60.00 s 0.01

CB fault delay CCBRBRF 0.00...60.00 s 0.01

Table 94. Multipurpose analog protection (MAPGAPC)

Characteristic Value

Operate time accuracy ±1.0% of the set value or ±20 ms

Table 95. Multipurpose analog protection (MAPGAPC) main settings

Parameter Function Value (Range) Step

Operation mode MAPGAPC Over -


Under

Start value MAPGAPC -10000.0...10000.0 0.1

Start value Add MAPGAPC -100.0...100.0 0.1

Operate delay time MAPGAPC 0.00...200.00 s 0.01

46 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 96. Operation characteristics

Parameter Value (Range)

Operating curve type 1 = ANSI Ext. inv.


2 = ANSI Very. inv.
3 = ANSI Norm. inv.
4 = ANSI Mod inv.
5 = ANSI Def. Time
6 = L.T.E. inv.
7 = L.T.V. inv.
8 = L.T. inv.
9 = IEC Norm. inv.
10 = IEC Very inv.
11 = IEC inv.
12 = IEC Ext. inv.
13 = IEC S.T. inv.
14 = IEC L.T. inv
15 = IEC Def. Time
17 = Programmable
18 = RI type
19 = RD type

Operating curve type (voltage protection) 5 = ANSI Def. Time


15 = IEC Def. Time
17 = Inv. Curve A
18 = Inv. Curve B
19 = Inv. Curve C
20 = Programmable
21 = Inv. Curve A
22 = Inv. Curve B
23 = Programmable

ABB 47
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Control functions

Table 97. Synchrocheck (SYNCRSYN)

Characteristic Value

Operation accuracy At the frequency f = fn

Voltage: ±1.0% or ±0.002 × Un


Frequency: ±10 mHz
Phase angle ±2°

Reset time <50 ms

Reset ratio Typically 0.96

Operate time accuracy +90ms/0 ms

48 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Supervision and monitoring functions

Table 98. Runtime counter for machines and devices (MDSOPT)

Characteristic Value

Motor run-time measurement accuracy 1) ±0.5%

1) Of the reading, for a stand-alone protection relay without time synchronization

Table 99. Runtime counter for machines and devices (MDSOPT) main settings

Parameter Function Value (Range) Step

Warning value MDSOPT 0...299999 h 1

Alarm value MDSOPT 0...299999 h 1

Initial value MDSOPT 0...299999 h 1

Operating time hour MDSOPT 0...23 h 1

Operating time mode MDSOPT Immediate -


Timed Warn
Timed Warn Alm

Table 100. Circuit breaker condition monitoring (SSCBR)

Characteristic Value

Current measuring accuracy At the frequency f = fn

±1.5% or ±0.002 × In (at currents in the range of 0.1…10 × In)


±5.0% (at currents in the range of 10…40 × In)

Operate time accuracy ±1.0% of the set value or ±20 ms

Traveling time measurement ±10 ms

Table 101. Fuse failure supervision (SEQRFUF)

Characteristic Value

Operation accuracy At the frequency f = fn

Current: ±1.5% of the set value or ±0.002 × In


Voltage: ±1.5% of the set value or ±0.002 × Un

Operate time1) • NPS function UFault = 1.1 × set Neg Seq voltage Typically 35 ms (±15 ms)
Lev Typically 25 ms (±15 ms)
UFault = 5.0 × set Neg Seq voltage
Lev

• Delta function ΔU = 1.1 × set Voltage change rate Typically 35 ms (±15 ms)
ΔU = 2.0 × set Voltage change rate Typically 28 ms (±15 ms)

1) Includes the delay of the signal output contact, fn = 50 Hz, fault voltage with nominal frequency injected from random phase angle

Table 102. Current circuit supervision (CCRDIF)

Characteristic Value

Operate time1) <30 ms

1) Including the delay of the output contact

ABB 49
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 103. Current circuit supervision (CCRDIF) main settings

Parameter Function Value (Range) Step

Start value CCRDIF 0.05...2.00 pu 0.01

Maximum operate current CCRDIF 0.05...5.00 pu 0.01

Table 104. Trip-circuit supervision (TCSSCBR)

