Fire Alarm Control Panel XLS 140

Download as pdf or txt
Download as pdf or txt
You are on page 1of 88
At a glance
Powered by AI
Fire alarm systems are designed to provide early warning of fires but have limitations. They do not guarantee protection from fire damage or ensure safety.

Fire alarm systems are designed to provide early warning against fire but do not guarantee warning or protection against all fires.

Fire alarm systems may not detect or warn of all types of fires due to limitations in smoke/heat detection, environmental factors, fire development factors or system/component failures.

XLS140

FIRE ALARM CONTROL PANEL

INSTALLATION MANUAL

Put Bar Code Here

P/N 51927:C • ECN 05-265 • 12/06/2005


Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of Heat detectors do not sense particles of combustion and
smoke detectors, heat detectors, manual pull stations, audible alarm only when heat on their sensors increases at a predeter-
warning devices, and a fire alarm control panel with remote mined rate or reaches a predetermined level. Rate-of-rise
notification capability—can provide early warning of a develop- heat detectors may be subject to reduced sensitivity over time.
ing fire. Such a system, however, does not assure protection For this reason, the rate-of-rise feature of each detector
against property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the National Fire Protection Association IMPORTANT! Smoke detectors must be installed in the
Standard 72-1999 (NFPA 72-1999), manufacturer's recom- same room as the control panel and in rooms used by the sys-
mendations, State and local codes, and the recommendations tem for the connection of alarm transmission wiring, communi-
contained in the Guide for Proper Use of System Smoke cations, signaling, and/or power. If detectors are not so
Detectors, which is made available at no charge to all installing located, a developing fire may damage the alarm system, crip-
dealers. A study by the Federal Emergency Management pling its ability to report a fire.
Agency (an agency of the United States government) indicated Audible warning devices such as bells may not alert people
that smoke detectors may not go off in as many as 35% of all if these devices are located on the other side of closed or
fires. While fire alarm systems are designed to provide early partly open doors or are located on another floor of a building.
warning against fire, they do not guarantee warning or protec- Any warning device may fail to alert people with a disability or
tion against fire. A fire alarm system may not provide timely or those who have recently consumed drugs, alcohol or medica-
adequate warning, or simply may not function, for a variety of tion. Please note that:
reasons:
• Strobes can, under certain circumstances, cause seizures
Smoke detectors may not sense fire where smoke cannot in people with conditions such as epilepsy.
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors • Studies have shown that certain people, even when they
also may not sense a fire on another level or floor of a building. hear a fire alarm signal, do not respond or comprehend the
A second-floor detector, for example, may not sense a first- meaning of the signal. It is the property owner's responsi-
floor or basement fire. bility to conduct fire drills and other training exercise to
make people aware of fire alarm signals and instruct them
Particles of combustion or “smoke” from a developing fire on the proper reaction to alarm signals.
may not reach the sensing chambers of smoke detectors
because: • In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow. A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
• Smoke particles may become “cold,” stratify, and not reach batteries only for a specified time and only if the batteries have
the ceiling or upper walls where detectors are located. been properly maintained and replaced regularly.
• Smoke particles may be blown away from detectors by air Equipment used in the system may not be technically com-
outlets. patible with the control panel. It is essential to use only equip-
• Smoke particles may be drawn into air returns before ment listed for service with your control panel.
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of “smoke” present may be insufficient to alarm premise to a central monitoring station may be out of service
smoke detectors. Smoke detectors are designed to alarm at or temporarily disabled. For added protection against tele-
various levels of smoke density. If such density levels are not phone line failure, backup radio transmission systems are rec-
created by a developing fire at the location of detectors, the ommended.
detectors will not go into alarm. The most common cause of fire alarm malfunction is inade-
Smoke detectors, even when working properly, have sensing quate maintenance. To keep the entire fire alarm system in
limitations. Detectors that have photoelectronic sensing excellent working order, ongoing maintenance is required per
chambers tend to detect smoldering fires better than flaming the manufacturer's recommendations, and UL and NFPA stan-
fires, which have little visible smoke. Detectors that have ion- dards. At a minimum, the requirements of NFPA 72-1999 shall
izing-type sensing chambers tend to detect fast-flaming fires be followed. Environments with large amounts of dust, dirt or
better than smoldering fires. Because fires develop in different high air velocity require more frequent maintenance. A main-
ways and are often unpredictable in their growth, neither type tenance agreement should be arranged through the local man-
of detector is necessarily best and a given type of detector ufacturer's representative. Maintenance should be scheduled
may not provide adequate warning of a fire. monthly or as required by National and/or local fire codes and
Smoke detectors cannot be expected to provide adequate should be performed by authorized professional fire alarm
warning of fires caused by arson, children playing with installers only. Adequate written records of all inspections
matches (especially in bedrooms), smoking in bed, and violent should be kept.
explosions (caused by escaping gas, improper storage of
flammable materials, etc.). Limit-C-9-2005

2 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be Like all solid state electronic devices, this system may
connected to the fire alarm control panel. Disconnect all operate erratically or can be damaged when subjected to light-
sources of power before servicing. Control unit and associ- ning induced transients. Although no system is completely
ated equipment may be damaged by removing and/or insert- immune from lightning transients and interference, proper
ing cards, modules, or interconnecting cables while the unit is grounding will reduce susceptibility. Overhead or outside aerial
energized. Do not attempt to install, service, or operate this wiring is not recommended, due to an increased susceptibility
unit until manuals are read and understood. to nearby lightning strikes. Consult with the Technical Ser-
CAUTION - System Re-acceptance Test after Software vices Department if any problems are anticipated or encoun-
Changes: To ensure proper system operation, this product tered.
must be tested in accordance with NFPA 72 after any pro- Disconnect AC power and batteries prior to removing or
gramming operation or change in site-specific software. Re- inserting circuit boards. Failure to do so can damage circuits.
acceptance testing is required after any change, addition or Remove all electronic assemblies prior to any drilling, filing,
deletion of system components, or after any modification, reaming, or punching of the enclosure. When possible, make
repair or adjustment to system hardware or wiring. All compo- all cable entries from the sides or rear. Before making modifi-
nents, circuits, system operations, or software functions known cations, verify that they will not interfere with battery, trans-
to be affected by a change must be 100% tested. In addition, former, or printed circuit board location.
to ensure that other operations are not inadvertently affected,
at least 10% of initiating devices that are not directly affected Do not tighten screw terminals more than 9 in-lbs. Over-
by the change, up to a maximum of 50 devices, must also be tightening may damage threads, resulting in reduced terminal
tested and proper system operation verified. contact pressure and difficulty with screw terminal removal.

This system meets NFPA requirements for operation at 0-49º This system contains static-sensitive components.
C/32-120º F and at a relative humidity (non condensing) of Always ground yourself with a proper wrist strap before han-
85% at 30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C dling any circuits so that static charges are removed from the
(89.6°F ± 1.1°F) per ULC. However, the useful life of the sys- body. Use static suppressive packaging to protect electronic
tem's standby batteries and the electronic components may be assemblies removed from the unit.
adversely affected by extreme temperature ranges and humid- Follow the instructions in the installation, operating, and pro-
ity. Therefore, it is recommended that this system and its gramming manuals. These instructions must be followed to
peripherals be installed in an environment with a normal room avoid damage to the control panel and associated equipment.
temperature of 15-27º C/60-80º F. FACP operation and reliability depend upon proper installation.
Verify that wire sizes are adequate for all initiating and indi- Precau-D1-9-2005
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.

FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.

HARSH™, NIS™, Notifier Integrated Systems™, ONYXWorks™, and Pinnacle™ are all trademarks; and Acclimate®, Filtrex®, FlashScan®, NION®,
NOTIFIER®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a
trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of
the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
©2005 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 3


Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any com-
ments or suggestions about our online Help or printed manuals, you can email us.

Please include the following information:


• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation

Send email messages to:


[email protected]

Please note this email address is for documentation feedback only. If you have any technical
issues, please contact Technical Services.

4 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Table of Contents
Section 1: About This Manual ................................................................................................. 9
1.1: Standards and Other Documents....................................................................................................................9
1.2: Supplemental Documentation......................................................................................................................10
1.3: Cautions and Warnings ................................................................................................................................11
Section 2: System Overview .................................................................................................. 13
2.1: System Description ......................................................................................................................................13
2.1.1: Standard Features ..............................................................................................................................13
2.1.2: Options ..............................................................................................................................................13
2.1.3: System Limitations ............................................................................................................................14
2.2: System Components ....................................................................................................................................14
2.2.1: Basic Equipment Required ................................................................................................................14
2.2.2: Control Panel Circuit Board .............................................................................................................15
2.2.3: Main Power Supply ...........................................................................................................................15
2.2.4: Circuit Board Components ................................................................................................................16
2.3: System Cabinets...........................................................................................................................................18
2.4: Optional Devices .........................................................................................................................................19
2.5: Intelligent Detectors.....................................................................................................................................20
2.6: Addressable Modules...................................................................................................................................22
2.7: Annunciation Modules.................................................................................................................................23
2.8: Annunciators................................................................................................................................................23
2.8.1: Annunciators with 24- and 48-Point Capacity ..................................................................................24
2.8.2: Annunciator Fixed Modules .............................................................................................................24
2.9: Peripheral Displays and Printers..................................................................................................................24
2.10: Panel Circuit Modules ..............................................................................................................................25
2.11: Voice Alarm System ..................................................................................................................................26
Section 3: Installation............................................................................................................. 29
3.1: Preparing for Installation .............................................................................................................................29
3.1.1: Standards and Codes..........................................................................................................................29
3.2: Installation Checklist ...................................................................................................................................30
3.3: Mounting a Cabinet .....................................................................................................................................30
3.4: Laying Out Equipment in Cabinet and Chassis ...........................................................................................31
3.5: Installing the Control Panel .........................................................................................................................33
3.5.1: Control Panel Circuit Board & Keypad/Display Unit .......................................................................33
3.5.2: Using XLS-NCA as Primary Display................................................................................................35
3.5.3: Loop Expander Module .....................................................................................................................36
3.5.4: Network Control Module...................................................................................................................37
3.5.5: Panel Circuit Modules and Other Option Boards..............................................................................37
3.6: Connecting the Power Cables ....................................................................................................................39
3.6.1: Overview ...........................................................................................................................................39
3.6.2: Connecting the Control Panel to AC Power......................................................................................39
3.6.3: Checking AC Power ..........................................................................................................................40
3.6.4: Installing and Connecting the Batteries ............................................................................................40
3.6.5: APS-6R Auxiliary Power Supply Connections .................................................................................41
3.6.6: External DC Power Output Connections...........................................................................................41
3.7: NAC Connections & Releasing Circuits .....................................................................................................42
3.8: Output Relay Connections ...........................................................................................................................42
3.9: Backup-Alarm Switches .............................................................................................................................43
3.10: Installing a Transmitter Module TM-4 ......................................................................................................43
3.11: UL Power-limited Wiring Requirements ...................................................................................................43
3.11.1: Labeling Modules and Circuits........................................................................................................44
3.12: Installing Panel Circuit Modules ..............................................................................................................44
3.12.1: Overview .........................................................................................................................................44
3.12.2: Mounting Expander Boards.............................................................................................................45

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 5


3.12.3: Connecting Ribbon Cables for a CAB-4 Series Backbox ...............................................................45
3.12.4: Installing the Panel Circuit Modules ...............................................................................................46
3.12.5: Connecting ICM-4RK and ICE-4 Modules .....................................................................................46
Power Supply Connections...................................................................................................................47
Multiple Power Supplies ......................................................................................................................47
3.12.6: Field-Wiring the ICM-4RK and ICE-4 (NFPA Style Y or Z).........................................................48
3.12.7: Connecting CRM-4RK/CRE-4 Modules .........................................................................................49
3.13: Auxiliary Relay Module (ARM-4): Product-Specific Details ...................................................................49
3.13.1: Overview..........................................................................................................................................49
3.13.2: Installation .......................................................................................................................................49
3.13.3: Field Wiring an Auxiliary Relay Module ........................................................................................50
3.14: Installing Remote Printers and/or CRT......................................................................................................51
3.14.1: Custom Cable Fabrication ...............................................................................................................51
3.14.2: Installing and Configuring the PRN Series Printer..........................................................................51
Connecting a Remote PRN Series Printer ............................................................................................51
Setting Printer Options .........................................................................................................................52
3.14.3: Installing and Configuring a Keltron Printer ...................................................................................52
Setting up the Keltron Printer ...............................................................................................................53
3.14.4: Installing and Configuring a CRT-2 ................................................................................................53
Setting CRT-2 Parameters ....................................................................................................................54
3.14.5: Connecting a PC ..............................................................................................................................55
3.14.6: Connecting Multiple Printers, CRTs, or CRT/PRN Combination ..................................................55
3.15: Wiring a Signaling Line Circuit (SLC)......................................................................................................56
Section 4: Applications .......................................................................................................... 59
4.1: Overview......................................................................................................................................................59
Municipal Box (Auxiliary) ...................................................................................................................59
4.2: NFPA 72-1999 Central or Remote Station Fire Alarm System (Protected Premises Unit).........................60
4.3: NFPA 72-1999 Proprietary Fire Alarm Systems .........................................................................................61
4.4: Fire/Security Applications ..........................................................................................................................61
4.4.1: General Operation..............................................................................................................................61
4.4.2: Installing a Security Tamper Switch..................................................................................................62
4.4.3: Receiving Unit ...................................................................................................................................62
4.4.4: Programming .....................................................................................................................................63
4.4.5: Wiring for Proprietary Security Alarm Applications ........................................................................63
4.5: Releasing Applications ................................................................................................................................64
4.5.1: Overview............................................................................................................................................64
4.5.2: Programming .....................................................................................................................................64
4.5.3: Wiring ................................................................................................................................................64
4.5.4: Connecting a Releasing Device to the Control Panel ........................................................................65
4.5.5: Connecting a Releasing Device to the XLS-CM-N/TC810N1013 Module ......................................66
4.5.6: Connecting an NBG-12LRA Agent Release-Abort Station ..............................................................67
Section 5: Testing the System .............................................................................................. 69
5.1: Acceptance Test ...........................................................................................................................................69
5.2: Periodic Testing and Service........................................................................................................................69
5.3: Operational Checks ......................................................................................................................................69
5.4: Battery Checks and Maintenance.................................................................................................................70
On-board Memory-Backup Battery......................................................................................................70
Appendix A: Power Supply Calculations ............................................................................. 71
A.1: Calculating AC Branch Circuit Current......................................................................................................71
AC Branch Circuit Installation .............................................................................................................71
A.2: Calculating the System Current Draws ......................................................................................................71
How to Use the Calculating Tables ......................................................................................................71
A.2.1: Calculating the Maximum Secondary Power Fire Alarm Current Draw..........................................74
A.3: Calculating the Battery Requirements ........................................................................................................75
A.3.1: Calculating the Battery Capacity ......................................................................................................75

6 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


A.3.2: Calculating the Battery Size .............................................................................................................76
Appendix B: Electrical Specifications .................................................................................. 77
B.1: Electrical Specifications..............................................................................................................................77
AC Power ...........................................................................................................................................77
Batteries................................................................................................................................................77
Signaling Line Circuit (SLC) ..............................................................................................................78
Notification Appliance Circuits & Releasing Circuits ........................................................................78
Output Relays .......................................................................................................................................78
Four-wire Smoke Detector Power ........................................................................................................78
Power Output........................................................................................................................................78
Operating Power: AC Branch Circuit...................................................................................................79
Operating Power: Secondary Power Source (Batteries).......................................................................79
B.2: Wire Requirements......................................................................................................................................79
Appendix C: Compatible Equipment..................................................................................... 81
Honeywell and Notifier Equipment .....................................................................................................81
System Sensor Equipment....................................................................................................................82
Appendix D: Canadian Applications ..................................................................................... 83
D.1: Standalone Application ...............................................................................................................................83
D.1.1: XLS140 with KDM-2 .......................................................................................................................83
D.1.2: XLS140 with XLS-NCA ..................................................................................................................83
D.2: Local Network Application ........................................................................................................................83
D.3: Automatic Alarm Signal Silence ................................................................................................................83
D.4: Annunciator Applications ...........................................................................................................................83
D.5: Releasing Devices.......................................................................................................................................83
Index......................................................................................................................................... 84

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 7


8 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
Section 1: About This Manual

1.1 Standards and Other Documents


This Fire Alarm Control Panel complies with the following NFPA standards:
• NFPA 12 CO2 Extinguishing Systems
• NFPA 12A Halon 1301 Extinguishing Systems
• NFPA 13 Sprinkler Systems
• NFPA 15 Water Spray Systems
• NFPA 16 Foam/Water Deluge and Foam/Water Spray Systems
• NFPA 17 Dry Chemical Extinguishing Systems
• NFPA 17A Wet Chemical Extinguishing Systems
• NFPA 72-1999 Central Station Fire Alarm Systems (Automatic, Manual and Waterflow)
Protected Premises Unit (requires Notifier UDACT).
• NFPA 72-1999 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm
Systems.
• NFPA 72-1999 Auxiliary (Automatic, Manual and Waterflow) Fire Alarm Systems (requires
TM-4).
• NFPA 72-1999 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Systems
• NFPA 72-1999 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems
(Protected Premises Unit).
• NFPA 2001 Clean Agent Fire Extinguishing Systems

The installer should be familiar with the following documents and standards:
• NFPA 72-1999 Initiating Devices for Fire Alarm Systems
• NFPA 72-1999 Inspection, Testing and Maintenance for Fire Alarm Systems
• NFPA 72-1999 Notification Appliances for Fire Alarm Systems
Underwriters Laboratories
• UL 38 Manually Actuated Signaling Boxes
• UL 217 Smoke Detectors, Single and Multiple Station
• UL 228 Door Closers - Holders for Fire Protective Signaling Systems
• UL 268 Smoke Detectors for Fire Protective Signaling Systems
• UL 268A Smoke Detectors for Duct Applications
• UL 346 Waterflow Indicators for Fire Protective Signaling Systems
• UL 464 Audible Signaling Appliances
• UL 521 Heat Detectors for Fire Protective Signaling Systems
• UL 864 Standard for Control Units for Fire Protective Signaling Systems
• UL 1481 Power Supplies for Fire Protective Signaling Systems
• UL 1971 Visual Signaling Appliances
• UL 1076 Proprietary Burglar Alarm Systems
• UL 60950 Safety of Information Technology Equipment
Underwriters Laboratories of Canada (ULC)
• Standard CAN/ULC-S527-M99
• CAN/ULC-S524-M91 Standard for the Installation of Fire Alarm Systems
Other
• EIA-485 and EIA-232 Serial Interface Standards
• NEC Article 300 Wiring Methods
• NEC Article 760 Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction
• C22.1-98 The Canadian Electrical Code, Part 1

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 9


About This Manual Supplemental Documentation

1.2 Supplemental Documentation


Table 1.1 below provides a list of documents referenced in this manual, as well as documents for
selected other compatible devices. The document series chart (DOC-HON) provides the current
document revision. A copy of this document is included in every shipment.

Document Number
(Form number if
Compatible Conventional Devices (Non-addressable) applicable)
Device Compatibility Document 51939 (74-3944)
Document Number
(Form number if
Fire Alarm Control Panel (FACP) and Main Power Supply Installation applicable)
XLS140 Installation, Operations, and Programming Manuals 51927 (95-7673),
51928 (85-0254),
51929 (85-0253)
Honeywell Voice Alarm System Manual 51931 (95-7674)
Honeywell SLC Wiring Manual 51932 (95-7675)
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Document Number
(Form number if
Off-line Programming Utility applicable)
VeriFire™ Tools CD help file HONEYWELL-TCD
Document Number
(Form number if
Cabinets & Chassis applicable)
CAB-3/CAB-4 Series Cabinet Installation Document 15330
Battery/Peripherals Enclosure Installation Document 50295
Document Number
(Form number if
Power Supplies, Auxiliary Power Supplies & Battery Chargers applicable)
ACPS-2406 Installation Manual 51304
APS-6R Instruction Manual 50702
CHG-120 Battery Charger Manual 50641
FCPS-24 Field Charger/Power Supply Manual 50059
FCPS-24S Field Charger/Power Supply Manual (Sync) 51977
Document Number
(Form number if
Networking applicable)
XLS-NET Manual, Network Version 5.0 51991 (95-7680)
NCM-W/F Installation Document 51533
Document Number
(Form number if
System Components applicable)
Annunciator Control System Manual 15842
Annunciator Fixed Module Manual 15048
AFM-16A Annunciator Fixed Module Manual 15207
ACM-8R Annunciator Control Module Manual 15342

Table 1.1 Reference Documentation (Sheet 1 of 2)

10 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Cautions and Warnings About This Manual

XLS-LCD-80 Manual 52079 (95-7682)


FDU-80 Remote Annunciator Manual 51264
LDM Series Lamp Driver Annunciator Manual 15885
Honeywell XLS-NCA Network Control Annunciator Manual 51941 (95-7679)
SCS Smoke Control Manual (Smoke and HVAC Control Station) 15712
DPI-232 Direct Panel Interface Manual 51499
TM-4 Installation Document (Reverse Polarity Transmitter) 51490
UDACT Manual (Universal Digital Alarm Communicator/Transmitter) 50050
ACT-2 Installation Document 51118
VEC 25/50 Manual 50686
RM-1 Series Remote Microphone Installation Document 51138
RA400Z Remote LED Annunciator Installation Document I56-508
RFX Wireless Interface Manual 51012
UZC-256 Universal Zone Coder Manual 15216
UZC-256 Programming Manual 15976
XP10-M Installation Document I56-1803
XP6-C Installation Document I56-1805
XP6-MA Installation Document I56-1806
XP6-R Installation Document I56-1804
XPIQ Audio Transponder Manual 51013

Table 1.1 Reference Documentation (Sheet 2 of 2)

1.3 Cautions and Warnings


This manual contains cautions and warnings to alert the reader as follows:

CAUTION:
! Information about procedures that could cause programming errors, runtime errors, or equipment
damage.

