Output Ratings: Diesel Generator Set Exclusively From Your Cat Dealer

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

GEP50-4

Diesel Generator Set


Exclusively from your Cat dealer

EU Stage II Emissions Compliant


Suitable for Mobile Applications in the European Community
EU Stage II Emissions Compliant

Output Ratings

Generating Set Model Prime* Standby*

380-415V,50Hz 45.0 kVA 49.7 kVA


36.0 kW 39.8 kW

- -
- -

* Refer to ratings definitions on page 4.


Ratings at 0.8 power factor.

Technical Data
Engine Make & Model: Perkins 1103C-33TG2/3

Alternator Model: LL2014C

Base Frame Type: Fbc2 - (08Hr)

Circuit Breaker Type: 3 Pole MCB

Frequency: 50 Hz 60 Hz

Engine Speed: RPM 1500 -

Fuel Tank Capacity: litres (US gal) 219 (57.9)

Fuel Consumption, Prime: l/hr (US gal/hr) 10.6 (2.8) -

Fuel Consumption, Standby : l/hr (US gal/hr) 11.8 (3.1) -


Engine Techncial Data
Physical Data Lubrication system
Manufacturer: Perkins Oil Filter Type: Spin-On, Full Flow
Model: 1103C-33TG2/3 Total Oil Capacity l (US gal): 8.3 (2.2)
No. of Cylinders/Alignment: 3 / In Line Oil Pan l (US gal): 7.8 (2.1)
Cycle: 4 Stroke Oil Type: API CG4 / CH4 15W-40
Induction: Turbocharged Cooling Method: Water

Cooling Method: Water


Governing Type: Mechanical Performance 50 Hz 60 Hz
Governing Class: ISO 8528 G2
Engine Speed: RPM 1500 -
Compression Ratio: 18.2:1
Gross Engine Power: kW (hp)
Displacement: l (cu.in) 3.3 (201.4)
-Standby: 46.5 (62.0) -
Bore/Stroke: mm (in) 105.0 (4.1)/127.0 (5.0)
-Prime: 41.9 (56.0) -
Moment of Inertia: kg m² (lb. in²) 1.14 (3896)
BMEP: kPa (psi)
Engine Electrical System: -Standby: 1127.0 (163.5) -
-Voltage/Ground: 12/Negative -Prime: 1016.0 (147.4) -
-Battery Charger Amps: 65 Regenerative Power: kW 7.7 -
Weight: kg (lb) - Dry: 420 (926)
- Wet: 438 (966)
Fuel System
Fuel Filter Type: Replaceable Element
Air System 50 Hz 60 Hz Recommended Fuel: Class A2 Diesel
Fuel Consumption: l/hr (US gal/hr)
Air Filter Type: Replaceable Element
110% 100% 75% 50%
Combustion Air Flow:
Load Load Load Load
m³/min (cfm) -Standby: 3.1 (109) -
Prime
-Prime: 2.9 (102) -
50 Hz 11.8 (3.1) 10.6 (2.8) 7.9 (2.1) 5.6 (1.5)
Max. Combustion Air Intake
60 Hz - - - -
Restriction: kPa (in H2O) 5.0 (20.1) -
Radiator Cooling Air Flow:
Standby
m³/min (cfm) 62.4 (2204) -
50 Hz 11.8 (3.1) 8.7 (2.3) 6.1 (1.6)
External Restriction to
60 Hz - - -
Cooling Air Flow: Pa (in H2O) 125 (0.5) -
(based on diesel fuel with a specific gravity of 0.85 and conforming to
BS2869, Class A2)

Cooling System 50 Hz 60 Hz Exhaust System 50 Hz 60 Hz


Cooling System Capacity: Silencer Type: Industrial
l (US gal) 10.2 (2.7) - Silencer Noise Reduction SD50 (1)
Water Pump Type: Centrifugal Pressure Drop Across
Heat Rejected to Water & Silencer System: kPa (in Hg) 1.14 (0.337) -
Lube Oil: kW (Btu/min) Silencer Noise Reduction
-Standby: 29.0 (1649) - Level: dB 15 -
-Prime: 26.4 (1501) - Max. Allowable Back
Heat Radiation to Room: Pressure: kPa (in. Hg) 12.0 (3.5) -
kW (Btu/min) -Standby: 8.5 (483) - Exhaust Gas Flow:
-Prime: 7.7 (438) - m³/min (cfm) -Standby: 7.7 (272) -
Radiator Fan Load: kW (hp) 1.0 (1.3) - -Prime: 7.0 (247) -
Exhaust Gas Temperature: °C (°F)
m³/min (cfm) -Standby: 660 (1220) -
Cooling system designed to operate in ambient conditions up to 50°C -Prime: 610 (1130) -
(122°F). Contact your local Olympian dealer for power ratings at specific
site conditions.