Characteristic Value

Time accuracy ±1.0% of the set value or ±40 ms

Table 105. Station battery supervision (SPVNZBAT)

Characteristic Value

Operation accuracy ±1.0% of the set value

Operate time accuracy ±1.0% of the set value or ±40 ms

Table 106. Energy monitoring (EPDMMTR)

Characteristic Value

Operation accuracy At all three currents in range 0.10…1.20 × Inn


At all three voltages in range 0.50…1.15 × Un
At the frequency f = fn
Active power and energy in range |PF| > 0.71
Reactive power and energy in range |PF| < 0.71

±1.5% for energy

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

50 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Measurement functions

Table 107. Three-phase current measurement (CMMXU)

Characteristic Value

Operation accuracy At the frequency f = fn

±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 108. Three-phase voltage measurement (phase-to-earth) (VPHMMXU)

Characteristic Value

Operation accuracy At the frequency f = fn

±0.5% or ±0.002 × Un
(at voltages in the range of 0.01...1.15 × Un)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 109. Three-phase voltage measurement (phase-to-phase) (VPPMMXU)

Characteristic Value

Operation accuracy At the frequency f = fn

±0.5% or ±0.002 × Un
(at voltages in the range of 0.01...1.15 × Un)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 110. Residual current measurement (RESCMMXU)

Characteristic Value

Operation accuracy At the frequency f = fn

±0.5% or ±0.002 × In
(at currents in the range of 0.01...4.00 × In)

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…


RMS: No suppression

Table 111. Residual voltage measurement (RESVMMXU)

Characteristic Value

Operation accuracy At the frequency f = fn

±0.5% or ±0.002 × Un

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…


RMS: No suppression

ABB 51
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 112. Power monitoring with P, Q, S, power factor, frequency (PWRMMXU)

Characteristic Value

Operation accuracy At all three currents in range 0.10…1.20 × Inn


At all three voltages in range 0.50…1.15 × Un
At the frequency f = fn
Active power and energy in range |PF| > 0.71
Reactive power and energy in range |PF| < 0.71

±1.5% for power (S, P and Q)


±0.015 for power factor

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

Table 113. Sequence current measurement (CSMSQI)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.0% or ±0.002 × In
at currents in the range of 0.01...4.00 × In

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

Table 114. Sequence voltage measurement (VSMSQI)

Characteristic Value

Operation accuracy At the frequency f = fn

±1.0% or ±0.002 × Un
At voltages in range of 0.01…1.15 × Un

Suppression of harmonics DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,…

52 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Control functions

Table 115. Synchrocheck (SYNCRSYN)

Characteristic Value

Operation accuracy At the frequency f = fn

Voltage: ±1.0% or ±0.002 × Un


Frequency: ±10 mHz
Phase angle ±2°

Reset time <50 ms

Reset ratio Typically 0.96

Operate time accuracy +90ms/0 ms

Table 116. Tap changer control with voltage regulator (OLATCC)

Characteristic Value

Operation accuracy 1) At the frequency f = fn

Differential voltage Ud:


±1.0% of the measured value or ±0.004 × Un (in measured voltages <2.0
× Un)

Operation value:
±1.0% of the Ud or ±0.004 × Un for Us = 1.0 × Un

Operate time accuracy in definite time mode 1) ±1.0% of the set value or 0.11 s

Operate time accuracy in inverse time mode 1) ±15.0% of the set value or 0.15 s
(at theoretical B in range of 1.1…5.0) Also note fixed minimum operate
time (IDMT) 1 s

Reset ratio for control operation Typically 0.80 (1.20)

Reset ratio for analog based blockings (except run back raise voltage Typically 0.96 (1.04)
blocking)

1) Default setting values used

ABB 53
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 117. Tap changer control with voltage regulator (OLATCC) main settings

