Compresor EKOM DK50DS
Compresor EKOM DK50DS
Compresor EKOM DK50DS
DK50 DS
MANUFACTURER
EKOM spol. s r. o.
Priemyselná 5031/18
SK-921 01 Piešťany
Slovenská Republika
tel.: +421 33 7967255
fax: +421 33 7967223
www.ekom.sk
email: [email protected]
CONTENTS
CONTENTS
1. GENERAL INFORMATION............................................................................................ 2
PURPOSE..............................................................................................................................................2
OPERATOR'S RESPONSIBILITY FOR PATIENT SAFETY .................................................................2
MARKING ..............................................................................................................................................2
WARNINGS ...........................................................................................................................................2
General safety warnings .............................................................................................................3
Electrical system safety warnings...............................................................................................3
ALERT NOTICES AND SYMBOLS .......................................................................................................4
USE ........................................................................................................................................................5
STORAGE AND TRANSPORT..............................................................................................................5
2. DEVICE DESCRIPTION................................................................................................. 6
3. TECHNICAL DATA........................................................................................................ 8
4. OPERATION .................................................................................................................. 9
INSTALLATION AND FIRST OPERATION ...........................................................................................9
Removal of transport stabilizers .................................................................................................9
Wheels installation......................................................................................................................9
Compressed air connection ......................................................................................................10
Electrical connection.................................................................................................................10
First operation ...........................................................................................................................10
Accessories...............................................................................................................................11
PERSONNEL .......................................................................................................................................12
Switching the compressor on....................................................................................................12
Running the compressor...........................................................................................................12
Cleaning and replacing the filters .............................................................................................13
Cleaning the compressor..........................................................................................................13
5. MAINTENANCE ........................................................................................................... 14
REPAIRS AND SERVICE ....................................................................................................................14
MAINTENANCE SCHEDULE ............................................................................................................14
Service kit .................................................................................................................................14
Maintenance replacement parts ...............................................................................................15
Maintenance replacement parts ...............................................................................................15
Safety valve check....................................................................................................................15
Check tightness of joints and inspect the appliance.................................................................15
Replacing filters in filter (19) .....................................................................................................16
Setting output air pressure........................................................................................................16
Replacing the suction filter (21) ................................................................................................17
Replacing the piston, connecting rod and piston rings.............................................................17
Replacing the bearing:..............................................................................................................18
Replacement of Printed Circuit (PS) SMART: ..........................................................................18
Stabilizing the compressor before shipping..............................................................................24
SHUT-DOWN.......................................................................................................................................24
DISPOSAL OF THE APPLIANCE........................................................................................................24
ACCUMULATOR DISPOSAL ..............................................................................................................25
6. TROUBLESHOOTING ................................................................................................. 25
7. PARTS LIST ................................................................................................................ 26
BASIC COMPONENTS........................................................................................................................26
ACCESSORIES ...................................................................................................................................26
8. ELECTRIC AND PNEUMATIC DIAGRAMS ................................................................ 27
WIRING DIAGRAM ..............................................................................................................................27
PNEUMATIC DIAGRAM ......................................................................................................................28
9. LIST OF SPARE PARTS ............................................................................................. 29
SM-DK50 DS-GB-3 1
GENERAL INFORMATION
1. GENERAL INFORMATION
PURPOSE
The EKOM DK50 DS is a medical air compressor that supplies clean, oil-free
pressurized air for use with medical ventilators.
Rx only
MARKING
Products marked with the CE mark of compliance meet the safety guidelines
of the European Union (93/42/EEC).
WARNINGS
2 SM-DK50 DS-GB-3
GENERAL INFORMATION
• Operation of the device must be in compliance with all local codes and
regulations.
• The original packaging should be kept for the possible return of the unit.
Only original packaging ensures optimal protection of the appliance during
transport. If it is necessary to return the appliance during the warranty
period, the manufacturer is not liable for damages caused by incorrect
packaging.
• If any problem occurs during use of the appliance, the user must notify his
supplier immediately.
• This product is not intended for use in areas with risk of explosion. Do not
operate the compressor in the presence of flammable anesthetics.
• Never put oxygen or nitrous oxide into the compressor. The components
are not approved for oxygen or nitrous oxide use.
SM-DK50 DS-GB-3 3
GENERAL INFORMATION
CE mark of compliance
Alternating current
Fuse
Condensate outlet
4 SM-DK50 DS-GB-3
GENERAL INFORMATION
USE
• The appliance can be installed and operated only in a dry, ventilated and
dust-free area. Climatic conditions for operation - see Technical data.
• The compressor must stand on a flat, sufficiently stable base.
