Chapter 1
INTRODUCTION
The fulfillments of the industrial goals were possible only because the modern industries
were able to find innovative technologies that have successfully become technological
developments. Continuous production throughout the period is ensured only when the
final objective is to optimize the production while achieving maximum profits and
The reason for demanding high quality un-interruptible power during production process
is mainly because of the modern manufacturing and process equipments that operate at
high efficiency requires stable and defect free power supply for the successful operation
more precisely. For instance, some instruments like adjustable speed drives, automation
devices, power electronic components etc. fall into the above category.
Cessation to provide the required quality power output may sometimes cause complete
shutdown of the industries which will make a significant financial loss to the industry
concerned. However blame due to degraded quality cannot be simply put on to the hands
of the utility itself. It has been observed that in industries, most of the conditions that can
disrupt the process are generated within the industry itself. For example, most of the non-
linear loads cause transients which can affect the reliability of the power supply.
2
Following mentioned are some aberrant electrical conditions that can disrupt a process
1. Voltage Sags
2. Phase Outages
3. Voltage Interruptions
4. Transients due to Lighting loads, capacitor switching, non linear loads, etc.
5. Harmonics
The industries may undergo burned-out motors, lost data on volatile memories, erroneous
motion of robotics, unnecessary downtime, increased maintenance costs and burning core
The solutions put forth as a consequence of the above mentioned anomalies are called as
utility based solutions and customer based solutions respectively. The finest examples for
those two types of solutions are FACTS devices (Flexible AC Transmission Systems) and
Custom power devices that are based on solid state power electronic components.
FACTS devices are controlled by the utility, whereas the Custom power devices are
operated, maintained and controlled by the customer itself and installed at the customer
premises.
3
Manufacturing cost and the reliability of those solid state devices have been improved as
new technologies emerged. So, the protection devices which include such solid state
devices can be purchased at a reasonable price with superior performance than the
Power Supplies (UPS), Dynamic Voltage Restorers (DVR) and Active Power Filters
(APF) are examples for commonly used custom power devices. Among those APF is
whereas UPS and DVR are used to compensate for voltage sag and surge conditions.
Voltage sag may occur from single phase to three phases. But it has been found that
single phase voltage sags are routine and most frequent in the power industry. Thus, the
industries that use single and three phase supply will undergo several interruptions during
their production process and they are forced to use some form of voltage compensation
equipment.
As soon as the fault occurs the action of DVR starts. On event of fault which results in
voltage sag, the magnitude reduction is accompanied by phase angle shift and the
remaining voltage magnitude with respective phase angle shift is provided by the DVR.
Employing minimum active voltage injection mode in the DVR with some phase angle
4
shift in the post fault voltage can result in miraculous use of DVR. If active voltage is
less prominent in DVR then it can be delivered to the load for maintaining stability.
Considering this, a transition process is proposed such that voltage restoration is achieved
by injecting the voltage difference between the pre sag and the in sag (source side)
voltages during the initial first cycle or so the sag. When the sag voltage phasor is
available, the injection voltage is controlled to move progressively from the in phase
injection point to the corresponding minimum active voltage injection point. The initial
voltage injection magnitude and phase angle of DVR can be categorized into different
The simulation of various 1 phase and 3 phase faults are done using MATLAB. The
present project deals with only voltage sag, voltage swell can be simulated in same way.
The simulation results show the very good performance of the controller theoretically.
The performance of DVR theoretically is tested. Therefore this project has contributed a
compensate the single-phase voltage sags and 3 phase balanced voltage sags.
