PCS-902 - X - Instruction Manual - EN - Overseas General - X - R2.10 PDF
PCS-902 - X - Instruction Manual - EN - Overseas General - X - R2.10 PDF
PCS-902 - X - Instruction Manual - EN - Overseas General - X - R2.10 PDF
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore, this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
DANGER! means that death, severe personal injury and considerable equipment damage
will occur if safety precautions are disregarded.
WARNING! means that death, severe personal and considerable equipment damage
could occur if safety precautions are disregarded.
CAUTION! means that light personal injury or equipment damage may occur if safety
precautions are disregarded.
NOTICE! is particularly applies to damage to device and to resulting damage of the protected
equipment.
DANGER!
NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live. Open CT circuit will produce a dangerously high
voltage that cause death.
WARNING!
ONLY qualified personnel should work on or in the vicinity of this device. This personnel
MUST be familiar with all safety regulations and service procedures described in this
manual. During operating of electrical device, certain part of the device is under high
voltage. Severe personal injury and significant device damage could result from
improper behavior.
WARNING!
Do NOT touch the exposed terminals of this device while the power supply is on. The
generated high voltage causes death, injury, and device damage.
WARNING!
Thirty seconds is NECESSARY for discharging the voltage. Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply.
CAUTION!
Earthing
Operating environment
ONLY use the device within the range of ambient environment and in an
Ratings
Check the input ratings BEFORE applying AC voltage/current and power supply to
the device.
Do NOT attach or remove printed circuit board if the device is powered on.
External circuit
Check the supply voltage used when connecting the device output contacts to
external circuits, in order to prevent overheating.
Connection cable
NOTICE!
We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
Documentation Structure
The manual provides a functional and technical description of this relay and a comprehensive set
of instructions for the relay’s use and application.
1 Introduction
Briefly introduce the application, functions and features about this device.
2 Technical Data
Introduce the technical data about this device, such as electrical specifications, mechanical
specifications, ambient temperature and humidity range, communication port parameters, type
tests, setting ranges and accuracy limits and the certifications that our products have passed.
3 Operation Theory
Introduce a comprehensive and detailed functional description of all protective elements.
4 Supervision
Introduce the automatic self-supervision function of this device.
5 Management
Introduce the management function (measurement and recording) of this device.
6 Hardware
Introduce the main function carried out by each plug-in module of this device and providing the
definition of pins of each plug-in module.
7 Settings
List settings including system settings, communication settings, label settings, logic links and etc.,
and some notes about the setting application.
9 Configurable Function
Introduce configurable function of the device and all configurable signals are listed.
10 Communication
Introduce the communication port and protocol which this device can support, IEC60970-5-103,
IEC61850 and DNP3.0 protocols are introduced in details.
11 Installation
Introduce the recommendations on unpacking, handling, inspection and storage of this device. A
guide to the mechanical and electrical installation of this device is also provided, incorporating
earthing recommendations. A typical wiring connection to this device is indicated.
12 Commissioning
Introduce how to commission this device, comprising checks on the calibration and functionality of
this device.
13 Maintenance
A general maintenance policy for this device is outlined.
Deviations may be permitted in drawings and tables when the type of designator can be obviously
derived from the illustration.
&
AND gate
≥1
OR gate
Comparator
BI
Binary signal via opto-coupler
SET I>
Input signal from comparator with setting
EN
Input signal of logic setting for function enabling
SIG
Input of binary signal except those signals via opto-coupler
XXX
Output signal
Timer
t
t
Timer (optional definite-time or inverse-time characteristic)
10ms 0ms
Timer [delay pickup (10ms), delay dropoff (0ms), non-settable]
[XXX] 0ms
Timer (delay pickup, settable)
0ms [XXX]
Timer (delay dropoff, settable)
[XXX] [XXX]
Timer (delay pickup, delay dropoff, settable)
IDMT
Timer (inverse-time characteristic)
Basic
A, B, C L1, L2, L3 R, Y, B
AN, BN, CN L1N, L2N, L3N RN,YN, BN
ABC L123 RYB
U (voltage) V U
Example
Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN
Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB
Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR
U0, U1, U2 VN, V1, V2 UN, U1, U2
1 Introduction
Table of Contents
1 Introduction ....................................................................................... 1-a
1.1 Application....................................................................................................... 1-1
1.2 Function ........................................................................................................... 1-4
1.3 Features ........................................................................................................... 1-7
List of Figures
Figure 1.1-1 Typical application of PCS-902 for single circuit breaker ................................. 1-1
Figure 1.1-2 Typical application of PCS-902 for double circuit breakers .............................. 1-2
1.1 Application
PCS-902 is a digital line distance protection with the main and back-up protection functions, which
is designed for overhead line or cables and hybrid transmission lines of various voltage levels.
52 52
In the case of main protection, PCS-902 provides dual-channels pilot distance protection (PUTT,
POTT, blocking and unblocking) and pilot directional earth-fault protection (selectable for
independent communication channel or sharing channel with POTT), which can clear any internal
fault instantaneously for the whole line with the aid of protection signal. Deviation of power
frequency component (DPFC) distance protection with fixed forward direction can perform
extremely high speed operation for close-up faults. There is direct transfer trip (DTT) feature
incorporated in the device.
PCS-902 also includes distance protection (1 forward zones and 4 settable forward or reverse
zone distance protection with selectable mho or quadrilateral characteristic, dedicated pilot
distance zone for pilot distance protection), out-of-step protection, 4 stages directional earth fault
protection, 4 stages directional phase overcurrent protection, 4 stages directional
negative-sequence overcurrent protection, 3 stages voltage protection (under/over voltage
protection), 1 stage negative-sequence overvoltage protection, 4 stages frequency protection
(under/over frequency protection), broken conductor protection, reverse power protection, pole
discrepancy protection, breaker failure protection, thermal overload protection, and dead zone
protection etc. Morever, a backup overcurrent and earth fault protection will be automatically
enabled when VT circuit fails.
In addition, stub differential protection is provided for one and a half breakers arrangement when
transmission line is put into maintenance.
PCS-902 can be configured to support single circuit breaker application or double circuit breakers
application by PCS-Explorer. If the device is applied to double circuit breakers mode, all protection
functions related to the number of circuit breaker will be affected, including circuit breaker position
supervision, breaker failure protection, dead zone protection, pole discrepancy protection,
synchrocheck, automatic reclosure, trip logic, CT circuit supervision, control and synchrocheck for
manual closing.
Bus1
Single-phase
voltage
52
PCS-902 Line 1
Three-phase
voltage
52
Line 2
Single-phase
voltage
52
Bus2
PCS-902 has selectable mode of single-phase tripping or three-phase tripping and configurable
auto-reclosing mode for 1-pole, 3-poles and 1/3-pole operation.
PCS-902 with appropriate selection of integrated protection functions can be applied for various
voltage levels and primary equipment such as cables, overhead lines, interconnectors and
transformer feeder, etc. It also supports configurable binary inputs, binary outputs, LEDs and IEC
61850 protocol.
BUS
52
81
21D 59Q
78
FL 59P
Data Transmit/Receive
27P
50DZ 87STB (Only for one and a half breakers arrangement)
SOTF 25 79
LINE
25 Fault location FL
1.2 Function
1. Protection Function
One zone distance protection with fixed forward direction (including phase-to-ground and
phase-to-phase, mho or quadrilateral characteristic)
One zone pilot distance protection with fixed forward direction (including phase-to-ground
and phase-to-phase, mho or quadrilateral characteristic)
One zone pilot distance protection with fixed reverse direction (including phase-to-ground
and phase-to-phase, mho or quadrilateral characteristic)
Four zones distance protection with settable forward or reverse direction (including
phase-to-ground and phase-to-phase, mho or quadrilateral characteristic)
Power swing blocking releasing, selectable for each of above mentioned zones
Out-of-step protection
Overcurrent protection
Four stages directional earth fault protection, selectable time characteristic (definite-time
or inverse-time) and directionality (forward direction, reverse direction or non-directional)
Voltage protection
Frequency protection
Control function
Synchro-checking
Automatic reclosure (single shot or multi-shot (max. 4) for 1-pole AR and 3-pole AR)
Dual-channels redundancy
Energy metering (active and reactive energy are calculated in import respectively export
direction)
3. Logic
4. Additional function
Fault location
VT circuit supervision
CT circuit supervision
Self diagnostic
Event Recorder including 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs.
Disturbance recorder including 32 disturbance records with waveforms (The file format of
disturbance recorder is compatible with international COMTRADE file.)
Conventional
PPS (RS-485): Pulse per second (PPS) via RS-485 differential level
PPM (DIN): Pulse per minute (PPM) via the optical coupler
PPS (DIN): Pulse per second (PPS) via the optical coupler
SAS
Advanced
NoTimeSync
5. Monitoring
Channel status
Frequency
6. Communication
Optional 2 or 4 Ethernet ports (depend on the chosen type of MON plug-in module) conform
to IEC 61850 protocol, DNP3.0 protocol or IEC 60870-5-103 protocol over TCP/IP
Optional 2 Ethernet ports via optic fiber (ST interface) conform to IEC 61850 protocol, DNP3.0
protocol or IEC 60870-5-103 protocol over TCP/IP
7. User Interface
Friendly HMI interface with LCD and 9-button keypad on the front panel.
Auxiliary software—PCS-Explorer
1.3 Features
The intelligent device integrated with protection, control and monitor provides powerful
protection function, flexible protection configuration, user programmable logic and
configurable binary input and binary output, which can meet with various application
requirements.
Fast fault clearance for faults within the protected line, the operating time is less than 10 ms
for close-up faults, less than 15ms for faults in the middle of protected line and less than 25ms
for remote end faults.
The unique DPFC distance element integrated in the protective device provides extremely
high speed operation and insensitive to power swing.
Self-adaptive floating threshold which only reflects deviation of power frequency component
improves the protection sensitivity and stability under the condition of load fluctuation and
system disturbance.
Advanced and reliable power swing blocking releasing feature which ensure distance
protection operate correctly for internal fault during power swing and prevent distance
protection from maloperation during power swing
Flexible automatic reclosure supports various initiation modes and check modes
Multiple setting groups with password protection and setting value saved permanently before
modification
Powerful PC tool software can fulfill protection function configuration, modify setting and
waveform analysis.
2 Technical Data
Table of Contents
2 Technical Data ................................................................................... 2-a
2.1 Electrical Specifications ................................................................................. 2-1
2.1.1 AC Current Input .................................................................................................................. 2-1
“System phase sequence”, which can be set by PCS-Explorer, this setting informs the
device of the actual system phase sequence, either ABC or ACB. CT and VT inputs on
the device, labeled as A, B and C, must be connected to system phase A, B and C for
correct operation.
2.6 Certifications
ISO9001:2008
ISO14001:2004
OHSAS18001:2007
ISO10012:2003
CMMI L5
2.7 Terminals
Connection Type Wire Size
2
AC current Screw terminals, 2.5mm lead
AC voltage Screw terminals, 1.5mm2 lead
Power supply Screw terminals, 1.0mm2~2.5mm2 lead
2 2
Contact I/O Screw terminals, 1.0mm ~2.5mm lead
Grounding (Earthing) Connection BVR type, 2.5mm²~6.0mm2 lead
2.10.18 Auto-reclosing
Phase difference setting range 0~89 (Deg)
Accuracy 2.0Deg
Voltage difference setting range 0.02Un~0.8Un (V)
Accuracy Max(0.01Un, 2.5%)
Frequency difference setting range 0.02~1 (Hz)
Accuracy 0.01Hz
Operating time of synchronism check ≤1%×Setting+20ms
Operating time of energizing check ≤1%×Setting+20ms
Operating time of auto-reclosing ≤1%×Setting+20ms
3 Operation Theory
Table of Contents
3 Operation Theory .............................................................................. 3-a
3.1 System Parameters ......................................................................................... 3-1
3.1.1 General Application.............................................................................................................. 3-1
List of Figures
Figure 3.3-1 Logic diagram of frequency calculation.............................................................. 3-3
Figure 3.7-1 Operating time of single-phase fault (50Hz, SIR=1) ......................................... 3-25
Figure 3.7-2 Operating time of single-phase fault (60Hz, SIR=1) ......................................... 3-25
Figure 3.7-3 Operating time of two-phase fault (50Hz, SIR=1) ............................................. 3-26
Figure 3.7-4 Operating time of two-phase fault (60Hz, SIR=1) ............................................. 3-26
Figure 3.7-5 Operating time of three-phase fault (50Hz, SIR=1) ........................................... 3-27
Figure 3.7-6 Operating time of three-phase fault (60Hz, SIR=1) ........................................... 3-27
Figure 3.7-7 Operating time of single-phase fault (50Hz, SIR=30) ....................................... 3-28
Figure 3.7-8 Operating time of single-phase fault (60Hz, SIR=30) ....................................... 3-28
Figure 3.7-9 Operating time of two-phase fault (50Hz, SIR=30) ........................................... 3-29
Figure 3.7-10 Operating time of two-phase fault (60Hz, SIR=30) ......................................... 3-29
Figure 3.7-11 Operating time of three-phase fault (50Hz, SIR=30) ....................................... 3-30
Figure 3.7-12 Operating time of three-phase fault (60Hz, SIR=30) ....................................... 3-30
Figure 3.7-17 Phase-to-ground operation characteristic for forward fault ......................... 3-36
Figure 3.7-19 Phase-to-phase operation characteristic for forward fault ........................... 3-38
Figure 3.7-23 Shift impedance characteristic of zone 1 and zone 2 .................................... 3-42
Figure 3.7-25 Logic diagram of distance protection (Mho zone 1) ...................................... 3-44
Figure 3.7-26 Logic diagram of distance protection (Mho zone i) ....................................... 3-46
Figure 3.7-29 Logic diagram of enabling distance protection (Quad) ................................. 3-51
Figure 3.7-30 Logic diagram of distance protection (Quad zone 1) .................................... 3-51
Figure 3.7-31 Logic diagram of distance protection (Quad zone i) ..................................... 3-53
Figure 3.7-34 Logic diagram of pilot distance zone (Mho characteristic) ........................... 3-56
Figure 3.7-35 Logic diagram of pilot distance zone (Quad characteristic) ......................... 3-57
Figure 3.7-39 The variation rule of oscillation center voltage .............................................. 3-61
Figure 3.7-40 Vector diagram of the oscillation center voltage ........................................... 3-62
Figure 3.7-44 Logic diagram of enabling distance SOTF protection ................................... 3-73
Figure 3.7-47 Logic diagram of distance SOTF protection by manual closing signal ...... 3-76
Figure 3.7-48 Logic diagram of distance SOTF protection by 1-pole or 3-pole AR ........... 3-77
Figure 3.7-49 Logic diagram of distance SOTF protection by PD condition ...................... 3-77
Figure 3.8-1 Direct optical link up to 2km with 850nm .......................................................... 3-80
Figure 3.8-2 Direct optical link up to 40km with1310nm or 100km with 1550nm ............... 3-81
Figure 3.9-5 Logic diagram of pilot distance protection (PUTT) .......................................... 3-91
Figure 3.9-7 Logic diagram of pilot distance protection (POTT) .......................................... 3-92
Figure 3.9-10 Logic diagram of pilot distance protection (Blocking) .................................. 3-94
Figure 3.9-11 Logic diagram of pilot distance protection (Unblocking) .............................. 3-95
Figure 3.10-1 Enabling/disabling logic of pilot directional earth-fault protection ........... 3-102
Figure 3.13-1 Logic diagram of earth fault protection (stage 1) ......................................... 3-126
Figure 3.13-2 Logic diagram of earth fault protection (stage i) .......................................... 3-127
Figure 3.15-1 Logic diagram of overcurrent protection for VT circuit failure................... 3-139
Figure 3.16-1 Logic diagram of residual current SOTF protection .................................... 3-142
Figure 3.20-2 Logic diagram of stage i of thermal overload protection ............................ 3-170
Figure 3.26-1 Relationship between reference voltage and synchronism voltage .......... 3-186
Figure 3.26-4 Voltage connection for double busbars arrangement ................................. 3-189
Figure 3.26-5 Voltage selection for double busbars arrangement ..................................... 3-189
Figure 3.26-6 Voltage connection for one and a half breakers arrangement ................... 3-190
Figure 3.26-7 Voltage selection for one and a half breakers arrangement ....................... 3-191
Figure 3.26-8 Voltage selection for one and a half breakers arrangement ....................... 3-192
Figure 3.26-9 Reference voltage circuit failure supervision logic ..................................... 3-193
Figure 3.26-10 Synchronism voltage circuit failure supervision logic .............................. 3-193
Figure 3.32-7 Configuration page of control output 01 (default configration) ................. 3-237
Figure 3.32-8 Configuration page of control output 02 (default configration) ................. 3-238
List of Tables
Table 3.1-1 System parameters .................................................................................................. 3-1
Table 3.15-2 I/O signals of overcurrent protection for VT circuit failure ........................... 3-138
Table 3.15-3 Settings of overcurrent protection for VT circuit failure ............................... 3-139
Table 3.17-6 Inverse-time curve parameters of phase undervoltage protection .............. 3-152
Further to correct configuration of analog input channels, other protected system information, such
as the parameters of voltage transformer and current transformer are also required.
The device generally considers transmission line as its protected object, current flows from busbar
to line is considered as the forward direction.
3.1.3 Settings
Table 3.1-1 System parameters
When the device equips with line protection functions, line parameters of protected line are
required, especially for fault location, precise line parameters are the basic criterion for accurate
fault location.
3.2.3 Settings
Table 3.2-1 Line parameters
System frequency is an important parameter to characterize power system, and the measurement
and calculation of system frequency are the basis of many protection functions. The frequency
calculation module can accurately calculate the frequency of voltage component.
The device can be applied to the power system within frequency range of 40Hz~63Hz, the
reference frequency can be set as 50Hz or 60Hz via the system setting [Opt_SysFreq].
The device provide frequency track function, which can improve the accuracy of protection
algorithms and the performance of protection functions. For the power system using 50Hz or 60Hz
as reference frequency, the frequency track function can be disabled if the fluctuation of the
frequency range is not great. For the power system that the fluctuation of the frequency range is
great, the frequency track function can be enabled to improve protection performance.
It adopts the positive-sequence voltage which derived from protection used voltage as the
calculation reference, the positive-sequence voltage can be calculated as following:
When no VT is connected to the device, the frequency track function is disabled automatically, and
then the device calculates protection algorithm using the system reference frequency. When the
device detects a fault happening to the power system or the voltage is smaller than 0.15Un, the
frequency track function is disabled.
FreqCal
FreqTrack f
fn Alm_Freq
3.3.5 Logic
SIG U3P
Frequency
SIG fn f
calculation
SIG FreqTrack
The status of circuit breaker (CB) position is applied for protection and control functions in this
device, such as, SOTF protection, auto-reclose and VT circuit supervision, etc. The status of CB
position can be applied as input signals for other features configured by user.
The signal reflecting CB position is acquired via opto-coupler with settable delay pickup and
dropoff, and forms digital signal used by protection functions. CB position can reflect the status of
each phase by means of phase-segregated inputs.
In order to prevent that wrong status of CB position is input into the device via binary input,
appropriate monitor method is used to check the rationality of the binary input. When the binary
input of CB open position is detected, the status of CB position will be thought as incorrect and an
alarm [Alm_52b] will be issued if there is current detected in the line.
Together with the status of circuit breaker and the information of external circuit, this function can
be used to supervise control circuit of circuit breaker.
External manual closing binary input (ManCls) is only used for SOTF logic application, the control
of circuit breaker (CB) closing or opening should refer to section 3.29 (Control and Synchrocheck
for Manual Closing).
CB Position Supervision
CBx.52b_PhA CBx.Alm_52b
CBx.52b_PhB
CBx.52b_PhC
CBx.ManCls
CBx.Test
CB Position Supervision
CBx.52b CBx.Alm_52b
CBx.ManCls
CBx.Test
TCCS
CBx.52a CBx.TCCS.Alm
CBx.52b
CBx.TCCS.Input
CBx.ManCls
CBx.Test
TCCS will be disabled automatically when it is used for phase-segregated circuit breaker. x=1 or 2
NOTICE!
The signal [CBx.52a] only take effect in the tripping/closing circuit supervision and not
affect any protection function. Only if tripping/closing circuit supervision is configured,
this signal needs to be connected to the device.
3.4.5 Logic
BI [CBx.52b_PhA] >=1
&
&
BI [CBx.52b_PhB] >=1
& &
>=1
10s 10s CBx.Alm_52b
BI [CBx.52b_PhC] >=1 >=1
&
BI [CBx.52b]
&
SIG CBx.Ia>I_Line
& >=1
SIG CBx.Ib>I_Line
&
SIG CBx.Ic>I_Line
BI [CBx.52a] >=1
>=1
BI [CBx.52b] [CBx.TCCS.t_DPU] [CBx.TCCS.t_DDO] CBx.TCCS.Alm
BI [CBx.TCCS.Input]
BI [CB1.52b_PhA] >=1
&
52b_PhA
BI [CB1.52b_PhB] >=1
BI [CB1.52b_PhC]
>=1
BI [CB1.52b]
BI [CB1.Test]
&
52b_PhB
BI [CB2.52b_PhA] >=1
BI [CB2.52b_PhB] >=1
BI [CB2.52b_PhC]
&
>=1 52b_PhC
BI [CB2.52b]
BI [CB2.Test]
x=1 or 2
I_Line is threshold value used to determine whether line is on-load or no-load. Default value
0.06In.
If there is any single phase tripping or breaker status [52b_Phx]=1 (x can be A, B or C) and
corresponding phase current is smaller than 0.06IN, then single pole open state is confirmed by the
device.
If there is three pole tripping or breaker status of three phases are all open and three phase
currents are all smaller than 0.06IN, then three pole open state is confirmed by the device.
>=1
SET
SIG Trp A S Q & Pole A open
50ms 0ms
SIG FD.Pkp R CLR Q
SIG Ia<I_Line
>=1
SET
SIG Trp B S Q & Pole B open
50ms 0ms
R CLR Q
SIG Ib<I_Line
>=1
SET
SIG Trp C S Q & Pole C open
50ms 0ms
R CLR Q
SIG Ic<I_Line
Where:
TrpA, TrpB and TrpC are the tripping signals of the device.
3.4.6 Settings
Table 3.4-2 Internal settings of CB position supervision
picks up to provide positive supply to output relays. The output relays can only operate when both
the fault detector in fault detector DSP and a protection element operate simultaneously.
Otherwise, the output relays would not operate. An alarm message will be issued with blocking
outputs if a protection element operates while the fault detector does not operate.
Main part of FD is DPFC current detector element that detects the change of phase-to-phase
power frequency current, and residual current fault detector element that calculates the vector
sum of 3 phase currents as supplementary. They are continuously calculating the analog input
signals.
1. Fault detector based on DPFC current: DPFC current is greater than the setting value
2. Fault detector based on residual current: Residual current is greater than the setting value
4. Fault detector based on phase current: Phase current is greater than the setting value
5. Fault detector based on voltage: Phase voltage or phase-to-phase voltage is greater than the
setting value
6. Fault detector based on circuit breaker position: Circuit breaker position discrepancy
If any of the above conditions is complied, FD will operate to activate the output circuit providing
DC power supply to the output relays. The fault detector based on DPFC current and the fault
detector based on residual current are always enabled, and all protection functions are permitted
to operate when they operate.
DPFC phase-to-phase current is obtained by subtracting the phase-to-phase current from that of a
cycle before.
I(k-24) is the value of a sampling point before a cycle, 24 is the sampling points in one cycle.
200
100
-100
-200
0 20 40 60 80 100 120
Original Current
100
50
-50
-100
0 20 40 60 80 100 120
DPFC current
From above figures, it is concluded that DPFC can reflect the sudden change of current at the
initial stage of a fault and has a perfect performance of fault detection.
It is used to determine whether this pickup condition is met according to Equation 3.5-1.
For multi-phase short-circuit fault, DPFC phase-to-phase current has high sensitivity to ensure the
pickup of protection device. For usual single phase to earth fault, it also has sufficient sensitivity to
pick up except the earth fault with very large fault resistance. Under this condition, DPFC current is
relative small, however, residual current is also used to judge pickup condition.
This element adopts adaptive floating threshold varied with the change of load current
continuously. The change of load current is small and steadily under normal or power swing
condition, the adaptive floating threshold with the ΔI Set is higher than the change of current under
these conditions and hence maintains the element stability.
Where:
ΔIΦΦMAX: The maximum half-wave integration value of phase-to-phase current (ΦΦ=AB, BC, CA)
The coefficient, 1.25, is an empirical value which ensures the threshold always higher than the
unbalance output value of the system.
If operation condition is met, the fault detector based on DPFC current will operate to provide DC
power supply for output relays, the pickup signal will maintain 7s after the fault detector based on
DPFC current drops off.
The operation condition will be met when 3I0 is greater than the setting [FD.ROC.3I0_Set]. The
fault detector based on residual current is always in service.
Where:
3I0: residual current calculates from the vector sum of Ia, Ib and Ic
When the fault detector based on residual current operates and lasts for longer than 10 seconds,
an alarm [Alm_Pkp_I0] will be issued.
If operation condition is met, the fault detector based on residual current will operate to provide DC
power supply for output relay, and the pickup signal will maintain 7s after the fault detector based
on residual current drops off.
The operation condition will be met when negative-sequence current (I2) is greater than the
setting [FD.NOC.I2_Set]. It can be enabled or disabled by the logic setting [FD.NOC.En].
If operation condition is met, the fault detector based on negative-sequence current will operate to
provide DC power supply for output relay, and the pickup signal will maintain 7s after the fault
detector based on negative-sequence current drops off.
The fault detector based on phase current will operate to provide DC power supply for output relay
when phase overcurrent protection is enabled and meets the operation condition, and the pickup
signal will maintain 500ms after the fault detector based on phase current drops off.
This fault detector based on voltage includes the fault detectors of overvoltage protection,
undervoltage protection and frequency protection. The fault detector based on voltage will operate
to provide DC power supply for output relay when corresponding voltage element is enabled and
meets the operation condition, and the pickup signal will maintain 500ms after the fault detector
based on voltage drops off.
When pole discrepancy protection is enabled, i.e. the logic setting [62PD.En] is set as “1”, and if
three phases of circuit breaker are not in the same status, the fault detector based on circuit
breaker position will operate to provide DC power supply for output relays, and the pickup signal
will maintain 500ms after the the fault detector based on circuit breaker position drops off.
The fault detector based on thermal overload logic will operate to provide DC power supply for
output relay when tripping logic of thermal overload protection meets the operation condition, and
the pickup signal will maintain 500ms after the fault detector based on thermal overload logic
drops off.
The fault detector based on auxiliary element will operate to provide DC power supply for output
relay when auxiliary element is enabled and meets the operation condition, and the pickup signal
will maintain 500ms after the fault detector based on auxiliary element drops off.
Under the normal state, the protection device will perform the following tasks:
3. Hardware self-check
6. Channel supervision
Once the protection fault detector element in protection calculation DSP picks up, the protection
device will switch to fault calculation program, for example the calculation of distance protection,
and to determine logic. If the fault is within the protected zone, the protection device will send
tripping command.
Main program
Sampling program
No Yes
Pickup?
The protection FD pickup conditions are the same as the FD in fault detector DSP as shown below.
The operation criteria for the conditions are also the same as that in fault detector DSP. Please
refer to section 3.5.2 for details.
FD
FD.Pkp
FD.DPFC.Pkp
FD.ROC.Pkp
FD.NOC.Pkp
3.5.6 Logic
Calculate negative-
I2>[FD.NOC.I2_Set] &
sequence current: I2
FD.NOC.Pkp
EN FD.NOC.En
3.5.7 Settings
Table 3.5-2 Settings of fault detector
Auxiliary element (AuxE) is mainly used to program logics to meet users’ applications or further
improve operating reliability of protection elements. Reliability of protective elements (such as
distance element or current differential element) is assured, auxiliary element is usually not
required to configure. Auxiliary elements including current change auxiliary element (AuxE.OCD),
residual current auxiliary element (AuxE.ROC), phase current auxiliary element (AuxE.OC),
voltage change auxiliary element (AuxE.UVD), phase under voltage auxiliary element (AuxE.UVG),
phase-to-phase under voltage auxiliary element (AuxE.UVS) and residual voltage auxiliary
element (AuxE.ROV), and they can be enabled or disabled by corresponding logic setting or
binary inputs. Users can configure them according to applications via PCS-Explorer software.
It shares DPFC current element of DPFC fault detector. If DPFC fault detector operates
(FD.DPFC.Pkp=1) and current change auxiliary element is enabled, current change auxiliary
element operates.
There are 3 stages for residual current auxiliary element (AuxE.ROC1, AuxE.ROC2 and
AuxE.ROC3). Each residual current auxiliary element will operate instantly if calculated residual
current amplitude is larger than corresponding current setting
AuxE.ROC1: 3I0>[AuxE.ROC1.3I0_Set]
AuxE.ROC2: 3I0>[AuxE.ROC2.3I0_Set]
AuxE.ROC3: 3I0>[AuxE.ROC3.3I0_Set]
Where:
There are 3 stages for phase current auxiliary element (AuxE.OC1, AuxE.OC2 and AuxE.OC3).
Each phase current auxiliary element will operate instantly if phase current amplitude is larger than
AuxE.OC1: IΦMAX>[AuxE.OC1.I_Set]
AuxE.OC2: IΦMAX>[AuxE.OC2.I_Set]
AuxE.OC3: IΦMAX>[AuxE.OC3.I_Set]
Where:
Δ UΦMAX>[AuxE.UVD.U_Set]
Where:
AuxE.UVG will operate instantly if any phase-to-ground voltage is lower than corresponding
voltage setting.
UΦMIN<[AuxE.UVG.U_Set]
Where:
AuxE.UVS will operate instantly if any phase-to-phase voltage is lower than corresponding voltage
setting.
UΦΦMIN<[AuxE.UVS.U_Set]
Where:
AuxE.ROV will operate instantly if calculated residual voltage is larger than corresponding voltage
setting.
3U0>[AuxE.ROV.3U0_Set]
Where:
AuxE
AuxE.OCD.En AuxE.St
AuxE.OCD.Blk AuxE.OCD.St_DDO
AuxE.ROCi.En AuxE.OCD.On
AuxE.ROCi.Blk AuxE.ROCi.St
AuxE.OCi.En AuxE.ROCi.On
AuxE.OCi.Blk AuxE.OCi.St
AuxE.UVD.En AuxE.OCi.StA
AuxE.UVD.Blk AuxE.OCi.StB
AuxE.UVG.En AuxE.OCi.StC
AuxE.UVG.Blk AuxE.OCi.On
AuxE.UVS.En AuxE.UVD.St
AuxE.UVS.Blk AuxE.UVD.St_DDO
AuxE.ROV.En AuxE.UVD.On
AuxE.ROV.Blk AuxE.UVG.St
AuxE.UVG.StA
AuxE.UVG.StB
AuxE.UVG.StC
AuxE.UVG.On
AuxE.UVS.St
AuxE.UVS.StAB
AuxE.UVS.StBC
AuxE.UVS.StCA
AuxE.UVS.On
AuxE.ROV.St
AuxE.ROV.On
3.6.5 Logic
SET 3I0>[AuxE.ROCi.3I0_Set]
SIG AuxE.ROCi.En
&
& AuxE.ROCi.St
SIG AuxE.ROCi.Blk
AuxE.ROCi.On
EN AuxE.ROCi.En
EN AuxE.ROV.En
SIG AuxE.OCi.En
&
SIG AuxE.OCi.Blk AuxE.OCi.On
EN AuxE.OCi.En
SET Ia>[AuxE.OCi.I_Set]
&
>=1 AuxE.OCi.St
SET Ib>[AuxE.OCi.I_Set]
SET Ic>[AuxE.OCi.I_Set]
SIG AuxE.UVG.En
&
SIG AuxE.UVG.Blk AuxE.UVG.On
EN AuxE.UVG.En
SET UA<[AuxE.UVG.U_Set]
&
>=1 AuxE.UVG.St
SET UB<[AuxE.UVG.U_Set]
SET UC<[AuxE.UVG.U_Set]
SIG AuxE.UVS.En
&
SIG AuxE.UVS.Blk AuxE.UVS.On
EN AuxE.UVS.En
SET UA<[AuxE.UVS.U_Set]
&
>=1 AuxE.UVS.St
SET UB<[AuxE.UVS.U_Set]
SET UC<[AuxE.UVS.U_Set]
SET Δ Ua>[AuxE.UVD.U_Set]
>=1
SET Δ Ub>[AuxE.UVD.U_Set] &
AuxE.UVD.St
SET Δ Uc>[AuxE.UVD.U_Set]
0s [AuxE.UVD.t_DDO] AuxE.UVD.St_DDO
SIG AuxE.UVD.En
&
SIG AuxE.UVD.Blk AuxE.UVD.On
EN AuxE.UVD.En
SIG AuxE.OCD.En
&
SIG AuxE.OCD.Blk AuxE.OCD.On
EN AuxE.OCD.En &
0s [AuxE.OCD.t_DDO] AuxE.OCD.St_DDO
SIG FD.DPFC.Pkp
SIG AuxE.OCD.St_DDO
SIG AuxE.ROC1.St
>=1
SIG AuxE.ROC2.St >=1 >=1
AuxE.St
SIG AuxE.ROC3.St
SIG AuxE.OC1.St
>=1
SIG AuxE.OC2.St
SIG AuxE.OC3.St
SIG AuxE.ROV.St
Where:
i=1, 2, 3
3.6.6 Settings
Table 3.6-2 Settings of auxiliary element
When a fault happens on a power system, distance protection will trip circuit breaker to isolate the
fault from power system with its specific time delay if the fault is within the protected zone of
distance protection.
The device provide various distance elements, including 1 DPFC distance zone with fixed forward
direction, 1 forward zones, 4 settable forward or reverse zone, and 1 forward zone and 1 reverse
zone dedicated for pilot distance protection. For each independent distance element zone, full
It is independent fast protection providing extremely fast speed to clear close up fault
especially on long line and thus improves system stability.
The pilot zone is for PUTT, POTT and blocking scheme. The forward direction element is for
sending signal for POTT and tripping upon receiving permissive signal for both PUTT and
POTT scheme. The forward direction element for blocking scheme is used to stop sending
blocking signal. The reverse direction element is only for POTT scheme with weak infeed
condition.
7. Load encroachment
It is used to prevent all distance elements from undesired trip due to load encroachment
under heavy load condition especially for long lines.
For power swing with external fault, distance protection is always blocked, but for power
swing with internal fault, PSBR will operate to release the blocking for distance protection.
For manual closing or automatic closing on to a fault, zone 2, 3 or 4 of distance protection will
accelerate to trip.
When VT circuit fails, VT circuit supervision logic will output a blocking signal to block all distance
protection except DPFC distance protection. The operating threshold will be increased to 1.5U N to
enhance stability.
Distance protection can select line VT or bus VT for protection algorithm by a setting
[VTS.En_LineVT]. When no VT is provided, logic setting [VTS.En_Out_VT] should be set as “1”,
all distance protection will be blocked automatically. The choice of impedance reach is as follow.
(only for reference)
The zone 1 impedance reach setting should be set to cover as much the protected line as possible
but not to respond faults beyond the protected line. The accuracy of the relay distance elements is
±2.5% in general applications, however, the error could be much larger due to errors of current
transformer, voltage transformer and inaccuracies of line parameter from which the relay settings
are calculated. It is recommended the zone 1 reach is set to 80%~85% of the protected line in
consideration the aforesaid errors and safety margin to prevent instantaneously tripping for faults
on adjacent lines. The remaining 20% of the protected line relies on the zone 2 distance elements.
With the pilot scheme distance protection, fast fault clearance could also be achieved for end zone
faults at both ends of the protected line.
The general rule for zone 2 impedance reach setting is set to cover the protected line plus 20% of
the adjacent line. However, the coverage of adjacent line should be extended in the presence of
additional infeed at the remote end of the protected line to ensure 20% coverage of adjacent line.
This assures the fast operation of zone 2 distance element for faults at the remote end of the
protected line since the fault is well within zone 2 reach. This is important for pilot protection as the
impedance reach of pilot zone is the same as that of zone 2 distance element. In a parallel line
situation, a fault cleared sequentially on a line may cause current reversal in the healthy line. If the
pilot zone settings are set to cover 50% of adjacent line and the POTT or Blocking scheme is used,
the current reversal in the healthy line could cause relay mal-operation. Therefore, current reversal
logic is required and explained in section 3.9.2.6.
For different system impedance ratio (SIR), the operating time of distance protection for different
fault location are shown as the following figures.
35
30
25
Operating Time (ms)
20
15
10
0
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
30
25
Operating Time (ms)
20
15
10
0
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
35
30
25
Operating Time (ms)
20
15
10
0
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
30
25
Operating Time (ms)
20
15
10
0
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
35
30
25
Operating Time (ms)
20
15
10
0
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
30
25
Operating Time (ms)
20
15
10
0
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
33
32.5
32
Operating Time (ms)
31.5
31
30.5
30
29.5
29
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
27.5
27
Operating Time (ms)
26.5
26
25.5
25
24.5
24
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
45
40
35
30
Operating Time (ms)
25
20
15
10
5
0
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
35
30
Operating Time (ms)
25
20
15
10
0
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
33
32
31
Operating Time (ms)
30
29
28
27
0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
27.5
27
26.5
Operating Time (ms)
26
25.5
25
24.5
24
23.5
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
As an independent fast protection, DPFC distance protection is mainly used to clear close up fault
of long line quickly, its protected range can set as 80%~85% of the whole line.
Since DPFC distance protection only reflects fault component and is not influenced by current
change due to load variation and power swing, power swing blocking (PSB) is this not required.
Moreover, there is no transient overreaching due to infeed current from the remote power supply
because it is not influenced by load current.
DPFC distance protection may not overreach, and its protected zone will be inverse-proportion
reduced with system impedance behind it, i.e. the protected zone will be less than setting if the
system impedance is greater. The protected zone will be close to setting value if the system
impedance is smaller. Therefore, DPFC distance protection is usually used for long transmission
line with large power source and it is recommended to disable DPFC distance protection for short
line or the line with weak power source.
ZZD
M F N
Z
EM EN
∆I
ZS ZK
jX
Zzd
Zk
Φ
R
Zs+Zk
-Zs
Where:
Figure 3.7-13 shows the operation characteristic of DPFC distance protection on R-X plane when
a fault occurs in forward direction, which is the circle with the –Zs as the center and the│Zs+Zzd│ as
the radius. When measured impedance Z k is in the circle, DPFC distance protection will operate.
DPFC distance protection has a larger capability of enduring fault resistance than distance
protection using positive-sequence as polarized voltage.
ZZD
F M N
Z
EM EN
∆I
ZK
Z′S
jX
Z's
Zzd
Φ R
-Zk
Figure 3.7-14 shows the operation characteristic of the DPFC distance element on R-X plane
when a fault occurs in reverse direction, which is the circle with the Z′S as the center and
the│Z′S-Zzd│as the radius. The region of operation is in the quadrant 1 but the measured
impedance -Zk is always in the quadrant 3, the DPFC distance protection will not operate.
The DPFC distance protection can be enabled or disabled by logic setting and binary input.
21D
21D.En 21D.Op
21D.Blk 21D.On
3.7.3.4 Logic
EN [21D.En]
&
SIG 21D.En 21D.On
SIG 21D.Blk
&
SIG FD.Pkp
EN [VTS.En_Out_VT]
SET [21D.Z_Set]<0.05Ω/In
SIG UPP<0.85Unn
NOTICE!
Pole open signal blocks DPFC distance element of corresponding phase-to-earth and
phase-to-phase DPFC distance protection, and healthy phases (operation phases) are
not affected. For example, if phase A open is confirmed, DPFC distance element of
phase A, phase AB and phase AC are blocked.
3.7.3.5 Settings
When distance protection is used to protect long, heavily loaded lines, the risk of encroachment of
the load impedance into the tripping characteristic of the distance protection may exist. A load
trapezoid characteristic for all zones is used to exclude the risk of unwanted fault detection by the
distance protection during heavy load flow.
As shown below, if the measured impedance into the load area, distance elements need to be
blocked.
jX
φLoad φLoad
RLoad RLoad
Two settings are equipped to exclude the encroachment of the load impedance:
LoadEnch
LoadEnch.En LoadEnch.St
LoadEnch.Blk LoadEnch.On
3.7.4.4 Settings
ZZD
M F N
Z IN
EM EN
I
ZS ZK
jX
ZZD
ZK
Φ
R
-2ZS/3
Where:
ZS: total impedance between local system and protective device location
For zone 1, 2:
Operation voltage:
Polarized voltage:
In short line, phase shift θ1 could be applied to the polarized voltage to improve the performance
against high resistance fault. The device provides an angle-shift setting, [21Mi.ZG.phi_Shift], to set
value of θ1 among 0°, 15°and 30°. Their impedance shift characteristics towards quadrant 1 are
respectively shown as the impedance circle A, B and C in Figure 3.7-23. (i=1, 2)
For zone 3, 4, 5:
Operation voltage:
Polarized voltage:
UPΦ uses phase positive-sequence voltage as polarized voltage. For earth fault, positive-sequence
voltage is mainly formed from healthy phases, basically retaining the phase of the
positive-sequence voltage before fault.
The operation characteristic is shown in Figure 3.7-17. Operation characteristic of ZK on R-X plane
is a circle with line connecting ends of ZZD and -2ZS/3 as the diameter. The origin is enclosed in the
circle.
The sensitivity of phase-to-ground distance element with Mho characteristic may be not enough
during ground fault with extreme high resistance. So additional quadrilateral characteristic for
phase-to-ground distance element is adopted in the equipment to compensate the sensitivity of
Mho characteristic. The logic relationship between quadrilateral distance element and Mho
distance element is OR. It means that any ground fault in one of the two operation zones will be
cleared. The quadrilateral phase-to-ground distance element can significantly improve the
sensitivity to clear ground fault with extreme high resistance. The three zones of quadrilateral
characteristic can be enabled or disabled by the logic setting [21Mi.ZGQ.En]. (i=1, 2, 3, 4, 5)
jX
[21Mi.ZG.Z_Set]
12°
Φ Φ
R
12°
[21Mi.ZGQ.R_Set]
Where:
i=1, 2, 3, 4, 5
jX
ZZD
ZK
Φ
R
-ZS/2
For zone 1, 2:
Operation voltage:
Polarized voltage:
Phase shift θ2 could be applied to polarized voltage of zones 1 and 2 just like θ1 in
phase-to-ground distance element. It is also used for improving performance against high
resistance fault in short line. The device provides an angle-shift setting, [21Mi.ZP.phi_Shift], to set
value of θ2 among 0°, 15°and 30°. Their impedance shift characteristics towards quadrant 1 are
respectively shown as the impedance circle A, B and C in Figure 3.7-23. (i=1, 2)
For zone 3, 4, 5:
Operation voltage:
Polarized voltage:
Figure 3.7-20 shows operation characteristic of measured impedance -ZK on R-X plane when an
asymmetric reverse fault occurs. This characteristic is a circle with line connecting ends of Z ZD and
Z'S as the diameter. It will operate only when -ZK is in the circle. Therefore, directionality of the
distanced protection is achieved.
ZZD
F M N
Z
EM EN
IΦ
ZK
Z′S
jX
Z'S
ZZD
Φ
R
-ZK
Z'S: total impedance between remote system and protective device location
jX
ZZD
ZK
Φ
R
Phase-to-phase distance protection is also used for three-phase short-circuit fault. The operation
characteristic is shown in Figure 3.7-21. Operation characteristic of ZK on R-X plane is a circle with
setting impedance ZZD as the diameter.
jX
ZZD
ZK
Φ
R
Circle C
-ZS Circle B
Circle A
Where:
ZS: total impedance between local system and protective device location
As shown in Figure 3.7-22, the characteristic of the distance protection for a three-phase fault on a
system is an impedance circle cross the origin, and there is a voltage dead zone around the origin.
In order to eliminate the dead zone of the distance protection for a close up three-phase fault
memorized positive-sequence voltage is adopted as polarized voltage when the
positive-sequence voltage drops down to 15%Un or below.
The transient (during process of memory) operation characteristic is shown as the impedance
circle A in the above figure. The circle takes Z ZD and -ZZS as diameter and thus the origin is within
the impedance circle. When three-phase fault happens in reverse direction, its transient
characteristic is shown in Figure 3.7-20, i.e. the distance protection has a clearly defined
directionality and no dead zone during the process of memory.
For phase-to-phase distance protection, if distance protection operates with memorized polarizing
voltage, this means a close up forward fault. When the memory fades out, the operation
characteristic will be reverse offset a little to enclose the origin as impedance circle B shown in
Figure 3.7-22 to ensure keeping operating of distance protection until the fault being cleared. If
distance protection does not operate with memorized polarizing voltage, it will be a close up
reverse fault. When the memory fades out, the operation characteristic will be forward offset not to
enclose the origin as impedance circle C shown in Figure 3.7-22, and the distance protection will
not mal-operate even if voltage is zero.
