Dosing System Design Description

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 4

DOCUMENT SUBMISSION STATUS: AP

REV DATE DESCRIPTION DRWN CHKD APPD

OWNER OWNER’S CONSULTANT

POYRY ENERGY LTD


VIETNAM OIL AND GAS GROUP (PVN)

EPC CONTRACTOR EPC CONTRACTOR’S CONSULTANT

VIETNAM MACHINERY
INSTALLATION CORPORATION (LILAMA)
FICHTNER GmbH & Co. KG

PROJECT TITLE
VUNG ANG 1 THERMAL POWER PLANT 2 x 600MW
BOILER ISLAND
CONTRACT No.
180609/LILAMA-BWBC
DRAWING TITLE
Dosing system Design Description
FUNCTION NAME SIGN DATE
SUB-CONTRACTOR

DRWN Wangzhencong 11.09.25


BABCOCK & WILCOX
CHKD Zhaoyan 11.09.25
BEIJING CO., LTD.
APPD Panting 11.09.25

SCALE REV A
DOCUMENT No. VA1-BWBC-00100-M-M1A-MAN-18902

BOILER BOP SUB- CONTRACTOR


ZHEJIANG ENERGY
ZHEJIANG ELECTRIC
CONSTRUCTION CO.,LTD

JIANGSU SHUANGLIANG BOILER CO., LTD

1
Dosing System Design Description

Jiangsu Shuangliang Boiler Co.,Ltd.


2011-8-25

1.0 Brief Description


This dosing system is ammonification device for feedwater. It controls the dosing
quantity by adjusting the rotary speed of special dosage pump. It is the function of

2
ammonification & dosing device to adjust the PH value of boiler feedwater and make
the PH value of feedwater keep within certain range, so that it can prevent the acid-
base corrosion of thermal force caused by PH value in coordination of feedwater and
keep the thermal system at the best operation state, extend the service life of thermal
devices and guarantee the thermal device run steadily and safely. The PH value of
feedwater should be in 8~9.
2.0 Principle of Ammonification System
The basic principle of ammonification treatment is to make use of the alkalinity
when ammonia dissolves in the water to neutralize the acidity when carbon dioxide
dissolves in the water. The ammonia is a kind of volatile substance, and it can
circulate with water and stream. When the CO2 is dissolved in the water, H2CO3 will
be produced; and when NH3 is dissolved in the water, NH4OH will be produced also.
H2CO3 and NH3 will carry out the neutralization reaction:
 NH4OH 十 H2CO3  NH4HCO3 十 H2O
 NH4HCO3 十 NH4OH (NH4)2CO3 十 H2O
Reaction result eliminates the acidity caused by CO2 and increases the pH value
of feedwater, so that surface protection film can prevent the metal equipment from
corrosion.
Ammonia treatment can basify the feedwater and increase the pH value. It will
not increase the salt content and alkalinity of feed water and affect the steam quality.
In addition, because of the volatility of ammonia, it can reach whole water steam
system, and protect the devices and pipelines of feedwater 、 condensing water and
drainage water systems.
3.0 Composition of ammonification system
Ammonification system is composed of stainless steel medical tank, mixing pump,
dosing pump and exit pipelines.

3.1 Dosing pump:


Type:JYM1.6-40-1.0 
Power:0.37KW 

3
Flow rate:40L 
Pressure:1.0MPA 
Power Supply Voltage:400V
Stirrer Type:GJ-1 
Power:0.75KW 
Rotate Speed:170R/MIN 
Power Supply Voltage:400V

4.0 reference drawing


VA1-BWBC-00100-M-M1A-PID-19086