5
Chapter 2
The name power quality has become one of the most productive concepts in the power
industry since late 1980s. Power Quality concept mainly deals with 3 factors namely
Power quality may be defined as the “Degree to which both the utilization and delivery
In a three-phase system, unbalanced voltages also are a power quality problem. Among
them, two power quality problems have been identified to be of major concern to the
customers are voltage sags and harmonics, but this project will be focusing on voltage
6
sags. Figure 2.3[10] describe the demarcation of the various power quality issues defined
Semiconductors are very sensitive to slightest change in the power supply. It is very
important for them to take care of the frequently occurring power quality defects in order
The five most common PQ defects defined by IEEE Std. 1159-1995[11] are:
7
i. Under Voltage: When the operating falls to a low value due to fault voltage.
ii. Dips or Surges: Fluctuations leading to frequent increase and decrease in the
iv. Harmonics: Voltage or Currents that are some integer multiple of operating
v. Burnouts: Period of very low frequency voltage or sometimes even zero leading
Power Quality problems happen when these ranges are crossed and this can occur in three
ways:
i. Frequency events: change of the supply frequency outside of the normal range.
ii. Voltage events: change of the voltage amplitude outside its normal range (may
iii. Waveform events: distortion of the voltage waveform outside the normal range.
i. Interrupting supply, Trip out variable speed drives and cause annoying light
flicker.
equipment to malfunction.
Over the last fifteen years, based on how the power quality instruments measure voltage
sags and swells the definitions have been developed. Power system communities state
sags or dips as a reduction in voltage below a user- defined low limit for between one
cycle and 2.55 seconds. Surges are now called as swells, except that the voltage exceeds a
particular user-defined high limit. While different definitions pertaining to the amplitude
and duration are still in use, the IEEE 1159-1995 Recommended Practice on Monitoring
Sag (dip) can be defined as, “A decrease to between 0.1 and 0.9 pu in rms voltage or
Swell can be defined as, “An increase to between 1.1 pu and 1.8 pu in rms voltage or
greater than or equal to 0.1 per unit (of nominal voltage). The IEEE 1159 document
further categorizes the duration values into: Instantaneous, momentary, and temporary, as
According to the IEEE Std. 1995-2009 a voltage sag is “A decrease in rms voltage or
current at the power frequency for duration of 0.5 cycle to 1 minute”. [1]
IEC has the following definition for a dip (IEC 61000-2-1, 1990) “A voltage dip is a
sudden reduction of the voltage at a point in the electrical system, followed by a voltage
recovery after a short period of time, from half a cycle to a few seconds”.[1]
10
Table 2.1 IEEE definitions of Voltage Sags and Voltage Swells [11]
It is blatant from the previous definitions that both voltage sag and voltage dip relate to
the same disturbance. Moreover, IEC states that “voltage sag is an alternative name for
[12]
11
The duration and amplitude value limits that are likely to cause problems with
equipments are already defined by both the ANSI C84.1-1989 Utility Power Profile and
the CBEMA (Computer and Business Equipment Manufacturers Association) curve. The
smaller the amplitude of a sag or higher the value of a swell, the shorter the duration
should be for equipment to follow through the disturbance, as in the following table
derived from such. The typical industrial utility power after building line losses is in the
The prime interest about voltage sags is their effect on sensitive electrical devices, such
other power electronic equipment. The least sensitive loads failed when the voltage
dropped to 30 % of the specified voltage. On the other hand, the most sensitive
components failed when the voltage dropped to 80-86 % of rated value. From the test
results, the calculated sag threshold to affect production at the utility PCC - point of
common coupling was 87 % of the nominal voltage for more than 8.3 ms.
Voltage Sag Classification based on type of Sag, duration and magnitude as shown in
Table 2.4
The power system voltage can be given by a sine wave. A reduction in the amplitude of
the waveform indicates a Voltage Sag. Figure 3.3 shows the voltage waveform during
voltage sag. The sag magnitude is characterized by the amplitude of the instantaneous
voltage.
