5 BS 5345 P3 Elect - Apparatus.explosive PDF
5 BS 5345 P3 Elect - Apparatus.explosive PDF
5 BS 5345 P3 Elect - Apparatus.explosive PDF
Contents
Page Page
Foreword Inside front cover IO. Environmental conditions 3
Cooperating organizations Back cover 11, Requirements for certification of apparatus 3
Figure
. 1. Selection chart for direct entry of cables
into flameproof enclosures'
This code of practice represents a standard of good practice and takes the form of recommendations. Compliance with it'
does not confer immunity from relevant statutory and legal requirements.
Foreword
Many gases, vapours, mists and dusts encountered in techniques (or 'types of protection' as they are known)
industry are flammable. When ignited they may burn have been used for many years and have come to be
readily and with considerable explosive force if mixed with regarded as traditional. Other types of protection have
air in the appropriate proportions. 'It is.often necessary t o been introduced only recently.
use electrical apparatus in locations where such flammable
materials may be present, and appropriate precautions This code of practice describes the basic safety features of
should therefore be taken to ensure that all such apparatus
is adequately protected in order to reduce the likelihood of
I
these types of protection, full details of which are given in
the relevant standards, and recommends the selection,
-0
ignition of any external explosive atmosphere. When using installation and maintenance procedures that should be
electrical apparatus, potential ignition sources include adopted to ensure the safe use of electrical apparatus in
electrical arcs and sparks, hot surfaces and, in certain hazardous areas. This code therefore takes account of the
circumstances, frictional sparks. significant developments that have taken place in area
In general, electrical safety is ensured by implementing one classification and in the design, manufacture and use of
electrical apparatus for hazardous areas since the prepara-
of two procedures. Either the electrical apparatus should be
tion of the earlier code of practice CP 1003.
located, whenever practicable, outside hazardous areas; or
the electrical apparatus should be designed, installed and It i s important to note that this code of practice deals with
maintained in accordance with measures recommended for explosion hazards due to the presence of flammable gadair
the area in which the apparatus is located. mixtures; it does not provide guidance on the extra
Several techniques are available for the protection of precautions to be taken where such gases involve a toxic
electrical apparatus in hazardous areas. Some of these hazard.
existing installations may need to be made in accordance 3.4 joint. The place where correspondingsurfaces of the
with the recommendations of the earlier code. It is different parts of an enclosure come together and where
intended, however, that CP 1003 : Parts 1,2 and 3 will flame paths from inside to the outside of the enclosure
eventually be withdrawn from use. occur.
Notwithstanding application of the installation 3.5 length of flame path (width of joint). The shortest
recommendations of this code to existing installations, distance, measured along the flame path from the inside
the recommendations for maintenance should be applied to the outside of the flameproof enclosure.
to all electrical apparatus and installations, irrespective of
age and date of installation. It should also be noted that the
installation and maintenance recommendations given in the 4. Description of technique
code are supplementary to, and not alternative to, require- Electrical apparatus complying with the requirements
ments that would apply to general industrial installations for type of protection 'd' is so designed and constructed
(see also Part 1 of the code). that it is not capable, under practical conditions of
operation within the rating of the apparatus (and
recognized overloads and defined fault conditions, if any,
associated therewith), of igniting a surrounding explosive
Section one. General principles atmosphere.
This i s achieved by:
1. Scope
(a) completely surrounding the electrical apparatus with
This Part of BC 5345 describes the concept of ensuring an enclosure, including flamepaths as necessary, of
electrical safety in hazardous areas by means of type of
sufficient strength and integrity of manufacture to
protection 'd': flameproof enclosure, and gives guidance
withstand internal explosions without suffering damage
on the selection, installation and maintenance of this type and without communicating the internal flammation to
of electrical apparatus. the external flammable gas or vapour for which it is
This code does not apply to the underground mining designed through any joints or structural openings in
industry, where other precautions are necessary, though the enclosure:
it is recognized that the code may be applied to the surface (b) restricting the maximum external surface tempera-
installations of mines. ture to below the ignition temperature of the gas or
Apparatus with type of protection 'd': flameproof vapour which presents the explosion risk.
enclosure is designed for use in areas with flammable gas NOTE. The maximum surface temperature should take into account
and vapour risks. Combustible dusts are excluded from this possible restrictions of air circulation, extreme environmental
Part and are dealt with in Part IO. conditions and heat from adjacent plant. See also Part 1 of the code.