The distance protection with such design thoroughly eliminates the dead zone when three-phase
close up fault occurs. It also has favorable directivity and will not operate for a reverse three-phase
fault at busbar.
When receiving manual closing signal or 3-pole reclosing signal, the operation characteristic of
phase to phase distance protection will always shift in reverse direction. It is ensured to enclose
the origin of impedance and without dead zone for three-phase fault, i.e. the reverse shift
impedance circle B shown in Figure 3.7-22.
jX
B: 15° C: 30°
ZZD
A: 0°
D
-ZS
The impedance characteristic of phase-to-ground distance protection is the circle with line
connecting ends of ZZD and -2ZS/3 as the diameter and that of phase-to-phase distance is the
circle with line connecting ends of ZZD and -ZS/2 as the diameter.
In order to prevent the transient overreach caused by the infeed power supply from the remote
end, the zero-sequence reactance line D is added. These measures have enhanced the capacity
against fault resistance when using distance protection in short lines.
21M
21.En 21Mi.On
21.Blk 21Mi.Op
21Mi.ZG.En
21Mi.ZP.En
21Mi.ZG.Blk
21Mi.ZP.Blk
21Mi.En_ShortDly
21Mi.Blk_ShortDly
21M1.En_Instant
3.7.5.4 Logic
SIG 21.Enable
&
EN [21M1.ZG.En]
& 21M1.ZG.Enable
&
SIG 21M1.ZG.En
SIG 21M1.ZP.Blk
&
SIG VTS.Alm >=1 21M1.ZP.Enable
EN [VTS.En_Out_VT]
SIG 21M1.Rls_PSBR
SET 3I0>[FD.ROC.3I0_Set]
>=1
SIG Flag.21M1.ZP & 21M1.Flg_PSBR
SIG 21M1.En_Instant
Where:
21M1.Rls_PSBR: is the signal of power swing blocking releasing signal, please refer to Figure
3.7-43.
LoadEnch.St (PG) means that load trapezoid characteristic for distance element is enabled and
measured phase-to-ground impedance into the load area.
LoadEnch.St (PP) means that load trapezoid characteristic for distance element is enabled and
measured phase-to-phase impedance into the load area.
SIG 21.Enable
&
EN [21Mi.ZG.En]
& 21Mi.ZG.Enable
&
SIG 21Mi.ZG.En
SIG 21Mi.ZP.Blk
&
SIG VTS.Alm >=1 21Mi.ZP.Enable
EN [VTS.En_Out_VT]
SIG 21Mi.Blk_ShortDly
&
EN [21Mi.En_ShortDly] 21Mi.Enable_ShortDly
SIG 21Mi.On
SET 3I0>[FD.ROC.3I0_Set]
Where:
i=2, 3, 4, 5
21Mi.Rls_PSBR: is the signal of power swing blocking releasing signal, please refer to Figure
3.7-43.
3.7.5.5 Settings
Features available with quadrilateral distance protection include 1 forward zone (zone 1)
phase-to-ground or phase-to-phase distance elements and 4 settable forward or reverse zones
(zone 2~5) phase-to-ground or phase-to-phase distance element. Each zone can respectively
enable or disable power swing blocking releasing. Quadrilateral distance protection will be
disabled when VT circuit fails.
jX
A ZZD
θ
B
α φ
φ
β R
O RZD
C
Where:
α: the angle of directional line in the second quadrant, set by the setting [21Q.Ang_Alpha]
Zone 2, 3, 4, 5 can be set as reverse direction by the setting [21-i.DirMode] (i=2, 3, 4, 5). When a
fault occurs on the busbar at the back, reverse distance element is provided to clear it with definite
time delay and is used as backup protection for reverse busbar fault.
jX
C
RZD β O
R
φ φ
α
B
θ
ZZD A
Where:
For quadrilateral distance protection, the reactance line should consider downward offset angle θ
as shown in Figure 3.7-27 and Figure 3.7-28. According to system status, the downward offset
angle can be independently set for phase-to-ground distance element and phase-to-phase
distance element. The downward offset angle of all zones can be settable by the corresponding
settings [21Qi.ZG.RCA] and [21Qi.ZP.RCA]. (i=1, 2, 3, 4, 5). Phase-to-ground distance protection
is controlled by the fault detector based on residual current.
21Q
21.En 21Qi.On
21.Blk 21Qi.Op
21Qi.ZG.En
21Qi.ZP.En
21Qi.ZG.Blk
21Qi.ZP.Blk
21Qi.En_ShortDly
21Qi.Blk_ShortDly
21Q1.En_Instant
3.7.6.4 Logic
SIG 21.Enable
&
EN [21Q1.ZG.En]
& 21Q1.ZG.Enable
&
SIG 21Q1.ZG.En
SIG 21Q1.ZP.Blk
&
SIG VTS.Alm >=1 21Q1.ZP.Enable
EN [VTS.En_Out_VT]
SIG 21Q1.ZP.Enable
&
SIG LoadEnch.St (PP) & &
[21Q1.ZP.t_Op] 0 >=1
SIG Flag.21Q1.ZP 21Q1.ZP.Op
&
SIG 21Q1.En_Instant
Where:
21Q1. Rls_PSBR: is the signal of power swing blocking releasing signal, please refer to Figure
3.7-43.
LoadEnch.St (PG) means that load trapezoid characteristic for distance element is enabled and
measured phase-to-ground impedance into the load area.
LoadEnch.St (PP) means that load trapezoid characteristic for distance element is enabled and
measured phase-to-phase impedance into the load area.
SIG 21.Enable
&
EN [21Qi.ZG.En]
& 21Qi.ZG.Enable
&
SIG 21Qi.ZG.En
SIG 21Qi.ZP.Blk
&
SIG VTS.Alm >=1 21Qi.ZP.Enable
EN [VTS.En_Out_VT]
SIG 21Qi.Blk_ShortDly
&
EN [21Qi.En_ShortDly] 21Qi.Enable_ShortDly
SIG 21Qi.On
SIG 21Qi.Enable_ShortDly
SIG Flag.21Qi.ZG
>=1
SIG 21Qi.Rls_PSBR 21Qi.Flg_PSBR
Where:
i=2, 3, 4, 5
21Qi.Z.Rls_PSBR: is the signal of power swing blocking releasing signal, please refer to Figure
3.7-43.
3.7.6.5 Settings
An independent pilot zone distance protection is used for PUTT and POTT scheme. There is also
a reverse pilot distance element available as an option for application of POTT on weak power
source system.
Pilot.Z_Set_B Pilot.Z_Rev_B
M N
EM A B C D
Pilot.Z_Rev_A Pilot.Z_Set_A
The operation characteristic of pilot zone is same as that of zone 2, including mho and
quadrilateral characteristic.
When an internal fault occurs, distance protection at weak source end may not operate due to
small fault current. Thus, a reverse distance element is provided to coordinate with the
independent pilot distance protection to implement weak infeed logic, ensure pilot distance
protection can operate to send signal or trip in the weak end. The operation characteristic is shown
in Figure 3.7-33. The reverse weak infeed distance element is forward offset with 1/4 of the
Operation characteristics of pilot reverse weak infeed element distance are shown as below.
jX
jX
B
β 21Q.Pilot.Z_Rev/4
21M.Pilot.Z_Rev/4
21Q.Pilot.R_Rev
Φ
o R
α
R φ φ
C
θ
21M.Pilot.Z_Rev 21Q.Pilot.Z_Rev
A
Where:
3.7.7.2 Logic
SIG 21.Enable
&
&
SIG 21M.Pilot.Rls_PSBR ZPilotP
SIG 21.Enable
&
&
SIG 21Q.Pilot.Rls_PSBR ZPilotP
Where:
LoadEnch.St (PG) means that load trapezoid characteristic for distance element is enabled and
measured phase-to-ground impedance into the load area.
LoadEnch.St (PP) means that load trapezoid characteristic for distance element is enabled and
measured phase-to-phase impedance into the load area.
3.7.7.3 Settings
When the disturbance happens to the power system because of some reason (such as short
circuit, fault clear, power supply injecting or separating, etc.), the phase angle difference of the
electric potential between the synchronous generators of parallel operation will change with time,
and the voltage of each node and the current of each circuit in the system also change with time,
this phenomenon is called oscillation. The oscillation that can keep system stably and
synchronously operate is called synchronous oscillation, and that leads to lose synchronization
and that the system can't normally operate is called asynchronous oscillation.
For the power grid of loss synchronous, the voltage of each node in the tie line that synchronous or
asynchronous oscillation happens to will oscillate periodically, and where the voltage oscillation is
the most violent in each tie line is the center of synchronous or asynchronous oscillation. In
general, the voltage oscillation is more violent more close to the oscillation center. Out-of-step
center is the point where the lowest voltage appears in the tie line of asynchronous oscillation in
the process of out-of-step oscillation, i.e., the oscillation center of the tie line of asynchronous
oscillation. The phase angle of bus voltage difference on either side of out-of-step center will
change within 0°~180°~360° periodically. Considering the selectivity, the separation should be
performed within 2~3 out-of-step period or the corresponding time delay after the system is out of
step, otherwise the out-of-step oscillation among multiple generators may is developed, further
expanding the accident, so as to cause system separation even collapse accident. So when the
out-of-step operation time or oscillation times is greater than specified value, out-of-step protection
should operate to separate.
In the event that the interconnected system is out-of-step, the system can be reduced as a
dual-machine system as shown in Figure 3.7-36.
EM U EN
I
ZLine
1. The potential of the two machines are E M and EN respectively, and their amplitude are both
equal to E1.
Taking EN as reference vector, whose initial phase angle is 0° and angle velocity is ω. At the side
M, the initial phase angle of equivalent potential E M is α (i.e., during normal operation condition,
the system′s power angle δ is α), whose increment of the angle velocity is Δω relative to side N, so
EN E1 cos( t )
EM E1 cos(( ) t )
t
The equivalent system vector diagram of Figure 3.7-36 is illustrated in Figure 3.7-37.
EM U U cos EN
U SCV
E1 E1
2
Where:
U SCV U cos E1 cos( )
2
In the case that the system is in synchronous condition, Δω=0, the voltage of oscillation center
maintains be unchanged, that is:
U SCV cos( )
2
d (U SCV ) E d ( )
1 sin( )
dt 2 2 dt
The above equation describe the relationship between the voltage change rate of oscillation
d ( )
center and system slip frequency , which indicates the voltage varation of oscillation center
dt
is independent of system impedance.
When the power angle is 180°, the voltage varation of oscillation center is maximum, and when the
power angle is 0°, the voltage varation of oscillation center is minimum.
In the case that the system is in out-of-step condition, the voltage of oscillation center varies
periodically with the oscillation cycle as 180°, that is:
If the value of Δω is larger than 0, namely accelerating out-of-step condition, the variation trend of
δ is 0°-360°(0°)-360°, the variation curve of oscillation center voltage is shown in Figure 3.7-38
(a)
If the value of Δω is less than 0, namely decelerating out-of-step condition, the variation trend of δ
is 360°-0°(360°)-0°, the variation curve of oscillation center voltage is shown in Figure 3.7-38
(b)
U U
1 1
t t
0 0
-1 -1
(a) (b)
According to the above analysis, it can be shown that there is certain functional relation between
the oscillation center voltage and power angle δ, thus the oscillation center voltage (Ucosφ) can
be used to reflect the variation of power angle. Power angle varies continuously as an
electrical quantity. As a result, the oscillation center voltage varies continuously during
out-of-step oscillation, crossing the zero point. However, sudden variation or discontinuous
change is a distinguished feature of oscillation center voltage during fault occurrence or
clearance. During synchronous oscillation, the oscillation center voltage also varies
continuously but it does not cross the zero point. Therefore, the oscillation center voltage can
be used to discriminate among out-of-step oscillation, short-circuit fault and synchronous
oscillation.
The variation range of oscillation center voltage (Ucosφ) can be divided into seven zones on the
variation plane, as shown in Figure 3.7-39.
From the above analysis, the variation rules of oscillation center voltage (Ucosφ) during
out-of-step oscillation are as follows:
U U
1 1
0 0
1 1
2 2
3 3
t t
0 4 0 4
5 5
6 6
-1
0 0
-1
If the oscillation center voltage varies as the above mentioned rules, the relay consider it as
out-of-step condition and issues tripping command after the time delay (i.e., the setting
[78.N_Limit]), performing separation.
The above analysis is based on the assumption that system impedance angle is 90°, while in
practical system it is not, thus angle compensation is required. As shown in Figure 3.7-40, setting
the system impedance angle φ L in the device, the angle compensation is made to the oscillation
center voltage,
U SCV U cos( 90 L )
I'
EM U EN
U cos
2
In order to locate the distance between the oscillation center and where the device is equipped,
setting impedance measurement element is used to confirm the operation range of separation
device, the operation characteristic of zone relay based on impedance discrimination is shown
in Figure 3.7-41.
EM EN
ZM Z L ine ZN
I
U
Z Re v Relay Z Fwd
jX ZN
Z Fwd
R
Z Re v δ
O
ZM
Where:
The measured impedance is the impedance of phase-BC, zone relay meet the operation criterion
when the measured impedance is within the range of operation characteristic. Out-of-step
protection will operate when both zone relay and out-of-step relay operate.
In order to prevent out-of-step protection from being initiated under normal conditions, the device
calculates in real-time the voltage vector of two points (ZFwd and ZRev) based on measured voltage
and current, so as to calculate the phase angle between two voltage (δ), which participates in logic
discrimination of out-of-step protection.
78
78.En 78.On
78.Blk 78.St
78.Clr_Counter 78.St_Zone
78.Op
3.7.8.5 Logic
SIG 78.Blk
&
SIG VTS.Alm t1 t2 78.St
SIG Ia>0.12In
&
SIG Ib>0.12In &
SIG Ic>0.12In
&
SIG |δ|>[78.phi_Start]
SIG
&
8>dδ/dt>0.2
Counter>[78.N_Limit] >=1
SIG Ucosφ from + to -
SIG 78.Clr_Counter
&
Counter>[78.N_Limit]
SIG Ucosφ - to +
&
EN [78.En_Trp] 78.Op
SIG
&
78.St_Zone
SIG 78.St
Where:
U1 is positive-sequence voltage.
t1 is the pickup time delay of discriminating oscillation, internal fixed value is 40ms
In order to prevent out-of-step protection from maloperation under normal conditions or faulty
conditions, the system will be think as oscillation only the following conditions are all met.
4. The power angle (δ) is greater than the minimum start angle ([78.Phi_Start]).
3.7.8.6 Settings
When power swing occurs on the power system, the impedance measured by the distance
measuring element may vary from the load impedance area into the operating zone of the
distance element. The distance measuring element may operate due to the power swing occurs in
many points of interconnected power systems. To keep the stability of whole power system,
tripping due to operation of the distance measuring element during a power swing is generally not
allowed. Our distance protection adopts power swing blocking releasing to avoid maloperation
resulting from power swing. In another word, distance protection is blocked all along under the
normal condition and power swing when the respective logic settings are enabled. Only when fault
(internal fault or power swing with internal fault) is detected, power swing blocking for distance
protection is released by PSBR element.
Power swing blocking for distance element will be released if any of the following PSBR elements
operates. Each distance zone elements has respective setting for selection this function.
If any of the following condition is matched, FD PSBR will operate for 160ms.
Positive sequence current is lower than the setting [21.I_PSBR] before general fault detector
element operates.
As shown in figure below, assuming that normal load impedance locates at position 1 and the
impedance locates at position 2 when positive-sequence current is lower than the setting
[21.I_PSBR], it means FD operates between point 1 and point 2 if operation condition for FD
PSBR mentioned above is fulfilled (point 3 as an example), and then FD PSBR will operate for
160ms.
[21.I_PSBR]
FD
Normal load
impedance
Point 1
Point 2
Point 3
I0+I2>m×I1
The “m”, an empirical value, is internal fixed coefficient which can ensure UF PSBR operation
during power swing with internal unsymmetrical fault, while no operation during power swing or
power swing with external fault.
In case of power swing or both power swing and external fault, asymmetric fault discriminating
element will not operate and distance protection will be blocked:
In case of power swing but no fault, I0 and I2 are near zero, but I1 is very large. Asymmetric fault
discriminating element will not operate.
In case of both power swing and external fault, if center of power swing is in scope of protection,
both phase-to-phase and grounding impedance relays may operate. At this time, selection of
value of m is used to ensure no operation of asymmetric fault discriminating element, blocking of
distance protection, and no incorrect operation without selectivity. If power swing center is not on
this line, distance protection will not operate incorrectly without selectivity due to power swing.
In case of internal asymmetric fault, asymmetric fault discriminating element operates and
distance protection will be release to clear internal fault:
In case of both power swing and internal fault, if at the instant of short circuit, system electric
potential angle is not laid out, asymmetric fault discriminating element will operate at once. If at the
instant of short circuit, system electric potential angle is laid out, asymmetric fault discriminating
element will operate when system angle gradually decreases, or local side tripping may be
activated after immediate operation of opposite side asymmetric fault discriminating element and
releasing of distance protection tripping. In case of normal internal asymmetric phase-to-phase or
grounding fault in the system, relatively large zero-sequence or negative-sequence component will
exist. At this time, the above equation is true and distance protection will be released.
If a three-phase fault occurs and FD PSBR is invalid (160ms after FD operates), neither FD PSBR
nor UF PSBR will be able to release the distance protection. Thus, SF PSBR is provided for this
case specially. This detection is based on measuring the voltage at power swing center, during
power swing, U1cosΦ will constantly change periodically.
UOS=U1×COSΦ
Where:
As shown in the figure below, assume system connection impedance angle of 90°, current vector
will be perpendicular to the line connecting E M and EN, and have the same phase as power swing
center voltage. During normal operation of system or power swing, U1cosΦ just reflects
positive-sequence voltage of power swing center. In case of 3-phase short circuit, U1cosΦ is
voltage drop on arc resistor, transition resistance is arc resistance, and voltage drop on arc resistor
is less than 5%UN. In actual system, line impedance angle is not 90°. Through compensation of
angle Φ, power swing center voltage can be measured accurately. After compensation, power
swing center voltage is U1cos(Φ+90o-ΦL), where ΦL is line impedance angle.
I
EM U EN
UOS
During power swing, power swing center voltage U 1cosΦ has the following characteristics: When
electric potential phase angle difference between power supplies at two sides is 180o, U1cosΦ=0
and change rate dU1cosΦ/dt is the maximum. When this phase angle difference is near 0 o, power
swing center voltage change rate dU 1cosΦ/dt is the minimum. During short circuit, U 1cosΦ
remains unchanged and dU1cosΦ/dt=0. However, in early stage of short circuit when normal state
enters short circuit state, dU1cosΦ/dt is very large. Therefore, use of dU 1cosΦ/dt solely to
differentiate power swing and short circuit is not complete.
For these reasons, the method to release distance protection on condition that power swing center
voltage U1cosΦ is less than a setting and after a short delay can be used as symmetric fault
discriminating element. This element can accurately differentiate power swing and 3-phase short
circuit fault, and constitute a complete power swing blocking scheme with other elements. The
element to open distance protection if U 1cosΦ is less than a certain setting and after a delay is
easy to realize and has short delay, and can trip fault more quickly and accurately trip 3-phase
short circuit fault during power swing.
The second criterion is a backup of the first criterion allowing longer monitoring period of voltage
variation.
To reduce the time delay for SF PSBR element during power swing, the change rate of voltage at
power swing center is also used which can release SF PSBR element quickly for the fault occurred
during power swing. The typical release time is less than 60ms.
21Mi
21Mi.En_PSBR 21Mi.Rls_PSBR
21Mi.Blk_PSBR 21M.Pilot.Rls_PSBR
21M.Pilot.En_PSBR
21M.Pilot.Blk_PSBR
21Qi
21Qi.En_PSBR 21Qi.Rls_PSBR
21Qi.Blk_PSBR 21Q.Pilot.Rls_PSBR
21Q.Pilot.En_PSBR
21Q.Pilot.Blk_PSBR
3.7.9.3 Logic
SIG 21Mi.Flg_PSBR
&
SIG Symmetrical |U1cosΦ |< t 0ms Unblocking for SF >=1 21Mi.Rls_PSBR
>=1
&
SIG Unsymmetrical |I0|+|I2|>
Unblocking for UF
SIG 21Mi.Flg_PSBR
SIG 21Qi.Flg_PSBR
&
SIG Symmetrical |U1cosΦ |< t 0ms Unblocking for SF >=1 21Qi.Rls_PSBR
>=1
&
SIG Unsymmetrical |I0|+|I2|>
Unblocking for UF
SIG 21Qi.Flg_PSBR
SIG 21M.Pilot.Flg_PSBR
&
SIG Symmetrical |U1cosΦ|< t 0ms Unblocking for SF >=1 21M.Pilot.Rls_PSBR
>=1
&
SIG Unsymmetrical |I0|+|I2|>
Unblocking for UF
SIG 21M.Pilot.Flg_PSBR
SIG 21Q.Pilot.Flg_PSBR
&
SIG Symmetrical |U1cosΦ|< t 0ms Unblocking for SF >=1 21Q.Pilot.Rls_PSBR
>=1
&
SIG Unsymmetrical |I0|+|I2|>
Unblocking for UF
SIG 21Q.Pilot.Flg_PSBR
Where:
i=1, 2, 3, 4, 5
21M.Pilot.Flg_PSBR and 21Q.Pilot.Flg_PSBR: Please refer to Figure 3.7-34 and Figure 3.7-35
3.7.9.4 Settings
When the circuit breaker is closed manually or automatically, it is possible to switch on to a fault.
This is especially critical if the line in the remote station is grounded, since the distance protection
would not clear the fault until overreach zones (zone 2 and/or zone 3) time delays have elapsed. In
this situation, however, the fastest possible clearance is required. The SOTF (switch onto fault)
protection is a complementary function to the distance protection. With distance SOTF protection,
a fast trip is achieved for a fault on the whole line, when the line is being energized. It shall be
responsive to all types of faults anywhere within the protected line.
21SOTF
21SOTF.En 21SOTF.On
21SOTF.Blk 21SOTF.Op
21SOTF.Op_PDF
3.7.10.3 Logic
EN [21SOTF.En]
Distance SOTF protection can be enabled or disabled, and can be initiated by several cases,
including manual closing signal, 3-pole reclosing, 1-pole reclosing and pole discrepancy
conditions.
SIG CB1.52b_PhA
>=1
SIG CB1.52b_PhB
SIG CB1.52b_PhC
&
SIG FD.Pkp
SET [SOTF.Opt_Mode_ManCls]=CBPos
>=1
SET [SOTF.Opt_Mode_ManCls]=ManClsBI/CBPos
SET [SOTF.Opt_Mode_ManCls]=All
SET [SOTF.Opt_Mode_ManCls]=ManClsBI
>=1
SET [SOTF.Opt_Mode_ManCls]=ManClsBI/CBPos
SET [SOTF.Opt_Mode_ManCls]=All
& >=1
SIG FD.Pkp 0 400ms Manual closing signal
SIG ManCls
SIG Uc<[SOTF.U_Ddl]
SIG Ia<0.06In
&
SIG Ib<0.06In
SIG Ic<0.06In
For double circuit breakers mode, the phase's open status corresponding to the line is invalid
unless both circuit breakers are in open position.
BI [CB1.52b_PhA] &
BI [CB2.52b_PhA]
BI [CB2.52b_PhB]
BI [CB1.52b_PhC] &
BI [CB2.52b_PhC]
&
SIG FD.Pkp
SET [SOTF.Opt_Mode_ManCls]=CBPos
>=1
SET [SOTF.Opt_Mode_ManCls]=ManClsBI/CBPos
SET [SOTF.Opt_Mode_ManCls]=All
SET [SOTF.Opt_Mode_ManCls]=ManClsBI
>=1
SET [SOTF.Opt_Mode_ManCls]=ManClsBI/CBPos
SET [SOTF.Opt_Mode_ManCls]=All
& >=1
SIG FD.Pkp 0ms 400ms Manual closing signal
SIG ManCls
SIG Ua<[SOTF.U_Ddl]
&
SIG Ub<[SOTF.U_Ddl]
SIG Uc<[SOTF.U_Ddl]
SIG Ia<0.06In
&
SIG Ib<0.06In
SIG Ic<0.06In
For accelerated tripping mode by manual closing signal, manual closing signal can be from circuit
breaker position, external binary signal of manual closing or dead line check.
When the circuit breaker is in open position while the device does not pick up, or external manual
closing binary input is energized, then manual closing signal will be kept for 400ms, which will
enable SOTF logic.
When the initiation mode of SOTF protection is set as “AutoInit” (i.e., [SOTF.Opt_Mode_ManCls] is
set as “AutoInit”), distance SOTF protection will be initiated by dead line check. When three
phases currents are all smaller than 0.06In and no fault detector element operates, SOTF logic will
be enabled only for 400ms if three phase voltages are all smaller than the setting [SOTF.U_Ddl]
with the time delay [SOTF.t_Ddl].
SIG FD.Pkp
&
& [21SOTF.t_ManCls] 0 21SOTF.Op_ManCls
EN [21SOTF.En_ManCls]
EN [21SOTF.Z2.En_ManCls] &
SIG 21M(21Q)2.Flg_PSBR
SIG 21M(21Q)3.Flg_PSBR
EN [21SOTF.Z4.En_ManCls] &
SIG 21M(21Q)4.Flg_PSBR
Figure 3.7-47 Logic diagram of distance SOTF protection by manual closing signal
EN [21SOTF.Z2.En_3PAR] &
SIG 21M(21Q)2.Flg_PSBR
>=1
EN [21SOTF.Z2.En_PSBR] &
SIG 21M(21Q)2.Rls_PSBR
EN [21SOTF.Z3.En_PSBR] &
SIG 21M(21Q)3.Rls_PSBR
EN [21SOTF.Z4.En_3PAR] &
SIG 21M(21Q)4.Flg_PSBR
>=1
EN [21SOTF.Z4.En_PSBR] &
SIG 21M(21Q)4.Rls_PSBR
EN [21SOTF.En_1PAR]
&
& [21SOTF.t_1PAR] 0
SIG PD signal
SIG 21M(21Q)2.Rls_PSBR
For single-phase permanent fault, distance SOTF protection for 1-pole reclosing onto the faulty
phase will trip three-phase circuit breaker.
SIG FD.Pkp
&
EN [21SOTF.En_PDF] [21SOTF.t_PDF] 0 21SOTF.Op_PDF
&
SIG 21M(21Q)2.Rls_PSBR &
SIG PD signal
Under pole discrepancy condition after single-phase tripping, distance SOTF protection will
accelerate to operate if another fault happens to the healthy phase.
3.7.10.4 Settings
The last four digital bits of the 12 have been assigned for pilot scheme protection. The
communication channel can be configured as single channel mode or as dual channels mode.
(FOx, x can be 1 or 2) according to the optical pilot channel module selected.
The modules can communicate in two modes via multiplexer or dedicated optical fibre.
Communication through dedicated fibre is usually recommended unless the received power does
not meet with the requirement. Channel of 64kbits/s or 2048kbits/s via dedicated fibre is shown in
Figure 3.8-1 and Figure 3.8-2. Two fibre cores of optical cable are dedicated to pilot scheme
protection. For dual firbre optical channels application, two fibre cores of optical cable are normally
in service, and all data are exchanged via the other healthy core if one core is failed.
TX RX
PCS-902 PCS-902
RX TX
ST connectors ST connectors
TX RX
RX TX
PCS-902 PCS-902
TX RX
RX TX
TX RX
PCS-902 PCS-902
RX TX
FC connectors FC connectors
TX RX
RX TX
PCS-902 PCS-902
TX RX
RX TX
Figure 3.8-2 Direct optical link up to 40km with1310nm or 100km with 1550nm
Channel of 64kbits/s or 2048kbits/s via multiplexer is shown in Figure 3.8-3, Figure 3.8-4 and
Figure 3.8-5.
C37.94 (N*64kbits/s)
Multi-mode FO
Communication convertor
E Interface
TX RX Link to
PCS-902 communicate
RX TX device
O
ST connectors ST connectors
E Interface
TX RX Link to
communicate
RX TX device
PCS-902
TX RX
RX TX O
ST connectors (FO2) ST connectors (FO2)
G.703 (64kbits/s)
Single-mode FO MUX-64
E Interface
TX RX Link to
PCS-902 communicate
RX TX device
O
FC connectors FC connectors
G.703 (64kbits/s)
Single-mode FO
MUX-64
FC connectors (FO1) FC connectors (FO1)
TX RX E
Interface
RX TX Link to
PCS-902 communicate
TX RX device
RX TX O
FC connectors (FO2) FC connectors (FO2)
G.703-E1 (2048kbits/s)
MUX-2M
Single-mode FO
E Interface
TX RX Link to
PCS-902 communicate
RX TX device
O
FC connectors FC connectors
E Interface
TX RX Link to
communicate
RX TX device
PCS-902
TX RX
RX TX O
FC connectors (FO2) FC connectors (FO2)
Valid messages exchange is key factor for digital pilot scheme protection.
The device transmits and receives messages based on respective clocks, which are called
transmit clock (i.e. clock TX) and receive clock (i.e. clock RX) respectively. Clock RX is fixed to be
extracted from message frame, which can ensure no slip frame and no error message received.
Clock TX has two options:
1. Use internal crystal clock, which is called internal clock. (master clock)
Depend on the clock used by the device at both ends, there are three modes.
1. Master-master mode
2. Slave-slave mode
3. Master-slave mode
One of them uses internal clock, the other uses external clock
The logic setting [FOx.En_IntClock] is used in pilot scheme protection to select the communication
clock. The internal clock is enabled automatically when the logic setting [FOx.En_IntClock] is set
as “1”. Contrarily, the external clock is enabled automatically when the logic setting
[FOx.En_IntClock] is set to “0”.
If the device uses multiplex PCM channel, logic setting [FOx.En_IntClock] at both ends should be
set as “0” (Mode 2). If the device uses dedicated optical fibre channel, clock Mode 1 and Mode 3
can be used. Mode 1 is recommended in considering simplification to user, i.e. logic setting
[FOx.En_IntClock] at both ends should be set as “1”.
In order to ensure reliability of the device when digital communication channel is applied, settings
[FO.LocID] and [FO.RmtID] are provided as identity code to distinguish uniquely the device at
remote end using same channel.
Under normal conditions, the identity code of the device at local end should be different with that at
remote end. In addition, it is recommended that the identity code of all devices, i.e., the setting
[FO.LocID], should be unique in the power grid. The setting range is from 0 to 65535. Only for loop
test, they are set as the same.
The setting [FO.LocID] of the device at an end should be the same as the setting [FO.RmtID] of
the device at opposite end and the greater [FO.LocID] between the two ends is chosen as a
master end for sampling synchronism, the smaller [FO.LocID] is slave end. If the setting [FO.LocID]
is set the same as [FO.RmtID], that implies the device in loopback testing state.
The setting [FO.LocID] is packaged in the message frame and transmitted to the remote end.
When the [FO.LocID] of the device at remote end received by local device is same to the setting
[FO.RmtID] of local device, the message received from the remote end is valid, and protection
information involved in message is read. When these settings are not matched, the message is
considered as invalid and protection information involved in message is ignored, corresponding
alarms will be issued.
The device has the function of on-line channel monitoring and channel statistics. It can produce
channel statistic report automatically at 9:00 every day and the report can be printed for operator
to check the channel quality. The monitoring contents of channel status are shown as follows, and
they can be viewed by the menu “Main Menu→Test→Prot Ch Counter→Chx Counter”.
It shows the starting time of the channel status statistics of the device at local end.
It shows the calculated communication channel time delay of the device at local end now (unit: us).
The calculation is based on the assumption of same channel path for to and from remote end. The
device measures propagation delay of communication channel based on the below principle.
Side S transmits a frame of message to side M, and meanwhile records the transmitting time “tss”
on the basis of clock on side S. When side M receives the message, it will record receiving time
“tmr” of the message with its own clock, and return a frame of message to side S at next fixed
transmitting time, meanwhile data of “tms-tmr” is included in the frame of message. Side S will
receive the message from side M at the time “tsr” and obtain the data of “tms-tmr”.
Therefore, the propagation delay of the channel “Td” is obtained through calculation:
(tsr t ss ) (tms t mr )
Td
2
By using the above calculated “Td”, the device automatically compensate time synchronization of
sampling data at each end and transimission time lag.
T1
It shows the total number of the error frames of the device at local end from starting time of
channel statistics until now. Error frame means that this frame fails in CRC check.
It shows the total number of abnormal messages of the device at local end from starting time of
channel statistics until now.
It shows the total number of the lost frames of the device at local end from starting time of channel
statistics until now.
7. FOx.N_RmtAbnor (total number of abnormal messages from the remote end of channel x)
It shows the total number of abnormal messages received from the remote end from starting time
of channel statistics until now.
It shows the total number of serious error frame seconds of the device at local end from starting
time of the channel statistics until now.
It shows the total number of loss synchronous of the device at local end from starting time of the
channel statistics until now.
FOx
FOx.En FOx.On
FOx.Sendi FOx.Recvi
FOx.Alm
FOx.Alm_ID
3.8.5 Logic
SIG FOx.Alm_ID
i can be 1, 2, 3, ......, 12
3.8.6 Settings
Table 3.8-2 Settings of pilot channel
The instant distance protection with underreaching setting is impossible to isolate the fault at
remote end of the line, while distance protection with overreaching setting needs a time delay to
grade with downstream protection to maintain discrimination. Pilot distance protection that
exchanges distance protection information at both ends of the line can remove the fault within this
Pilot distance protection is used to protect the whole line, and its setting is set as 1.2 times the line
length at least, so the problem of overreaching does not exist and pilot distance protection,
compared with the distance protection, it is not required to coordinate with other zones. In order to
simplify setting calculation, the downward offset angle of the reactance of pilot distance protection
with quadrilateral characteristic is fixed 12 °without setting, which has been well proved to be a
reliable angle by large project experience and test data. The angle of directional line in the second
quadrant (α) and the angle of directional line in the fourth quadrant (β) are as same as those of
distance protection with quadrilateral characteristic.
Pilot distance protection with permissive scheme receives permissive signal from the remote end,
so as to combine with local discrimination condition to accelerate tripping, so it has high security.
Blocking scheme will operate with a short time delay [85.t_DPU_Blocking1] if forward pilot zone
element operates and not receiving blocking signal before the short time delay expired.
Pilot distance protection can be enabled or disabled by input signals, logic setting and blocking
signal, as shown in Figure 3.9-1.
SIG 85-x.Z.En1
&
SIG 85-x.Z.En2
EN [85.Z.En]
&
85-x.Z.On
SIG 85-x.Z.Blk
Pilot distance protection receives and sends signals via pilot channel, and the logic of receiving
signal is shown in Figure 3.9-2.
SET [85.Opt_PilotMode]=POTT
When pilot scheme protection is out of service due to pilot channel failure or no pilot scheme
protection is provided. The fault outside zone 1 only can be cleared by zone 2 with a time delay. It
can not ensure that all faults within protected line are cleared instantaneously. As a supplement of
pilot scheme protection, zone extension can clear the fault within the whole line instantaneously.
Different with pilot distance protection, zone extension can also operate for external close up fault
in parallel line, but power supply can be restored by AR. So zone extension should be blocked
when AR is out of service and is not ready.
In order to prevent too many lines from disconnecting with system due to zone extension operate
when the circuit breaker is closed into permanent fault, zone extension should be blocked when
AR operates. For temporary fault, the line can be into service again after AR operates successfully.
For permanent fault in either local line or parallel line, distance protection with a time delay will
operate.
SIG 85-x.ZX.Blk2
&
SIG 79.Ready & [85.t_DPU_ZX] 0ms 85-x.Op_ZX
SIG Zpilot
Zone extension uses the setting of pilot zone (ZPilot), and its operation characteristic can be Mho
or Quad.
Distance elements zone 1 (Z1) with underreaching setting and pilot zone (ZPilot) with
overreaching setting are used for this scheme. Z1 element will send permissive signal to the
remote end and release tripping after Z1 time delay expired. After receiving permissive signal with
ZPilot element pickup, a tripping signal will be released.
The signal transmission element for PUTT is set according to underreaching mode, so current
reversal need not be considered.
For PUTT, there may be a dead zone under weak power source condition. If the fault occurs
outside Z1 zone at strong power source side, Z1 at weak power supply side may not operate to trip
and transmit permissive signal, and pilot distance protection will not operate. Therefore, the
system fault can only be removed by Z2 at strong power source side with time delay.
ZPilot
Z2
Z1
M
EM A Fault B EN
Z1 N
Z2
ZPilot
Relay A Relay B
Z1 Z1
& &
85-x.Op_Z 85-x.Op_Z
ZPilot ZPilot
Pilot distance protection always adopts pilot channel 1, and the logic of PUTT is shown in Figure
3.9-5.
SIG 85-x.Valid_Recv1
SIG ZPilot
ZPilot will send permissive signal to remote end once it picks up and release tripping signal upon
receiving permissive signal from the remote end.
When POTT is applied on parallel lines arrangement and the ZPilot setting covers 50% of the
parallel line, there may be a problem under current reversal condition, settings for current reversal
condition should be considered, please refer to section 3.9.2.6 for details.
Under weak power source condition, the problem of dead zone at weak power source end is
eliminated by the weak infeed logic, please refers to section 3.9.2.7 for details.
ZPilot
Z2
Zpilot_Rev
M
EM A Fault B EN
N
Zpilot_Rev Z2
ZPilot
Relay A Relay B
& &
ZPilot >=1 85-x.Op_Z 85-x.Op_Z >=1 ZPilot
WI WI
SIG 52b_PhA
& & >=1
SIG 52b_PhB &
200ms 0ms
SIG 52b_PhC &
85-x.Send1
SIG 85-x.Valid_Recv1 &
SIG 85-x.Z.FwdDir &
&
>=1 t1 t2
SIG 85-x.Z.On
SIG WI
&
& 85-x.Op_Z
SIG FD.Pkp 8ms 0ms
SET [85.Opt_PilotMode]=POTT
Where:
3.9.2.4 Blocking
Permissive scheme has high security, but it relies on pilot channel seriously. Pilot distance
protection will not operate when there is an internal fault with abnormal channel. Blocking scheme
could be considered as an alternative.
Blocking scheme takes use of pilot distance element Zpilot operation to terminate sending of
blocking signal. Blocking signal will be sent once fault detector picks up without pilot zone Zpilot
operation. Pilot distance protection will operate with a short time delay if pilot distance element
operates and not receiving blocking signal after timer expired.
The setting of pilot zone element Zpilot in Blocking scheme is overreaching, so current reversal
condition should be considered. However, the short time delay of pilot distance protection has an
enough margin for current reversal, that this problem has been resolved.
The short time delay must consider channel delay and with a certain margin to set. As shown in
Figure 3.9-8, an external fault happens to line MN. The fault is behind the device at M side, for
blocking scheme, the device at M side will send blocking signal to the device at N side. If channel
delay is too long, the device at side N has operated before receiving blocking signal. Hence, the
time delay of pilot distance protection adopted in blocking scheme should be set according to
channel delay.
Blocking signal
M N
EM Fault A B EN
For blocking scheme, pilot distance protection will operate when there is an internal fault with
abnormal channel, however, it is possible that pilot distance protection issue an undesired trip
when there is an external fault with abnormal channel.
ZPilot
Zpilot_Rev
M
EM A Fault B EN
N
Zpilot_Rev
ZPilot
Relay A Relay B
FD.Pkp & & FD.Pkp
SIG 52b_PhB
&
SIG 52b_PhA & >=1
SIG 52b_PhC
&
200ms 0ms
SIG 85-x.Valid_Recv1
&
85-x.Send1
&
SIG 85-x.Z.FwdDir >=1
SIG WI
&
SIG FD.Pkp [85.t_DPU_Blocking1] 85-x.Op_Z
SIG 85-x.Z.On
Current reversal logic is only used for permissive scheme. For blocking scheme, the time delay of
pilot distance protection has enough margin for current reversal, so current reversal need not be
considered.
3.9.2.5 Unblocking
Permissive scheme will trip only when it receives permissive signal from the remote end. However,
it may not receive permissive signal from the remote end when pilot channel fails. For this case,
pilot distance protection can adopt unblocking scheme. Under normal conditions, the signaling
equipment works in the pilot frequency, and when the device operates to send permissive signal,
the signaling equipment will be switched to high frequency. While pilot channel is blocked, the
signaling equipment will receive neither pilot frequency signal nor high frequency signal. The
signaling equipment will provide a contact to the device as unblocking signal. When the device
receives unblocking signal from the signaling equipment, it will recognize channel failure, and
unblocking signal will be taken as permissive signal temporarily.
The unblocking function can only be used together with PUTT and POTT.
EN [85.En_Unblocking1]
[85.t_Unblocking1] 0ms
SET [85.Opt_PilotCh1]
&
85-x.Unblocking1 Valid
SIG Pilot distance forward element
When there is a fault in one of the parallel lines, the direction of the fault current may change
during the sequence tripping of the circuit breaker at both ends as shown in Figure 3.9-12: When a
fault occurs on line C–D near breaker D, the fault current through line A-B to D will flow from A to B.
When breaker D is tripped, but breaker C is not tripped, the fault current in line A-B will then flow
from B to A. This process is the current reversal.
M N M N
Strong Weak
A B A B
source source
EM EN EM EN
C D C D
As shown above, the device A judges a forward fault while the device B judges a reverse fault
before break D is tripped. However, the device A judges a reverse fault while the device B judges a
forward fault after breaker D is tripped. There is a competition between pickup and drop off of pilot
zones in the device A and the device B when the fault measured by the device A changes from
forward direction into reverse direction and vice versa for the device B. There may be
maloperation for the device in line A-B if the forward direction of the device B has operated but the
forward direction of the device A drops off slightly slower or the forward direction of the device B
has operated but the forward direction information of the device A is still received due to the
channel delay (the permissive signal is received).
In general, the following two methods shall be adopted to solve the problem of current reversal:
1. The fault shall be measured by means of the reverse element of the device B. Once the
reverse element of the device B operates, the send signals and the tripping circuit will be
blocked for a period of time after a short time delay. This method can effectively solve the
problem of competition between the device A and the device B, but there shall be a
precondition. The reverse element of the device B must be in cooperation with the forward
element of the device A, i.e. in case of a fault in adjacent lines, if the forward element of the
device A operates, and the reverse element of the device B must also operate. Once the
bilateral cooperation fails, the anticipated function cannot be achieved. In addition, the
blocking time for sending signals and the tripping circuit after the reverse element of the
device B operates shall be set in combination with the channel time delay.
2. Considering the pickup and drop off time difference of distance elements and the channel time
delay between the device A and the device B, the maloperation due to current reversal shall
be eliminated by setting the time delay. The reverse direction element of the device is not
required for this method, the channel time delay and the tripping time of adjacent breaker
shall be taken into account comprehensively.
This protection device adopts the second method to eliminate the maloperation due to current
reversal.
t1: [85.t_DPU_CR1]
t2: [85.t_DDO_CR1]
Referring to above figure, when signal from the remote end is received without pilot forward zone
pickup, the current reversal blocking logic is enabled after t1 delay.
The time delay of t1 [85.t_DPU_CR1] shall be set the shortest possible but allowing sufficient time
for pilot forward zone pickup, generally set as 25ms.
Once the current reversal logic is enabled, the healthy line device B transfer tripping is blocked.
The logic will be disabled by either the dropoff of signal or the pickup of pilot forward zone. A time
delay t2 [85.t_DDO_CR1] is required to avoid maloperation for the case that the pilot forward zone
(or forward element of pilot directional earth-fault protection) of device B picks up before the signal
from device A drops off. Considering the channel propagation delay and the pickup and drop-off
time difference of pilot forward zone (or pilot directional earth-fault element) with margin, t2 is
generally set between 25ms~40ms.
Because the time delay of pilot distance protection has an enough margin to current reversal,
current reversal blocking only used for permissive scheme not blocking scheme.
In case of a fault in line at one end of which there is a weak power source, the fault current
supplied to the fault point from the weak power source is very small or even nil, and the
conventional distance element could not operate. The weak infeed logic combines the protection
information from the strong power source end and the electric feature of the local end to cope with
the case.
The weak infeed logic can be only applied for BOTT and POTT. The weak infeed logic has options
for echo or both echo and tripping.
ZPilot
Z1 Zpilot_Rev
M
EM A Fault B EN
Z1 N
Zpilot_Rev
ZPilot
Load
When the weak infeed logic is enabled, distance forward and reverse element and direction
element of directional earth-fault protection do not operate with the voltage lower than the setting
[85.U_UV_WI] after the device picks up, upon receiving signal from remote end, the weak infeed
logic will echo the signal back to remote end for 200ms if the weak infeed echo is enabled, the
weak infeed end will echo signal and release tripping according to the logic.