There are various causes of voltage sags in a power system. Voltage sags can be
loads with large amounts of initial starting or inrush current such as motors, transformers,
One of the major factors critical to the operation of the power plant is voltage sags due to
faults. The magnitudes of the voltage sags can be equal in each phase or unequal
For faults in the transmission system, customers do not experience interruption since
At a certain point in the system parameters affecting the sag magnitude due to faults are:
ii Fault impedance
The frequently occurring voltage sags are single phase events which are basically due to a
phase to ground fault occurring somewhere on the system. On other feeders from the
same substation this phase to ground fault appears as single phase voltage sag. Typical
causes are lightning strikes, tree branches, animal contact etc. It is common to see single
The 2 Phase or Phase to phase sags may be caused by tree branches, adverse weather,
animals or vehicle collision with utility poles. These types of sags typically appear on
These are caused by switching or tripping of a 3 phase circuit breaker, switch or recloser
which will create three phase voltage sag on other lines fed from the same substation.
Symmetrical 3 phase sags arise from starting large motors and they account for less than
17
20% of all sag events and are usually confined to an industrial plant or its immediate
neighbors.
A greater awareness of voltage quality has been created with the recent growth in the use
of digital computers and PWM adjustable speed drives. Voltage dips and its associated
phase angle jumps can cause equipment to fail or malfunction which in turn can lead to
production downtime. Since a very long time interval is needed to restart industrial
processes, these effects can be greatly expensive for the clients/customers who are
continuously seeking for cost effective sag mitigation techniques. These interests have
resulted in the development of power electronics based devices with sag mitigation
capability. These devices can be classified into two classes, namely Custom Power
N G Hingorani put forward the idea of custom power devices in 1995 as shown in the
figure above. Like Flexible AC Transmission Systems (FACTS), the term custom power
devices relates to the use of power electronics controllers in a distribution system, to deal
with various power quality problems. Just as FACTS improves the power transfer
capabilities and stability margins, custom power devices ascertain that customers get pre-
specified quality and reliability of supply. Without significant effect on the terminal
voltages this pre-specified quality may contain a combination of the following, low phase
unbalance, no power interruptions, low flicker at the load voltage, low harmonics
19
distortion in load voltage, magnitude and duration of over voltages and under voltages
within specified limits, acceptance of fluctuations and poor power factor loads.
Custom Power Devices are recently being developed under the Custom Power Program
initiated by the Electric Power Research Institute (EPRI). Typical custom power
Compensator (D-STATCOM), Solid State Fault Current Limiter (SSFCL). These devices
There are many types of Custom power devices like those listed below:
The conventional approach is adding Power Line Conditioners to the distribution systems
as a form of load side solution. These devices work by providing voltage sag ride through
capability to critical loads. Examples of these devices include motor-generator sets (M-G
sets) uninterruptible power supplies (UPSs), magnetic synthesisers and super conducting
Uninterruptible Power Supplies (UPS), Dynamic Voltage Restorers (DVR) and Active
Power Filters (APF) with voltage sag compensation facility are the most common custom
power devices to compensate for the voltage sags and swells. UPS is ubiquitous whereas
DVR and APF are less popular due to the fact that they are still in the developing stage,
even though they are highly efficient and cost effective than UPSs. Due to the rapid
ongoing development in the power electronic industry, low cost power devices like DVR
and APF will become much popular among the industries in the near future.
DVR and APF are normally used to eliminate two different types of abnormalities that
affect the power quality. They are discussed based on two different load situations
namely linear loads and non-linear loads. The load is considered to be a linear when both
the dependent variable and the independent variable show linear changes to each other.
21
Example: Resistors. The non-linear load on the other hand does not show a linear change.
Here, the custom power device together with the defected supply should
the device should be able to supply the missing voltage/current component of the
source. A reliable device that can be used for the above case (for voltage
ii. When the Power supplied is in normal condition with a non linear load
In this case, when non-linear loads are connected to the system, the supply
current also becomes non-linear and this will cause harmonic problems in the
the current to make the supply current sinusoidal. So, the supply treats both the
non-linear load and the APF as a single load, which draws a fundamental
sinusoidal current.