Parameter Function Value (Range) Step

Operation mode OLATCC Manual -


Auto single
Auto parallel
Input control

Custom Man blocking OLATCC Custom disabled -


OC
UV
OC, UV
EXT
OC, EXT
UV, EXT
OC, UV, EXT

Delay characteristic OLATCC Inverse time -


Definite time

Band width voltage OLATCC 1.20...18.00% 0.01

Load current limit OLATCC 0.10...5.00 pu 0.01

Block lower voltage OLATCC 0.10...1.20 pu 0.01

Runback raise V OLATCC 0.80...1.60 pu 0.01

Cir current limit OLATCC 0.10...5.00 pu 0.01

LDC limit OLATCC 0.00...2.00 pu 0.01

Lower block tap OLATCC -36...36 1

Raise block tap OLATCC -36...36 1

LDC enable OLATCC FALSE -


TRUE

Auto parallel mode OLATCC Master 1


Follower
NRP
MCC

Band center voltage OLATCC 0.000...2.000 pu 0.001

Line drop V Ris OLATCC 0.0...25.0% 0.1

Line drop V React OLATCC 0.0...25.0% 0.1

Band reduction OLATCC 0.0...9.0% 0.1

Stability factor OLATCC 0.0...70.0% 0.1

Load phase angle OLATCC -89...89° 1

Control delay time 1 OLATCC 1.0...300.0 s 0.1

Control delay time 2 OLATCC 1.0...300.0 s 0.1

54 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

19. Front panel user interface LED indicators. The 15 programmable alarm LEDs can indicate
The 630 series protection relays can be ordered with a a total of 45 alarms. The local HMI offers full front-panel user-
detached front-panel user interface (HMI). An integrated HMI is interface functionality with menu navigation, menu views and
available for 4U high housing. The local HMI includes a large operational data. In addition, the local HMI can, using PCM600,
graphical monochrome LCD with a resolution of 320 x 240 be configured to show a single-line diagram (SLD). The SLD
pixels (width x height). The amount of characters and rows view displays the status of the primary apparatus such as circuit
fitting the view depends on the character size as the characters' breakers and disconnectors, selected measurement values and
width and height may vary. busbar arrangements.

In addition, the local HMI includes dedicated open/close


operating buttons and five programmable function buttons with

GUID-5CFD3446-A92F-4A5F-B60D-90025DCFDC61 V2 EN

Figure 6. Local user interface

20. Mounting methods • 19” rack mounting


By means of appropriate mounting accessories the standard • Wall mounting
relay case for the 630 series protection relays can be flush • Mounting with a RTXP8, RTXP18 or RTXP24 test switch to a
mounted, semi-flush mounted or wall mounted. Detachable 19”rack
HMI is intended for optimized mounting in medium voltage • Door mounting of the local HMI, relay case mounted in the
metal-clad switchgear, thus reducing wiring between the low- low-voltage compartment of the switchgear
voltage compartment and the panel door. Further, the
protection relays can be mounted in any standard 19”
To ensure grounding of the RTD channels, a separate cable
instrument cabinet by means of 19” rack mounting accessories.
shield rail is included in the protection relay delivery when the
For the routine testing purposes, the relay cases can be optional RTD/mA module is ordered.
installed with RTXP test switches (RTXP8, RTXP18 or RTXP24)
For further information regarding different mounting options see
which can be mounted side by side with the relay case in a 19”
the installation manual.
rack.

Mounting methods:
• Flush mounting
• Semi-flush mounting
• Overhead/ceiling mounting

ABB 55
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

270
252,5

366

13

101,6
180
ø6,8

GUID-945D3C86-A432-4C1F-927A-A208E0C1F5F6 V2 EN

Figure 9. Wall mounting


GUID-8E2EDADD-D709-423D-8677-E3CF75DB256F V1 EN

GUID-AF1BEC0B-A9DC-4E9B-9C89-98F28B1C81DB V1 EN
Figure 7. Flush mounting
Figure 8. Semi-flush mounting

,5 22 0
25

25 8,
177

13
265,9

4
22

GUID-A368C5C3-D4A9-40B7-BD0E-181A6BB7ECA6 V1 EN

Figure 10. 6U half 19" unit wall mounted with two mounting brackets
and detached LHMI

56 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

21. Selection and ordering data The order code consists of a string of letters and digits
generated from the hardware and software modules of the
The IED type and serial number label identifies the protection protection relay. Use the ordering key information in tables to
and control relay. The label placed is on the side of the generate the order code when ordering protection and control
protection relay's case. The labels include a set of smaller size relays.
labels, one label for each module in the protection relay. The
module labels state the type and serial number of each module.