WARNING:
! Indicates information about procedures that could cause irreversible damage to the control panel,
irreversible loss of programming data or personal injury.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 11


About This Manual Cautions and Warnings

12 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Section 2: System Overview

2.1 System Description


The XLS140 and XLS140E control panels are modular, intelligent fire alarm control panels
(FACPs) with an extensive list of powerful features. The control panel integrates a central
processing unit (CPU), a 6 amp power supply, and a battery charger. This is combined with a
mounting chassis and cabinet to create a complete fire alarm control system. The panel supports
FlashScan® protocol and has network capabilities. A single SLC loop is supported with the basic
equipment package; a second SLC loop can be added by attaching an optional loop expander
module (LEM-320).
Modular devices mount to the chassis to provide additional output circuits, including voice and
telephone modules to form a complete voice evacuation system. Five cabinet options for enclosing
system components are available.
The control panel has the capacity for installing up to 636 addressable points; 159 detectors and
159 monitor/control modules per SLC (Signaling Line Circuit).

2.1.1 Standard Features


• Uses early warning fire detection and the FlashScan® or Classic Loop Interface Protocol
(CLIP) families of detectors and modules
• Four standard Notification Appliance Circuits (NAC), Class A or B
• Alarm, Trouble, Supervisory and Security relays
• Support for 32 annunciator addresses, with 10 special annunciator groups
• Supports Style 4, Style 6, Style 7 SLC loops
• Connections to easily mount an expander board to add a second SLC loop
• Releasing service using on-board NACs or XLS-CM-N/XLS-CM-N/TC810N1013 modules
• Logic Equations
• Display scroll selection
• Alarm verification supervisory indication (NYC)
• Supervisory duct detectors
• Supports Advanced Warning Addressable Combustion Sensing (AWACS) algorithms
• Network operation
• Battery charger supports 12-55 amp hour sealed lead-acid batteries
• EIA-485 connections for wiring ACS annunciators (including LDM custom graphic
annunciators), TM-4 transmitter
• EIA-232 connections for printer, CRT, printer/CRT, or network operation
• Autoprogram feature for faster programming of new devices
• The control panel provides 6.0 amps of usable output power in an alarm condition; it provides
3.0 amps of usable output power in normal or continuous operating conditions
• Diagnostic LEDs and switches
• Ground fault detection
• Battery and battery-charger supervision, voltage-monitoring, and current-monitoring
• Panel circuit modules support up to 64 circuits
• Programmable for strobe synchronization

2.1.2 Options
Refer to Section 2.2 “System Components” for descriptions of the various optional modules.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 13


System Overview System Components

• QWERTY silicone-rubber keypad with a 2x40 LCD display and eight indicator LEDs
• Optional LEM-320 provides a second SLC loop that is electrically identical to the one on the
main board
• Optional devices include: UDACT Universal Digital Alarm Communicator/Transmitter,
ACM-8R remote relay module to increase point capacity, audio and voice components, and
panel circuit modules
• Optional XLS-LCD-80 connected through an EIA-485 interface allows monitoring the
system—up to 6,000 feet (1,829 meters) from the control panel

2.1.3 System Limitations


System expansion must take into consideration the following:
1. The physical limitations of the cabinet configuration.
2. The electrical limitations of the system power supply.
3. The capacity of the secondary power source (standby batteries).

2.2 System Components


2.2.1 Basic Equipment Required
A basic XLS140 system requires at least the following components:
1. The control panel. XLS140-CPU (120V operation) or XLS140-CPUE (240V operation).
This printed circuit board is the “control panel” itself and the heart of the system. It also
includes an expander cable for connecting panel modules, a grounding cable, battery
interconnect cables, and document kit.
2. One or more chassis. CHS-M2 mounts the XLS140-CPU or XLS140-CPUE.
To mount additional rows of optional equipment, order one or more chassis from this list:
CHS-M2, CHS-4N (included in shipkit CHS-4MB), CHS-4L.
3. A primary display. Generally this is a KDM-2 keypad/display, a DP-DISP dress panel, and
two BMP-1 blank module panels. For information on using XLS-NCA as primary display
instead of KDM-2, see Section 3.5.2 “Using XLS-NCA as Primary Display” and the XLS-NCA
Manual.
4. A backbox and door:
SBB-A4 and XLS-DR-A4 (one row of equipment) or
SBB-B4 and XLS-DR-B4 (two rows of equipment) or
SBB-C4 and XLS-DR-C4 (three rows of equipment) or
SBB-D4 and XLS-DR-D4 (four rows of equipment)
(For a solid-metal door add “B” to the part number; for a red door add “R”.)
5. A battery dress panel BP-4
6. Batteries (Refer to Appendix A.3 “Calculating the Battery Requirements” for system
current-draw calculations; CAB-4 series backboxes holds batteries up to 24 AH maximum.)

14 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


System Components System Overview

2.2.2 Control Panel Circuit Board


The control panel electronics are contained on one four-layer printed circuit board (PCB) that
incorporates a 6 amp power supply with battery charger, a signaling line circuit (SLC) and the
central processing unit. A keypad/display unit can be installed over the power supply as shown
Figure 2.1.

POWER FIRE PRE-ALARM SECURITY SUPERVISORY SYSTEM SIGNALS POINT


ALARM TROUBLE SILENCED DISABLED

ACKNOWLEDGE SIGNAL DRILL SYSTEM LAMP


SCROLL DISPLAY SILENCE HOLD 2 SECONDS RESET TEST

*
1 2 3 4 5 6 7 8 9 0 NEXT
+
! @ = , % : . ? DETECTOR SELECTION

Q W E R T Y U I O P MODULE # PREVIOUS
SELECTION

nfs640-panel.cdr
Esc RECALL
A S D F G H J K L OUTPUT & LAST
ENTRY
(

Enter )
Z X C V B N M SPACE BATTERY
LEVELS / INCREMENT
NUMBER

Figure 2.1 XLS140 Control Panel with Optional Keypad/Display Unit Installed

2.2.3 Main Power Supply


The main power supply is an integral part of the
control panel’s circuit board. It provides a total of
3 A (6 A in alarm) and contains an integral battery
charger. This can be used for many functions
including:
• Powering the XLS140
• Powering a variety of UL-listed 24 VDC
notification appliances from four built-in NAC
outputs
• Providing up to 1.25 A of resettable power for
nfs-640-panel-iso.cdr

four-wire smoke detectors


• Providing up to 1.25 A of non-resettable power
for external devices such as the TM-4
Transmitter Module.

Figure 2.2 Main Power Supply on


Control Panel

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 15


System Overview System Components

2.2.4 Circuit Board Components


The following two figures illustrate the location of the various connections, switches, jumpers and
LEDs on the circuit board. Figure 2.3 shows wiring connections. Figure 2.4 shows jumpers, LEDs
and switches. See Section 3 “Installation” for more details.
J8 - Zone Code Input

TB7 - DC Power (24 VDC power-limited, non-resettable)


TB7 - DC Power (24 VDC power-limited, resettable)

TB8 - Alarm Relay


TB9 - Trouble Relay See Section 3.8 “Output Relay
TB10 - Supervisory Relay Connections” for details.
TB11 - Security Relay

TB12 - EIA-485 Terminal Mode Connection (supervised)


TB13 - EIA-485 ACS Mode Connection (supervised)
TB14 - EIA-232 Printer Connection
TB15 - EIA-232 PC/Terminal Connection (CRT)
J1 - Network/Service Connection (NUP)
(power-limited, supervised)

TB16 - SLC #1 Connections (Detectors,


Modules) (supervised)
+ - + - NO NC C NO NC C NO NC C NO NC C + - + - + - TX RX REF TX RX REF B+ A+ B- A-
B+ B- A+ A-
B+ B- A+ A-

TB6 - NAC#1 All NAC Circuits: power-limited, supervised


TB5 - NAC#2
TB4 - NAC#3
B+ B- A+ A-

TB3 - NAC#4
B+ B- A+ A-

J7 - Accessory Power Connection

TB2 - AC Power Connection


BATT+ BATT- EARTH NTRL HOT

nfs640-board2.cdr

J3 - LEM-320
J4 - KDM-2 Connector
Connection (SLC Loop #2)

10 Amp Slo-Blow Fuse J10 - Security Tamper Switch


P/N 12067 J11 - Auxiliary Trouble Input

TB1 - Battery Connection J5 - Panel Circuits (supervised)


(over-current protected) J6 - Panel Circuits (supervised)

Figure 2.3 Circuit Board Components: Wiring Connections

16 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


System Components System Overview

D55 - Main SLC Ground


Fault LED
JP7 - Charger
Disable Jumper

SW1, SW5 - JP6 - Ground


Relay Switches Fault Jumper
(SLC #1)
JP13 - General Board JP12 - 200MA
Ground Fault Jumper Jumper
NAC LEDs

+ - + - NO NC C NO NC C NO NC C NO NC C + - + - + - TX RX REF TX RX REF B+ A+ B- A-
B+ B- A+ A-
B+ B- A+ A-
B+ B- A+ A-
B+ B- A+ A-

Disable - Enable
Switches for
Backup Alarm
BATT+ BATT- EARTH NTRL HOT

nfs640-board2.cdr
System Switches - ‘No D72 - General D67 -LEM-320
Keyboard Operation’ Board Ground Ground Fault LED
SW2 - Acknowledge Fault LED
SW3 - Silence D82 - Power-on LED
SW4 - Reset (AC or battery)

D54 - ‘AC ON’ / Power LED


D75 - Fire Alarm LED
D76 - Pre-Alarm LED
D77 - Security LED

D81 - Point Disabled LED


D80 - Signals Silenced LED
D79 - System Trouble LED
D78 - Supervisory LED

Figure 2.4 Circuit Board Components: Jumpers, LEDs and Switches

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 17


System Overview System Cabinets

2.3 System Cabinets


The control panel and modules are installed in a CAB-4 series backbox. There are four different
sizes available, holding from one to four rows of equipment plus batteries (up to two 25AH
batteries). Backboxes are ordered separately from doors. The doors can be mounted on the left or
the right side of the cabinet; reversible hinges are provided so that this choice can be made in the
field. Doors open a full 180 degrees and have locks. Mounting methods include surface-mounting
or semi-flush mounting on a wall between 16 inch (40.64 cm) on-center studs. A trim ring option is
available for semi-flush mounting.
External measurements for each backbox are provided below; door dimensions are larger. Refer to
CAB-3/CAB-4 Series Cabinet Installation Document (shipped with the cabinet) for specific
mounting drawings and door dimensions.

A-size backbox 24.00 in (60.96 cm) wide Optional trim ring TR-A4
(one row) 20.00 in (50.8 cm) tall Opening: 24.062 in (61.118 cm) wide;
5.218 in (13.254 cm) deep 20.062 in (50.881 cm) tall.
Uses optional trim ring TR-A4 Molding width: 1.375 in (3.493 cm)

B-size backbox 24.00 in (60.96 cm) wide Optional trim ring TR-B4
(two rows) 28.5 in (72.39 cm) tall Opening: 24.062 in (61.118 cm) wide;
5.218 in (13.254 cm) deep 28.562 in (72.548 cm) tall.
Uses optional trim ring TR-B4 Molding width: 1.375 in (3.493 cm)

C-size backbox 24.00 in (60.96 cm) wide Optional trim ring TR-C4
(three rows) 37.125 in (94.297 cm) tall Opening: 24.062 in (61.118 cm) wide;
5.218 in (13.254 cm) deep 37.187 in (94.455 cm) tall.
Uses optional trim ring TR-C4 Molding width: 1.375 in (3.493 cm)

D-size backbox 24.00 in (60.96 cm) wide Optional trim ring TR-D4
(four rows) 45.75 in (1162.05 cm) tall Opening: 24.062 in (61.118 cm) wide;
5.218 in (13.254 cm) deep 45.812 in (114.775 cm) tall.
Uses optional trim ring TR-D4 Molding width: 1.375 in (3.493 cm)

Trim Rings: When using trim rings, mount backbox with at least 1 inch (2.54 cm) between wall surface and
front of backbox, to allow door to open fully past the trim ring.

The control panel and adjacent first-row modules mount in chassis CHS-M2, typically in the
first/top row of the backbox. Additional rows of modules can be mounted in chassis CHS-4N
and/or CHS-4L.

NOTE: If using the new CHS-M2 in a CAB-3 series backbox or in a CAB-4 series backbox
manufactured before October 2002, verify stud height and cut any stud that exceeds 0.375 in.
(9.525 mm) if a CPU is being mounted above it. See warning and instructions in Section 3.5.1
“Control Panel Circuit Board & Keypad/Display Unit”.

Some additional components available in the CAB-4 series include:


DP-DISP An Inner Dress Panel for covering the backbox area surrounding display panels and
various modules (required for Canadian installations).

NOTE: For use with XLS-NCA, KDM-2, and primary displays.

BMP-1 Blank Module Plate for covering an unused dress-panel position. Provides another option
for mounting modules such as TM-4, NCM-W, or NCM-F.
BP-4 Battery dress panel

18 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Optional Devices System Overview

VP-2B or MP-1B (with DP-1B) For covering top row(s) of backbox if control panel is mounted
in a lower row. MP-1B is also used to mount panel circuit modules.

2.4 Optional Devices


Several optional components can be installed within the XLS140 system. This list provides only a
sample of common equipment; for a complete list of what is available, refer to Appendix C
“Compatible Equipment” and for a list of conventional equipment, refer to the Device
Compatibility Chart.
Network Control Annunciator - XLS-NCA. Provides a text-based, 24 VDC powered,
display and control device for XLS-NET. It incorporates a large LCD display and a silicone-rubber
QWERTY keypad. It will display all events from the system.
Network Control Module - NCM-W/F. The NCM is an interface between the panel and
XLS-NET. It comes in two models: wire and fiber-optic cable. Refer to the NCM-W/F Installation
Document for more information and installation instructions.
Loop Expander Module - LEM-320. The LEM plugs into the control panel, expanding the
board’s function to control two Signaling Line Circuits (SLCs). Each XLS140 can have one LEM.
Refer to Section 3.5 “Installing the Control Panel” for installation instructions.
Auxiliary Power Supply - APS-6R. The optional Auxiliary Power Supply is a 150W
cabinet-mounted power supply, designed to power devices that require filtered, non-resettable
power, such as NAC modules, and addressable Honeywell appliance circuit modules. The APS-6R
provides three 24 VDC output circuits (6 A total in alarm, 4 A continuous): two power-limited
circuits (3 A each) and one non-power-limited circuit (6 A). Refer to the APS-6R Instruction
Manual for further information and installation instructions.
Addressable Charger/Power Supply - ACPS-2406. The optional ACPS-2406 is an
addressable loop-based power supply and battery charger. This cabinet-mounted unit provides four
individually addressable Notification Appliance Circuits. In addition, each circuit can provide
notification appliance synchronization without an additional module. The unit charges 7 to 25 AH
batteries with full supervision. The ACPS-2406 provides up to four 24 VDC (filtered) output
circuits (2.5 A max each, 5.0 A total continuous, 6.0 A during a fire alarm). Refer to the
ACPS-2406 Instruction Manual for further information, installation instructions, and battery
calculations.
Batteries and Battery Boxes. The control panel uses only sealed lead-acid batteries for
standby power. Maximum battery capacity is 55 AH (ampere-hour). Minimum battery capacity
depends upon the system configuration; absolute minimum is 12 AH. CAB-4 Series backboxes
provide space for two 25 AH (or smaller) batteries. Use external battery boxes if the installation
requires larger capacity batteries. Battery boxes mount directly below the main cabinet. Battery box
model XLS-LBB holds batteries up to 55 AH. Refer to Section 4.2 “NFPA 72-1999 Central or
Remote Station Fire Alarm System (Protected Premises Unit)” and Section A.3 “Calculating the
Battery Requirements” for further information. See Battery/Peripherals Enclosure document for
backbox measurements and installation instructions.
Universal Digital Alarm Communicator/Transmitter (UDACT). Transmits system status to
UL-listed Central Station Receivers over a public switched telephone network. Mounting is in a
CAB-4 Series backbox or remotely in the ABS-8R enclosure. The unit connects to the EIA-485
annunciator port and 24 VDC (nominal) power. Refer to the UDACT Instruction Manual for further
information and installation instructions.
Transmitter Module - TM-4. The TM-4 includes three reverse polarity outputs and a Fire
Municipal Box Trip in a single module. It provides a means for the FACP to control Alarm,
Trouble, and Supervisory reverse polarity outputs (15 mA, 24 VDC nominal) or a Fire Municipal
Box Trip output. All output circuits are supervised. The Transmitter Module communicates over

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 19


System Overview Intelligent Detectors

the standard EIA-485 connection like an ACS device and mounts easily in standard module
locations within the cabinet or external boxes. Refer to the Transmitter Module TM-4 installation
document for further information and installation instructions.
Universal Zone Coder - UZC-256. A circuit board, used for NAC coding applications, that
provides three NAC output circuits and up to 256 zone codes. Refer to the UZC-256 Universal
Zone Coder and UZC-256 Programming manuals for further information and installation
instructions.
Field Charger/Power Supply - FCPS-24, FCPS-24S6, FCPS-24S8. Compact,
cost-effective remote power supply and battery charger with a filtered, 24 VDC output that can
drive up to four Notification Appliance Circuits (NACs). The FCPS-24S6/FCPS-24S8 can also
synchronize the NACs. Refer to the FCPS-24 Field Charger/Power Supply Manual or the
FCPS-24S Field Charger/Power Suppply Manual for further information and installation
instructions.
Battery Charger - CHG-120. Designed to charge lead-acid batteries that provide emergency
standby power for a Fire Alarm Control Panel. Provides two (2) output circuits for connection to
multiple loads. Can be mounted into the CAB-4 Series backbox or the XLS-LBB Battery Box.
Refer to the CHG-120 Battery Charger manual for further information and installation instructions.
Liquid Crystal Display - XLS-LCD-80. An alphanumeric display module that is an ancillary
device which has two basic modes of operation. In Terminal Mode it acts as a display interface and
in ACS Mode as an alphanumeric annunciator. Refer to the XLS-LCD-80 Liquid Crystal Display
manual for further information and installation instructions.
Remote Fire Annunciator - XLS-FDU-80. An 80-character LCD that displays all panel
information remotely. Refer to the XLS-FDU-80 Manual for further information and installation
information.
SCS-8 Series Smoke Control System. The Smoke Control Station (SCS-8) module uses
eight groups of four annunciator points for fan shutdown control or other heating, ventilation or air
conditioning functions. The Smoke Control Expander (SCE-8) is used to expand the SCS-8 by an
additional eight groups of four annunciator points. Only one expander can be used per SCS-8. The
Smoke Control Lamp Driver Station (SCS-8L) module uses eight groups of four annunciator points
for fan shutdown control or other heating, ventilation or air conditioning functions. Must be
mounted in custom graphic annunciator panel. The Smoke Control Expander (SCE-8L) is used to
expand the SCS-8L by an additional eight groups of four annunciator points. Only one expander
can be used per SCS-8L. Must be mounted in custom graphic annunciator panel. For more details
on the SCS Smoke Control System, refer to the SCS Manual.

2.5 Intelligent Detectors


Introduction
Intelligent, addressable detectors provide analog information to the control panel on a Signaling
Line Circuit (SLC). This allows the control panel to continually process this information to
determine the status (alarm, trouble, maintenance, or normal) of each detector. Each detector
responds to an SLC address that is set in the detector head using built-in rotary switches. Each SLC
loop can support up to 159 detectors. The sensitivity of each intelligent detector can be
programmed (refer to Appendix C in the XLS140 Programming Manual for details).

NOTE: A blinking LED on an intelligent detector indicates communication between the detector
and the control panel.

20 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Intelligent Detectors System Overview

Detectors
The FlashScan® algorithm provides high-speed communication between analog intelligent
devices, by polling in groups unless new information is reported. If one of the devices within the
group has new information, the control panel stops the group poll and concentrates on single points.
CLIP (Classic Loop Interface Protocol) is standard polling of each intelligent devices.
TC840M1021 (Acclimate™) Intelligent detector that combines a photoelectric sensing
chamber and fixed temperature heat detection (135°F/57.2°C). FlashScan capable.
TC847A1004 (TC847A1004A Canadian) Addressable, intelligent, single-ended beam smoke
detector with built-in sensitivity testing. Supports FlashScan and CLIP mode.
TC807B1059 (TC807B1059CDN Canadian) Addressable, intelligent smoke detector that
incorporates an ionization sensing chamber. Designed to provide open area protection. FlashScan
capable.
TC806B1076 (TC806B1076CDN Canadian) Analog, addressable intelligent smoke detector that
uses a photoelectric sensing chamber. Listed for use in ducts. Designed to provide open area
protection. FlashScan capable. The TC806B1084 adds thermal sensors that will alarm at a fixed
temperature of 135°F (57°C).
TC808B1041 (TC808B1041CDN Canadian) Intelligent thermistor sensing circuit for fast
response. Designed to provide open area protection with 50 foot spacing capability. A fixed
temperature sensor with 135°F fixed temperature alarm. FlashScan capable. The TC808B1058
(TC808B1058CDN Canadian) incorporates a thermal rate of rise of 15°F (9.4°C). FlashScan
capable. The TC808B1066 (TC808B1066CDN Canadian) is a high temperature sensor with 190°F
(87.8°C) fixed temperature alarm.
TC806D1011 Photoelectric Duct Detector. The TC806D1018 includes an alarm relay. The
TC806D1049 (TC806D1049CDN Canadian) and TC806D1056 (TC806D1056CDN Canadian)
are low-flow detectors.
TC844A1007 (Filtrex) A special smoke detector that provides early warning smoke detection in
hostile environments where traditional smoke detectors are not practical. CLIP mode only.
TC844A1015 (Filtrex) A special smoke detector that provides early warning smoke detection in
hostile environments where traditional smoke detectors are not practical. FlashScan and CLIP .
TC846A1005 Early detection laser detector, similar to the TC846A1013 Pinnacle, but limited to
CLIP mode operation only.
TC846A1013 Pinnacle Low Profile Laser Detector An advanced intelligent photoelectric
detector that uses a laser diode, special optics, and signal processing to obtain extremely high
sensitivity. FlashScan mode only.