-
2. References
5. Relewant specifications
The t i t l e s of the standards publications referred to in this
code are listed on the inside back cover. The specifications currently available for apparatus with
type of protection 'd': flameproof enclosure are as follows:
3. Definitions and explanations of terms (a) I EC Publication 79-1'Electrical apparatus for
The definitions and terms generally applicable to hazardous explosive gas atmospheres' published by the International
areas and electrical apparatus used therein are included in Electrotechnical Commission.
Part 1 of the code, to which reference should be made. The (b) EN 50 018 'Electrical apparatus for potentially
definitions and terms that are particularly relevant to explosive atmospheres- Flameproof enclosure 'd' '
individual types of protection are given in the appropriate prepared by the European Committee for Electro-
Parts of the code, For the purposes of this Part, the technical Standardization (CENELEC), the English
following definitions and terms apply. language version being BS 5501 'Electrical apparatus for
NOTE. The following definitions are derived from BS 4683 : Part 2 potentially explosive atmospheres' Part 5 'Flameproof
and BS 229. Other very similar definitions may be found in IEC enclosure 'd".
Publication 79-1 and BS 5501 : Part 5.
(cl BS 4683 'Electrical apparatus for explosive
3.1 type of protection 'd': flameproof enclosure. A method
atmospheres' Part 2 'The construction and testing of
of protection where enclosures for electrical apparatus will
flameproof enclosures of electrical apparatus'.
withstand an internal explosure of the flammable gas or
vapour which may enter it, without suffering damage and (d) BS 229 'Flameproof enclosure of electrical apparatus'.
without communicating the internal flammation to the NOTE 1. BS 5501 : Part 5 (EN 50 018) and BS 4683 : Part 2 are
used for all new certification applications and for all new designs of
external flammable gas or vapour for which it is designed,
flameproof enclosures.
through any joints or structural openings in the enclosure.
NOTE 2. Although superseded by BS 5501 : Part 5 and BS 4683 :
3.2 gap (diametral clearance). The distance between the Part 2, BS 229 remains valid for the manufacture of existing
corresponding surfaces a t a joint, measured normally to the certified equipment. Equipment certified t o editions of BS 229
surfaces. For cylindrical surfaces, the gap is the difference prior to 1946 should not be newly installed without consultation
with the authority having jurisdiction in the industry or area
between the two diameters and i s usually referred to as the concerned. It i s intended that BS 229 will eventually be withdrawn.
diametral clearance.
-k (e) IEC Publication 79-8'Classification of maximum
3.3 'gap (maximum experimental safe). The maximum gap
which has been found to prevent ignition of the most easily surface temperatures'.
ignited external mixture when the most incendive mixture (f) BS 4683 'Electrical apparatus for explosive
of the same flammable material is exploded inside the t e s t atmospheres' Part 1 'Classification of maximum surface
vessel. temperatures'.
2 Standards
COPYRIGHT British Standards Institute on ERC Specs and
Licensed by Information Handling Services
B S I BSX5345 P A R T * 3 77 Lb24bb7 011181181 5 M
be invalidated if the apparatus is used a t an ambient to prevent any external solid obstacle which is not part
temperature higher than that for which the certification of the apparatus, such as steelwork, walls, weatherguards,
applies. mounting brackets, pipes or other electrical equipment,
approaching nearer than the distance recommended in
COPYRIGHT British Standards Institute on ERC Specs and Standards 3 table 2 from the outer edge of the enclosure flange or .
Licensed by Information Handling Services oDenina.'
BSI B S m 5 3 4 5 PART*3 79 W 3 6 2 4 6 6 9 0348482 7
~
'
apparatus certified to this standard should be available with
BS 5345 : Part 3 : 1979 any thread form that the manufacturer originally specified,
inlcuding I S 0 metric threads, as given in BS 31 and
ES 4568.
__
-
- --A
detectors, It cannot be too strongly emphasized that Conduit systems should be installed in accordance with'
the recommendations of Part 1 of the code. , It is
/1\
extreme care should be exercised in the selection and
application of these substances to ensure the retention of recommended that the use of conduit in outdoor locations
the non-settingcharacteristics, and subsequent separation is kept to an absolute minimum.
- -
of the joint surfaces.
NOTE. The use of silicone based compounds for the sealing of gas 15.3.2 Stopper boxes or other approved sealing devices
detector heads and associated fittings is not recommended because should be fitted a t each point of connection with flame-
of the poisoning effect of silicones on most detector elements. The proof apparatus. The exception to this is where a sealing
manufacturer of the gas detector units should be consulted for
advice on suitable sealing compounds. device forms an integral part of the apparatus and i s
certified as such.
