Coolex Fcu PDF
Coolex Fcu PDF
Coolex Fcu PDF
INTRODUCTION 3
NOMENCLATURE 3
STANDARD SPECIFICATIONS 4
OUT STANDING FEATURES 5
OPTIONAL SPECIFICATIONS 6
GENERAL DATA - 3 ROWS COOLING COIL 7
GENERAL DATA - 4 ROWS COOLING COIL 8
SELECTION PROCEDURE 9
UNIT ELECTRICAL DATA 10
FAN PERFORMANCE 11
PERFORMANCE DATA TABLES - 3 ROWS COOLING COIL 13
PERFORMANCE DATA TABLES - 4 ROWS COOLING COIL 15
PERFORMANCE DATA TABLES - HEATING COIL 17
UNIT DIMENSIONS 18
TYPICAL WIRING DIAGRAMS 19
ABOUT RIC 22
RIC Distributors 23
NOMENCLATURE
NGW - 080 S 3 L S
Construction
No. of Rows
S - Single Skin
D - Double Skin 3 - 3 Rows
4 - 4 Rows
3 www.ric.com.kw
STANDARD SPECIFICATIONS
General
Fan coil units are provided with the latest advanced technology to provide quiet, reliable performance.Chilled water coils are designed to give
optimum heat transfer efficiency. Units casings designed to provide easy accessibility for Chilled water coil and unit fan deck.
Unit Construction
Fan Coil unit consists of a coil, motor/blower assembly and a drain pan securely mounted on heavy gauge galvanized steel housing.
4 www.ric.com.kw
OUT STANDING FEATURES
Electrical Panel
• Easy access to the electrical
panels with removable panel for
electrical parts.
5 www.ric.com.kw
OPTIONAL SPECIFICATIONS
Finned Type Electric heater Following capacity range 6 Kits of valves packages available for models
flow control as per illustrated diagrams
Model Capacity (KW)
NGW-026 35-55
NGW-040 60-80
NGW-050 85-115
NGW-080 120-160
NGW-100 165-210
• Cooling Coil
- Left or Right Hand Pipe Connection
- Threaded pipe connection
• Construction
- Double skin
- Stainless steel drain pan
• Fan Motor
Tottaly Enclosed Fan Cooled (TEFC) Class F insulation
• Heating Coil
- Left or Right Hand Pipe Connection
- Threaded pipe connection
• Air Filter
- Aluminum V Type filter
- Bag Filter
• Thermostats
Decorative wall mounted type.
Micro-processor controlled with intelligent
control algorhythm (PID) Consequently, apart from the display of the
room applications.
Operating Mode : Cooling, Heating, Controlling valve packages and
Electric Heater.
6 www.ric.com.kw
GENERAL DATA - 3 ROWS COOLING COIL
Model NGW-026 NGW-040 NGW-050 NGW-080 NGW-100
Minimum, MBH 60.0 107.3 131.8 205.1 253.6
Cooling Capacity
Maximum, MBH 83.9 127.9 160.0 248.3 294.1
Number of Rows 3
Diameter, in 12 15 15 12 15
Width, in 11 15 15 12 15
Qty 1 1 1 2 2
Fans
Type Double Width Double Inlet Forward Curved Directly Driven
Nominal HP 1.5 2 3 5 5
Motor Qty 1
Note:
1. Cooling capacities are based on 80°/67°F entering air temperarture and 44°F/54°F entering/leaving chilled water
temperature.
2. The above data maybe changed without prior notice due to continous improvement in quality and performance.
7 www.ric.com.kw
GENERAL DATA - 4 ROWS COOLING COIL
Model NGW-026 NGW-040 NGW-050 NGW-080 NGW-100
Minimum, MBH 71.4 123.2 166.7 221.9 301.7
Cooling Capacity
Maximum, MBH 102.7 149.9 205.0 270.9 354.3
Number of Rows 4
Diameter, in 12 15 15 12 15
Width, in 11 15 15 12 15
Qty 1 1 1 2 2
Fans
Type Double Width Double Inlet Forward Curved Directly Driven
Nominal HP 1.5 2 3 5 5
Motor Qty 1
Note:
1. Cooling capacities are based on 80°/67°F entering air temperarture and 44°F/54°F entering/leaving chilled water
temperature.
2. The above data maybe changed without prior notice due to continous improvement in quality and performance.
8 www.ric.com.kw
SELECTION PROCEDURE
The below example illustrates the selection procedure to assist using this catalog to
select the appropriate NGW unit that meets the design requirements.
Altitude Correction
[ft] factor
Example : Sea level 1
7000 0.960
Using the correction factor table at the specified altitude, thereby the From fan performance (page 10) & performance table - 3 Rows
required capacity will be: cooling coil (page 11), the closest cooling capacity data and the
closest selection model to the required Capacity is NGW-080.
