THREE-PHASE

ELECTRICITY
ELECTRONIC METER
ENERLUX T
ENERLUX T meters belong to the category of the work measuring means and are meant for
active and reactive electric energy metering for residential consumers and commercial and
industrial agents that use multi-tariff systems for electric energy billing on low, medium and
high voltage networks. The instrument enables electric energy metering in both directions of
energy circulation. • meters of the latest generation,
multitariff, multifunctional
TECHNICAL CHARACTERISTICS:
• active and reactive energy metering in 4
Rated values:
dials, class 0.2S; 0.5S; 1 (SREN 61036,
- Rated voltage Un (V): 3x58/100 V...3x240/416 V; 3x100 V...3x416 V
- Rated current In (A): 1 A, 5 A for the meter with transformer connection SREN 60687 or SREN 61268)
- Base current Ib (A): 5 A, 10 A for the meter with direct connection • demand registering
- Maximum current Imax (A): - 6 A, 10 A, 20 A for the meter with transformer
connection
• communication possibilities (IEC 61107)
- 40 A, 60 A, 80 A, 100 A for the meter with direct
connection
- Rated frequency fn (Hz): 50 Hz or 60 Hz
- Frequency range (Hz): 45...65
- Meter constant (imp/kWh): 1000/5000/10000
* Other variants available on request.
Accuracy characteristics and influences:
- class 0.2S, 0.5 S, for active energy, according to IEC 62052-22;
- class 1, 2, for active energy, according to IEC 62052-21;
- class 2, 3, for reactive energy, according to IEC 62052-23
- Time base accuracy: max.±0.5s/24h according to IEC 1038
Climatic characteristics:
o
- Operating temperature range: -40...+60 C
o
- Transport and storage temeprature: -40...+80 C
Mechanical and constructive characteristics:
- Overall dimensions: 254x178x70 mm, according to figure 1
- Fixing dimensions in 3 points: 154x171 mm, according to figure 1
- Display: LCD custom design 80x30 mm according to fig. 2
- Wiring diagram: L1L1L2L2L3L3NN
- Optical port and current loop: according to IEC 62056-21
- Protection degree: IP 51
- Meter testing device: LED for imp/kWh + LED for imp/kvarh