• The compressor must not be exposed to rain. The appliance must not be
used in humid or wet environments. Never use the compressor in the
presence of flammable liquids or gasses.
• Before connecting the compressor to a respiratory appliance, make sure
that it meets the requirements of the respiratory appliance. Refer to the
Technical data for this purpose.
• Any use other than the compressor‘s intended use is not considered to be
safe. The manufacturer is not responsible for any damages that result if
the compressor is used for any other purpose. This risk is assumed only
by the operator/user.
The compressor is shipped from the factory in transport packaging with the
pump stabilized, protecting it from damage during transport.
For transport, always use the original packaging and secure the compressor
in the upright position.
Before moving or transporting the compressor, the pressure in the air tank
and hoses must be released and any condensed water must be drained.
Secure the motor before shipping.
SM-DK50 DS-GB-3 5
DEVICE DESCRIPTION
2. DEVICE DESCRIPTION
6 SM-DK50 DS-GB-3
DEVICE DESCRIPTION
SM-DK50 DS-GB-3 7
TECHNICAL DATA
3. TECHNICAL DATA
TYPE DK50 DS
-1
40 L.min
Output flow -1
50 L.min
200* L.min ( 7 Cft. min-1 )
-1
Peak flow
USA Model
Voltage / Frequency V/Hz 230/50 230/60 120/60 100/50-60
Nominal current A 2.8 2.8 5.6 5.6
Air filtration µm 5
-1 5°C (9°F) below the ambient temperature
Pressure dew point at 40 L.min
10°C (18°F) below ambient temperature – version with membrane
( 1.4 Cft. min-1 ), 3 bar( 43.5 psig ), 20°C (68°F)
dryer
DISS 1160-A (3/4"-16 UNF)
Outlet connection
NIST (EN 739)
Sound level dB(A) ≤ 50 ≤ 51 ≤ 51 ≤ 51
Mode of operation Continuous - S1
Separation of condensed water Automatic
Yellow (working pressure < 2,4 bar (34.8 psig) )
Indication of drying
Green (working pressure ≥ 2,4 bar (34.8 psig) )
Alarm of low pressure Decrease in output pressure under 2.1 bar ( 30.5 psig )
Alarm of cooling failure Increase in internal temperature above 80°C (176°F)
Output pressure Adjustable to max. 3.5 bar (51 psig)
Decrease in pressure in the central distribution under
Automatic turn-on pressure
2.8 bar ( 40.6 psig)
Air tank capacity 2 L (0.61gall UK)
Pressure range 5 bar ( 72.5 psig ) – 6.5 bar ( 94 psig)
Operating pressure of safety valve 8 bar ( 116 psig )
Adjustment of output air pressure Pressure regulator
Dimensions of compressor wxdxh 445 x 355 x 440 mm ( 17.5 x 14 x 17 in )
Dimensions of compressor with weels wxdxh 470 x 380 x 520 mm ( 18.5 x 15x 20.5 in )
Dimensions of compressor with trolley wxdxh 535 x 575 x 1054 mm ( 21 x 22,5 x 41,5 in )
Dimensions of packaging wxdxh 510 x 480 x 470 mm ( 20 x 19 x 18.5 in )
Dimensions of packaging 560 x 630 x 900 mm ( 22 x 25 x 35,5 in )
Net weight 30 kg ( 66 lbs )
Net weight of compressor with weels 31 kg ( 68 lbs )
Net weight of compressor with trolley 47 kg ( 104 lbs )
Gross weight 37 kg ( 82 lbs )
Gross weight of compressor with weels 38 kg ( 84 lbs )
Gross weight of compressor with trolley 54 kg ( 119 lbs )
Implementation according to EN 60601-1, EN 12021 Type B class I.
Classification according to MDD 93/42 EEC II b
* With 0.6 bar drop (8.7 psig)
8 SM-DK50 DS-GB-3
OPERATION
4. OPERATION
Only qualified personnel can install the compressor and put it into
operation for the first time. The installer shall train the operating
personnel in the use and routine maintenance of the appliance.
Installation and training of personnel should be acknowledged by the
installer‘s signature on the certificate of installation.
Never block the air intake filter in backside and the ventilating outlets
on the upside of the appliance.
Wheels installation
SM-DK50 DS-GB-3 9
OPERATION
The medical compressor is equipped with fast-on couplings WALL (10) and
OUT (9) on the rear of the cabinet.
To the fast-on coupling OUT (9) -output compressed air- connect the
pressure hose leading to the applicable appliance/respiratory apparatus.