Corrected capacity = Required capacity
/corr. factor
Total capacity = 240,697 [Btu/hr]
Corrected total capacity = 238,000 (Btu/hr)/0.99
= 240,404 (Btu/hr)/0.99
Sensible capacity = 168,422 [Btu/hr]
Corrected sensible capacity = 166,000 (Btu/hr)/0.99
= 167,677 (Btu/hr)/0.99
9 www.ric.com.kw
UNIT ELECTRICAL DATA
Volt 415
Unit Power
Supply Phase 3
Hz 50
V - Ph - Hz 415-3-50
Compressor HP 1.5 2 3 5 5
LEGEND:
10 www.ric.com.kw
FAN PERFORMANCE
Model CFM 0.25 0.40 0.70 1.00 1.20 1.40 1.60 1.80 2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2600 775 0.74 827 0.82 929 1.00 1026 1.18 1087 1.30 1146 1.43 1202 1.56 - - - -
3000 795 0.96 843 1.04 935 1.22 1025 1.42 1083 1.55 1139 1.69 1194 1.83 1247 1.98 1298 2.13
Model CFM 0.30 0.50 0.70 1.00 1.20 1.40 1.60 1.80 2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3500 703 1.02 762 1.18 817 1.34 895 1.58 945 1.75 992 1.93 - - - - - -
NGW-040 3700 706 1.10 763 1.26 818 1.43 895 1.69 944 1.86 991 2.01 1036 2.22 - - - -
4000 711 1.24 767 1.41 820 1.58 895 1.85 943 2.03 989 2.22 1034 2.41 1077 2.61 1119 2.80
4200 716 1.34 771 1.51 823 1.69 897 1.97 944 2.16 989 2.35 1033 2.54 1076 2.74 1117 2.95
Model CFM 0.35 0.50 0.70 1.00 1.20 1.40 1.60 1.80 2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4400 734 1.49 775 1.62 826 1.81 899 2.09 945 2.28 990 2.48 1033 2.68 1075 2.89 1116 3.10
4700 742 1.66 781 1.80 831 1.99 903 2.29 948 2.49 992 2.70 1034 2.91 1076 3.12 1116 3.34
5000 750 1.86 789 2.00 838 2.20 908 2.51 952 2.72 995 2.93 1037 3.15 1077 3.37 1117 3.60
NGW-050
5300 759 2.07 797 2.22 845 2.42 914 2.74 957 2.96 1000 3.18 1041 3.41 1080 3.64 1119 3.87
5600 770 2.30 806 2.46 853 2.67 921 3.00 964 3.22 1005 3.46 1045 3.69 1084 3.93 1122 4.17
6000 785 2.65 820 2.81 865 3.03 931 3.37 973 3.61 1013 3.85 1053 4.09 1091 4.34 1128 4.59
11 www.ric.com.kw
FAN PERFORMANCE
Model CFM 0.40 0.60 0.70 1.00 1.20 1.40 1.60 1.80 2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6200 927 2.40 987 2.66 1016 2.79 1101 3.18 1155 3.45 1207 3.72 1258 4.00 1308 4.29 1357 4.57
6500 933 2.60 992 2.86 1021 3.00 1104 3.40 1157 3.68 1209 3.96 1259 4.25 1308 4.54 1356 4.84
7000 945 2.95 1003 3.24 1031 3.38 1111 3.81 1163 4.10 1213 4.40 1262 4.70 1309 5.00 1356 5.31
NGW-080
7500 958 3.34 1015 3.64 1042 3.79 1121 4.25 1171 4.56 1219 4.87 1267 5.18 1313 5.50 1358 5.82
8000 972 3.76 1028 4.08 1055 4.25 1132 4.73 1181 5.06 1228 5.39 1274 5.72 1319 6.05 1363 6.38
8400 984 4.12 1039 4.47 1065 4.64 1141 5.15 1190 5.49 1236 5.83 1281 6.17 1326 6.52 1369 6.87
Model CFM 0.45 0.60 0.70 1.00 1.60 1.80 2.00 2.50 3.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8600 786 3.22 824 3.49 849 3.68 921 4.24 1055 5.43 1096 5.84 1137 6.25 - - - -
9000 790 3.45 828 3.73 852 3.92 923 4.51 1055 5.72 1096 6.14 1136 6.57 1232 7.66 - -
9500 795 3.77 832 4.05 857 4.25 926 4.85 1056 6.11 1096 6.54 1136 6.98 1231 8.11 1320 9.27
NGW-100
10000 799 3.96 836 4.26 860 4.46 929 5.07 1056 6.35 1097 6.79 1136 7.24 1230 8.39 1319 9.57
10500 808 4.46 844 4.77 867 4.98 935 5.62 1060 6.96 1099 7.42 1138 7.88 1230 9.08 1317 10.31
11000 815 4.85 850 5.17 874 5.39 940 6.05 1063 7.42 1102 7.89 1140 8.37 1231 9.61 1317 10.87
LEGEND:
Note:
1. Internal Static pressure is based on pressure drops through evaporator coil, fan casing and 2” washable filters.
2. The blue shaded area indicates the operating range of a standard pulley combination.
3. The blue and green shaded area indicates the operating range of a standard motor; out of this range shift to next
larger motor size.