Bases
Several bases, to which the detectors are affixed, are available:
14507371-001(14507371-001CDN Canadian) Standard U.S. Low-Profile base
14506414-002 (14506414-002CDN Canadian) Standard European flangeless base
B501BH, B501BHT Sounder base, includes 14506414-002/CDN Sounder base with temporal
sounder
B224RB, 14507371-003 (14507371-003CDN Canadian) Low Profile Intelligent relay bases
14507371-005 (14507371-005CDN Canadian) Low Profile Intelligent isolator bases
14507371-008 Filtrex base.

Accessories
RA400Z A Remote Single LED Annunciator that can be wired directly off of an addressable
detector for annunciation of that detector's alarm status.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 21


System Overview Addressable Modules

2.6 Addressable Modules


Control Modules and Monitor Modules provide an interface between the control panel and
conventional notification and initiating devices. Each module can be set to respond to an address
with built-in rotary switches. FlashScan-mode devices can select up to 159 addresses; CLIP mode
devices can select up to 99 addresses. An LED will blink on a monitor module to indicate
communication between the module and the control panel.

NOTE: For a list of approved notification and initiating devices, refer to the Device Compatibility
Document.

Monitor and Zone Interface Modules - XLS-MM-A (FlashScan), TC809A1059 (CLIP),


TC809A1067CDN (Canadian CLIP), XLS-MM-Z (FlashScan), TC841A1000 (CLIP;
TC841A1000CDN Canadian) & XLS-MM-D (FlashScan), TC809D1004 (CLIP;
TC809D1004CDN Canadian) Addressable monitor modules for monitoring conventional
initiating devices. The XLS-MM-A and TC809A1059 are used for normally open contact alarm
initiating devices, such as manual pull stations, four-wire smoke detectors, heat detectors,
waterflow, and supervisory devices. Use the XLS-MM-Z/TC841A1000 for interface to two-wire
smoke detectors in addition to normally open contacts. The XLS-MM-D and TC809D1004 provide
two independent 2-wire Initiating Device Circuits (IDCs) at two separate, consecutive addresses.
Wire supervised IDCs as NFPA Style B (Class B) or Style D (Class A) circuits. The modules come
with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
Monitor Module - XLS-MM-B/TC809B1008 (TC809B1016CDN Canadian) An
addressable module that is functionally similar to the XLS-MM-A/TC809A1059 Monitor
Modules—but offered in a smaller package for mounting directly in the electrical box of the device
being monitored. (Class B input circuit only.)
Control Module, NAC - XLS-CM-N (FlashScan), TC810N1013 (CLIP, TC810N1013CDN
Canadian) Addressable Control Module used as Notification Appliance Circuits (NACs) to
power and supervise compatible, UL-listed notification appliances. Wired supervised NACs as
NFPA Style Y (Class B) or Style Z (Class A). The modules come with a thermoplastic cover for
mounting to a 4-inch (10.16 cm) square mounting box.
Control Module, Relay - XLS-CM-R (FlashScan), TC810R1024 (CLIP,
TC810R1024CDN Canadian) Similar to the XLS-CM-N/TC810N1013 except used as a
Form-C control relay module.
Fault Isolator Module - TC811A-1006 (TC811A1014 Canadian) This module is not
addressable, but listed here due to its use in an SLC. Protects the system against wire-to-wire short
circuits on the SLC. It should be placed between groups of sensors in a Style 6 or Style 7 SLC to
isolate short- and open-circuit problems and protect the rest of the loop so it can continue to operate
normally.
Pull Station - XLS-MPS (FlashScan) / S464G1007 (CLIP) An addressable manual pull
station with key-lock reset feature. The addressable module is housed within the pull station.
Quad Intelligent Audio Transponder - XPIQ The XPIQ is an integrated audio amplification
and distribution subsystem that can direct up to four low-level audio signals through four audio
amplifiers to integrated, continuously supervised speaker circuits. An on-board power supply
charges and supervises battery backup.
Multi-Input/Output Modules - XP6-C (XP6-CA Canadian), XP6-R, XP10-M (XP10-MA
Canadian), XP6-MA (XP6-MAA Canadian) FlashScan capable multi-input/output modules are
available for use on the SLC loop. All are FlashScan capable.
• XP6-C controls six NAC or speaker/telephone circuits. For more information see the XP6-C
Installation Document. (Not listed for use in releasing applications.)
• XP6-R controls six Form-C relays.

22 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Annunciation Modules System Overview

• XP10-M supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor
normally open contact initiating devices. .
• XP6-MA enables an intelligent alarm system to monitor six zones of conventional two-wire
detectors.
For installation instructions, refer to the documentation provided with the modules.

2.7 Annunciation Modules


Introduction
This section contains brief descriptions and model numbers of annunciator modules that can be
connected to the control panel. Communication between the control panel and annunciators takes
place over a two-wire serial interface connected to the control panel’s EIA-485 ACS Mode
connection. Section 2.8 “Annunciators” contains more detailed information.

Description
Below are descriptions of the Annunciator Modules and Expander Modules used with the control
panel.
Annunciator Control Module - ACM-8R Provides the control panel with a mappable relay
control module. Relays can be selected for mapping anywhere in the system memory (in groups of
eight). Provides eight Form-C relays with 5 A @ 125 VAC (resistive) or 5 A @ 30 VDC (resistive)
or 2 A @ 125 VAC (inductive) contacts. Tracks any group of eight zones within the system.
Refer to ACM-8R Annunciator Control Module manual for more information.
Lamp Driver Annunciator Module - LDM-32 Provides 32 alarm lamp driver outputs for
connection to a custom graphic annunciator. DIP switch selectable for 32 alarm outputs or 16
alarm/16 trouble outputs, and 16 switch inputs for control of system control functions as Signal
Silence and System Reset.
Refer to the LDM Series Lamp Driver Annunciator Modules manual for more information.
Lamp Driver Annunciator Expander Module - LDM-E32 Expands the LDM-32 by 32
system points, to a maximum of 64 points.
Lamp Driver Relay Expander Module - LDM-R32 Provides the LDM-32 or LDM-E32 with
32 dry Form-A (normally open) contacts.

2.8 Annunciators
The Annunciator Control System provides the control panel with 32 remote annunciators. The
number of points a particular annunciator can support is reflected in the part number. For example,
an ACM-24AT has 24 points and an ACM-48A has 48 points. The number of points on an
Annunciator Expander Module must match the number of points on the Annunciator Control
Module it is expanding. One Annunciator Fixed Module can also be used per system. Connections
are through an EIA-485 ACS Mode connection on the Control Panel.

NOTE: The XLS140 can only support 64 points per annunciator address regardless of the model
used.

Brief descriptions follow of specific modules used with the control panel. For detailed information,
refer to the specified product manual.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 23


System Overview Peripheral Displays and Printers

2.8.1 Annunciators with 24- and 48-Point Capacity


For specific installation information, refer to the Annunciator Control Module manual. For
Canadian requirements, see Appendix D “Canadian Applications”.
Annunciator Control Module - ACM-24AT A one-channel Class-B unit with 24 switch
controlled annunciator points. Each point is controlled by a silicone-rubber switch with indicator
LED. Multi-color LEDs can be programmed to produce one of three colors: red, green or yellow.
Annunciator Expander Module - AEM-24AT An expander board for the ACM-24AT that
provides an additional 24 points and is identical in size and appearance. Up to three expanders can
be used with an ACM-24AT.

NOTE: An AEM-24AT cannot be used to expand an ACM-48A.

Annunciator Control Module - ACM-48A A one-channel Class- B unit with 48 annunciator


points for indicating current system status. Each annunciator point has a red LED for alarm, and a
green LED for normal; each module has a yellow unit-trouble LED at the top.
Annunciator Expander Module - AEM-48A An expander board for the ACM-48A that
provides an additional 48 points and is identical in size and appearance. One expander can be used
with an ACM-48A.

NOTE: An AEM-48A cannot be used to expand an ACM-24AT.

2.8.2 Annunciator Fixed Modules


Introduction
Provide the control panel with discrete display and control points. Fixed modules turn their LEDs
on and off as directed by the control panel, and also report switch activations to the control panel
for action. You can only use one fixed module in a system. Each annunciator’s address is fixed at
address 1.
Refer to the Annunciator Fixed Module manual for further information.

Description
Annunciator Fixed Module - AFM-16AT Contains 16 red alarm and 16 yellow trouble LEDs,
a system trouble LED, an Online/Power LED, and a local sounder, and switches for control panel
Acknowledge, Alarm Silence, and System Reset. Use the AFM-16AT for systems that require 16 or
fewer annunciation points.
Annunciator Fixed Module - AFM-32A Contains 32 red alarm LEDs, a system trouble LED,
an ON LINE/POWER LED, and a local panel sounder with a silence/acknowledge switch. The
AFM-32A is fixed at address 1, and will not accept expander modules.

2.9 Peripheral Displays and Printers


The control panel is compatible with the following printers and display devices:
• PRN Series Printer
• Keltron Remote Printer VS4095
• CRT-2 Display Terminal
All EIA-232 devices must be located in the same room in conduit within 20 feet (6.1 m) of the
control panel.

24 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Panel Circuit Modules System Overview

Printer - PRN Series Printer The PRN is an optional printer that connects directly to the
control panel through an EIA-232 interface (TB14) and can be located up to 20 feet (6.1 m) from
the control panel. It creates a printed record (80 columns of data on standard 9" x 11" tractor-feed
paper) of all system events (alarm, trouble) and status changes within the system. The printout is
time-stamped with the current time-of-day and date.
Keltron Remote Printer The VS4095 is a two-color (red/black), 40-column, 24 VDC printer
that can print 50 messages in 90 seconds. This printer connects to the control panel through an
EIA-232 interface (TB14) and mounts in a separate cabinet next to the control panel. The VS4095
meets UL fire and security requirements for an ancillary device.
For more information, contact the manufacturer (Keltron Corp., Waltham, MA)
Display Terminal - CRT-2 This optional display terminal connects to the control panel through
an EIA-232 interface (TB15). The terminal can control and view events, points and history reports,
control the system (Acknowledge, Alarm Silence, and System Reset). The terminal displays 26
lines by 80 columns and can be located up to 50 feet (15.24 m) from the control panel within the
same room.

NOTE: The CRT cannot be connected at the same time as the network.

2.10 Panel Circuit Modules


Introduction
The control panel supports the following modules to control external circuits and relays:
• Indicating Circuit Module (ICM-4RK) & Indicating Circuit Expander (ICE-4)
• Control Relay Module (CRM-4RK) & Control Relay Expander (CRE-4)
• Auxiliary Relay Module (ARM-4)
• Voice Control Module (VCM-4RK), Dual Channel Module (DCM-4RK) & Voice Control
Expander (VCE-4)
Up to eight of these modules (in any combination) can be controlled by the panel. Below are brief
descriptions of the modules; for a description of VCM-4RK and DCM-4RK, see Section 2.11
“Voice Alarm System”.
Indicating Circuit Module - ICM-4RK Provides four (4) NACs for Style Y (Class B) or Style
Z (Class A) operation. Circuits are field-programmable to respond to a single initiating zone, a
group of zones, or all initiating zones. Maximum signaling current is 3 A per circuit or 6 A per
module, limited by the power supply.
An Auxiliary Power Harness (P/N 71091) is provided. Note: ICM-4RK is not listed for use with
XLS140 in releasing applications.
Indicating Circuit Expander - ICE-4 An attaching circuit board that expands the ICM-4RK to
a total of eight Style Y (Class B) or Style Z (Class A) NAC’s. Maximum signaling current is 3 A
per circuit or 6 A per module, limited by the power supply. An Auxiliary Power Harness (P/N
71091) is provided.
Control Relay Module - CRM-4RK Provides four (4) standard dry Form-C relay contacts.
Each relay is field-programmable to respond to a single initiating device circuit, a group of circuits,
or all initiating device circuits. Each relay features manual On/Off control switches and can be
disabled or enabled. Contacts rated for 5 A at 120 VAC or 28 VDC (resistive). Note: CRM-4RK is
not listed for use with XLS140 in releasing applications.
Control Relay Expander - CRE-4 An attaching circuit board that expands the capacity of the
Control Relay Module (CRM-4RK) to eight (8) Form-C alarm relays. May also be used to expand
the ICM-4RK to provide four (4) Form-C control relays. Contacts rated for 5 A at 120 VAC or 28
VDC (resistive).

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 25


System Overview Voice Alarm System

Auxiliary Relay Module - ARM-4 Provides four (4) auxiliary Form-C relays that can be
controlled by a CRM-4RK or CRE-4 relay module. Normally-open contacts rated for 20 A and the
normally-closed contacts are rated for 10 A at 125 VAC and 30 VDC (resistive). An Auxiliary
Power Harness (P/N 71092) is provided.

2.11 Voice Alarm System


Introduction
Voice Alarm equipment provides a manual or automatic supervised paging system for transmitting
voice messages (information, instructions, directions) on a selective or all call basis. For more
information and installation instructions refer to the Voice Alarm System manual.

Configuration
XLS-VCC-1B Voice Control Center Basic equipment package for single-channel audio
evacuation system that includes: AMG-1 Audio Message Generator (with microphone), CHS-4L
Chassis, DPSW-1B Single-well Dress Panel, and Cable assemblies required to connect to control
panel.
XLS-VTCC-1B Voice/Telephone Control Center Basic equipment package for
single-channel audio evacuation system employing a Fire Fighter’s Telephone system that includes:
FFT-7 Fire Fighter’s Telephone, AMG-1 Audio Message Generator (with microphone), CHS-4L
Chassis, DPDW-1B Double-well Dress Panel, and Cable assemblies required to connect to control
panel.
XLS-TCC-1B Telephone Control Center Basic equipment package for a Fire Fighter’s
Telephone system with no voice evacuation or paging capabilities that includes: FFT-7 Fire
Fighter’s Telephone, CHS-4L Chassis, TBP-1B Blank Panels (2), DPDW-1B Double-well Dress
Panel, and Cable assemblies required to connect to control panel.

Descriptions
Audio Message Generator (AMG-1 & AMG-E) Provides a variety of tones and a built-in
microphone allows for paging through speaker circuits. Optionally, you can install up to four
digitally-recorded voice messages into the AMG-1: two factory prerecorded voice messages, two
user-defined messages. You can create both user-defined messages through the AMG-1 built-in
microphone, or download messages from a standard audio cassette recorder.
The AMG-E is an AMG-1 without a microphone. It is used for applications that require multiple
Audio Message Generators.
Fire Fighters Telephone (FFT-7 and FFT-7S) Provides the Voice Alarm System with fire
fighter's telephone capability. With these units, up to seven telephones can be used to hold a
simultaneous conversation. The FFT-7S does not provide paging capability.
Voice Control Module (VCM-4RK) Provides the system with up to four (4) Style Y (Class B)
or Style Z (Class A) speaker circuits, or up to four Style Y (Class B) telephone circuits. Moving a
jumper on the module configures it for driving FFT-7 circuits. When configured for telephone
circuits, the VCM-4RK accepts its signal directly from a Fire Fighters Telephone. Add an optional
Voice Control Expander (VCE-4) to the back of the module to provide four additional telephone or
speaker circuits.
Dual Channel Module (DCM-4RK) Provides the system with the capability to select one of
two types of audio sources for switching to a specified speaker circuit. The module provides up to
four circuits.
Audio Amplifiers The control panel uses three types of audio amplifiers with an installed Voice
Alarm System:
• AA-30 – Provides up to 30 watts of audio power for driving 25 Vrms speaker circuits.
• AA-100 – Provides 100 watts of audio power for driving 25 Vrms and 70.7 Vrms speaker
circuits.

26 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Voice Alarm System System Overview

• AA-120 – Provides 120 watts of audio power for driving 25 Vrms speakers.
Each AA amplifies the audio signal coming in from an Audio Message Generator (AMG-1 or
AMG-E).
Audio Coupling Transformer ACT-1 Couples low-level audio to audio amplifiers or other
audio inputs, such as the AMG-1 Audio Message Generator. Provides Common Mode Noise
Rejection (CMNR), greatly reducing crosstalk from the SLCs. For more information and
installation instructions refer to the Voice Alarm System manual.
Audio Coupling Transformer ACT-2 When used with an AMG-1/-E, RM-1 and AA-30 this
unit provides a means to drive thousands of amplifiers in large audio system applications. The
ACT-2 provides electrical isolation between its input & output and attenuates the signal from
high-level audio to low-level audio. For more information and installation instructions refer to the
ACT-2 Product Installation Drawing.

Additional Devices
The following devices are not part of the Voice Control System, but are listed here for continuity.
Remote Microphone (RM-1 and RM-1SA) Provides paging capabilities to speaker systems
driven by the low level audio source of the AMG-1. The RM-1 assembly can be installed in a
CAB-4 Series backbox, while the RM-1SA is installed in a CAB-RM cabinet. For more
information and installation instructions see the RM-1 Series Remote Microphone installation
document.
Quad Intelligent Audio Transponder - XPIQ See product description on page 22.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 27


System Overview Voice Alarm System

28 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Section 3: Installation

3.1 Preparing for Installation


Choose a location for the fire alarm system that is clean, dry, and vibration-free with moderate
temperature. The area should be readily accessible with sufficient room to easily install and
maintain it. There should be sufficient space for cabinet door(s) to open completely.
Carefully unpack the system and inspect for shipping damage. Count the number of conductors
needed for all devices and find the appropriate knockouts. (Refer to Section 3.11 “UL
Power-limited Wiring Requirements” for selection guidelines.)
Before installing the fire alarm system, read the following:
• Review the installation precautions at the front of this manual, including temperature and
humidity limits for the system (Page 3).
• All wiring must comply with the National and Local codes for fire alarm systems.
• Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet except when using a
separate battery cabinet; this space is for internal battery installation.
• Review installation instructions in Section 3.2 “Installation Checklist”.

CAUTION:
! Make sure to install system components in the sequence listed below. Failure to do so can damage
the control panel and other system components.

WARNING:
! This system contains static-sensitive components. Always ground yourself with a proper wrist strap
before handling any circuits. Use static-suppressive packaging to protect electronic assemblies
removed from the unit.

3.1.1 Standards and Codes


In addition, installers should be familiar with the following standards and codes:
• NEC Article 300 Wiring Methods.
• NEC Article 760 Fire Protective Signaling Systems.
• Applicable Local and State Building Codes.
• Requirements of the Local Authority Having Jurisdiction.
• C22.1-98 The Canadian Electrical Code, Part 1.
• CAN/ULC-S5524-01 Standard for the Installation of Fire Alarm Systems.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 29


Installation Installation Checklist

3.2 Installation Checklist


Table 3.1 provides an installation checklist for installing, wiring, and testing the XLS140 system. It
has references to installation information included in manuals listed in Section 1.2 “Supplemental
Documentation”.
Seq Task Refer to
1. Mount the cabinet backbox to the wall. Section 3.3 “Mounting a Cabinet”
2. Install all required chassis in cabinet. Section 3.5 “Installing the Control Panel”
3. Install control panel onto chassis. Section 3.5.1 “Control Panel Circuit Board & Keypad/
Display Unit”
4. Optional: Install auxiliary power supply and/or external Auxiliary power manuals
battery charger
5. Calculate the proper battery rating. Appendix A “Power Supply Calculations”
6. Connect AC wiring, place batteries into backbox without Section 3.6 “Connecting the Power Cables”
connecting them, and run cable to optional power supplies,
DC power outputs, NACs, and relays.
CAUTION: Do not apply AC or DC power at this time.
7. Set switches for backup alarm (SW6-SW9). Section 3.9 “Backup-Alarm Switches”
8. Optional: Install and wire Auxiliary Relay Module (ARM-4). Section 3.13 “Auxiliary Relay Module (ARM-4):
Product-Specific Details”
9. Optional: Install Panel Circuit Modules (ICM-4RK, Section 3.12 “Installing Panel Circuit Modules”, and Voice
CRM-4RK, VCM-4RK, DCM-4RK) and Voice Alarm System Alarm System Manual
components (AMG-1, FFT-7, Audio Amplifiers)
10. Optional: Install output devices such as a printer, or CRT Section 3.14 “Installing Remote Printers and/or CRT”
terminal.
11. Optional: Install XLS-NCA. XLS-NCA Manual
12. Secure any unused mounting holes in control panel circuit Figure 3.4
board.
13. Wire the Signaling Line Circuits. Section 3.15 “Wiring a Signaling Line Circuit (SLC)”
14. Connect wire shielding as instructed. SLC Wiring Manual
15. Apply AC power to the control panel by placing the external circuit breaker to the ON position.
Do NOT connect batteries.
16. Check AC power. Table 3.3 in Section 3.6 “Connecting the Power Cables”
17. Connect the batteries using interconnect cable, P/N 75560 and 75561.
18. Install the CAB-4 series door. CAB-3/CAB-4 Series
Cabinet Installation Document
19. Program the control panel. XLS140 Programming Manual.
20. Field test the system. Section 5 “Testing the System”

Table 3.1 Installation Checklist

3.3 Mounting a Cabinet


This section provides instructions for mounting a CAB-4 Series backbox to a wall. Follow these
guidelines when mounting the backbox:
• Locate the backbox so that the top edge is 66 inches (1.6764 m) above the surface of the
finished floor.
• Access to the cabinet shall be provided in accordance with NFPA 90, article 110.33.
• Allow sufficient clearance around cabinet for door to swing freely. (See Section 2.3 “System
Cabinets”.)
• Use the four holes in the back surface of the backbox to provide secure mounting. (See
Figure 3.1.)