Equipment options:
A - Auxiliary supply voltage; C - Load profile memory;
D* - Sealable maximum demand reset button; G - Pulse generator;
M - RS232 port with DB9 connector for R - Signalling relays;
remote reading;
S* - Sealable button for blocking the parameters changing
* options D and S can not be chosen together for the same meter
All the equipment options are optional.
The 3 auxiliary outputs (G and R equipment options) can be configured as:
- pulse generators;
- signalling relays;
The electrical characteristics of the auxiliary outputs:
- voltage max. 40 V;
- current max. 100 mA;
- pulse length for the pulse generator: min. 30 ms
Operational characteristics:
• Energy metering, as presented below:
a). 3 registers of active imported, exported, and active unidirectional energy (W+, W-,
W++W-);
b). 9 registers of active energy in quadrants I, II, III, IV imported (I+II), exported (III+IV),
inductive (I+III), capacitive (II+IV), total reactive (I+II+III+IV);
c). 2 registers of apparent imported and exported energy.
Eight of the energy types, as per clauses a)...c) (programmable) can be metered in up to 4
time zones.
• Demand registering
The meter is provided with: - 8 registers for 8 demands
- 8 cumulative registers corresponding to the 8 demands
Each of the 8 demands can be programmed to be calculated from each of energy types,
according to clauses a), b), c).
The programmable time interval with 5, 10, 15, 20, 30, 60 min. using block or sliding window
method .
The demand registering functions can be suspended for some time after the supply
breakdown and its resuming. The time interval will be programmable from 0 to 60 minutes with
one minute resolution.
M5 M6 M7 M8 D2 Rst 9s TEST
For each of the 8 demands a threshold can be programmed; if the threshold is exceeded by the
calculated demands for demand registering, the meter detects and stores these exceeding Fig. 2
values as an event, and signals them out as relay contact outputs.
• Display
• Clock-calendar
According to figure 2, the LCD displays the folowing:
The meter is provided with the clock-calendar function and the observance of leap years.
- voltage on each phase L1, L2, L3;
The meter clock-calendar function enables the automatic change of the summer/winter hour
- active tariff (T1, T2, T3, T4);
according to "last Sunday in March/October" rule, with programmable changing hour and
- the programmed demand which is calculated as per
direction, and with the possibility of disabling this function.
programming (M1, M2, M3, M4, M5, M6, M7, M8, as per fig. 2);
• Tariff programs - code of displayed quantity according to IEC 62056-61
The meter enables tariffying the energy in up to 4 time zones. Up to 8 of the measured energy Electricity metering - Data exchange for meter reading, tarrif
types, as per clauses a), b), c) can be configured to be tariffyed in time zones. and load control - Part 61 - OBIS Object Identification System;
There can be defined two independent tariffying sequences in the tariffying program for time - the measured value, displayed on up to 8 digits;
zones. - measuring units for active, reactive, apparent energies and
The time zones metering program is annual. There can be defined up to 12 seasons in a year. powers, voltages, currents, with k, M, G multiples;
Within each season, the weekly program will be defined, it being made up of 7 types of days - quantities measured by the meter (active power in one or two
chosen from the 24 types of days which can be defined. Every day there can be defined up to directions +P ºi -P and/or reactive power in one or two directions
12 switchings for each of the two sequences of the daily program. The programming resolution +Q and -Q);
is of 30 minutes. - momentary directions of active and reactive measured
There can also be defined 64 more holidays groups within the tariffying program. The time energy: active imported energy , active exported
length of a holidays group can be programmed for an interval of 1 to 4 days. Each holidays energy , reactive imported energy , reactive exported
group of days can be defined with or without annual repetition. energy ;
- annunciators which indicate the following:
• Meter self-reading (for billing purposes) • meter operation with the second display sequence,
The meter self-reading enables the following: "D2 annunciator";
- energy indexes memorizing (46 registers); • demands reset and the meter self-reading, "RST
- registered demands memorizing; annunciator";
- demands summing up in cumulative registers; • the last 9 seconds for the demand calculation time
- demand registers with automatic reset; interval, "9S annunciator";
- billing time interval. • test mode meter operation, "TEST annunciator".
The meter memorizes the self-read values of the last 12 self-readings. Meter display modes: two programmable sequences, that can
• Load profile (optional) be scrolled manually or automatically.
The load profile memorizing capacity ensures a channel of 235 days time length for the 15 min.
acquisition period.
The number of the load profile channels is programmable from 1 to 8. The load profile
acquisition period is programmable with 1...60 min. The load profile registers absolute energy
values (not differences), and time markers for any acquisition.
• Events
The list of events contains 500 events.
Types of events: • Errors and warnings diagnosis
1). Supply voltage drop 19). M6 power threshold exceeding The meter is provided with self-diagnosis facilities for the
2). Restored supply voltage 20). Restored power under M6 threshold measuring circuit, and thus when the error is detected, "Err dSP"
3). Voltage drop on phase R 21). M7 power threshold exceeding message is displayed. The following warning messages can also
4). Restored voltage on phase R 22). Restored power under M7 threshold be displayed:
5). Voltage drop on phase S 23). M8 power threshold exceeding - "lo batt" indicates low battery;
6). Restored voltage on phase S 24). Restored power under M8 threshold - "oLo xxxx" indicates the programmed power threshold
7). Voltage drop on phase T 25). Frequency exceeds -6%...+4% fn range, exceeding, where x=1, 2, 3, 4, 5, 6, 7, 8.
8). Restored voltage on phase T limits according to SR EN 50160
9). M1 power threshold exceeding 26). Energy direction reversing • Communication
10). Restored power under M1 threshold 27). Positive energy direction Through the optical port and the current loop, according to IEC
11). M2 power threshold exceeding 28). RTS phases succession (fault) 62056-21: Direct local data exchange (3rd edition of IEC 62056-
12). Restored power under M2 threshold 29). RST phases succession (normal) 21).
13). M3 power threshold exceeding 30). Meter programming (without clock) For modem communication or other possibilities, according to
14). Restored power under M3 threshold 31). Meter clock programming IEC dedicated (optional), the meter is provided with RS232 port.
15). M4 power threshold exceeding 32). Low battery • Supplementary functions
16). Restored power under M4 threshold 33). Measuring circuit error - Three configurable auxiliary outputs:
17). M5 power threshold exceeding 34). Different energy directions per phase - 2 pulse generators outputs that can be configured for
18). Restored power under M5 threshold 35). Normal energy direction per phase restored active and reactive energy (optional);
- 3 relay outputs (optional) that can be configured for:
SYMBOLS: signalling out the power threshold exceeding; signalling out
the interval end; load control.
ENERLUX T - A, C, D, G, M, R, S (option)
- facilities concerning the energy quality, according to
3x230/400 V, 1(6) A, 50 Hz, cl. 0.5S
EN 50160:
- time metering with fn outside fn±1% range;
- time metering with Un outside Un±10% range;
- event generation at fn outside fn -6%...+4% range.
OVERALL AND FIXING DIMENSIONS, SEALS:

Seria: xxxx /04

(147,3 ±1,8)
171±1,8
Contor trifazat de energie electricã
EnerluxT
3000 3x230/400V 5(100)A 50Hz Cl.1
imp/kWh Uc: 100V Ic: 0,1A RO
xxx/04

255 3000
imp/kvarh
! Li
Fig. 1

241
154,6±9,8
74,5
179

WIRING DIAGRAM:

EnerluxT EnerluxT EnerluxT


DB9 R1 R2 R3 COM.
DB9
R1 R2 R3 COM.
DB9
R1 R2 R3 COM.
1 1 1
(-) (+) (-) (+) (-) (+)
9 15 16 17 18 19 20 21 22 9 9
15 16 17 18 19 20 21 22 15 16 17 18 19 20 21 22

1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11
1 1
2 2
3 3
N
S1 S2
1
P1 P2 S1 S2
2
P1 P2 S1 S2
3
N P1 P2

EnerluxT EnerluxT EnerluxT


DB9 DB9
R1 R2 R3 COM. R1 R2 R3 COM.
DB9
R1 R2 R3 COM.
1 1 1
(-) (+) (-) (+) (-) (+)
9 15 16 17 18 19 20 21 22 9 15 16 17 18 21 22 9
19 20 15 16 17 18 19 20 21 22

1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11

A a A a A a
a b a b

S1 S2
1 S1 S2
B b B b B b 1 A B A B
P1 P2
2 P1 P2
S1 S2 2
3
S1 S2 1 S1 S2
P1 P2 S1 S2 3
P1 P2 2
S1 S2 P1 P2
P1 P2
3
N P1 P2

S.C. AEM S.A. Timisoara


Calea Buziasului nr. 26
300693, Timisoara
Tel: 0256-222200; Fax: 0256-490928
E-mail: [email protected]
Internet: http://www.aem.ro
Quality management system
ISO 9001 certified by KEMA
v.09.2007