4. To determine the power of motor to be installed, just multiply the value of the absorbed power indicated above by
1.2.
12 www.ric.com.kw
PERFORMANCE DATA TABLES - 3 ROWS COOLING COIL
42 ˚F 43 ˚F 44 ˚F 45 ˚F
Model Air Flow
Total Sensible Water Total Sensible Water Total Sensible Water Total Sensible Water
CFM WPD WPD WPD WPD
Capacity Capacity Flow Capacity Capacity Flow Capacity Capacity Flow Capacity Capacity Flow
Btu/hr Btu/hr GPM Ft H2O Btu/hr Btu/hr GPM Ft H2O Btu/hr Btu/hr GPM Ft H2O Btu/hr Btu/hr GPM Ft H2O
1800 67,141 44,415 13.43 7.10 63,616 42,669 12.72 6.44 60,008 40,880 12.00 5.79 56,227 38,995 11.25 5.13
2000 72,056 47,935 14.41 8.09 68,252 46,047 13.65 7.33 64,327 44,094 12.87 6.57 60,282 42,072 12.06 5.83
NGW-026
2200 76,891 51,409 15.38 9.07 72,811 49,381 14.56 8.22 68,577 47,267 13.72 7.35 64,268 45,107 12.85 6.53
2400 81,646 54,836 16.33 10.06 77,295 52,670 15.46 9.11 72,759 50,398 14.55 8.13 68,186 48,100 13.64 7.23
2600 86,081 58,075 17.22 11.04 81,474 55,777 16.29 9.99 76,667 53,363 15.33 8.92 71,830 50,923 14.37 7.92
3000 94,222 64,460 18.84 12.97 89,094 61,544 17.82 11.70 83,881 58,925 16.78 10.49 78,546 56,223 15.71 9.32
3200 119,078 79,468 23.82 6.40 113,297 76,630 22.66 5.80 107,312 73,686 21.46 5.19 99,281 69,574 19.86 4.60
NGW-040
3500 126,519 84,838 25.30 7.14 120,109 81,669 24.02 6.45 113,106 78,167 22.62 5.78 105,384 74,246 21.08 5.12
3700 131,479 88,418 26.30 7.64 124,650 85,028 24.93 6.89 116,969 81,154 23.39 6.17 109,453 77,360 21.89 5.47
4000 138,336 93,444 27.67 8.37 130,946 89,755 26.19 7.54 123,514 86,043 24.70 6.75 115,080 81,738 23.02 5.99
4200 142,908 96,794 28.58 8.86 135,143 92,906 27.03 7.98 127,878 89,303 25.58 7.14 118,832 84,656 23.77 6.33
4400 148,723 100,844 29.74 3.55 140,359 96,634 28.07 3.20 131,800 92,303 26.36 2.85 122,954 87,783 24.59 2.51
4700 155,142 105,602 31.03 3.83 146,387 101,185 29.28 3.45 137,435 96,643 27.49 3.08 128,185 91,902 25.64 2.71
NGW-050
5000 161,561 110,360 32.31 4.11 152,415 105,736 30.48 3.70 143,069 100,983 28.61 3.30 133,415 96,020 26.68 2.90
5300 167,194 114,636 33.44 4.62 157,700 109,825 31.54 3.94 147,974 104,861 29.59 3.51 138,273 99,710 27.65 3.09
5600 173,220 119,154 34.64 5.02 163,357 114,145 32.67 4.19 153,243 108,970 30.65 3.73 143,317 103,615 28.66 3.28
6000 180,993 125,016 36.20 4.68 170,652 119,751 34.13 4.51 160,026 114,295 32.01 4.01 149,918 108,678 29.98 3.54
6200 228,293 152,622 45.66 13.30 216,816 146,958 43.36 12.11 205,104 141,174 41.02 10.95 193,124 135,240 38.62 9.82
6500 235,328 157,762 47.07 14.05 223,457 151,896 44.69 12.78 211,343 145,905 42.27 11.59 198,959 139,760 39.79 10.36
NGW-080
7000 247,053 166,328 49.41 15.29 234,524 160,127 46.90 13.90 221,741 153,790 44.35 12.66 208,683 147,292 41.74 11.25
7500 257,751 174,278 51.55 16.51 244,614 167,764 48.92 15.01 231,219 161,106 46.24 13.61 217,505 154,257 43.50 12.12
8000 268,448 182,229 53.69 17.73 254,705 175,401 50.94 16.11 240,697 168,422 48.14 14.57 226,327 161,221 45.27 12.99
8400 277,006 188,589 55.40 18.70 262,777 181,510 52.56 17.00 248,279 174,275 49.66 15.33 233,384 166,793 46.68 13.69
8600 282,707 192,568 56.54 12.41 268,317 185,417 53.66 11.29 253,641 178,104 50.73 10.20 238,554 170,537 47.71 9.11
9000 290,576 198,499 58.12 13.04 275,743 191,117 55.15 11.86 260,619 183,565 52.12 10.71 245,069 175,747 49.01 9.56
NGW-100
9500 300,411 205,912 60.08 13.83 285,025 198,242 57.00 12.57 269,342 190,392 53.87 11.34 253,214 182,260 50.64 10.13
10000 310,247 213,326 62.05 14.62 294,307 205,367 58.86 13.28 278,064 197,219 55.61 11.98 261,358 188,773 52.27 10.70
10500 319,351 220,283 63.87 15.40 302,897 212,050 60.58 13.98 286,080 203,592 57.22 12.60 268,887 194,880 53.78 11.25
11000 328,455 227,240 65.69 16.17 311,487 218,733 62.30 14.68 294,095 209,964 58.82 13.21 276,415 200,987 55.28 11.80
Note:
1. Cooling capacities are based on 80°/67°F entering air temperarture and 44°F/54°F entering/leaving chilled water
temperature.