14.4 Joints should not be treated with substances which
harden in use. 15.3.3 Stopper boxes or other approved sealing devices
should be fitted to all enclosures accommodating cable
1 .I-
$14 5 ___ joints and/or terminals and conduit fittings containing
For any Group II apparatus, non-hardeningtape shoulJ terminals, e.g. conduit junction boxes with terminals
be employed only where such apparatus is used in
including earth terminals.
conjunction with gases allocated to Group IIA (see
tables 3 and 5 of Part 1 of the code), 15.3.4 Where every item of flameproof apparatus
connected to a conduit system has a sealing device fitted
Unless expert advice is sought, non-hardeningtape to each point of entry, it is permissible to use conduit and
should not be employed where Group II B or II C
fittings complying with the requirements of BS 31 or
apparatus is used in conjunction with gases allocated
to Group II B. ES 4568 provided that there is no discontinuity in the
conductors or their insulation. Where terminals or
Non-hardeningtape should not be employed where
group II C apparatus i s used in conjunction with terminations are required they should be protected by a
gases allocated to Group II C.'
- ~ __
flameproof enclosure. .
15.3.5 Where it is necessary to employ a joint other than a
a
14.6 Weatherseals for entry devices may be by means of -. screwed coupler, suitable unions approved for the purpose
purpose designed sealing washers or a suitable thread sealant should be used. Running couplers are not permitted.
(see 14.3). However the minimum number of threads 15.3.6 All screwed joints should be pulled up tight and
engaged should s t i l l be in accordance with the flamepath should in addition, for parallel threaded components, be
-*
requirements for the apparatus group concerned and the provided with locknut.
earth continuity should be maintained through the entry
device to the enclosure. 15.3.7 All conduit and conduit fittings should be checked
before assembly to remove all sharp edges and burrs which
could cause damage to cables when being pulled in.
15, Wiring systems -
' The general recommendations and requirements for wiring 9 -
I
NOTE 2. Where a factory-made termination of the encapsulated
type is used, no attempt should be made to interfere with the
connection to the apparatus or to replace the cable, The apparatus
should be returned to the manufacturer for repair.'
5
COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
I . .._. .
BS 5345 : Part 3 : 1979
. - . 19.3 Care should be taken to avoid paint or any other enclosures, except by the complete assembly or part
. .
.i
. i,
.. . .. .. .... .
.....
I
...
'
coating entering the gap. See clause 14. obtainable from the manufacturer, and complying with
.
. .... . . . the flameproof certificate.
19.4 Equipment enclosures and fittings should be
examined to see that all stopping plugs (see clause 16) and 19.6 Repairs and refurbishing of apparatus with type of
. - bolts are in position and tight. Locking and sealing devices protection 'd' should be performed only by the original
should be checked to confirm that they are secured in the
. . ..
.. . .. manufacturer, his authorized agents or a repairer who i s
:
...
. .- ' . prescribed manner. Replacement cover securing fasteners,
nuts, studs or bolts should be types specified by the
conversant with the construction standards for flameproof
. . . . ... . equipment and demonstrates the ability t o understand
manufacturer for the particular apparatus. certification restraints.
19.5 No attempt should be made to replace or repair a
glass in a flameproof enclosure, eng. in a luminaire or other
. .
. .
. . _
: . . .. . .
..
.. . .
. .
. . . .
. . --. .
..
. . . .. - .. ..
. .
. .... .
. .
..
-..
.. ..
-.
.-...: Table 1. Inspection schedule; apparatus with type of protection 'd': flameproof enclosure
. .
Initial Periodic
. ..
._
- Enclosures, glasses and glasslmetal seals are Satisfactory A A
There i s no undue accumulation of dust or dirt B B Accumulation of dust Or dirt can interfere
- . with heat dissipation and result in surface
. . temperatures higher than those permitted in
.. the hazardous area.
. .
All conduit runs and fittings are tight and free from corrosion A B
..
Earthing i s satisfactory A A
Lamp rating and type are correct A B An 'initial' inspection is necessary after
relamping.
'Category A inspections should be carried out in all cases and, where 'periodic', at intervals not exceeding two years. More frequent andlor
more detailed inspectionwill be necessary where there is a corrosive or other adverse atmosphere, a high risk of mechanical damage or
'
vibration, or where there are other onerous circumstances. The need for more frequent inspection may also be determined by operating
experience.
The need for, the method, and the frequency of category B inspections is at the discretionof the engineer responsible. It is not intendedthat
periodic inspections should incur undue disturbances of apparatus, unless considered necessary by the engineer responsible.
- 7
COPYRIGHT British Standards Institute on ERC Specs and Standards
Licensed by Information Handling Services
BSI B S m 5 3 4 5 PART*3 79 Lb24669 0 1 4 8 4 8 6 4 M
.~ .