SBGAABACBBAZAANBXD

# Description
1 IED
630 series, 4U half 19” housing S
630 series, 6U half 19” housing T
630 series, 4U half 19” housing & connector set U
630 series, 6U half 19” housing & connector set V
2 Standard
IEC B
3 Main application
Generator protection and control G
GUID-6D418C83-076D-494E-B0DC-8379B03E2EBA V3 EN

The preconfiguration determines the analog input and binary I/O options. SBGAABACBBAZAANBXD
The example below shows standard configuration “A” with chosen options.

# Description
4-8 Functional application, preconfigurations:
A = Preconfiguration A for directly connected generator set
N = None
Pre- Available analog input options Available binary input/
conf. output
options
AA = 14 BI + 9 BO

AB = 7I (I0 1/5 A) + 3U AB = 23 BI + 18 BO
A BB = 7I (I0 1/5 A) + 3U + AC1,3) = 32 BI + 27 BO
8mA/RTD in + 4mA out AD2) = 41 BI + 36 BO
AE2,3) = 50 BI + 45 BO
AA = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
AB = 7I (I0 1/5 A) + 3U
AA = 14 BI + 9 BO
AC = 8I (I0 1/5 A) + 2U
AB = 23 BI + 18 BO
BA = 4I (I0 1/5 A) + 1I (I0 0.1/0.5 A) + 4U
N 8mA/RTD in + 4mA out AC1) = 32 BI + 27 BO

BB = 7I (I0 1/5 A) + 3U + AD2) = 41 BI + 36 BO


8mA/RTD in + 4mA out AE´2,3) = 50 BI + 45 BO
BC = 8I (I0 1/5 A) + 2U +
8mA/RTD in + 4mA out

1) Binary input/output option AC is not available for 4U high variant (digit #1 = S or U) with RTD card option
(digit #5-6 = BA, BB or BC)
2) Binary input/output options AD and AE require 6U half 19” IED housing (digit #1 = T or V)
3) Binary input/output option AE is not available for 6U high variant (digit #1 = T or V) with RTD card option
(digit #5-6 = BA, BB or BC)
GUID-4642B41A-FAA5-4178-B117-5CB69DC75A70 V3 EN

ABB 57
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

SBGAABACBBAZAANBXD

# Description
9 Communication modules (Serial)
Serial glass fibre (ST connector) A
Serial plastic fibre (Snap-in connector) B
10 Communication modules (Ethernet)
Ethernet 100Base-FX (LC connector) A
Ethernet 100Base-TX (RJ-45 connector) B
11 Communication (Protocol)
IEC 61850 protocol A
IEC 61850 and DNP3 TCP/IP protocols B
IEC 61850 and IEC 60870-103 protocols C
GUID-A0EFE2B7-D63B-4BBB-9F53-A49D3125D585 V3 EN

SBGAABACBBAZAANBXD

# Description
12 Language
Language package Z
13 Front panel
Integrated LHM1) A
Detached LHMI + 1 m cable B
Detached LHMI + 2 m cable C
Detached LHMI + 3 m cable D
Detached LHMI + 4 m cable E
Detached LHMI + 5 m cable F
No LHMII 2)
N
14 Option 1
Transformer differential protection for two-winding transformers3) A
Third harmonic based stator earth-fault protection 4)
B
All options3,4) Z
None N
15 Option 2
None N
16 Power supply
Power supply 48-125 VDC A
Power supply 110-250 VDC, 100-240 VAC B
17 Reserved
Undefined X
18 Version
Version 1.3 D

1) Integrated HMI is not available for 6 U high variant (digit #1 = T or V)


2) Preconfiguration requires HMI, so option N is not valid if preconfiguration is selected. A detached LHMI cannot be used if No
LHMI configuration has been chosen
3) Transformer differential protection requires at least 6 CTs, so AIM options AA and BA (digit # 5-6) are not possible
4) Third harmonic based stator earth-fault protection can be used in two modes. Third harmonic neutral undervoltage mode requires
voltage measurement in the generator neutral. Additionally phase-to-earth voltages in the terminal side are required, if third har-
monic differential mode is to be applied
GUID-A561D9AC-44CC-4643-B862-9796930337F6 V3 EN