13 www.ric.com.kw
PERFORMANCE DATA TABLES - 3 ROWS COOLING COIL
46 ˚F 47 ˚F 48 ˚F
Model Air Flow
Total Sensible Water Total Sensible Water Total Sensible Water
CFM WPD WPD WPD
Capacity Capacity Flow Capacity Capacity Flow Capacity Capacity Flow
Btu/hr Btu/hr GPM Ft H2O Btu/hr Btu/hr GPM Ft H2O Btu/hr Btu/hr GPM Ft H2O
1800 52,402 37,077 10.48 4.52 48,458 35,078 9.69 3.93 44,287 32,923 8.86 3.34
2000 56,167 40,000 11.23 5.14 51,897 37,823 10.38 4.45 47,456 35,517 9.49 3.79
NGW-026
2200 59,868 42,883 11.97 5.75 55,280 40,531 11.06 4.97 50,569 38,074 10.11 4.24
2400 63,505 45,725 12.70 6.36 58,607 43,202 11.72 5.49 53,626 40,593 10.73 4.69
2600 66,884 48,406 13.38 6.97 61,708 45,727 12.34 6.02 56,456 42,962 11.29 5.13
3000 73,053 53,407 14.61 8.16 67,435 50,483 13.49 7.07 61,622 47,392 12.32 6.01
3200 92,263 66,016 18.45 4.03 85,030 62,299 17.01 3.47 77,441 58,317 15.49 2.93
NGW-040
3500 97,916 70,445 19.58 4.48 90,235 66,482 18.05 3.87 82,210 62,252 16.44 3.27
3700 101,685 73,397 20.34 4.78 93,705 69,270 18.74 4.13 85,389 64,875 17.08 3.49
4000 106,891 77,543 21.38 5.05 98,490 73,179 19.70 4.51 89,746 68,536 17.95 3.81
4200 110,361 80,307 22.07 5.23 101,680 75,785 20.34 4.77 92,650 70,976 18.53 4.03
4400 113,912 83,111 22.78 2.05 104,514 78,164 20.90 1.88 94,772 72,914 18.95 1.57
4700 118,740 87,004 23.75 2.29 108,934 81,822 21.79 2.03 98,780 76,326 19.76 1.70
NGW-050
5000 123,568 90,897 24.71 2.53 113,353 85,480 22.67 2.17 102,788 79,737 20.56 1.82
5300 127,778 94,380 25.56 2.68 117,197 88,744 23.44 2.31 106,264 82,776 21.25 1.93
5600 132,297 98,068 26.46 2.87 121,329 92,205 24.27 2.45 110,005 86,001 22.00 2.05
6000 138,117 102,849 27.62 3.10 126,646 96,689 25.33 2.63 114,817 90,177 22.96 2.20
6200 180,799 129,023 36.16 8.70 168,218 122,767 33.64 7.64 155,235 116,146 31.05 6.61
6500 186,218 133,347 37.24 9.18 173,217 126,836 34.64 8.05 159,806 119,976 31.96 6.96
NGW-080
7000 195,249 140,554 39.05 9.97 181,548 133,617 36.31 8.74 167,425 126,358 33.49 7.55
7500 203,463 147,190 40.69 10.74 189,122 139,896 37.82 9.41 174,341 132,259 34.87 8.13
8000 211,677 153,825 42.34 11.51 196,695 146,176 39.34 10.08 181,257 138,161 36.25 8.70
8400 218,248 159,134 43.65 12.13 202,754 151,199 40.55 10.62 186,790 142,882 37.36 9.16
8600 223,203 162,777 44.64 8.11 207,476 154,734 41.50 7.08 191,249 146,291 38.25 6.11
9000 229,258 167,734 45.85 8.50 213,063 159,427 42.61 7.43 196,356 150,704 39.27 6.41
NGW-100
9500 236,828 173,931 47.37 8.99 220,046 165,292 44.01 7.86 202,741 156,221 40.55 6.79
10000 244,397 180,128 48.88 9.48 227,030 171,158 45.41 8.30 209,125 161,738 41.83 7.16
10500 251,389 185,934 50.28 9.97 233,433 176,624 46.69 8.72 215,016 166,903 43.00 7.52
11000 258,380 191,740 51.68 10.46 239,836 182,090 47.97 9.14 220,906 172,067 44.18 7.88
Note:
1. Cooling capacities are based on 80°/67°F entering air temperarture and 44°F/54°F entering/leaving chilled water
temperature.