I
'Table 2. Minimum distance of obstruction from
flange or opening
Minimum distance
. .- .
.'.
. :
. . .. . ...
.
. .... .
. . .:. .
. i _
. . IIB 30
IIC 40
. - 'Apparatiis designed for a particular subgroup but used in a gas for '
i: . , .
. . which another lower subgroup would normally be applicable
... .. . .
(see 7.4.Z(c) of Part 1 of the code) may alternatively observe the
. . clearances for the gas in questlon, e.g. for Group IIC apparatus
. _.... . .
. _.
....-..
'
. used in a Group IIA atmosphere the 10 mm distance may apply
. . . Insteadof 40 mm:
. ,. .
Figure 1. Selection chart for direct entry of cables into flameproof enclosures
. .
. .
. .
- .
~-
. . . . Use
. . . . . ....
.. . . .. .
I appropriate
miIIera I
. . . . . . , insdared
.. glands t o
15.4.3
.
.. .
. .
. .
. ..
.'. . . . .
. . . _
. . . -
Use enrry ac
ce itif ied
see
15.4.2(a)
and (b)
Use any
. . suitable
I .
--
No
. . .
Internal sources of ignition include sparks or equipment temperatures occurring in normal service which can cause ignition. An enclosure
containing terminals only or an indirect entry enclosure is considered not to constitute an internal source of ignition.
Cooperating organizations
The General Electrotechnical Engineering Standards Committee, Thear@anizations marked with an asterisk in the above list, together
under whose direction this British Standard was prepared, consists with ttìe following, were directly represented on the committee
of representatives from the following Governmenf departments and entrusted with the preparat.ion of this British Standard:
scientific and industrial organizations: Association of British Mining Equipment Companies
-
*Associated Offices Technical Committee Association of Consulting Engineers
cg,
'British Approval? Service for Electric Cables Association of Mining Electrical and Mechanical Engineers
'British Electrical and Allied Manufacturers' Association (BEAMA) British Electrical Systems Association (BEAMA)
British Radio Equipment Manufacturers' Association British Gas Corporation
British Steel Corporation British Industrial Measuring and Control Apparatus Manufacturers'
Department of Energy (Electricity) Association
*Electric Cable Makers' Confederation British Industrial Truck Association
*Electrical Contractors' Association CBMPE
Electrical Contractors' Association of Scotland Chief and Assistant Chief Fire Officers' Association
*Electrical Research Association Civil Aviation Authority (Airworthiness Division)
*Electricity Supply Industry in England and Wales Council for Electrical Equipment for Flammable Atmospheres
*Electronic Components Industry Federation (BEAMA)
Electronic Engineering Association . Department of Energy (Petroleum) (O1L)
*Engineering Equipment Users' Association Department of the Environment
*Health and Safety Executive Department of the Environment (Building Research Establishment)
Home Office (Fire Research Station)
*Institution of Electrical Engineers Department of Trade (Marine Division)
'Ministry of Defence Fire Offices Committee
*National Coal Board Fire Protection Association
*Oil Companies Materials Association General Council of British Shipping
+Post Office Institute of Petroleum
Institution of Gas Engineers
Institution of Mining Engineers
Lighting Industry Federation Ltd.
Rotating Electrical Machines Association (BEAMA)
Scientific Instrument Manufacturers' Association
Telecommunication Engineering and Manufacturing Association
(TEMA)
- -
British Standards Institution 2 Park Street London W1A 2BS Telephone 01-629 9000 Telex 266933 -
GEL11 14
-
861 1 -5 -2k-B . _
AMD 5958
Amendment No. 1
published and effective from 31 July 1989
to BS 5345 : Part 3 : 1979
Code of practice for selection, installation and
maintenance of electrical apparatus for use in
potentially explosive atmospheres (other than
mining applications or explosive processing
and manufacture)
Part 3. Installation and maintenance requirements
for electrical apparatus with type of
protection 'd'. Flameproof enclosure
Revised text
Figure
1. Selection chart for direct entry of cables
into flameproof enclosures'
I IC 40
Use
appropriate
mineral
insulated
glands to
15.43
-
Apply
subclause
. .
15.4.4
Use entry a:
certified
see
15.4.2(a)
and (6)
Use any
suitable
certified
flameproof
cable gland,
e.g. BC 5501
Apply
subclause
15.4.4
*Internal sources of ignition include sparks or equipment temperatures occurring in normal service which can cause ignition. A n enclosure
containing terminals only or an indirect entry enclosure is considered not t o constitute an internal source of ignition.
Figure 1. Selection chart for direct entry of cables into flameproof enclosures