30 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Laying Out Equipment in Cabinet and Chassis Installation

• Mount the backbox on a surface that is in a clean, dry, vibration-free area.

CAUTION:
! Unless you are familiar with the placement of components within this backbox, only use the knockout
locations provided for conduit entry.

Follow the instructions below.


1. Mark and pre-drill holes for the top two keyhole mounting bolts (0.25 inch, 0.635 cm). Use
mounting hardware appropriate for the mounting surfaces; see UL 2017 Pull-Test
Requirements.
2. Select and punch open the appropriate knock-outs. (For selection guidelines, see Section 3.11
“UL Power-limited Wiring Requirements”.)
3. Using the keyholes, mount the backbox over the two screws.
4. Mark the location for the two lower holes, remove the backbox and drill the mounting holes.
5. Mount the backbox over the top two screws, then install the remaining fasteners. Tighten all
fasteners securely.
6. Feed wires through appropriate knockouts.
7. Install control panel and other components according to Section 3.5 “Installing the Control
Panel” before installing hinges and door according to CAB-3/CAB-4 Series Cabinet
Installation Document.

CAB-4
Series
CAB-4
Backbox,
Series Keyholes
D-size
Backbox, 2 places
(four-row)
A-size
(one-row)
Mounting holes

nfs640cabinetmountingholes.cdr
2 places

Figure 3.1 Mounting Holes of a Backbox

3.4 Laying Out Equipment in Cabinet and Chassis


The XLS140 allows for flexible system design. Follow these guidelines when deciding where to
locate equipment in the backbox.
The first row of equipment mounts in chassis CHS-M2. Mount second, third, or fourth rows of
equipment in chassis CHS-4N (panel circuit modules, see Section 3.12 “Installing Panel Circuit
Modules”), or in chassis CHS-4L (voice components, see the Voice Alarm System Manual). Some
equipment, such as the XLS-NCA and annunciators, may be door-mounted; refer to the
equipment’s documentation for instructions.
There are four basic positions available on a chassis (side-by-side); the number of modules that can
be mounted in each position depends on the chassis model and the module size.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 31


Installation Laying Out Equipment in Cabinet and Chassis

The CHS-M2 accepts four layers of equipment, including the control panel. The control panel fills
three positions in the first-installed layer, its integral power supply occupies two positions in the
next two layers, and the optional display occupies the two left-most slots in the fourth layer (flush
with the door). Panel circuit modules and other modules of the same sizing can be mounted in
several layers, depending on the desired configuration; see Table 3.2 to determine hardware. Some
equipment, such as the XLS-NCA, may be door-mounted directly in front of the control panel. The
BMP-1 Blank Module Plate covers unused positions in a dress-panel, providing another mounting
location for some modules, such as TM-4 (see BMP-1 Product Installation Drawing for details).

Mounting location
for LEM-320

Typical mounting location


for NCM-W/F or TM-4

nfs640-chs-m2-11-03.wmf
KDM-2

Panel circuit module mounted


on flanges above control panel
Available mounting slots for
panel circuit modules, TM-4,
and NCM-W/F.

Figure 3.2 Equipment Mounting Locations (First-Row Chassis CHS-M2)

NOTE: When designing the cabinet layout, consider separation of power-limited and
non-power-limited wiring as discussed in Section 3.11 “UL Power-limited Wiring Requirements”.

32 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Installing the Control Panel Installation

From… To… Required Stand-off or Hardware

Chassis CHS-M2 Control panel or Not applicable; integral to the chassis.


module on first layer

Control panel or Option board, 2nd layer 4 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.
Option board, 1st layer (includes LEM-320)

Option board, 2nd layer Option board, 3rd layer 4 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.

Chassis Option board, 4th layer Attaches directly to flanges on chassis. (Screws provided with option
(flush with door) boards & panel circuit modules)

Chassis Panel circuit module Attaches directly to flanges on chassis. (Screws provided with option
(flush with door) boards & panel circuit modules)

Control panel KDM-2 (upper edge) 2 stacks of male-female stand-offs:


P/N 42185 (2.0 inch, 50.8 mm) and
P/N 42186 (1.312 inch, 33.33 mm)

Chassis rail KDM-2 (lower edge) 2 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.

Dress panel XLS-NCA Attaches directly to dress panel.


DP-DISP or ADP-4B (Nuts provided with XLS-NCA.)

Dress panel Option board BMP-1 attaches to dress panel; option module attaches to BMP-1
DP-DISP or ADP-4B (screws provided with option module).
Note: The initial release of chassis CHS-M2 used L-brackets and stand-offs of different lengths than the current model; refer to
Doc. 51927, Rev A (Form Number 95-7673).
Table 3.2 Stand-off Lengths

3.5 Installing the Control Panel


3.5.1 Control Panel Circuit Board & Keypad/Display Unit
The control panel mounts in chassis CHS-M2, which is usually positioned in the top row of the
backbox. The control panel’s CPU occupies three positions at the back of the chassis; the KDM-2
occupies two positions flush with the door. The XLS-NCA may be door-mounted directly in front
of the control panel if no KDM-2 is being used; see the XLS-NCA Manual for details and
restrictions.

NOTE: For initial release of XLS140, mounting instructions were different. Refer to the
installation manual shipped with the panel (Rev A).

1. Verify height of the mounting stud in the backbox. In older backboxes, the stud must be
shortened to prevent damage to the XLS140-CPU. All electronics must be removed from the
backbox before shortening. See instructions in the warning below.

WARNING:
! For retrofit applications, verify the height of the backbox’s mounting stud on left side under CPU, as
shown in Figure 3.3 below. Stud height must not exceed 0.375 in. (9.525 mm). Early versions of the
CAB-4 Series backboxes and all CAB-3 Series backboxes have studs that require shortening.
Failure to shorten this 0.625 in. (15.875 mm) mounting stud will cause damage to the control panel’s
CPU. Remove electronics from backbox, permanently mount empty CHS-M2 chassis to backbox,
apply nut to mounting stud to protect threading, then cut stud to proper length. Reinstall electronics
as discussed in the steps below.

WARNING:
! Do not cut without washers and nuts in place to protect threading. Wear protective eye covering.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 33


Installation Installing the Control Panel

If using a new CHS-M2 in a CAB-3


series backbox or in a CAB-4 series
backbox manufactured before October
2002, verify stud height and cut any stud
that exceeds 0.375 in. (9.525 mm) as
per Step 1 above if a CPU is being
mounted above it. Reinstall electronics
as discussed in the steps below.

CHS-M2-11-03-CAB-3.wmf
Figure 3.3 Using the Redesigned CHS-M2 with Older Backboxes

2. Screw chassis to the backbox.


3. Attach XLS140-CPU to the chassis. Slide control-panel tabs into slots on chassis and lay the
board onto stand-offs so that mounting holes line up with those on the chassis. Secure with
six (6) screws (four across the top of the board, and two to the left of the power supply)
provided with the chassis. (See Figure 3.4.)
4. If installing KDM-2, install the stand-offs included with the keyboard kit. (See Figure 3.4.)
• The upper edge of the keyboard mounting plate rests on two stacked pairs of male-female
stand-offs. Connect P/N 42185 (2.0 inch, 50.8 mm) to P/N 42186 (1.312 inch, 33.33 mm).
• Thread the stacked pairs of stand-offs through mounting holes on the control panel as shown in
Figure 3.4.
• Thread two P/N 42166 (0.937 inch, 23.8 mm) male-female stand-offs through mounting holes
in the chassis rail.
• Attach ribbon cable from keypad to J4 connector on control panel. (See Figure 2.3.)
• Align the keypad with the stand-offs and screw it down.
5. If using the XLS-NCA instead of the KDM-2, refer to Section 3.5.2 “Using XLS-NCA as
Primary Display” and the XLS-NCA Installation Manual.
6. If not using an LEM-320, secure the last 4 mounting holes with screws.

CAUTION:
! It is critical that all mounting holes of the XLS140 are secured with a screw or standoff to insure
continuity of Earth Ground.

34 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Installing the Control Panel Installation

Stack of two male-female stand-offs:


connect P/N 42185 (2.0 inch, 50.8 mm)
to P/N 42186 (1.312 inch, 33.33 mm).
Note: If not using this location,
secure these mounting holes
with screws.

CHS-M2-0604-assy.wmf
Attach two (0.937 inch, 23.8 mm) stand-offs
to chassis rail; screw keypad mounting
plate to the stand-offs.

Lower edge of panel circuit modules slide into chassis slots,


and upper edge mounts onto PEM studs on the chassis flange.

Figure 3.4 Locating and Aligning Stand-offs for Keypad/Display and Panel Circuits
(Chassis CHS-M2 shown)

3.5.2 Using XLS-NCA as Primary Display


The XLS140 can be set up to use an XLS-NCA instead of a KDM-2. In this system design, connect
the network/service port on the XLS140 (J1) directly to the network/service port on the XLS-NCA
(J3); see the XLS-NCA Manual for specific instructions.

NOTE: This system design is required in Canadian stand-alone applications.

If the XLS140 and XLS-NCA are being used as a stand-alone pair, each device must be
programmed separately using VeriFire Tools in its off-line programming mode. Because the
VeriFire Tools computer also uses the network/service port, XLS140 and XLS-NCA must be
temporarily disconnected for programming. If the XLS140 with XLS-NCA is connected to a
network, there are two additional options for programming: either connect the VeriFire Tools
programming PC to the network port on the NCM board, or program the XLS140 through another
network node. (See VeriFire Tools on-line help for details.)

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 35


Installation Installing the Control Panel

3.5.3 Loop Expander Module


Installing a Loop Expander Module adds a
second SLC loop to the control panel. Refer

TB1
B+ A+ B- A-

to the Figure 3.6 for connector illustrations.


1. Thread four (4) 0.937 inch (23.8 mm)
stand-offs through indicated holes in the
XLS140-CPU board.
2. Plug stacker-connector into J3 on the

TB1
XLS140-CPU.
3. Lay the LEM onto the standoffs and B+ A+ B- A-
connect the Loop Expander Module
(LEM) into the stacker-connector
attached to J3.
4. Attach LEM using screws provided with
the module.

Lem-slc.cdr
5. After LEM is mounted on the control
panel, connect the SLC loops to TB1 on LEM-320PCA J1

the LEM and TB16 on the


Figure 3.5 SLC Connections for LEM-320
XLS140-CPU. This system supports
either FlashScan or CLIP mode devices.
Refer to the SLC loop manual for wiring requirements and specific details.

LEM-320 XLS140-CPU
Stacker-connector

J3

J1

The short-pin end plugs


directly into the top of the
XLS140-CPU plug.

The long-pin end


plugs into the back
of the LEM board.

CAUTION:
! If the stacker-connector is installed incorrectly, the short-pin end of the plug can fail to make a secure
connection when plugged through the back of the LEM.

Figure 3.6 Mounting LEM-320 with the Stacker-connector

36 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Installing the Control Panel Installation

3.5.4 Network Control Module


If networking two or more control panels (including XLS-NCAs), each unit requires a Network
Control Module (NCM); wire and fiber versions are available. The NCM-W/F can be installed in
any panel circuit module position (see Section 3.5.5 “Panel Circuit Modules and Other Option
Boards”); the default position is immediately to the right of the control panel.
1. Mount the NCM in the selected position. If another board is going to be mounted in the slot
immediately in front of it, use stand-offs provided with the next board to secure it in place.
Otherwise use the screws provided with the NCM.
2. Connect J1 on the control panel to J3 on the NCM using the network cable provided (P/N
75556) as described in the NCM Installation Document. Do not connect two NCMs via NUP
ports (NUP to NUP).
3. Connect Channel A and/or Channel B as described in the NCM Installation Document.

NOTE: See the XLS-NET Manual and NCM Installation Document for wiring diagrams and
system configuration information. See the BMP-1 Product Installation Drawing if considering
mounting the module behind blank module plate in a dress plate or annunciator backbox.

3.5.5 Panel Circuit Modules and Other Option Boards


If installing option boards into a CAB-4 Series backbox, mount and connect those boards at this
time. General instructions follow; the sections about individual option boards contain any
module-specific instructions. Option boards can be mounted in the front (fourth) layer of CHS-M2
(see flanges as shown in Figure 3.4), or in any position on the other row(s) of equipment, using
0.937" (23.8 mm) standoffs between layers.

NOTE: An option board can be mounted above a Loop Expander Module or Network Control
Module; for ease of access, be sure to complete installation of those devices before mounting a
second layer.

1. Slide the tabs at the bottom of the option board into slots on the chassis as shown in Figure 3.7.
2. Lay the board back onto the flanges so that the studs line up with mounting holes on the option
board.
3. Attach the option board using screws provided with the module.

NOTE: See the BMP-1 Product Installation Drawing for details if considering mounting the
module behind blank module plate in a dress plate or annunciator backbox. This dress plate is
suitable for modules that do not need to be visible or accessible when the door is closed.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 37


Installation Installing the Control Panel

Module
Screw

Slots

nfs640-mnticm.cdr
Shown with CHS-M2 Shown with CHS-4N

Figure 3.7 Inserting a Module into a Chassis

Chassis CHS-4N

Install stand-offs on these


two (2) studs in any one of
four positions along chassis.
CHS-4studpos.cdr

Figure 3.8 Location of Stand-offs on Module Chassis

Mount single-space blank plate


onto compatible dress panel or
backbox trim ring
tm4adp4.cdr

Single-space
blank plate

Mount optional module


onto standoffs on the
blank plate

Fasten optional module to


the plate with four screws
(included).

Figure 3.9 Mounting Single-space Blank Plate with Optional Module

38 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Connecting the Power Cables Installation

3.6 Connecting the Power Cables


WARNING:
! Remove all power sources to equipment while connecting electrical components. Leave the
external, main power breaker OFF until installation of the entire system is complete.

WARNING:
! Several sources of power can be connected to the control panel. Before servicing the control panel,
disconnect all sources of input power including the battery. While energized, the control panel and
associated equipment can be damaged by removing and/or inserting cards, modules, or
interconnecting cables.

3.6.1 Overview
Complete all mounting procedures and check all wiring before applying power. Electrical
connections include the following:
• Primary AC power source – 120 VAC, 50/60 Hz, 3.0 A (XLS140E uses 240 VAC, 50/60 Hz,
1.5 A) from line voltage source. Overcurrent protection for this circuit must comply with
Article 760 of the National Electrical Code (NEC) and/or local codes. Use 12 AWG (3.31
mm2) wire (maximum) with a 600-volt rating.
• Secondary power source – 24 VDC from batteries, installed in the control panel (or in an
optional battery cabinet). Secondary (battery) power is required to support the system during
loss of primary power.
• External power sources – 24 VDC power for Smoke Detectors (4 wire), NACs, and
Annunciators.
See Appendix B “Electrical Specifications” for details and overall installation guidelines.

3.6.2 Connecting the Control Panel to AC Power


Connect primary power as follows (see Figure 3.10 below):
1. Turn off the circuit breaker at the main power distribution panel.
2. Remove the plastic insulating cover from TB2.
3. Connect the service ground to terminal marked EARTH.
4. Connect the primary neutral line to terminal marked NEUTRAL and the primary Hot line to
terminal marked HOT.
5. Reinstall the plastic insulating cover over TB2.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 39


Installation Connecting the Power Cables

TB2

Hot

EARTH NEUTRAL HOT


Neutral

Ground
(Earth)

Battery (-)

BATT –

nfs640-acdc.cdr
Battery (+)

BATT+
TB1

Figure 3.10 AC & DC Power Connections

3.6.3 Checking AC Power


Table 3.3 contains a checklist for checking the system with AC power applied:

CAUTION:
! While checking AC power, make sure batteries are not connected.
Follow the sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is Step 16.

Component Status
Control panel circuit The green AC Power indicator on; the system Trouble indicator on because batteries are not connected.
board
Each panel circuit The yellow Trouble indicator may come on for approximately 10 seconds after applying AC power. (This
module only applies to an unconfigured system.)
Each auxiliary power The yellow Trouble indicator comes on because batteries are not connected.
supply

Table 3.3 AC Power Checklist

3.6.4 Installing and Connecting the Batteries


w

WARNING:
! Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy
fabrics. If contact is made with sulfuric acid, immediately flush skin or eyes with water for 15 minutes
and seek immediate medical attention.

WARNING:
! Do not connect the Battery Interconnect Cables (P/N 75560 and 75561) at this time. Make this
connection AFTER initial system primary powerup. Follow sequence of steps in Section 3.2
“Installation Checklist”, Table 3.1; this is Step 17.

Batteries (2) are installed in the control panel cabinet or in a separate battery cabinet which can be
mounted below the control panel or up to 20 feet (6.096 m) away from the control panel, in conduit
in the same room.
Connect the battery as follows (see Figure 3.10 above):
1. Install batteries (2) into bottom of cabinet or into separate battery cabinet.
2. Connect the red cable from TB1(+) on the control panel to the positive (+) terminal of one
battery.

40 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Connecting the Power Cables Installation

3. Connect the black cable from TB1(–) on the control panel to the negative (–) terminal of the
other battery.
4. Connect the remaining cable between the negative (-) terminal on the first battery to the
positive (+) terminal on the second battery.

3.6.5 APS-6R Auxiliary Power Supply Connections


If an optional APS-6R power supply is installed in the cabinet, connect it with no power applied;
follow sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is Step 4. For all
information pertaining to these connections see the APS-6R Instruction Manual.

3.6.6 External DC Power Output Connections


Terminal TB7 provides two (2) power outputs, resettable and non-resettable. Each output is
power-limited. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is
part of Step 6.

Non-resettable Resettable
Power Power

+ – + –
TB7

nfs640-dcout.cdr
Figure 3.11 Power Supply DC Outputs - TB7

24 VDC Resettable Power Circuit (Four-Wire Smoke Detectors). The power supply
provides a single 24 VDC filtered, power-limited, resettable power circuit for devices that require
resettable power (such as four-wire smoke detectors). This circuit is power-limited, but must be
supervised. To provide supervision, install a UL-listed end-of-line power supervision relay (such as
the EOLR-1) after the last device. Connect the power supervision relay normally open contact in
series with an Initiating Device Circuit (IDC). The four-wire power circuit energizes the power
supervision relay. When you reset the system, the control panel removes power from these
terminals for approximately 15 seconds.
Connect external field wires to the power supply terminals TB7 RESET(+) and (–) to provide up to
1.25 A of current for powering four-wire smoke detectors. See Figure 3.11 above.
24 VDC Non-resettable Power Circuit. The power supply provides one 24 VDC filtered,
power-limited, non-resettable power output, capable of up to 1.25 A. Use this circuit to power
devices that require low-noise 24 VDC power (such as annunciators or the TM-4).
Connect external field wires to power supply terminals TB7 NONRST(+)and(–) to provide up to
1.25 A of non-resettable current for powering external devices such as annunciators. See
Figure 3.11 above.

CAUTION:
! During system reset, power remains at terminals TB7 NONRST(+)and(–).

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 41


Installation NAC Connections & Releasing Circuits

3.7 NAC Connections & Releasing Circuits


The control panel provides four NAC terminals as shown in Figure 3.12. Each can be configured as
Style Y (Class B) or Style Z (Class A) as shown in Figure 3.13. Each circuit can provide 2.5 A of
current, but the total current drawn from the main power supply cannot exceed 6.0 A in alarm
condition (refer to Table A.2). NAC circuits are supervised and power-limited. Use UL-listed
24 VDC notification appliances only (refer to the Device Compatibility Document).

UL-listed ELR-2.2K,
1/2 W (supplied)
B+ B- A+ A-

TB6 - NAC#1
B+ B- A+ A-

TB5 - NAC#2

nfs640-nacout.cdr
B+ B– A+ A– B+ B– A+ A– B+ B– A+ A–
B+ B- A+ A-

TB4 - NAC#3
nfs640-NACS.cdr

Unused Circuits Style Y (Class B) Style Z (Class A)


B+ B- A+ A-

TB3 - NAC#4 Connection Connection

Figure 3.13 Notification Appliance Circuit


Figure 3.12 NAC Terminals Connections

NOTE: Any NAC can be programmed as a releasing circuit, but only one releasing device
per circuit is allowed. For more information, refer to Section 4.5 “Releasing Applications” in this
manual and the XLS140 Programming Manual. Refer to the Device Compatibility Document for
UL-listed compatible releasing devices. Sample connections for NAC terminals are shown in
Figure 3.13. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is part
of Step 6.

3.8 Output Relay Connections


The panel provides a set of Form-C relays. These are rated for 2.0 A at 30 VDC (resistive):
• Alarm - TB8
• Trouble - TB9
• Supervisory - TB10
• Security - TB11
The Supervisory and Security contacts can also be configured as Alarm contacts by setting
switches SW1 and SW5 away from the factory default positions shown in Figure 3.14. Follow
sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is part of Step 6.

42 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Backup-Alarm Switches Installation

ALARM RELAY TROUBLE RELAY SUPERVISORY RELAY SECURITY RELAY


NO NC C NO NC C NO NC C NO NC C

TB11
SW1 is set to Supervisory
TB8 TB9 TB10 SW1 SW5 SW5 is set to Security
Move switch to opposite
SUPV ALARM SECUR ALARM position to set to Alarm.

nfs640-relay.cdr
Figure 3.14 Form-C Relay Connections

3.9 Backup-Alarm Switches


WARNING:
! Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!

Backup alarm switches are provided that enable NACs 1 NAC 3


and the alarm relay to activate during a backup alarm

SW6

DISAB ENAB
condition. If the main board’s microcontroller fails and

SW8
an alarm is reported by any detector or a monitor 2 4

SW9
module that has backup reporting enabled, the NAC

SW7
will turn on if the corresponding switch was enabled.
The alarm will activate during microcontroller failure

nfs640-sw6-9.cdr
regardless of the settings of Switch 6-9.
• Switch 6 - NAC#1
• Switch 7 - NAC#2
Figure 3.15 Backup Alarm
• Switch 8 - NAC#3 Switches
• Switch 9 - NAC#4
So, for example, if Switch 6 and Switch 8 were enabled at the time of an alarm during
microcontroller failure, NAC#1 and NAC#3 would activate. Follow sequence of steps in Section
3.2 “Installation Checklist”, Table 3.1; this is Step 7.