58 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Example code: S B G A A B A C B B A Z A A N B X D

Your ordering code:

Digit (#) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18

Code
GUID-E3F56E28-FDF2-4963-A1FE-D79599D4FE3A V3 EN

Figure 11. Ordering key for complete protection relays

22. Accessories

Table 118. Mounting accessories

Item Order number

Flush mounting kit for one 4U half 19” housing the protection relay 1KHL400040R0001

Semi-flush mounting kit for one 4U half 19” housing the protection relay 1KHL400444R0001

Wall-mounting kit (cabling towards the mounting wall) for one 4U half 19” housing the protection relay 1KHL400067R0001

Wall-mounting kit (cabling to the front) for one 4U half 19” housing the protection relay 1KHL400449R0001

19" rack mounting kit for one 4U half 19” housing the protection relay 1KHL400236R0001

19" rack mounting kit for two 4U half 19” housing the protection relays 1KHL400237R0001

Overhead/ceiling mounting kit (with cable space) for one 4U half 19” housing the protection relay 1KHL400450R0001

Wall-mounting kit for direct rear wall mounting (with cabling to the front) of one 6U half 19" housing the protection 1KHL400452R0001
relay

Wall-mounting kit (with cabling towards the mounting wall) for one 6U half 19" housing the protection relay 1KHL400200R0001

Overhead/ceiling mounting kit (with cable space) for one 6U half 19" housing the protection relay 1KHL400464R0001

Table 119. Test switch mounting accessories

Item Order number

19" rack mounting kit for one RTXP8 test switch (the test switch is not included in the delivery) 1KHL400465R0001

19" rack mounting kit for one RTXP18 test switch (the test switch is not included in the delivery) 1KHL400467R0001

19" rack mounting kit for one RTXP24 test switch (the test switch is not included in the delivery) 1KHL400469R0001

Table 120. Connector sets

Item Order number

Connector set for one 4U housing the protection relay including analog input variant 4I + 5U or 5I + 4U 2RCA021735

Connector set for one 6U housing the protection relay including analog input variant 4I + 5U or 5I + 4U 2RCA021736

Connector set for one 4U housing the protection relay including analog input variant 7I + 3U 2RCA023041

Connector set for one 6U housing the protection relay including analog input variant 7I + 3U 2RCA023042

Connector set for one 4U housing the protection relay including analog input variant 8I + 2U 2RCA023039

Connector set for one 6U housing the protection relay including analog input variant 8I + 2U 2RCA023040

ABB 59
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 121. Optional cables for external display module

Items Order number

LHMI cable (1 m) 2RCA025073P0001

LHMI cable (2 m) 2RCA025073P0002

LHMI cable (3 m) 2RCA025073P0003

LHMI cable (4 m) 2RCA025073P0004

LHMI cable (5 m) 2RCA025073P0005

24. Tools using a web browser (IE 7.0 or later). For security reasons, the
The protection relay is delivered either with or without an web-browser based user interface is disabled by default. The
optional factory made preconfiguration. The default parameter interface can be enabled with the PCM600 tool or from the front
setting values can be changed from the front-panel user panel user interface. The functionality of the interface is by
interface, the web-browser based user interface (WebHMI) or default limited to read-only, but can be configured to enable
the PCM600 tool in combination with the relay-specific read and write access by means of PCM600 or the local HMI.
connectivity package.
The relay connectivity package is a collection of software and
PCM600 offers extensive relay configuration functions such as specific protection relay information, which enable system
relay application configuration, signal configuration, DNP3 products and tools to connect and interact with the protection
communication configuration and IEC 61850 communication relay. The connectivity packages reduce the risk of errors in
configuration including horizontal communication, GOOSE. system integration, minimizing device configuration and set-up
times.
When the web-browser based user interface is used, the
protection relay can be accessed either locally or remotely

Table 122. Tools

Description Version

PCM600 2.5 or later

Web browser IE 8.0, IE 9.0 or IE 10.0

REG630 Connectivity Package 1.3 or later

60 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 123. Supported functions