ZPilot_Rev at weak source end must coordinate with ZPilot_Set of the remote end. The coverage
of ZPilot_Rev must exceed that of ZPilot_Set of the remote end. ZPilot_Rev only activates in the
protection calculation when the weak infeed logic is enabled. In case of the weak infeed logic not
enabled, the setting coordination is not required.
If the device does not pick up, and the weak infeed logic is enabled, upon receiving signal from
remote end with the voltage lower than the setting [85.U_UV_WI], the weak infeed logic will echo
back to remote end for 200ms. When either weak infeed echo or weak infeed tripping is enabled,
then the weak infeed logic is deemed to be enabled. During the device picking up, the weak infeed
logic is shown in Figure 3.9-15.
SIG FD.Pkp
SIG 85-x.Valid_Recv1
EN [85.En_WI]
SET Upp<[85.U_UV_WI]
If the device does not pick up, the weak infeed logic is shown as the following figure:
For permissive scheme, the signal receive condition means that the permissive signal is received
or the unblocking signal is valid.
3.9.2.8 CB Echo
A feature is also provided which enables fast tripping to be maintained along the whole length of
the protected line, even when one terminal is open. The device will initiate sending a pulse of
200ms permissive signal when signal receive condition is met during CB is in open position.
SIG 52b_PhC
SET [85.Opt_PilotMode]=POTT
CB Echo logic is only applied to permissive overreach mode not underreach mode, and it is
processed without the device pickup. This logic will be terminated immediately once the device
picks up.
85
85-x.Z.En1 85-x.Z.On
85-x.Z.En2 85-x.ZX.On
85-x.Z.Blk 85-x.Op_Z
85-x.Abnor_Ch1 85-x.Send1
85-x.Rcv1 85-x.SendB
85-x.RcvB 85-x.SendC
85-x.RcvC 85-x.Op_ZX
85-x.ExTrp 85-x.ZX_St
85-x.Unblocking1
85-x.ZX.En1
85-x.ZX.En2
85-x.ZX.Blk1
85-x.ZX.Blk2
79.Ready
Input signal of initiating sending permissive signal from external tripping signal for
8 85-x.ExTrp
pilot distance protection x (x=1 or 2)
9 85-x.Unblocking1 Unblocking signal 1 of pilot distance protection x (x=1 or 2)
Zone Extension enabling input 1 of pilot distance protection x, it is triggered from
10 85-x.ZX.En1
binary input or programmable logic etc. (x=1 or 2)
Zone Extension enabling input 2 of pilot distance protection x, it is triggered from
11 85-x.ZX.En2
binary input or programmable logic etc. (x=1 or 2)
Zone Extension blocking input 1 of pilot distance protection x, it is triggered from
12 85-x.ZX.Blk1
binary input or programmable logic etc. (x=1 or 2)
Zone Extension blocking input 2 of pilot distance protection x, it is triggered from
13 85-x.ZX.Blk2
binary input or programmable logic etc. (x=1 or 2)
14 79.Ready AR has been ready for reclosing cycle.
No. Output Signal Description
1 85-x.Z.On Pilot distance protection x is enabled. (x=1 or 2)
2 85-x.ZX.On Zone extension protection of pilot distance protection x is enabled. (x=1 or 2)
3 85-x.Op_Z Pilot distance protection x operates. (x=1 or 2)
Output signal of sending permissive signal 1 or sending A-phase permissive
4 85-x.Send1 signal of pilot distance protection x (only for phase-segregated command scheme,
x=1 or 2)
Output signal of sending B-phase permissive signal of pilot distance protection x
5 85-x.SendB
(only for phase-segregated command scheme, x=1 or 2)
Output signal of sending C-phase permissive signal of pilot distance protection x
6 85-x.SendC
(only for phase-segregated command scheme, x=1 or 2)
7 85-x.Op_ZX Zone extension protection of pilot distance protection x operates. (x=1 or 2)
8 85-x.ZX_St Zone extension protection of pilot distance protection x starts (x=1 or 2)
3.9.5 Settings
Table 3.9-2 Settings of pilot distance protection
Directional earth fault protection needs to coordinate with downstream protection with definite or
inverse time delay so it cannot clear an internal fault quickly. Pilot directional earth-fault protection
takes use of directional earth fault elements on both ends, it can detect high resistance fault and
maintain high-speed operation.
Pilot protection requires communication channel to exchange the protection information at both
ends. The channel may be dedicated or multiplexed channel through optical fiber or any other
communication media.
Pilot directional earth-fault protection can be used independently, for example, no distance
protection is equipped with the device but fast operation is required for the whole line, or it is used
as backup protection of pilot distance protection to enhance the sensitivity for an earth fault with
high fault resistance.
Sending permissive signal (or terminating sending signal) to the opposite end is controlled by
forward direction element. Current reversal logic is available for parallel line operation and CB
echo logic is provided once pilot directional earth fault protection is enabled. Current reversal logic
is only used for permissive scheme. For blocking scheme, current reversal need not be considered
because there is a settable time delay in pilot directional earth-fault protection.
Pilot directional earth-fault protection can be enabled or disabled by input signals, logic setting and
blocking signal, as shown in Figure 3.10-1.
SIG 85-x.DEF.En1
&
SIG 85-x.DEF.En2
EN [85.DEF.En]
&
85-x.DEF.On
SIG 85-x.DEF.Blk
Pilot directional earth-fault protection comprises permissive scheme and blocking scheme. It can
share pilot channel 1 ([85.DEF.En_IndepCh]=0) with pilot distance protection, or uses independent
pilot channel 2 ([85.DEF.En_IndepCh]=1) by setting logic setting [85.DEF.En_IndepCh]. For
underreach mode, pilot directional earth-fault always adopts independent pilot channel 2. The
logic of receiving signal is shown in Figure 3.10-2.
&
SIG 85-x.Abnor_Ch1
SIG 85-x.Abnor_Ch2
Pilot protection with permissive scheme receives permissive signal from the device of remote end,
so as to combine with local discrimination condition to accelerate tripping, so it has high security.
Operation of forward directional earth fault element is used to send permissive signal to the
remote end when the protection is enabled and will release tripping signal upon receiving
permissive signal from the remote end with further guarded by no operation of reverse directional
earth fault element. This ensures the security of the protection.
85-x.FwdDir_DEF_Pilot
85-x.RevDir_DEF_Pilot
M
EM A Fault B EN
N
85-x.RevDir_DEF_Pilot
85-x.FwdDir_DEF_Pilot
Relay A
85-x.FwdDir_DEF_Pilot & &
[85.DEF.t_DPU] 85-x.Op_DEF 85-x.Op_DEF [85.DEF.t_DPU]
85-x.FwdDir_DEF_Pilot
Relay B
SIG 52b_PhA
& & >=1
SIG 52b_PhB &
[85.DEF.t_DPU]+200ms 0ms
SIG 52b_PhC
SIG 85-x.Valid_Recv_DEF
&
SIG FD.Pkp 85-x.Send_DEF
SIG 85-x.RevDir_DEF_Pilot
&
&
SIG 85-x.Valid_Recv_DEF t1 t2
&
SIG FD.Pkp
SIG 85-x.DEF.On
&
& 85-x.Op_DEF
[85.DEF.t_DPU] >=1
&
EN [85.DEF.En_IndepCh]
When sharing pilot channel 1 with pilot distance protection, t1 and t2 are the settings
[85.t_DPU_CR1] and [85.t_DDO_CR1] respectively.
3.10.2.2 Blocking
Permissive scheme has high security, but it relies on pilot channel seriously. Pilot directional
earth-fault protection will not operate when there is an internal fault with abnormal channel.
Blocking scheme could be considered as an alternative.
Blocking scheme sends blocking signal when fault detector picks up and zero-sequence forward
element does not operate or both zero-sequence forward element and zero-sequence reverse
element do not operate. Pilot directional earth-fault protection will operate if forward directional
zero-sequence overcurrent element operates and not receiving blocking signal.
85-x.FwdDir_DEF_Pilot
85-x.RevDir_DEF_Pilot
M
EM A Fault B EN
N
85-x.RevDir_DEF_Pilot
85-x.FwdDir_DEF_Pilot
Relay A Relay B
FD.Pkp FD.Pkp
& &
85-x.RevDir_DEF_Pilot & & 85-x.RevDir_DEF_Pilot
85-x.FwdDir_DEF_Pilot 85-x.FwdDir_DEF_Pilot
& &
& 85-x.Op_DEF 85-x.Op_DEF &
[85.DEF.t_DPU] [85.DEF.t_DPU]
SIG 52b_PhA
& >=1
SIG 52b_PhB &
85-x.Send_DEF
SIG 52b_PhC
SIG FD.Pkp
SIG 85-x.DEF.On
When DEF shares pilot channel 1 with pilot distance protection, time delay of pilot directional
earth-fault protection will change from the setting [85.DEF.t_DPU] to the setting
[85.t_DPU_Blocking1].
Because the time delay of pilot directional earth-fault protection has enough margin for current
reversal, so blocking scheme should not consider the current reversal condition.
For blocking scheme, pilot directional earth-fault protection will operate when there is an internal
fault with abnormal channel, however, it is possible that pilot directional earth-fault protection issue
an undesired trip when there is an external fault with abnormal channel.
3.10.2.3 Unblocking
Permissive scheme will operate only when it receives permissive signal from the remote end.
However, it may not receive permissive signal from the remote end when pilot channel fails. For
this case, pilot directional earth-fault protection can adopt unblocking scheme. Under normal
conditions, the signaling equipment works in the pilot frequency, and when the device operates to
send permissive signal, the signaling equipment will be switched to high frequency. While the
channel is blocked, the signaling equipment will receive neither pilot frequency signal nor high
frequency signal. The signaling equipment will provide a contact to the device as unblocking signal.
When the device receives unblocking signal from the signaling equipment, it will recognize
channel failure, and unblocking signal will be taken as permissive signal temporarily.
The unblocking scheme can only be used together with permissive scheme.
EN [85.En_Unblocking2] &
&
SIG 85-x.Unblocking2 & 85-x.Unblocking2 Valid
[85.t_Unblocking2] 0ms
EN [85.Opt_PilotCh2]
The reach of directional earth-fault protection is difficult to define. There may have problem for
pilot direction earth-fault protection applied on parallel line arrangement due to current reversal
phenomenon. Current reversal blocking logic using time delay method is adopted in the device. It
is the same logic as pilot distance protection. Please refer to section 3.9.2.6 for details. The only
difference is that different signal receive terminal is used if independent channel is selected.
3.10.2.5 CB Echo
When CB Echo logic is applied for DEF, the device will initiate sending a pulse of permissive signal
if signal receive condition is met during CB is in open position.
SIG FD.Pkp
SIG 52b_PhA
&
>=1
SIG 52b_PhB
SIG 52b_PhC
EN 85.DEF.En_IndepCh
85
85-x.DEF.En1 85-x.DEF.On
85-x.DEF.En2 85-x.Op_DEF
85-x.DEF.Blk 85-x.DEF_BlkAR
85-x.Abnor_Ch1 85-x.Send1
85-x.Abnor_Ch2 85-x.Send2
85-x.Rcv1
85-x.Rcv2
85-x.ExTrp
85-x.Unblocking1
85-x.Unblocking2
3.10.5 Settings
Table 3.10-2 Settings of pilot directional earth-fault protection
L M N
EM C D A B EN
Fault
When line LM has an earth fault, the fault currents flowing through the relay A and the relay D are
of similar magnitude in most cases. It is desirable that the fault is isolated from the power system
by tripping the circuit breaker C and circuit breaker D. Hence, the overcurrent protection of relay A
and relay D require to associate with current direction to fulfill selective tripping.
Directional earth fault protection has a time delay due to coordinate with that of downstream so it
cannot clear the fault quickly. Pilot directional earth-fault protection, which is fulfilled by directional
earth fault element on both ends, it can maintain fast operation and achieve high sensitivity to
detect high resistance fault.
The module computes direction of phase current and phase-to-phase current, zero-sequence
current and negative-sequence current.
The direction of phase current and phase-to-phase current equips with an under-voltage direction
function to ensure that phase or phase-to-phase overcurrent protection has explicit directionality
when the polarized voltage is too low for close up fault.
The direction of zero-sequence current and negative-sequence current direction equips with an
impedance compensation function to ensure that zero-sequence or negative-sequence
overcurrent protection has explicit directionality when the zero-sequence voltage or the
negative-sequence voltage is too low.
By setting the characteristic angle [RCA_OC] to determine the most sensitive forward angle of
phase current and phase-to-phase current, power value is calculated using phase current with
phase polarized voltage or phase-to-phase current with phase-to-phase polarized voltage to
determine the direction of phase current or phase-to-phase current respectively in forward
direction or reverse direction. When the power value is zero, neither forward direction nor reverse
direction is considered. As shown below:
jX
U
φ
θ I
R
O
Forward direction
Reverse direction
Where:
P=U×[I×COS(θ-φ)]
From above diagram can be seen, when θ=φ, P reaches to the maximum value. It is considered
as the most sensitive forward direction. Hence, φ is called as sensitivity angle of phase
overcurrent protection.
In the event of asymmetrical fault, because phase or phase-to-phase voltage may decrease to
very low voltage whereas positive-sequence voltage does not, the polarized voltage of phase or
phase-to-phase current direction uses positive-sequence voltage to avoid wrong direction due to
too low polarized voltage. Therefore, using positive-sequence voltage as polarized voltage can
ensure that the direction determination has no dead zone for asymmetrical fault. For symmetric
fault, if positive-sequence voltage decreases to 15%Un, the device uses memorized
positive-sequence voltage as polarized voltage, the memorized positive-sequence voltage is 1.5
cycles pre-fault positive-sequence voltage.
When using normal polarized voltage to calculate phase and phase-to-phase current direction,
there are total twelve direction determination algorithm including forward direction and reverse
direction.
When the symmetrical fault occurs on a power system, positive-sequence voltage may reduce to
less than 0.15Un, the device will switch to phase or phase-to-phase current direction for
under-voltage condition. The 1.5 cycle pre-fault positive-sequence voltage is used as polarized
voltage with reverse threshold to ensure stable direction decision when three-phase voltage goes
to approximately zero due to close up fault.
At first, the threshold is forward offset before direction is determined, and the threshold will be
reversed offset after direction is determined.
By setting the characteristic angle [RCA_ROC] and [RCA_NegOC] to determine the most
sensitive forward angle of zero-sequence current and negative-sequence current, power value is
calculated using zero-sequence current with zero-sequence voltage or negative-sequence current
When the power value is between 0 and -0.1In, neither forward direction nor reverse direction is
considered.
jX 3U0
θ-180°
-3I0
φ
R
O
3I0
θ Reverse direction
Forward direction
Where:
P=U×[I×COS(θ-φ)]
Calculating the power value using zero-sequence current (3I0) and zero-sequence voltage (3U0)
to determine the direction of zero-sequence current
The zero-sequence current and the zero-sequence voltage can be gained by calculation
Calculating the power value using negative-sequence current (3I2) and negative-sequence
voltage (3U2) to determine the direction of negative-sequence current
The negative-sequence current and the negative-sequence voltage can be gained by calculation
is the setting [Z0_Comp], which cannot exceed the total zero-sequence impedance of
is the setting [Z2_Comp], which cannot exceed the total negative-sequence impedance
DIR
FwdDir_ROC
RevDir_ROC
FwdDir_NegOC
RevDir_NegOC
FwdDir_A
FwdDir_B
FwdDir_C
RevDir_A
RevDir_B
RevDir_C
FwdDir_AB
FwdDir_BC
FwdDir_CA
RevDir_AB
RevDir_BC
RevDir_CA
3.11.5 Settings
Table 3.11-3 Settings of current direction
When a fault occurs in power system, usually the fault current would be very large and phase
overcurrent protection operates monitoring fault current is then adopted to avoid further damage to
protected equipment. Directional element can be selected to improve the sensitivity and selectivity
of the protection. For application on feeder-transformer circuits, second harmonic can also be
selected to block phase overcurrent protection to avoid the effect of inrush current on the
protection.
1. Four-stage phase overcurrent protection with independent logic, current and time delay
settings.
3. Direction control element can be selected to control each stage phase overcurrent protection
with three options: no direction, forward direction and reverse direction.
4. Second harmonic can be selected to block each stage of phase overcurrent protection.
3.12.2.1 Overview
2. Direction control element: one direction control element shared by all overcurrent elements,
and each overcurrent element can individually select protection direction.
3. Harmonic blocking element: one harmonic blocking element shared by all overcurrent
elements and each phase overcurrent element can individually enable the output signal from
harmonic element as a blocking input.
Where:
When the percentage of second harmonic component to fundamental component of any phase
current is greater than the setting [50/51P.K_Hm2], harmonic blocking element operates to block
stage x overcurrent element if corresponding logic setting [50/51Pi.En_Hm2_Blk] enabled.
Operation criterion:
Where:
If fundamental component of any phase current is lower than the minimum operating current
(0.1In), then harmonic calculation is not carried out and harmonic blocking element does not
operate.
Equation 3.12-3
Where:
α is a constant.
K is a constant.
C is a constant.
The user can select the operating characteristic from various inverse-time characteristic curves by
setting [50/51Pi.Opt_Curve], and parameters of available characteristics for selection are shown in
the following table.
If all available curves do not comply with user application, user may set [50/51Pi.Opt_Curve] as
“UserDefine” to customize the inverse-time curve characteristic with constants α, K and C. (only
stage 1)
When inverse-time characteristic is selected, if calculated operating time is less than setting
[50/51Pi.tmin], then the operating time of the protection changes to the value of setting
[50/51Pi.tmin] automatically.
Define-time or inverse-time phase overcurrent protection drops off instantaneously after fault
current disappears.
50/51Pi
50/51Pi.En1 50/51Pi.On
50/51Pi.En2 50/51Pi.StA
50/51Pi.Blk 50/51Pi.StB
50/51Pi.StC
50/51Pi.St
50/51Pi.Op
3.12.5 Logic
EN [50/51Pi.En]
&
SIG 50/51Pi.En1 &
50/51Pi.On
SIG 50/51Pi.En2
>=1
SIG 50/51Pi.Blk 50/51Pi.St
EN [50/51Pi.En_VTS_Blk]
SET [50/51Pi.Opt_Dir]=Non_Directional
SET [50/51Pi.En_Hm2_Blk]
SIG FD.Pkp
& Timer
t
SIG 50/51Pi.St
i=1, 2, 3, 4
3.12.6 Settings
Table 3.12-3 Settings of phase overcurrent protection
In order to improve the selectivity of earth fault protection in power grid with multiple power
sources, directional element can be selected to control earth fault protection. For application on
line-transformer unit, second harmonic also can be selected to block earth fault protection to avoid
the effect of sympathetic current on the protection.
1. Four-stage earth fault protection with independent logic, current and time delay settings.
3. Directional element can be selected to control each stage of earth fault protection with three
4. Second harmonic can be selected to block each stage of earth fault protection.
5. Stage 2, 3, 4 of earth fault protection can enable short time delay to improve operation speed.
3.13.2.1 Overview
1. Overcurrent element: each stage equipped with one independent overcurrent element.
2. Directional control element: one direction control element shared by all overcurrent elements,
and each overcurrent element can individually select protection direction.
3. Harmonic blocking element: one harmonic blocking element shared by all overcurrent
elements and each overcurrent element can individually enable the output signal of harmonic
blocking element as a blocking input.
The operation criterion for each stage of earth fault protection is:
Where:
In order to prevent effects of inrush current on earth fault protection, harmonic blocking function
can be selected for each stage of earth fault element by configuring logic setting
[50/51Gi.En_Hm2_Blk].
Operation criterion:
Where:
If fundamental component of residual current is lower than the minimum operating current (0.1In)
then harmonic calculation is not carried out and harmonic blocking element does not operate.
All 4 stages earth fault protection can be selected as definite-time or inverse-time characteristic,
and inverse-time operating time curve is as follows.
Equation 3.13-3
Where:
K is a constant
C is a constant.
α is a constant.
The user can select the operating characteristic from various inverse-time characteristic curves by
setting [50/51Gi.Opt_Curve], and parameters of available characteristics for selection are shown
in the following table.
If all available curves do not comply with user application, user may set [50/51Gi.Opt_Curve] as
“UserDefine” to customize the inverse-time curve characteristic, and constants K, α and C with
configuration tool software. (only stage 1)
When inverse-time characteristic is selected, if calculated operating time is less than setting
[50/51Gi.tmin], then the operating time of the protection changes to the value of setting
[50/51Gi.tmin] automatically.
Define-time or inverse-time directional earth-fault protection drops off instantaneously after fault
current disappears.
50/51Gi
50/51Gi.En1 50/51Gi.On
50/51Gi.En2 50/51Gi.On_ShortDly
50/51Gi.Blk 50/51Gi.St
50/51Gi.En_ShortDly 50/51Gi.Op
50/51Gi.Blk_ShortDly
3.13.5 Logic
EN [50/51G1.En]
&
SIG 50/51G1.En1 &
50/51G1.On
SIG 50/51G1.En2
SIG 50/51G1.Blk
&
SIG FD.Pkp
SET 3I0>[50/51G1.3I0_Set]
EN [50/51G1.En_Abnor_Blk] >=1
&
SET [50/51G1.Opt_Dir]=Non_Directional
EN [50/51G1.En_CTS_Blk]
>=1
SIG Three phase currents 2nd Hm Detect &
SIG I0_2nd>[50/51G. K_Hm2]×I0
SET [50/51G1.En_Hm2_Blk]
>=1
& 50/51G1.Op
[50/51G1.t_Op] 0
SET [50/51G1.Opt_Curve]=DefTime
EN [50/51Gi.En_ShortDly]
&
SIG 50/51Gi.En_ShortDly 50/51Gi.On_ShortDly
SIG 50/51Gi.Blk_ShortDly
EN [50/51Gi.En]
&
SIG 50/51Gi.En1 &
50/51Gi.On
SIG 50/51Gi.En2
SIG 50/51Gi.Blk
&
SIG FD.Pkp
SET 3I0>[50/51Gi.3I0_Set]
EN [50/51Gi.En_Abnor_Blk] >=1
&
SET [50/51Gi.Opt_Dir]=Non_Directional
EN [50/51Gi.En_CTS_Blk]
>=1
SIG I3P 2nd Hm Detect &
SET [50/51Gi.En_Hm2_Blk]
& >=1
[50/51Gi.t_Op] 0 50/51Gi.Op
SET [50/51Gi.Opt_Curve]=DefTime
&
[50/51Gi.t_ShortDly] 0
SIG 50/51Gi.On_ShortDly
i=2, 3, 4
Abnormal condition 1: when the system is under pole disagreement condition, for 1-pole AR, earth
fault protection will operate. If the logic setting [50/51Gi.En_Abnor_Blk] is set as “1”, the stage x of
earth fault protection will be blocked. If the logic setting [50/51Gi.En_Abnor_Blk] is set as “0”, earth
fault protection is not controlled by direction element.
Abnormal condition 2: When manually closing circuit breaker, three phases of the circuit breaker
maybe not operate simultaneously, and SOTF protection should operate. If the logic setting
[50/51Gi.En_Abnor_Blk] is set as “1”, the stage x of earth fault protection will be blocked. If the
logic setting [50/51Gi.En_Abnor_Blk] is set as “0”, earth fault protection is not controlled by
direction element.
Abnormal condition 3: VT circuit failure. If the logic setting [50/51Gi.En_Abnor_Blk] is set as “1”,
the stage x of earth fault protection will be blocked. If the logic setting [50/51Gi.En_Abnor_Blk] is
set as “0”, earth fault protection is not controlled by direction element.
3.13.6 Settings
Table 3.13-3 Settings of earth fault protection
When an asymmetric short-circuit fault happens to the power system or the power system is under
asymmetrical three-phase operation, the power system will generate negative-sequence current.
Negative-sequence overcurrent will cause generator, motor and other equipments serious
damage, so negative-sequence overcurrent protection is used to prevent them. In order to make
negative-sequence overcurrent protection own selectivity in multiplex power supply system,
negative-sequence overcurrent protection can be controlled by direction control element.
2. Each stage can be selected to block AR by the setting and stage 4 of negative-sequence
overcurrent protection can be selected to operate to trip or alarm.
6. Each stage can select independent releasing threshold based on the ratio of
negative-sequence current to positive-sequence current to prevent negative-sequence
overcurrent protection from undesired operation for three-phase fault with asymmetrical
position exchange of three-phase.
3.14.2.1 Overview
1. Fault detector: each stage is controlled by the fault detector based on negative-sequence
current. Negative-sequence overcurrent protection can operate when the fault detector based
on negative-sequence current operate and it is enabled.
2. Overcurrent element: each stage is equipped with one independent overcurrent element.
3. Directional control element: one direction control element is shared by all overcurrent
elements, and each overcurrent element can individually select protection direction.
4. Ratio element: each stage is equipped with one independent ratio element (I2/I1), usually the
same setting is applied for all stages.
The operation criterion for each stage of negative-sequence overcurrent protection is:
I2>[50/51Qi.I2_Set]
I2/I1>[50/51Qi.I2/I1_Set]
Where:
Equation 3.14-2
Where:
K is a constant
C is a constant.
α is a constant.
The user can select the operating characteristic from various inverse-time characteristic curves by
setting [50/51Qi.Opt_Curve], and parameters of available characteristics for selection are shown
in the following table.
If all available curves do not comply with user application, user may set [50/51Qi.Opt_Curve] as
“UserDefine” to customize the inverse-time curve characteristic, and constants K, α and C with
configuration tool software. (only stage 1)
When inverse-time characteristic is selected, if calculated operating time is less than setting
[50/51Qi.tmin], then the operating time of the protection changes to the value of setting
[50/51Qi.tmin] automatically.
50/51Qi
50/51Gi.En1 50/51Qi.On
50/51Gi.En2 50/51Qi.St
50/51Qi.Blk 50/51Qi.Op
50/51Q4.Alm
3.14.5 Logic
EN [50/51Qi.En]
&
SIG 50/51Qi.En1 &
50/51Qi.On
SIG 50/51Qi.En2
SIG 50/51Qi.Blk
SET I2>[50/51Qi.I2_Set]
EN [50/51Qi.En_Abnor_Blk] >=1
& & &
SIG No abnormal conditions 50/51Qi.St
& Timer
t
50/51Qi.Op
t
SET [50/51Qi.Opt_Dir]=Non_Directional
SI G CTS.Alm &
EN [50/51Qi.En_CTS_Blk]
SI G FD.NOC.Pkp
i=1, 2, 3
Abnormal condition 1: when the system is under pole disagreement condition, for 1-pole AR,
negative-sequence overcurrent protection will operate. If the logic setting [50/51Qi.En_Abnor_Blk]
is set as “1”, the stage x of negative-sequence overcurrent protection will be blocked. If the logic
setting [50/51Qi.En_Abnor_Blk] is set as “0”, negative-sequence overcurrent protection is not
controlled by direction element.
Abnormal condition 2: When manually closing circuit breaker, three phases of the circuit breaker
maybe not operate simultaneously, and SOTF protection should operate. If the logic setting
[50/51Qi.En_Abnor_Blk] is set as “1”, the stage x of negative-sequence overcurrent protection will
be blocked. If the logic setting [50/51Qi.En_Abnor_Blk] is set as “0”, negative-sequence
overcurrent protection is not controlled by direction element.
Abnormal condition 3: VT circuit failure. If the logic setting [50/51Qi.En_Abnor_Blk] is set as “1”,
the stage x of negative-sequence overcurrent protection will be blocked. If the logic setting
[50/51Qi.En_Abnor_Blk] is set as “0”, negative-sequence overcurrent protection is not controlled
by direction element.
EN [50/51Q4.En]
&
SIG 50/51Q4.En1 &
50/51Q4.On
SIG 50/51Q4.En2
SIG 50/51Q4.Blk
SET I2>[50/51Q4.I2_Set]
EN [50/51Q4.En_Abnor_Blk] >=1
& & &
SIG No abnormal conditions 50/51Q4.St
&
& Timer
SET [50/51Q4.Opt_Dir]=Non_Directional t
50/51Q4.Alm
t
SIG CTS.Alm &
EN [50/51Q4.En_CTS_Blk]
& Timer
SIG FD.NOC.Pkp t
50/51Q4.Op
t
EN [50/51Q4.En_Trp]
3.14.6 Settings
Table 3.14-3 Settings of negative-sequence overcurrent protection
Equation 3.15-1
Where:
α is a constant.
K is a constant.
C is a constant.
The user can select the operating characteristic from various inverse-time characteristic curves by
setting [50PVT.Opt_Curve] and [50GVT.Opt_Curve], and parameters of available characteristics
for selection are shown in the following table.
When inverse-time characteristic is selected, if calculated operating time is less than setting
[50PVT.tmin] or [50GVT.tmin], then the operating time of the protection changes to the value of
setting [50PVT.tmin] or [50GVT.tmin] automatically.
50PVT/50GVT
50PVT.En1 50PVT.On
50PVT.En2 50PVT.Op
50PVT.Blk 50PVT.St
50GVT.En1 50PVT.StA
50GVT.En2 50PVT.StB
50GVT.Blk 50PVT.StC
50GVT.On
50GVT.Op
50GVT.St
3.15.5 Logic
SIG 50PVT.En1
&
SIG 50PVT.En2 &
50PVT.On
EN [50PVT.En]
SIG 50PVT.Blk
& >=1
& [50PVT.t_Op] 0ms 50PVT.Op
SIG FD.Pkp
50PVT.St
SIG VTS.Alm
&
50PVT.StA
SET Ia>[50PVT.I_Set]
&
50PVT.StB
SET Ib>[50PVT.I_Set]
&
50PVT.StC
SET Ic>[50PVT.I_Set]
& Timer
t
>=1
& 50PVT.Op
[50PVT.t_Op] 0
SET [50PVT.Opt_Curve]=DefTime
SIG 50GVT.En1
&
SIG 50GVT.En2 &
50GVT.On
EN [50GVT.En]
SIG 50GVT.Blk
&
SIG FD.Pkp
&
SET 3I0>[50GVT.3I0_Set] 50GVT.St
SIG VTS.Alm
& Timer
t
>=1
& 50GVT.Op
[50GVT.t_Op] 0
SET [50GVT.Opt_Curve]=DefTime
3.15.6 Settings
Table 3.15-3 Settings of overcurrent protection for VT circuit failure
Residual current SOTF (switch onto fault) protection is a complementary function to earth fault
protection. With residual current SOTF protection, a fast trip is achieved for a fault on the line,
when the line is being energized. It shall be responsive to all types of earth faults anywhere within
the protected line, and it shall be enabled for the setting [SOTF.t_En] when the circuit is energized
either manually or via an auto-reclosing system.
Residual current SOTF protection will operate to trip three-phase circuit breaker with a time delay of
[50GSOTF.t_Op_3P] when 3-pole auto-reclosing or closing manually.
50GSOTF
50GSOTF.En1 50GSOTF.On
50GSOTF.En2 50GSOTF.Op
50GSOTF.Blk 50GSOTF.St
3.16.5 Logic
EN [50GSOTF.En]
3.16.6 Settings
Table 3.16-2 Settings of residual current SOTF protection
Abnormal high voltages often occur e.g. in low loaded, long distance transmission lines, in
islanded systems when generator voltage regulation fails, or load rejection of a generator. Even if
compensation reactors are provided to avoid line overvoltage by compensation of the line
capacitance and thus reduction of the overvoltage, the overvoltage will endanger the insulation if
the reactors fail. The line must be de-energized within a very short time.
The overvoltage protection in this device detects the phase voltages Ua, Ub and Uc or the
phase-to-phase voltages Uab, Ubc and Uca with an option of any phase or all phases operation
for output. The overvoltage protection can be used for tripping purpose as well as to initiate
transfer trip, which selectable controlled by local circuit breaker.
1. Three stages phase overvoltage protection with independent logic, voltage and time delay
settings.
4. “1-out-of-3” or “3-out-of-3” logic can be selected for protection criterion. (1-out-of-3 means any
1. Operation Criterion
Users can select phase voltage or phase-to-phase voltage for the protection calculation. If setting
[59Pi.Opt_Up/Upp] is set to “0”, phase voltage criterion is selected and if [59Pi.Opt_Up/Upp] is set
to “1”, phase-to-phase voltage criterion is selected.
When phase voltage or phase-to-phase voltage is greater than any enabled stage voltage setting,
the stage protection picks up and operates after delay, which will drop off instantaneously when
fault voltage disappears.
Two operation criteria of definite-time overvoltage protection are shown as follows, which of them
is applied depending on the logic setting [59Pi.Opt_1P/3P].
or
Where:
When [59Pi.Opt_1P/3P] is set as “1”, “1-out-of-3” logic (Equation 3.17-1) is selected as operation
criterion, and when set as “0”, “3-out-of-3” logic (Equation 3.17-2) is selected.
Two operation criteria of definite-time overvoltage protection are shown as follows, which of them
is applied depending on the logic setting [59Pi.Opt_1P/3P].
or
When [59Pi.Opt_1P/3P] is set as “1”, “1-out-of-3” logic (Equation 3.17-3) is selected as operation
criterion, and when set as “0”, “3-out-of-3” logic (Equation 3.17-4) is selected.
2. Characteristic Curve
Equation 3.17-5
Where:
K is a constant.
C is a constant.
α is a constant.
When inverse-time characteristic is selected, if calculated operating time is less than setting
[59Pi.tmin], then the operating time changes to the value of setting [59Pi.tmin] automatically.
59Pi
59Pi.En1 59Pi.On
59Pi.En2 59Pi.St
59Pi.Blk 59Pi.St1
59Pi.St2
59Pi.St3
59Pi.Op
59Pi.Alm
59Pi.Op_InitTT
3.17.1.5 Logic
EN [59Pi.En]
&
SIG 59Pi.En1 &
59Pi.On
SIG 59Pi.En2
SIG 59Pi.Blk
SIG 52b_PhA
&
SIG 52b_PhB & &
SIG 52b_PhC
>=1
59Pi.Op_InitTT
EN [59Pi.En_52b_TT]
&
EN [59Pi.En_TT]
EN [59Pi.Opt_1P/3P]
SIG 59Pi.On
EN [59Pi.Opt_Up/Upp] Timer
& & t
>=1 t
&
SET UA>[59Pi.U_Set] &
&
SET UAB>[59Pi.U_Set]
Timer
& & t
>=1 t
SET UB>[59Pi.U_Set]
&
SET UBC>[59Pi.U_Set]
>=1 >=1
Timer
& & t
&
>=1 t
SET UC>[59Pi.U_Set]
& 59Pi.St1
&
59Pi.Op
59Pi.St2
SET UCA>[59Pi.U_Set]
59Pi.St3
EN [59Pi.En_Alm] &
59Pi.Alm
SIG 59Pi.St1
>=1
SIG 59Pi.St2 59Pi.St
SIG 59Pi.St3
Where:
i=1, 2, 3
3.17.1.6 Settings
59Q
59Q.En1 59Q.On
59Q.En2 59Q.Op
59Q.Blk 59Q.St
3.17.2.4 Logic
SIG 59Q.En1
&
SIG 59Q.En2 &
59Q.On
EN [59Q.En]
SIG 59Q.Blk
[59Q.t_Op] 59Q.Op
&
59Q.St
SET U2>[59Q.U_Set]
3.17.2.5 Settings
The undervoltage protection can be applied to trip when fault occurs in a system. Two stages of
undervoltage protection are available measuring phase voltages U A, UB and UC or phase-to-phase
voltages UAB, UBC and UCA. The protection output can be selected for either any phase or all
phases operation. The undervoltage protection is normally used as decoupling system rather than
load shedding.
1. Three stages phase undervoltage protection with independent logic, voltage and time delay
settings.
4. “1-out-of-3” or “3-out-of-3” logic can be selected for protection criterion. (1-out-of-3 means any
of three phase voltages, 3-out-of-3 means all three phase voltages)
1. Operation Criterion
Users can select phase voltage or phase-to-phase voltage for the protection calculation. If setting
[27Pi.Opt_Up/Upp] is set to “0”, phase voltage criterion is selected and if [27Pi.Opt_Up/Upp] is set
to “1”, phase-to-phase voltage criterion is selected.
When phase voltage or phase-to-phase voltage is less than any enabled stage voltage setting, the
stage protection picks up and operates after delay, which will drop off instantaneously when fault
voltage disappears.
Two operation criteria of definite-time undervoltage protection are shown as follows, which of them
is applied depending on the logic setting [27Pi.Opt_1P/3P].
or
Where:
When [27Pi.Opt_1P/3P] is set as “1”, “1-out-of-3” logic (Equation 3.17-6) is selected as operation
criterion, and when set as “0”, “3-out-of-3” logic (Equation 3.17-7) is selected.
Two operation criteria of definite-time undervoltage protection are shown as follows, which of them
is applied depending on the logic setting [27Pi.Opt_Up/Upp].
or
Where:
When the setting [27Pi.Opt_1P/3P] is set as “1”, “1-out-of-3” logic (Equation 3.17-8) is selected as
operation criterion, and when it is set as “0”, “3-out-of-3” logic (Equation 3.17-9) is selected.
2. Characteristic Curve
Equation 3.17-10
Where:
K is a constant.
C is a constant.
α is a constant.
When inverse-time characteristic is selected, if calculated operating time is less than setting
[27Pi.tmin], then the operating time changes to the value of setting [27Pi.tmin] automatically.
Define-time or inverse-time phase under voltage protection drops off instantaneously when
measured voltage is higher than reset voltage.
27Pi
27Pi.En1 27Pi.On
27Pi.En2 27Pi.Alm
27Pi.Blk 27Pi.Op
27Pi.St
27Pi.St1
27Pi.St2
27Pi.St3
27Pi.U_Absent
3.17.3.5 Logic
In order to prevent undervoltage protection from undesired operation, after the device powered on,
if any phase current is greater than 0.06In or circuit breaker is in closed posion, undervoltage
protection will be in service with a time delay of 100ms when the corresponding phase voltage is
greater than 0.1Un. Otherwise, undervoltage protection will be blocked by the signal
“27Pi.U_Absent”
When the setting [27Pi.En_FD_Ctrl] is set as “1”, undervoltage protection will be blocked if FD
element reflecting current does not operate.
When the setting [27Pi.En_Curr_Ctrl] is set as “1”, undervoltage protection will be blocked if
current condition (>0.06In) is not met.
When the setting [27Pi.En_VTS_Blk] is set as “1”, undervoltage protection will be blocked if VT
circuit fails.
If any phase of circuit breaker is open (binary input of normal close contact of breaker is energized)
and the corresponding phase current is smaller than 0.06In, undervoltage protection will be
blocked.
EN [27Pi.En_VTS_Blk]
SIG 27Pi.U_Absent
EN [27Pi.En]
&
SIG 27Pi.En1 &
27Pi.On
SIG 27Pi.En2
SIG 27Pi.Blk
&
>=1
UV_PhAB_Curr_Rls
&
>=1
UV_PhBC_Curr_Rls
&
>=1
UV_PhCA_Curr_Rls
EN [27Pi.En_Curr_Ctrl]
EN [27Pi.En_Alm]
SET [27Pi.Opt_1P/3P]
SIG 27Pi.On
SIG Block UV
SET [27Pi.Opt_Up/Upp]
& & Timer &
t
SIG UV_PhA_Curr_Rls >=1 &
t
SET UA<[27Pi.U_Set]
&
SIG UV_PhB_Curr_Rls
SET UAB<[27Pi.U_Set]
Timer &
& &
t 27Pi.Op
SIG UV_PhC_Curr_Rls >=1
t
SET UB<[27Pi.U_Set]
&
&
>=1 27Pi.Alm
SIG UV_PhAB_Curr_Rls
&
SET UBC<[27Pi.U_Set] >=1
& & Timer
t
SIG UV_PhBC_Curr_Rls >=1
t
SET UC<[27Pi.U_Set]
27Pi.St1
&
27Pi.St2
SIG UV_PhCA_Curr_Rls
27Pi.St3
SET UCA<[27Pi.U_Set] >=1
27Pi.St
i=1, 2, 3
3.17.3.6 Settings
If the power frequency of regional rises due to the active power excess demand, overfrequency
protection operates to perform generator rejection to shed part of the generators automatically
according to the rising frequency so that power supply and the load are re-balanced.
The device provides four stages overfrequency protection. When system frequency is greater than
the setting [81O.f_Pkp], overfrequency protection will put into service.
If the positive voltage U1<0.15Un, the calculation of protection is not carried out and the output
relay will be blocked.
Where:
f is system frequency.
81O.OFi
81O.En1 81O.OFi.On
81O.En2 81O.St
81O.Blk 81O.OFi.Op
3.18.1.5 Logic
SIG 81O.St2
>=1
SIG 81O.St3 >=1 81O.St
SIG 81O.St4
SIG 81O.En1
&
SIG 81O.En2 &
81O.OFi.On
EN [81O.OFi.En]
SIG 81O.Blk
&
SIG FD.Pkp
EN [81O.OFi.En]
i=1, 2, 3, 4
3.18.1.6 Settings
In case of frequency decline due to lack of active power in the power system, underfrequency
protection operates to shed part of the load according to the declined value of frequency to
re-balance the power supply and the load.
The device provides four stages underfrequency protection. When system frequency is smaller
than the setting [81U.f_Pkp], underfrequency protection will put into service.
If the positive voltage U1<0.15Un, the calculation of protection is not carried out and the output
relay will be blocked.
If -df/dt≥[81U.df/dt_Blk], the calculation of protection is not carried out and the output relay will
be blocked. The blocking element will not be released automatically until the system frequency
recovers to be less than the setting [81U.f_Pkp].
Where:
f is system frequency.
Where:
df/dt is the frequency slip speed and the time step (i.e. dt) for the calucation is equal to 5 cycle.
Underfrequency protection can be blocked by the frequency slip speed (df/dt). If the logic setting
[81U.UFi.En_df/dt_Blk] is set as “1”, when Equation 3.18-2 and Equation 3.18-3 are met, it is
decided that a fault occurred and the corresponding stage underfrequency protection is blocked at
the same time for the purpose of waiting for operation of other related protection. The blocking
signal will not reset until the system frequency recovers, i.e. the system frequency is greater than
the setting [81U.f_Pkp]. If the logic setting is set as “0”, when Equation 3.18-2 and Equation 3.18-3
are met, the stage underfrequency protection will be released to operate.
81U.UFi
81U.En1 81U.UFi.On
81U.En2 81U.St
81U.Blk 81U.UFi.Op
3.18.2.5 Logic
SIG 81U.St2
>=1
SIG 81U.St3 >=1 81U.St
SIG 81U.St4
SIG 81U.En1
&
SIG 81U.En2
EN [81U.UFi.En]
&
81U.UFi.On
SIG 81U.Blk
&
SIG FD.Pkp &
SIG U1<0.15Un >=1
EN [81U.UFi.En]
i=1, 2, 3, 4
3.18.2.6 Settings
Duplicated protection configurations are usually adopted for EHV power system, but the primary
equipment, circuit breaker, is not duplicated. Breaker failure protection is adopted to cater circuit
breaker tripping failure.
Breaker failure protection issues a back-up trip command to trip adjacent circuit breakers in case
of a tripping failure of the circuit breaker, and clears the fault as requested by the device. To utilize
the protection information of faulty equipment and the electrical information of failure circuit
breaker to constitute the criterion of breaker failure protection, it can ensure that the adjacent
circuit breakers of failure circuit breaker are tripped with a shorter time delay, so that the affected
area is minimized, and ensure stable operation of the entire power grid to prevent generators,
transformers and other components from seriously damaged.
NOTICE!
For double circuit breakers mode, the device will provide independent breaker failure
protection for CB1 and CB2 respectively. Both breaker failure protections have the
same logic.The difference is that the prefix “CBx.” is added to all signals and settings for
circuit breaker No.x (x=1 or 2).
When both the phase-segregated tripping contact from line protection and the corresponding
phase overcurrent element operate, or both the three-phase tripping contact and any phase
overcurrent element operate, breaker failure protection will send three-phase tripping command to
trip local circuit breaker after time delay of [CBx.50BF.t1_Op] and trip all adjacent circuit breakers
after time delay of [CBx.50BF.t2_Op].
When the protection element except undervoltage element within this device operates and issues
tripping signal, breaker failure protection will also be initiated.
Taking into account that the faulty current is too small for generator or transformer fault, the
sensitivity of phase current element may not meet the requirements, zero-sequence current
criterion and negative-sequence current criterion are provided in addition to the phase overcurrent
element for breaker failure protection initiated by input signal [CBx.50BF.ExTrp3P_GT] from
generator and transformer protection. They can be enabled or disabled by logic settings
[CBx.50BF.En_3I0_3P] and [CBx.50BF.En_I2_3P] respectively.
For some special fault (for example, mechanical protection or overvoltage protection operating),
maybe faulty current is very small and current criterion of breaker failure protection is not met, in
order to make breaker failure protection can also operate under the above situation, an input
signal [CBx.50BF.ExTrp_WOI] is equipped to initiate breaker failure protection, once the input
signal is energized, normally closed auxiliary contact of circuit breaker is chosen in addition to
breaker failure current check to trigger breaker failure timer. The device takes current as priority
with CB auxiliary contact (52b) as an option criterion for breaker failure check.