22
It is clear from Figure2.6 that the DVR is series connected to the power line, while APF
is shunt connected. Among the custom power devices, UPS and DVR can be qualified as
the devices that inject a voltage waveform to the distribution line. The UPS is always
supplying the full voltage to the load irrespective of whether the wave form is distorted or
not unlike DVR. This property of the UPS leaves it always operating at its full power
whereas the DVR injects only the difference between the pre-sag and the sagged voltage
and that also only during the sagged period. Therefore as compared to UPS, DVR
operating losses and the required power rating are very low. Hence DVR is considered as
There are numerous reasons why DVR is preferred over other devices:
i. Although, SVC predominates the DVR but the latter is still preferred
iii. UPS also needs high level of maintenance because it has problem of
iv. DVR has a relatively higher energy capacity and costs less compared to
SMES device.
Chapter 3
One of the major factors that determine the quality of power supply is the voltage
magnitude. For various reasons frequent voltage sags are often experienced by loads at
distribution level. For some sensitive loads such as those in high-tech industries voltage
sags are highly undesirable. It is a challenging task to maintain the load voltage
requirements with proper magnitude and correct the voltage sag during voltage
Generally voltage sag can be very expensive and cause severe problems for the customers
as it may lead to production damage and downtime. By using power electronics devices
also known as customer power device a certain amount of voltage and power can be
injected into the distribution system and this severe problem of voltage sag can be
minimized. Out of the various approaches that have been have been proposed to limit the
cost causes by voltage sag, dynamic voltage restorer (DVR) is one of the best methods to
address voltage sag problems. This method is briefly discussed in our thesis and it can be
A DVR is a solid state power electronics switching device which comprises of either
GTO or IGBT, a capacitor bank as energy storage device and injection transformers.
From the figure it can be seen that DVR is connected in between the distribution system
and the load. The basic idea of DVR is that by means of an injecting transformer a
control voltage is generated by a forced commuted convertor which is in series to the bus
Under normal operating conditions when there is no voltage sag, DVR provides very less
magnitude of voltage to compensate for the voltage drop of transformer and device
losses. But when there is a voltage sag in distribution system, DVR will generate a
required controlled voltage of high magnitude and desired phase angle which ensures that
load voltage is uninterrupted and is maintained. In this case the capacitor will be
Figure 3.1 Principle of DVR with a Response Time of Less Then One Millisecond [21]
Note that the DVR capable of generating or absorbing reactive power but the reactive
power injection of the device must be provided by an external energy source or energy
storage system. The response time of DVD is very short and is limited by the power
electronics devices and the voltage sag detection time. The expected response time is
about 25 milliseconds, and which is much less than some of the traditional methods of
Power circuit and the control circuit are the 2 main parts of the DVR. There are various
critical parameters of control signals such as magnitude, phase shift, frequency etc. which
are injected by DVR. These parameters are derived by the control circuit. This injected
voltage is generated by the switches in the power circuit based on the control signals.
Furthermore the basic structure of DVR is described by the power circuit and is discussed
in this section. The 5 main important parts of power circuit, their function and
energy storage (SMES) and Super-Capacitors can be used as energy storage devices. The
main function of these energy storage units is to provide the desired real power during
28
voltage sag. The amount of active power generated by the energy storage device is a key
factor, as it decides the compensation ability of DVR. Among all others, lead batteries are
But the discharge rate is dependent on the chemical reaction rate of the battery so that the
convert this DC voltage into an AC voltage a Voltage Source Inverter is used. In order to
boost the magnitude of voltage during sag, in DVR power circuit a step up voltage
injection transformer is used. Thus a VSI with a low voltage rating is sufficient.
To convert the PWM inverted pulse waveform into a sinusoidal waveform, low pass
passive filters are used. In order to achieve this it is necessary to eliminate the higher
which will also distort the compensated output voltage. These filters which play a vital
role can be placed either on high voltage side i.e. load side or on low voltage side i.e.
inverter side of the injection transformers. We can avoid higher order harmonics from
29
passing through the voltage transformer by placing the filters in the inverter side. Thus it
also reduces the stress on the injection transformer. One of the problems which arise
when placing the filter in the inverter side is that there might be a phase shift and voltage
drop in the inverted output. So this could be resolved by placing the filter in the load side.