14 www.ric.com.kw
PERFORMANCE DATA TABLES - 4 ROWS COOLING COIL
42 ˚F 43 ˚F 44 ˚F 45 ˚F
Model Air Flow
Total Sensible Water Total Sensible Water Total Sensible Water Total Sensible Water
CFM WPD WPD WPD WPD
Capacity Capacity Flow Capacity Capacity Flow Capacity Capacity Flow Capacity Capacity Flow
Btu/hr Btu/hr GPM Ft H2O Btu/hr Btu/hr GPM Ft H2O Btu/hr Btu/hr GPM Ft H2O Btu/hr Btu/hr GPM Ft H2O
1800 79,626 51,641 15.93 5.80 75,602 49,654 15.12 5.20 71,436 47,603 14.3 4.70 67,166 45,501 13.43 4.20
2000 85,871 55,960 17.17 6.63 81,498 53,800 16.30 6.00 76,988 51,577 15.4 5.40 72,363 49,296 14.47 4.83
NGW-026
2200 92,116 60,280 18.42 7.47 87,393 57,947 17.48 6.80 82,540 55,552 16.5 6.10 77,559 53,091 15.51 5.47
2400 98,361 64,599 19.67 8.30 93,289 62,093 18.66 7.60 88,092 59,526 17.6 6.80 82,756 56,886 16.55 6.10
2600 103,852 68,492 20.77 9.20 98,467 65,828 19.69 8.40 92,953 63,100 18.6 7.50 87,281 60,287 17.46 6.73
3000 114,834 76,278 22.97 11.00 108,823 73,299 21.76 10.00 102,675 70,249 20.5 8.90 96,332 67,088 19.27 8.00
3200 137,865 89,799 27.57 4.70 130,615 86,208 26.12 4.20 123,157 82,519 24.6 3.80 115,416 78,681 23.08 3.40
NGW-040
3500 147,234 96,278 29.45 5.30 139,454 92,422 27.89 4.74 131,460 88,464 26.3 4.28 123,170 84,347 24.63 3.82
3700 153,480 100,597 30.70 5.70 145,346 96,565 29.07 5.10 136,995 92,427 27.4 4.60 128,339 88,124 25.67 4.10
4000 162,223 106,724 32.44 6.24 153,585 102,438 30.72 5.64 144,727 98,044 28.9 5.08 135,548 93,471 27.11 4.52
4200 168,051 110,808 33.61 6.60 159,077 106,354 31.82 6.00 149,881 101,788 30.0 5.40 140,354 97,036 28.07 4.80
4400 184,227 120,564 36.85 20.10 175,545 116,319 35.11 18.40 166,676 111,995 33.3 16.80 157,598 107,575 31.52 15.10
4700 192,730 126,561 38.55 21.80 183,597 122,094 36.72 19.95 174,271 117,543 34.9 18.15 164,699 112,873 32.94 16.35
NGW-050
5000 201,233 132,558 40.25 23.50 191,649 127,868 38.33 21.50 181,865 123,090 36.4 19.50 171,800 118,171 34.36 17.60
5300 208,809 138,024 41.76 10.61 198,816 133,129 39.76 23.02 188,591 128,126 37.7 20.89 178,132 123,008 35.63 18.82
5600 216,849 143,755 43.37 5.02 206,425 138,647 41.29 24.56 195,751 133,418 39.2 22.26 184,849 128,076 36.97 20.06
6000 227,260 151,220 45.45 29.10 216,276 145,833 43.26 26.60 205,008 140,304 41.0 24.10 193,548 134,679 38.71 21.70
6200 246,736 162,837 49.35 8.80 234,430 156,779 46.89 8.00 221,907 150,622 44.4 7.30 209,079 144,309 41.82 6.50
6500 254,671 168,506 50.93 9.33 241,944 162,237 48.39 8.49 228,973 155,854 45.8 7.71 208,931 149,308 41.79 6.88
NGW-080
7000 267,895 177,953 53.58 10.20 254,466 171,334 50.89 9.30 240,750 164,575 48.2 8.40 208,683 157,640 41.74 7.50
7500 280,058 186,781 56.01 11.06 265,947 179,817 53.19 10.09 251,537 172,701 50.3 9.08 225,208 165,402 45.04 8.14
8000 292,221 195,609 58.44 11.91 277,427 188,299 55.49 10.87 262,324 180,827 52.5 9.76 241,733 173,164 48.35 8.79
8400 301,951 202,671 60.39 12.60 286,612 195,085 57.32 11.50 270,954 187,328 54.2 10.30 254,953 179,373 50.99 9.30
8600 335,671 222,244 67.13 9.50 318,847 213,957 63.77 8.70 301,733 205,534 60.3 7.80 284,148 196,858 56.83 7.00
9000 345,811 229,547 69.16 10.01 328,445 220,988 65.69 9.16 310,756 212,272 62.2 8.23 292,606 203,305 58.52 7.40
NGW-100
9500 358,487 238,677 71.70 10.66 340,443 229,776 68.09 9.73 322,034 220,694 64.4 8.76 303,179 211,364 60.64 7.90
10000 371,162 247,806 74.23 11.30 352,440 238,565 70.49 10.30 333,312 229,116 66.7 9.30 313,752 219,423 62.75 8.40
10500 383,008 256,448 76.60 11.95 363,612 246,864 72.72 10.90 343,810 237,068 68.8 9.85 323,566 227,017 64.71 8.85
11000 394,853 265,090 78.97 12.60 374,784 255,162 74.96 11.50 354,308 245,019 70.9 10.40 333,379 234,611 66.68 9.30
Note:
1. Cooling capacities are based on 80°/67°F entering air temperarture and 44°F/54°F entering/leaving chilled water
temperature.