50BF
CBx.50BF.ExTrp3P_L CBx.50BF.On
CBx.50BF.ExTrp3P_GT CBx.50BF.Op_ReTrpA
CBx.50BF.ExTrp_WOI CBx.50BF.Op_ReTrpB
CBx.50BF.ExTrpA CBx.50BF.Op_ReTrpC
CBx.50BF.ExTrpB CBx.50BF.Op_ReTrp3P
CBx.50BF.ExTrpC CBx.50BF.Op_t1
CBx.50BF.En CBx.50BF.Op_t2
CBx.50BF.Blk
3.19.5 Logic
SIG CBx.50BF.En
&
EN [CBx.50BF.En] CBx.50BF.On
SIG CBx.50BF.Blk
SIG CBx.50BF.On
&
SIG FD.Pkp
EN [CBx.50BF.En_ReTrp]
EN [CBx.50BF.En_3I0_1P] >=1
SET 3I0>[CBx.50BF.3I0_Set]
&
SIG CBx.BFI_A >=1 & [CBx.50BF.t_ReTrp] 0ms CBx.50BF.Op_ReTrpA
BI [CBx.50BF.ExTrpA]
SET IA>[CBx.50BF.I_Set]
&
SIG CBx.BFI_B >=1 & [CBx.50BF.t_ReTrp] 0ms CBx.50BF.Op_ReTrpB
BI [CBx.50BF.ExTrpB]
SET IB>[CBx.50BF.I_Set]
&
SIG CBx.BFI_C >=1 & [CBx.50BF.t_ReTrp] 0ms CBx.50BF.Op_ReTrpC
BI [CBx.50BF.ExTrpC] >=1
BI [CBx.50BF.ExTrp_WOI]
&
EN [CBx.50BF.En_3I0_3P] &
SET 3I0>[CBx.50BF.3I0_Set]
& >=1 >=1 [CBx.50BF.t1_Op] 0ms CBx.50BF.Op_t1
EN [CBx.50BF.En_I2_3P] & &
[CBx.50BF.t2_Op] 0ms CBx.50BF.Op_t2
SET I2>[CBx.50BF.I2_Set]
&
EN [CBx.50BF.En_CB_Ctrl]
BI [CBx.52b_PhA]
&
BI [CBx.52b_PhB]
BI [CBx.52b_PhC]
SIG FD.Pkp
3.19.6 Settings
Table 3.19-2 Settings of breaker failure protection
During overload operation of a transmission line (specially for cable), great current results in
greater heat to lead temperature increase and if the temperature reaches too high values the
equipment might be damaged.
Thermal overload protection estimates the internal heat content (temperature) continuously. This
estimation is made by using a thermal model with two time constants, which is based on current
measurement.
When the temperature increases to the alarm value, the protection issues alarm signals to remind
the operator for attention, and if the temperature continues to increase to the trip value, the
protection sends trip command to disconnect the protected line.
Two stages for alarm purpose and two stages for trip purpose
The device provides a thermal overload model which is based on the IEC60255-8 standard. The
thermal overload formulas are shown as below.
Where:
ln = Natural logarithm
t Refer to IEC60255-8
Ip
P=—
IB
P = 0.0
P = 0.6
P = 0.8
P = 0.9
kIB I
The hot start characteristic is adopted in the device. The calculation is carried out at zero of Ip, so
users need not to set the value of Ip.
Tripping outputs of the protection is controlled by current, even if the thermal accumulation value is
greater than the setting for tripping, the protection drops off instantaneously when current
disappears. Alarm outputs of the protection is not controlled by current, and only if the thermal
accumulation value is greater than the setting for alarm, alarm output contacts, which can be
connected to block the auto-reclosure, will operate.
49
49.Clr_Cmd 49.On
49.En 49.St
49.Blk 49-i.Alm
49-i.Op
3.20.5 Logic
EN [49-i.En_Trp] >=1
EN [49-i.En_Alm]
&
SIG FD.Pkp 49.St
& Timer
t
49-i.Op
t
SIG I3P
& Timer
t
49-i.Alm
SET [49.Ib_Set]
t
BI [49.Clr_Cmd]
i=1, 2
3.20.6 Settings
Table 3.20-2 Settings of thermal overload protection
Stub differential protection is mainly designed for one and a half breakers arrangement. When line
disconnector is open and transmission line is put into maintenance, line VT is no voltage. Distance
protection is disabled, and stub differential protection is enabled. It is used to protect stub section
among two circuit breakers and line disconnector. Usually, stub differential protection is enabled
automatically by normally closed auxiliary contact of line disconnector.
CT1 CT2
Bus Bus
To the device
Line Line
Stub differential element is composed of percentage differential principle. Stub differential element
can be controlled by normally closed auxiliary contact of line disconnector to enabled or disabled.
The normally closed auxiliary contact of line disconnector is closed when line disconnector is open.
The operation criterion is:
I 1 I 2 [87STB.I_Pkp]
I I
1 2 [87STB.Slop e] I 1 I 2
Where:
I 1 、 I 2 are secondary phase currents corresponding to both circuit breakers, are formed by
phase A, B, C
Under normal conditions, when stub differential protection is enabled, the device will issue the
alarm signal [87STB.Alm_Diff] with the time delay if the following operation criterion is met.
I 1 I 2 [87STB.I_Al m]
I I
1 2 0.15 I 1 I 2
The device will issue the alarm signal [87STB.Alm_89b_DS] with the time delay of 10s if the signal
[87STB.89b_DS] is energized and the line is live, and the alarm signal will drop off with the time
delay of 10s after the abnormality disappears.
When the alarm signal of disconnector position appears, the operator should confirm the status of
disconnector position in time. The user can use programable logic to determine whether the
disconnector position alarm will blocked stub differential protection.
3.21.2.4 CT Saturation
When there is an external fault, transient CT saturation may be happened. In order to prevent stub
differential protection from undesired operation, the floating technology of adaptive restraint
current is adopted to ensure that the device does not maloperate due to the serious saturation.
87STB
87STB.En1 87STB.On
87STB.En2 87STB.On_Local
87STB.Blk 87STB.Op
87STB.89b_DS 87STB.St
87STB.89b_DS_Rmt 87STB.StA
87STB.StB
87STB.StC
87STB.Alm_Diff
87STB.Alm_89b_DS
3.21.5 Logic
Based on calculating vector summation of currents from dual CTs, the logic scheme of stub
differential protection is shown as Figure 3.21-2.
SIG 87STB.En1
&
SIG 87STB.En2 &
Enable 87STB
EN [87STB.En]
SIG 87STB.Blk
SIG 87STB.89b_DS_Rmt
&
SET Idiffa>[87STB.I_Alm] &
SET IdiffA>0.15×IBiasA
& >=1
SET Idiffb>[87STB.I_Alm] & &
10s 10s 87STB.Alm_Diff
SET IdiffB>0.15×IBiasB
&
SET Idiffc>[87STB.I_Alm] &
SET IdiffC>0.15×IBiasC
EN [87STB.En_Alm]
SET IdiffA>[87STB.Slope]×IBiasA
&
SET Idiffb>[87STB.I_Pkp] & 87STB.StB
SET IdiffB>[87STB.Slope]×IBiasB
&
SET Idiffc>[87STB.I_Pkp] & 87STB.StC
SET IdiffC>[87STB.Slope]×IBiasC
3.21.6 Settings
Table 3.21-2 Settings of stub differential protection
NOTICE!
For double circuit breakers mode, the device will provide independent dead zone
protection for CB1 and CB2 respectively. Both dead zone protections have the same
logic.The difference is that the prefix “CBx.” is added to all signals and settings for
circuit breaker No.x (x=1 or 2).
The criterion for dead zone protection is: when dead zone protection is enabled, binary input of
initiating dead zone protection is energized (by default, three-phase tripping signal is used to
initiate dead zone protection), if overcurrent element for dead zone protection operates, then
corresponding circuit breaker is tripped and three phases normally closed contact of the circuit
breaker are energized, dead zone protection will operate to trip adjacent circuit breaker after a
time delay.
50DZ
CBx.50DZ.En1 CBx.50DZ.On
CBx.50DZ.En2 CBx.50DZ.Op
CBx.50DZ.Blk CBx.50DZ.St
CBx.50DZ.Init
3.22.5 Logic
EN [CBx.50DZ.En]
&
SIG CBx.50DZ.En1 &
CBx.50DZ.On
SIG CBx.50DZ.En2
SIG CBx.52b_PhA
&
SIG CBx.52b_PhB
SIG CBx.52b_PhC
SIG CBx.Trp
3.22.6 Settings
Table 3.22-2 Settings of dead zone protection
The pole discrepancy of circuit breaker may occur during operation of a breaker with segregated
operating gears for the three phases. The reason could be an interruption in the tripping/closing
circuits, or mechanical failure. A pole discrepancy can only be tolerated for a limited period. When
there is loading, zero-sequence or negative-sequence current will be generated in the power
system, which will result in overheat of the generator or the motor. With the load current increasing,
overcurrent elements based on zero-sequence current or negative-sequence current may operate.
Pole discrepancy protection is required to operate before the operation of these overcurrent
elements.
NOTICE!
For double circuit breakers mode, the device will provide independent pole discrepancy
protection for CB1 and CB2 respectively. Both pole discrepancy protections have the
same logic.The difference is that the prefix “CBx.” is added to all signals and settings for
circuit breaker No.x (x=1 or 2).
Pole discrepancy protection determines three-phase breaker pole discrepancy condition by its
phase segregated CB auxiliary contacts. In order to improve the reliability of pole discrepancy
protection, the asymmetrical current component can be selected as addition criteria when needed.
62PD
CBx.62PD.En1 CBx.62PD.On
CBx.62PD.En2 CBx.62PD.Op
CBx.62PD.Blk CBx.62PD.St
3.23.5 Logic
Phase-segregated circuit breaker auxiliary contacts are connected to the device. When the state
of three phase-segregated circuit breaker auxiliary contacts are inconsistent, pole discrepancy
protection will be started and initiate output after a time delay [CBx.62PD.t_Op].
Pole discrepancy protection can be blocked by external input signal [62PD.Blk]. In general, this
input signal is usually from the output of 1-pole AR initiation, so as to prevent pole discrepancy
protection from operation during 1-pole AR initiation.
SIG CBx.62PD.En1
&
SIG CBx.62PD.En2 &
62PD.On
EN [CBx.62PD.En]
SIG CBx.62PD.Blk
&
SIG FD.Pkp
EN [CBx.62PD.En_3I0/I2_Ctrl] >=1
SET 3I0>[CBx.62PD.3I0_Set] >=1
SET I2>[CBx.62PD.I2_Set]
BI [CBx.52b_PhB] &
SIG CBx.Ib<0.06In
>=1
BI [CBx.52b_PhC] &
SIG CBx.Ic<0.06In
Where:
3.23.6 Settings
Table 3.23-2 Settings of pole discrepancy protection
The network of single-phase broken condition is similar to that of two-phases earthing fault,
positive-sequence, negative-sequence and zero-sequence network is connected in parallel, I2/I1=
Z0/(Z0+Z2), generally, zero-sequence impedance is larger than positive-sequence impedance, i.e.
I2/I1>0.5. The network of two-phases broken condition is similar to that of single-phase earthing
fault, positive-sequence, negative-sequence and zero-sequence network is connected in series,
so I2/I1=1.
46BC
46BC.En1 46BC.On
46BC.En2 46BC.St
46BC.Blk 46BC.Op
46BC.Alm
3.24.5 Logic
SIG [46BC.En2]
& 46BC.On
SET Ic>[46BC.I_Min]
SET I2/I1>[46BC.I2/I1_Set]
&
46BC.Op
SET [46BC.En_Trp]
&
46BC.Alm
SET [46BC.En_Alm]
3.24.6 Settings
Table 3.24-2 Settings of broken conductor protection
Due to various reasons lead to lose motivity, synchronous generator is changed to run as a motor
state, Absorbing energy from the power grid to drive a turbine (gas turbine) operation. In order to
prevent turbine blade or gas turbine gear from being damaged, reverse power protection (reversal
direction) should be configured.
Reverse power protection provides two stages: stage 1 can be set as alarm purpose or tripping
purpose, and stage 2 is only for tripping purpose. When reverse power value of the generator
detected is greater than reverse power protection setting ([32R1.P_Set]), reverse power protection
can operate to alarm or trip with the time delay. After overload protection, over-excitation
protection or loss-of-excitation protection, such as abnormal operation protection operates, the
generator needs sequential tripping. The steam valve of turbine has to be closed firstly, and
sequential tripping reverse power protection blocked by position contact of steam valve and circuit
breaker operates to trip with the time delay.
The level of generator absorbing the active power will depend on the need to overcome the friction
loss, according to different types of generator units, the settings of reverse power protection will be
different. During testing in the primary side of the generator unit, the active power absorbed by the
generator can be measured by the device.
When the device is equipped with power plant side, reverse power is negative value, and reverse
power is positive value when it is equipped with substation side.
or
32R
32Ri.En P1
32Ri.Blk 32Ri.On
32Ri.St
32Ri.Op
32R1.Alm
3.25.5 Logic
SIG 32R1.Blk
&
EN [32R1.En_Alm] >=1 32R1.On
EN [32R1.En_Trp]
SIG 32R1.On
SIG P1<-[32R1.P_Set]
&
>=1 32R1.St
SET [32R.Opt_Dir]=Forward &
SIG P1>[32R1.P_Set]
&
[32R1.t_Alm] 0s 32R1.Alm
EN [32R1.En_Alm]
&
[32R1.t_Trp] 0s 32R1.Op
EN [32R1.En_Trp]
SIG 32R2.Blk
&
32R2.On
EN [32R2.En_Trp]
SIG P1>[32R2.P_Set]
&
[32R2.t_Trp] 0s 32R2.Op
EN [32R2.En_Trp]
When stage 2 of reverse power protection is used as sequential tripping reverse power protection,
it can be selectable to be controlled by position contact of steam valve and circuit breaker
3.25.6 Settings
Table 3.25-2 Settings of broken conductor protection
3.26 Synchrocheck
3.26.1 General Application
The purpose of synchrocheck is to ensure two systems are synchronism before they are going to
be connected.
When two asynchronous systems are connected together, due to phase difference between the
two systems, larger impact will be led to the system during closing. Thus auto-reclosing and
manual closing are applied with the synchrocheck to avoid this situation and maintain the system
stability. The synchrocheck includes synchronism check and dead charge check.
NOTICE!
For double circuit breakers mode, the device will provide independent synchrocheck
function for CB1 and CB2 respectively. Both synchrocheck functions have the same
logic.The difference is that the prefix “CBx.” is added to all signals and settings for
circuit breaker No.x (x=1 or 2).
of the circuit breaker and compares them with the corresponding settings. The output is only given
if all measured quantities are simultaneously within their set limits.
The dead charge check function measures the amplitude of line voltage and bus voltage between
both sides of the circuit breaker, and then compare them with the live check setting [CBx.25.U_Lv]
and the dead check setting [CBx.25.U_Dd]. The output is only given when the measured
quantities comply with the criteria.
The synchrocheck in this device can be used for auto-reclosing and manual closing for both single
circuit breaker and dual circuit breakers. When applied for single circuit breaker, the comparison
relationship between reference voltage (CBx.Uref) and synchronism voltage (CBx.Usyn) for
synchronism check is as shown in Figure 3.26-1.
CBx.Uref CBx.Usyn
When both line and busbar are live, the synchronism check element operates if voltage difference,
phase angle difference and frequency difference are all within their setting values.
CBx.Usyn≥[CBx.25.U_Lv]
CBx.Uref≥[CBx.25.U_Lv]
[CBx.25.U_Diff]≥|CBx.Usyn-CBx.Uref|
CBx.Usyn×CBx.Uref×cosØ≥0
CBx.Usyn×CBx.Uref×sin([CBx.25.phi_Diff])≥CBx.Usyn×CBx.Uref×|sinØ|
Where,
|f(CBx.Usyn)-f(CBx.Uref)|≤[CBx.25.f_Diff]
If frequency check is disabled (i.e. [CBx.25.En_fDiffChk] is set as “0”), a detected maximum slip
cycle can also be determined by the following equation based on phase difference setting and the
f =[CBx.25.phi_Diff]/(180×[CBx.25.t_SynChk])
Where:
f is slip cycle
This function module supports voltage switching. In general, voltage switching is fulfilled by
external circuit, and the busbar arrangement should be determined, including three options, single
busbar arrangement, double busbars arrangement and 1½ breakers arrangement, if using this
module to fulfill voltage switching.
Analog input defines four voltage inputs, UL1, UB1, UL2, UB2, and their usage are as follow:
UL1: it connects with three-phase protection voltages (from line or busbar), which mainly are used
by distance protection, voltage protection and so on.
UL2: it connects with single synchronism voltage (from the other line of the same diameter in 1½
breakers arrangement). When voltage switching is available, it is only used by 1½ breakers
arrangement.
UB2: it connects with single synchronism voltage (from busbar). When voltage switching is
available, it is only used by double busbars arrangement and 1½ breakers arrangement.
The reference voltage (Uref) is determined to use phase voltage or phase-to-phase voltage (UL1)
from three-phase protection voltages and by the setting [CBx.25.Opt_Source_UL1].
The synchronism voltage (Usyn) always connects with UB1 if not adopting voltage switching. It
connects with one of UB1, UL2 and UB2 according to the result of voltage switching if adopting
voltage switching.
Voltage selection function is not required for this busbar arrangement, the connection of the
voltage signals and respective VT MCB auxiliary contacts to the device is shown in the Figure
3.26-2 and Figure 3.26-3.
Bus
Ua
UL1 Ub CB
Uc
25.MCB_VT_UL1
UB1
25.MCB_VT_UB1
Line
Bus
UB1 CB
25.MCB_VT_UB1
Ua
UL1 Ub
Uc
25.MCB_VT_UL1 Line
In the figures, the setting [VTS.En_LineVT] is used to determine protection voltage signals (Ua, Ub,
Uc) from line VT or bus VT according to the condition.
Bus2
Bus1
B1D B2D
UB1
25.MCB_VT_UB1
UB2
25.MCB_VT_UB2
25.NC_UB1DS
25.NO_UB1DS CB
25.NC_UB2DS
25.NO_UB2DS
Ua
UL1 Ub
Line
Uc
25.MCB_VT_UL1
For double busbars arrangement, selection of appropriate voltage signals from Bus 1 and Bus 2
for synchronizing are required. Line VT signal is taken as reference to check synchronizing with
the voltage after voltage selection function. Selection approach is as follows.
For the disconnector positions, the normally open (NO) and normally closed (NC) contacts of the
disconnector for bus 1 and bus 2 are required to determine the disconnector open and closed
positions. The voltage selection logic is as follows.
BI 25.NC_UB1DS &
Voltage Selection Logic
CBx.UB1_Sel
BI 25.NO_UB1DS
BI 25.NC_UB2DS &
CBx.UB2_Sel
BI 25.NO_UB2DS
&
CBx.Alm_Invalid_Sel
UB1 CBx.Usyn
UB2
After acquiring the disconnector open and closed positions of double busbars, use the following
logic to acquire the feeder voltage of double busbars.
For one and a half breakers arrangement, selection of appropriate voltage signals among Line1
VT, Line2 VT and Bus 2 VT as reference voltage to check synchronizing with Bus 1 voltage signal
for closing breaker at Bus 1 side.
Bus1
UB1
25.MCB_VT_UB1
25.NC_UB1DS
B1D
25.NO_UB1DS
Ua Line 1
UL1 Ub
Uc
25.MCB_VT_UL1
L1D
25.NC_UL1DS
25.NO_UL1DS
Line 2
UL2
25.MCB_VT_UL2
25.NC_UL2DS
25.NO_UL2DS
L2D
25.NC_UB2DS
25.NO_UB2DS
UB2
25.MCB_VT_UB2
B2D
Bus2
Figure 3.26-6 Voltage connection for one and a half breakers arrangement
For the circuit breaker at bus side (take bus breaker of bus 1 as an example), the device acquires
the disconnector open and closed positions of two feeders and bus 2. The voltage selection logic
is as follows.
BI 25.NC_UL1DS &
CBx.UL1_Sel
BI 25.NO_UL1DS
&
BI 25.NC_UL2DS & CBx.UL2_Sel
BI 25.NO_UL2DS
&
BI 25.NC_UB2DS & CBx.UB2_Sel
BI 25.NO_UB2DS
&
CBx.Alm_Invalid_Sel
UL1 CBx.Uref
UL2
UB2
UB1 CBx.Usyn
Figure 3.26-7 Voltage selection for one and a half breakers arrangement
For the tie breaker, the device acquires the disconnector open and closed positions of two feeders
and two busbars. Either Line 1 VT or Bus 1 VT signal is selected as reference voltage to check
synchronizing with the selected voltage between Line 2 VT and Bus 2 VT. The voltage selection
logic is as follows.
BI 25.NC_UL1DS &
CBx.UL1_Sel
BI 25.NO_UL1DS
&
BI 25.NC_UB1DS & CBx.UB1_Sel
BI 25.NO_UB1DS
&
UL1 CBx.Uref
UB1
BI 25.NC_UL2DS &
CBx.UL2_Sel
BI 25.NO_UL2DS
&
BI 25.NC_UB2DS & CBx.UB2_Sel
BI 25.NO_UB2DS
>=1
& CBx.Alm_Invalid_Sel
UL2 CBx.Usyn
UB2
Figure 3.26-8 Voltage selection for one and a half breakers arrangement
When the voltage selection fails (including VT circuit failure and MCB failure), the device will issue
the corresponding failure signal. If the voltage selection is invalid (CBx.Alm_Invalid_Sel=1), keep
original selection and without switchover.
In order to simplify description, one of the two voltages used in the synchrocheck (synchronism check
and dead charge check) which obtained after voltage selection function is regarded as line voltage,
and another is bus voltage.
If synchronism voltage and reference voltage are used for auto-reclosing with synchronism or
dead line or busbar check, the VT circuit of synchronism voltage and reference voltage are
monitored.
Under normal conditions, the circuit breaker is in closed position but the synchronism voltage is
lower than the setting [CBx.25.U_Lv], it means that synchronism voltage circuit fails and an alarm
[CBx.25.Alm_VTS_Usyn] or [CBx.25.Alm_VTS_Uref] will be issued with a time delay of 10s. If
MCB of synchronism voltage or reference voltage is open, an alarm [CBx.25.Alm_VTS_Usyn] or
[CBx.25.Alm_VTS_Uref] will be issued instantaneously. After synchronism voltage reverted to
normal condition, the alarm will be reset automatically with a time delay of 10s. When synchronism
voltage circuit failure is detected, dead check in auto-reclosing logic will be disabled. If the logic
setting [CBx.25.En_NoChk] is set as “1”, synchronism voltage circuit failure supervision will be
disabled.
SIG CBx.79.Inprog
&
10s 10s >=1
SIG CBx.Uref<[CBx.25.U_Lv] &
CBx.25.Alm_VTS_Uref
SIG 25.MCB_VT_Uref
SIG CBx.25.On_LvL_DdB
&
SIG CBx.25.Blk_VTS_UL
SIG CBx.79.Inprog
&
10s 10s >=1
SIG CBx.Usyn<[CBx.25.U_Lv] &
CBx.25.Alm_VTS_Usyn
SIG 25.MCB_VT_Usyn
SIG CBx.25.On_LvL_DdB
&
SIG CBx.25.Blk_VTS_UB
As shown in Figure 3.26-9 and Figure 3.26-10, 25.MCB_VT_Uref is MCB signal corresponding to
reference voltage after switching and 25.MCB_VT_Usyn is MCB signal corresponding to
synchronism voltage after switching.
25
CBx.25.Blk_Chk CBx.UL1_Sel
CBx.25.Blk_SynChk CBx.UL2_Sel
CBx.25.Blk_DdChk CBx.UB1_Sel
CBx.25.Start_Chk CBx.UB2_Sel
CBx.25.Start_3PLvChk CBx.Alm_Invalid_Sel
CBx.25.Sel_SynChk CBx.25.Ok_fDiffChk
CBx.25.Sel_DdL_DdB CBx.25.Ok_UDiffChk
CBx.25.Sel_DdL_LvB CBx.25.Ok_phiDiffChk
CBx.25.Sel_LvL_DdB CBx.25.Ok_DdL_DdB
CBx.25.Sel_NoChk CBx.25.Ok_DdL_LvB
CBx.25.Blk_VTS_Uref CBx.25.Ok_LvL_DdB
CBx.25.Blk_VTS_Usyn CBx.25.Chk_LvL
25.MCB_VT_UL1 CBx.25.Chk_DdL
25.MCB_VT_UL2 CBx.25.Chk_LvB
25.MCB_VT_UB1 CBx.25.Chk_DdB
25.MCB_VT_UB2 CBx.25.Ok_DdChk
25.NC_UL1DS CBx.25.Ok_SynChk
25.NO_UL1DS CBx.25.Ok_Chk
25.NC_UB1DS CBx.25.Ok_3PLvChk
25.NO_UB1DS CBx.25.Alm_VTS_Uref
25.NC_UL2DS CBx.25.Alm_VTS_Usyn
25.NO_UL2DS CBx.25.f_Ref
25.NC_UB2DS CBx.25.f_Syn
25.NO_UB2DS CBx.25.U_Diff
CBx.25.f_Diff
CBx.25.Phi_Diff
3.26.5 Logic
3.26.5.1 Synchronism Check Logic
The frequency difference, voltage difference, and phase difference of voltages from both sides of
the circuit breaker are calculated in the device, they are used as input conditions of the
synchronism check. When the synchronism check function is enabled and the voltages of both
ends meets the requirements of the voltage difference, phase difference, and frequency difference,
and there is no synchronism check blocking signal, it is regarded that the synchronism check
conditions are met.
Synchronism check logic is usually used for 3-pole AR, and 1-pole AR usually adopts no check
logic. However, the circuit breaker at local end can not reclosed unless the circuit breaker at
remote end is reclosed successfully. In order to meet this requirement, live three-phase check can
be used for 1-pole AR, determined by the setting [CBx.25.En_3PLvChk], ensure that three-phase
voltages is restored to normal at local end after the circuit breaker at remote end is reclosed.
1
EN [CBx.25.En_SynChk]
CBx.25.On_SynChk
SIG CBx.25.Sel_SynChk
0
EN [CBx.25.SetOpt]
1
EN [CBx.25.En_DdL_DdB]
CBx.25.On_DdL_DdB
SIG CBx.25.Sel_SynChk
0
EN [CBx.25.SetOpt]
1
EN [CBx.25.En_LvL_DdB]
CBx.25.On_LvL_DdB
SIG CBx.25.Sel_LvL_DdB
0
EN [CBx.25.SetOpt]
1
EN [CBx.25.En_DdL_LvB]
CBx.25.On_DdL_LvB
SIG CBx.25.Sel_DdL_LvB
0
EN [CBx.25.SetOpt]
1
EN [CBx.25.En_NoChk]
CBx.25.On_NoChk
SIG CBx.25.Sel_NoChk
0
EN [CBx.25.SetOpt]
EN [CBx.25.En_3PLvChk]
SIG CBx.Uref.a>[CBx.25.U_Lv]
>=1
&
SIG CBx.Uref.b>[CBx.25.U_Lv]
SIG CBx.Uref.c>[CBx.25.U_Lv]
&
SIG CBx.25.Start_3PLvChk 200ms 0ms CBx.25.Ok_3PLvChk
SIG CBx.25.On_SynChk
&
SIG CBx.25.Start_Chk
SIG CBx.Usyn>[CBx.25.U_Lv]
& &
SIG CBx.Uref>[CBx.25.U_Lv] 50ms 0ms & [CBx.25.t_SynChk] 0ms CBx.25.Ok_SynChk
SIG CBx.25.Ok_UdiffChk
SIG CBx.25.Ok_phiDiffChk
SIG CBx.25.Ok_fDiffChk
The dead charge check conditions have three types, namely, live-bus and dead-line check,
dead-bus and live-line check and dead-bus and dead-line check. The above three modes can be
enabled and disabled by the corresponding logic settings. The device can calculate the measured
bus voltage and line voltage at both sides of the circuit breaker and compare them with the
settings [CBx.25.U_Lv] and [CBx.25.U_Dd]. When the voltage is higher than [CBx.25.U_Lv], the
bus/line is regarded as live. When the voltage is lower than [CBx.25.U_Dd], the bus/line is
regarded as dead.
SIG CBx.Usyn<[CBx.25.U_Dd]
SIG CBx.Usyn>[CBx.25.U_Lv]
SIG CBx.Usyn<[CBx.25.U_Dd]
SIG CBx.25.Alm_VTS_Uref
SIG CBx.25.Ok_SynChk
>=1
SIG CBx.25.On_NoChk CBx.25.Ok_Chk
SIG CBx.25.Ok_DdChk
3.26.6 Settings
Table 3.26-2 Synchrocheck settings
breakers
3/2TieCB: line side circuit
breaker for one and a half
breakers
To maintain the integrity of the overall electrical transmission system, the device is installed on the
transmission system to isolate faulted segments during system disturbances. Faults caused by
lightning, wind, or tree branches could be transient in nature and may disappear once the circuit is
de-energized. According to statistics, for overhead transmission line, 80%~90% of the faults on
overhead lines are the transient faults. Auto-reclosing systems are installed to restore the faulted
section of the transmission system once the fault is extinguished (providing it is a transient fault).
For certain transmission systems, auto-reclosure is used to improve system stability by restoring
critical transmission paths as soon as possible.
Besides overhead lines, other equipment failure, such as cables, busbar, transformer fault and so
on, are generally permanent fault, and auto-reclosing is not initiated after faulty feeder is tripped.
For some mixed circuits, such as overhead line with a transformer unit, hybrid transmission lines,
etc., it is required to ensure that auto-reclosing is only initiated for faults overhead line section, or
make a choice according to the situation.
NOTICE!
For double circuit breakers mode, the device will provide independent automatic
reclosure function for CB1 and CB2 respectively. Both automatic reclosure functions
have the same logic.The difference is that the prefix “CBx.” is added to all signals and
settings for circuit breaker No.x (x=1 or 2).
When external auto-reclosure is used, the device can output some configurable output to initiate
external AR, such as, contact of initiating AR, phase-segregated tripping contact, single-phase
tripping contact, three-phase tripping contact and contact of blocking AR. According to
requirement, these contacts can be selectively connected to external auto-reclosure device to
initiate AR.
For phase-segregated circuit breaker, AR mode can be 1-pole AR for single-phase fault and
3-pole AR for multi-phase fault, or always 3-pole AR for any kinds of fault according to system
requirement. For persistent fault or multi-shot AR number preset value is reached, the device will
send final tripping command. The device will provide appropriate tripping command based on
AR can be enabled or disabled by logic setting or external signal via binary input. When AR is
enabled, the device will output contact [CBx.79.On], otherwise, output contact [CBx.79.Off]. After
some reclosing conditions, such as, CB position, CB pressure and so on, is satisfied, the device
will output contact [CBx.79.Ready].
According to requirement, the device can be set as one-shot or multi-shot AR. When adopting
multi-shot AR, the AR mode of first time reclosing can be set as 1-pole AR, 3-pole AR or 1/3-pole
AR. The rest AR mode is only 3-pole AR and its number is determined by the maximum 3-pole
reclosing number.
For one-shot AR or first reclosing of multi-shot AR, AR mode can be selected by logic setting
[CBx.79.En_1PAR], [CBx.79.En_3PAR] and [CBx.79.En_1P/3PAR] or external signal via binary
inputs. When 3-pole or 1/3-pole AR mode is selected, the following three types of check modes
can be selected: dead charge check, synchronism check and no check.
79
CBx.79.En CBx.79.On
CBx.79.Blk CBx.79.Off
CBx.79.Sel_1PAR CBx.79.Close
CBx.79.Sel_3PAR CBx.79.Ready
CBx.79.Sel_1P/3PAR CBx.79.AR_Blkd
CBx.79.Trp CBx.79.Active
CBx.79.Trp3P CBx.79.Inprog
CBx.79.TrpA CBx.79.Inprog_1P
CBx.79.TrpB CBx.79.Inprog_3P
CBx.79.TrpC CBx.79.Inprog_3PS1
CBx.79.LockOut CBx.79.Inprog_3PS2
CBx.79.PLC_Lost CBx.79.Inprog_3PS3
CBx.79.WaitMaster CBx.79.Inprog_3PS4
CBx.79.CB_Healthy CBx.79.WaitToSlave
CBx.79.Clr_Counter CBx.79.Perm_Trp1P
CBx.79.Ok_Chk CBx.79.Perm_Trp3P
CBx.79.Ok_3PLvChk CBx.79.Rcls_Status
CBx.79.Fail_Rcls
CBx.79.Succ_Rcls
CBx.79.Fail_Chk
CBx.79.Mode_1PAR
CBx.79.Mode_3PAR
CBx.79.Mode_1/3PAR
0: AR is ready.
1: AR is in progress.
2: AR is successful.
18 CBx.79.Fail_Rcls Auto-reclosing fails
19 CBx.79.Succ_Rcls Auto-reclosing is successful
20 CBx.79.Fail_Chk Synchrocheck for AR fails
21 CBx.79.Mode_1PAR Output of 1-pole AR mode
22 CBx.79.Mode_3PAR Output of 3-pole AR mode
23 CBx.79.Mode_1/3PAR Output of 1/3-pole AR mode
Automatic reclosure counter
24 CBx.79.N_Total_Rcls Recorded number of all reclosing attempts
25 CBx.79.N_1PS1 Recorded number of first 1-pole reclosing attempts
26 CBx.79.N_3PS1 Recorded number of first 3-pole reclosing attempts
27 CBx.79.N_3PS2 Recorded number of second 3-pole reclosing attempts
28 CBx.79.N_3PS3 Recorded number of third 3-pole reclosing attempts
29 CBx.79.N_3PS4 Recorded number of fourth 3-pole reclosing attempts
3.27.5 Logic
3.27.5.1 AR Ready
For the first reclosing of multi-shot AR, AR mode can be 1-pole AR or 3-pole AR, however, the
selection is valid only to the first reclosing, after that it can only be 3-pole AR. When logic setting
[CBx.79.SetOpt] is set as “1”, AR mode is determined by logic settings. When logic setting
[CBx.79.SetOpt] is set as “0”, AR mode is determined by external signal via binary inputs.
An auto-reclosure must be ready to operate before performing reclosing. The output signal
[CBx.79.Ready] means that the auto-reclosure can perform at least one time of reclosing function,
i.e., breaker open-close-open.
When the device is energized or after the settings are modified, AR can not be ready unless the
following conditions are met:
1. AR function is enabled.
2. The circuit breaker is ready, such as, normal storage energy and no low pressure signal.
3. The duration of the circuit breaker in closed position before fault occurrence is not less than
the setting [CBx.79.t_CBClsd].
After the auto-reclosure operates, the auto-reclosure must reset, i.e., [CBx.79.Active]=0, in
addition to the above conditions for reclosing again.
When there is a fault on an overhead line, the concerned circuit breakers will be tripped normally.
After fault is cleared, the tripping command will drop off immediately. In case the circuit breaker is
in failure, etc., and the tripping signal of the circuit breaker maintains and in excess of the time
delay [CBx.79.t_PersistTrp], AR will be blocked, as shown in Figure 3.27-1.
EN [CBx.79.En_PDF_Blk]
& >=1
&
The input signal [CBx.79.CB_Healthy] must be energized before auto-reclosure gets ready.
Because most circuit breakers can finish one complete process: open-closed-open, it is necessary
that circuit breaker has enough energy before reclosing. When the time delay of AR is exhausted,
AR will be blocked if the input signal [CBx.79.CB_Healthy] is still not energized within time delay
[CBx.79.t_CBReady]. If this function is not required, the input signal [CBx.79.CB_Healthy] can be
not to configure, and its state will be thought as “1” by default.
In orde to block AR reliably even if the signal of manually open circuit breaker not connected to the
input of blocking AR, when the circuit breaker is open by manually and there is CB position input
under normal conditions, AR will be blocked with the time delay of 100ms if AR is not initated and
no any trip signal.
When the input signal [CBx.79.LockOut] is energized, auto-reclosure will be blocked immediately.
The blocking flag of AR will be also controlled by the internal blocking condition of AR. When the
blocking flag of AR is valid, auto-reclosure will be blocked immediately. The logic of AR ready is
shown in Figure 3.27-2.
>=1
SIG 3 CB closed [CBx.79.t_CBClsd] 100ms &
SIG CBx.79.Active >=1
EN [CBx.79.En] &
>=1
EN [CBx.79.En_ExtCtrl] CBx.79.On
&
SIG CBx.79.En &
SIG CBx.79.Blk
When a fault occurs under pole disagreement condition, blocking AR can be enabled or disabled.
The time delay [CBx.79.t_SecFault] is used to discriminate another fault which begins after 1-pole
AR initiated. AR will be blocked if another fault happens after this time delay if the logic setting
[CBx.79.En_PDF_Blk] is set as “1”, and 3-pole AR will be initiated if [CBx.79.En_PDF_Blk] is set
as “1”.
AR will be blocked immediately once the blocking condition of AR appears, but the blocking
condition of AR will drop off with a time delay [CBx.79.t_DDO_BlkAR] after blocking signal
disappears.
When one-shot and 1-pole AR is enabled, auto-reclosure will be blocked immediately if there are
binary inputs of multi-phase CB position is energized.
When any protection element operates to trip, the device will output a signal [CBx.79.Active] until
AR drop off (Reset Command). Any tripping signal can be from external protection device or
internal protection element.
AR function can be enabled by internal logic settings of AR mode or external signal via binary
inputs in addition to internal logic setting [CBx.79.En]. When logic setting [CBx.79.En_ExtCtrl] is
set as “1”, AR enable are determined by external signal via binary inputs and logic settings. When
logic setting [CBx.79.En_ExtCtrl] set as “0”, AR enable are determined only by logic settings.
For one-shot reclosing, if 1-pole AR mode is selected, auto-reclosure will reset when there is
three-phase tripping signal or input signal of multi-phase open position.
SIG CBx.79.On
SIG CBx.79.Mode_3PAR
SIG CBx.79.Ready
SIG CBx.79.Trp
SIG CBx.79.Trp3P
SIG CBx.79.TrpC
When AR is enabled, the device will output the signal [CBx.79.Perm_Trp3P] if AR is not ready, or
AR mode is set as 3-Pole AR, or another fault occurs after the circuit breaker is open.
3.27.5.2 AR Initiation
AR mode can be selected by external signal via binary inputs or internal logic settings. If the logic
setting [CBx.79.SetOpt] set as “1”, AR mode is determined by the internal logic settings. If the logic
settings [CBx.79.SetOpt] set as “0”, AR mode is determined by the external inputs.
AR can be initiated by tripping signal of line protection, and the tripping signal may be from internal
trip signal or external trip signal.
When selecting 1-pole AR or 1/3-pole AR, line single-phase fault will trigger 1-pole AR. When AR
is ready to reclosing (“CBx.79.Ready”=1) and the single-phase tripping command is received, this
single-phase tripping command will be kept in the device, and 1-pole AR will be initiated after the
single-phase tripping command drops off. The single-phase tripping command kept in the device
will be cleared after the completion of auto-reclosing sequence (Reset Command). Its logic is
shown in Figure 3.27-4.
&
&
SIG CBx.79.Ready 1-pole AR Initiation
SIG CBx.79.Sel_1P/3PAR
When selecting 3-pole AR or 1/3-pole AR, three-phase tripping will trigger 3-pole AR. When AR is
ready to reclosing (“CBx.79.Ready”=1) and the three-phase tripping command is received, this
three-phase tripping command will be kept in the device, and 3-pole AR will be initiated after the
three-phase tripping command drops off. The three-phase tripping command kept in the device will
be cleared after the completion of auto-reclosing sequence (Reset Command). Its logic is shown
in Figure 3.27-5.
&
&
SIG CBx.79.Ready 3-pole AR Initiation
SIG CBx.79.Sel_1P/3PAR
2. AR initiated by CB state
A logic setting [CBx.79.En_CBInit] is available for selection that AR is initiated by CB state. Under
normal conditions, when AR is ready to reclosing (“CBx.79.Ready”=1), AR will be initiated if circuit
breaker is open and corresponding phase current is nil. AR initiated by CB state can be divided
into initiating 1-pole AR and 3-pole AR, their logics are shown in Figure 3.27-6 and Figure 3.27-7
respectively. Usually normally closed contact of circuit breaker is used to reflect CB state.
SIG CBx.79.Sel_1P/3PAR
EN [CBx.79.Sel_3PAR] >=1
EN [CBx.79.Sel_1P/3PAR]
3.27.5.3 AR Reclosing
After AR is initiated, the device will output the initiating contact of AR. For 1-pole AR, in order to
prevent pole discrepancy protection from maloperation under pole discrepancy conditions, the
contact of “1-pole AR initiation” can be used to block pole discrepancy protection.
When the dead time delay of AR expires after AR is initiated, as for 1-pole AR, when the setting
[CBx.25.En_3PLvChk] is set as “0”, the result of synchronism check will not be judged, and
reclosing command will be output directly. When the setting [CBx.25.En_3PLvChk] is set as “1”,
the reclosing is not permissible unless live three-phase check is met. As far as the 3-pole AR, if the
synchronism check is enabled, the release of reclosing command shall be subject to the result of
synchronism check. After the dead time delay of AR expires, if the synchronism check is still
unsuccessful within the time delay [CBx.79.t_wait_Chk], the signal of synchronism check failure
(CBx.79.Fail_Syn) will be output and the AR will be blocked. If 3-pole AR with no-check is enabled,
the condition of synchronism check success (CBx.25.Ok_Chk) will always be established. And the
signal of synchronism check success (CBx.25.Ok_Chk) from the synchronism check logic can be
applied by auto-reclosing function inside the device or external auto-reclosure device.
CBx.79.Inprog_1P
SIG 1-pole AR Initiation >=1
CBx.79.Inprog
SIG 3-pole AR Initiation
CBx.79.Inprog_3P
&
SIG CBx.79.Ok_3PLvChk
>=1
& [CBx.79.t_Wait_Chk] 0ms CBx.79.Fail_Chk
SIG CBx.79.Ok_Chk
In the process of channel abnormality, an internal fault occurs on the transmission line, backup
protection at both ends of line will operate to trip the circuit breaker of each end. The operation
time of backup protection at both ends of the line is possibly non-accordant, whilst the time delay
of AR needs to consider the arc-extinguishing and insulation recovery ability for transient fault, so
the time delay of AR shall be considered comprehensively according to the operation time of the
device at both ends. When the communication channel of main protection is abnormal (input
signal [CBx.79.PLC_Lost] is energized), and the logic setting [CBx.79.En_AddDly] is set as “1”,
then the dead time delay of AR shall be equal to the original dead time delay of AR plus the extra
time delay [CBx.79.t_AddDly], so as to ensure the recovery of insulation intensity of fault point
when reclosing after transient fault. This extra time delay [CBx.79.t_AddDly] is only valid for the
first shot AR.
>=1
SIG CBx.79.PLC_Lost
&
SIG CBx.79.Active
&
Extend AR time
EN [CBx.79.En_AddDly]
Reclosing pulse length may be set through the setting [CBx.79.t_PW_AR]. For the circuit breaker
without anti-pump interlock, a logic setting [CBx.79.En_CutPulse] is available to control the
reclosing pulse. When this function is enabled, if the device operates to trip during reclosing, the
reclosing pulse will drop off immediately, so as to prevent multi-shot reclosing onto fault. After the
reclosing command is issued, AR will drop off with time delay [CBx.79.t_Reclaim], and can carry
out next reclosing.
EN [CBx.79.En_CutPulse]
>=1
&
SIG CBx.79.AR_Out [CBx.79.t_Reclaim] 0ms Reset Command
The reclaim timer defines a time from the issue of the reclosing command, after which the
reclosing function resets. Should a new trip occur during this time, it is treated as a continuation of
the first fault. The reclaim timer is started when the CB closing command is given.
SET [CBx.79.Opt_Priority]=High
For transient fault, the fault will be cleared after the device operates to trip. After the reclosing
command is issued, AR will drop off after time delay [CBx.79.t_Reclaim], and can carry out next
reclosing. When the reclosing is unsuccessful or the reclosing condition is not met after AR
initiated, the reclosing will be considered as unsuccessful, including the following cases.
1. If any protection element operates to trip when AR is enabled ([CBx.79.On]=1) and AR is not
ready ([CBx.79.Ready]=0), the device will output the signal (CBx.79.Fail_Rcls).
2. For one-shot AR, if the tripping command is received again within reclaim time after the
3. For multi-shot AR, if the reclosing times are equal to the setting value of AR number and the
tripping command is received again after the last reclosing pulse is issued, the reclosing shall
be considered as unsuccessful.