3.10 Installing a Transmitter Module TM-4


TM-4 is power-limited. Connections are on TB7 nonresettable output and TB13 EIA-485 ACS
Mode. Refer to the Transmitter Module TM-4 installation document for installation details.

3.11 UL Power-limited Wiring Requirements


Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25 inches (6.35 mm) from any
nonpower-limited circuit wiring. All power-limited and nonpower-limited circuit wiring must enter
and exit the cabinet through different knockout and or conduits. To maintain separation, group
non-power limited modules together, i.e., group modules on the same side of the enclosure or in
separate rows.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 43


Installation Installing Panel Circuit Modules

Figure 3.16 shows one configuration that meets these UL requirements. The first two rows of
modules are configured with at least a 0.25 inch (6.35 mm) separation between power-limited and
nonpower-limited wiring; AC and battery wiring is routed away from power-limited wiring.

Power-limited Circuits

Nonpower-
limited Power-limit
circuits ed
circuits

nfs640-pwrlmtwir.cdr
To cabinet-mounted battery

Figure 3.16 Typical Wiring for UL Power-limited Wiring Requirements

NOTE: AC and battery wiring are not power-limited. Maintain at least 0.25 inches (6.35 mm)
between power-limited and non power-limited circuit wiring. Install tie wraps and adhesive squares
to secure the wiring. Use a power-limited source for relay output on terminals TB8 – TB11.

3.11.1 Labeling Modules and Circuits


At the time of installation, each nonpower-limited circuit connected to ACM-8R, ARM-4,
CRM-4RK, CRE-4, and LDM-R32 modules must be identified in the space provided on the cabinet
door label when connected to a non-power-limited source of power.
The label lists all compatible power-limited modules and circuits; also see Figure 2.3 at the start of
this manual.
The following devices are power-limited only when connected to power-limited sources: ARM-4,
CRM-4RK, CRE-4, LDM-R32. When one of these devices is connected to a non-power-limited
source, the power-limited marking must be removed.

3.12 Installing Panel Circuit Modules


3.12.1 Overview
Installation of a panel circuit module is divided into five (5) operations:
• Mounting an optional expander board to the module (e.g. mounting ICE-4 onto an ICM-4RK).
• Connecting communication ribbon cables from Control Panel to the module.
• Installing the module onto a chassis.
• Connecting modules to the power supply.
• Field wiring the module.

44 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Installing Panel Circuit Modules Installation

Refer to Section 2.10 “Panel Circuit Modules” for a complete list of modules and their expanders.

3.12.2 Mounting Expander Boards


Expander Board Modules, such as ICE-4 or CRE-4, need to be mounted onto their respective
modules (ICM-4RK, CRM-4RK) prior to installation onto a chassis. Figure 3.17 illustrates the
steps to mount an Expander Module:
1. Remove one module support screw and set it aside for later use.
2. Replace the module support screw with one module stand-off.
3. Repeat Steps 1 and 2 for the three remaining module support screws.
4. Insert pins on the front of the expander board into connector on the back of the module. Make
sure the pins are in line; then, press the two units together until they snap into place.
5. Install the four module support screws (removed earlier) through the back of the expander
board and into the stand-offs. Tighten securely.
Remove existing
module support Install module
screw stand-off

Steps 1 & 2

Plug in the expander board

Secure with module


support screws

nfs640-pcmods.cdr

Steps 4 & 5

Figure 3.17 Expander Module Installation

3.12.3 Connecting Ribbon Cables for a CAB-4 Series Backbox


Expander Row Ribbon Cables connect panel circuit modules to the Control Panel.
Figure 3.18 shows a typical wiring setup using two Expander Row Ribbon Cables (P/N 71088) to
connect the control panel to two rows of four (4) panel circuit modules each below the Control
Panel in a CAB-4 Series backbox.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 45


Installation Installing Panel Circuit Modules

J6 - Third Row J5 - Second Row

Expander Row Ribbon Cable (P/N 71088)

MODULE MODULE
TYPE TYPE
LAMPS LAMPS MODULE MODULE MODULE MODULE MODULE MODULE
TYPE TYPE TYPE TYPE TYPE TYPE
SWITCH SWITCH
LAMPS LAMPS
LAMPS LAMPS LAMPS LAMPS
SWITCH SWITCH
SWITCH SWITCH SWITCH SWITCH

Group of panel
modules in second
cabinet row

P1.1–P1.8 P2.1–P2.8 P3.1–P3.8 P4.1–P4.8

Expander Row Ribbon Cable (P/N 71088)

MODULE MODULE MODULE MODULE MODULE MODULE MODULE MODULE


TYPE TYPE TYPE TYPE TYPE TYPE

nfs640-icmribbon.cdr
TYPE TYPE
LAM PS LAMPS LAMPS LAMPS LAMPS LAMPS
LAM PS LAM PS
SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH
SWITCH SWITCH

Group of panel
modules in third
cabinet row

P5.1–P5.8 P6.1–P6.8 P7.1–P7.8 P8.1–P8.8

Figure 3.18 Expander Row Ribbon Cable Setup

3.12.4 Installing the Panel Circuit Modules


To install a panel circuit module such as the ICM-4RK or CRM-4RK into the chassis:
1. Angle the module into the chassis so that the lower board edge slips into the chassis slots as
shown in Figure 3.7.
2. Push the upper end of the module into the upper opening in the chassis.
3. Secure the module to the chassis with the two module screws (provided with the module).
Tighten securely.
4. Connect the Ribbon Cable to the module.

3.12.5 Connecting ICM-4RK and ICE-4 Modules


The total current available for any group of Notification Appliance Circuits (NACs), other than the
four NACs on the control panel, cannot exceed the following:
• 6.0 A when powered from the APS-6R
• 1.25 A when powered from a XLS140 DC power output terminal
Figure 3.19 shows the wire connectors on the bottom of the ICM-4RK and the ICE-4 modules.

46 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Installing Panel Circuit Modules Installation

ICM-4RK
J5

nfs640-icmconn.cdr
J6

J5
ICE-4
J6

Figure 3.19 ICM-4RK/ICE-4 Connectors

Power Supply Connections


Figure 3.20 illustrates typical connections from main power supply.

Bell power cable (P/N 75400) or Eight NACs that


alternate Power Harness (P/N 71093, with share 1.25 A
lugs removed and wires stripped)

Black wire (–), Blue wire (+) J5


ICM-4
J6
+ – + –
TB7

nfs640-icmnac.cdr
J5 ICE-4

24V NONRST 24V RESET Power Cable P/N 71091


TB7 on Control Panel

Figure 3.20 Main Power Supply Connection

Multiple Power Supplies


Cut JP1 and JP2 on ICM-4RK when supplying 24V power from two separate sources to the
ICM-4RK. ICM-4RK circuits 1-2 will receive their power from J5; ICM-4RK circuits 3-4 will
receive their power from J6.
Cut JP1 and JP2 on ICE-4 when supplying power from separate sources to expander circuits 5-8.
ICM-4RK circuits 5-6 will receive power from J5 on the ICE-4 and ICM-4RK circuits 7-8 will
receive power from J6 on the ICE-4.
See Figure 3.21 for jumper locations.

ICM-4RK/ICE-4 Jumpers
JP1
JP2
J5 J6

Two circuits that


APS-6R #1 J5 share 3 A of one
APS-6R (#1)
ICM-4RK
Two circuits that
J6
APS-6R #2 share 3 A of one
APS-6R (#2)

Figure 3.21 Sample ICM-4RK Configuration for Multiple Power Supplies

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 47


Installation Installing Panel Circuit Modules

3.12.6 Field-Wiring the ICM-4RK and ICE-4 (NFPA Style Y or Z)


Guidelines for field-wiring:
• Notification Appliance Circuits (NACs) are supervised, power-limited, and can connect to a
power-limited cable.
• Use only the compatible, UL-listed notification appliances listed in the Device Compatibility
Document.
• Wire notification appliances according to the manufacturer's instructions.
• Maximum current per circuit is 3.0 A. Maximum current per module depends on the type of
power supply (standard or auxiliary).
• Canadian installations require model N-ELR End-of-Line Resistor Assembly (Style Y only).
• Size NAC wiring so the voltage drop does not exceed the minimum rated voltage of the
notification appliance used as the last device on the circuit.
• For zone coded applications, refer to the UZC-256 Universal Zone Coder manual.
• The ICM-4RK is California Code programmable (microprocessor P/N 34077 Rev. B or
higher). To program for California Code, cut diode D35 as shown in Figure 3.23. (See
appendix section of the Programming Manual for more detail.)

Typical NFPA Typical NFPA


Style Y (Class B) NAC Style Z (Class A) NAC
4.7K,
1/2 watt ELR
P/N 71252
UL-listed 24 VDC
Polarized Devices

Jumpers for Jumpers for


unused circuits unused circuits

ICM4wire-YB.cdr
B+ A+ A– B– B+ A+ A– B– B+ A+ A– B– B+ A+ A– B–

Figure 3.22 Field-Wiring an ICM-4RK/ICE-4


icm-4rk-d35.cdr

Cut D35 on the circuit board to


produce California code.

Figure 3.23 Location of D35 on ICM-4RK Circuit Board

48 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Auxiliary Relay Module (ARM-4): Product-Specific Details Installation

3.12.7 Connecting CRM-4RK/CRE-4 Modules


Guidelines for field-wiring the CRM-4RK and the CRE-4:
• Form-C relay contacts (silver alloy) used for medium duty switching or pilot duty.
• Terminals will accept wire sizes from 12 AWG to 18 AWG (3.31 to 0.82 mm2).
• Activation of a module or expander relay occurs automatically when an alarm is detected on a
programmed IDC.
• UL contact ratings are 5 A at 125 VAC (resistive) or 30 VDC (resistive) and 2 A at 125 VAC
(inductive).
• For more information, refer to Section 3.11 “UL Power-limited Wiring Requirements”.
• For typical field-wiring connections, refer to Figure 3.24.

Optional CRE-4 Control


Relay Expander

CREEXPCO-RK.cdr
CONTROL CONTROL
RELAY RELAY

Typical connections for a


Form-C control relay in
normal position. CRM-4RK

Figure 3.24 Field-Wiring a CRM-4RK or CRE-4 Module

3.13 Auxiliary Relay Module (ARM-4): Product-Specific


Details
3.13.1 Overview
If a CRM-4RK/CRE-4 is to be incorporated into the control panel and an ARM-4 is being driven by
it, note the following:
• Each ARM-4 must be supported by one CRM-4RK or one CRE-4.
• If using ARM-4’s for both modules, mount two ARM-4’s in separate positions.
• If mounted in FACP enclosure keep all non-power limited wiring separate from power limited
wiring.
For ease of installation, service, and wiring mount the ARM-4 module in a position on the chassis
that will not have any other module or expander board in front of it. However, you can install the
ARM-4 directly behind the CRM-4RK or CRE-4.
ARM-4 mounts in the second, third or fourth row of a CAB-4 series backbox, against the back of a
chassis CHS-4 or CHS-4L. The ARM-4 may be mounted in any of the 8 adjacent backbox
positions the cable can reach.

3.13.2 Installation
To install the Auxiliary Relay Module in the chassis:
• Select a mounting position for the module on the chassis.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 49


Installation Auxiliary Relay Module (ARM-4): Product-Specific Details

• Install two (2) mounting stand-offs onto the studs of the chassis, at the selected location, as
shown in Figure 3.8 on page 38 and Figure 3.25. Tighten securely.
• Install three (3) support stand-offs, with screws, onto the PC board in the locations shown in
Figure 3.8 or in the two right-hand positions on the first row. Tighten securely.
• Position module over the stand-offs on the chassis; fasten the module to the chassis with the
two (2) retaining screws. Tighten securely.
• Connect one end of the Cable (P/N 71092) to plug P1 on the ARM-4.
Note: The other end of the cable is connected to jumper JP5 on the CRM-4RK or CRE-4.
• Connect all available external wiring at this time. Refer to Section 3.13.3 “Field Wiring an
Auxiliary Relay Module”.

Terminal
Assignments
(typ. 4 places)
NC NO C Com K1 K2 K3 K4 NC NO C
– + + + +

These 2 holes for These 3 holes for


mounting stand-offs. support stand-offs.
NC NO C NC NO C (Also see Figure 3.8
on page 38 for
chassis drawing.)

P2
P-1
Connection for
Cable P/N 71092 P1

ARM-4.cdr
Figure 3.25 ARM-4 Stand-off and Terminal Locations

3.13.3 Field Wiring an Auxiliary Relay Module


The figure above shows terminal assignments for ARM-4 module control relays K1-K4, which
control nonpower-limited circuits. Power-limited and nonpower-limited circuit wiring must remain
separated by at least 0.25 inch (6.35 mm) within the cabinet and exit the cabinet through different
knockouts, conduits, or both.

NOTE: For more information, refer to Section 3.11 “UL Power-limited Wiring Requirements”.

The table contains contact ratings for relays K1-K4 on the ARM-4 module:
Contacts
Resistive Load Normally Open (N.O.) Normally Closed (N.C.)
125 VAC 20 A 10 A
30 VDC 20 A 10 A

Table 3.4 Contact Ratings for K1-K4 on the ARM-4 Module

50 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Installing Remote Printers and/or CRT Installation

3.14 Installing Remote Printers and/or CRT


3.14.1 Custom Cable Fabrication
A custom cable needs to be fabricated to connect the PRN Printer, Keltron Printer or the CRT-2
Monitor to the system. Length of the cable will vary with each installation, but should not exceed a
maximum length of 20 feet (6.1 m). Printer must be installed in the same room as panel in conduit.
Construct cable as follows:
1. Using overall foil/braided-shield twisted-pair cable, properly connect one end to the DB-25
Connector using the wiring specifications shown in the table below. (Custom cable kit P/N
90106 is provided.)
2. Tighten clamp on connector to secure cable.
DB-25 Connector
TB14 on Control Panel
(Custom cable kit 90106)
Pin 3 TX
Pin 2 RX
Pin 7 REF

3.14.2 Installing and Configuring the PRN Series Printer


When connected to the Control Panel via an EIA-232 interface, the PRN prints a copy of all status
changes within the control panel and time-stamps the printout with the time of day and date the
event occurred. It provides 80 columns of data on standard 9" by 11" tractor-feed paper.

NOTE: You can also use the EIA-232 printer interface with UL-listed information technology
equipment, such as personal computers, to monitor the control panel for supplementary
purposes.

This section contains information on connecting a printer to the control panel and for setting the
printer options.
Connecting a Remote PRN Series Printer
Remote printers require a 120 VAC, 50/60 Hz primary power source. If required for the fire alarm
system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Because a secondary power source is not provided, use a
separate Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective Signaling. You
may use your building emergency power supply, so long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB14 terminal block on the control
panel as shown in Figure 3.26.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the remote printer.
Tighten securely.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 51


Installation Installing Remote Printers and/or CRT

Note: Outputs are


power-limited but
are not supervised.
DB-25 connector
on PRN series
printer (female
Terminate one end of
socket shown)
shield at backbox
PRINTER PC/CRT
TX RX REF TX RX REF

nfs640-prn5conn.cdr
Control Panel
TB14 TB15

Figure 3.26 Remote Printer Connections

Setting Printer Options


Refer to the documentation supplied with the PRN series printer for instructions on using the
printer menu controls. Set the printer options (under the menu area) according to the settings listed
in Table 3.5.
Option Setting Option Setting
Font HS Draft CPI 10 CPI
LPI 6 LPI Skip 0.5
ESC Character ESC Emulate Epson FX-850
Bidirectional Copy ON I/O
CG-TAB Graphic Buffer 40K
Country E-US ASCII Serial
Auto CR OFF Baud 9600 or 2400
Color Option Not Installed Format 7 Bit, Even, 1 Stop
Protocol XON/XOFF
Formlen
Character Set Standard
Lines 6LPI=60
Standard Exec 10.5 Sl.Zero On
Auto LF Off
PAPER
BIN 1 12/72"
BIN 2 12/72"
SINGLE 12/72"
PUSH TRA 12/72"
PULL TRA 12/72"
PAP ROLL 12/72"

Table 3.5 PRN Setup Options

3.14.3 Installing and Configuring a Keltron Printer


Connect the remote printer to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB14 terminal block on the control
panel as shown in Figure 3.27.
2. Connect DC power from TB7 terminal block on the control panel as shown in Figure 3.27.
3. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the Keltron printer.
Tighten securely.

52 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Installing Remote Printers and/or CRT Installation

Keltron printer
24 VDC
connections DB-25 connector
(14 AWG, on Keltron Printer
2.08 mm2) (female socket Terminate one end of
shown) shield at backbox

24V NONRST 24V RESET PRINTER PC/CRT


+ – + – TX RX REF TX RX REF

TB7

nfs640-keltconn.cdr
Control Panel

TB14 TB15

Figure 3.27 Keltron Printer Connections

Setting up the Keltron Printer


Set up a Keltron printer as follows:
1. The printer communicates using the following protocol:
• Baud Rate: 9600 • Parity: Even • Data bits: 7
2. Set the printer DIP switches SP1 and SP2 according to settings in Table 3.6.

SP1 On Off SP2 On Off


1 X 1 X
2 X 2 X
3 X 3 X
4 X 4 X
5 X 5 X
6 X 6 X
7 X 7 X
8 X 8 X

Table 3.6 Keltron DIP Switch Settings

3.14.4 Installing and Configuring a CRT-2


A CRT-2 can only be used in a non-networked application when used with the XLS140. For further
details on setting up the CRT-2, refer to the XLS140 Operations Manual.
Connect a CRT-2 to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB15 terminal block on the control
panel as shown in Figure 3.28.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the CRT-2. Tighten
securely.
3. Set parameters as discussed in Table 3.28.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 53


Installation Installing Remote Printers and/or CRT

DB-25 connector
on CRT-2 (female
socket shown) Terminate one end of
shield at backbox

PRINTER PC/CRT
TX RX REF TX RX REF
Control

nfs640-crt2conn.cdr
Panel

TB14 TB15

Figure 3.28 Connecting a CRT-2

Setting CRT-2 Parameters


The CRT-2 communicates with the control panel through a protocol defined by thirteen groups of
parameters. To access a parameter group, press the corresponding function key (F1-F12) as shown
in Table 3.7 below. You can then program parameters in each group.
Enter the CRT-2 setup menu by pressing and holding the <Ctrl> key while pressing the <Scroll
Lock> key. Use arrow keys to move through the selections in each setup group; press the space bar
to view the options for each parameter. When finished programming all setup groups, press the
<Pause> key. To save all changes, press <Y>.
Table 3.7 shows the standard settings for using the CRT-2 with the XLS140; for one instance where
these settings may change slightly see Section 3.14.6 “Connecting Multiple Printers, CRTs, or
CRT/PRN Combination”. The basic settings for using the CRT-2 with XLS140 are:
• Baud Rate 9600 • Data format 8 1 N • Protocol xon/off.

NOTE: This section covers installation only; for information on how the CRT-2 functions as part
of the fire alarm system, see the XLS140 Operations Manual.

Function Key CRT-2 Parameters


F1: Quick Emulation=CRT-2 EIA Baud Rate=9600 EIA Data Format=8/1/N
(“Read Status” key) Comm Mode=Full Duplex Aux Baud Rate=9600 Aux Data Format=8/1/N
Enhanced=On Language=U.S. Host/Printer=EIA/Aux
F2:Genrl Emulation=CRT-2 Enhanced=On Auto Wrap=Off
(“Alter Status” key) Auto Font Load=On Auto Page=Off Auto Scroll=On
Monitor Mode=Off Bell Volume=09 Warning Bell=On
Host/Printer=EIA/Aux
F3: Displ Page Length=24 Screen Length=26 Lines Screen Video=Normal
(“Prog” key) Display Cursor=On Cursor=Blink Line Auto Adjust Cursor=On
Columns=80 Width Change Clear=Off Speed=Normal
Scroll=Jump Refresh Rate=60 Hz Overscan Borders=Off
F4: Kybd Language=U.S. Char Set Mode=ASCII Key Mode=ASCII
(“Spl Funct” key) Keyclick=Off Key Repeat=Off Margin Bell=Off
Key Lock=Caps Keyboard Present=Yes
F5: Keys Enter Key=<CR> Return Key=<CR> Backspace=<BS>/<DEL>
(“Prior” key) Alt Key=Meta Disconnect=Pause Desk Acc=Disabled
Pound Key=U.S.
F6: Ports EIA Baud Rate=9600 EIA Data Format=8/1/N EIA Parity Check=On
(“Next” key) Aux Baud Rate=9600 Aux Data Format=8/1/N Aux Parity Check=On
EIA Xmt=Xon-Xoff EIA Recv=Xon-Xoff(XPC) EIA Xmt Pace=Baud
Aux Xmt=Xon-Xoff Aux Recv=Xon-Xoff(XPC) Aux Xmt Pace=Baud
EIA Break=Off EIA Modem Control=Off EIA Disconnect=2 sec
Aux Break=Off Aux Modem Control=Off Aux Disconnect=2 sec

Table 3.7 Standard CRT-2 Settings for Use with XLS140 (Sheet 1 of 2)

54 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Installing Remote Printers and/or CRT Installation

Function Key CRT-2 Parameters


F1: Quick Emulation=CRT-2 EIA Baud Rate=9600 EIA Data Format=8/1/N
(“Read Status” key) Comm Mode=Full Duplex Aux Baud Rate=9600 Aux Data Format=8/1/N
Enhanced=On Language=U.S. Host/Printer=EIA/Aux
F7: Host Comm Mode=Full Duplex Local=Off Recv <CR>=<CR>
(“Auto Step” key) Recv <DEL>=Ignore Send ACK=On Send Line Term=<CR><LF>
Send Block Term=<CR> Null Suppress=On
F8: Print Prnt Line Term=<CR><LF> Prnt Block Term=<CR> Secondary Recv=Off
(“Activ Signal” key)
F9: Emul Attribute=Page Bright Video=Off Page Edit=Off
WPRT Intensity=Dim WPRT Reverse=Off WPRT Underline=Off
WPRT Blink=Off Display NV Labels=Off Save Labels=On
Status Line=Off Fkey Speed=Normal
F10 Setup Group F10 does not affect communications with the control panel.
F11 Setup Group F11 does not affect communications with the control panel.
F12: Prog Program the function keys as follows: F1 ~A F2 ~B F3 ~C F4 ~D F5 ~E F6 ~F F7 ~G
(“Ack Step” key) F8 ~H F9 ~I F10 ~J F11 ~K F12 ~L F13 ~M F14 ~N F15 ~O F16 ~P Shift F13 ~Q

Table 3.7 Standard CRT-2 Settings for Use with XLS140 (Sheet 2 of 2)

3.14.5 Connecting a PC
A PC can be hooked up to the Control Panel EIA-232 port (J1) to allow the VeriFire Tools
programming utility to upload and download the operating program of the control panel. Refer to
the insert in the VeriFire Tools CD and to the program’s on-line help function for instructions.