15 www.ric.com.kw
PERFORMANCE DATA TABLES - 4 ROWS COOLING COIL
46 ˚F 47 ˚F 48 ˚F
Model Air Flow
Total Sensible Water Total Sensible Water Total Sensible Water
CFM WPD WPD WPD
Capacity Capacity Flow Capacity Capacity Flow Capacity Capacity Flow
Btu/hr Btu/hr GPM Ft H2O Btu/hr Btu/hr GPM Ft H2O Btu/hr Btu/hr GPM Ft H2O
1800 62,736 43,313 12.55 3.70 58,158 41,037 11.63 3.30 53,359 38,619 10.67 2.80
2000 67,568 46,921 13.51 4.27 62,625 44,455 12.53 3.77 57,455 41,839 11.49 3.20
NGW-026
2200 72,399 50,529 14.48 4.83 67,092 47,874 13.42 4.23 61,550 45,060 12.31 3.60
2400 77,231 54,137 15.45 5.40 71,559 51,292 14.31 4.70 65,646 48,280 13.13 4.00
2600 81,441 57,372 16.29 5.93 75,426 54,343 15.09 5.17 69,189 51,154 13.84 4.40
3000 89,860 63,843 17.97 7.00 83,160 60,446 16.63 6.10 76,275 56,902 15.26 5.20
3200 107,447 74,712 21.49 3.00 99,107 70,513 19.82 2.60 90,367 66,043 18.07 2.20
NGW-040
3500 114,653 80,095 22.93 3.36 105,758 75,606 21.15 2.90 96,465 70,838 19.29 2.44
3700 119,457 83,684 23.89 3.60 110,192 79,001 22.04 3.10 100,531 74,034 20.11 2.60
4000 126,145 88,760 25.23 3.96 116,347 83,792 23.27 3.40 106,157 78,535 21.23 2.90
4200 130,604 92,144 26.12 4.20 120,451 86,986 24.09 3.60 109,907 81,536 21.98 3.10
4400 148,253 103,017 29.65 13.50 138,706 98,347 27.74 12.00 128,900 93,515 25.78 10.50
4700 154,904 108,088 30.98 14.65 144,881 103,169 28.98 12.95 134,553 98,062 26.91 11.35
NGW-050
5000 161,554 113,158 32.31 15.80 151,056 107,991 30.21 13.90 140,205 102,609 28.04 12.20
5300 167,451 117,768 33.49 16.86 156,516 112,374 31.30 14.90 145,233 106,755 29.05 13.04
5600 173,724 122,609 34.74 17.96 162,334 116,977 32.47 15.88 150,573 111,101 30.11 13.88
6000 181,838 128,909 36.37 19.40 169,853 122,967 33.97 17.20 157,485 116,763 31.50 15.00
6200 195,942 137,819 39.19 5.80 182,361 131,056 36.47 5.10 168,451 124,054 33.69 4.40
6500 202,065 142,562 40.41 6.14 188,040 135,564 37.61 5.40 173,656 128,304 34.73 4.63
NGW-080
7000 212,271 150,467 42.45 6.70 197,504 143,076 39.50 5.90 182,331 135,386 36.47 5.00
7500 221,637 157,847 44.33 7.24 206,147 150,063 41.23 6.36 190,210 141,947 38.04 5.43
8000 231,004 165,227 46.20 7.77 214,789 157,050 42.96 6.83 198,089 148,509 39.62 5.86
8400 238,497 171,131 47.70 8.20 221,703 162,640 44.34 7.20 204,392 153,758 40.88 6.20
8600 266,289 188,022 53.26 6.20 247,747 178,759 49.55 5.50 228,780 169,181 45.76 4.70
9000 274,102 194,128 54.82 6.54 254,987 184,559 51.00 5.79 225,095 174,627 45.02 4.96
NGW-100
9500 283,868 201,760 56.77 6.97 264,037 191,809 52.81 6.14 220,488 181,435 44.10 5.28
10000 293,634 209,392 58.73 7.40 273,087 199,059 54.62 6.50 215,882 188,242 43.18 5.60
10500 302,743 216,610 60.55 7.80 281,494 205,894 56.30 6.85 241,563 194,670 48.31 5.90
11000 311,852 223,827 62.37 8.20 289,900 212,729 57.98 7.20 267,243 201,098 53.45 6.20
Note:
1. Cooling capacities are based on 80°/67°F entering air temperarture and 44°F/54°F entering/leaving chilled water
temperature.