SIG CBx.79.On
&
SIG CBx.79.Ready
SIG CBx.79.AR_Blkd
>=1
&
SIG AR Pulse [CBx.79.t_Fail] 0ms &
SIG 3 CB closed
EN [CBx.79.En_FailCheck] &
& CBx.79.Succ_Rcls
0ms [CBx.79.t_Fail]
After unsuccessful AR is confirmed, AR will be blocked. AR will not enter into the ready state
unless the circuit breaker position drops off , and can only begin to enter into the ready state again
after the circuit breaker is closed.
The device may be set up into one-shot or multi-shot AR. Through the setting [CBx.79.N_Rcls],
the maximum number of reclosing attempts may be set up to 4 times. Generally, only one-shot AR
is selected. Some corresponding settings may be hidden if one-shot AR is selected.
1. 1-pole AR
[CBx.79.N_Rcls]=1 means one-shot reclosing. For one-shot 1-pole AR mode, 1-pole AR will be
initiated only for single-phase fault and respective faulty phase selected, otherwise, AR will be
blocked. For single-phase transient fault on the line, line protection device will operate to trip and
1-pole AR is initiated. After the dead time delay for 1-pole AR is expired, the device will send
reclosing pulse, and then the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim] to
ready for the next reclosing. For permanent fault, the device will operate to trip again after the
reclosing is performed, and the device will output the signal of reclosing failure [CBx.79.Fail_Rcls].
[CBx.79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 1-pole AR mode, the
first reclosing is 1-pole AR, and the subsequent reclosing can only be 3-pole AR. For single-phase
transient fault on the line, line protection device will operate to trip and then 1-pole AR is initiated.
After the dead time delay of the first reclosing is expired, the device will send reclosing pulse, and
then the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim] to ready for the next
reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed,
and then 3-pole AR is initiated. At this time, the time delay applies the setting [CBx.79.t_Dd_3PS2].
After the time delay is expired, if the reclosing condition is met, the device will send reclosing pulse.
The sequence is repeated until the reclosing is successful or the maximum permit reclosing
number [CBx.79.N_Rcls] is reached. If the first fault is multi-phase fault, the device operates to trip
three-phase and initiate 3-pole AR. At this time, the time delay applies the setting
[CBx.79.t_Dd_3PS1]. For the possible reclosing times of 3-pole AR in 1-pole AR mode, please
refer to Figure 3.27-13.
2. 3-pole AR
[CBx.79.N_Rcls]=1 means one-shot reclosing. For one-shot 3-pole AR mode, line protection
device will operate to trip when a transient fault occurs on the line and 3-pole AR will be initiated.
After the dead time delay for 3-pole AR is expired, the device will send reclosing pulse, and then
the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim] to ready for the next
reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed,
and the device will output the signal of reclosing failure [CBx.79.Fail_Rcls].
[CBx.79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 3-pole AR mode, line
protection device will operate to trip when a transient fault occurs on the line and 3-pole AR will be
initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing
pulse, and then the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim] to ready for
the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is
performed, and then 3-pole AR is initiated after the tripping contact drops off. After the time delay
for AR is expired, the device will send reclosing pulse. The sequence is repeated until the
reclosing is successful or the maximum permit reclosing number [CBx.79.N_Rcls] is reached.
3. 1/3-pole AR
[CBx.79.N_Rcls]=1 means one-shot reclosing. For one-shot 1/3-pole AR mode, line protection
device will operate to trip when a transient fault occurs on the line and 1-pole AR will be initiated
for single-phase fault and 3-pole AR will be initiated for multi-phase fault. After respective dead
time delay for AR is expired, the device will send reclosing pulse, and then the auto-reclosure will
drop off after the time delay [CBx.79.t_Reclaim] to ready for the next reclosing. For permanent
fault, the device will operate to trip again after the reclosing is performed, and the device will
output the signal of reclosing failure [CBx.79.Fail_Rcls].
[CBx.79.N_Rcls]>1 means multi-shot reclosing. For multi-shot reclosing in 1/3-pole AR mode, line
protection device will operate to trip when a transient fault occurs on the line and AR will be
initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing
pulse, and then the auto-reclosure will drop off after the time delay [CBx.79.t_Reclaim] to ready for
the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is
performed, and then 3-pole AR is initiated after the tripping contact drops off. After the time delay
for AR is expired, the device will send reclosing pulse. The sequence is repeated until the
reclosing is successful or the maximum permit reclosing number [CBx.79.N_Rcls] is reached. For
the possible reclosing times of 3-pole AR in 1/3-pole AR mode, please refer to Figure 3.27-14.
The table below shows the number of reclose attempts with respect to the settings and AR modes.
Duplicated protection configurations are normally applied for UHV lines. If reclosing function is
integrated within line protections, the auto-reclosing function can be enabled in any or both of the
line protections without coordination.
If both sets of reclosing functions are enabled, when one of them first recloses onto a permanent
fault, the other will block the reclosing pulse according to the latest condition of the faulty phase.
For one-shot AR mode, if the current is detected in the faulty phase, AR will be blocked
immediately to prevent the circuit breaker from repetitive reclosing. For multi-shot AR mode, if the
current is detected in the faulty phase, the current reclosing pulse will be blocked and go into the
next reclosing pulse logic automatically. If the maximum permitted reclosing number
[CBx.79.N_Rcls] is reached, the auto-reclosure will drop off after the time delay
[CBx.79.t_Reclaim].
For one-shot or multi-shot AR, there is a corresponding reclosing counter at each stage. After
reclosing pulse is sent, the corresponding reclosing counter will plus 1 and the reclosing counter
may be cleared by the submenu “Clear Counter”. If the circuit breaker is reclosed by other
devices during AR initiation, the auto-reclosure will go into the next reclosing pulse logic.
The following two examples indicate typical time sequence of AR process for transient fault and
permanent fault respectively.
Signal
Fault
Trip
CB 52b
Open
CBx.79.t_Reclaim [CBx.79.t_Reclaim]
CBx.79.Active
CBx.79.Inprog [CBx.79.t_Dd_1PS1]
CBx.79.Inprog_1P [CBx.79.t_Dd_1PS1]
CBx.79.Ok_Chk
AR Out [CBx.79.t_PW_AR]
CBx.79.Perm_Trp3P
CBx.79.Fail_Rcls
Time
Signal
Fault
Trip
Open Open
52b
CBx.79.t_Reclaim [CBx.79.t_Reclaim]
CBx.79.Active
CBx.79.Inprog
CBx.79.Inprog_1P [CBx.79.t_Dd_1PS1]
CBx.79.Inprog_3PS2 [CBx.79.t_Dd_3PS2]
CBx.79.Ok_Chk
CBx.79.Perm_Trp3P
CBx.79.Fail_Rcls 200ms
Time
3.27.6 Settings
Table 3.27-3 Auto-reclosing settings
TT
TT.Init TT.Alm
TT.En TT.Op
TT.Blk TT.On
etc.
Transfer trip blocking input, it is triggered from binary input or programmable logic
3 TT.Blk
etc.
No. Output Signal Description
1 TT.Alm Input signal of receiving transfer trip is abnormal
2 TT.Op Transfer trip operates
3 TT.On Transfer trip is enabled
3.28.5 Logic
SIG TT.Alm
BI TT.Init
3.28.6 Settings
Table 3.28-2 Settings of transfer trip
For any enabled protection tripping elements, their operation signal will convert to appropriate
tripping signals through trip logics and then trigger output contacts by configuration.
NOTICE!
For double circuit breakers mode, the device will provide independent trip logic for CB1
and CB2 respectively. Both trip logics have the same logic.The difference is that the
prefix “CBx.” is added to all signals for circuit breaker No.x (x=1 or 2). For trip logic
settings, only the setting [En_Trp3P] will be added the prefix “CBx.” for circuit breaker
No.x, which means that both circuit breakers corresponding to the same line protection
can be set different trip mode.
This module gathers signals from phase selection and protection tripping elements and then
converts the operation signal from protection tripping elements to appropriate tripping signals.
The device can implement phase-segregated tripping or three-phase tripping, and may output the
contact of blocking AR and the contact of initiating breaker failure protection.
TRP
CBx.TRP.En CBx.TrpA
CBx.TRP.Blk CBx.TrpB
CBx.PrepTrp3P CBx.Trp
CBx.BFI_C
CBx.BFI
CBx.Trp3P_PSFail
CBx.TRP.BlkAR
CBx.TRP.On
3.29.5 Logic
After tripping signal is issued, the tripping pulse will be kept as same as the setting [t_Dwell_Trp] at
least. When the time delay is expired, for phase-segregated tripping, the tripping signal will drop
off immediately if the faulty current of corresponding phase is less than 0.06In (In is secondary
rated current), otherwise the tripping signal will be always kept until the faulty current of
corresponding phase is less than 0.06In. For three-phase tripping, the tripping signal will drop off
immediately if three-phase currents are all less than 0.06In, otherwise the tripping signal will be
always kept until three-phase currents are all less than 0.06In.
& >=1
SIG FPS (phase A) &
& >=1
SIG FPS (phase B) &
& >=1
SIG FPS (phase C) &
SIG CBx.Trp
CBx.Trp3P_PSFail
>=1
&
200ms 0ms
SIG Line tripping element
&
SIG CBx.TrpA [t_Dwell_Trp] 0 & CBx.TrpA
SIG Ia<0.06In
&
SIG CBx.TrpB [t_Dwell_Trp] 0 & CBx.TrpB
SIG Ib<0.06In
&
SIG CBx.TrpC [t_Dwell_Trp] 0 & CBx.TrpC
SIG Ic<0.06In
SIG CBx.TrpA
>=1
SIG CBx.TrpB CBx.Trp
SIG CBx.TrpC
SIG CBx.TrpA
&
SIG CBx.TrpB CBx.Trp3P
SIG CBx.TrpC
>=1
Except undervoltage protection, &
tripping elements of all CBx.BFI
protections all initiate BFP
&
CBx.BFI_B
SIG CBx.TrpB
&
CBx.BFI_C
SIG CBx.TrpC
EN [85.DEF.En_BlkAR]
SIG 78.Op
EN [Yi.ZG.En_BlkAR]
EN [50/51Pm.En_BlkAR]
EN [50/51Gm.En_BlkAR]
EN [50/51Qm.En_BlkAR]
SIG 50PVT.Op
>=1
SIG 50GVT.Op
SIG 46BC.Op
SIG 81O.OFm.Op
>=1 >=1
SIG 81U.UFm.Op
SIG TT.Op
SIG CBx.50BF.Op_t1
>=1
SIG CBx.50BF.Op_t2
SIG CBx.50DZ.Op
SIG 49-1.Op
>=1
SIG 49-2.Op
SIG CBx.62PD.Op
SIG 59Pz.Op
>=1
SIG 27Pz.Op
SIG 59Q.Op
EN En_MPF_Blk_AR &
EN En_PhSF_Blk_AR &
i can be 1, 2, 3, 4 or 5
m can be 1, 2, 3 or 4
z can be 1, 2 or 3
x can be 1 or 2
3.29.6 Settings
Table 3.29-2 Settings of trip logic
The purpose of VT circuit supervision is to detect whether VT circuit is normal. Because some
protection functions, such as distance protection, under-voltage protection and so on, will be
influenced by VT circuit failure, these protection functions should be disabled when VT circuit fails.
VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit fault,
poor contact of VT circuit, VT maintenance and so on. The device can detect them and issue an
alarm signal to block relevant protection functions. However, the alarm of VT circuit failure should
not be issued when the following cases happen.
2. Only current protection functions are enabled and VT is not connected to the device.
Under normal conditions, the device detect residual voltage greater than 8% of Unn to determine
single-phase or two-phase VT circuit failure, and detect positive-sequence voltage less than
0.3Unn to determine three-phase VT circuit failure. Upon detecting abnormality on VT circuit, an
alarm will comes up with the time delay [VTS.t_DPU] and drop off with the time delay [VTS.t_DDO]
after VT circuit restored to normal.
VT (secondary circuit) MCB auxiliary contact as a binary input can be connected to the binary
input circuit of the device. If MCB is open (i.e. [VTS.MCB_VT] is energized), the device will
consider the VT circuit is not in a good condition and issues an alarm without a time delay.
When VT is not connected into the device, the alarm will be not issued if the logic setting
[VTS.En_Out_VT] is set as “1”. However, the alarm is still issued if the binary input [VTS.MCB_VT]
is energized, no matter that the logic setting [VTS.En_Out_VT] is set as “1” or “0”.
When VT neutral point fails, third harmonic of residual voltage is comparatively large. If third
harmonic amplitude of residual voltage is larger than 0.2Unn and without operation of fault
detector element, VT neutral point failure alarm signal [VTNS.Alm] will be issued with the time
delay [VTS.t_DPU] and drop off with the time delay [VTS.t_DDO] after three phases voltage
restored to normal.
VTS VTNS
VTS.Blk VTNS.Blk
VTS.MCB_VT
logic etc.
VT supervision blocking input, it is triggered from binary input or programmable
2 VTS.Blk
logic etc.
VT neutral point supervision enabling input, it is triggered from binary input or
3 VTNS.En
programmable logic etc.
VT neutral point supervision blocking input, it is triggered from binary input or
4 VTNS.Blk
programmable logic etc.
5 VTS.MCB_VT Binary input for VT MCB auxiliary contact
No. Output Signal Description
1 VTS.Alm Alarm signal to indicate VT circuit fails
2 VTNS.Alm Alarm signal to indicate VT neutral point fails
3.30.5 Logic
SIG 3U0>0.08Unn
SIG U1<0.3Unn
>=1
&
If the signal [FD.Pkp] or [CBx.79.Inprog] operates,
EN [VTS.En_LineVT] >=1 the circuit of time delay will be interrupted.
SIG 52b_PhA
&
&
SIG 52b_PhB
[VTS.t_DPU] [VTS.t_DDO] &
SIG 52b_PhC
>=1 >=1
EN [VTS.En_Out_VT] & VTS.Alm
BI [VTS.MCB_VT]
EN [VTS.En]
&
SIG [VTS.En]
SIG [VTS.Blk]
&
SIG FD.Pkp >=1
SIG 79.Inprog
If the signal [FD.Pkp] or [CBx.79.Inprog] operates,
the circuit of time delay will be interrupted.
SIG U03>0.2Unn & >=1
[VTS.t_DPU] [VTS.t_DDO] & VTNS.Alm
EN [VTS.En_Out_VT]
EN [VTS.En]
&
SIG [VTNS.En]
SIG [VTNS.Blk]
Where:
If there is already a VTS alarm before FD operated, VTS will continue to block distance protection,
that is VTS will be latched when FD operates.
3.30.6 Settings
Table 3.30-2 VTS settings
NOTICE!
For double circuit breakers mode, the device will provide independent CT circuit
supervision function for CB1 and CB2 respectively. Both CT circuit supervision
functions have the same logic.The difference is that the prefix “CBx.” is added to all
signals for circuit breaker No.x (x=1 or 2).
CTS
CBx.CTS.En CBx.CTS.Alm
CBx.CTS.Blk
3.31.5 Logic
SIG 3I0>0.1In
&
SIG 3U0<3V
SIG IA<0.06In
>=1
SIG IB<0.06In
SIG IC<0.06In
The purpose of control is to open or close primary equipment, including circuit breaker (CB),
disconnector (DS) and earth switch (ES), or to issue outputs for signaling purpose. Synchronism
check and dead check are also provided for the control processes as below:
3. Remote closing CB from SCADA (i.e., local HMI system) or control center (CC)
Programmable interlocking logics within a bay and amongst different bays are provided by using
PCS-Explorer.
NOTICE!
For double circuit breakers mode, the device will provide independent control and
synchrocheck function of manual closing for CB1 and CB2 respectively. Both control
and synchrocheck for manual closing functions have the same logic.The difference is
that the prefix “CBx.” is added to all signals and settings for circuit breaker No.x (x=1 or
2).
1. Control
High reliability is ensured by adopting the principle of selection before operation (abbreviated
SBO). When the binary input [BI_Maintenance] is energized as “1”, remote control from
SCADA/CC will be disabled, but local control will not be influenced.
1) The control source (SCADA/CC, or local LCD control operation, or manual control operation)
sends control selection command to this device
2) This device sends back the control selection result (success or failure) to the control source
after logic judgment
3) The control source sends control operation command to this device if the control selection
result is “success”. The control source will send control cancellation command to this device if
the control selection result is “failure”.
4) This device sends back the control operation result (success or failure) to the control source
after logic judgment.
Logic calculation result of interlocking is input to the remote control module as a criterion of remote
operation. When the enabling parameter of remote open/close interlock is “1”, remote control
module determines whether it can be output according to the calculation result of interlocking. If
the current breaker position or programmable part can meet the interlocking condition, remote
control can be output normally, otherwise remote operation is blocked. When the enabling
parameter of remote open/close interlock is “0”, interlocking function is disabled and remote
control will be output directly without the judgment of interlocking.
Holding time of each binary output contact can be set by configuring corresponding settings and is
often configured as 250ms. However, for the control circuits without latched relays, the holding
time must be longer to ensure successful control operation.
1
EN [MCBrd.CBx.25.En_SynChk]
MCBrd.CBx.25.On_SynChk
SIG MCBrd.CBx.25.Sel_SynChk
0
EN [MCBrd.CBx.25.SetOpt]
1
EN [MCBrd.CBx.25.En_NoChk]
MCBrd.CBx.25.On_NoChk
SIG MCBrd.CBx.25.Sel_NoChk
0
EN [MCBrd.CBx.25.SetOpt]
SIG BIinput.CILO.Disable
>=1
EN [CSWI01.En_Cls_Blk]
SIG CSWI01.CILO.EnCls
&
SIG BIinput.LocCtrl
SIG CSWI01.Cmd_LocCtrl
SIG MCBrd.CB1.25.Ok_Chk
EN [MCBrd.CB1.25.En_VTS_Blk_SynChk]
EN [MCBrd.CB1.En_Alm_VTS] &
&
SIG MCBrd.CB1.Alm_VTS
EN [MCBrd.CB1.25.En_VTS_Blk_DdChk]
EN [MCBrd.CB1.25.En_LvL_DdB]
>=1 & >=1
EN [MCBrd.CB1.25.En_DdL_LvB] >=1
EN [MCBrd.CB1.25.En_DdL_DdB]
SIG MCBrd.CB1.25.Ok_Chk
SIG MCBrd.CB1.25.On_NoChk
SIG BIinput.CILO.Disable
>=1
EN [CSWI02.En_Cls_Blk]
SIG CSWI02.CILO.EnCls
&
SIG BIinput.LocCtrl
SIG CSWI02.Cmd_LocCtrl
SIG MCBrd.CB2.25.Ok_Chk
EN [MCBrd.CB2.25.En_VTS_Blk_SynChk]
EN [MCBrd.CB2.En_Alm_VTS] &
&
SIG MCBrd.CB2.Alm_VTS
EN [MCBrd.CB2.25.En_VTS_Blk_DdChk]
EN [MCBrd.CB2.25.En_LvL_DdB]
>=1 & >=1
EN [MCBrd.CB2.25.En_DdL_LvB] >=1
EN [MCBrd.CB2.25.En_DdL_DdB]
SIG MCBrd.CB2.25.Ok_Chk
SIG MCBrd.CB2.25.On_NoChk
As shown in Figure 3.32-3, for double circuit breakers application, both the first closing command
“CSWI01.Op_Cls” and the second closing command “CSWI02.Op_Cls”, which are controlled by
synchrocheck logic, can be used for CB closing, otherwise, the logic of the second closing
command “CSWI02.Op_Cls” should comply with Figure 3.32-4.
After receiving a closing command, this device will continuously check whether the 2 voltages
(Incoming voltage and reference voltage) involved in synchronism check (or dead check) can meet
the criteria. Within the duration of [MCBrd.CBx.25.t_Wait_Chk], if the synchronism check (or dead
check) criteria are not met, the signal “MCBrd.CBx.25.Ok_Chk” will be set as “0”; if the
synchronism check (or dead check) criteria are met, the signal “MCBrd.CBx.25.Ok_Chk” will be
set as “1”.
When any of the following criteria is fulfilled, an alarm signal [MCBrd.CBx.Alm_VTS] will be issued
with a time delay of 1.25s, and drop off with a time delay of 10s after three phases voltage restored
to normal. The alarm signal will block the closing command for circuit breaker.
2. The positive-sequence voltage is smaller than 30V, and any phase current is greater than
0.04In.
SIG BIinput.CILO.Disable
>=1
EN [CSWIxx.En_Cls_Blk] &
[CSWIxx.t_PW_Cls] 0ms [CSWIxx.Op_Cls]
SIG CSWIxx.CILO.EnCls
SIG CSWIxx.Cmd_RmtCtrl
SIG CSWIxx.Cmd_LocCtrl
Access the menu “Local Cmd→Control” to issue control command locally, and this signal
“CSWIxx.Cmd_LocCtrl” will be set as “1”. Remote control commands from SCADA/CC can be
transmitted via IEC 60870-5-103 protocol or IEC 61850 protocol, and this signal
“CSWIxx.Cmd_RmtCtrl” will be set as “1”.
SIG BIinput.CILO.Disable
>=1
EN [CSWI01.En_Opn_Blk] &
[CSWI01.t_PW_Opn] 0ms CSWI01.Op_Opn
SIG CSWI01.CILO.EnOpn
SIG CSWI01.Cmd_LocCtrl
SIG BIinput.CILO.Disable
>=1
EN [CSWI02.En_Opn_Blk] &
[CSWI02.t_PW_Opn] 0ms CSWI02.Op_Opn
SIG CSWI02.CILO.EnOpn
SIG CSWI02.Cmd_LocCtrl
SIG BIinput.CILO.Disable
>=1
EN [CSWIxx.En_Opn_Blk] &
[CSWIxx.t_PW_Opn] 0ms CSWIxx.Op_Opn
SIG CSWIxx.CILO.EnOpn
SIG CSWIxx.Cmd_LocCtrl
The control output fulfills signal output circuit, and opens or closes circuit breaker, disconnector
and earth switch according to the control command. Object manipulation strictly performs three
steps: selection, check and excute, and perform output relay check, to ensure that the remote
control can be excuted safely and reliably.
When logic interlock is enabled, the device can receive the programmable interlock logic. The
device can automatically initiate the interlock logic to determine whether to allow control
operations. The device provides corresponding settings ([CSWIxx.En_Opn_Blk] and
[CSWIxx.En_Cls_Blk]) for each control object. When they are set as “1”, the interlock function of
the corresponding control object is enabled. The interlock logic can be configured by using
PCS-Explorer, and downloaded to the device via the Ethernet port. If the interlock function is
enabled, but it is not configured the interlock logic, the result of the logic output is 0.
The control record is a file which is used to store remote control command records of this device
circularly. If the record number is to 256, the storage area of the control record will be full. If this
device has received a new remote command, this device will delete the oldest remote control
record, and then store the latest remote control record.
There are 15 configuration pages corresponding to 15 control outputs in totall respectively. Each
configuration page can finish some signals configuration, including remote control, local control,
disable interlock blocking, and so on.
In order to conveniently configure control output, the same output signals, including
“BIinput.RmtCtrl”, “BIinput.LocCtrl” and “BIinput.CILO.Disable”, are available after processing
binary signals internally, as shown in figure below.
The configuration rule about remote control and local control to binary outputs is as bellow:
Remot Local
CSWIxx. BIinput. CSWIxx. BIinput. Control Mode
RmtCtrl RmtCtrl LocCtrl LocCtrl
X X X X Neither Local control nor remote control are permissible.
0 X X X
Only local control is permissible.
X 0 X X
1 X X X
Only remote control is permissible.
X 1 X X
X X 0 X
Only remote control is permissible.
X X X 0
X X 1 X
Only local control is permissible.
X X X 1
0 X 0 X
0 X X 0
Neither Local control nor remote control are permissible.
X 0 0 X
X 0 X 0
0 X 1 X
X 0 1 X Only local control is permissible.
0 X X 1
X 0 X 1
1 X 0 X
1 X X 0
Only remote control is permissible.
X 1 0 X
X 1 X 0
1 X 1 X
1 X X 1
Both Local control and remote control are permissible.
X 1 1 X
X 1 X 1
For remote control or local control, they can be configured by either of “CSWIxx.RmtCtrl” and
“BIinput.RmtCtrl”, or either of “CSWIxx.LocCtrl” and “BIinput.LocCtrl”.
2. Synchrocheck
Three synchrocheck modes are designed for CB closing: no check mode, dead check mode and
synchronism check mode, if any one of the condition of three synchrocheck modes satisfied, then
synchrocheck signal “MCBrd.CBx.25.Ok_Chk” will be asserted.
The synchronism check function measures the conditions across the circuit breaker and compares
them with the corresponding settings. The output is only given if all measured quantities are
simultaneously within their set limits. Compared to the synchronism check for auto-reclosing, an
additional criterion is applied to check the rate of frequency change (df/dt) between both sides of
the CB.
When the following four conditions are all met, the synchronism check is successful.
1) Phase angle difference between incoming voltage and reference voltage is less than the
setting [MCBrd.CBx.25.phi_Diff]
2) Frequency difference between incoming voltage and reference voltage is less than
[MCBrd.CBx.25.f_Diff]
3) Voltage difference between between incoming voltage and reference voltage is less than
[MCBrd.CBx.25.U_Diff]
4) Rate of frequency change between incoming voltage and reference voltage is less than
[MCBrd.CBx.25.df/dt]
The dead check function measures the amplitude of line voltage and bus voltage at both sides of
the circuit breaker, and then compare them with the live check setting [MCBrd.CBx.25.U_Lv] and
the dead check setting [MCBrd.CBx.25.U_Dd]. The dead check is successful when the measured
quantities comply with the criteria.
When this device is set to work in no check mode and receives a closing command, CB will be
closed without synchronism check and dead check.
Synchrocheck for manual closing also supports voltage switching. In general, voltage switching is
fulfilled by external circuit ([CBx.CBConfigMode]=NoVoltSel). If using this module to fulfill voltage
switching, the busbar arrangement should be determined by the setting [CBx.CBConfigMode],
including:
Analog input defines four voltage inputs, UL1, UB1, UL2, UB2, and their usage are as follow:
UL1: it connects with three-phase protection voltages (from line or busbar), which mainly are used
by distance protection, voltage protection and so on. According to the voltage switching result,
synchrocheck logic choose one voltage to be used for synchrocheck function, synchrocheck
function requires to judgment the phase identification information of the voltage, which is
determined by the setting [MCBrd.CBx.25.Opt_Source_UL1]. If voltage switching function is not
used, the reference voltage will be selected from UL1 fixedly.
UB1: according to the voltage switching result, synchrocheck logic determined whether the voltage
is used for synchrocheck function. Synchrocheck function requires to judgment the phase
identification information of the voltage, which is determined by the setting
[MCBrd.CBx.25.Opt_Source_UB1]. If voltage switching function is not used, UB1 will be taken as
the synchronism voltage.
UL2: according to the voltage switching result, synchrocheck logic determined whether the voltage
is used for synchrocheck function. Synchrocheck function requires to judgment the phase
identification information of the voltage, which is determined by the setting
[MCBrd.CBx.25.Opt_Source_UL2]. When voltage switching is available, it is only available for 1½
breakers arrangement, it is fixedly connected to the voltage of the other line of the same diameter
in 1½ breakers arrangement.
UB2: according to the voltage switching result, synchrocheck logic determined whether the voltage
is used for synchrocheck function. Synchrocheck function requires to judgment the phase
identification information of the voltage, which is determined by the setting
[MCBrd.CBx.25.Opt_Source_UB2]. When voltage switching is available, it is connected to
synchronism voltage for double busbars arrangement or 1½ breakers arrangement.
Synchrocheck for manual closing supports voltage switching function, and the switching logic is as
same as that of synchrocheck for protection closing. The setting [CBx.CBConfigMode] should be
set according to the actual primary busbar arrangement, otherwise, the voltage switching of
synchrocheck for manual closing will fail, so as to block manual closing with synchrocheck.
During dead charge check, when only single-phase voltage is connected to UL1, live voltage is
valid if the setting [VTS.En] should be set as “0” and the connected single-phase voltage is higher
than the setting [MCBrd.CBx.25.U_Lv], otherwise, live voltage is regarded as live only when three
phases voltages are all higher than [MCBrd.CBx.25.U_Lv].
CSWI01
CSWI01.CILO.EnOpn CSWI01.Op_Opn
CSWI01.CILO.EnCls CSWI01.Op_Cls
CSWI01.RmtCtrl
CSWI01.LocCtrl
CSWI01.CILO.Disable
CSWI02
CSWI02.CILO.EnOpn CSWI02.Op_Opn
CSWI02.CILO.EnCls CSWI02.Op_Cls
CSWI02.RmtCtrl
CSWI02.LocCtrl
CSWI02.CILO.Disable
CSWIxx
CSWIxx.CILO.EnOpn CSWIxx.Op_Opn
CSWIxx.CILO.EnCls CSWIxx.Op_Cls
CSWIxx.RmtCtrl
CSWIxx.LocCtrl
CSWIxx.CILO.Disable
BIinput
BIinput.RmtCtrl BIinput.RmtCtrl
BIinput.LocCtrl BIinput.LocCtrl
BIinput.CILO.Disable BIinput.CILO.Disable
CSWI01.ManSynCls
CSWI01.ManOpn
CSWI02.ManSynCls
CSWI02.ManOpn
xx can be from 02 or 03 to 15
to execute manually open the circuit breaker. (for double circuit breakers
application)
14 MCBrd.CBx.25.Sel_SynChk Synchronism check for manual closing is selected.
15 MCBrd.CBx.25.Sel_NoChk No check for manual closing is selected.
No. Output Signal Description
1 CSWIxx.Op_Opn Open output of binary output No.xx. (xx=01~15)
2 CSWIxx.Op_Cls Closing output of binary output No.xx. (xx=01~15)
3 BIinput.RmtCtrl In order to be convenient to user configure control output, three same
output signals with input signals are available. The relationship with 15
4 BIinput.LocCtrl
binary output have been configured inside the device. The user only
assigns a specific binary input to input signal, the relevant function can
5 BIinput.CILO.Disable be gained. If some binary output need not be controlled by three signals,
please cancle the configuration by PCS-Explorer, and configure it
independently.
6 MCBrd.CBx.Alm_VTS VT circuit of circuit breaker No.x is abnormal.
3.32.5 Settings
Table 3.32-2 Function settings
Faulty phase selection is used to discriminate faulty phase for all kinds of fault type. If protection
element operates, faulty phase selection is succeeded and the device output tripping command.
Faulty phase selection is adaptive to both earthed system and unearthed system. For unearthed
system, earthed protection elements should be disabled, such as phase-to-ground distance
protection, earth fault protection, and only phase-to-phase protection elements are enabled, such
as phase-to-phase distance protection, phase overcurrent protection.
3. When phase overcurrent element operates, pickup phase due to overcurrent is judged as
faulty phase.
4. When phase overvoltage element operates, pickup phase due to overvoltage is judged as
faulty phase.
5. When phase undervoltage element operates, pickup phase due to undervoltage is judged as
faulty phase.
1) Phase A: ΔUOPA
2) Phase B: ΔUOPB
3) Phase C: ΔUOPC
If ΔUOΦMAX is several times higher than the variation of operating voltages of other two phases, the
single-phase fault is ensured, otherwise, the multi-phase fault is ensured.
ΔUOPA Phase A
ΔUOPB Phase B
ΔUOPC Phase C
ΔUOPAB Phase AB
ΔUOPBC Phase BC
ΔUOPCA Phase CA
The phase selection algorithm uses the angle relation between I 0 and I2A of the device. As shown
in Figure 3.33-1, there are three faulty phase selection regions.
Region A
60° -60°
Region B Region C
180°
Depended on the phase relation between I0 and I2A, the faulty phase can be determined.
For single-phase earth fault, I0 and I2 of faulty phase are in-phase and its distance element
operates.
For phase-to-phase earth fault, I0 and I2 of non-faulty phase are in-phase but its distance element
does not operate.
When phase overcurrent element or phase voltage element, the corresponding phase which is
overcurrent, overvoltage or undervoltage will be judged as faulty phase.
SIG 50/51Pi.StA
SIG 87STB.StA
>=1
Phase A
SIG 50PVT.Op &
SIG 50PVT.StA
SIG 59Pz.St1
SIG 50/51Pi.StB
SIG 87STB.StB
>=1
Phase B
SIG 50PVT.Op &
SIG 50PVT.StB
SIG 59Pz.St2
SIG 50/51Pi.StC
SIG 87STB.StC
>=1
Phase C
SIG 50PVT.Op &
SIG 50PVT.StC
SIG 59Pz.St3
i= 1, 2, 3, 4
z=1, 2, 3
PhSel
PhSA
PhSB
PhSC
GndFlt
NOTICE!
For single phase earth fault, for example phase-A earth fault, PhsA” and “GndFlt”
operate. For phase-to-phase fault, for example phase-BC short-circuit fault, “PhsB”
and “PhsC” operate. For two phase earth fault, for example phase-BC earth fault,
“PhsB”, “PhsC” and “GndFlt” operate. For three phases fault, “PhsA”, “PhsB” and
“PhsC” operate.
3.34.1 Application
The main objective of line protection is fast, selective and reliable operation for faults on a
protected line section. Besides this, information on distance to fault is very important for those
involved in operation and maintenance. Reliable information on the fault location greatly
decreases the outage of the protected lines and increases the total availability of a power system.
This fault location function cannot be used for the transmission line with series compensation.
The fault location is an essential function to various line protection devices, after selecting faulty
phase, it measures and indicates the distance to the fault with high accuracy. Thus, the fault can
be quickly located for repairs. The calculation algorithm considers the effect of load currents,
double-end infeed and additional fault resistance. Both double-end fault location and single-end
fault location are available in line differential relay, but only single-end fault location is provided in
other relays. The calculation equation is:
Where:
Zcalc: The impedance value calculated from the location of protection device to fault point
When an earth fault occurred on a line of parallel lines arrangement, a distance relay at one end of
the faulty line will tend to underreach whilst the distance relay at the other end will tend to
overreach. Usually the degree of underreach or overreach is acceptable, however, for cases
where precise fault location is required for long lines with high mutual coupling, mutual
compensation is then required to improve the distance measurement. Practically, the mutual effect
between the parallel lines is insignificant to positive and negative sequence and thus the mutual
compensation is only for zero sequence
A Ia B
ZM
k
C Ic D
kZL (1-k)ZL
ZS
ZL
The principle in the application of mutual compensation is shown as follows with the aid of
following sequence network diagram figure. The diagram indicates a parallel lines arrangement
with an earth fault at location k on line CD.
The equivalent sequence network for an earth fault on a parallel lines arrangement with single
source is shown as below.
Ia1 ZL1
ZS1
kZL1 (1-k)ZL1
Ic1
Ia2 ZL2
ZS2
kZL2 (1-k)ZL2
Ic2
Ia0 ZL0
ZS0
Z0M
kZL0 (1-k)ZL0
Ic0
The device at location C without mutual compensation will have voltage U RC and current IRC
measured as shown in the expression
The residual current from the parallel line should be added to the device. It should be connected to
terminal 08 and star point of the parallel line CT connected to terminal 07 as shown in the following
figure. Please note the connection diagram and the terminal numbers are for reference only. The
final connection terminals are subject to the device configuration at site.
P2 S2 P2 S2
P1 S1 P1 S1
02 01 02 01
04 03 04 03
06 05 06 05
08 07 08 07
NOTICE!
The mutual compensation only is to improve the accuracy of fault location for parallel
lines arrangement, and it is not used by settings calculation of earth fault protections.
FL
FPS_Fault Fault_Location
FD.Pkp Fault_Phase
Fault_Phase_Curr
Fault_Resid_Curr
4 Supervision
Table of Contents
4 Supervision ........................................................................................ 4-a
4.1 Overview .......................................................................................................... 4-1
4.2 Supervision Alarms ......................................................................................... 4-1
4.3 Relay Self-supervision.................................................................................... 4-8
4.3.1 Relay Hardware Monitoring ................................................................................................. 4-8
List of Tables
Table 4.2-1 Alarm description..................................................................................................... 4-1
4.1 Overview
Protection system is in quiescent state under normal conditions, and it is required to respond
promptly for faults occurred on power system. When the device is in energizing process before the
LED “HEALTHY” is on, the device need to be checked to ensure no abnormality. Therefore, the
automatic supervision function, which checks the health of the protection system when startup and
during normal operation, plays an important role.
The numerical relay based on the microprocessor operations is suitable for implementing this
automatic supervision function of the protection system.
In case a defect is detected during initialization when DC power supply is provided to the device,
the device will be blocked with indication and alarm of relay out of service. It is suggested a trial
recovery of the device by re-energization. Please contact supplier if the device is still failure.
When a failure is detected by the automatic supervision, it is followed by a LCD message, LED
indication and alarm contact outputs. The failure alarm is also recorded in event recording report
and can be printed If required.
A minor abnormality may block a certain number of protections functions while the other functions
can still work. However, if severe hardware failure or abnormality, such as PWR module failure,
DC converter failure and so on, are detected, all protection functions will be blocked and the LED
“HEALTHY” will be extinguished and blocking output contacts BO_FAIL will be given. The
protective device then can not work normally and maintenance is required to eliminate the failure.
All the alarm signals and the corresponding handling suggestions are listed below.
NOTICE!
If the device is blocked or alarm signal is sent during operation, please do find out its
reason with the help of self-diagnostic record. If the reason can not be found at site,
please notify the factory NR. Please do not simply press button “TARGET RESET” on
the protection panel or re-energize on the device.
1. check whether the selected clock synchronization mode matches the clock
synchronization source;
2. check whether the wiring connection between the device and the clock
synchronization source is correct
29 Alm_TimeSyn 3. check whether the setting for selecting clock synchronization (i.e.
[Opt_TimeSyn]) is set correctly. If there is no clock synchronization, please
set the setting [Opt_TimeSyn] as ”No TimeSyn”.
If 52b of three phases are energized that indicates circuit breaker is open but there is still current
detected in the line (the measured current is greater than a settable threshold value) or
three-phase circuit breaker is in pole disagreement, an alarm signal [Alm_52b] will be issued after
10 seconds.
5 Management
Table of Contents
5 Management ...................................................................................... 5-a
5.1 Measurement ................................................................................................... 5-1
5.1.1 Measurement Values ........................................................................................................... 5-1
5.1 Measurement
PCS-902 performs continuous measurement of the analogue input quantities. The current full
scale of relay is 40 times of rated current, and there is no effect to the performance of IED due to
overflowing of current full scale. The device samples 24 points per cycle and calculates the RMS
value in each interval and updated the LCD display in every 0.5 second. The measurement data
can be displayed on the LCD of the relay front panel or on the local/remote PC via software tool.
Navigate the menu to view the sampling value through LCD screen.
NOTICE!
This device can be configured to support single circuit breaker application or double
circuit breakers application by PCS-Explorer. For double circuit breakers mode, the
prefix “CBx.” is added to related measurement quantities for circuit breaker No.x (x=1 or
2).
“Measurements1” is used to display measured values from protection calculation DSP. The
measurement values can be displayed in primary value or secondary value by the setting
[Opt_Display_Status].
No.x
“Measurements2” is used to display measured values from fault detector DSP. The measurement
values can be displayed in primary value or secondary value by the setting [Opt_Display_Status].
“Measurements3” is used to display measured values of other calculated quantities related to the
measurement and control. The measurement values are always displayed in primary value.
breaker No.x
“Metering” is used to display metering values of active and reactive energy. The metering values
are always displayed in primary value.
5.2 Recording
5.2.1 Overview
PCS-902 provides the following recording functions:
1. Event recording
2. Disturbance recording
3. Present recording
All the recording information except waveform can be viewed on local LCD or by printing.
Waveform could only be printed or extracted with PCS-Explorer software tool and a waveform
analysis software.
The device can store the latest 1024 disturbance records, 1024 binary events, 1024 supervision
events, 256 control logs and 1024 device logs. All the records are stored in non-volatile memory,
and when the available space is exhausted, the oldest record is automatically overwritten by the
latest one.
When any protection element operates or drops off, such as fault detector, distance protection etc.,
they will be logged in event records.
The device is under automatic supervision all the time. If there are any failure or abnormal
condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged in event
records.
When there is a binary input is energized or de-energized, i.e., its state has changed from “0” to “1”
or from “1” to “0”, it will be logged in event records.
When the total number of control command records reaches 256, “Control_Logs” memory area
will be full. If the device receives a new control command now, the oldest control command record
will be deleted, and then the latest control command record will be stored and displayed.
If an operator implements some operations on the device, such as reboot protective device,
modify setting, etc., they will be logged in event records.
Disturbance records can be used to have a better understanding of the behavior of the power
network and related primary and secondary equipment during and after a disturbance. Analysis of
the recorded data provides valuable information that can be used to improve existing equipment.
This information can also be used when planning for and designing new installations.
5.2.3.2 Design
A disturbance record consists of fault record and fault waveform. The disturbance record can be
initiated by fault detector element, tripping element, reclosing element or configurable signal
[BI_TrigDFR].
The device can store up to 32 disturbance records with waveform in non-volatile memory. It is
based on first in first out queue that the oldest disturbance record will be overwritten by the latest
one.
1. Sequence number
Each operation will be recorded with a sequence number in the record and displayed on LCD
screen.
The time resolution is 1ms using the relay internal clock synchronized via clock synchronized
device if connected. The date and time is recorded when a system fault is detected.
An operating time (not including the operating time of output relays) is recorded in the record.
4. Faulty phase
5. Fault location
To get accurate result of fault location, the following settings shall be set correctly:
6. Protection elements
MON module can store 32 pieces of fault waveform oscillogram in non-volatile memory. If a new
fault occurs when 32 fault waveform have been stored, the oldest will be overwritten by the latest
one.
Each fault record consists of all analog and digital quantities related to protection, such as original
current and voltage, alarm elements, and binary inputs and etc.
Each waveform recording includes pre-fault waveform that is determined by the setting
[Num_Cyc_PreTrigDFR] and post-fault waveform that is 250 cycles at least, and a completed
waveform recording can record 500 cycles at most. Each cycle waveform is high-frequency
recording at a rate of 1200Hz or 1440Hz (24 points per cycle).
Each waveform recording includes pre-fault waveform that is determined by the setting
[Num_Cyc_PreTrigDFR] and 250-cycles post-fault waveform. Each cycle waveform is
high-frequency recording at a rate of 1200Hz or 1440Hz (24 points per cycle).
6 Hardware
Table of Contents
6 Hardware ............................................................................................ 6-a
6.1 Overview .......................................................................................................... 6-1
6.2 Typical Wiring .................................................................................................. 6-4
6.2.1 Conventional CT/VT (For reference only) ........................................................................... 6-4
List of Figures
Figure 6.1-1 Rear view of fixed module position ..................................................................... 6-1
Figure 6.3-10 View of AI plug-in module for one CT group input (NR1401) ........................ 6-17
Figure 6.3-14 View of AI plug-in module for one CT group input (NR1408) ........................ 6-20
Figure 6.3-17 View of AI plug-in module for two CT group input (NR1401) ........................ 6-23
Figure 6.3-20 View of AI plug-in module for two CT group input (NR1401) ........................ 6-25
List of Tables
Table 6.3-1 Terminal definition and description of PWR plug-in module ............................ 6-10
6.1 Overview
PCS-902 adopts 32-bit microchip processor CPU produced by FREESCALE as control core for
management and monitoring function, meanwhile, adopts high-speed digital signal processor DSP
for all the protection calculation. 24 points are sampled in every cycle and parallel processing of
sampled data can be realized in each sampling interval to ensure ultrahigh reliability and safety of
the device.
PCS-902 is comprised of intelligent plug-in modules, except that few particular plug-in modules’
position cannot be changed in the whole device (gray plug-in modules as shown in Figure 6.1-1),
other plug-in modules like AI (analog input) and IO (binary input and binary output) can be flexibly
configured in the remaining slot positions.
MON module
PWR module
DSP module
DSP module
CH Module
BO module
BO module
BO module
BO module
AI module
BI module
BI module
Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
PCS-902 has 16 slots, PWR plug-in module, MON plug-in module, DSP plug-in module and CH
plug-in module are assigned at fixed slots.
Besides 5 fixed modules are shown in above figure, there are 12 slots can be flexibly configured.
AI plug-in module, BI plug-in module and BO plug-in module can be configured at position
between slot 02, 03 and 06~15. It should be pay attention that AI plug-in module will occupy two
slots.
This device is developed on the basis of our latest software and hardware platform, and the new
platform major characteristics are of high reliability, networking and great capability in
anti-interference. See Figure 6.1-2 for hardware diagram.