Function WebHMI PCM600

Parameter setting ● ●

Disturbance handling ● ●

Signal monitoring ● ●

Event viewer ● ●

Alarm LED viewing ● ●

Hardware configuration - ●

Signal matrix - ●

Graphical display editor - ●

IED configuration templates - ●

Communication management - ●

Disturbance record analysis - ●

IED user management - ●

User management - ●

Creating/handling projects - ●

Graphical application configuration - ●

IEC 61850 communication configuration, including GOOSE - ●

IED Compare - ●

25. Supported ABB solutions substation automation standard, are fast communication
ABB’s 630 series protection and control protection relays capability, continuous supervision of the protection and
together with the Grid Automation controller COM600 communication system's integrity, and an inherent flexibility
constitute a genuine IEC 61850 solution for reliable power regarding reconfiguration and upgrades
distribution in utility and industrial power systems. To facilitate
and streamline the system engineering ABB’s relays are At substation level, COM600 uses the logic processor and data
supplied with connectivity packages. The connectivity content of the bay level devices to enhance substation level
packages include a compilation of software and relay-specific functionality. COM600 features a Web-browser based HMI
information such as single-line diagram templates, manuals which provides a customizable graphical display for visualizing
and a full relay data model including event and parameter lists. single line mimic diagrams for switchgear bay solutions. To
With the connectivity packages, the relays can be readily enhance personnel safety, the Web HMI also enables remote
configured via the PCM600 Protection and Control IED access to substation devices and processes. Furthermore,
Manager and integrated with the Grid Automation controller COM600 can be used as a local data warehouse for technical
COM600 or the MicroSCADA Pro network control and documentation of the substation and for network data collected
management system. by the devices. The collected network data facilitates extensive
reporting and analyzing of network fault situations using the
The 630 series relays offer support for the IEC 61850 standard data historian and event handling features of COM600.
including horizontal GOOSE messaging. Compared to
traditional hard-wired, inter-device signaling, peer-to-peer COM600 also features gateway functionality providing
communication over a switched Ethernet LAN offers an seamless connectivity between the substation devices and
advanced and versatile platform for power system protection. network-level control and management systems such as
Among the distinctive features of the protection system MicroSCADA Pro and System 800xA.
approach, enabled by the full implementation of the IEC 61850

ABB 61
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 124. Supported ABB solutions

Product Version

Grid Automation Controller COM600 3.5 or later

MicroSCADA Pro SYS 600 9.3 FP1 or later

System 800xA 5.1 or later

62 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

26. Terminal diagrams

REG630 High Medium 6U: REG630 High Medium 6U:

X101 X430 X430 X410 X101 X430 X430 X410


1 -/ 1 1 1 -/ 1 1
CT U aux 2 2 CT U aux 2 2
2 +/ 2 +/
3 3 3 3
3 3
CT CT
4 X329 X309 4 X329 X309
5 1 5 1
CT IRF 2 CT IRF 2
6 3 6 3
7 7
CT CT
8 X327 X307 8 X327 X307
9 9
CT sens BO1_PO_TCS CT BO1_PO_TCS
10 10
1 1
TCS TCS
2 2
X102 BO2_PO_TCS X102 BO2_PO_TCS
1 3 1 3
TCS CT TCS
2 4 2 4

3 BO3_PO_TCS 3 BO3_PO_TCS
VT 5 CT 5
4 TCS 4 TCS
6 6
5 5
VT VT, CT
6 BO4_PO 6 BO4_PO
7 7
7 7
VT 8 VT 8
8 8
BO5_PO BO5_PO
9 9
VT 9 VT 9
10 10 10 10

X304 BO6_PO X304 BO6_PO


1 11 1 11
12 12
BI1 13 BI1 13
2 BO7_SO 2 BO7_SO
14 14
BI2 BI2
3 15 3 15
BO8_SO BO8_SO
BI3 BI3
4 16 4 16

BI4 17 BI4 17
5 BO9_SO 5 BO9_SO
6 18 6 18

BI5 BI5
7 7

BI6 BI6
8 8

BI7 BI7
9 9

BI8 BI8
10 10
11 11

BI9 BI9
12 12

BI10 BI10
13 13

BI11 BI11
14 14
15 15

BI12 BI12
16 16

BI13 BI13
17 17

BI14 BI14
18 18

X9 X9
(glass) transmitter (glass) transmitter
1) 1)
TX Fiber optic (plastic) transmitter TX Fiber optic (plastic) transmitter
RX Fiber optic (glass) receiver 1)
RX Fiber optic (glass) receiver 1)
(plastic) receiver (plastic) receiver
X4 X4
1 GNDC 1 GNDC
2 NC 2 NC
3 IRIG-B- 3 IRIG-B-
4 IRIG-B+ 4 IRIG-B+