Please note that the air supply from central distribution entering the
compressor must be medical grade air (particulate size, humidity.) The
compressor does not modify the air from central distribution.
Electrical connection
The electrical cord must not be stressed or have any tension exerted
upon it, and must always be free.
• The socket must be accessible for safety reasons so that the appliance
can be safely disconnected from the mains supply in case of emergency.
• The relevant current circuit must be safeguarded.
• Connection of the ground connection (12) to other appliances must adhere
to local electrical regulations.
• Fasten down the electrical cord through the holder (13).
First operation
• Make sure that the stabilizing screws used during transport were
removed.
• Check that the connection to the compressed air supply is correct.
• Check for proper connection to the mains supply.
10 SM-DK50 DS-GB-3
OPERATION
After the compressor is put into operation, it shall work in one of the following
modes depending upon the pressure level in the central distribution and upon
air consumption.
Accessories
Rack SD 30 (24)
SM-DK50 DS-GB-3 11
OPERATION
PERSONNEL
In case of emergency, switch the appliance off at the switch and pull
out the mains plug.
The green indicator POWER (8) is lit up during operation. Display displays
the value of output pressure with accuracy ± 5% in BAR or PSI units. An
indicator is lit on the display next to the relevant unit. Ask serviceman for a
change of display of units if necessary. After pressing the TIME (6) button,
the display shows the number of hours in operation. Indicator DRYING (4)
displays the drying status. Green indicates satisfactory drying; yellow
indicates unsatisfactory drying. If the yellow indicator DRYING (4) stays on,
make sure that the air consumption from the compressor did not exceed the
output flow according to specification. If air consumption is within normal
parameters, contact servicing centre.
Cooling failure is indicated by alarm TEMP (3) which sounds an alarm and
illuminates the yellow indicator. The device must be immediately
disconnected from the electrical mains and cooled down. Cooling failure
activation may indicate that the venting holes were covered, the filter in the
bottom part of the compressor is contaminated or the compressor works in
environment with higher temperature. If none of these circumstances apply,
a malfunction has occurred and service is required.
Illumination of yellow indicator BATTERY (7) signals low battery. During the
equipment operation the battery is recharged automatically. If the yellow
control light does not turn off after 24 hours of the equipment operation, it is
necessary to change the battery. The battery powers the MAINS (5) alarm
and has no impact on other functions of the device. Entrust an authorized
service provider with its replacement. Exchange the battery for identical type
with the original one - NiMH 9V 200mAh.
12 SM-DK50 DS-GB-3
OPERATION
The condensed liquid drains into a vessel (14) at the back of the device.
When the vessel fills up, it must be emptied.
At least once a week take out and clean the output filter (15) located on the
back side. Wash the filter in warm soapy water, rinse thoroughly and allow
them to dry. Insert the clean filters so that the intake openings are completely
covered by the filters.
SM-DK50 DS-GB-3 13
MAINTENANCE
5. MAINTENANCE
The manufacturer reserves the right to modify the appliance in any way
that will not alter the function or the operation of the appliance.
MAINTENANCE SCHEDULE
Service kit
A
4000 hrs. Input filter Filter Filter
Type 4KC-500 40 µm 5 µm
Number 025000018 025200142 025200113
pc 1 1 1
B
Piston with Filter coverSolenoid
8000 hrs . Suction filter O-ring Bearing Hose
rod complete
bubble to according to
Type 4KA-292 4CA-396 D50x2 6204 2RS DN8x400
AF20,AW20 model
Number 025200139 604021396 073000109 024000881 025900018 072000039
pc 1 1 2 1 2 1 1
14 SM-DK50 DS-GB-3
MAINTENANCE
Never use the safety valve to depressurize the air tank. This could damage
the safety valve.
SM-DK50 DS-GB-3 15
MAINTENANCE
• Check the condition of the filter. With regular operation, condensate from
the filter (19) drains automatically. Verify this function by comparing the
level of condensate in the bottle to the scale line indicating the maximum
level. If the level of condensate is above the scale line, replace the faulty
parts.
• Examine the pump for:
- impurities in the crankcase
- free movement of the crank shaft
• If necessary, replace any faulty parts.
• Unscrew the cover and pull it out using the enclosed wrench (26).
• Unscrew the filter holder.
• Replace the filter and screw the filter holder
into place. 26
• Screw the cover back in place.
16 SM-DK50 DS-GB-3
MAINTENANCE
SM-DK50 DS-GB-3 17
MAINTENANCE
Disassembly
• Remove the bearing using the bearing 6204 removal tool (Part No.
604001094).
• If the bearing is damaged and missing its external ring, use the metal ring
together with the clamping sleeve.