Output Relay
Binary Input
External
Protection
Conventional CT/VT A/D Calculation
DSP
ECVT
Fault
A/D Detector Pickup
DSP Relay
ECVT
ETHERNET
LCD +E
Clock SYN
Power
Uaux LED CPU
Supply
RJ45
Keypad
PRINT
The working process of the device is as shown in above figure: current and voltage from
conventional CT/VT are converted into small voltage signal and sent to DSP module after filtered
and A/D conversion for protection calculation and fault detector respectively (ECVT signal is sent
to the device without small signal and A/D convertion). When DSP module completes all the
protection calculation, the result will be recorded in 32-bit CPU on MON module. DSP module
carries out fault detector, protection logic calculation, tripping output, and MON module perfomes
SOE (sequence of event) record, waveform recording, printing, communication between the
device and SAS and communication between HMI and CPU. When fault detector detects a fault
and picks up, positive power supply for output relay is provided.
The items can be flexibly configured depending on the situations like sampling method of the
device (conventional CT/VT or ECT/EVT), and the mode of binary output (conventional binary
output or GOOSE binary output). The configurations for PCS-900 series based on microcomputer
are classified into standard and optional modules.
MON module provides functions like communication with SAS, event record, setting
management etc.
AI module converts AC current and voltage from current transformers and voltage
transformers respectively to small voltage signal.
DSP module performs filtering, sampling, protection calculation and fault detector calculation.
CH module performs information exchange with the remote device through a dedicated
optical fibre channel, multiplex optical fibre channel or PLC channel.
BI module provides binary inputs via opto-couplers with rating voltage among
24V/110V/125V/220V/250V (configurable).
BO module provides output contacts for tripping, and signal output contact for annunciation
signal, remote signal, fault and disturbance signal, operation abnormal signal etc.
PWR module converts DC 250/220/125/110V into various DC voltage levels for modules of
the device.
NET-DSP module receives and sends GOOSE messages, sampled values (SV) from
merging unit by IEC61850-9-2 protocol.
HMI module is comprised of LCD, keypad, LED indicators and multiplex RJ45 ports for user
as human-machine interface.
PCS-902 is made of a 4U height 19” chassis for flush mounting. Components mounted on its front
include a 320×240 dot matrix LCD, a 9 button keypad, 20 LED indicators and a multiplex RJ45
port. A monolithic micro controller is installed in the equipment for these functions.
1 11
HEALTHY PCS-902
2 12
ALARM
3 13
4 14
GRP
5 15
6 16 ENT
ESC
7 17
8 18
9 19
10 20
20 LED indicators are, from top to bottom, operation (HEALTHY), self-supervision (ALARM),
others are configurable.
For the 9-button keypad, “ENT” is “enter”, “GRP” is “group number” and “ESC” is “escape”.
NR1102 NR1401 NR1161 NR1213 NR1161 NR1504 NR1504 NR1521 NR1521 NR1521 NR1521 NR1301
5V OK ALM
TX
BO_ALM BO_FAIL
RX
ON
TX
OFF
RX
DANGER
1 BO_COM1
2 BO_FAIL
3 BO_ALM
4 BO_COM2
5 BO_FAIL
6 BO_ALM
7 OPTO+
8 OPTO-
9
10 PWR+
11 PWR-
12 GND
NR1102 NR1401 NR1161 NR1213 NR1161 NR1504 NR1521A NR1521C NR1521C NR1521F NR1301
MON module
PWR module
DSP module
DSP module
CH Module
BO module
BO module
BO module
BO module
AI module
BI module
Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
…
CH-TX
…
0203
0204 Ib BI_12 + 0814
0205
To parallel line Ic Not used 0815
0206
0207 BI_13 + 0816
From parallel line 0208 IM0
…
0213
Protection Voltage
Controlled by fault
0218
detector element
BO_01 1102
1103
0219
Synchronism Voltage
BO_02 1104
0220 UB1
…
1121
0221 BO_11
UL2 1122
0222
0223
1201
Signal Binary Output
0224 UB2
BO_01 1202
1203
PWR+ P110 BO_02
External DC power Power 1204
…
B 0102
COM
1503
SGND 0103 BO_CtrlCls1 1504
0104
…
BO_CtrlOpn5 1518
SYN- 0102
SGND 0103 1519
BO_CtrlCls5 1520
0104
1521
PRINTER
TXD 0106
Multiplex P112
SGND 0107 RJ45 (Front)
0225
Grounding
Bus
PCS-902 (conventional CT/VT and conventional binary input and binary output)
Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
Module ID NR1102 NR1401 NR1161 NR1213 NR1504 NR1504 NR1521 NR1521 NR1521 NR1521 NR1301
PCS-902 (conventional CT/VT and GOOSE binary input and binary output)
Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
NET-DSP Module
MON module
PWR module
DSP module
DSP module
CH Module
BO module
BO module
BI module
Slot No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
terminal
CH-RX BI_03 + 0805
…
BI_11 + 0821
Phase A RX
Phase B
(LC Type)
Up to 8
Phase C TX 1101
Controlled by fault
detector element
BO_01 1102
…
1103
BO_02 1104
…
1121
BO_11 1122
PWR+ P110
External DC power Power
1201
…
1221
P102 BO_FAIL BO_11 1222
P103 BO_ALM
P101 COM 1501
P105 BO_FAIL BO_CtrlOpn1 1502
P106
Signal Binary Output (option)
BO_ALM 1503
P104 COM BO_CtrlCls1 1504
…
A 0101
B 0102 1517
COM
cable with single point earthing
To the screen of other coaxial
BO_CtrlOpn5 1518
SGND 0103
0104 1519
BO_CtrlCls5 1520
SYN+ 0101 1521
Clock SYN
RTS 0105
PRINT
P112
TXD 0106
Multiplex
SGND 0107 RJ45 (Front) 0225 Grounding
Bus
Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
Slot No. 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 P1
Module ID NR1102 NR1161 NR1213 NR1136 NR1504 NR1504 NR1521 NR1521 NR1521 NR1521 NR1301
NET-
MON DSP CH BI BI BO BO BO BO PWR
DSP
In the protection system adopting electronic current and voltage transformer (ECT/EVT), the
merging unit will merge the sample data from ECT/EVT, and then send it to the device through
multi-mode optical fibre. DSP module receives the data from merging unit through the optical-fibre
interface to complete the protection calculation and fault detector.
The difference between the hardware platform based on ECT/EVT and the hardware platform
based on conventional CT/VT lies in the receiving module of sampled values only, and the device
receives the sampled value from merging unit through multi-mode optical fibre.
6.2.3 CT Requirement
-Rated primary current Ipn:
-Rated short-time thermal current Ith and rated dynamic current Idyn:
Performance verification
For example:
= 30×5×(1+60/25)=510V
Esl′ = 2×Ipcf×Isn×(Rct+Rb)/Ipn
= 2×Ipcf ×Isn×(Rct+(Rr+2×RL+Rc))/Ipn
= 2×40000×5×(1+(0.1+2×0.5+0.1))/2000=440V
The +5V DC output provides power supply for all the electrical elements that need +5V DC power
supply in this device.
The use of an external miniature circuit breaker is recommended. The miniature circuit breaker
must be in the on position when the device is in operation and in the off position when the device is
in cold reserve.
A 12-pin connector is fixed on PWR module. The terminal definition of the connector is described
as below.
NR1301
5V OK ALM
BO_ALM BO_FAIL
ON
OFF
1 BO_COM1
2 BO_FAIL
3 BO_ALM
4 BO_COM2
5 BO_FAIL
6 BO_ALM
7 OPTO+
8 OPTO-
9
10 PWR+
11 PWR-
12 GND
The power switch in the dotted box of above figure maybe is not existed.
01
BO_FAIL
02
BO_ALM
03
04
BO_FAIL
05
BO_ALM
06
NOTICE!
The standard rated voltage of PWR module is self-adaptive to 88~300 Vdc. If input
voltage is out of range, an alarm signal (Fail_Device) will be issued. For non-standard
rated voltage power supply module please specify when place order, and check if the
rated voltage of power supply module is the same as the voltage of power source
before the device being put into service.
PWR module provides terminal 12 and grounding screw for device grounding. Terminal
12 shall be connected to grounding screw and then connected to the earth copper bar
of panel via dedicated grounding wire.
Effective grounding is the most important measure for a device to prevent EMI, so
effective grounding must be ensured before the device is put into service.
PCS-902, like almost all electronic relays, contains electrolytic capacitors. These
capacitors are well known to be subject to deterioration over time if voltage is not
applied periodically. Deterioration can be avoided by powering the relays up once a
year.
MON module uses the internal bus to receive the data from other modules of the device. It
communicates with the LCD module by RS-485 bus. This module comprises 100BaseT Ethernet
interfaces, RS-485 communication interfaces that exchange information with above system by
using IEC 61850, PPS/IRIG-B differential time synchronization interface and RS-232 printing
interface.
Modules with various combinations of memory and interface are available as shown in the table
below.
CAUTION!
Do NOT look into the end of an optical fiber connected to an optical port.
TX
ETHERNET ETHERNET
RX
TX
RX
ETHERNET
The correct connection is shown in Figure 6.3-4. Generally, the shielded cable with two pairs of
twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to connect
the “+” and “–” terminals of difference signal. The other pair of twisted pairs are used to connect
the signal ground of the communication interface. The module reserves a free terminal for all the
communication ports. The free terminal has no connection with any signal of the device, and it is
used to connect the external shields of the cable when connecting multiple devices in series. The
external shield of the cable shall be grounded at one of the ends only.
B 02
COM
SGND 03
cable with single point earthing
To the screen of other coaxial
04
SYN- 02
SGND 03
04
Cable
RTS 05
PRINT
TXD 06
SGND 07
Pin1
Pin2
Pin3
NOTICE!
As shown in Figure 6.3-5, the external receiving mode of IRIG-B differential time
synchronization interface can be set by the jumper J8&J9.
For AI module, if the plug is not put in the socket, external CT circuit is closed itself. Just shown as
below.
Plug
Socket
In
Out
In
Out
There are three types of AI module with rating 1A (NR1401), 5A (NR1401) or 1A/5A (NR1408).
Please declare which kind of AI module is needed before ordering. Maximum linear range of the
current converter is 40In.
1. One CT group input without synchronism voltage switchover (optional NR1401 or NR1408)
NR1401
For one CT group input, three phase currents (Ia, Ib and Ic) and residual current from parallel line
(for mutual compensation) are input to AI module separately. Terminal 01, 03, 05 and 07 are
polarity marks. It is assumed that polarity mark of CT installed on line is at line side.
Three phase voltages (Ua, Ub, and Uc) for protection calculation and one synchronism voltage are
input to AI module. The synchronism voltage could be any phase-to-ground voltage or
phase-to-phase voltage.
If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage
should be disconnected.
In order to accurately locate the fault for parallel lines arrangement, residual current from parallel
line is required to be connected to the device to eliminate the mutual effect between the parallel
lines. Otherwise, residual current from parallel line is not necessary.
P2 S2 P2 S2
P1 S1 P1 S1
02 01 02 01
04 03 04 03
06 05 06 05
08 07 08 07
13 14
15 16
17 18
19 20
13 14
15 16
17 18
19 20
Ia 01 Ian 02
NR1401
Ib 03 Ibn 04
Ic 05 Icn 06
IM0 07 IM0n 08
09 10
11 12
Ua 13 Uan 14
Ub 15 Ubn 16
Uc 17 Ucn 18
Us 19 Usn 20
21 22
23 24
Figure 6.3-10 View of AI plug-in module for one CT group input (NR1401)
NR1408
For one CT group input, three phase currents (Ia, Ib and Ic) and residual current from parallel line
(for mutual compensation) are input to AI module separately. Terminal 01 (or 03), 05 (or 07), 09 (or
11) and 13 (or 15) are polarity marks. It is assumed that polarity mark of CT installed on line is at
line side.
Three phase voltages (Ua, Ub, and Uc) for protection calculation and one synchronism voltage are
input to AI module. The synchronism voltage could be any phase-to-ground voltage or
phase-to-phase voltage.
If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage
should be disconnected.
In order to accurately locate the fault for parallel lines arrangement, residual current from parallel
line is required to be connected to the device to eliminate the mutual effect between the parallel
lines. Otherwise, residual current from parallel line is not necessary.
P2 S2 P2 S2
P1 S1 P1 S1
17 18
19 20
21 22
23 24
17 18
19 20
21 22
23 24
Ia-1A 01 Ian-1A 02
NR1408
Ia-5A 03 Ian-5A 04
Ib-1A 05 Ibn-1A 06
Ib-5A 07 Ibn-5A 08
Ic-1A 09 Icn-1A 10
Ic-5A 11 Icn-5A 12
IM0-1A 13 IM0n-1A 14
IM0-5A 15 IM0n-5A 16
Ua 17 Uan 18
Ub 19 Ubn 20
Uc 21 Ucn 22
Us 23 Usn 24
Figure 6.3-14 View of AI plug-in module for one CT group input (NR1408)
For two circuit breakers configuration with two CT groups input, three phase currents
corresponding to CB1 and CB2 respectively (Ia1, Ib1, Ic1 and Ia2, Ib2, Ic2) are input to AI module.
Terminal 01, 03, 05, 07, 09 and 11 are polarity marks. It is assumed that polarity mark of CT
installed on line is at line side.
Three phase voltages (Ua, Ub, and Uc) are input to AI module. UB1, UB2 and UL2 are the
synchronism voltage from bus VT and line VT used for synchrocheck, it could be any
phase-to-ground voltage or phase-to-phase voltage. The device can automatically switch
synchronism voltage according to auxiliary contact of CB position or DS position.
If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage
should be disconnected.
P2 P1 P1 P2 A
S2 S1 S1 S2 C
02 01
04 03
06 05
08 07
10 09
12 11
A B C A B C
13 14
15 16
17 18
19 20
21 22
23 24
Ia1 01 Ia1n 02
NR1401
Ib1 03 Ib1n 04
Ic1 05 Ic1n 06
Ia2 07 Ia2n 08
Ib2 09 Ib2n 10
Ic2 11 Ic2n 12
Ua 13 Uan 14
Ub 15 Ubn 16
Uc 17 Ucn 18
UB1 19 UB1n 20
UL2 21 UL2n 22
UB2 23 UB2n 24
Figure 6.3-17 View of AI plug-in module for two CT group input (NR1401)
For two circuit breakers configuration with two CT groups input, three phase currents
corresponding to CB1 and CB2 respectively (Ia1, Ib1, Ic1 and Ia2, Ib2, Ic2), and residual current
from parallel line (for mutual compensation) are input to AI module. Terminal 01, 03, 05, 07, 09, 11
and 13 are polarity marks. It is assumed that polarity mark of CT installed on line is at line side.
Three phase voltages (Ua, Ub, and Uc) for protection calculation and one synchronism voltage are
input to AI module. The synchronism voltage could be any phase-to-ground voltage or
phase-to-phase voltage.
If the auto-reclosing is enabled but synchronism check is not required, the synchronism voltage
should be disconnected.
P2 P1 P1 P2 A
S2 S1 S1 S2 C
02 01
04 03
06 05
08 07
10 09
12 11
To parallel line
14 13
From parallel line
A B C A B C
15 16
17 18
19 20
21 22
23 24
Ia1 01 Ia1n 02
NR1401
Ib1 03 Ib1n 04
Ic1 05 Ic1n 06
Ia2 07 Ia2n 08
Ib2 09 Ib2n 10
Ic2 11 Ic2n 12
IM0 13 IM0n 14
Ua 15 Uan 16
Ub 17 Ubn 18
Uc 19 Ucn 20
Us 21 Usn 22
23 24
Figure 6.3-20 View of AI plug-in module for two CT group input (NR1401)
NR1161
This device can be equipped with 2 DSP plug-in modules at most and 1 DSP plug-in module at
least. The default DSP plug-in module is necessary, which mainly is responsible for protection
function including fault detector and protection calculation.
The default module consists of high-performance double DSP (digital signal processor),16-digit
high-accuracy ADC that can perform synchronous sampling and manage other peripherals. One
of double DSP is responsible for protection calculation, and can fulfill analog data acquisition,
protection logic calculation and tripping output. The other is responsible for fault detector, and can
fulfill analog data acquisition, fault detector and providing power supply to output relay.
When the module is connected with conventional CT/VT, it can perform the synchronous data
acquisition through AI plug-in module. When the module is connected with ECT/EVT, it can
receive the real-time synchronous sampled value from merging unit through NET-DSP plug-in
module.
The other module is optional and it is not required unless control and manual closing with
synchronism check are equppied with this device. The default DSP plug-in module is fixed at slot
04 and the option DSP plug-in module is fixed at slot 06.
NR1136A NR1136C
RX
This module consists of high-performance DSP (digital signal processor), 2~8 100Mbit/s
optical-fibre interface (LC type) and selectable IRIG-B interface (ST type). It supports GOOSE and
SV by IEC 61850-9-2 protocols. It can receive and send GOOSE messages to intelligent control
device, and receive SV from MU (merging unit).
This module supports IEEE1588 network time protocol, E2E and P2P defined in IEEE1588
protocol can be selected. This module supports Ethernet IEEE802.3 time adjustment message
format, UDP time adjustment message format and GMRP.
CAUTION!
Do NOT look into the end of an optical fiber connected to an optical port.
The device can output q data by GOOSE, and an output signal is provided “Output_q”. This signal
is used to indicate the quality of all output signals. According to the standard definition about the
quality by IEC 61850, the value of this signal is “0” under normal conditions, and it will be “2048”
(Bit1 is “1”, and other bits is “0”) when the device is under maintenance condtion.
The definition of each bit about quality signal by IEC 61850 is as below.
2. Step2: Taking “PTRC_out” module as an example, which can be found in “Symbol Library”
and instanced as bellow.
3. Step3: Double click the instanced module, the parameter list is displayed as bellow. Tr1~Tr8
are used for sending signals, q1~q8 are used for q data, the relationship between them is one
to one. Only one total q data can be added to all 8 sending signals by “batch_q”.
4. Step4: The output q data, named “Output_q” in variable library, is used for all sending signals.
The path is shown as bellow which is marked in red color.
5. Step5: Put the mouse on the “Output_q” signal, hold the left button of the mouse and drag it to
the corresponding position, and then release. The detail is as bellow.
After the above steps, save the modifications and compress driver file. Check the latest GOOSE
and CID file.
TX TX TX TX
RX RX RX RX
TX TX
RX RX
NR1213 NR1213
NR1214 NR1214
TX TX
RX RX
TX1 TX1
RX1 RX1
TX1
TX1 TX1
RX1
RX1 RX1
PCS-902 series can exchange information with the device at the remote end through a dedicated
optical fibre channel or multiplex channel. The module transmits and receives optical signal using
FC/PC or ST optical connector.
NOTICE!
When using dedicated optical fibre channel, if the transmission distance is longer than
50km, the transmitted power may be enchanced to ensure received power larger than
receiving sensitivity. Please notify supplier before ordering and it will be considered as
special project using 1550nm laser diode.
When using multiplex channel, the sending power of the device is fixed.
When using channel multiplexing equipment, the parameters are shown as follows:
1. The routine of both direction shall be same to each other, so the time delays of both direction
are the same.
2. The maximum one-way channel propagation delay shall be less than 15 ms.
CAUTION!
Do NOT look into the end of an optical fiber connected to an optical port.
Voltage
264
176
154
140
110
87.5
77
62.5
55
Operation
Operation uncertain
No operation
0 110V 125V 220V 220V
The well-designed debouncing technique is adopted in this device, and the state change of binary
input within “Debouncing time” will be ignored. As shown in Figure 6.3-25.
Debouncing time
Time
T0 T1
1. NR1503
Each BI module is with a 22-pin connector for 11 binary inputs, and its rated voltage can be
selected to be 110Vdc, 125Vdc, 220Vdc. Each binary input of NR1503A and NR1503AR has
independent negative power input of opto-coupler and can be configurable. NR1503A′s pickup
voltage and dropoff voltage are fixed value, and the range is from 55%Un to 70%Un. NR1503AR′s
pickup voltage and dropoff voltage are settable by the setting [xx.U_Pickup_BI] and
[xx.U_Dropoff_BI] from 55%Un to 80%Un.
BI_01 01
NR1503 Opto01- 02
BI_02 03
Opto02- 04
BI_03 05
Opto03- 06
BI_04 07
Opto04- 08
BI_05 09
Opto05- 10
BI_06 11
Opto06- 12
BI_07 13
Opto07- 14
BI_08 15
Opto08- 16
BI_09 17
Opto09- 18
BI_10 19
Opto10- 20
BI_11 21
Opto11- 22
[BI_n] can be configured as a specified binary input by PCS-Explorer software (n=01, 02, ……).
Terminal description for NR1503 is shown as follows.
2. NR1504
Each BI module is with a 22-pin connector for 18 binary inputs, and its rated voltage can be
selected to be 110Vdc, 125Vdc, 220Vdc. All binary inputs of NR1504A and NR1504AR share one
common negative power input and can be configurable. NR1504A′s pickup voltage and dropoff
voltage are fixed value, and the range is from 55%Un to 70%Un. NR1504AR′s pickup voltage and
dropoff voltage are settable by the setting [xx.U_Pickup_BI] and [xx.U_Dropoff_BI] from 55%Un to
80%Un.
Opto+ 01
NR1504 BI_01 02
BI_02 03
BI_03 04
BI_04 05
BI_05 06
BI_06 07
08
BI_07 09
BI_08 10
BI_09 11
BI_10 12
BI_11 13
BI_12 14
15
BI_13 16
BI_14 17
BI_15 18
BI_16 19
BI_17 20
BI_18 21
COM- 22
[BI_n] can be configured as a specified binary input by PCS-Explorer software (n=01, 02, ……).
Terminal description for NR1504 is shown as follows.
3. NR1508
NR1508A is with a 22-pin connector for 11 binary inputs, and its rated voltage is 220Vdc. Each
binary input of NR1508A has independent negative power input of opto-coupler and can be
configurable. NR1508A′s pickup voltage and dropoff voltage are fixed value, and the range is from
75%Un to 80%Un.
BI_01 01
NR1508A Opto01- 02
BI_02 03
Opto02- 04
BI_03 05
Opto03- 06
BI_04 07
Opto04- 08
BI_05 09
Opto05- 10
BI_06 11
Opto06- 12
BI_07 13
Opto07- 14
BI_08 15
Opto08- 16
BI_09 17
Opto09- 18
BI_10 19
Opto10- 20
BI_11 21
Opto11- 22
[BI_n] can be configured as a specified binary input by PCS-Explorer software (n=01, 02, ……).
Terminal description for NR 1508A is shown as follows.
NOTICE!
A default configuration is given for first four binary signals (BI_01, BI_02, BI_03, BI_04)
in first BI plug-in module, and they are [BI_TimeSyn], [BI_Print], [BI_Maintenance] and
[BI_RstTarg] respectively. They can alos be configured as other signals. Because the
first binary signal [BI_01] is set as [BI_TimeSyn] by default (the state change
information of binary signal [BI_TimeSyn] does not need be displayed), new binary
signal should be added to state change message if it is set as other signal.
It is used to receive clock synchronization signal from clock synchronization device, the binary
input [BI_TimeSyn] will change from “0” to “1” once pulse signal is received. When the device
adopts “Conventional” mode as clock synchronization mode (refer to section “Communication
Settings”), the device can receives PPM (pulse per minute) and PPS (pulse per second). If the
setting [Opt_TimeSyn] is set as other values, this binary input is invalid.
It is used to manually trigger printing latest report when the equipment is configured as manual
printing mode by logic setting [En_AutoPrint]=0. The printer button is located on the panel usually.
If the equipment is configured as automatic printing mode ([En_AutoPrint]=1), report will be printed
automatically as soon as it is formed.
It is used to block communication export when this binary input is energized. During device
maintenance or testing, this binary input is then energized not to send reports via communication
port, local display and printing still work as usual. This binary input should be de-energized when
the device is restored back to normal.
The application of the binary input [BI_Maintenance] for digital substation communication adopting
IEC61850 protocol is given as follows.
a) The protection device should send the state of this binary input to client.
b) When this binary input is energized, the bit “Test” of quality (Q) in the sent message changes
to “1”.
c) When this binary input is energized, the client cannot control the isolator link and circuit
breaker, modify settings and switch setting group remotely.
d) According to the value of the bit “Test” of quality (Q) in the message sent, the client
discriminate whether this message is maintenance message, and then deal with it correspondingly.
If the message is the maintenance message, the content of the message will not be displayed on
real-time message window, audio alarm not issued, but the picture is refreshed so as to ensure
that the state of the picture is in step with the actual state. The maintenance message will be
stored, and can be inquired, in independent window.
a) When this binary input is energized, the bit “Test” in the GOOSE message sent by the
protection device changes to “1”.
b) For the receiving end of GOOSE message, it will compare the value of the bit “Test” in the
GOOSE message received by it with the state of its own binary input (i..e [BI_Maintenance]), the
message will be thought as invalid unless they are conformable.
a) When this binary input of merging unit is energized, the bit “Test” of quality (Q) of sampling
data in the SV message sent change “1”.
b) For the receiving end of SV message, if the value of bit “Test” of quality (Q) of sampling data
in the SV message received is “1”, the relevant protection functions will be disabled, but under
maintenance state, the protection device should calculate and display the magnitude of sampling
data.
c) For duplicated protection function configurations, all merging units of control module
configured to receive sampling should be also duplicated. Both dual protection devices and dual
merging units should be fully independent each other, and one of them is in maintenance state will
not affect the normal operation of the other.
It is used to reset latching signal relay and LCD displaying. The reset is done by pressing a button
on the panel.
NOTICE!
The rated voltage of binary input is optional: 110V, 125V, 220V or 250V, which must be
specified when placed order. It is necessary to check whether the rated voltage of BI
module complies with site DC supply rating before put the relay in service.
There three binary signals are fixed for measurement functions, they are [BI_Rmt/Loc],
[BI_ManSynCls] and [BI_ManOpen] respectively.
“1”: the remote control, all the binary outputs can only be remotely controlled by SCADA or control
centers.
“0” the local control, each binary output can only be applied to open/close CB/DS/ES locally. Each
binary output can also be applied issue a signal locally.
When the device is under local control condition (i.e. [BI_Rmt/Loc] is de-energized), the manual
synchronism check for closing circuit breaker will be initiated if it is energized.
When the device is under local control condition (i.e. [BI_Rmt/Loc] is de-energized), the manual
control for open circuit breaker will be initiated if it is energized.
The following signals can be configured to output contacts controlled by fault detector or output
contacts without controlled by fault detector.
However, the signals which will be control the circuit breaker directly or initate breaker failure
protection must be configured to output contacts controlled by fault detector.
The following signals must be configured to output contacts without controlled by fault detector.
Related signals with voltage switchover and synchrocheck and related signals with AR except
reclosing signal and AR failure signal.
01
BO_01
NR1521A 02
03
BO_02
04
05
BO_03
06
07
BO_04
08
09
BO_05
10
11
BO_06
12
13
BO_07
14
15
BO_08
16
17
BO_09
18
19
BO_10
20
21
BO_11
22
01
BO_01
NR1521C 02
03
BO_02
04
05
BO_03
06
07
BO_04
08
09
BO_05
10
11
BO_06
12
13
BO_07
14
15
BO_08
16
17
BO_09
18
19
BO_10
20
21
BO_11
22
BO plug-in module (NR1521F) is dedicatedly for remote/manual open or closing to circuit breaker,
disconnector and earth switch. 5 pairs of binary outputs (one for open and the other for closing)
can be provided by this BO plug-in module configured in slot 15 if measurement and control
function is equipped with the device. More binary outputs can be provided by another BO plug-in
modules that can be configured in slot 11, 12, 13, 14 if open or closing contacts is not enough.
First pair of binary outputs are used to remote/manual open or close circuit breaker, and second
pair of binary outputs are also used to remote/manual open or close circuit breaker for double
circuit breakers application.
A normally open contact is presented via terminal 21-22 designated as ROS (i.e. remote operation
signal). Whenever any of binary output contacts for open or closing is closed, ROS contact will
close to issue a signal indicating that this device is undergoing a remote operation.
01
BO_CtrlOpn01
NR1521F 02
03
BO_CtrlCls01
04
05
BO_CtrlOpn02
06
07
BO_CtrlCls02
08
09
BO_CtrlOpn03
10
11
BO_CtrlCls03
12
13
BO_CtrlOpn04
14
15
BO_CtrlCls04
16
17
BO_CtrlOpn05
18
19
BO_CtrlCls05
20
21
BO_Ctrl
22
NR1521G can provide 11 output contacts without controlled by fault detector. The first four output
contacts are in parallel with instantaneous operating contacts which are recommended to be
configured as fast signaling contacts to send PLC signal.
01
BO_01
NR1521G 02
03
BO_02
04
05
BO_03
06
07
BO_04
08
09
BO_05
10
11
BO_06
12
13
BO_07
14
15
BO_08
16
17
BO_09
18
19
BO_10
20
21
BO_11
22
NR1580A can provide 6 output contacts with controlled by fault detector. It is a heavy-capacity
binary output plug-in module, which can be used to control the circuit breaker directly.
+ 01
NR1580A BO_01 02
- 03
04
+ 05
BO_02 06
- 07
08
+ 09
BO_03 10
- 11
12
+ 13
BO_04 14
- 15
16
+ 17
BO_05 18
- 19
20
+ 21
BO_06
- 22
7 Settings
Table of Contents
7 Settings .............................................................................................. 7-a
7.1 System Settings .............................................................................................. 7-1
7.1.1 Setting Description............................................................................................................... 7-1
7.5 Control and Synchrocheck for Manual Closing Settings .......................... 7-50
7.5.1 Setting Description............................................................................................................. 7-50
List of Tables
Table 7.1-1 System settings ....................................................................................................... 7-1
The device has some setting groups for protection to coordinate with the mode of power system
operation, one of which is assigned to be active. However, communication settings, system
settings, device settings, logic link settings and measurement and control settings are common for
all protection setting groups.
NOTICE!
All current settings in this chapter are secondary current converted from primary current
by CT ratio. Zero-sequence current or voltage setting is configured according to 3I0 or
3U0 and negative sequence current setting according to I2 or U2.
1. Active_Grp
The number of active setting group, 10 setting groups can be configured for protection settings,
and only one is active at a time
2. PrimaryEquip_Name
It is recognized by the device automatically. Such setting is used for printing messages
3. Opt_SysFreq
4. Un1
5. Un2
6. CBx.I1n
7. I1n_Base
8. I2n_Base
9. f_High_FreqAlm
It is frequency upper limit setting. The device will issue an alarm [Alm_Freq], when system
frequency is higher than the setting.
10. f_Low_FreqAlm
It is frequency lower limit setting. The device will issue an alarm [Alm_Freq], when system
frequency is lower than the setting.
6 Bxx.U_Pickup_BI 55%Un~80%Un
7 Bxx.U_Dropoff_BI 55%Un~80%Un
8 En_MDisk 0 or 1
1. HDR_EncodeMode
2. Opt_Caption_103
3. En_Send_MMS_Qual_Chg
It is used to enable or disable that IEC 61850 communication program uploads tha variation of
data quality.
0: disable
1: enable
4. Opt_DualNetMode_MM
It is used to select network mode of MMS network for the communication with SCADA
0: Single network
5. Bxx.Un_BinaryInput
This setting is used to set voltage level of binary input module. If low-voltage BI module is
equipped, 24V, 30V or 48V can be set according to the actual requirement, and if high-voltage BI
module is equipped, 110V, 125V or 220V can be set according to the actual requirement.
6. Bxx.U_Pickup_BI
This setting is used to set pickup voltage of binary input module. Bxx: this plug-in module is
inserted in slot xx.
7. Bxx.U_Dropoff_BI
This setting is used to set dropoff voltage of binary input module. Bxx: this plug-in module is
inserted in slot xx.
8. En_MDisk
A moveable mdisk is implemented on the MON plug-in module to backup and restore programs,
settings and configurations.
If MON plug-in module is broken, remove the mdisk and put it into a new MON plug-in module, use
the menu on HMI to restore the backup programs and configurations. If DSP plug-in module is
broken, after a new DSP plug-in module is installed, use the menu on HMI to restore the backup
programs and configurations. If the moveable mdisk is broken, after a new mdisk is installed on
the MON plug-in module, use the menu on HMI to back up the current programs and
configurations into the new mdisk.
13 Gateway 000.000.000.000~255.255.255.255
14 En_Broadcast Disable or enable
15 Addr_RS485A 0~255
21 Threshold_Measmt_Net 0~100%
22 Period_Measmt_Net 0~65535s
23 Format_Measmt 0, 1
24 Baud_Printer 4800,9600,19200,38400,57600,115200 (bps)
27 IP_Server_SNTP 000.000.000.000~255.255.255.255
28 IP_StandbyServer_SNTP 000.000.000.000~255.255.255.255
29 OffsetHour_UTC -12~+12 (hrs)
30 OffsetMinute_UTC 0~60 (min)
31 Opt_Display_Status PriValue, SecValue
32 Num_Cyc_PreTrigDFR 0~140 (cycles)
33 En_TCPx_DNP 0 or 1
34 Addr_Slave_TCPx_DNP 0~65519
35 Addr_Master_TCPx_DNP 0~65519
1. IEDNAME
IED name of this device. If this setting is modified, the IED name in ".cid" file will be changed
simultaneously and vice versa.
IP address of Ethernet port 1, Ethernet port 2, Ethernet port 3 and Ethernet port 4
Subnet mask of Ethernet port 1, Ethernet port 2, Ethernet port 3 and Ethernet port 4
They are used for Ethernet communication based on the IEC 60870-5-103 protocol. When the IEC
61850 protocol is applied, the IP address of Ethernet A will be GOOSE source MAC address.
5. Gateway
6. En_Broadcast
This setting is only used only for IEC 60870-5-103 protocol. If NR network IEC 60870-5-103
protocol is used, the setting must be set as “1”.
7. Addr_RS485A, Addr_RS485B
They are the device′s communication address used to communicate with the SCADA or RTU via
serial ports (port A and port B).
8. Baud_RS485A, Baud_RS485B
9. Protocol_RS485A, Protocol_RS485B
Resv1: Reserved 1
NOTICE!
Above table listed all the communication settings, the device delivered to the user
maybe only show some settings of them according to the communication interface
configuration. If only the Ethernet ports are applied, the settings about the serial ports
(port A and port B) are not listed in this submenu. And the settings about the Ethernet
ports only listed in this submenu according to the actual number of Ethernet ports.
The standard arrangement of the Ethernet port is two, at most four (predetermined
when ordering). Set the IP address according to actual arrangement of Ethernet
numbers and the un-useful port/ports need not be configured. If PCS-Explorer
configuration tool auxiliary software is connected with this device through the Ethernet,
the IP address of PCS-Explorer must be set as one of the available IP address of this
device.
10. Threshold_Measmt_Net
11. Period_Measmt_Net
The time period for equipment sends measurement data to SCADA through IEC 60870-5-103
protocol via Ethernet port.
12. Format_Measmt
The setting is used to select the format of measurement data sent to SCADA through IEC
60870-5-103 protocol.
1: GDD data type through IEC103 protocol is 7, i.e. 754 short real number of IEEE standard
13. Baud_Printer
14. En_AutoPrint
If automatic print is required for fault report after protection operating, it is set as “1”. Otherwise, it
should be set to “0”.
15. Opt_TimeSyn
There are four selections for clock synchronization of device shown as follow.
Conventional
PPS (RS-485): Pulse per second (PPS) via RS-485 differential level
PPM (DIN): Pulse per minute (PPM) via the binary input [BI_TimeSyn]
PPS (DIN): Pulse per second (PPS) via the binary input [BI_TimeSyn]
SAS
Advanced
PPS (Fiber) PPS: Pulse per second (PPS) via optical-fibre interface
NoTimeSync
When no time synchronization signal is connected to the device, please select this option and the
alarm message [Alm_TimeSyn] will not be issued anymore.
“Conventional” mode and “SAS” mode are always be supported by the device, but “Advanced”
mode is only supported when NET-DSP module is equipped. The alarm signal [Alm_TimeSyn]
may be issued to remind user loss of time synchronization signals.
1) When “SAS” is selected, if there is no conventional clock synchronization signal, the device
will not send the alarm signal [Alm_TimeSyn]. When “Conventional” mode is selected, if there
is no conventional clock synchronization signal, “SAS” mode will be enabled automatically
with the alarm signal [Alm_TimeSyn] issued simultaneously.
3) When “NoTimeSyn” mode is selected, the device will not send alarm signals without time
synchronization signal. But the device can be still synchronized if receiving time
synchronization signal.
NOTICE!
The clock message via IEC 60870-5-103 protocol is invalid when the device receives
the IRIG-B signal through RCS-485 port.
16. IP_Server_SNTP
It is the address of the SNTP time synchronization server which sends SNTP timing messages to
the relay or BCU.
17. IP_StandbyServer_SNTP
If the IEC61850 protocol is adopted in substations, the time tags of communication messages are
required according to UTC (Universal Time Coordinated) time.
The setting [OffsetHour_UTC] is used to set the hour offset of the current time zone to the GMT
(Greenwich Mean Time) zone; for example, if a relay is applied in China, the time zone of China is
east 8th time zone, so this setting is set as “8”. The setting [OffsetMinute_UTC] is used to set the
minute offset of the current time zone to the GMT zone.
st nd rd th th
Time zone GMT zone East 1 East 2 East 3 East 4 East 5
Setting 0 1 2 3 4 5
th th th th th
Time zone East 6 East 7 East 8 East 9 East 10 East 11th
Setting 6 7 8 9 10 11
th st nd rd th th
Time zone East/West 12 West 1 West 2 West 3 West 4 West 5
Setting 12/-12 -1 -2 -3 -4 -5
th th th th th th
Time zone West 6 West 7 West 8 West 9 West 10 West 11
Setting -6 -7 -8 -9 -10 -11
19. Opt_Display_Status
This setting is used to set display mode of current and voltage in fault records, primary value or
secondary value. The sampled values of current and voltage are displayed as secondary value by
default. When it is set as primary value, both secondary voltage and secondary current are
converted into primary voltage and primary current according to rated secondary and primary
value of VT and CT respectively.
20. Num_Cyc_PreTrigDFR
The setting is used to set the cycle number recorded by the device before the trigger element
operating.
21. En_TCPx_DNP
The logic setting is used to enable or disable network No.x DNP client. (x=1, 2, 3, 4)
1: enable
0: disable
When network No.x DNP client is not configured to be in service by PCS-Explorer, DNP client
settings corresponding to network No.x will be hidden.
22. Addr_Slave_TCPx_DNP
23. Addr_Master_TCPx_DNP
24. IP_Master_TCPx_DNP
25. Opt_Map_TCPx_DNP
26. Obj01DefltVar_TCPx_DNP
27. Obj02DefltVar_TCPx_DNP
28. Obj30DefltVar_TCPx_DNP
AI32Int: Analog Input with a flag octet and a 32-bit, signed integer value
AI16Int: Analog Input with a flag octet and a 16-bit, signed integer value
AI32Flt: Analog Input with a flag octet and a single-precision, floating-point value
29. Obj32DefltVar_TCPx_DNP
AI32IntEvWoutT: Analog Input Event with a flag octet and a 32-bit, signed integer value (but
without time-of-occurence)
AI16IntEvWoutT: Analog Input Event with a flag octet and a 16-bit, signed integer value (but
without time-of-occurence)
AI32FltEvWoutT: Analog Input Event with single-precision, floating-point value (but without
time-of-occurence)
30. Obj40DefltVar_TCPx_DNP
AO32Int: Analog Output with a flag octet and a 32-bit, signed integer value
AO16Int: Analog Output with a flag octet and a 16-bit, signed integer value
AO32Flt: Analog Output with a flag octet and a single-precision, floating-point value
31. t_AppLayer_TCPx_DNP
32. t_KeepAlive_TCPx_DNP
33. En_UR_TCPx_DNP
The logic setting is used to enable or disable the unsolicited message function of network No.x
DNP client. (x=1, 2, 3, 4)
1: enable
0: disable
34. Num_URRetry_TCPx_DNP
It is the online retransmission number of the unsolicited message of network No.x DNP client. (x=1,
2, 3, 4)
35. t_UROfflRetry_TCPx_DNP
It is the offline timeout of the unsolicited message of network No.x DNP client. (x=1, 2, 3, 4)
36. Class_BI_TCPx_DNP
It is the class level of the “Binary Input” of network No.x DNP client. (x=1, 2, 3, 4)
37. Class_AI_TCPx_DNP
It is the class level of the “Analog Input” of network No.x DNP client. (x=1, 2, 3, 4)
38. t_Select_TCPx_DNP
39. t_TimeSynIntvl_TCPx_DNP
It is the time interval of the time synchronization function of network No.x DNP client. (x=1, 2, 3, 4)
ManClsBI
CBPos
15 SOTF.Opt_Mode_ManCls Option of manual SOTF mode ManClsBI/ CBPos
AutoInit
All
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 1 of phase ANSIE
9 50/51P1.Opt_Curve
overcurrent protection ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
UserDefine
Time multiplier setting for stage 1 of inverse-time
10 50/51P1.TMS 0.010~200.000
phase overcurrent protection
Minimum operating time for stage 1 of inverse-time
11 50/51P1.tmin 0.000~20.000 (s)
phase overcurrent protection
Constant “α” for stage 1 of customized inverse-time
12 50/51P1.Alpha 0.010~5.000
characteristic phase overcurrent protection
Constant “C” for stage 1 of customized inverse-time
13 50/51P1.C 0.000~20.000
characteristic phase overcurrent protection
Constant “K” for stage 1 of customized inverse-time
14 50/51P1.K 0.050~20.000
characteristic phase overcurrent protection
Current setting for stage 2 of phase overcurrent
15 50/51P2.I_Set (0.050~30.000)×In (A)
protection
Time delay for stage 2 of phase overcurrent
16 50/51P2.t_Op 0.000~20.000 (s)
protection
17 50/51P2.En Enable stage 2 of phase overcurrent protection 0 or 1
Enable auto-reclosing blocked when stage 2 of
18 50/51P2.En_BlkAR 0 or 1
phase overcurrent protection operates
Enable stage 2 of phase overcurrent protection is
19 50/51P2.En_VTS_Blk 0 or 1
blocked by VT circuit failure
Non_Directional
Direction option for stage 2 of phase overcurrent
20 50/51P2.Opt_Dir Forward
protection
Reverse
Enable second harmonic blocking for stage 2 of
21 50/51P2.En_Hm2_Blk 0 or 1
phase overcurrent protection
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 2 of phase
22 50/51P2.Opt_Curve ANSIE
overcurrent protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Time multiplier setting for stage 2 of inverse-time
23 50/51P2.TMS 0.010~200.000
phase overcurrent protection.