NOTE: Download operations that change the basic program of the control panel must be
performed by responsible service personnel in attendance at the control panel. After downloading
a program, test the control panel in accordance with NFPA 72-1999.

3.14.6 Connecting Multiple Printers, CRTs, or CRT/PRN


Combination
Connecting multiple devices requires changing the CRT-2 setup using the F1(Quick) menu:
• Set Host/Printer=EIA/AUX.
• Set EIA Data Format=8/1/N.
• If the AUX device is a printer, set the Printer and AUX Data Format=7/1/E.
• If the AUX device is a second CRT-2, set the AUX Data Format=8/1/N.
Connect multiple devices as shown in Figure 3.29.
To Control Panel
TB15-REF
TB15-TX
7 3 2 7 3 2 TB15-RX

To AUX Port of CRT-2 To EIA-232 port of CRT-2


(female socket shown) (female socket shown)
prncrt-conn.cdr

7 3 2
To EIA-232 port of next
CRT-2 or PRN (female socket shown)

Note: For wire requirements, see Table B.1 in Appendix B “Electrical Specifications”.

Figure 3.29 Connecting Multiple Devices on the EIA-232 Circuit

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 55


Installation Wiring a Signaling Line Circuit (SLC)

3.15 Wiring a Signaling Line Circuit (SLC)


Overview
Communication between the control panel and intelligent and addressable initiating, monitor, and
control devices takes place through a Signaling Line Circuit (SLC). You can wire an SLC to meet
the requirements of NFPA Style 4, Style 6, or Style 7 circuits. This manual provides requirements
and performance details specific to this control panel; for installation information and general
information, refer to the SLC Wiring Manual.

Wiring

Maximum wiring distance of an SLC using 12 AWG (3.31 mm2) wire is 12,500 feet (3810 meters)
total twisted-pair for Style 4, Style 6 and Style 7 circuits.

Capacity
The XLS140 provides one (1) SLC, with a total capacity of 318 intelligent/addressable devices:
• 01-159 intelligent detectors
• 01-159 monitor and control modules
An optional expander board provides one (1) additional SLC, with the same capacity.

Installation
This control panel supports one or two SLC loops; a second SLC loop is obtained by installing an
LEM-320 module. SLC loop #1 connects to TB16 on the control panel; SLC loop #2 connects to
TB1 on the LEM-320. For details on designing, installing and configuring SLC loops, see the SLC
Wiring Manual.

SLC1
B+ A+ B- A-
B+ A+ B- A- TB1

TB16
SLC Loop #1 Connections SLC Loop #2 Connections
on FACP’s main circuit board on Loop Expander Module

SLC B SLC A

nfs640-slcloops.cdr, nfs640-slc-tb.cdr, LEM320-slc-tb.cdr

SLC B (output loop)

SLC A (loop return)

T-Tapping is not allowed


on a four-wire SLC.
Use either
B+ A+ B- A- SLC Loop #1 B+ A+ B- A-
or SLC Loop #2
Style 4 SLC Loops Style 6 SLC Loops

Figure 3.30 SLC Loop Connections and Wiring

56 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Notes

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 57


Installation Wiring a Signaling Line Circuit (SLC)

58 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Section 4: Applications

4.1 Overview

Chapter Covers the following topics


Section 4.2 “NFPA 72-1999 How to install UDACT with the control panel for use as a NFPA
Central or Remote Station Fire Central or Remote Station Fire Alarm System (Protected
Alarm System (Protected Premises Unit)
Premises Unit)”
Section 4.3 “NFPA 72-1999 How to set up a Protected Premises Unit to communicate with a
Proprietary Fire Alarm Systems” listed compatible Protected Premises Receiving Unit.
Section 4.4 “Fire/Security How to use the control panel as a combination Fire/Security
Applications” system, including the following:
• Installing a Security Tamper Switch into the cabinet
• Circuit Wiring
Section 4.5 “Releasing How to install the following releasing applications:
Applications”
• Releasing Device to the Control Panel (NAC integral circuits)
• Releasing Device to the XLS-CM-N/TC810N1013 Module
• NBG-12LRA Agent Release-Abort Station

Municipal Box (Auxiliary)


Municipal Box applications require a TM-4 Transmitter module. Refer to the Transmitter Module
TM-4 installation document for installation details.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 59


Applications NFPA 72-1999 Central or Remote Station Fire Alarm System (Protected Premises Unit)

4.2 NFPA 72-1999 Central or Remote Station Fire Alarm


System (Protected Premises Unit)
Figure 4.1 shows typical wiring diagram for a NFPA 72-1999 Central Station Fire Alarm System
(Protected Premises Unit) or a Remote Station Fire Alarm System (Protected Premises Unit) using
the Universal Digital Alarm Communicator/Transmitter (UDACT) and control panel. This
provides typical wiring only; connect and program the UDACT according to the directions given in
the UDACT Instruction Manual.

NOTE: An NFPA 72-1999 Central Station requires 24 hours of standby power; an


NFPA 72-1999 Remote Station requires 60 hours of standby power.

NOTE: This application can also be done with the TM-4 Transmitter; refer to the Transmitter
Module TM-4 document for more details.

Ferrite cores
FACP Cabinet P/N 29090

To supervised Solid earth


phone lines ground

24V NONRST 24V RESET EIA-485


+ – + – + ACS –
TB7

TB13

24 VDC EIA-485
Nonresettable power (ACS Mode)

Supervised and power-limited


EIA-485 and power wiring

nfs640-udact.cdr

UDACT in ABS-8R
(shown with cover removed)

Figure 4.1 Typical Wiring Diagram for a Central Station Fire Alarm System

NOTE: Install a UL-listed 120 ohm End-of-Line resistor (P/N 71244) UDACT TB1 terminals 3
and 4 if this is the last or only device on EIA-485 line.

60 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


NFPA 72-1999 Proprietary Fire Alarm Systems Applications

4.3 NFPA 72-1999 Proprietary Fire Alarm Systems


When connected and configured as a protected premises unit with UDACT, the XLS140 will
automatically transmit General Alarm, General Trouble, and General Supervisory signals to a listed
compatible Protected Premises Receiving Unit. See the UDACT Manual for compatible receiving
units. A simplified drawing of connections between a receiving unit and an XLS140 protected
premises unit is shown in Figure 4.2.
Connect the receiving unit to the protected premises unit as shown in Section 4.2 “NFPA 72-1999
Central or Remote Station Fire Alarm System (Protected Premises Unit)”.
For information on installing and programming the Receiving unit, refer to the documentation for
that control panel.

Telephone line & backup

UDACT

Compatible Receiving Unit


(see UDACT Manual) XLS140

XLS140
Protected Premises Unit

Figure 4.2 Typical Proprietary Fire Alarm Systems Wiring Connections

4.4 Fire/Security Applications


NOTE: XLS140 is not approved for use in security applications in Canada.

4.4.1 General Operation


The control panel can be used as a combination Fire/Security system when installed and operated
according to the instructions in this section.
For security applications, program one or more monitor modules (listed for security applications)
with the SECURITY Type Code, and wire as shown in Figure 4.4. Activating this type of module
lights the SECURITY LED, and displays a security alarm condition on the control panel LCD display.
The panel sounder will sound until the Security alarm is acknowledged. You can also program
additional sounders or output devices to activate with the security alarm initiating device. The
SECURITY Type Code is designed to indicate an alarm as follows: (a) on an open or short circuit; or
(b) on a ±50% change in resistance value from the End-of-Line resistor value.
A tamper switch installed in the cabinet door will indicate a door tamper condition whenever the
door is open. If the control panel indicates a Security alarm, you can acknowledge, silence, and
reset the condition from the control panel.
When the system resets, a 30-second exit timer starts. During this time the tamper switch and all
Security alarms are ignored. There is no entrance delay timer.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 61


Applications Fire/Security Applications

For bypass of security zones, use the DISABLE routine (covered in the Status Change section of
the XLS140 Operations Manual) for Security type devices.

WARNING:
! Damage can result from incorrect wiring connections.

4.4.2 Installing a Security Tamper Switch


To wire the cabinet with a Security Tamper Switch kit model STS-1, refer to Figure 4.3:
1. Install the STS-1 Tamper Switch onto the side of the backbox opposite the door hinge, pushing
the switch through the opening until it snaps into place.
2. Install the magnet on the same side of the cabinet door as the lock. Push the magnet through
the opening in the door until it snaps into place.
3. Connect the STS-1 connector to J10 (Tamper) on the Control Panel.

Connect to
J10 “Tamper”

STS-1 mounting location


(side opposite of door hinges)

nfs640-sts1.cdr

Figure 4.3 Installing the STS-1 Security Tamper Switch

4.4.3 Receiving Unit


For applications requiring transmission of security alarm information to a central receiving unit, the
control panel may be connected via a UDACT to a compatible receiving unit (see the UDACT
Manual). For information on configuring the Receiving unit for Combination Fire/Security
applications, refer to the documentation for that control panel.

62 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Fire/Security Applications Applications

4.4.4 Programming
The control panel can communicate with any number of security devices. To do so, program the
points as follows:
1. Select the address of the module(s) to be used for security.
2. Select the Type Code SECURITY.

NOTE: For detailed instruction on programming Type Codes, refer to the XLS140 Programming
Manual.

4.4.5 Wiring for Proprietary Security Alarm Applications


Table 4.4 shows typical wiring for proprietary security alarm applications with XLS-MM-A/
TC809A1059 modules. Note the following:
• The module is programmed with software SECURITY Type Code.
• Supplementary use only applies to UL-listed systems.
• NAC devices used for security cannot be shared with fire NAC devices.
• Refer to the Device Compatibility Document for compatible NAC devices.
• All monitor modules used for security application must be installed in the XLS140 cabinet
with STS-1 Security Tamper Switch.
XLS140 Protected Premises Unit

UL-listed 47K UL-listed,


End-of-Line Resistor normally-open
(provided with module) security switch
9 0
5
6 7 8 9 10
SLC
8
4 11 –
3
2
1 0 1514
12
13
1 Channel
7 TENS
6789
2 + A or B
5
6 4
3
3
2
10
5 ONES 4 nfs640-burg.cdr
LOOP ADDRESS

UL-listed, normally-closed
security switch
XLS-MM-A

(Note: TC809A1059 has same connections)

Figure 4.4 Wiring Diagram for Proprietary Security Alarm Applications

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 63


Applications Releasing Applications

4.5 Releasing Applications


WARNING:
! When used for CO2 releasing applications, observe proper precautions as stated in NFPA 12.
Do not enter the protected space unless physical lockout and other safety procedures are fully
completed. Do not use software disable functions in the panel as lockout.

WARNING:
! Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!

4.5.1 Overview
This control panel can be used for agent release or preaction/deluge control applications. In a
properly configured system with compatible, listed actuating and initiating devices, this control
panel complies with the following NFPA standards for installation in accordance with the
acceptable standard:
Standard Covers
NFPA 12 CO2 Extinguishing Systems
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam-Water Deluge and Foam-water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems

Table 4.1 NFPA Standards for Releasing Applications

4.5.2 Programming
The control panel supports up to ten releasing software zones. You can map these zones to activate
Control Panel releasing outputs and XLS-CM-N/TC810N1013 modules. Program the XLS-CM-N/
TC810N1013 module for the appropriate type code according to the chart below:

Type Code: RELEASE CKT Type Code: REL CKT ULC


• For use in UL applications. • For use in UL or ULC applications.
• Do not use REL device at the solenoid. • Requires REL device at solenoid.
• Cannot use power-limited wiring. • Power-limited wiring.
• Supervised for open circuit only. • Supervised for open circuit and shorts.
• Supervised for power loss with • Supervised for power loss with
power-supervision relay. power-supervision relay.

For more information, refer to the XLS140 Programming Manual.

4.5.3 Wiring
References to wiring diagrams for releasing applications:
To connect Refer to
A releasing device to the control panel. Section 4.5.4 “Connecting a Releasing Device to the Control Panel”.
A releasing device to the XLS-CM-N/ Section 4.5.5 “Connecting a Releasing Device to the XLS-CM-N/TC810N1013
TC810N1013 Module. Module”.
An NBG-12LRA Agent Release-Abort Station. Section 4.5.6 “Connecting an NBG-12LRA Agent Release-Abort Station”.

64 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Releasing Applications Applications

4.5.4 Connecting a Releasing Device to the Control Panel


Use TB3 (NAC#4), TB4 (NAC#3), TB5 (NAC#2), or TB6 (NAC#1) on the control panel for
NAC⁄Releasing Circuits. Only one listed, compatible releasing device can be installed per NAC.

B+ NAC/Releasing output (source)


B– NAC/Releasing output (source)
A+ Class A (return for NAC only)
A– Class A (return for NAC only)
Compatible UL-listed
24 VDC releasing device

nfs640-relconn1.cdr
+
REL-2.2K (Use with Type Code
Rel Ckt ULC, or see Circuit
Note: See text below for circuit requirements. Requirement 4.)

Figure 4.5 Typical Style 4 Connection of a Releasing Device to Control Panel

WARNING:
! Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!

Circuit Requirements. When connecting a releasing device, note the following:


1. The control panel provides four NAC/Releasing Circuits (Style Y or Z). Each circuit can
provide 2.5 A. Total current drawn from the power supply cannot exceed 6 A in an alarm
condition (refer to Table A.2, “System Draw Current Calculations,” on page 73). Use
compatible UL-listed 24 VDC appliances only. For more information on compatible
appliances, refer to the Device Compatibility Document.
2. Refer to the XLS140 Programming Manual for instructions on setting the Soak Timer.
3. For applications using power-limited circuits:
a) Use an in-line supervisory device (P/N REL-2.2K) with control panel releasing circuits.
Connect the End-of-Line device as shown in Figure 4.5.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts.
4. For applications not requiring power-limited circuits –
a) If the application does not require supervising the releasing device against shorts, in-line
supervisory devices (P/N REL-2.2K) are not required.
b) In non-power-limited applications, program the releasing circuit for Type Code
RELEASE CKT.
c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit
device wiring and any power-limited circuit wiring.)
5. The releasing circuit must be programmed with a releasing type code listed in the XLS140
Programming Manual.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 65


Applications Releasing Applications

4.5.5 Connecting a Releasing Device to the XLS-CM-N/


TC810N1013 Module
The module can control 1 A of current. Make sure to keep total system current within the limits of
the power supply. You can power the module from the power supply of the Control Panel or any
UL 864-listed 24 VDC regulated power-limited power supply for Fire Protective Signaling. For
more information, refer to the Device Compatibility Document.

SLC from FACP


or LEM-320
+

– +

Compatible UL-listed
24 VDC releasing device 9 0
6 7 8 9 10
5

8
4
3
11
12 1 Non-resettable
– 7
2
TENS
1 0 1514
13

2 24 VDC Power
6 7 8 9

6 4
5
3 –
Brown Red 3
+ 5
2
10
4
+

Relconn-fcm.cdr
REL-47K ONES
ADDRESS
LOOP
(Use with Type Code
Rel Ckt ULC, N.C. Supervision
or see Circuit
Relay Contact Power Supervision
Requirement 3.)
Part of EOLR-1 Relay (EOLR-1)
XLS-CM-N

Note: See text for circuit requirements.


SLC from FACP
or LEM-320
+ -
+

Compatible UL-listed
24 VDC releasing device 9 6789
0
5

8
4
3 1 Non-resettable
– 2
7 TENS07 8
1
2 24 VDC Power
6 9

6
5
-

Relconn-TC810a.cdr
Brown Red
4
3 3
+ 5
2
10
4
+
REL-47K LOOP
ONES
ADDRESS
(Use with Type Code
Rel Ckt ULC, N.C. Supervision
or see Circuit Power Supervision
Requirement 3.) Relay Contact
Relay (EOLR-1)
Part of EOLR-1 TC810N1013

Note: See text for circuit requirements.

Figure 4.6 Typical Connection of a 24 VDC Releasing Device to XLS-CM-N/TC810N1013 Modules

Circuit Requirements. When connecting a releasing device to the XLS-CM-N/TC810N1013


module, note the following:
1. Refer to the XLS140 Programming Manual for instructions on setting the Soak Timer.
2. For applications using power-limited circuits:
a) Use an in-line supervisory device (P/N REL-47K) with the XLS-CM-N/TC810N1013
module. Connect the in-line supervisory device as shown in Figure 4.6.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts.
3. For applications not requiring power-limited circuits:
a) in-line supervisory devices (P/N REL-47K) are not required; however, the releasing device
circuit is not supervised against shorts.
b) In non-power-limited applications, program the releasing circuit for Type Code
RELEASE CKT.

66 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Releasing Applications Applications

c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit.
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit
device wiring and any power-limited circuit wiring.

4.5.6 Connecting an NBG-12LRA Agent Release-Abort Station


SLC loop to
FACP or LEM-320
NBG-12LRA Manual Abort Yellow XLS-MM-B/
Black
See Document 51369 – TC809B1008 – –
for installation details.
Violet Red
+ + +

Manual Release Yellow Black


XLS-MM-A/
– TC809A1059 –

Violet Red
+ +
Normal Non-resettable +24 VDC
from main power supply
ELR mode R-47K Release
supervised and

NBG640-NBG12LRA.cdr

power-limited 1
XLS-CM-R/
6
TC810R1024
2 +
C.
5 4
N.C. N.O.
System
Common (–)
24 VDC power
from FACP’s
0
main power supply
24 VDC UL-listed 7- 1–
XLS-CM-N/
releasing device TC810N1013 2 +
6+ 3– –
Brown Red N.C. Supervision 4 +
REL-47K Relay Contact +
(use with Type Code
Rel Ckt ULC)
Power Supervision
Relay (EOLR-1)

Figure 4.7 Typical Connections for an NBG-12LRA Agent Release-Abort Station

NOTE: If using the on-board NACs, see Circuit Requirements for Section 4.5.4 “Connecting a
Releasing Device to the Control Panel” on page 65. If using XLS-CM-N/TC810N1013, see Circuit
Requirements for Section 4.5.5 “Connecting a Releasing Device to the XLS-CM-N/TC810N1013
Module” on page 66.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 67


Notes

68 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Section 5: Testing the System

5.1 Acceptance Test


When finished with the original installation and all modifications, conduct a complete operational
test on the entire installation to verify compliance with applicable NFPA standards. Testing should
be conducted by a factory-trained fire alarm technician in the presence of a representative of the
Authority Having Jurisdiction and the owner's representative. Follow procedures outlined in NFPA
Standard 72-1999, Chapter 7, Inspection, Testing and Maintenance.

5.2 Periodic Testing and Service


Periodic testing and servicing of the control panel, all initiating and notification devices, and any
other associated equipment is essential to ensure proper and reliable operation. Test and service the
control panel according to the schedules and procedures outlined in the following documents:
• NFPA Standard 72-1999, Chapter 7, Inspection, Testing and Maintenance.
• Service manuals and instructions for the peripheral devices installed in the system. Correct any
trouble condition or malfunction immediately.

5.3 Operational Checks


Between formal periodic testing and servicing intervals, the following operation checks should be
performed monthly, or more frequently when required by the Authority Having Jurisdiction.
Before proceeding: a) notify the fire department and the central alarm receiving station if
transmitting alarm conditions; b) notify facility personnel of the test so that alarm sounding
devices are disregarded during the test period; and c) when necessary, disable activation of
alarm notification appliances and speakers to prevent their sounding.
Disconnect all releasing devices to prevent accidental activation.

WARNING:
! Do not rely on disable/enable software settings to lockout releasing devices.

Check that the green POWER LED lights.


Check that all status LEDs are off.
Press and hold the LAMP TEST key. Verify that all LEDs and all LCD display segments work.
Activate an Initiating Device Circuit using an alarm initiating device or an addressable
initiating device on the SLC and check that all programmed active notification appliances
function. Reset the alarm initiating device, the control panel, and any other associated
equipment. In voice alarm applications, confirm that the proper tone(s) and/or messages sound
during alarm conditions. Select the paging function and confirm that the message can be heard
in the affected fire zones. Repeat the above step with each Initiating Device Circuit and each
addressable device.
On systems equipped with a fire fighter’s telephone circuit, make a call from a telephone
circuit and confirm a ring tone. Answer the call and confirm communication with the incoming
caller. End the call and repeat for each telephone circuit in the system.
Remove AC power, activate an Initiating Device Circuit through an alarm initiating device or
an addressable initiating device on the SLC, and check that programmed active notification
appliances sound, and alarm indicators illuminate. Measure the battery voltage with

Continued on next page...

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 69


Testing the System Battery Checks and Maintenance

notification appliances active. Replace any battery with a terminal voltage less than 21.6 VDC
and reapply AC Power.