But this would allow higher order harmonic currents to penetrate to the secondary side of
Now DVR is a series connected device. If there is a fault current due to fault in the
downstream, it will flow through the inverter. Now the power components of inverter are
not highly rated but normally rated due to its cost. So in order to protect the inverter a
By-pass switch is used. Generally a crowbar switch is used which bypasses the inverter
30
circuit. So crowbar switch will sense the magnitude of the current, if it is normal and
within the handling range of inverter components it (the crowbar switch) will be inactive.
On the other hand if current is high it will bypass the components of inverter.[18]
The primary side of the injection transformer is connected in series to the distribution
line, while the secondary side is connected to the DVR power circuit. Now 3 single phase
transformers or 1 three phase transformer can be used for 3 phase DVR whereas 1 single
phase transformer can be used for 1 phase DVR. The type of connection used for 3 phase
DVR if 3 single phase transformers are used is called “Delta-Delta” type connection as
shown in Figure 3.4 a [22]. If a winding is missing on primary and secondary side then
Figure 3.4 a Connection Method for Injection Transformer Delta-Delta Connection [22]
Figure 3.4 b Connection Method for Injection Transformer Open-Delta Connection [22]
32
Basically the injection transformer is a step up transformer which increases the voltage
supplied by filtered VSI output to a desired level and it also isolates the DVR circuit from
the distribution network. Winding ratios are very important and it is predetermined
according to the required voltage at the secondary side. High winding ratios would mean
high magnitude currents on the primary side which may affect the components of inverter
circuit. When deciding the performance of DVR, the rating of the transformer is an
important factor. The winding configuration of the injection transformer is very important
connection with the grounded neutral there will not be any zero sequence current flowing
into the secondary during an unbalance fault or an earth fault in the high voltage side.
Thus only the positive and negative sequence components are compensated by the DVR.
The difference between the pre sag voltage and the sag voltage is injected by the DVR by
supplying the real power from the energy storage element and the reactive power. The
DVR injects the difference between the pre-sag and the sag voltage, by supplying the real
power requirement from the energy storage device together with the reactive power. Due
to the ratings of DC energy storage and the voltage injection transformer ratio the
maximum capability of DVR is limited. The magnitude of the injected voltage can be
33
controlled individually in the case of three single-phase DVRs. With the network
voltages the injected voltages are made synchronized (i.e. same frequency and the phase
angle)
During the normal operation as there is no sag, DVR will not supply any voltage to the
load. It will be in a standby mode or it operates in the self charging mode if the energy
storage device is fully charged. The energy storage device can be charged either from the
3.3.3 During a short circuit or fault in the downstream of the distribution line
In this case we have seen before that a bypass switch (crossbar switch) will be activated
and it will bypass the inverter circuit in order to protect the electronic components of the
inverter.
34
Pre-sag compensation is a method which is generally used for non linear loads such as
thyristor controlled drives. In non linear loads the voltage magnitude as well as he phase
angle needs to be compensated. Figure 3.5 below describes the pre-sag compensation
technique. A higher rated energy storage device and voltage injection transformers are
required. In this particular method the compensated voltage is in phase with the sagged
voltage. [1] This particular compensation technique is shown in Figure 5.6. It is clear
from the Figure 3.6, that there is a phase shift between the voltages before the sag and
It should be noted that the techniques mentioned in 3.4.1 and 3.4.2 need both the real and
reactive power1 for the compensation and the DVR is supported by an Energy storage
device.
36
Chapter 4
Depending upon the compensation that DVR provides, various modes of operation can be
designed. The figure below shows the mode which only deals with the reactive power.