16 www.ric.com.kw
PERFORMANCE DATA TABLES - HEATING COIL
1 ROW 2 ROWS
Model Air Flow
Total Capacity Water Flow WPD Total Capacity Water Flow WPD
CFM
Btu/hr GPM Ft H2O Btu/hr GPM Ft H2O
1800 75,503 7.70 3.84 129,831 13.30 2.94
2000 80,605 8.30 4.31 140,125 14.30 3.34
NGW-026
Note:
1. Heating capacities are based on 70°F entering air temperarture and 180°F/160°F entering/leaving heating water
temperature.
17 www.ric.com.kw
UNIT DIMENSIONS
18 www.ric.com.kw
TYPICAL WIRING DIAGRAM
19 www.ric.com.kw
NOTES
20 www.ric.com.kw
NOTES
21 www.ric.com.kw
About RIC نبذة عن ال�شركة
Refrigeration Industries Company (KSE 504) is a group holding �شركة �صناعات التربيد )متداولة يف �سوق الكويت للأوراق املالية برقم
company with diversified interests in manufacturing, contracting and ( هي �شركة متنوعة الأن�شطة تعمل يف جمال الت�صنيع واملقاوالت504
services. Recognized regionally for our engineering capabilities and ونحن نقدم جمموعة كبرية من املنتجات واخلدمات واحللول.واخلدمات
management excellence, RIC and its subsidiaries offer a wide range وقد حازت.التقنية يف جمال مواجهة الظروف املناخية وحلول التخزين
of high quality products and services that cater to both residential and .ال�شركة على �إعرتاف �إقليمي بقدراتها الهند�سية وكفاءتها الإدارية
commercial customers, in the areas of climate control technologies �شركة �صناعات التربيد هي جمموعة �شركات تهدف �إلى توفري �أعلى
and specialized storage solutions. م�ستويات اجلودة من حيث املنتجات واخلدمات التي تلبي �إحتياجات
وعلى مدى ثالثة و �أربعون عاما م�ضت على.عمالئها ال�سكنية والتجارية
In view of the growing Kuwait infrastructure and the limitations
�إن�شاء �شركتنا فقد �إ�ستطعنا �أن نوطد �أقدامنا يف جميع قطاعات ال�سوق
imposed on it by the country’s arid climate, the Refrigeration Industries �إال �أننا �أ�شد فخرا, ونحن �إذ نفتخر بالإجنازات التي حققناها.الكويتي
Company was established 43 years ago in 1973, by Amiri Decree. The ب�أننا متكنا من الوقوف �إلى جانب �أهل الكويت على مدى �سنوات طويلة
company’s operations began with the construction of the first cold يف مواجهة تقلبات الظروف املناخية القا�سية �سواء من حيث درجات
stores in the region, to enable the storage of the imported foods, on .احلرارة العالية �أو الأتربة �أو الرطوبة
which Kuwait relied. Along with the development and advancement فقد،وب�إعتبارها �إحدى ال�شركات ال�صناعية العاملة يف دولة الكويت
of the country, so has RIC prospered and expanded, and is now a وقد،واجهت ال�شركة حتديات و�آمال كبرية يف �سعيها لتحقيق النجاح
milestone in the history of modern Kuwait. كانت ال�شركة – وال تزال – معلما من املعامل املهمة يف نظر �أهل الكويت
RIC takes pride in its successful record and the many accolades it ملا قدمته من منتجات وخدمات �إ�ستطاعت �أن تغري الطبيعة القا�سية
has garnered over time, but the greatest achievement has been the ال يزال ال�س�ؤال مطروحا حول، عاما تقريبا43 فبعد نحو.ملناخ الكويت
provision of comfort and protection from the harsh climate, to the فهل �إ�ستطاعت ال�شركة �أن تتحمل م�س�ؤولياتها،حتقيقنا لهذه التوقعات
people of Kuwait.