NOTE: The battery test requires fully charged batteries. If batteries are new or discharged due
to a recent power outage, allow the batteries to charge for 48 hours before testing.

Return all circuits to their pretest condition.


Check that all status LEDs are off and the green POWER LED is on.
Notify fire, central station and/or building personnel when you finish testing the system.

5.4 Battery Checks and Maintenance


Maintenance-free sealed lead-acid batteries used in the system do not require the addition of water
or electrolyte. These batteries are charged and maintained in a fully charged state by the main
power supply's float charger during normal system operation. A discharged battery typically
charges at 1.5–1.8 A and reaches the float voltage of 27.6 VDC within 48 hours.
Sealed lead-acid batteries must be replaced within at most 5 years from their date of manufacture.
Minimal replacement battery capacity appears on the control panel marking label. Immediately
replace a leaking or damaged battery. You can get replacement batteries from the manufacturer.

WARNING:
! Batteries contain Sulfuric Acid which can cause severe burns to the skin and eyes and damage to
fabrics.

• If a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or
eyes with water for at least 15 minutes. Water and household baking soda provides a good
neutralizing solution for Sulfuric Acid.
• If Sulfuric Acid gets into eyes, seek immediate medical attention.
• Ensure proper handling of the battery to prevent short circuits.
• Take care to avoid accidental shorting of the leads from uninsulated work benches, tools,
bracelets, rings, and coins.

WARNING:
! Shorting the battery leads can damage the battery, equipment, and could cause injury to personnel.

On-board Memory-Backup Battery


A snap-in lithium battery on the CPU provides backup of the CPU’s on-board memory during
power loss. The expected shelf-life for this battery is 10+ years. However if battery connections
are damaged or the battery does lose power, a system trouble message will appear: “Bat. Backup
RAM”.

70 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Appendix A: Power Supply Calculations
Calculations must be done to determine standby and alarm DC current loads. Ampere-hour
requirements must be calculated as well to determine battery size.
The on-board power supply provides filtered 24VDC power that may be used for operating external
devices. Use Table A.2 to determine if external loading is within the capabilities of the power
supply.

A.1 Calculating AC Branch Circuit Current


Use Table A.1 below to determine the total amount of current, in AC amperes, that a 120 VAC, 50/
60 Hz service must be able to supply to the fire alarm system. Devices rated for 240 VAC operation
will draw approximately one-half the current listed in Table A.1.

Device Type No. of Devices Current (amps) Total Current


Main Power Supply [ 1 ] X 3.0 = 3.0
AA-30 [ ] X 1.00 =
AA-120 [ ] X 1.85 =
ACPS-2406 [ ] X 2.7* =
APS-6R [ ] X 2.5 =
CHG-120 [ ] X 2.0 =
Sum column for AC Branch Current required=amps

Table A.1 120 VAC Fire Alarm Circuit


* Separate calculations are required for any devices powered by the
ACPS-2406. It has its own integral battery charger and batteries can be
connected directly to it. Refer to the ACPS-2406 Installation Manual for its
battery calculations.

AC Branch Circuit Installation


For guidelines on wiring the AC branch circuit current, see “Operating Power: AC Branch Circuit”
on page 79 in Appendix B.1 “Electrical Specifications”.

A.2 Calculating the System Current Draws


The control panel’s main power supply must be able to power all internal system devices (and
several types of external devices) continuously during non-fire alarm conditions. Use column 1 in
Table A.2 to calculate the Non-Fire Alarm Load on the power supply regulator when applying
primary power. The main power supply must also provide a finite amount of additional current
during a fire alarm condition. Use column 2 in Table A.2 to calculate the additional current needed
during fire alarms. The requirements for non-fire alarm and fire alarm current loads cannot exceed
the capabilities of the power supply as listed below:
• 3 A at 24 VDC during Standby; and
• 6 A at 24 VDC during Alarm.
How to Use the Calculating Tables
As used in this section, “Primary” refers to the control panel’s on-board power supply, its primary
source of AC power. “Secondary” refers to the control panel’s backup batteries (or any other 24
VDC power supply listed for Fire Protective Signaling and connected in place of the batteries). The
term “standby” refers to the output current required when no fire alarm is present. The term “alarm”
refers to the output current required when a fire alarm is present.
The Primary Power Source Non-Alarm Current and Alarm Current columns are DC current
calculations. These calculations confirm that the power supply can provide enough current to
support the system during Primary Non-Fire Alarm and Fire Alarm conditions.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 71


Power Supply Calculations Calculating the System Current Draws

Quantities List the number of devices powered by the Panel Output (TB2) and the Accessories
Output (TB6). Devices powered by the Accessories Output draw current directly from the panel.
Devices powered by the Panel Output draw current through the fire panel’s connection to the power
supply. Use these quantities to calculate total current draw of each set of devices in calculation
columns 1, 2, and 3.
Calculation Column 1 (Primary, Non-Fire Alarm Current in amps) Add the contents of
calculation column 1 to get the current drawn from the power supply during a non-alarm condition,
with AC power applied. This current draw cannot exceed 3 A without an auxiliary power supply.
Calculation Column 2 (Primary, Fire Alarm Current in amps) Calculation column 2 lets
the system designer determine the current load that the power supply must support during a fire
alarm. The total current draw during a fire alarm cannot exceed 6 A without an auxiliary power
supply.
Typically, a system should contain capacity to activate all output circuits and relays, and support
fire alarms on no less than 10% of Initiating Device Circuits, subject to the requirements of the
Authority Having Jurisdiction (AHJ).
The Control Panel provides power for Notification Appliance Circuits. Refer to the Device
Compatibility Document for 24 VDC notification appliances that are UL- and ULC-listed for fire
alarm systems.
Calculation Column 3 [Secondary (Battery) Non-Alarm Current] Column 3 lets the
system designer calculate the non-fire alarm current drawn from the secondary source in a non-fire
alarm condition during AC power loss.The non-fire alarm current is required to complete the
standby battery calculations. After summing all current draws, insert the total in Table A.3.

72 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Calculating the System Current Draws Power Supply Calculations

Calculation Column 1 Calculation Column 2 Calculation Column 3


Category Primary, Non-Fire Alarm Primary, Fire Alarm Secondary, Non-Fire Alarm
Current (amps) Current (amps) Current (amps)
Qty X [current draw]= Total Qty X [current draw]= Total Qty X [current draw]= Total
XLS140-CPU/E 1 x [0.230] = 1 x [0.230] = 1 x [0.230] =
KDM-2 [ ] x [0.094]= [ ] x [0.094]= [ ] x [0.040]=
LEM-320 0/1 x [0.100]= 0/1 x [0.100]= 0/1 x [0.100]=
SLC loop*: 0/1/2 0/1/2 0/1/2
with jumper JP12 cut on CPU x [0.200]= x [0.200]= x [0.200]=
or without jumper JP12 cut on CPU x [0.400]= x [0.400]= x [0.400]=
XLS-NCA (back light on) [ ] x [0.400]= [ ] x [0.400]= [ ] x [0.400]=
NCM-W, NCM-F [ ] x [0.110]= [ ] x [0.110]= [ ] x [0.110]=
TM-4 [ ] x [0.110]= [ ] x [0.175]= [ ] x [0.110]=
DPI-232 (Refer to Doc. 51499) [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
APS-6R [ ] x [0.025]=
ACPS-2406 [ ] x [0.0013]=
ICM-4RK, ICM-4, CRM-4, CRM-4RK [ ] x [0.007]= [ ] x [0.072]= [ ] x [0.007]=
ICE-4 [ ] x [0.001]= [ ] x [0.065]= [ ] x [0.001]=
CRE-4 N/A x [0.065]= N/A
DCM-4RK, DCM-4 [ ] x [0.008]= [ ] x [0.080]= [ ] x [0.008]=
VCE-4 [ ] x [0.001]= [ ] x [0.040]= [ ] x [0.001]=
VCM-4RK, VCM-4 [ ] x [0.007]= [ ] x [0.040]= [ ] x [0.007]=
ARM-4 Auxiliary Relay [ ] x [0.146]=
AA-30 [ ] x [0.045]=
AA-100, AA-120 [ ] x [0.050]=
ACM-24AT [ ] x [0.016]= [ ] x [0.070]= [ ] x [0.016]=
ACM-48A [ ] x [0.016]= [ ] x [0.070]= [ ] x [0.016]=
AEM-24AT [ ] x [0.002]= [ ] x [0.056]= [ ] x [0.002]=
AEM-48A [ ] x [0.002]= [ ] x [0.056]= [ ] x [0.002]=
Maximum number of LEDs illuminated on [ ] x [0.0054]= [ ] x [0.0054]=
these annunciators during non-fire
conditions:
AFM-16AT, AFM-32A [ ] x [0.040]= [ ] x [0.056]= [ ] x [0.040]=
AFM-16A [ ] x [0.025]= [ ] x [0.065]= [ ] x [0.025]=
XLS-LCD-80 [ ] x [0.100]= [ ] x [0.100]= [ ] x [0.050]=
ACM-8R (refer to manual) [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
LDM (refer to Doc. 15885) [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
UZC-256 [ ] x [0.035]= [ ] x [0.085]= [ ] x [0.035]=
XLS-FDU-80 [ ] x [0.0643]= [ ] x [0.0643]= [ ] x [0.0643]=
AMG-1, AMG-E [ ] x [0.060]= [ ] x [0.060]= [ ] x [0.060]=
FFT-7, FFT-7S [ ] x [0.060]= [ ] x [0.120]= [ ] x [0.060]=
RM-1 [ ] x [0.020]= [ ] x [0.020]= [ ] x [0.020]=
XLS-MM-Z, TC841A1000/CDN [ ] x [0.0094]= [ ] x [0.090]= [ ] x [0.0094]=
XPIQ (Refer to Doc. 51013) [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
RPT-W, RPT-WF, RPT-F [ ] x [0.017]= [ ] x [0.017]= [ ] x [0.017]=
RPT-485W, RPT-485WF
RFX (Refer to Doc. 51012) [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
UDACT Communicator [ ] x [0.040]= [ ] x [0.100]= [ ] x [0.040]=
VEC-25/50 [ ] x [0.215]= [ ] x [1.215]= [ ] x [0.215]=
with optional FC-AAM25 [ ] x [0.245]= [ ] x [2.215]= [ ] x [0.245]=
Four-Wire Smoke Detectors† [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
[ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
Power Supervision Relay [ ] x [0.020]= [ ] x [0.020]= [ ] x [0.020]=
EOLR-1 or A77-716B
Notification Appliance powered from Main [ ] x[ ]=
Power Supply‡ [ ] x[ ]=
DHX-501, TC806D1018, TC806D1056/ [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
CDN (Duct Detectors with internal relays) [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
Refer to installation document
CHG-120 Battery Charger [ ] x [0.060]=
Local Energy Municipal Box [ ] x[ ]=
Compatable Devices not listed above** [ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
[ ] x[ ]= [ ] x[ ]= [ ] x[ ]=
Sum each column for totals Primary, non-alarm: Primary, alarm: Secondary, non-alarm:

Table A.2 System Draw Current Calculations


* Value represents an SLC’s maximum current draw. Refer to device datasheets for individual current draws. If jumper JP12 is cut, total device current cannot
exceed 200 mA; if jumper JP12 is not cut, total device current cannot exceed 400 mA.
† The total regulated load current supplied to four-wire smoke detector and power supervision relays cannot exceed 1.25 A.
‡ Enter the total notification appliance draw from the Main Power Supply, excluding the current from APS-6R supplies. Refer to Device Compatibility Document.
** Refer to manual and/or Device Compatibility Document.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 73


Power Supply Calculations Calculating the System Current Draws

A.2.1 Calculating the Maximum Secondary Power Fire Alarm


Current Draw
Use Table A.3 below to determine the maximum current requirements of secondary power source
during fire alarm conditions. The result obtained is the amount of current that the batteries must be
able to supply to the fire alarm system. Use the result in Table A.4 to determine the size of the
batteries needed for the fire alarm system.
Results taken from Table A.3 below assume that, while in a fire alarm condition, batteries must
feed the main power supply (and any additional supplies such as the APS-6R and AA-30) with the
maximum rated power each supply can provide.

Current
Device Quantity Total Current/Type
(in amps)

Alarm Current, from Table A.2, col 2 =

APS-6R* [ ] X 6 =

AA-30 [ ] X 3 =

AA-1202 [ ] X 7.3 =

Sum Column for Secondary Fire Alarm Load =

Table A.3 Maximum Secondary Power Fire Alarm Current Draw


* Actual load current may be used in place of maximum rated supply
current. To calculate actual load current, sum the current draws for each
appliance connected to APS-6R supplies.
† Exclude Amplifiers that are employed for backup.

NOTE: The Secondary Fire Alarm Load cannot exceed the following:
• 9 A with BAT-12120 batteries (12 V, 12 AH).
• 12 A with BAT-12250 batteries (12 V, 26 AH).
• 20 A with BAT-12550 batteries (12 V, 55 AH).

74 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Calculating the Battery Requirements Power Supply Calculations

A.3 Calculating the Battery Requirements


A.3.1 Calculating the Battery Capacity
Use this table to determine the battery capacity needed for the system:
Current (amps) X Time (hours) = AH
Secondary Non-Fire Alarm Current Required Secondary Non-Fire Alarm
(from column 3 in Table A.2) Standby Time (24 or 60 hours)

________________ X ________________ = _________AH


APS-6R Required Secondary Non-Fire Alarm
Standby Load Current Standby Time (24 or 60 hours)

________________ X ________________ = _________AH


Secondary Fire Alarm Load Required Fire Alarm Standby Time:
(from Table A.3) (for 5 minutes, enter 0.084; for 15
minutes, enter 0.25)

________________ X ________________ = _________AH


Sum Column for Total Secondary Amp Hours calculated = _________AH
Multiply by the derating factor x 1.2 (see Note 7) = _________AH
Battery Size – Total Secondary Amp Hours Required = _________AH
1. NFPA 72-1999 Local, Proprietary, and Central Station systems requires 24 hours of standby power
followed by 5 minutes in alarm.
2. NFPA 72-1999 Auxiliary and Remote Station Systems require 60 hours or standby power followed by
5 minutes in alarm.
3. Batteries installed in a system powered by an automatic starting engine generator need to provide at
least 4 hours of standby power.
4. Factory Mutual requires 90 hours of standby for deluge-preaction systems.
5. Emergency voice/alarm communications systems require 2 hours of operation in the alarm condition.
Due to the sporadic nature of voice operation, however, NFPA 72-1999 permits 15 minutes of operation
at a maximum connected load to equal 2 hours of normal use.
6. If the total exceeds 25 AH, the system requires a separate XLS-LBB battery enclosure for two
BAT-12550, 55 AH batteries in a separate XLS-LBB enclosure. If the total exceeds 55 AH, the system
requires an auxiliary battery charger with sufficient amp-hour capacity; this charger must be UL-listed for
Fire-Protective Signaling. If CHG-120 battery charger is used, it requires a second XLS-LBB enclosure.
7. The following battery derating factors must be used for Canadian installations using XLS140 charger:
• For a 12 AH battery, use derating factor of 1.2
• For a 25 AH battery, use derating factor of 1.5
• For a 55 AH battery, use derating factor of 1.8
When batteries are charged by CHG-120 charger use a derating factor of 1.2 for 25 AH and 55 AH
batteries.

Table A.4 Secondary Power Standby and Fire Alarm Load

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 75


Power Supply Calculations Calculating the Battery Requirements

A.3.2 Calculating the Battery Size


Use this table to choose the battery size, in amp-hours, needed to support the fire alarm system.
Select batteries that meet or exceed the Total Amp-Hours calculated in Table A.4 and that are
within the acceptable battery charger range (12-55 AH). Write the amp-hours requirements on the
Protected Premises label.
Voltage Number Part
Battery Size Backbox Size
Rating Required Number
12 AH 12 volts two BAT-12120 SBB-A4*, SBB-B4*,
SBB-C4*, SBB-D4*
25 AH 12 volts two BAT-12250 SBB-A4*, SBB-B4*,
SBB-C4*, SBB-D4*
55 AH 12 volts two BAT-12550 XLS-LBB*
* Red version available; add “R” to part number listed here

Table A.5 Selecting the Battery Size

76 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Appendix B: Electrical Specifications

B.1 Electrical Specifications


AC Power
Component Values
Main Power Supply 120 VAC, 50/60 Hz, 3.0 A; or
240 VAC, 50/60 Hz, 1.5 A
Wire size Maximum 12 AWG (3.31 mm2) with 600 VAC insulation

NOTE: If using an auxiliary power supply such as APS-6R, ACPS-2406, or audio amplifiers,
refer to the documentation for that equipment.

Batteries
The control panel uses only sealed lead-acid batteries for secondary standby power. Maximum
battery capacity for the control panel’s integral main power supply is 55 AH. Batteries larger than
25 AH require the XLS-LBB or other UL-listed battery cabinet. The table below contains
specifications for batteries that can be used with the control panel; see also Appendix A.3.2
“Calculating the Battery Size”:
Charger Description Specifications
Main Power Supply An internal battery charger for 12 Dual Rate: High Charge: 29.1 VDC
AH to 55 AH Normal Float Charge: 27.6 VDC
Charging Current: 2.0 A max (1.5 A typical)
CHG-120 An external battery charger Dual Rate: High Charge: 28.1 VDC
Battery Charger designed to charge lead-acid Normal Float Charge: 27.6 VDC
batteries between 25 AH and 120 Charging Current: 4.5 A
AH
ACPS-2406 An internal battery charger for Normal Float Charge: 27.6 VDC
Auxiliary Charger/ 7AH to 25 AH Charging Current: 1.1 A max (0.750 A typical)
Power Supply

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 77


Electrical Specifications Electrical Specifications

Signaling Line Circuit (SLC)


Item Value
Voltage 24 VDC nominal, 27.6 VDC maximum
Maximum length 12,500 ft. (3810 m) per channel (NFPA Style 4) or 10,000 ft. (3048 m) total
loop or circuit length (NFPA Style 6 and 7)
Note: Refer to Appendix B.2 “Wire Requirements” for limitations.
Maximum current 400 mA peak, 200 mA average (max short circuit; circuit will shut down until
short is fixed)
Maximum resistance 50 ohms (supervised and power-limited)

Notification Appliance Circuits & Releasing Circuits


Item Value
Max. wiring voltage drop 2 VDC (except CMX which is 1.2 VDC)
Nominal operating voltage 24 VDC
Current for all external 6.0 A in alarm (3 A continuous)
devices connected to the
control panel’s power supply
Optional ACPS-2406 Total 6 A in alarm (5 A continuous)
Optional APS-6R Total 6 A in alarm (4 A continuous)
Maximum signaling current/ 2.5 A
circuit per NAC Note: Some devices have maximum draws less than this; refer to the device’s
documentation.
End-of-Line Resistors Control Panel NACs (TB3, TB4, TB5, TB6): 2.2K, 1/2 watt
(ELRs) ICM-4RK, ICE-4, VCM-4RK, VCE-4, and DCM-4RK: 4.7K,
1/2 watt (2 watts on 70 Vrms audio)
XP6-C, XLS-CM-N/TC810N1013 Modules: 47K, 1/2 watt

Output Relays
Output relays for Alarm, Trouble, Supervisory, and Security are available on power supply
terminals TB8, TB9, TB10, and TB11 respectively.
Contact ratings: 2.0 A @ 30 VDC (resistive)
Four-wire Smoke Detector Power
Control Panel terminals TB7 RESET (+) and (–) supply filtered, low-noise power for four-wire
smoke detectors. Specifications are:
• Nominal voltage: 24 VDC
• Maximum rated current: 1.25 A DC
• Maximum ripple voltage: 176 mVrms
Refer to the Device Compatibility Document for compatible 24 VDC detectors.
Power Output
Control Panel terminals TB7 NONRST (+) and (–) supply one (1) power-limited circuit available
to power external devices, such as notification appliances and annunciators.
• Nominal voltage: 24 VDC
• Maximum rated current: 1.25 A DC
• Maximum ripple voltage: 176 mVrms
Refer to the Device Compatibility Document for compatible devices and notification appliances.

NOTE: The Control Panel provides a total of 6.0 A of power in alarm (3 A in standby), shared by
all internal circuitry and external provisions (24 V resettable and non-resettable). For power
requirements, refer to the power supply calculation tables in Appendix A.

78 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Wire Requirements Electrical Specifications

Operating Power: AC Branch Circuit


The control panel requires connection to a separate dedicated AC branch circuit. Follow these
guidelines when connecting the AC branch circuit:
• Label the branch circuit “Fire Alarm”. This must be a separate dedicated AC fire alarm circuit.
• Connect the branch circuit to the line side of the main power feed of the protected premises.
• Do not power other equipment from the fire alarm branch circuit.
• Run the AC branch circuit wire continuously, without any disconnect devices except for
overcurrent protection, from the power source to the fire alarm control panel.
• Overcurrent protection for the AC branch circuit must comply with Article 760 of the National
Electrical Codes, as well as local codes.
• Use 12 AWG (3.31 mm2) wire with 600 VAC insulation for the AC branch circuit.
Connect the ground terminal (TB2-Earth) to a solid earth ground (a metallic, cold water pipe may
be suitable in some installations). This connection is vital to maintaining the control panel's
immunity to unwanted transients generated by lightning and electrostatic discharge.
Operating Power: Secondary Power Source (Batteries)
The battery charger is current-limited and can recharge sealed lead-acid type batteries. The battery
charger shuts off when the control panel is in alarm.

B.2 Wire Requirements


Each type of circuit within the Fire Alarm Control System requires use of a specific wire type to
ensure proper circuit operation. The wire gauge of a particular circuit depends on the length of that
circuit and the current traveling through it. Use Table B.1 below to determine the specific wiring
requirements for each circuit.
Compliance with the Federal Communications Commission (FCC) and Canadian Department of
Communication regulations on electrical energy radiation requires the following: Use twisted-pair
shielded wire for any non-SLC-loop wiring entering or exiting the cabinet that is not enclosed in
conduit. Use twisted-pair unshielded wiring for SLC-loop wiring.

NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce
problems by exclusively using electronic sounders (such as the Spectralert or MA/SS-24 Series)
instead of more electronically noisy notification appliances (such as electromechanical bells or
horns).

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 79


Electrical Specifications Wire Requirements

Circuit Distance
Circuit Type
Function
Wire Requirements
(feet/meters) Typical Wire Type*

SLC Connects to Twisted-unshielded pair, 12 to 18 AWG 12,500 ft. (3,810 m) 12 AWG (3.31 mm2)
(power limited) intelligent and (3.31 to 0.82 mm2). 50 ohms maximum per 9,500 ft. (2,895.6 m) 14 AWG (2.08 mm2)
addressable length of Style 6 & 7 loops. 50 ohms per 6,000 ft. (1,828.8 m) 16 AWG (1.31 mm2)
modules. branch maximum for Style 4 loop. 3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)

or Untwisted, unshielded wire, in conduit or 1,000 ft. (304.8 m) 12 to 18 AWG (3.31 to


outside of conduit. 0.82 mm2)

Note: Maximum total capacitance of all


SLC wiring (both between conductors and
from any conductor to ground) should not
exceed 0.5 mircofarads.

EIA-485 Connects to Twisted-shielded pair with a characteristic 6,000/1829 16 AWG (1.31 mm2)
(power limited) XLS-LCD-80, impedance of 120 ohms. 18 AWG (0.82 (max)
ACS modules, mm2) minimum.
or TM-4
Transmitter

EIA-232 Connects to Twisted-shielded pair in conduit. 50/15.24 16 AWG (1.31 mm2)


(power limited) Printers, CRT, 18 AWG (0.82 mm2) minimum. (without modem)
or PC.

IDC XLS-MM-A/ 12-18 AWG (3.31 to 0.82 mm2). 12 to 18 AWG (3.31 to


Initiating Device TC809A1059, Maximum circuit resistance is 20 ohms. 0.82 mm2)
Circuit XLS-MM-B/
TC809B1008,
XP5-M,
XP10-M,
XP6-MA
(power limited)

NAC XLS-CM-N/ 12-18 AWG (3.31 to 0.82 mm2). To meet 1.2 V drop, 12 to 18 AWG (3.31 to
Notification TC810N1013, At alarm current level, no more than a 1.2 or sized to provide 0.82 mm2)
Appliance XP6-C (power V drop at the end of the circuit, or sized to the minimum rated
Circuit limited) provide the minimum rated operating operating voltage of
voltage of the appliances used. the appliances used.

24 VDC Power To TM-4 12-18 AWG (3.31 to 0.82 mm2). To meet 1.2 volt drop 12 to 18 AWG (3.31 to
Runs Transmitter, Size wire so that no more than 1.2 V drop 0.82 mm2)
(power-limited) Annunciator and across wire run from supply source to end
XLS-CM-N/ of any branch.
TC810N1013
modules

CHG-120 External battery 12 AWG (3.31 mm2) in conduit 20/6.1 (max) 12 AWG (3.31 mm2)
charger

Table B.1 Wire Requirements


* Notifier brand cable is recommended; see the product catalog available from Paige Electric.

NOTE: Lightning arresters required on circuits extending between buildings; 999 meter length
maximum to meet UL 1459.

80 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Appendix C: Compatible Equipment
These are the most common devices at time of publishing; the most complete list of compatible
intelligent SLC loop devices is provided in the SLC Wiring Manual; for conventional
non-addressable equipment see the Device Compatibility Document.
Honeywell and Notifier Equipment
AA-30 30-Watt Audio Amplifier TR-B4 B-sized trim ring
AA-100 100-Watt Audio Amplifier TR-C4 C-sized trim ring
AA-120 120-Watt Audio Amplifier TR-D4 D-sized trim ring
XLS-ABF-1B Annunciator Flush Box CCM-1 Communication Converter Module
XLS-ABF-1DB Annunciator Flush Box with Door CHS-4L Chassis for voice equipment
XLS-ABF-2B Annunciator Flush Box CHS-M2 Chassis for 1st row (included in basic equipment
XLS-ABF-2DB Annunciator Flush Box with Door package)
XLS-ABF-4B Annunciator Flush Box CHS-4MB Assembly: CHS-4N with MP-1B
ABF-4DB Annunciator Flush Box with Door CHS-4N Chassis for 2nd, 3rd, 4th rows
ABM-16AT Annunciator Blank Module CHG-120 Battery Charger
ABM-32A Annunciator Module Blank XLS140-CPU/E control panel circuit board
XLS-ABS-1TB Annunciator Surface Box TC807A1036 Ionization Smoke Detector
ABS-1B Annunciator Surface Box TC807B1000 Intelligent Ionization Smoke Detector
ABS-2B Annunciator Surface Box CRE-4 Control Relay Expander
XLS-ABS-4B Annunciator Surface Box CRM-4RK Control Relay Module
ABS-8R Annunciator Backbox for ACM-8R CRT-2 Video Display Monitor with Keyboard
ACM-24AT Annunciator Control Module DCM-4RK Dual Channel Module
ACM-48A Annunciator Control Module DP-1B Blank Dress Plate
ACM-8R Annunciator Control Module DP-DISP Display Dress Plate
ACPS-2406 Auxiliary Charger/Power Supply DPDW-1B Double Well Dress Plate
ACT-1 Audio Coupling Transformer DPSW-1B Single Well Dress Plate
ACT-2 Audio Coupling Transformer DPI-232 Direct Panel Interface
ADP-4B Annunciator Dress Panel XLS-CM-N/TC810N1013 NAC Module
AEM-24AT Annunciator Expander Module FCPS-24, FCPS-24S6/S8 Field Charger Power Supply
AEM-48A Annunciator Expander Module TC808A1027 Intelligent Thermal Sensor
AFM-16A Annunciator Fixed Module XLS-FDU-80 Remote Fire Annunciator
AFM-16AT Annunciator Fixed Module FFT-7 Fire Fighters Telephone
AFM-32A Annunciator Fixed Module FFT-7S Fire Fighters Telephone
AKS-1B Annunciator Key Switch FHS Fireman's Handset
APJ-1B Annunciator Phone Jack XLS-MM-A (FlashScan), TC809A1059 (CLIP) Monitor Module
AMG-1 Audio Message Generator XLS-MM-B (FlashScan), TC809B1008 (CLIP) Mini Monitor
AMG-E Audio Message Generator Module
APS-6R Auxiliary Power Supply TC847A1004/A Single-ended beam smoke detector with
ARM-4 Auxiliary Relay Module sensitivity testing
AVL-1 Audio Voice Link (Not ULC-listed) TC806D1011 Photoelectric Duct Detector
BMP-1 Blank Module Plate TC806D1018 Photoelectric Duct Detector with alarm relay
BP-4 Battery Dress Plate TC806D1049/CDN Low-flow DUCT Detector
14506414-002/CDN Intelligent base TC806D1056/CDN Low-flow Duct Detector with alarm relay
B501BH Sounder base DHX-501, DHX-502 Duct Detectors
14507371-001/CDN Intelligent detector base Ion Detector
CAB-4 Series Mounting Hardware (Doors and backboxes are TC807B1059/CDN Ion Detector
ordered separately. Black unless “R” is added to the P/N.) TC844A1015 Filtrex Smoke Detector(FlashScan/CLIP)
Doors (Add B to the P/N for blank door) TC844A1007Filtrex (CLIP)
XLS-DR-A4 A-sized door, 1 row of equipment TC846A1013 Pinnacle Low Profile Laser Detector
XLS-DR-B4 B-sized door, 2 rows of equipment TC809B1032 Pull Station Monitor Module
XLS-DR-C4 C-sized door, 3 rows of equipment FPJ Firefighter’s Phone Jack
XLS-DR-D4 D-sized door, 4 rows of equipment XLS-CM-R (FlashScan), TC810R1024/CDN (CLIP) Relay
Backboxes (For red, add “R” to the P/N) Module
SBB-A4 A-sized backbox TC806B1076/CDN Photo Detector
SBB-B4 B-sized backbox continued…
SBB-C4 C-sized backbox
SBB-D4 D-sized backbox
Trim Rings
TR-A4 A-sized trim ring

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 81


Compatible Equipment

TC808B1041/CDN Thermal Detector RA400 Remote Annunciator


TC808B1058/CDN Thermal Detector (rate of rise) RA400Z Remote Annunciator with diode
TC808B1066/CDN High Temperature Detector RFX Wireless Transmitter (version 2.0 and higher): SDRF-751
XLS-CM-TXLS-MM-Z (FlashScan), TC841A1000/CDN (CLIP) Wireless Photo/Thermal Smoke Detector; 5817CB Wireless
Monitor and Zone Interface Module Monitor Module
XLS-MM-D (FlashScan), TC809D1004/CDN (CLIP) Dual RPJ-1 Fireman's Phone Jack
Monitor and Zone Interface Module RPT-485F EIA-485 Repeater (Fiber)
ICE-4 Indicating Control Expander RPT-485W EIA-485 Repeater (Wire)
ICM-4RK Indicating Control Module RPT-485WF EIA-485 Repeater (Wire/Fiber)
TC840A1001Combination Smoke Sensor (Discontinued) RM-1 Remote Microphone
TC811A-1006/TC811A1014 Loop Fault Isolator Module RM-1SA Remote Microphone
KDM-2 Keypad/Display Unit SCS-8, SCE-8 Smoke Control Station
L20-300-BX Enclosure; recessed mount SCS-8L, SCE-8L Smoke Control Lamp Driver
L20-310-BX Enclosure; surface mount TC806A1037 Intelligent Photoelectric Detector
XLS-LCD-80 Liquid Crystal Display Module Intelligent Photoelectric Detector
LDM-32 Lamp Driver Module STS-1 Security Tamper Switch
LDM-E32 Lamp Driver Module TM-4 Transmitter Module
LDM-R32 Lamp Driver Module UDACT Universal Digital Alarm Communicator Transmitter
LEM-320 Loop Expander Module UZC-256 Universal Zone Coder
TC846A1005 Pinnacle Low Profile Laser Detector (CLIP mode) VCE-4 Voice Control Expander
MP-1B Panel Module Dress Plate VCM-4RK Voice Control Module
NBG-12LRA Agent Release-Abort Station VeriFire™ Tools Upload/Download Software
S464G1007 Addressable Manual Pull Station VP-2B 2” Filler Dress Plate
XLS-NCA Network Control Annunciator XPDP Transponder Dress Panel
NCM-F Network Control Module (Fiber) XPIQ Quad Intelligent Audio Transponder
NCM-W Network Control Module (Wire) XP6-C/XP6-CA Supervised Control Module
N-ELR Assortment ELR Pack with Mounting Plate XP6-R/XP6-RA Six Relay Control Module
EOL-CB/EOL-CR End of Line Resistors XP6-MA/XP6-MAA Six Zone Interface Module
XLS-LBB Battery Box XP10-M/XP10-MA Ten Input Monitor Module
XLS-LBBR Red Battery Box
P-40 Keltron Printer
P40-KITB Dress plate for Keltron Printer
PRN Series 80-Column Printers (PRN-4, PRN-5, XLS-PRN-6)
BAT-12120 Battery 12-volt, 12 amp-hour
BAT-12180 Battery 12-volt, 18 amp-hour
BAT-12250 Battery 12-volt, 25 amp-hour
BAT-12550 Battery 12-volt, 55 amp-hour
BAT-12600 Battery 12-volt, 60 amp-hour
R-120 120 Ohm End-of-Line Resistor
R-2.2K 2.2K End-of-Line Resistor
R-27K 27K End-of-Line Resistor
R-470 470 End-of-Line Resistor
R-47K 47K End-of-Line Resistor
A77-716B End-of-Line Resistor Assembly

System Sensor Equipment


A2143-00 End of Line Resistor Assembly
EOLR-1 End-of-Line Resistor Assembly
FSB-200S Beam Detectors
TC847A1004/A Beam Detector

82 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


Appendix D: Canadian Applications

D.1 Standalone Application


D.1.1 XLS140 with KDM-2
If using KDM-2 as the primary display for XLS140, an ACS series annunciator must be mounted
adjacent to the panel or within XLS140 enclosure.

D.1.2 XLS140 with XLS-NCA


Network Control Annunciator (XLS-NCA) with 640-character, multi-line display complies with
ULC requirements when used as the primary display for XLS140.

D.2 Local Network Application


To meet ULC requirements, the network’s Manual Controls may only be operated from one
location at any given time. When panels are networked (using NCM Network Control Modules),
employ AKS-1B Key Switch on each panel’s Primary Annunciator to enable its functions.
XLS-NCA may be a Primary Annunciator when AKS-1B is installed. Refer to the XLS-NCA
Manual for more information.
An XLS-NCA may be employed as a Display and Control Center. In the event that communication
fails between the panels and the Control Center, the panels will continue to function in local/
standalone mode.

D.3 Automatic Alarm Signal Silence


If selecting this feature for a system requiring annunciators, consult the Authority Having
Jurisdiction.

D.4 Annunciator Applications


1. In Canada, the ACM series annunciator modules must be used to annunciate the fire alarm
input points/zones only, if no multi-line sequential display is installed.
2. For Canadian applications, the following LED colors must be employed:
– Red must be used to indicate active alarm inputs.
– Yellow must be used to indicate supervisory, burglary or trouble signals.
– Green must be used to indicate the presence of power or an activated output.

D.5 Releasing Devices


Supervision for shorts is required; use REL devices and type code REL CKT ULC.
(With on-board NACs, use REL-2.2K; with XLS-CM-N/TC810N1013 modules use REL-47K.
Refer to Section 4.5 “Releasing Applications” for details.

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 83


Index
Numerics see also Power: DC 40
Blank modules 18
14507371-003/CDN 21
14507371-005/CDN 21 C
24 VDC, see also Power:DC 41
Cabinets 18
A Battery backboxes 19
Mounting 30
A77-716B
California code 48
Replaced by EOLR-1
See power supervision relay Canadian Applications 35, 83
AC, see Power 40 central receiving unit
see also UDACT manual 62
Acceptance Test 69
Chassis 18, 38, 49
ACM-8R
labeling requirements 44 CHG-120 (Overview) 20
Circuit Board, see CPU
Overview 23
Compatible Equipment 81
ACPS-2406 (Overview) 19
Components 16, 17
ACS, see Annunciators 23
Added index marker for monitor module 63 Control Modules (Overview) 22
Addressable Modules (Overview) 22 Control Panel Circuit Board, see CPU
CPU
AFM-16AT
drawing 15, 16, 17
Overview 24
AFM-32A Installation steps 33
Overview 24 Overview 15
Agent Release-Abort Station 67 CRM-4RK, CRE-4
Connections 49
Alarm relays, see Form-C relays 42
AMG-1, see also Voice Alarm System 26 Driving an ARM-4 49
Annunciator Fixed Modules (Overview) 24 Mounting instructions 45
see Annunciator Fixed Module Manual non-power-limited circuits 44
Annunciators 23 Overview 25
ACM-24AT, AEM-24AT 24 CRTs 55
ACM-48A, AEM-48A 24 CRT/PRN combination 55
Overview 23 CRT-2 Configuration 53
APS-6R 19 CRT-2 Function Keys and parameters 54
See Auxiliary Power 41 CRT-2 Overview 25
ARM-4 Installation 51–55
Installation steps 49 D
non-power-limited circuits 44
D35 on ICM-4RK 48
Stand-off and Terminal Locations 50
DC, see Power 40
Audio Amplifiers (Overview) 26
Detectors
see also Voice Alarm System
Detector bases 21
Auxiliary Relay Module, see ARM-4 49
listing 21
B Detectors (Overview) 20
Display Terminal (Overview) 25
B224RB 21
Dress Panels 18
Backboxes, see Cabinets
Dual Channel Module (Overview) 26
Backup-alarm switches 43
see also Voice Alarm System
Basic Equipment Packages 14
Batteries E
Battery Boxes 19
Electrical connections 39
Battery calculations 71, 73, 74, 75, 76
Electrical Specifications 77
Battery Checks and Maintenance 70
EOLR-1 See power supervision relay
Battery specifications 77
Expander boards, see Panel Circuit Modules: Expander
Connections 40
Board Modules 45
Overview 19

84 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


F–Q

F NCM-W/F (Overview) 19
NFPA Applications
FCPS-24, FCPS-24S (Overview) 20
NFPA 72 Central or Remote Station Fire Alarm
Fire Fighters Telephone, see also Voice Alarm System
System 60
Manual 26
NFPA Applications (Overview) 59
Fire/Security Applications 61–63
Nonpower-limited circuits
FlashScan® (Overview) 21
UL wiring requirements 43, 44
Form-C relays 22, 23, 25, 42, 49, 78
Notification Appliance Circuits, see NACs
Four-wire Smoke Detector
Specifications 78 O
I Operating Power 79
Operational Checks 69
ICM-4RK (Overview) 25
Output relays
see also Panel Circuit Modules
Connections 22, 23, 25, 42, 49, 78
Installation
Specifications 78
Checklist 30
Preparation 29 P
J Panel Circuit Modules
ICM-4RK Connections 47
Jumper locations 16, 17
ICM-4RK Field-wiring 48
ICM-4RK 47
ICM-4RK Jumpers 47
K ICM-4RK Resistors 48
KDM-2 ICM-4RK/ICE-4 Connections 46
Installation steps 33 Installation steps 37, 44
Keltron printer (Overview) 25 Mounting Expander Boards 45
Keltron, see also Printers 52 Overview and complete list 25
Ribbon cables 45
L see also ICM-4RK, ICE-4, CRM-4RK, CRE-4,
LDM-32 (Overview) 23 VCM-4RK, DCM-4RK, VCE-4 44
LDM-R32 Periodic Testing 69
non-power-limited circuits 44 Power
LDM-R32 (Overview) 23 AC Power Checklist 40
LED locations 17 AC power connections 39, 40
LEM-320 (Overview) 19 AC specifications 77
lockout 69 Auxiliary Power 41
Loop Expander Module DC power connections 40, 41
Installation steps 36 Installation steps 39
Power specifications 39, 78
M power supervision relay 66, 67
Main power supply 15 Power supply calculations 71, 73, 74, 75, 76
Maintenance 69 Power-limited Wiring Requirements 43
microcontroller failure 43 primary display 14, 35
Monitor Modules (Overview) 22 Printers 55
Mounting Installation 51–55
LEM 36 Keltron printer Connections 52
Panel Circuit Modules 45 Overview 24
Multi-Input/Output Modules 22 PRN series (overview) 25
PRN series connections 51
N PRN settings 52
NACs (Notification Appliance Circuits) PRN/CRT combination 55
Backup option 43 Proprietary Security Alarm Applications
NAC Connections 42 Wiring 63
Releasing applications 42, 43, 64, 65 Protected Premises Unit 60
Specifications 78
NBG-12LRA 67 Q
NCM-W/F, see Networking Quad Intelligent Audio Transponder
Networking 37 see also XPIQ 22

XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 85


R–X

R Terminal block locations 16, 17


Testing 69
RA400Z 21
TM-4
Related Documentation 10
see Transmitter Module TM-4 43
Relays, see Form-C relays 42
TM-4 (Overview) 19
Releasing Circuits
Connections 42 Trouble relays, see Form-C relays 42
Releasing Applications 64–67 U
Releasing Applications, Canada 83
UDACT (Overview) 19
Specifications 78
UL nonpower-limited wiring requirements 43
Releasing Device
UL Requirements 43
Connections 65
UZC-256 (Overview) 20
TC810N1013 Connections 66
XLS-CM-N Connections 66 V
Remote Microphone, see Voice Alarm System 27
VCM-1 (Overview) 26
Resistor locations
see also Voice Alarm System
ICM-4RK 48
VeriFire 55
S Voice Alarm System
Overview 26
S464G1007 22
see also Voice Alarm System Manual
S5000 modules, see Panel Circuit Modules 25
Voice Alarm System (Overview) 27
Security relays, see Form-C relays 42
Security Tamper Switch 62, 63 W
Service 69
Wiring
Signaling Line Circuit, see SLC 20 Proprietary Security Alarm Applications 63
SLC 20, 36 Wire Requirements 79
see also SLC Wiring Manual 56
specifications 78 X
Specifications 78 XLS140-CPU (120V operation), see Basic Equipment
Stacker-connector 36 Packages 14
Stand-off Lengths 33 XLS140-CPUE (240V operation), see Basic Equipment
STS-1, see also Security Tamper Switch 63 Packages 14
Supervisory and Security contacts XLS-CM-N 22, 66
configuring as Alarm contacts 42 XLS-CM-R 22
Supervisory relays, see Form-C relays 42 XLS-FDU-80 20
Supplemental Documentation 10 XLS-LCD-80
Switches Overview 20
Backup-alarm 43 XLS-MM-A 63
switch locations 16, 17 XLS-MM-D 22
System XLS-MM-Z 22
Description of features 13 XLS-NCA 34, 35
Limitations 14 also see Primary display 14
Options 13 Overview 19
System current draws 71, 73, 74, 75, 76 XLS-TCC-1B, see Voice Alarm System 26
T XLS-VCC-1B, see Voice Alarm System 26
XLS-VTCC-1B, see Voice Alarm System 26
TC807B1059/CDN 21
XP10-MA 22
TC808B1041/CDN 21
XP6-C, XP6-R, XP10-M, XP6-MA 22
TC808B1058/CDN 21
XP6-CA 22
TC808B1066/CDN 21
XP6-MAA 22
TC809A1059 63
XPIQ (Overview) 22
TC809D1004/CDN 22
TC810N1013 66
TC810N1013/CDN 22
TC810R1024/CDN 22
TC811A-1006/TC811A1014 22
TC847A1004/A 21

86 XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005


XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005 87
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9
customer.honeywell.com

® U.S. Registered Trademark


© 2005 Honeywell International Inc.
95-7673-3 C. Rev. 12-05

You might also like