From the phasor diagram we can see that minute control in voltage magnitudes difficult
and V desired and V obtained are somewhat deviating. Now on the other hand when we
observe the phasor diagram 4.2 it can be seen that V desired and V obtained can be
accurately same. Thus we can conclude by saying the DVR with active and reactive
Figure 4.2 b Phasor Diagram of Active and Reactive Power Configuration in DVR [9]
38
4.2 Review of the Existing Method used for DVR Voltage Injection
One of the methods that are widely used in DVR is briefly discussed in this section. We
can see from the figure 4.3 that the phasor diagram for pre fault and post fault conditions
are illustrated. When the system behaves normally the pre fault voltage is Uo whereas in
abnormal conditions the voltage locus lies anywhere in the range of Uo. We can also see
that when there is an effect of voltage sag, Us is a post fault voltage. Furthermore there is
also reduction in phase angle and magnitude as shown in figure 4.3. Voltage injected by
DVR for compensation is Uin and Uon is the pre fault voltage obtained from Us and Uin.
Also there is phase angle advancement of Uin which is done in minute steps. The
simplest process is to compare the Uin voltage and the max injection limit of DVR
termed as Uinj. If injection is less compared to max limit than the system conditions will
be restored. On the other hand when limit is exceeded the pre fault magnitude is more
than the output voltage. This method is highly accurate and hence widely used.
Figure 4.3 Existing method used for DVR voltage Injection [6]
39
The previous method described is good but it is not the best. As discussed earlier the
existing method is good but not the best. Now if the active voltage is minimal then more
voltage can be fed to the load area from the source. So active voltage should be minimum
and reactive voltage should be dominating. We can see from the figure 4.4 that Uin is the
compensated voltage generated by DVR to maintain the pre sag voltage. The active
voltage Uia1 is given to produce Ui1. Similarly Uia2 is the voltage injected to produce
the desired output. In both the cases the supply voltage as well as the voltage injected by
the DVR will produce same results. Thus we define 2 important operating points P1 and
P2. Now the size of DVR is reduced when there is a minimal active power injection at
operating point P2. Thus operating point P2 is proffered over P1.Thus this scheme can be
Chapter 5
Matlab Code
%CASEA: When operating voltage falls below the nominal voltage due to Sag
uo_pa=uo_pad*pi/180;
uo_r=uo_m*cos(uo_pa);
uo_i=uo_m*sin(uo_pa);
uo=uo_r+j*uo_i;
plot(t,uo_plot, t, us_plot)
x=uinj+us_m
y=uo_pa-us_pa
uinj_plot=x*sin(t*freq_RPS+y);
plot(t,uo_plot, t, uinj_plot)
Case A: When the event of a Voltage Sag decreases the Operating supply Voltage
magnitude and phase.
The graph below represents Single Phase supply voltage used in America with Magnitude
of 120 V and Frequency of 60 Hz.
In our example as shown in graph 5.2 the supply voltage and frequency drops down
drastically.
46
Matlab Code
uo=uo_r+j*uo_i;
us_i=us_m*sin(us_pa);
us_plot=us_m*sin(t*freq_RPS+us_pa);
plot(t,uo_plot, t, us_plot)
x=us_m-uinj
y=us_pa-uo_pa
uinj_plot=x*sin(t*freq_RPS+y);
plot(t,uo_plot, t,uinj_plot)
The graph below represents Single Phase supply voltage with Magnitude of 140 V and
Frequency of 60 Hz. We have changed the supply voltage to a value other than 120V
used in America solely to utilize the exhaustive restore property of DVR.
In our example as shown in graph 5.5 below the supply voltage and frequency increases
catastrophically.
51
Our project has proposed an improved progressive phase changing scheme of post fault
voltage. For any fault situation of Voltage Sag this method is effective which is proved
from the analysis and MATLAB simulation results. We chose MATLAB programming
because it is easy and can be easily fed in any microprocessor chip. The sag transients
can be easily mitigated and pre fault voltage can be established. For real time
fast speed.