Minimum operating time for stage 2 of inverse-time
24 50/51P2.tmin 0.000~20.000 (s)
phase overcurrent protection
Current setting for stage 3 of phase overcurrent
25 50/51P3.I_Set (0.050~30.000)×In (A)
protection
Time delay for stage 3 of phase overcurrent
26 50/51P3.t_Op 0.000~20.000 (s)
protection
27 50/51P3.En Enable stage 3 of phase overcurrent protection 0 or 1
Enable auto-reclosing blocked when stage 3 of
28 50/51P3.En_BlkAR 0 or 1
phase overcurrent protection operates
Enable stage 3 of phase overcurrent protection is
29 50/51P3.En_VTS_Blk 0 or 1
blocked by VT circuit failure
Non_Directional
Direction option for stage 3 of phase overcurrent
30 50/51P3.Opt_Dir Forward
protection
Reverse
Enable second harmonic blocking for stage 3 of
31 50/51P3.En_Hm2_Blk 0 or 1
phase overcurrent protection
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 3 of phase
32 50/51P3.Opt_Curve ANSIE
overcurrent protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Non_Directional
22 50/51G2.Opt_Dir Direction option for stage 2 of earth fault protection Forward
Reverse
Enable second harmonic blocking for stage 2 of
23 50/51G2.En_Hm2_Blk 0 or 1
earth fault protection
Enable blocking for stage 2 of earth fault protection
24 50/51G2.En_Abnor_Blk 0 or 1
under abnormal conditions
Enable blocking for stage 2 of earth faultv protection
25 50/51G2.En_CTS_Blk 0 or 1
under CT failure conditions
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 2 of earth
26 50/51G2.Opt_Curve ANSIE
fault protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Time multiplier setting for stage 2 of inverse-time
27 50/51G2.TMS 0.010~200.000
earth fault protection
Minimum operating time for stage 2 of inverse-time
28 50/51G2.tmin 0.050~20.000 (s)
earth fault protection
29 50/51G3.3I0_Set Current setting for stage 3 of earth fault protection (0.050~30.000)×In (A)
30 50/51G3.t_Op Time delay for stage 3 of earth fault protection 0.000~20.000 (s)
31 50/51G3.t_ShortDly Short time delay for stage 3 of earth fault protection 0.000~20.000 (s)
32 50/51G3.En Enable stage 3 of earth fault protection 0 or 1
Enable short time delay for stage 3 of earth fault
33 50/51G3.En_ShortDly 0 or 1
protection
Enable auto-reclosing blocked when stage 3 of
34 50/51G3.En_BlkAR 0 or 1
earth fault protection operates
Non_Directional
35 50/51G3.Opt_Dir Direction option for stage 3 of earth fault protection Forward
Reverse
Enable second harmonic blocking for stage 3 of
36 50/51G3.En_Hm2_Blk 0 or 1
earth fault protection
Enable blocking for stage 3 of earth fault protection
37 50/51G3.En_Abnor_Blk 0 or 1
under abnormal conditions
Enable blocking for stage 3 of earth fault protection
38 50/51G3.En_CTS_Blk 0 or 1
under CT failure conditions
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 3 of earth
39 50/51G3.Opt_Curve ANSIE
fault protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Time multiplier setting for stage 3 of inverse-time
40 50/51G3.TMS 0.010~200.000
earth fault protection
Minimum operating time for stage 3 of inverse-time
41 50/51G3.tmin 0.050~20.000 (s)
earth fault protection
42 50/51G4.3I0_Set Current setting for stage 4 of earth fault protection (0.050~30.000)×In (A)
43 50/51G4.t_Op Time delay for stage 4 of earth fault protection 0.000~20.000 (s)
44 50/51G4.t_ShortDly Short time delay for stage 4 of earth fault protection 0.000~20.000 (s)
45 50/51G4.En Enable stage 4 of earth fault protection 0 or 1
Enable short time delay for stage 4 of earth fault
46 50/51G4.En_ShortDly 0 or 1
protection
Enable auto-reclosing blocked when stage 4 of
47 50/51G4.En_BlkAR 0 or 1
earth fault protection operates
Non_Directional
48 50/51G4.Opt_Dir Direction option for stage 4 of earth fault protection Forward
Reverse
Enable second harmonic blocking for stage 4 of
49 50/51G4.En_Hm2_Blk 0 or 1
earth fault protection
Enable blocking for stage 4 of earth fault protection
50 50/51G4.En_Abnor_Blk 0 or 1
under abnormal conditions
Enable blocking for stage 4 of earth fault protection
51 50/51G4.En_CTS_Blk 0 or 1
under CT failure conditions
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 4 of earth
52 50/51G4.Opt_Curve ANSIE
fault protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Time multiplier setting for stage 4 of inverse-time
53 50/51G4.TMS 0.010~200.000
earth fault protection
Minimum operating time for stage 4 of inverse-time
54 50/51G4.tmin 0.050~20.000 (s)
earth fault protection
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 1 of ANSIE
9 50/51Q1.Opt_Curve
negative-sequence overcurrent protection ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
UserDefine
Time multiplier setting for stage 1 of inverse-time
10 50/51Q1.TMS 0.010~200.000
negative-sequence overcurrent protection
Minimum operating time for stage 1 of inverse-time
11 50/51Q1.tmin 0.050~20.000 (s)
negative-sequence overcurrent protection
Constant “α” for stage 1 of customized inverse-time
12 50/51Q1.Alpha characteristic negative-sequence overcurrent 0.010~5.000
protection
Constant “C” for stage 1 of customized inverse-time
13 50/51Q1.C characteristic negative-sequence overcurrent 0.000~20.000
protection
Constant “K” for stage 1 of customized inverse-time
14 50/51Q1.K characteristic negative-sequence overcurrent 0.050~20.000
protection
Current setting for stage 2 of negative-sequence
15 50/51Q2.I2_Set (0.050~30.000)×In (A)
overcurrent protection
Ratio coefficient (I2/I1) for stage 2 of
16 50/51Q2.I2/I1_Set 0.00~1.00
negative-sequence overcurrent protection
Time delay for stage 2 of negative-sequence
17 50/51Q2.t_Op 0.000~20.000 (s)
overcurrent protection
Enable stage 2 of negative-sequence overcurrent
18 50/51Q2.En 0 or 1
protection
Enable auto-reclosing blocked when stage 2 of
19 50/51Q2.En_BlkAR 0 or 1
negative-sequence overcurrent protection operates
Non_Directional
Direction option for stage 2 of negative-sequence
20 50/51Q2.Opt_Dir Forward
overcurrent protection
Reverse
Enable blocking for stage 2 of negative-sequence
21 50/51Q2.En_Abnor_Blk 0 or 1
overcurrent protection under abnormal conditions
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 3 of
34 50/51Q3.Opt_Curve ANSIE
negative-sequence overcurrent protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Time multiplier setting for stage 3 of inverse-time
35 50/51Q3.TMS 0.010~200.000
negative-sequence overcurrent protection
Minimum operating time for stage 3 of inverse-time
36 50/51Q3.tmin 0.050~20.000 (s)
negative-sequence overcurrent protection
Current setting for stage 4 of negative-sequence
37 50/51Q4.I2_Set (0.050~30.000)×In (A)
overcurrent protection
Ratio coefficient (I2/I1) for stage 4 of
38 50/51Q4.I2/I1_Set 0.00~1.00
negative-sequence overcurrent protection
Time delay for stage 4 of negative-sequence
39 50/51Q4.t_Op 0.000~20.000 (s)
overcurrent protection
Enable stage 4 of negative-sequence overcurrent
40 50/51Q4.En 0 or 1
protection
Enable stage 4 of negative-sequence overcurrent
41 50/51Q4.En_Trp 0 or 1
protection operate to trip or alarm.
Enable auto-reclosing blocked when stage 4 of
42 50/51Q4.En_BlkAR 0 or 1
negative-sequence overcurrent protection operates
Non_Directional
Direction option for stage 4 of negative-sequence
43 50/51Q4.Opt_Dir Forward
overcurrent protection
Reverse
Enable blocking for stage 4 of negative-sequence
44 50/51Q4.En_Abnor_Blk 0 or 1
overcurrent protection under abnormal conditions
Enable blocking for stage 4 of negative-sequence
45 50/51Q4.En_CTS_Blk 0 or 1
overcurrent protection under CT failure conditions
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 4 of
46 50/51Q4.Opt_Curve ANSIE
negative-sequence overcurrent protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Time multiplier setting for stage 4 of inverse-time
47 50/51Q4.TMS 0.010~200.000
negative-sequence overcurrent protection
Minimum operating time for stage 4 of inverse-time
48 50/51Q4.tmin 0.050~20.000 (s)
negative-sequence overcurrent protection
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 1 of overvoltage
9 59P1.Opt_Curve ANSIE
protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Time multiplier setting for stage 1 of inverse-time
10 59P1.TMS 0.010~200.000
overvoltage protection
Minimum delay for stage 1 of inverse-time overvoltage
11 59P1.tmin 0.050~20.000 (s)
protection
12 59P2.U_Set Voltage setting for stage 2 of overvoltage protection Un~2Unn (V)
13 59P2.t_Op Time delay for stage 2 of overvoltage protection 0.000~30.000 (s)
14 59P2.En Enable stage x of overvoltage protection 0 or 1
Option of 1-out-of-3 mode or 3-out-of-3 mode for stage
15 59P2.Opt_1P/3P 0 or 1
2 of overvoltage protection
Option of phase-to-phase voltage or phase voltage for
16 59P2.Opt_Up/Upp 0 or 1
stage 2 of overvoltage protection
Enable stage 2 of overvoltage protection for alarm
17 59P2.En_Alm 0 or 1
purpose
Enable transfer trip controlled by CB open position for
18 59P2.En_52b_TT 0 or 1
stage 2 of overvoltage protection
Enable stage 2 of overvoltage protection operate to
19 59P2.En_TT 0 or 1
initiate transfer trip
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 2 of overvoltage
20 59P2.Opt_Curve ANSIE
protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
DefTime
IECN
IECV
IECE
IECST
IECLT
Option of characteristic curve for stage 3 of
34 27P3.Opt_Curve ANSIE
undervoltage protection
ANSIV
ANSI
ANSIM
ANSILTE
ANSILTV
ANSILT
Time multiplier setting for stage 3 of inverse-time
35 27P3.TMS 0.010~200.000
undervoltage protection
Minimum delay for stage 3 of inverse-time undervoltage
36 27P3.tmin 0.050~20.000 (s)
protection
NOTICE!
NOTICE!
NOTICE!
NOTICE!
NoVoltSel
Option of circuit breaker configuration, and it
DblBusOneCB
5 CBx.CBConfigMode should be set as “NoVoltSel” if no voltage selection
3/2BusCB
is adopted.
3/2TieCB
NOTICE!
NOTICE!
Each logic link settings is an “AND” condition of enabling the relevant function with the
corresponding binary input and logic setting. Through SAS or RTU, logic link settings can be set
as “1” or “0”; and it means that the relevant function can be in service or out of service through
remote command. It provides convenience for operation management.
The function link settings can be defined according to project specification through the
configuration tool, PCS-Explorer.
Thses settings are applied to configure the status change confirmation time for No.xx double point
binary inputs. Up to 15 virtual double point binary inputs are provided in this device.
If a double point binary input changes from normal status to invalid status, i.e.: double point error
occurs, [CSWIxx.t_DPU_DPS] will be applied as the debouncing time for No.xx double point
binary input. (xx=01, 02….15)
Table of Contents
8 Human Machine Interface ................................................................ 8-a
8.1 Overview .......................................................................................................... 8-1
8.1.1 Keypad Operation ................................................................................................................ 8-2
List of Figures
Figure 8.1-1 Front panel .............................................................................................................. 8-1
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel .................................. 8-4
Figure 8.1-5 Rear view and terminal definition of NR1102D ................................................... 8-5
List of Tables
Table 8.1-1 Definition of the 8-core cable ................................................................................. 8-4
The operator can access the protective device from the front panel. Local communication with the
protective device is possible using a computer via a multiplex RJ45 port on the front panel.
Furthermore, remote communication is also possible using a PC with the substation automation
system via rear RS485 port or rear Ethernet port. The operator is able to check the protective
device status at any time.
This chapter describes human machine interface (HMI), and give operator an instruction about
how to display or print event report, setting and so on through HMI menu tree and display metering
value, including r.m.s. current, voltage and frequency etc. through LCD. Procedures to change
active setting group or a settable parameter value through keypad is also described in details.
NOTICE!
About the measurements and metering in menu “Measurements”, please refer to the
following description:
“Measurements2” is used to display measured values from fault detector DSP. The
measurement values can be displayed in primary value or secondary value by the
setting [Opt_Display_Status].
“Metering” is used to display metering values of active and reactive energy. The
metering values are always displayed in primary value.
8.1 Overview
The human-machine interface consists of a human-machine interface (HMI) module which allows
a communication to be as simple as possible for the user.
1 11
HEALTHY PCS-902
2 12
5
ALARM
3 13
4 14
GRP
5 15
6 16 ENT
ESC
7 17
4
8 18
1
9 19
3
10 20
The HMI module helps to draw your attention to something that has occurred which may activate a
LED or a report displayed on the LCD. Operator can locate the data of interest by navigating the
keypad. The function of HMI module:
ENT
ESC
1. “ESC”:
2. “ENT”:
3. “GRP”
Page up/down
HEALTHY
ALARM
Steady Green Lit when the equipment is in service and ready for operation.
NOTICE!
“HEALTHY” LED can only be turned on by energizing the device and no abnormality
detected.
“ALARM” LED is turned on when abnormalities of device occurs like above mentioned
and can be turned off after abnormalities are removed except alarm report [CTS.Alm]
which can only be reset only when the failure is removed and the device is rebooted or
re-energized.
Other LED indicators with no labels are configurable and user can configure them to be
lit by signals of operation element, alarm element and binary output contact according
to requirement through PCS-Explorer software, but as drawn in figure, 2 LEDs are fixed
as the signals of “HEALTHY” (green) and “ALARM” (yellow), 18 LEDs are configurable
with selectable color among green, yellow and red.
P2
P1
P3
Figure 8.1-4 Corresponding cable of the RJ45 port in the front panel
P1: To connect the multiplex RJ45 port. An 8-core cable is applied here.
The definition of the 8-core cable in the above figure is introduced in the following table.
The Ethernet port can be used to communication with PC via auxiliary software (PCS-Explorer)
after connecting the protection device with PC, so as to fulfill on-line function (please refer to the
instruction manual of PCS-Explorer). At first, the connection between the protection device and PC
must be established. Through setting the IP address and subnet mask of corresponding Ethernet
interface in the menu “Settings→Device Setup→Comm Settings”, it should be ensured that the
protection device and PC are in the same network segment. For example, setting the IP address
and subnet mask of network A. (using network A to connect with PC)
The IP address and subnet mask of protection device should be [IP_LAN1]= 198.87.96.XXX,
[Mask_LAN1]=255.255.255.0, [En_LAN1]=1. (XXX can be any value from 0 to 255 except 102)
If the logic setting [En_LAN1] is non-available, it means that network A is always enabled.
NR1102D
ETHERNET
Network A
Network B
Network C
Network D
NOTICE!
If using other Ethernet port, for example, Ethernet B, the logic setting [En_LAN2] must
be set as “1”.
Press “▲” to enter the main menu with the interface as shown in the following diagram:
MainMenu
Language
Clock
Quick Menu
For the first powered device, there is no record in quick menu. Press “▲” to enter the main menu
with the interface as shown in the following diagram:
Measurements
Status
Records
Settings
Print
Local Cmd
Information
Test
Clock
Language
The descriptions about menu are based on the maximized configuration, for a specific project, if
some function is not available, the corresponding submenu will hidden.
Main Menu
Measurements
Status
Records
Settings
Local Cmd
Information
Test
Clock
Language
Under main interface, press “▲” to enter main menu, and select submenu by pressing “▲”, “▼”
and “ENT”. The command menu adopts a tree shaped content structure. The above diagram
provides the integral structure and all main menus (first-level menus) under menu tree of the
device.
Main Menu
Measurements
Measurements1
Measurements2
Measurements3
Metering
This menu is used to display real-time measured values, including AC voltage, AC current, phase
angle and calculated quantities. These data can help users to acquaint the device′s status. This
menu comprises following submenus. Please refer to section “Measurement” about the detailed
measured values.
8.2.3.2 Status
Main Menu
Status
Inputs
Outputs
Superv State
This menu is used to display real time input signals, output signals and alarm signals of the device.
These data can help users to acquaint the device′s status. This menu comprises following
submenus. Please respectively refer to section “Signal List” about the detailed introduction of input
signals and output signals, and section “Supervision Alarms” about the detailed introduction of
alarm signals.
Main Menu
Status
Inputs
Contact Inputs
GOOSE Inputs
Prot Ch Inputs
1 Contact Inputs Display states of binary inputs derived from opto-isolated channels
3 Prot Ch Inputs Display states of binary inputs received from protection channel.
Main Menu
Status
Outputs
Contact Outputs
GOOSE Outputs
Interlock Status
Prot Ch Outputs
Main Menu
Status
Superv State
Prot Superv
FD Superv
GOOSE Superv
SV Superv
BCU Superv
1 Prot Superv Display states of self-supervision signals from protection calculation DSP
8.2.3.3 Records
Main Menu
Records
Disturb Records
Superv Events
IO Events
Device Logs
Control Logs
Clear Records
This menu is used to display all kinds of records, including the disturbance records, supervision
events, binary events and device logs, so that the operator can load to view and use as the
reference of analyzing accidents and repairing the device. All records are stored in non-volatile
memory, it can still record them even if it loses its power.
8.2.3.4 Settings
Main Menu
Settings
System Settings
Prot Settings
BCU Settings
Logic Links
Device Setup
This menu is used to check the device setup, system parameters, protection settings and logic
links settings, as well as modifying any of the above setting items. Moreover, it can also execute
the setting copy between different setting groups.
Check or modify the logic links settings, including function links, SV links,
4 Logic Links
GOOSE links and spare links
Main Menu
Settings
Prot Settings
12 SOTF Settings Check or modify SOTF distance and overcurrent protection settings
14 VTF OC Settings Check or modify overcurrent protection settings for VT circuit failure
28 VTS/CTS Settings Check or modify VT circuit supervision and CT circuit supervision settings
Main Menu
Settings
BCU Settings
FUN Settings
BI Settings
Control Settings
Interlock Settings
2 CB1 Syn Settings Check or modify manual sysnchronism check settings for circuit breaker 1
3 CB2 Syn Settings Check or modify manual sysnchronism check settings for circuit breaker 2
Main Menu
Settings
Logic Links
Function Links
SV Links
Main Menu
Settings
Device Setup
Device Settings
Comm Settings
Label Settings
3 Label Settings Check or modify the label settings of each protection element.
8.2.3.5 Print
Main Menu
Device Info
Settings
Disturb Records
Superv Events
IO Events
Prot Ch Superv
Prot Ch Statistics
Device Status
Waveforms
IEC103 Info
Cancel Print
This menu is used to print device description, settings, all kinds of records, waveforms, information
related with IEC60870-5-103 protocol, channel state and channel statistic.
Print the statistic report of optical fibre channel, which is formed A.M.
7 Prot Ch Statistics
9:00 every day
Print the current state of the device, including the sampled value of
8 Device Status
voltage and current, the state of binary inputs, setting and so on
Main Menu
Settings
System Settings
Prot Settings
BCU Settings
Logic Links
Device Setup
All Settings
Main Menu
Settings
Prot Settings
Main Menu
Settings
BCU Settings
FUN Settings
BI Settings
Control Settings
Interlock Settings
All Settings
2 CB1 Syn Settings Print manual sysnchronism check settings for circuit breaker 1
3 CB2 Syn Settings Print manual sysnchronism check settings for circuit breaker 2
Main Menu
Settings
Logic Links
Function Links
SV Links
All Settings
Main Menu
Settings
Device Setup
Device Settings
Comm Settings
Label Settings
All Settings
Main Menu
Prot Ch Superv
Channel 1
Channel 2
Print the self-check information of optical fibre channel 1, which is made of some
1 Channel 1
hexadecimal characters and used to developer analyze channel state
Print the self-check information of optical fibre channel 2, which is made of some
2 Channel 2
hexadecimal characters and used to developer analyze channel state
Main Menu
Prot Ch Statistics
Channel 1
Channel 2
Print the statistic report of optical fibre channel 1, which is formed A.M. 9:00 every
1 Channel 1
day
Print the statistic report of optical fibre channel 2, which is formed A.M. 9:00 every
2 Channel 2
day
Main Menu
Waveforms
Wave
Main Menu
Local Cmd
Reset Target
Trig Oscillograph
Control
Download
Clear Counter
This menu is used to reset the tripping relay with latch, indicator LED, LCD display, and as same
as the reset function of binary inputs. This menu provides a method of manually recording the
current waveform data of the device under normal condition for printing and uploading SAS.
Besides, it can send out the request of program download, clear statistic information about
GOOSE, SV, AR, FO channel and energy.
1 Reset Target Reset the local signal, indicator LED, LCD display and so on
8.2.3.7 Information
Main Menu
Information
Version Info
Board Info
MOT Info
In this menu, LCD can display software information of all kinds of intelligent plug-in modules,
which consists of version, creating time of software, CRC codes and management sequence
number. Besides, plug-in module information and MOT information can also be viewed.
Display software information of DSP module, MON module and HMI module,
1 Version Info which consists of version, creating time of software, CRC codes and
management sequence number.
2 Board Info Monitor the current working state of each intelligent module.
8.2.3.8 Test
Main Menu
Test
Prot Ch Counter
SV Comm Counter
Device Test
Internal Signal
AR Counter
HMI Setup
This menu is mainly used for developers to debug the program and for engineers to maintain the
device. It can be used to fulfill the communication test function. It is also used to generate all kinds
of reports or events to transmit to the SAS without any external input, so as to debug the
communication on site. Besides, it can also display statistic information about GOOSE, SV, AR
and FO channel.
7 HMI Setup Configure LCD display and check LCD display and LED indicators
Main Menu
Test
Prot Ch Counter
Ch1 Counter
Ch2 Counter
Main Menu
Test
Device Test
Disturb Events
Superv Events
IO Events
View the relevant information about disturbance records (only used for
1 Disturb Events
debugging persons)
View the relevant information about supervision events (only used for
2 Superv Events
debugging persons)
View the relevant information about binary events (only used for debugging
3 IO Events
persons)
Users can respectively execute the test automatically or manually by selecting commands “All
Test” or “Select Test”.
Main Menu
Test
Device Test
Disturb Events
All Test
Select Test
Main Menu
Test
Device Test
Superv Events
All Test
Select Test
Main Menu
Test
Device Test
IO Events
All Test
Select Test
Main Menu
Test
AR Counter
CB1 AR Counter
CB2 AR Counter
Main Menu
Test
HMI Setup
Contrast
BacklitDur
LgtIntnsty
SupervLCD
SupervLED
8.2.3.9 Clock
The current time of internal clock can be viewed here. The time is displayed in the form
YY-MM-DD and hh:mm:ss. All values are presented with digits and can be modified.
8.2.3.10 Language
According to different access authority, the corresponding operations to the device by LCD panel
can be allowed to perform. For the operation that requires authorization, the corresponding user
logs in and the correct password must be input after the operation can be performed.
Taking “User1” as an example, four kinds of authorities: View, Control, Setting, Project are shown
as below.
1. Press the “▲” to enter the main menu, the following interface will be shown when performing
an operation. (Multi-users have been configured in advance)
2. Press the “◄” or “►” to select username, and press the “ESC” to exit this menu
Username User1
Password
3. Press the “ENT” or “▼” to move, and the following interface will be shown after the username
is confirmed.
Username User1
Password ******
0 1 2 3 4 5 6 7 8 9 [OK]
4. Press the “◄” or “►” to select number or letter, and press “ENT” to ensure selected character.
5. Press the “▲” or “▼” to page up/down to select previous group or next group characters.
7. When the password reaches to 8 bits, the device will verify whether the username and
password are correctly. If the password is shorter than 8 bits, select and press “OK” to begin
to verify whether the username and password are correctly.
8. Press the “ESC” to cancel entered character during entering password, and the password will
be cleared if the password check fails. When the password is cleared, press the “ESC” to
select the username again.
9. The device provides the function of password memory, the following interface will be shown if
the valid time of the password is set and last entered password is no timeout.
Username User1
Password *******
10. Press the “ENT” to verify the password, press the “◄” or “►” to switch the username and the
password will be cleared, and press the “ESC” to exit the interface.
11. If the password is correct and the user owns the authority of the operation performed, the
operation will be performed.
If the password is incorrect, the device will issue an alarm signal “Password Error”. If the password
is correct but the user has no the authority of the operation performed, the device will issue an
alarm signal “Unauthorized”. If the password is incorrect or the user has no the authority of the
operation performed more than three times, the device will issue an alarm signal “PWD Error or
Unauthorized, Screen Locked” and the device will return to main interface after the screen is
locked for 1 minutes, which will be recorded in device log.
and then it will return to the previous display interface automatically. Device logs will not pop up
and can only be viewed by navigating the corresponding menu.
1. Right-click the menu “LCD Graph”, and select the menu item “Edit Shortcut Key” to display
the configuration interface of function key shortcuts as shown below.
2. In configuration interface, double-click the table item in the list of “Extend Command” to select
LCD extend command of dropdown list corresponding with keypads in front panel as shown
below. Select the first blank item in dropdown list to cancel the setup.
3. Double-click the table item in the list of “Attribute” to edit the attribute of keypad in front panel
as shown below. When the attribute is set as “1”, the corresponding operation can not execute
unless input correct password. When the attribute is set as “0” or blank, password is not
required. After finishing configuration, click the button “OK”.
4. The name description of extend command can be modified in signal setup interface, the
operation “Refresh” in the interface of “Source” must be execute at first before configuring
function shortcuts key or generating drive file package.
5. Right-click device node and execute the menu “Compress Driver File” to generate drive file
package of the device. The file “LCDConfig.txt” in drive file package of the device records
related contents about shortcuts key. If shortcuts keys are not required, set “Extend
Command” corresponding with function shortcuts key as blank, and generate drive file
package of the device again.
In general, the function of “GRP” is switch setting group, however, the original function of “GRP” is
blocked when configuring function shortcuts key. (the setting group can be switched by shortcuts
key, binary input or modifying the setting) Under main interface, press “GRP” to display the
interface of function shortcuts key and press “ESC” to return to main interface.
Shortcut keys
[ ] LCD.ExtCmd04
[ ] LCD.ExtCmd05
[ ] LCD.ExtCmd06
[ ] LCD.ExtCmd07
[ + ] LCD.ExtCmd08
[ - ] LCD.ExtCmd09
[ ENT ] LCD.ExtCmd10
The device support 10 extended command, LCD.ExtCmd01~LCD.ExtCmd10, and the name can
be modified by PCS-Explorer. The first three extend command is fixed in program, so only
LCD.ExtCmd04~LCD.ExtCmd10 are configurable, and configured as any of seven function
shortcuts key (“▲”, “▼”, “◄”, “►”, “+”, “-” and “ENT”).
Password:
000
Under the interface of function shortcuts key, press a shortcuts key to execute corresponding
operation. If the attribute of the extend command is set as “1”, the corresponding operation can not
execute unless input correct password. The extend command executed by shortcuts key outputs a
pulse signal with 500ms, and for the operation requiring latching signal, the device provides
“T_FF” and “RS_FF” to fulfill the application, which can be configured by PCS-Explorer.
The device can display single line diagram (SLD) and primary operation information, it can support
wiring configuration function. LCD configuration file can be downloaded via the network. Remote
control operation through single line diagram is also supported.
Under normal condition, LCD will display the following interface. LCD adopts white color as its
backlight that is activated if once there is any keyboard operation, moreover, the backlight will be
extinguished automatically if no keyboard operation is detected for a duration.
S 2010-06-08 10:10:00
Ia 0.00A
Ib 0.00A
Ic 0.00A
3I0 0.00A
Ua 0.02V
Ub 0.00V
Uc 0.00V
3U0 0.02V
U_Syn 0.00V
f 50.00Hz
The content displayed on the screen contains: the current date and time of the device (with a
format of yyyy-mm-dd hh:mm:ss:), the active setting group number, three-phase current sampling
value, residual current sampling value, three-phase voltage sampling value, residual voltage
sampling value, the synchronism voltage sampling value, line frequency and the address relevant
to IP address of Ethernet A. If all the sampling values of the voltage and the current can’t be fully
displayed within one screen, they will be scrolling-displayed automatically from the top to the
bottom.
If the device has detected any abnormal state, it′ll display the self-check alarm information.
“S” indicates that device clock is synchronized. If “S” disappears, it means that device clock is not
synchronized.
For the situation that the disturbance records and the supervision events coexist, the upper half
part is the disturbance record, and the lower half part is the supervision event. The following items
are listed in the upper half part: record No., record name, generation time of the disturbance
record. If there is protection element operation, faulty phase and relative operation time (with
reference to the corresponding fault detector element) will be displayed. If the disturbance records
can not be displayed in one page, they will be displayed in several pages alternately.
If there is no supervision event, disturbance records will be displayed as shown in the following
figure.
0000ms FD.DPFC.Pkp
0024ms AB 21Q.Z1.Op
If the device has the supervision event, the display interface will show the disturbance record and
the supervision event at the same time.
0000ms FD.DPFC.Pkp
0024ms AB 21Q.Z1.Op
Superv Events
Alm_Device
2013-01-15 13:22:23:669 shows the time of the disturbance record, the format is
“yyyy-mm-dd hh:mm:ss:fff”.
0000ms FD.DPFC.Pkp shows fault detector element and its operation time (set as
“0000ms” fixedly).
0024ms AB 21Q.Z1.Op shows operation element and its relative operation time (with
reference to the corresponding fault detector element).
All the protection elements have been listed in chapter “Operation Theory”, and please refer to
each protection element for details. The reports related to oscillography function are showed in the
following table.
S Superv Events
Alm_Device
Alm_Version
Alm_Version
BI_Maintenance 0 1
2013-01-15 13:31:23:669 shows date and time when the report occurred, the format is
“yyyy-mm-dd hh:mm:ss:fff”.
BI_Maintenance 0→1 shows the state change of binary input, including binary input
name, original state and final state.
Device Logs NO. 4 shows the title and the number of the device log
2008-11-28 10:18:47:569 shows date and time when the report occurred, the format is
year–month-date and hour:minute:second:millisecond
It will be displayed on LCD before disturbance records and supervision events are confirmed. Only
pressing both “ENT” and “ESC” at the same time can switch among disturbance records,
supervision events and the normal running state of the device to display it. IO events will be
displayed for 5s and then it will return to the previous display interface automatically.
2. Press the “▲” or “▼” to move the cursor to the “Measurements” menu, and then press
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;
4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most);
6. Press the “ENT” or “ESC” to exit this menu (returning to the “Measurements” menu);
2. Press the key “▲” or “▼” to move the cursor to the “Status” menu, and then press the
“ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to any command menu item, and then press
the key “ENT” to enter the submenu.
4. Press the “▲” or “▼” to page up/down (if all information cannot be displayed in one
display screen, one screen can display 14 lines of information at most).
5. Press the key “◄” or “►” to select pervious or next command menu.
6. Press the key “ENT” or “ESC” to exit this menu (returning to the “Status” menu).
2. Press the “▲” or “▼” to move the cursor to the “Records” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;
7. Press the “ENT” or “ESC” to exit this menu (returning to the “Records” menu);
2. Press the “▲” or “▼” to move the cursor to the “Print” menu, and then press the “ENT” or
“►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;
Selecting the “Disturb Records”, and then press the “+” or “-” to select pervious
or next record. After pressing the key “ENT”, the LCD will display “Start Printing... ”,
and then automatically exit this menu (returning to the menu “Print”). If the printer
doesn’t complete its current print task and re-start it for printing, and the LCD will
display “Printer Busy…”. Press the key “ESC” to exit this menu (returning to the
menu “Print”).
Selecting the command menu “Superv Events” or “IO Events”, and then press the
key “▲” or “▼” to move the cursor. Press the “+” or “-” to select the starting and
ending numbers of printing message. After pressing the key “ENT”, the LCD will
display “Start Printing…”, and then automatically exit this menu (returning to the
menu “Print”). Press the key “ESC” to exit this menu (returning to the menu “Print”).
4. If selecting the command menu “Device Info”, “Device Status“ or “IEC103 Info”, press
the key “ENT”, the LCD will display “Start printing..”, and then automatically exit this menu
(returning to the menu “Print”).
5. If selecting the “Settings”, press the key “ENT” or “►” to enter the next level of menu.
6. After entering the submenu “Settings”, press the key “▲” or “▼” to move the cursor, and
then press the key “ENT” to print the corresponding default value. If selecting any item to
printing:
Press the key “+” or “-” to select the setting group to be printed. After pressing the key
“ENT”, the LCD will display “Start Printing…”, and then automatically exit this menu
(returning to the menu “Settings”). Press the key “ESC” to exit this menu (returning to the
menu “Settings”).
7. After entering the submenu “Waveforms”, press the “+” or “-” to select the waveform
item to be printed and press ”ENT” to enter. If there is no any waveform data, the LCD will
display “No Waveform Data!” (Before executing the command menu “Waveforms”, it is
necessary to execute the command menu “Trig Oscillograph” in the menu “Local Cmd”,
otherwise the LCD will display “No Waveform Data!”). With waveform data existing:
Press the key “+” or “-” to select pervious or next record. After pressing the key “ENT”, the LCD
will display “Start Printing…”, and then automatically exit this menu (returning to the menu
“Waveforms”). If the printer does not complete its current print task and re-start it for printing, and
the LCD will display “Printer Busy…”. Press the key “ESC” to exit this menu (returning to the menu
“Waveforms”).
2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;
7. Press the “ESC” to exit this menu (returning to the menu “Settings”).
NOTICE!
If the displayed information exceeds 14 lines, the scroll bar will appear on the right side
of the LCD to indicate the quantity of all displayed information of the command menu
and the relative location of information where the current cursor points at.
2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to any command menu, and then press the
“ENT” to enter the menu;
7. Press the “ESC” to exit this menu (returning to the menu “Settings” );
8. If selecting the command menu “System Settings”, move the cursor to the setting item
to be modified, and then press the “ENT”;
Press the “+” or “-” to modify the value (if the modified value is of multi-bit, press the “◄” or “►”
to move the cursor to the digit bit, and then press the “+” or “-” to modify the value), press the
“ESC” to cancel the modification and return to the displayed interface of the command menu
“System Settings”. Press the “ENT” to automatically exit this menu (returning to the displayed
interface of the command menu “System Settings”).
Move the cursor to continue modifying other setting items. After all setting values are modified,
press the “◄”, “►” or “ESC”, and the LCD will display “Save or Not?”. Directly press the “ESC” or
press the “◄” or “►” to move the cursor. Select the “Cancel”, and then press the “ENT” to
automatically exit this menu (returning to the displayed interface of the command menu “System
Settings”).
Press the “◄” or “►” to move the cursor. Select “No” and press the “ENT”, all modified setting item
will restore to its original value, exit this menu (returning to the menu “Settings”).
Press the “◄” or “►” to move the cursor to select “Yes”, and then press the “ENT”, the LCD will
display password input interface.
Password:
____
Input a 4-bit password (“+”, “◄”, “▲” and “-”). If the password is incorrect, continue inputting it,
and then press the “ESC” to exit the password input interface and return to the displayed interface
of the command menu “System Settings”. If the password is correct, LCD will display “Save
Setting Now…”, and then exit this menu (returning to the displayed interface of the command
menu “System Settings”), with all modified setting items as modified values.
NOTICE!
For different setting items, their displayed interfaces are different but their modification
methods are the same. The following is ditto.
9. If selecting the submenu “Prot Settings”, and press “ENT” to enter. After selecting
different command menu, the LCD will display the following interface: (take “FD
Settings” as an example)
FD Settings
Active Group: 01
Selected Group: 02
Press the “+” or “-” to modify the value, and then press the “ENT” to enter it. Move the cursor to
the setting item to be modified, press the “ENT” to enter.
Take the setting [FD.DPFC.I_Set] as an example is selected to modify, then press the “ENT” to
enter and the LCD will display the following interface. Press “+” or “-” to modify the value and
then press the “ENT” to confirm.
FD.DPFC.I_Set
NOTICE!
After modifying protection settings in current active setting group or system parameters
of the device, the “HEALTHY” LED indicator the device will be lit off, and the MON
module will check the new settings. If the abnormality is detected during the setting
check, corresponding alarm signals will be issued. Moreover, if the critical error is
detected, the device will be blocked.
2. Press the “▲” or “▼” to move the cursor to the “Settings” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to the command menu “Copy Settings”, and
then press the “ENT” to enter the menu.
Copy Settings
Active Group: 01
Copy To Group: 02
Press the “+” or “-” to modify the value. Press the “ESC”, and return to the menu “Settings”.
Press the “ENT”, the LCD will display the interface for password input, if the password is incorrect,
continue inputting it, press the “ESC” to exit the password input interface and return to the menu
“Settings”. If the password is correct, the LCD will display “Settings Copied!”, and exit this menu
(returning to the menu “Settings”).
Active Group: 01
Change To Group: 02
Press the “+” or “-” to modify the value, and then press the “ESC” to exit this menu (returning to
the main menu). After pressing the “ENT”, the LCD will display the password input interface. If the
password is incorrect, continue inputting it, and then press the “ESC” to exit the password input
interface and return to its original state. If the password is correct, the “HEALTHY” indicator lamp
of the protection device will go out, and the protection device will re-check the protection setting. If
the check doesn’t pass, the protection device will be blocked. If the check is successful, the LCD
will return to its original state.
2. Press the “+”, “-”, “+”, “-” and “ENT”; Press the “ESC” to exit this menu (returning to
the original state). Press the “ENT” to carry out the deletion.
NOTICE!
The operation of deleting device message will delete all messages saved by the
protection device, including disturbance records, supervision events, binary events, but
not including device logs. Furthermore, the message is irrecoverable after deletion, so
the application of the function shall be cautious.
2. Press the key “▲” or “▼” to move the cursor to the command menu “Local Cmd”, and
then press the key “ENT” to enter submenus. Press the key “▲” or “▼” to move the
cursor to the command menu “Control”, and then press the key “ENT” to enter and the
following display will be shown on LCD.
Password:
000
Input a 3-bit password (“111”). If the password is incorrect, continue inputting it, and then press the
“ESC” to exit the password input interface and return to the displayed interface of the command
menu “Control”. If the password is correct, it will go to the following step.
3. Press the key “▲” or “▼” to move the cursor to the control object and press the key
“ENT” to select control object.
Control
Step1: select Control Object
1. CSWI01
2. CSWI02
3. CSWI03
4. CSWI04
5. CSWI05
6. CSWI06
7. CSWI07
8. CSWI08
9. CSWI09
10. CSWI10
4. Press the key “◄” or “►” to select control command press the key “ENT” to the next step.
3) (Stop): Reserved
CSWI01
Step2: select Control Command
InterlockChk InterlockNotChk
Result
5. Press the key “◄” or “►” to select synchronism check mode and press the key “ENT” to
the next step.
4) LoopCheck: Reserved
CSWI01
Step3: select Execution Condition
InterlockChk InterlockNotChk
Result
6. Press the key “◄” or “►” to select interlock mode and press the key “ENT” to next step.
CSWI01
Step4: select Interlock Condition
InterlockChk InterLockNotChk
Result
7. Press the key “◄” or “►” to select control type and press the key “ENT”.
As shown in the following figure, operation results will be shown after “Result” at the bottom of the
LCD.
CSWI01
Step5: select Control Type
InterlockChk InterLockNotChk
Result
NOTICE!
An example of normal display with SLD is shown in the following figure. The single line diagram of
the default display on the LCD is shown as below when the device is in normal situation, if this
device adopts the single line diagram as default display.
Bus1
Bus2
M011 M0112
M0131
M01
M0151
M0171
Feeder M01
Press key “▼” continuously to select a circuit breaker or a switch which will be opened or closed.
Then press key “ENT” to start to control the selected circuit breaker or switch. If it is the first time to
do control operation after a long time, it needs to input a correct password. The control operation
window will be valid for 150s after inputting correct password. The password for control operation
is fixed, and it is “111”.
Bus1
Bus2
M011 M0112
M0131
M01
M0151
M0171 Password:
Feeder M01 000
After inputting correct password, press key “ENT” to control the selected circuit breaker or switch.
Press key “▼” continuously to select the expected circuit breaker or switch with closed position,
and then press key “ENT” to start to open the selected circuit breaker or switch.
Bus1
Bus2
M011 M0112
M0131
M01
M0151
M0171
Feeder M01 Open Close?
Bus1
Bus2
M011 M0112
M0131
M01
M0151
M0171
Feeder M01 Op Success
2. Press the “▲” or “▼” to move the cursor to the “Clock” menu, and then press the “ENT”
to enter clock display
3. Press the “▲” or “▼” to move the cursor to the date or time to be modified;
4. Press the “+” or “-” to modify value, and then press the “ENT” to save the modification
and return to the main menu;
5. Press the “ESC” to cancel the modification and return to the main menu.
NOTICE!
Move the cursor to select the item “Format” to setup time display format. Press the “+”
or “-” to modify from the following options.
2. YYYY/MM/dd
3. DD-MM-YYYY
4. DD/MM/YYYY
5. MM-DD-YYYY
6. MM/DD/YYYY
Clock
Year: 2008
Month: 11
Day: 28
Hour: 20
Minute: 59
Format: YYYY/MM/DD
2. Press the “▲” or “▼” to move the cursor to the “Information” menu, and then press the
“ENT” or “►” to enter the menu;
3. Press the “▲” or “▼” to move the cursor to the command menu “Board Info”, and then
press the “ENT” to enter the menu;
5. Press the “ENT” or “ESC” to exit this menu (returning to the “Information” menu).
2. Press the “▲” or “▼” to move the cursor to the “Information” menu, and then press the
“ENT” to enter the submenu.
3. Press the key “▲” or “▼” to move the cursor to the command menu “Version Info”, and
then press the key “ENT” to display the software version.
2. Press the key “▲” or “▼” to move the cursor to the “Test” menu, and then press the key
“ENT” or “►” to enter the menu.
3. Press the key “▲” or “▼” to move the cursor to the submenu “Device Test”, and then
press the key “ENT” to enter the submenu,to select test item. If “Disturb Events”
“Superv Events” or “IO Events” is selected, two options “All Test” and “Select Test” are
provided.
4. Press the key “▲” or “▼” to move the cursor to select the corresponding command menu
“All Test” or “Select Test”. If selecting the “All Test”, press the “ENT”, and the device will
successively carry out all operation element message test one by one.
5. If “Select Test” is selected, press the key “ENT”. Press the “+” or “-” to page up/down,
and then press the key “▲” or “▼” to move the scroll bar. Move the cursor to select the
corresponding protection element. Press the key “ENT” to execute the communication
test of this protection element, the substation automatic system (SAS) will receive the
corresponding message.
NOTICE!
If no input operation is carried out within 60s, exit the communication transmission and
return to the “Test” menu, at this moment, the LCD will display “Communication Test
Timeout and Exiting...”.
Press the key “ESC” to exit this menu (returning to the menu “Test”, at this moment, the LCD will
display “Communication Test Exiting…”.
2. Press the key “▲” or “▼” to move the cursor to the command menu “Language”, and
then press the key “ENT” to enter the menu and the following display will be shown on
LCD.
1 中文
2 English
3 XXXX
3. Press the key “▲” or “▼” to move the cursor to the language user preferred and press
the key “ENT” to execute language switching. After language switching is finished, LCD
will return to the menu “Language”, and the display language is changed. Otherwise,
press the key “ESC” to cancel language switching and return to the menu “Language”.
NOTICE!
LCD interface provided in this chapter is only a reference and available for explaining
specific definition of LCD. The displayed interface of the actual device may be some
different from it, so you shall be subject to the actual protection device.
9 Configurable Function
Table of Contents
9 Configurable Function ...................................................................... 9-a
9.1 Overview .......................................................................................................... 9-1
9.2 Introduction on PCS-Explorer Software ........................................................ 9-1
9.3 Signal List ........................................................................................................ 9-2
9.3.1 Input Signal .......................................................................................................................... 9-2
List of Tables
Table 9.3-1 Input signals ............................................................................................................. 9-2
9.1 Overview
After function configuration is finished, disabled protection function will be hidden in the device and
in setting configuration list of PCS-Explorer Software. The user can select to show or hide some
setting by this way, and modify the setting value.
Please refer to the instruction manual “PCS-Explorer Auxiliary Software” for details.
Overall functions:
Programmable logic
Device configuration
Function configuration
LCD configuration
Setting configuration
Analysis of waveform
File downloading/uploading
If an input signal or output signal is gray in PCS-Explorer, it means that the input signal or output
signal is not configurable. Otherwise, it is configurable signal.
NOTICE!
All input signals of this device are listed in the following table.
10 Communication
Table of Contents
10 Communication ............................................................................. 10-a
10.1 Overview ...................................................................................................... 10-1
10.2 Rear Communication Port Information ..................................................... 10-1
10.2.1 RS-485 Interface.............................................................................................................. 10-1
List of Figures
Figure 10.2-1 EIA RS-485 bus connection arrangements ..................................................... 10-2
Figure 10.4-1 Dual-net full duplex mode sharing the RCB block instance ......................... 10-9
Figure 10.4-2 Dual-net hot-standby mode sharing the same RCB instance ..................... 10-10
Figure 10.4-3 Dual-net full duplex mode with 2 independent RCB instances .................. 10-11
10.1 Overview
This section outlines the remote communications interfaces of NR Relays. The protective device
supports a choice of three protocols via the rear communication interface (RS-485 or Ethernet),
selected via the model number by setting. The protocol provided by the protective device is
indicated in the menu “Settings→Device Setup→Comm Settings”.
The rear EIA RS-485 interface is isolated and is suitable for permanent connection of whichever
protocol is selected. The advantage of this type of connection is that up to 32 protective devices
can be “daisy chained” together using a simple twisted pair electrical connection.
It should be noted that the descriptions contained within this section do not aim to fully detail the
protocol itself. The relevant documentation for the protocol should be referred to for this
information. This section serves to describe the specific implementation of the protocol in the relay.
The EIA RS-485 two-wire connection provides a half-duplex fully isolated serial connection to the
product. The connection is polarized and whilst the product’s connection diagrams indicate the
polarization of the connection terminals it should be borne in mind that there is no agreed
definition of which terminal is which. If the master is unable to communicate with the product, and
the communication parameters match, then it is possible that the two-wire connection is reversed.
The EIA RS-485 bus must have 120Ω (Ohm) ½ Watt terminating resistors fitted at either end
across the signal wires (refer to Figure 10.2-1). Some devices may be able to provide the bus
terminating resistors by different connection or configuration arrangements, in which case
separate external components will not be required. However, this product does not provide such a
facility, so if it is located at the bus terminus then an external termination resistor will be required.
EIA RS-485
Master 120 Ohm
120 Ohm
The EIA RS-485 standard requires that each device is directly connected to the physical cable that
is the communications bus. Stubs and tees are expressly forbidden, such as star topologies. Loop
bus topologies are not part of the EIA RS-485 standard and are forbidden by it also.
