Mean Well SE-100-5

You are on page 1of 2

100W Single Output Switching Power Supply SE-100 series

■ Features :
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
LED indicator for power on
100% full load burn-in test
2 years warranty

SPECIFICATION
MODEL SE-100-5 SE-100-7.5 SE-100-9 SE-100-12 SE-100-15 SE-100-24 SE-100-48
DC VOLTAGE 5V 7.5V 9V 12V 15V 24V 48V
RATED CURRENT 20A 13.6A 11.2A 8.5A 7A 4.5A 2.3A
CURRENT RANGE 0 ~ 20A 0 ~ 13.6A 0 ~ 11.2A 0 ~ 8.5A 0 ~ 7A 0 ~ 4.5A 0 ~ 2.3A
RATED POWER 100W 102W 100.8W 102W 105W 108W 110.4W
RIPPLE & NOISE (max.) Note.2 80mVp-p 120mVp-p 120mVp-p 120mVp-p 120mVp-p 120mVp-p 150mVp-p
OUTPUT VOLTAGE ADJ. RANGE 4.75 ~ 5.5V 7.13 ~ 8.3V 8.55 ~ 9.9V 11.4 ~ 13.2V 14.25 ~ 16.5V 22.8 ~ 26.4V 45.6 ~ 52.8V
VOLTAGE TOLERANCE Note.3 ±2.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
LINE REGULATION Note.4 ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5%
LOAD REGULATION Note.5 ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5%
SETUP, RISE TIME 1000ms, 20ms/230VAC 1000ms, 20ms/115VAC at full load
EO

HOLD UP TIME (Typ.) 30ms/230VAC 25ms/115VAC at full load


VOLTAGE RANGE Note.8 85 ~ 132VAC / 176 ~ 264VAC selected by switch 248 ~ 373VDC
FREQUENCY RANGE 47 ~ 63Hz
EFFICIENCY (Typ.) 80% 81% 81% 83% 84% 86% 86%
INPUT
AC CURRENT (Typ.) 2A/115VAC 1.2A/230VAC
L

INRUSH CURRENT (Typ.) COLD START 45A


LEAKAGE CURRENT <2mA / 240VAC
110 ~ 150% rated output power
OVERLOAD Protection type : Hiccup mode, recovers automatically after fault condition is removed
PROTECTION
5.75 ~ 6.75V 8.6 ~ 10.1V 10.4 ~ 12.2V 13.8 ~ 16.2V 17.25 ~ 20.25V 27.6 ~ 32.4V 55.2 ~ 64.8V
OVER VOLTAGE
Protection type : Hiccup mode, recovers automatically after fault condition is removed
WORKING TEMP. -20 ~ +60℃ (Refer to "Derating Curve")
WORKING HUMIDITY 20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/℃ (0 ~ 50℃)
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
SAFETY STANDARDS Note.6 UL60950-1, CB(IEC60950-1),CCC GB4943.1:2011 approved
SAFETY & WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
EMC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
(Note 7) EMC EMISSION Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3
EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-1, light industry level, criteria A
MTBF 320.7Khrs min. MIL-HDBK-217F (25℃)
OTHERS DIMENSION 159*97*38mm (L*W*H)
PACKING 0.55Kg; 30pcs/17.5Kg/0.97CUFT
1. All parameters not specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
NOTE
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Line regulation is measured from low line to high line at rated load.
5. Load regulation is measured from 0% to 100% rated load.
6. For the request of GB4943.1,the power supply is only suitable for use in the altitude 2000m below and the non tropical climate condition.
7. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
8. When using DC voltage as the input, please connect positive pole of input voltage to mark “N” of the terminal block and negative pole of input voltage
to mark “L” of the terminal block.

File Name:SE-100-SPEC 2017-07-07


100W Single Output Switching Power Supply SE-100 series

Mechanical Specification Case No. 901 Unit:mm

152.5

7
3.5
1

9.5

65
3

84.5
97
8.2
5
3
6 2-M

+V ADJ.

.5
ψ3
4.5
24 78
Terminal Pin No. Assignment 159
Pin No. Assignment Pin No. Assignment
1 AC/L 4,5 DC OUTPUT -V 6.5 150
2 AC/N 6,7 DC OUTPUT +V
3 FG
9

9
18.5
ψ3

3.5
3-

38
18
M3
.5

28.5
EO

22 117

Block Diagram fosc : 60KHz


220
L

110

RECTIFIERS POWER RECTIFIERS +V


EMI
I/P & &
FILTER SWITCHING -V
FILTER FILTER

DETECTION
FG CIRCUIT
PWM
O.L.P.
CONTROL
O.V.P.

Derating Curve Static Characteristics

100
100
Others
90
80
80

60 70
50 5V
LOAD (%)

LOAD (%)

60
40
50
20
40

-20 0 10 20 30 40 50 60 70 (HORIZONTAL) 85 100 115 120 125 130 132


176 200 220 240 264
AMBIENT TEMPERATURE (℃) INPUT VOLTAGE (VAC) 60Hz

File Name:SE-100-SPEC 2017-07-07