The analysis done in this paper are done for Voltage sag affecting Single Phase supply
only. Similarly simulations can be carried for Voltage swells and Three-Phase Supply
Fault. We have not shown Voltage Swell and Three-phase Simulation because that is out
Hereby, the effectiveness of proposed method is tested and is proven error free. This
proposed method is tested theoretically only however, exact practical testing is left. The
effect of harmonic induction and voltage drop due to connection of DVR are to be tested
in actual experimental setup. Lab Testing of DVR can be implemented as a part of future
research work.
53
APPENDIX
SYMBOL DESCRIPTION
Uinj Maximum Injection Limit of DVR
Uo Pre sag voltage on the line
Us Post sag voltage on the line(after fault)
Uin Injected voltage by DVR
Uso Voltage in the line at operating point(minimum active voltage).
Uo Injected voltage by DVR at operating point(minimal active voltage).
Uinj_pa(X&Y) Injection limit of DVR to be entered byUSER
Uo_m Magnitude of Pre sag voltage on the line to be entered by USER
Uo_pad Phase angle in degree of Pre sag voltage on the line to be entered by
USER
Us_m Magnitude of Post sag voltage on the line to be entered by USER
Us_pad Phase angle in degree of Post sag voltage on the line to be entered by
USER
FACTS Flexible AC Transmission System
UPS Uninterruptible Power Supply
APF Active Power Filter
PLC Programmable Logic Controller
IEEE Institute Of Electrical and Electronics Engineers
IEC International Electrotechnical Commission
CBEMA Computer and Business Engg. Manufactuer Association
PCC Point of Common Coupling
EPRI Electrical Power Research Institute
D-STATCOM Distribution Static Compensator
SSFCL Solid State Fault Current Limiter
M-G Motor-Generator
SSDs Super Conducting Storage Devices
GTO Gate Turn Off Thyristor
IGBT Insulated Gate Bipolar Transistor
SMES Super conducting Magnetic Emergency Storage
PWMVSI Pulse Width Modulation Voltage Source Inverter
54
REFERENCES
Refinery with Induction Motors Loads” 2010 Science Publications available from
http://www.scipub.org/fulltext/ajeas/ajeas31144-151.pdf
from
http://www.leonardo-energy.org/webfm_send/972
[3] Shairul Wizmar Wahab and Alia Mohd Yusof “Voltage Sag and mitigation Using
http://myais.fsktm.um.edu.my/2489/1/paper6dec06_shairul_wizmar.pdf
available from
www.tijsat.tu.ac.th/issues/2006/no3/2006_V11_No3_1.PDF
[7] Mehmet Tumay ,Ahmet Teke , K Cagatay Baymdr and M Ugras Cuma
http://www.emo.org.tr/ekler/ee5605917626676_ek.pdf
http://www.electrotek.com/voltsag.htm.
[9] C S Chang, Y.S. Ho, P.C. Lo “Voltage Quality Enhancement with Power
http://ieeexplore.ieee.org/ebooks/5270869/5271123.pdf
56
[11] IEEE Standard 1159-1995 “IEEE Recommended Practice for Monitoring Electric
http://www.dranetz-bmi.com/pdf/sags-swells.pdf
Sag Due to Fault in the Power System” Vol. 5, No.1, May2008, 171-182, Serbian
[14] Alexander Eigels Emanuel, John A. McNeill “Electric Power Quality”. Annu.
[15] Mohd Izhwan Muhammad, Norman Mariun, Mohd Amran Mohd Radzi “ Effects
http://ieeexplore.ieee.org/stamp/stamp.jsp?arnumber=04451410
[16] Narain G. Hingorani, “Introducing custom power” IEEE spectrum, June 1995
pg.41-48.
pg.533-542.
[18] P.T. Nguyen, Tapan K. Saha, “Dynamic Voltage Restorer against balanced and
http://ftp.ibiblio.org/kuphaldt/electricCircuits/AC/AC_10.html