Solution:
1. We can determine the properties of the air at on/off coil from the
below link for psychrometric properties:
http://www.sugartech.co.za/psychro/index.php
hoff coil=31.4 kJ/kg and RH=100%. These two properties fix the state of
the off coil temp. Other properties of the off coil are determined
from the above link:
2. The room is perfectly sealed and insulated, thus as we mix at the first time
step, the temperature will be reduced, and then the next time step the
In fact, there is no easy way to calculate the time except knowing the heat
extraction rate and the initial condition. basically, we will treat the cooling
coil as a black box that is just providing 1 TR= 3.517 kW of cooling. in this
case:
𝒖𝟏 = 𝟒𝟗. 𝟖𝟑 𝑲𝑱/𝒌𝒈
𝑢2 = ℎ2 − 𝑝1 𝜗2 → 𝑢1 = 31.4 𝐾𝐽/𝑘𝑔 − (1.013 𝐾𝑁/𝑚2 × 0.814 𝑚3 /𝑘𝑔) →
𝒖𝟐 = 𝟑𝟎. 𝟓𝟕 𝑲𝑱/𝒌𝒈
𝑉 5×5×3
𝑚1 = = = 87.21 𝑘𝑔
𝜗1 0.86
𝑚2 = 87.0 𝑘𝑔
𝑘𝐽
3.517 × 𝑡𝑖𝑚𝑒 = 𝑚1 𝑢1 − 𝑚2 𝑢2 →
𝑠
𝑘𝐽
3.517 × 𝑡𝑖𝑚𝑒 = (87.21 × 49.83) − (87.0 × 30.57) = 1,686.08