• Put the clamping sleeve and the metal ring on the internal ring. Tighten
the clamp.
Assembly
18 SM-DK50 DS-GB-3
MAINTENANCE
SM-DK50 DS-GB-3 19
MAINTENANCE
shall not display this up-date. The reason of this solution is not to interrupt
processor and let it regulate.
- Check whether the compressor works correctly in the corresponding working
mode and whether SoftStartStop functions works correctly on the basis of
the values of working and output pressure.
- In the case the incorrect function is indicated in clause 2 due to incorrect
calibration, remedy the fault using PC with “SERV_SMART v.1.0.1” software
by zeroing the offset of pressure sensors. When zeroing the offset of
pressure sensor, consistently take care after ensuring zero pressure in the
system. Offset zeroing without calibration is a makeshift solution.
- The compressor is constantly on or constantly off. Attempt to remedy the
fault using PC with "SERV_SMART v.1.0.1” software by setting the standard
initial condition followed by calibration. In the case the electronics does not
communicate, i.e. no values from the measurement of pressures,
temperature and worked out hours are displayed in the entrance window and
we are sure the communication cable is correctly connected and
communication port on PC is correctly set, the electronics board must be
replaced.
- In the case the compressor works correctly, “SERV_SMART v.1.0.1”
software displays the correct values of pressures and temperature and
incorrect data are on the foil keypad, the replacement of keypad board with
connecting cable is necessary.
Fig. 1
For setting the standard initial condition use PC with “SERV_SMART v.1.0.1”
software. Connect the computer with the compressor using “RS232 SERVIS
SMART” cable for PC. The correctness of cable connection and selection
of the correct communication port on PC is indicated by displaying the
measured values of pressures, temperature and worked out hours. The
displayed values are changing with the changes of the values of pressures
20 SM-DK50 DS-GB-3
MAINTENANCE
and temperature. Set the initial standard condition by clicking SETUP button.
This command writes the initial regulation parameters into EEPROM
memory of control microprocessor. Manufacturer recommends the
increased caution when using this command since this command
overwrites calibration! For this reason operator must respond to a question
„Are You Sure?". The acknowledgement of record is indicated by “„Default
Calibration and Setup OK“ message sent back by the microprocessor. After
setting the standard initial condition, the compressor shall work flawlessly but
the values of pressures and temperatures shall not be accurately set. The
increase of accuracy of pressure measurement shall be achieved by
measuring pressure sensor offset zeroing. Carry out the accurate setting of
these values in calibration mode.
Calibration
Compressor
Fig. 2
SM-DK50 DS-GB-3 21
MAINTENANCE
• Connect the measuring device - Fig. 2 onto the outlet of air from
compressor.
• Set regulation valve of output pressure of compressor so that the value of
its output pressure was the same as the value of working pressure.
• Turn on DK50 DS compressor with zero output consumption of
compressed air set. When electronics gets “STANDBY” mode, working
pressure reaches almost the maximal value, start “SERV_SMART v.1.0.1”
software. Activate “CAL” button from "Working Pressure” environment.
When SMART board starts communicating with PC, the compressor shall
stop and CAL message is displayed on the display of SMART electronics
and OK status appears on the computer.
• Carry out calibration in two points withal the first point is the current value
of working pressure measured by calibration gauge. The second point is
the zero value of pressure we reach after the complete release of
compressed air from the compressor.
• The acknowledgement of calibration of the relevant sensor is indicated by
“Calibration OK“ message on PC“.
• Connect the measuring device – Fig. 2 onto the outlet of air from
compressor.
• Set regulation valve of output pressure of compressor so that the value of
its output pressure was the same as the value of working pressure.
• Turn on DK50 DS compressor with zero output consumption of
compressed air set. When electronics gets “STANDBY” mode, working
pressure reaches almost the maximal value, start “SERV_SMART v.1.0.1”
software. Activate “CAL” button from "Working Pressure” environment.
When SMART board starts communicating with PC, the compressor shall
stop and CAL message is displayed on the display of SMART electronics
and OK status appears on the computer.
• Carry out calibration in two points withal the first point is the current value
of working pressure measured by calibration gauge. The second point is
the zero value of pressure we reach after the complete release of
compressed air from the compressor.
• The acknowledgement of calibration of the relevant sensor is indicated by
“Calibration OK“ message on PC.