Consult your Olympian representative for more information


Alternator Performance Data
50 Hz 60 Hz
Data Item 415/240V 400/230V 380/220V

Motor Starting
Capability* kVA 90 84 76 - - - - - -

Short Circuit
Capacity** % 300 300 300 300 300 300 300 300 300

Reactances:
Per Unit

Xd 2.662 2.866 3.175 - - - - - -

X'd 0.120 0.130 0.140 - - - - - -

X''d 0.059 0.063 0.070 - - - - - -

Reactances shown are applicable to standby ratings.


* Based on 30% voltage dip.
** With optional Permanent Magnet generator or AREP excitation.

Alternator Technical Data

Physical Data Operating Data

Manufacturer: OLYMPIAN Overspeed: RPM 2250

Model: LL2014C Voltage Regulation (steady state) (%): +/- 0.5

No. of Bearings: 1 Wave Form NEMA = TIF: 50

Insulation Class: H Wave Form IEC = THF: 2.0%

Winding Pitch - Code: 2/3 - 6 Total Harmonic Content LL/LN: 4.0%

Supression is in line with European


Wires: 12 Radio Interference: Standard EN61000-6

Ingress Protection Rating: IP23 Radiant Heat: kW (Btu/min)

Excitation System: -50 Hz: 5.7 (324)


SHUNT

-60 Hz: -
AVR Model: R250

Consult your Olympian representative for more information


Technical Data
3 Phase Ratings and Performance at 50 Hz, 1500 RPM 3 Phase Ratings and Performance at 60 Hz, - RPM

Voltage Prime Standby Voltage Prime Standby


kVA kW kVA kW kVA kW kVA kW
415/240V 45.0 36.0 49.8 39.8
400/230V 45.0 36.0 49.7 39.8
380/220V 44.8 35.8 49.4 39.5

Weights & Dimensions


Weights: kg (lb) Dimensions: mm (in)
Net (+ lube oil) 909 (2004) Length 1925 (75.8)
Wet (+ lube oil & coolant) 922 (2033) Width 1120 (44.1)
Fuel, lube oil & coolant 1107 (2442) Height 1361 (53.6)

Note: General configuration not to be used


for installation. See general dimension
drawings for detail.

Definitions General Data


Standby Rating Documents
These ratings are applicable for supplying continuous electrical A full set of operation and maintenance manuals and circuit wiring
power (at variable load) in the event of a utility power failure. No diagrams.
overload is permitted on these ratings. The alternator on this model
is peak continuous rated (as defined in ISO 8528-3).
Quality Standards
BS4999, BS5000, BSEN60034, BSEN61000, IEC60034.
Prime Rating
These ratings are applicable for supplying continuous electrical
power (at variable load) in lieu of commercially purchased power.
There is no limitation to the annual hours of operation and this Warranty
model can supply 10% overload power for 1 hour in 12 hours. All equipment carries full manufacturer's warranty.

Standard Reference Conditions


Note: Standard reference conditions 25°C (77°F) air inlet temp,
100m (328ft) A.S.L. 30% relative humidity. Fuel consumption data
at full load with diesel fuel with specific gravity of 0.85 and
conforming to BS2869: 1998, Class A2.

Information contained in this publication may be considered confidential. www.CAT-ElectricPower.com


Discretion is recommended when distributing.
Materials and specifications are subject to change without notice. © 2010 Caterpillar
Market: International
CAT, CATERPILLAR, their respective logos OLYMPIAN, ''Caterpillar Yellow'' and the "Power Edge" trade dress, as well as All rights reserved.
LEHF0098-01
LEHF0098-00 (08-10) corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission. Printed in U.S.A.

You might also like