X1 X1
LAN 1 2) LAN 1 2)

X0 X0
LAN / HMI 3) LAN / HMI 3)

1) Optional 1) Optional

2) 100 BaseTx / RJ-45 2) 100 BaseTx / RJ-45


100 BaseFx / LC 100 BaseFx / LC
3) 100 BaseTx / RJ-45 3) 100 BaseTx / RJ-45
Power over Ethernet Power over Ethernet

GUID-78CCF517-A2D8-49C3-9E61-15A6879DA9AE V1 EN

Figure 12. REG630 terminal diagram

ABB 63
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

GUID-5E27DD50-FD15-4824-BDFB-DD52E29730EA V2 EN

Figure 13. 630 series BIO module option

Table 125. BIO options

Unit BI/BO

4U X319 + X3161)

X324 + X321

6U X324 + X3211)

X329 + X326

X334 + X331

X339 + X336

1) Occupied by RTD module when ordered

64 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

GUID-CB7B1CF8-A0E4-42F5-998C-701641515127 V1 EN

Figure 14. 630 series RTD module option

27. References You will find the latest relevant information on the REG630
The www.abb.com/substationautomation portal offers you protection relay on the product page. Scroll down the page to
information about the distribution automation product and find and download the related documentation.
service range.

ABB 65
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

28. Functions, codes and symbols

Table 126. Functions included in the relay

Description IEC 61850 IEC 60617 ANSI

Protection

Three-phase non-directional overcurrent protection, low stage PHLPTOC 3I> 51P-1

Three-phase non-directional overcurrent protection, high stage PHHPTOC 3I>> 51P-2

Three-phase non-directional overcurrent protection, PHIPTOC 3I>>> 50P/51P


instantaneous stage

Voltage dependent overcurrent protection PHPVOC I(U)> 51V

Three-phase directional overcurrent protection, low stage DPHLPDOC 3I> -> 67-1

Three-phase directional overcurrent protection, high stage DPHHPDOC 3I>> -> 67-2

Non-directional earth-fault protection, low stage EFLPTOC I0> 51N-1

Non-directional earth-fault protection, high stage EFHPTOC I0>> 51N-2

Non-directional earth-fault protection, instantaneous stage EFIPTOC I0>>> 50N/51N

Directional earth-fault protection, low stage DEFLPDEF I0> -> 67N-1

Directional earth-fault protection, high stage DEFHPDEF I0>> -> 67N-2

Third harmonic based stator earth-fault protection H3EFPSEF dUo(3H)>/Uo(3H)< 27/59THD

High-impedance based restricted earth-fault protection HREFPDIF dI0Hi> 87NH

Rotor earth-fault protection MREFPTOC Io>R 64R

Negative-sequence overcurrent protection for machines MNSPTOC I2>G/M 46G/46M

Three-phase thermal overload protection, two time constants T2PTTR 3Ith>T/G 49T/G

Three-phase current inrush detection INRPHAR 3I2f> 68

Transformer differential protection for two-winding transformers TR2PTDF 3dI>T 87T

High-impedance or flux-balance based differential protection for


machines MHZPDIF 3dIHi>G/M 87GH/87MH

Stabilized differential protection for machines MPDIF 3dI>G/M 87G/87M

Three-phase overvoltage protection PHPTOV 3U> 59

Three-phase undervoltage protection PHPTUV 3U< 27

Positive-sequence overvoltage protection PSPTOV U1> 47O+

Positive-sequence undervoltage protection PSPTUV U1< 47U+

Negative-sequence overvoltage protection NSPTOV U2> 47O-

Residual overvoltage protection ROVPTOV U0> 59G

Directional reactive power undervoltage protection DQPTUV Q>-->,3U< 32Q,27

Reverse power/directional overpower protection DOPPDPR P> 32R/32O

Underpower protection DUPPDPR P< 32U

Frequency gradient protection DAPFRC df/dt> 81R

Overfrequency protection DAPTOF f> 81O

Underfrequency protection DAPTUF f< 81U

Low voltage ride through protection function LVRTPTUV U<RT 27RT

Overexcitation protection OEPVPH U/f> 24

66 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 126. Functions included in the relay, continued