Two-core screened cable is recommended. The specification of the cable will be dependent on the
application, although a multi-strand 0.5mm 2 per core is normally adequate. Total cable length must
not exceed 500m. The screen must be continuous and connected to ground at one end, normally
at the master connection point; it is important to avoid circulating currents, especially when the
cable runs between buildings, for both safety and noise reasons.
This product does not provide a signal ground connection. If a signal ground connection is present
in the bus cable then it must be ignored, although it must have continuity for the benefit of other
devices connected to the bus. At no stage must the signal ground be connected to the cables
screen or to the product’s chassis. This is for both safety and noise reasons.
10.2.1.4 Biasing
It may also be necessary to bias the signal wires to prevent jabber. Jabber occurs when the signal
level has an indeterminate state because the bus is not being actively driven. This can occur when
all the slaves are in receive mode and the master is slow to turn from receive mode to transmit
mode. This may be because the master purposefully waits in receive mode, or even in a high
impedance state, until it has something to transmit. Jabber causes the receiving device(s) to miss
the first bits of the first character in the packet, which results in the slave rejecting the message
and consequentially not responding. Symptoms of these are poor response times (due to retries),
increasing message error counters, erratic communications, and even a complete failure to
communicate.
Biasing requires that the signal lines be weakly pulled to a defined voltage level of about 1V. There
should only be one bias point on the bus, which is best situated at the master connection point.
The DC source used for the bias must be clean; otherwise noise will be injected. Note that some
devices may (optionally) be able to provide the bus bias, in which case external components will
not be required.
NOTICE!
It is extremely important that the 120Ω termination resistors are fitted. Failure to do so
will result in an excessive bias voltage that may damage the devices connected to the
bus.
As the field voltage is much higher than that required, NR cannot assume responsibility
for any damage that may occur to a device connected to the network as a result of
incorrect application of this voltage.
Ensure that the field voltage is not being used for other purposes (i.e. powering logic
inputs) as this may cause noise to be passed to the communication network.
It is recommended to use twisted screened eight-core cable as the communication cable. A picture
is shown bellow.
Each equipment is connected with an exchanger via communication cable, and thereby it forms a
star structure network. Dual-network is recommended in order to increase reliability. SCADA is
also connected to the exchanger and will play a role of master station, so the every equipment
which has been connected to the exchanger will play a role of slave unit.
SCADA
Switch: Net A
Switch: Net B
……
To use the rear port with IEC60870-5-103 communication, the relevant settings to the protective
device must be configured.
The IEC60870-5-103 interface over serial port (RS-485) is a master/slave interface with the
protective device as the slave device. It is properly developed by NR.
Initialization (reset)
Time synchronization
General interrogation
General commands
Disturbance records
The link layer strictly abides by the rules defined in the IEC60870-5-103.
10.3.2 Initialization
Whenever the protective device has been powered up, or if the communication parameters have
been changed, a reset command is required to initialize the communications. The protective
device will respond to either of the two reset commands (Reset CU or Reset FCB), the difference
is that the Reset CU will clear any unsent messages in the transmit buffer.
The protective device will respond to the reset command with an identification message ASDU 5,
the COT (Cause Of Transmission) of this response will be either Reset CU or Reset FCB
depending on the nature of the reset command.
If the protective device clock is synchronized using the IRIG-B input then it will not be possible to
set the protective device time using the IEC60870-5-103 interface. An attempt to set the time via
the interface will cause the protective device to create an event with the current date and time
taken from the IRIG-B synchronized internal clock.
status of binary signal and alarm element are sent by ASDU1 (time-tagged message). The cause
of transmission (COT) of these responses is 1.
All spontaneous events can be gained by printing, implementing submenu “IEC103 Info” in the
menu “Print”.
Refer the IEC60870-5-103 standard can get the enough details about general interrogation.
All general classification service group numbers can be gained by printing, implementing submenu
“IEC103 Info” in the menu “Print”.
The disturbance records are stored in uncompressed format and can be extracted using the
standard mechanisms described in IEC60870-5-103.
All channel numbers (ACC) of disturbance data can be gained by printing, implementing submenu
“IEC103 Info” in the menu “Print”.
10.4.1 Overview
The IEC 61850 standard is the result of years of work by electric utilities and vendors of electronic
equipment to produce standardized communications systems. IEC 61850 is a series of standards
describing client/server and peer-to-peer communications, substation design and configuration,
testing, environmental and project standards. The complete set includes:
IEC 61850-5: Communications and requirements for functions and device models
IEC 61850-7-1: Basic communication structure for substation and feeder equipment–
Principles and models
IEC 61850-7-2: Basic communication structure for substation and feeder equipment - Abstract
communication service interface (ACSI)
IEC 61850-7-3: Basic communication structure for substation and feeder equipment–
Common data classes
IEC 61850-7-4: Basic communication structure for substation and feeder equipment–
Compatible logical node classes and data classes
IEC 61850-8-1: Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO
9506-1 and ISO 9506-2) and to ISO/IEC 8802-3
IEC 61850-9-1: Specific Communication Service Mapping (SCSM) – Sampled values over
serial unidirectional multidrop point to point link
IEC 61850-9-2: Specific Communication Service Mapping (SCSM) – Sampled values over
ISO/IEC 8802-3
These documents can be obtained from the IEC (http://www.iec.ch). It is strongly recommended
that all those involved with any IEC 61850 implementation obtain this document set.
1. MMS protocol
IEC 61850 specifies the use of the Manufacturing Message Specification (MMS) at the upper
(application) layer for transfer of real-time data. This protocol has been in existence for a number
of years and provides a set of services suitable for the transfer of data within a substation LAN
environment. IEC 61850-7-2 abstract services and objects are mapped to actual MMS protocol
services in IEC61850-8-1.
2. Client/server
This is a connection-oriented type of communication. The connection is initiated by the client, and
communication activity is controlled by the client. IEC61850 clients are often substation computers
running HMI programs or SOE logging software. Servers are usually substation equipment such
as protection relays, meters, RTUs, transformer, tap changers, or bay controllers.
3. Peer-to-peer
A substation configuration language is a number of files used to describe IED configurations and
communication systems according to IEC 61850-5 and IEC 61850-7. Each configured device has
an IED Capability Description (ICD) file and a Configured IED Description (CID) file. The
substation single line information is stored in a System Specification Description (SSD) file. The
entire substation configuration is stored in a Substation Configuration Description (SCD) file. The
SCD file is the combination of the individual ICD files and the SSD file, moreover, add
communication system parameters (MMS, GOOSE, control block, SV control block) and the
connection relationship of GOOSE and SV to SCD file.
Client-server mode is adopted: clients (SCADA, control center and etc.) communicate with the
IEDs via MMS communication network, and the IEDs operate as the servers. IEDs are connected
to clients passively, and they can interact with the clients according to the configuration and the
issued command of the clients.
Three modes for dual-MMS Ethernet (abbreviated as dual-net) are provided as below.
NOTICE!
Hereinafter, the normal operation status of net means the physical link and TCP link are
both ok. The abnormal operation status of net means physical link or TCP link is
broken.
10.4.3.1 Dual-net Full Duplex Mode Sharing the Same RCB Instance
Client Client
Figure 10.4-1 Dual-net full duplex mode sharing the RCB block instance
Net A and Net B share the same report control block (abbreviated as RCB) enabled by the client.
IED sends undifferentiated date through dual-net to the clients. If one net is physically
disconnected, the flag of RCB instance (i.e.: “RptEna” in above figure) is still “true”. Only when
both Net A and Net B are disconnected, the flag of the RCB instance will automatically change to
“false”.
In normal operation status of this mode, IED provides the same MMS service for Net A and Net B.
If one net is physically disconnected (i.e.: “Abnormal operation status” in above figure), the
working mode will switch to single-net mode seamlessly and immediately. Network communication
supervision is unnecessary here, and Buffered Report Control Block (abbreviated as BRCB) need
not to be used. On the other net, date alternation works normally. Therefore, MMS service can
interact normally without interruption. This mode ensures no data loss during one net is in
abnormal operation status.
In this mode, one report will be transmitted twice via dual nets for the same report instance, so the
client needs to distinguish whether two reports are same according to corresponding EntryIDs.
Client Client
Figure 10.4-2 Dual-net hot-standby mode sharing the same RCB instance
In this mode, the MMS service is provided on main MMS link, no MMS service interacts on the
standby MMS link. The definitions of two links are as follows:
Main MMS Link: Physically connected, TCP level connected, MMS report service available.
Standby MMS Link: Physically connected, TCP level connected, MMS report service not
available.
If the main net fails to operate (i.e.: “Abnormal operation status” in the above figure), the IED will
set “RptEna” to “false”. Meanwhile the client will detect the failure by heartbeat message or
“keep-alive”, it will automatically enable the RCB instance by setting “RptEna” back to “true”
through standby MMS link. By the buffer function of BRCB, the IED can provide uninterrupted
MMS service on the standby net. However, the differences of BRCB standards among different
manufacturers may cause data loss. Moreover, if duration of net switch is too long, the data loss is
positively as the capacity of BRCB’s buffer function is limited.
NOTICE!
The first mode and second mode, Net A IED host address and Net B IED host address
must be the same.
Client Client
Figure 10.4-3 Dual-net full duplex mode with 2 independent RCB instances
In this mode, IED provides 2 report instances for each RCB, Net A and Net B work independently
from each other, failures of any net will not affect the other net at all. Tow report instances are
required for each client. Therefore, the IED may be unable to provide enough report instances if
there are too many clients.
Net A and Net B send the same report separately when they operates normally, To ensure no
repeated data is saved into database, massive calculation is required for the client.
Moreover, accurate clock synchronization of the IED is required to distinguish whether 2 reports
are the same report according to the timestamps. Clock synchronization error of the IED may lead
to report loss/redundancy.
As a conclusion, for the second mode, it’s difficult to realize seamless switchover between dual
nets, however, for the third mode, the IED may be unable to provide enough report instances if too
many clients are applied on site. Considering client treatment and IED implementation, the first
mode (Dual-net full duplex mode sharing the same report instance) is recommended for MMS
communication network deployment.
Each IED represents one IEC61850 physical device. The physical device contains one or more
logical device(s), and the logical device contains many logical nodes. The logical node LPHD
contains information about the IED physical device. The logical node LLN0 contains common
The GGIO logical node is available in the PCS-900 series relays to provide access to digital status
points (including general I/O inputs and warnings) and associated timestamps and quality flags.
The data content must be configured before the data can be used. GGIO provides digital status
points for access by clients. It is intended that clients use GGIO in order to access digital status
values from the PCS-900 series relays. Clients can utilize the IEC61850 buffered reporting
features available from GGIO in order to build sequence of events (SOE) logs and HMI display
screens. Buffered reporting should generally be used for SOE logs since the buffering capability
reduces the chances of missing data state changes. All needed status data objects are transmitted
to HMI clients via buffered reporting, and the corresponding buffered reporting control block
(BRCB) is defined in LLN0.
Most of analog measured values are available through the MMXU logical nodes, and metering
values in MMTR, the else in MMXN, MSQI and so on. Each MMXU logical node provides data
from a IED current/voltage “source”. There is one MMXU available for each configurable source.
MMXU1 provides data from CT/VT source 1(usually for protection purpose), and MMXU2 provides
data from CT/VT source 2 (usually for monitor and display purpose). All these analog data objects
are transmitted to HMI clients via unbuffered reporting periodically, and the corresponding
unbuffered reporting control block (URCB) is defined in LLN0. MMXUx logical nodes provide the
following data for each source:
MMXU.MX.Hz: frequency
The following list describes the protection elements for PCS-902 series relays. The specified relay
will contain a subset of protection elements from this list.
PTUC: Undercurrent
PTOC: Phase overcurrent, zero-sequence overcurrent and overcurrent when VT circuit failure
PTUV: Undervoltage
PTOF: Overfrequency
PTUF: Underfrequency
RBRF:Breaker failure
RSYN: Synchronism-check
The protection elements listed above contain start (pickup) and operate flags, instead of any
element has its own start (pickup) flag separately, all the elements share a common start (pickup)
flags “PTRC.ST.Str.general”. The operate flag for PTOC1 is “PTOC1.ST.Op.general”. For
PCS-902 series relays protection elements, these flags take their values from related module for
the corresponding element. Similar to digital status values, the protection trip information is
reported via BRCB, and BRCB also locates in LLN0.
Logical node LLN0 is essential for an IEC61850 based IED. This LN shall be used to address
common issues for Logical Devices. Most of the public services, the common settings, control
values and some device oriented data objects are available here. The public services may be
BRCB, URCB and GSE control blocks and similar global defines for the whole device; the
common settings include all the setting items of communication settings, system settings and
some of the protection setting items, which can be configured to two or more protection elements
(logical nodes). In LLN0, the item Loc is a device control object, this Do item indicates the local
operation for complete logical device, when it is true, all the remote control commands to the IED
will be blocked and those commands make effective until the item Loc is changed to false. In
PCS-900 series relays, besides the logical nodes we describe above, there are some other logical
nodes below in the IEDs:
MMXU: This LN shall be used to acquire values from CTs and VTs and calculate measurands
such as r.m.s. values for current and voltage or power flows out of the acquired voltage and
current samples. These values are normally used for operational purposes such as power
flow supervision and management, screen displays, state estimation, etc. The requested
LPHD: Physical device information, the logical node to model common issues for physical
device.
PTRC: Protection trip conditioning, it shall be used to connect the “operate” outputs of one or
more protection functions to a common “trip” to be transmitted to XCBR. In addition or
alternatively, any combination of “operate” outputs of protection functions may be combined to
a new “operate” of PTRC.
RDRE: Disturbance recorder function. It triggers the fault wave recorder and its output refers
to the “IEEE Standard Format for Transient Data Exchange (COMTRADE) for Power System”
(IEC 60255-24). All enabled channels are included in the recording, independently of the
trigger mode.
IEC61850 buffered and unbuffered reporting control blocks locate in LLN0, they can be configured
to transmit information of protection trip information (in the Protection logical nodes), binary status
values (in GGIO) and analog measured/calculated values (in MMXU, MMTR and MSQI). The
reporting control blocks can be configured in CID files, and then be sent to the IED via an
IEC61850 client. The following items can be configured.
- Bit 1: Data-change
- Bit 4: Integrity
- Bit 1: Sequence-number
- Bit 2: Report-time-stamp
- Bit 3: Reason-for-inclusion
- Bit 4: Data-set-name
- Bit 5: Data-reference
- Bit 8: Conf-revision
- Bit 9: Segmentation
MMS file services are supported to allow transfer of oscillography, event record or other files from
a PCS-900 series relay.
10.4.5.3 Timestamps
The Universal Time Coordinated(UTC for short) timestamp associated with all IEC61850 data
items represents the latest change time of either the value or quality flags of the data item.
IEC61850 specifies that each logical node can have a name with a total length of 11 characters.
The name is composed of:
Complete names are of the form xxxxxxPTOC1, where the xxxxxx character string is configurable.
Details regarding the logical node naming rules are given in IEC61850 parts 6 and 7-2. It is
recommended that a consistent naming convention be used for an entire substation project.
IEC61850 specifies the type of broadcast data transfer services: Generic Object Oriented
Substation Events (GOOSE). IEC61850 GOOSE services provide virtual LAN (VLAN) support,
Ethernet priority tagging, and Ether-type Application ID configuration. The support for VLANs and
priority tagging allows for the optimization of Ethernet network traffic. GOOSE messages can be
given a higher priority than standard Ethernet traffic, and they can be separated onto specific
VLANs. Devices that transmit GOOSE messages also function as servers. Each GOOSE
publisher contains a “GOOSE control block” to configure and control the transmission.
The GOOSE transmission (including subscribing and publishing) is controlled by GOOSE logic link
settings in device.
The PCS-900 series relays support IEC61850 Generic Object Oriented Substation Event (GOOSE)
communication. All GOOSE messages contain IEC61850 data collected into a dataset. It is this
dataset that is transferred using GOOSE message services. The GOOSE related dataset is
configured in the CID file and it is recommended that the fixed GOOSE be used for
implementations that require GOOSE data transfer between PCS-900 series relays.
IEC61850 GOOSE messaging contains a number of configurable parameters, all of which must be
correct to achieve the successful transfer of data. It is critical that the configured datasets at the
transmission and reception devices are an exact match in terms of data structure, and that the
GOOSE addresses and name strings match exactly.
Where:
C1: Shall be "M" if support for LOGICAL-DEVICE model has been declared
O: Optional
M: Mandatory
M7-6 buffer-overflow Y Y N
M7-7 entryID Y Y Y
M7-8 BufTm N N N
M7-9 IntgPd Y Y Y
M7-10 GI Y Y Y
M8 Unbuffered report control M M Y
M8-1 sequence-number Y Y Y
M8-2 report-time-stamp Y Y Y
M8-3 reason-for-inclusion Y Y Y
M8-4 data-set-name Y Y Y
M8-5 data-reference Y Y Y
M8-6 BufTm N N N
M8-7 IntgPd N Y Y
Logging
M9 Log control O O N
M9-1 IntgPd N N N
M10 Log O O N
GSE
M12 GOOSE O O Y
M13 GSSE O O N
M14 Multicast SVC O O N
M15 Unicast SVC O O N
M16 Time M M Y
M17 File transfer O O Y
Where:
C2: Shall be "M" if support for LOGICAL-NODE model has been declared
C3: Shall be "M" if support for DATA model has been declared
C4: Shall be "M" if support for DATA-SET, Substitution, Report, Log Control, or Time models has
been declared
C5: Shall be "M" if support for Report, GSE, or SMV models has been declared
M: Mandatory
S2 Associate M Y
S3 Abort M Y
S4 Release M Y
Logical device
S5 LogicalDeviceDirectory M Y
Logical node
S6 LogicalNodeDirectory M Y
S7 GetAllDataValues M Y
Data
S8 GetDataValues M Y
S9 SetDataValues M Y
S10 GetDataDirectory M Y
S11 GetDataDefinition M Y
Data set
S12 GetDataSetValues M Y
S13 SetDataSetValues O Y
S14 CreateDataSet O N
S15 DeleteDataSet O N
S16 GetDataSetDirectory M Y
Substitution
S17 SetDataValues M Y
Setting group control
S18 SelectActiveSG M/O Y
S19 SelectEditSG M/O Y
S20 SetSGValuess M/O Y
S21 ConfirmEditSGValues M/O Y
S22 GetSGValues M/O Y
S23 GetSGCBValues M/O Y
Reporting
Buffered report control block
S24 Report M Y
S24-1 data-change M Y
S24-2 qchg-change M N
S24-3 data-update M N
S25 GetBRCBValues M Y
S26 SetBRCBValues M Y
Unbuffered report control block
S27 Report M Y
S27-1 data-change M Y
S27-2 qchg-change M N
S27-3 data-update M N
S28 GetURCBValues M Y
S29 SetURCBValues M Y
Logging
Log control block
S30 GetLCBValues O N
S31 SetLCBValues O N
Log
S32 QueryLogByTime O N
S33 QueryLogAfter O N
S34 GetLogStatusValues O N
Generic substation event model (GSE)
GOOSE control block
S35 SendGOOSEMessage M Y
S36 GetGoReference O Y
S37 GetGOOSEElementNumber O N
S38 GetGoCBValues M Y
S39 SetGoCBValuess M N
Control
S51 Select O N
S52 SelectWithValue M Y
S53 Cancel M Y
S54 Operate M Y
S55 Command-Termination O Y
S56 TimeActivated-Operate O N
File transfer
S57 GetFile M/O Y
S58 SetFile O N
S59 DeleteFile O N
S60 GetFileAttributeValues M/O Y
Time
SNTP M Y
The PCS-902 series relays support IEC61850 logical nodes as indicated in the following table.
Note that the actual instantiation of each logical node is determined by the product order code.
Nodes PCS-902
L: System Logical Nodes
LPHD: Physical device information YES
LLN0: Logical node zero YES
P: Logical Nodes For Protection Functions
PDIF: Differential -
ZBSH: Bushing -
ZCAB: Power cable -
ZCAP: Capacitor bank -
ZCON: Converter -
ZGEN: Generator -
ZGIL: Gas insulated line -
ZLIN: Power overhead line -
ZMOT: Motor -
ZREA: Reactor -
ZRRC: Rotating reactive component -
ZSAR: Surge arrestor -
ZTCF: Thyristor controlled frequency converter -
ZTRC: Thyristor controlled reactive component -
10.5.1 Overview
The descriptions given here are intended to accompany this relay. The DNP3.0 protocol is not
described here; please refer to the DNP3.0 protocol standard for the details about the DNP3.0
implementation. This manual only specifies which objects, variations and qualifiers are supported
in this relay, and also specifies what data is available from this relay via DNP3.0.
The relay operates as a DNP3.0 slave and supports subset level 3 of the protocol, plus some of
the features from level 4. The DNP3.0 communication uses the Ethernet ports (electrical or optical)
at the rear side of this relay.
The supported object groups and object variations are show in the following table.
This relay now supports 4 Ethernet clients and 2 serial port clients. Each client can be set the DNP
related communication parameters respectively and be selected the user-defined communication
table. This relay supports a default communication table and 4 user-defined communication tables,
and the default communication table is fixed by the manufacturer and not permitted to configure by
the user.
The user can configure the user-defined communication table through the PCS-Explorer
configuration tool auxiliary software. The object groups “Binary Input”, “Binary Output”, “Analog
Input” and “Analog Output” can be configured according to the practical engineering demand.
To the analog inputs, the attributes “deadband” and “factor” of each analog input can be configured
independently. To the analog outputs, only the attribute “factor” of each analog output needs to be
configured. If the integer mode is adopted for the data formats of analog values (to “Analog Input”,
“Object Variation” is 1, 2 and 3; to “Analog Output”, “Object Variation” is 1 and 2.), the analog
values will be multiplied by the “factor” respectively to ensure their accuracy. And if the float mode
is adopted for the data formats of analog values, the actual float analog values will be sent directly.
The judgment method of the analog input change is as below: Calculate the difference between
the current new value and the stored history value and make the difference value multiply by the
“factor”, then compare the result with the “deadband” value. If the result is greater than the
“deadband” value, then an event message of corresponding analog input change will be created.
In normal communication process, the master can online read or modify a “deadband” value by
reading or modifying the variation in “Group34”.
The remote control signals, logic links and external extended output commands can be configured
into the “Binary Output” group. The supported control functions are listed as below.
Information Point Pulse On/Null Pulse On/Close Pulse On/Trip Latch On/Null Latch Off/Null
Remote Control Not supported Close Trip Close Trip
Logic Link Not supported Set Clear Set Clear
Extended Output See following description
This relay does not transmit the unsolicited messages if the related logic setting is set as “0”. If the
unsolicited messages want to be transmitted, the related logic setting should be set as “1” or the
DNP3.0 master will transmit “Enable Unsolicited” command to this relay through “Function Code
20” (Enable Unsolicited Messages). If the “Binary Input” state changes or the difference value of
the “Analog Input” is greater than the “deadband” value, this device will transmit unsolicited
messages. If the DNP3.0 master needs not to receive the unsolicited messages, it should forbid
this relay to transmit the unsolicited messages by setting the related logic setting as “0” or through
the “Function Code 21” (Disable Unsolicited Messages).
If the DNP3.0 master calls the Class0 data, this relay will transmit all actual values of the “Analog
Input”, “Binary Input” and “Analog Output”. The classes of the “Analog Input” and “Binary Input”
can be defined by modifying relevant settings. In communication process, the DNP3.0 master can
online modify the class of an “Analog Input” or a “Binary Input” through “Function Code 22” (Assign
Class).
11 Installation
Table of Contents
11 Installation ...................................................................................... 11-a
11.1 Overview ....................................................................................................... 11-1
11.2 Safety Information ........................................................................................ 11-1
11.3 Checking Shipment ...................................................................................... 11-2
11.4 Material and Tools Required ........................................................................ 11-2
11.5 Device Location and Ambient Conditions .................................................. 11-2
11.6 Mechanical Installation ................................................................................ 11-3
11.7 Electrical Installation and Wiring ................................................................ 11-4
11.7.1 Grounding Guidelines .......................................................................................................11-4
List of Figures
Figure 11.6-1 Dimensions and panel cut-out of PCS-902 ..................................................... 11-3
Figure 11.6-2 Demonstration of plugging a board into its corresponding slot .................. 11-3
Figure 11.7-4 Glancing demo about the wiring for electrical cables ................................... 11-7
11.1 Overview
The device must be shipped, stored and installed with the greatest care. Choose the place of
installation such that the communication interface and the controls on the front of the device are
easily accessible.
Air must circulate freely around the equipment. Observe all the requirements regarding place of
installation and ambient conditions given in this instruction manual.
Take care that the external wiring is properly brought into the equipment and terminated correctly
and pay special attention to grounding. Strictly observe the corresponding guidelines contained in
this section.
In certain cases, the settings have to be configured according to the demands of the engineering
configuration after replacement. It is therefore assumed that the personnel who replace modules
and units are familiar with the use of the operator program on the service PC.
WARNING!
ONLY insert or withdraw a module while the device power supply is switched off. To this
end, disconnect the power supply cable that connects with the PWR module.
NOTICE!
Industry packs and ribbon cables may ONLY be replaced on a workbench for electronic
equipment. Electronic components are sensitive to electrostatic discharge when not in
the unit's housing.
A module can ONLY be inserted in the slot designated in the chapter 6. Components
can be damaged or destroyed by inserting module in a wrong slot.
1. Should boards have to be removed from this relay installed in a grounded cubicle in an HV
switchgear installation, please discharge yourself by touching station ground (the cubicle)
beforehand.
2. Only hold electronic boards at the edges, taking care not to touch the components.
3. Only works on boards that have been removed from the cubicle on a workbench designed for
electronic equipment and wear a grounded wristband. Do not wear a grounded wristband,
however, while inserting or withdrawing units.
4. Always store and ship the electronic boards in their original packing. Place electronic parts in
electrostatic screened packing materials.
Visually inspect all the material when unpacking it. When there is evidence of transport damage,
lodge a claim immediately in writing with the last carrier and notify the nearest NR Company or
agent.
If the equipment is not going to be installed immediately, store all the parts in their original packing
in a clean dry place at a moderate temperature. The humidity at a maximum temperature and the
permissible storage temperature range in dry air are listed in Chapter “Technical Data”.
A suitable drill and spanners are required to secure the cubicles to the floor using the plugs
provided (if this relay is mounted in cubicles).
Excessively high temperature can appreciably reduce the operating life of this device.
The place of installation should permit easy access especially to front of the device, i.e. to the
human machine interface of the equipment.
There should also be free access at the rear of the equipment for additions and replacement of
electronic boards.
Since every piece of technical equipment can be damaged or destroyed by inadmissible ambient
conditions, such as:
1. The location should not be exposed to excessive air pollution (dust, aggressive substances).
2. Severe vibration, extreme changes of temperature, high levels of humidity, surge voltages of
high amplitude and short rise time and strong induced magnetic fields should be avoided as
far as possible.
The equipment can in principle be mounted in any attitude, but it is normally mounted vertically
(visibility of markings).
It is necessary to leave enough space top and bottom of the cut-out in the cubicle for
heat emission of this device.
The device adopts IEC standard chassis and is rack with modular structure. It uses an integral
faceplate and plug terminal block on backboard for external connections. PCS-902 series is IEC
4U high, and Figure 11.6-1 shows its dimensions and panel cut-out.
Front Side
Cut-Out
The safety instructions must be abided by when installing the boards, please see Section 11.2 for
the details.
Following figure shows the installation way of a module being plugged into a corresponding slot.
In the case of equipment supplied in cubicles, place the cubicles on the foundations that have
been prepared. Take care while doing so not to jam or otherwise damage any of the cables that
have already been installed. Secure the cubicles to the foundations.
All these precautions can only be effective if the station ground is of good quality.
Switching operations in HV installations generate transient over voltages on control signal cables.
There is also a background of electromagnetic RF fields in electrical installations that can induce
spurious currents in the devices themselves or the leads connected to them.
On the other hand, electronic apparatus can transmit interference that can disrupt the operation of
other apparatus.
In order to minimize these influences as far as possible, certain standards have to be observed
with respect to grounding, wiring and screening.
Metal accessories such as side plates, blanking plates etc., must be effectively connected
surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF
interference. The contact surfaces must not only conduct well, they must also be non-corroding.
NOTICE!
If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it
forming a resonant circuit at certain frequencies that would amplify the transmission of
interference by the devices installed and also reduce their immunity to induced
interference.
Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be
effectively grounded to the frame by three braided copper strips (see Figure 11.7-1).
The metal parts of the cubicle housing and the ground rail are interconnected electrically
conducting and corrosion proof. The contact surfaces shall be as large as possible.
NOTICE!
For metallic connections please observe the voltage difference of both materials
according to the electrochemical code.
The cubicle ground rail must be effectively connected to the station ground rail by a
grounding strip (braided copper).
Door or hinged
equipment frame
Cubicle ground
rail close to floor
Braided
copper strip
Station
ground
Conducting
connection
There are some ground terminals on some connectors of this relay, and the sign is “GND”. All the
ground terminals are connected in the cabinet of this relay. So, the ground terminal on the rear
panel (see Figure 11.7-2) is the only ground terminal of this device.
The grounding strips must therefore be of (preferably tinned) braided copper and not round copper
conductors, as the cross-section of round copper would have to be too large.
Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting
them firmly to the items to be connected.
The surfaces to which the grounding strips are bolted must be electrically conducting and
non-corroding.
Press/pinch fit
cable terminal
Braided
copper strip Terminal bolt
Contact surface
Power supply, binary inputs & outputs: stranded conductor, 1.0mm 2 ~ 2.5mm 2
DANGER!
NEVER allow a open current transformer (CT) secondary circuit connected to this
device while the primary system is live. Open CT circuit will produce a dangerously high
voltage that cause death.
A female connector is used for connecting the wires with it, and then a female connector plugs into
a corresponding male connector that is in the front of one board. See Chapter “Hardware” for
further details about the pin defines of these connectors.
The following figure shows the glancing demo about the wiring for the electrical cables.
01 02
03 04
Tighten 05 06
07 08
09 10
11 12
01
13 14
15 16
17 18
19 20
21 22
23 24
Figure 11.7-4 Glancing demo about the wiring for electrical cables
12 Commissioning
Table of Contents
12 Commissioning ............................................................................. 12-a
12.1 Overview ...................................................................................................... 12-1
12.2 Safety Instructions ...................................................................................... 12-1
12.3 Commission Tools ...................................................................................... 12-2
12.3.1 Minimum Equipment Required ........................................................................................ 12-2
12.1 Overview
This device is fully numerical in their design, implementing all protection and non-protection
functions in software. The relay employs a high degree of self-checking and in the unlikely event of
a failure, will give an alarm. As a result of this, the commissioning test does not need to be as
extensive as with non-numeric electronic or electro-mechanical relays.
To commission numerical relays, it is only necessary to verify that the hardware is functioning
correctly and the application-specific software settings have been applied to the relay.
Blank commissioning test and setting records are provided at the end of this manual for
completion as required.
Before carrying out any work on the equipment, the user should be familiar with the contents of the
safety and technical data sections and the ratings on the equipment’s rating label.
DANGER!
WARNING!
ONLY qualified personnel should work on or in the vicinity of this device. This personnel
MUST be familiar with all safety regulations and service procedures described in this
manual. During operating of electrical device, certain part of the device is under high
voltage. Severe personal injury and significant device damage could result from
improper behavior.
1. The earthing screw of the device must be connected solidly to the protective earth conductor
before any other electrical connection is made.
2. Hazardous voltages can be present on all circuits and components connected to the supply
voltage or to the measuring and test quantities.
3. Hazardous voltages can be present in the device even after disconnection of the supply
voltage (storage capacitors!)
4. The limit values stated in the Chapter “Technical Data” must not be exceeded at all, not even
during testing and commissioning.
5. When testing the device with secondary test equipment, make sure that no other
measurement quantities are connected. Take also into consideration that the trip circuits and
maybe also close commands to the circuit breakers and other primary switches are
disconnected from the device unless expressly stated.
Modern test set may contain many of the above features in one unit.
1. Multifunctional dynamic current and voltage injection test set with interval timer.
2. Multimeter with suitable AC current range and AC/DC voltage ranges of 0~440Vac and
0~250Vdc respectively.
1. An electronic or brushless insulation tester with a DC output not exceeding 500V (for
insulation resistance test when required).
2. A portable PC, with appropriate software (this enables the rear communications port to be
tested, if this is to be used, and will also save considerable time during commissioning).
3. EIA RS-485 to EIA RS-232 converter (if EIA RS-485 IEC60870-5-103 port is being tested).
With the front cover in place all keys are accessible. All menu cells can be read. The LED
indicators and alarms can be reset. Protection or configuration settings can be changed, or fault
and event records cleared. However, menu cells will require the appropriate password to be
entered before changes can be made.
These product checks cover all aspects of the relay which should be checked to ensure that it has
not been physically damaged prior to commissioning, is functioning correctly and all input quantity
measurements are within the stated tolerances.
If the application-specific settings have been applied to the relay prior to commissioning, it is
advisable to make a copy of the settings so as to allow them restoration later. This could be done
by extracting the settings from the relay itself via printer or manually creating a setting record.
This relay is fully numerical and the hardware is continuously monitored. Commissioning tests can
be kept to a minimum and need only include hardware tests and conjunctive tests. The function
tests are carried out according to user’s correlative regulations.
The following tests are necessary to ensure the normal operation of the equipment before it is first
put into service.
1. Hardware tests
These tests are performed for the following hardware to ensure that there is no hardware defect.
Defects of hardware circuits other than the following can be detected by self-monitoring when the
DC power is supplied.
5. Function tests
These tests are performed for the following functions that are fully software-based. Tests of the
protection schemes and fault locator require a dynamic test set.
7. Timers test
9. Conjunctive tests
The tests are performed after the relay is connected with the primary equipment and other external
equipment.
After unpacking the product, check for any damage to the relay case. If there is any damage, the
internal module might also have been affected, contact the vendor. The following items listed is
necessary.
1. Protection panel
Carefully examine the protection panel, protection equipment inside and other parts inside to see
that no physical damage has occurred since installation.
The rated information of other auxiliary protections should be checked to ensure it is correct for the
particular installation.
2. Panel wiring
Check the conducting wire which is used in the panel to assure that their cross section meeting the
requirement.
Carefully examine the wiring to see that they are no connection failure exists.
3. Label
Check all the isolator binary inputs, terminal blocks, indicators, switches and push buttons to make
sure that their labels meet the requirements of this project.
Check each plug-in module of the device on the panel to make sure that they are well installed into
the equipment without any screw loosened.
5. Earthing cable
Check whether the earthing cable from the panel terminal block is safely screwed to the panel
steel sheet.
Check whether all the switches, equipment keypad, isolator binary inputs and push buttons work
normally and smoothly.
Insulation resistance tests are only necessary during commissioning if it is required for them to be
done and they have not been performed during installation.
Isolate all wiring from the earth and test the isolation with an electronic or brushless insulation
tester at a DC voltage not exceeding 500V, The circuits need to be tested should include:
3. DC power supply
5. Output contacts
6. Communication ports
Test method:
To unplug all the terminals sockets of this relay, and do the Insulation resistance test for each
circuit above with an electronic or brushless insulation tester.
On completion of the insulation resistance tests, ensure all external wiring is correctly reconnected
to the protection.
Check that the external wiring is correct to the relevant relay diagram and scheme diagram.
Ensure as far as practical that phasing/phase rotation appears to be as expected.
Check the wiring against the schematic diagram for the installation to ensure compliance with the
customer’s normal practice.
WARNING!
Energize this device ONLY if the power supply is within the specified operating range in
Chapter “Technical Data”.
The relay only can be operated under the auxiliary power supply depending on the relay’s nominal
power supply rating.
The incoming voltage must be within the operating range specified in Chapter “Technical Data”,
before energizing the relay, measure the auxiliary supply to ensure it within the operating range.
Other requirements to the auxiliary power supply are specified in Chapter “Technical Data”. See
this section for further details about the parameters of the power supply.
The current and voltage transformer connections must remain isolated from the relay for these
checks. The trip circuit should also remain isolated to prevent accidental operation of the
associated circuit breaker.
Connect the relay to DC power supply correctly and turn the relay on. Check program version and
forming time displayed in command menu to ensure that are corresponding to what ordered.
If the time and date is not being maintained by substation automation system, the date and time
should be set manually.
Set the date and time to the correct local time and date using menu item “Clock”.
In the event of the auxiliary supply failing, with a super capacitor fitted on MON board, the time and
date will be maintained. Therefore when the auxiliary supply is restored the time and date will be
correct and not need to set again.
To test this, remove the auxiliary supply from the relay for approximately 30s. After being
re-energized, the time and date should be correct.
On power up, the green LED “HEALTHY” should have illuminated and stayed on indicating that
the relay is healthy.
The relay has latched signal relays which remember the state of the trip, auto-reclose when the
relay was last energized from an auxiliary supply. Therefore these indicators may also illuminate
when the auxiliary supply is applied. If any of these LEDs are on then they should be reset before
proceeding with further testing. If the LED successfully reset, the LED goes out. There is no testing
required for that that LED because it is known to be operational.
It is likely that alarms related to voltage transformer supervision will not reset at this stage.
Apply the rated DC power supply and check that the “HEALTHY” LED is lighting in green. We
need to emphasize that the “HEALTHY” LED is always lighting in operation course except that the
equipment find serious errors in it.
Produce one of the abnormal conditions listed in Chapter “Supervision”, the “ALARM” LED will
light in yellow. When abnormal condition reset, the “ALARM” LED extinguishes.
NOTICE!
The closing circuit should remain isolated during these checks to prevent accidental
operation of the associated circuit breaker.
This test verified that the accuracy of current measurement is within the acceptable tolerances.
Apply rated current to each current transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the relays menu.
The measurement accuracy of the protection is 2.5% or 0.02In. However, an additional allowance
must be made for the accuracy of the test equipment being used.
Group No. Item Input Value Input Angle Display Value Display Angle
Three-phase current 1 Ia
Group No. Item Input Value Input Angle Display Value Display Angle
Ib
Ic
Ia
Three-phase current 2 Ib
Ic
Ia
Three-phase current 3 Ib
Ic
Ia
Three-phase current …… Ib
Ic
NOTICE!
The closing circuit should remain isolated during these checks to prevent accidental
operation of the associated circuit breaker.
This test verified that the accuracy of voltage measurement is within the acceptable tolerances.
Apply rated voltage to each voltage transformer input in turn; checking its magnitude using a
multimeter/test set readout. The corresponding reading can then be checked in the relays menu.
The measurement accuracy of the relay is 2.5% or 0.1V. However an additional allowance must be
made for the accuracy of the test equipment being used.
Group No. Item Input Value Input Angle Display Value Display Angle
Ua
Three-phase voltage 1 Ub
Uc
Ua
Three-phase voltage 2 Ub
Uc
Ua
Three-phase voltage 3 Ub
Uc
Ua
Three-phase voltage……
Ub
Group No. Item Input Value Input Angle Display Value Display Angle
Uc
Residual voltage 1 3U0
Residual voltage 2 3U0
Residual voltage 3 3U0
Residual voltage …… 3U0
This test checks that all the binary inputs on the device are functioning correctly. The binary inputs
should be energized one at a time, see external connection diagrams for terminal numbers.
Ensure that the voltage applied on the binary input must be within the operating range. The status
of each binary input can be viewed using relay menu. Sign “1” denotes an energized input and
sign “0” denotes a de-energized input.
In order to acquire the details of protection operation, it is convenient to print the fault report of
protection device. The printing work can be easily finished when operator presses the print button
on panel of protection device to energize binary input [BI_Print] or operate control menu. What
should be noticed is that only the latest fault report can be printed if operator presses the print
button. A complete fault report includes the content shown as follows.
3. Self-check and the transition of binary input in the process of devices start
1. Confirm the external wiring to the current and voltage inputs is correct.
However, these checks can only be carried out if there are no restrictions preventing the
Remove all test leads, temporary shorting leads, etc. and replace any external wiring that has
been removed to allow testing.
If it has been necessary to disconnect any of the external wiring from the protection in order to
perform any of the foregoing tests, it should be ensured that all connections are replaced in
accordance with the relevant external connection or scheme diagram. Confirm current and voltage
transformer wiring.
After the above tests are completed, remove all test or temporary shorting leads, etc. If it has been
necessary to disconnect any of the external wiring from the protection in order to perform the
wiring verification tests, it should be ensured that all connections are replaced in accordance with
the relevant external connection or scheme diagram.
If the protection is in a new installation or the circuit breaker has just been maintained, the circuit
breaker maintenance and current counters should be zero. If a test block is installed, remove the
test plug and replace the cover so that the protection is put into service.
Ensure that all event records, fault records, disturbance records and alarms have been cleared
and LED’s has been reset before leaving the protection.
13 Maintenance
Table of Contents
13 Maintenance .................................................................................. 13-a
13.1 Overview ...................................................................................................... 13-1
13.2 Appearance Check ...................................................................................... 13-1
13.3 Failure Tracing and Repair ......................................................................... 13-1
13.4 Replace Failed Modules ............................................................................. 13-2
13.4.1 Preparation for Replace Module ...................................................................................... 13-2
13.1 Overview
The device is designed to require no special maintenance. All measurement and signal processing
circuit are fully solid state. All input modules are also fully solid state. The output relays are
hermetically sealed.
Since the device is almost completely self-monitored, from the measuring inputs to the output
relays, hardware and software defects are automatically detected and reported. The
self-monitoring ensures the high availability of the device and generally allows for a corrective
rather than preventive maintenance strategy. Therefore, maintenance checks in short intervals are
not required.
Operation of the device is automatically blocked when a hardware failure is detected. If a problem
is detected in the external measuring circuits, the device normally only provides alarm messages.
2. It is only allowed to plug or withdraw relay board when the supply is reliably switched off.
Never allow the CT secondary circuit connected to this equipment to be opened while the primary
system is live when withdrawing an AC module. Never try to insert or withdraw the relay board
when it is unnecessary.
3. Check weld spots on PCB whether they are well soldered without any rosin joint. All dual
inline components must be well plugged.
When a failure is detected by supervision, a remote alarm is issued and the failure is indicated on
the front panel with LED indicators and LCD display. It is also recorded in the event record.
Failures detected by supervision are traced by checking the “Superv Events” screen on the LCD.
WARNING!
Module can ONLY be replaced while the device power supply is switched off.
ONLY appropriately trained and qualified personnel can perform the replacement by
strictly observing the precautions against electrostatic discharge.
WARNING!
Five seconds is NECESSARY for discharging the voltage. Hazardous voltage can be
present in the DC circuit just after switching off the DC power supply.
CAUTION!
Take anti-static measures such as wearing an earthed wristband and placing modules
on an earthed conductive mat when handling a module. Otherwise, electronic
components could be damaged.
CAUTION!
If the failure is identified to be in the relay module and the user has spare modules, the user can
recover the protection by replacing the failed modules.
Repair at the site should be limited to module replacement. Maintenance at the component level is
not recommended.
Check that the replacement module has an identical module name (AI, PWR, MON, DSP, BI, BO,
etc.) and hardware type-form as the removed module. Furthermore, MON module replaced should
have the same software version. In addition, the AI and PWR module replaced should have the
same ratings.
The module name is indicated on the top front of the module. The software version is indicated in
LCD menu “Version Info”.
3. Short circuit all AC current inputs and disconnect all AC voltage inputs
2. Unplug the ribbon cable on the front panel by pushing the catch outside.
6. After replacing the MON or DSP module, input the application-specific setting values again.
13.5 Cleaning
Before cleaning the relay, ensure that all AC/DC supplies, current transformer connections are
isolated to prevent any chance of an electric shock whilst cleaning. Use a smooth cloth to clean
the front panel. Do not use abrasive material or detergent chemicals.
13.6 Storage
The spare relay or module should be stored in a dry and clean room. Based on IEC standard
60255-1 the storage temperature should be from -40°C to +70°C, but the temperature of from 0°C
to +40°C is recommended for long-term storage.
Table of Contents
14 Decommissioning and Disposal ................................................. 14-a
14.1 Decommissioning ....................................................................................... 14-1
14.2 Disposal ....................................................................................................... 14-1
14.1 Decommissioning
DANGER!
Switch OFF the circuit breaker for primary CTs and VTs BEFORE disconnecting the
cables of AI module.
WARNING!
Switch OFF the external miniature circuit breaker of device power supply BEFORE
disconnecting the power supply cable connected to the PWR module.
WARNING!
1. Switching off
To switch off the PCS-902, switch off the external miniature circuit breaker of the power supply.
2. Disconnecting Cables
Disconnect the cables in accordance with the rules and recommendations made by relational
department.
3. Dismantling
The PCS-902 rack may now be removed from the system cubicle, after which the cubicles may
also be removed.
14.2 Disposal
In every country there are companies specialized in the proper disposal of electronic waste.
NOTICE!
Strictly observe all local and national laws and regulations when disposing the device.