فعلى مدى ثالثة و �أربعني،على الوجه الأكمل؟ وي�أتي الرد بالإيجاب
عاما تقريبا مل تتوقف ال�شركة خاللها عن الإ�ستمرار يف تقدمي خدماتها
More than 43 years of uninterrupted service, overcoming extreme و�أعمالها رغم ال�صعوبات التي متثلت يف ظروف الطق�س القا�سية �أو
weather conditions, war, economic recessions and ever increasing فقد كانت كل،احلروب �أو الك�ساد االقت�صادي �أو �إرتفاع حدة املناف�سة
competition, is testimony to the fact that RIC has met the expectations واحدة من هذه الظروف مبثابة �شهادة على �أننا حققنا ما وعدنا به وما
and responsibilities that was envisioned at the beginning and also .عقدنا العزم على تنفيذه
highlights the tenacity and vision to exceed them in the future. حقائق وتواريخ
Facts throughout the years . مت �إن�شاء امل�ستودعات بناء على مر�سوم �أمريي1973
1973 Warehouses were established by Amiri Decree. عهدت وزارة ال�صحة الكويتية ل�شركة �صناعات التربيد ب�إن�شاء1979
وقد كان هذا املجمع حينها,جممع م�ستودعات خمازن التربيد الطبية
1979 RIC Constructed the Medical Cold Stores Complex, the world’s وقد و�صلت تكلفته �إلى,هو الأ�ضخم من نوعه على م�ستوى العامل
largest at that time. . دينار كويتي12,000,000
1980 RIC Air Conditioning manufacturing plant set up in Sulaibya. مت �إن�شاء م�صنع مكيفات الهواء التابع ل�شركة �صناعات التربيد يف1980
1981 Production of Package & Mini-Split A/Cs started under York-Gulf. .ال�صليبية
بدء �إنتاج �أجهزة التكييف املدجمة واملنف�صلة ال�صغرية حتت عالمة1981
1984 RIC was listed in Kuwait Stock Exchange. .York-Gulf
1986 COOLEX brand Production Launched. . مت قيد �شركة �صناعات التربيد يف �سوق الكويت للأوراق املالية1984
1991 RIC rebuilt the manufacturing plant destroyed during the war. . بدء �إنتاج مكيفات عالمة كولك�س1986
1997 Achieved ISO Certification ISO 9001:1994.
قامت �شركة �صناعات التربيد ب�إعادة بناء م�صنعها الذي دمرته1991
.احلرب
2002 ETL Designed testing lab became fully operational. 1994:9001 احل�صول على �شهادة الآيزو1997
2004 Privatization of RIC. (ETL) بدء ت�شغيل خمترب فح�ص وحدات التكييف2002
2010 COOLEX becomes the first A/C Unit to Pass MEW’s new . خ�صخ�صة �شركة �صناعات التربيد2004
regulations. كانت وحدات كولك�س �أول وحدات تكييف هواء جتتاز اللوائح التي2010
.(�أقرتها )وزارة الكهرباء واملاء
2010 RIC Factory Renovation and Expansion into neighboring countries.
مت جتديد م�صنع �شركة �صناعات التربيد وبدء التو�سع والت�صدير2010
2012 Achieved UL & AHRI Certification for Coolex Units. .�إلى الدول املجاورة
2014 Achieved SASO Certification for Concealed Ducted Split Series. . لأجهزة التكييف كولك�سAHRI وUL احل�صول على �شهادة2012
. لأجهزة التكييف املنف�صلةSASO احل�صول على �شهادة2014
2014 Achieved EUROVENT Certification for Air Handling Units AHU.
. لأجهزة مناولة الهواءEUROVENT احل�صول على �شهادة2014
2014 Achieved UL Certification for Air Cooled Chillers. . ملربدات الهواء ال�شيلرUL احل�صول على �شهادة2014
2015 Achieved ISO 17025 Certification for Psychrometric Laboratory. . ملخترب ال�سيكرومرتيةISO 17025 احل�صول على �شهادة الأيزو2015
2016 Achieved Energy Efficiency Certification for Concealed Ducted احل�صول على �شهادة كفاء الطاقة لأجهزة التكييف املنف�صلة و2016
Split Series & Rooftop Package units (Kingdom of Bahrain). .(الوحدات املدجمة )مملكة البحرين
22 www.coolex.com.kw
COOLEX DISTRIBUTORS
United Arab Emirates UAE
Obaid Humaid Al-Tayer Engineering Division
Al Tayer Group
Address : Dubai – UAE, PO Box 2623
Tel : +971 4 2011272
Fax : +971 4 2825008
Mobile : +971 50 3500747
Email : [email protected]
Website : www.altayer.com
Please contact Sales and Marketing Department CENTRAL AIR CONDITIONING AND SPLIT UNIT
[email protected] or www.coolex.com.kw for Coolex continuously works towards the improvement of
specific information on the current design and its products. Hence, the design and specifications of the
specifications. Ref no.: CNW18-5-000 ordered product may vary without prior notice.