Calibration of Temperature t
22 SM-DK50 DS-GB-3
MAINTENANCE
Fig. 3
P1 P2 t
The control electronics has the feature for the conversion of display of output
pressure from physical units “bar” to “psi”. Conversion is to be carried out
using “JM1” jumper (bar - 1,2) (psi - 2,3) that is set by manufacturer in
“bar” position. Indication of setup is displayed on the display as follows:
• Bar – horizontal line on top
• Psi – horizontal line in the centre
SM-DK50 DS-GB-3 23
MAINTENANCE
1 2 3
SHUT-DOWN
24 SM-DK50 DS-GB-3
TROUBLESHOOTING
ACCUMULATOR DISPOSAL
6. TROUBLESHOOTING
Prior to servicing the appliance, reduce the pressure in the air tank to
zero and disconnect the appliance from the mains supply.
Only trained service personnel can perform the activities listed in the
troubleshooting guide.
PROBLEM POTENTIAL CAUSE SOLVING COMMON PROBLEMS
The STANDBY mode, the compressor starts
There is pressure in the air tank
upon the pressure decrease
Switched off mains breaker in distribution
system
Check supply
No mains voltage
Compressor does Replace the defective fuse
not start Loose wire terminal – tighten
Power cord defective – replace
Interrupted winding of motor, damaged
Replace motor
thermal protection
Defective capacitor Replace capacitor
Jammed piston or other part Replace damaged parts
Leakage of air from pneumatic Inspect pneumatic distribution system – seal
distribution system loose connection
DRYING indicator Large consumption of compressed air Do not exceed max. flow (see Technical data)
lights yellow Worn out piston rings Replace worn out piston rings
permanently
Dirty air suction filter Replace the dirty air suction filter
Dirty air intake filter Clean or replace the dirty air intake filter
Leakage of air from pneumatic Inspect the pneumatic distribution system –
distribution system seal loose connection
Large consumption of compressed air Do not exceed max. flow (see Technical data)
PRESSURE
alarm is activated Worn out piston rings Replace worn out piston rings
permanently Dirty air suction filter Replace the dirty air suction filter
Dirty air intake filter Clean or replace the dirty air intake filter
Dirty filter inserts of filter Replace the dirty inserts
Dirty air blow filter Clean or replace the dirty air blow filter
TEMP alarm is Covered vent holes Uncover vent holes
activated Cooling fans don´t work Replace fans
Unit is hot, unventilated area Relocate unit
Damaged piston bearing or bearing in
Compressor is Replace damaged bearing
motor
noisy (knocking,
Loose (cracked) belt of the air pump
metal noises) Replace damaged hanger
hanger
Water coming out Dirty water trap in filter and filter
Clean or replace the water trap
of outlets regulator
Compressor
Failure of control unit Adjust using service software
malfunction
SM-DK50 DS-GB-3 25
PARTS LIST
7. PARTS LIST
BASIC COMPONENTS
• Compressor 1 pc
• Installation, Operation and Maintenance Manual 1 pc
• Air intake filter (15) 025000018 1 pc
• Filtration inserts (19a)(Bronze)AF20P-060S-7-40B 025200142 1 pc
• Filtration inserts (19b)(Plastic) AF20P-060S 025200113 1 pc
• Fuse 2 pcs
Version 230V T6,3A 038100004
100V, 120V T10A 038100005
• Insertion DISS 1160-A 024000261 2 pcs
• Screw-wrench No. 3 192000005 1 pc
• Wrench for de-fixation and replacement of filtration inserts
023000933 1 pc
ACCESSORIES
These items are not components of the compressor and must be ordered
separately.
26 SM-DK50 DS-GB-3
ELECTRIC AND PNEUMATIC DIAGRAMS
WIRING DIAGRAM
DISPLAY
YV ST
?
14
1 X2
14
U Display
Valve
N
N - +
N
9V
N
battery
U ~
U Motor
U Fan
3rd contact
X1
M
XC 1
M EV1 EV2
U PE N
Wiring diagram DK50 DS
SM-DK50 DS-GB-3 27
ELECTRIC AND PNEUMATIC DIAGRAMS
PNEUMATIC DIAGRAM
10 11
4 8
OUT
T1 9
6 7 6
3 2 WALL
5 12
P1 P2
1. Suction filter
2. Compressor
3. Solenoid valve
4. Return valve
5. Cooler
6. Filter with water trap
7. Pressure regulator
8. Air outlet
9. Air inlet
10. Air tank
11. Safety valve
12. Shuttle valve
28 SM-DK50 DS-GB-3
LIST OF SPARE PARTS
SM-DK50 DS-GB-3 29
LIST OF SPARE PARTS
30 SM-DK50 DS-GB-3
LIST OF SPARE PARTS
SM-DK50 DS-GB-3 31
LIST OF SPARE PARTS
32 SM-DK50 DS-GB-3