Description IEC 61850 IEC 60617 ANSI

Voltage vector shift protection VVSPPAM VS 78V

Three-phase underexcitation protection UEXPDIS X< 40

Three-phase underimpedance protection UZPDIS Z< GT 21GT

Circuit breaker failure protection CCBRBRF 3I>/I0>BF 51BF/51NBF

Tripping logic TRPPTRC I -> O 94

Multipurpose analog protection MAPGAPC MAP MAP

Control

Bay control QCCBAY CBAY CBAY

Interlocking interface SCILO 3 3

Circuit breaker/disconnector control GNRLCSWI I <-> O CB/DC I <-> O CB/DC

Circuit breaker DAXCBR I <-> O CB I <-> O CB

Disconnector DAXSWI I <-> O DC I <-> O DC

Local/remote switch interface LOCREM R/L R/L

Synchrocheck SYNCRSYN SYNC 25

Generic process I/O

Single point control (8 signals) SPC8GGIO - -

Double point indication DPGGIO - -

Single point indication SPGGIO - -

Generic measured value MVGGIO - -

Logic Rotating Switch for function selection and LHMI SLGGIO - -


presentation

Selector mini switch VSGGIO - -

Pulse counter for energy metering PCGGIO - -

Event counter CNTGGIO - -

Supervision and monitoring

Runtime counter for machines and devices MDSOPT OPTS OPTM

Circuit breaker condition monitoring SSCBR CBCM CBCM

Fuse failure supervision SEQRFUF FUSEF 60

Current circuit supervision CCRDIF MCS 3I MCS 3I

Trip-circuit supervision TCSSCBR TCS TCM

Station battery supervision SPVNZBAT U<> U<>

Energy monitoring EPDMMTR E E

Measured value limit supervision MVEXP - -

Measurement

Three-phase current measurement CMMXU 3I 3I

Three-phase voltage measurement (phase-to-earth) VPHMMXU 3Upe 3Upe

Three-phase voltage measurement (phase-to-phase) VPPMMXU 3Upp 3Upp

Residual current measurement RESCMMXU I0 I0

ABB 67
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

Table 126. Functions included in the relay, continued


Description IEC 61850 IEC 60617 ANSI

Residual voltage measurement RESVMMXU U0 U0

Power monitoring with P, Q, S, power factor, frequency PWRMMXU PQf PQf

Sequence current measurement CSMSQI I1, I2 I1, I2

Sequence voltage measurement VSMSQI U1, U2 V1, V2

Analog channels 1-10 (samples) A1RADR ACH1 ACH1

Analog channels 11-20 (samples) A2RADR ACH2 ACH2

Analog channels 21-30 (calc. val.) A3RADR ACH3 ACH3

Analog channels 31-40 (calc. val.) A4RADR ACH4 ACH4

Binary channels 1-16 B1RBDR BCH1 BCH1

Binary channels 17 -32 B2RBDR BCH2 BCH2

Binary channels 33 -48 B3RBDR BCH3 BCH3

Binary channels 49 -64 B4RBDR BCH4 BCH4

Station communication (GOOSE)

Binary receive GOOSEBINRCV - -

Double point receive GOOSEDPRCV - -

Interlock receive GOOSEINTLKRCV - -

Integer receive GOOSEINTRCV - -

Measured value receive GOOSEMVRCV - -

Single point receive GOOSESPRCV - -

68 ABB
Generator Protection and Control 1MRS757583 C
REG630
Product version: 1.3

29. Document revision history

Document revision/date Product version History

A/2012-08-29 1.2 First release

B/2014-12-03 1.3 Content updated to correspond to the product version

C/2019-02-25 1.3 Content updated

ABB 69
70

ABB Distribution Solutions
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone +358 10 22 11

www.abb.com/mediumvoltage
www.abb.com/relion
1MRS757583 C

© Copyright 2019 ABB. All rights reserved.

You might also like