Fire Alarm Control Panel XLS 140
Fire Alarm Control Panel XLS 140
Fire Alarm Control Panel XLS 140
INSTALLATION MANUAL
This system meets NFPA requirements for operation at 0-49º This system contains static-sensitive components.
C/32-120º F and at a relative humidity (non condensing) of Always ground yourself with a proper wrist strap before han-
85% at 30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C dling any circuits so that static charges are removed from the
(89.6°F ± 1.1°F) per ULC. However, the useful life of the sys- body. Use static suppressive packaging to protect electronic
tem's standby batteries and the electronic components may be assemblies removed from the unit.
adversely affected by extreme temperature ranges and humid- Follow the instructions in the installation, operating, and pro-
ity. Therefore, it is recommended that this system and its gramming manuals. These instructions must be followed to
peripherals be installed in an environment with a normal room avoid damage to the control panel and associated equipment.
temperature of 15-27º C/60-80º F. FACP operation and reliability depend upon proper installation.
Verify that wire sizes are adequate for all initiating and indi- Precau-D1-9-2005
cating device loops. Most devices cannot tolerate more than a
10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A limits
used in accordance with the instruction manual may for radiation noise emissions from digital apparatus set
cause interference to radio communications. It has been out in the Radio Interference Regulations of the Cana-
tested and found to comply with the limits for class A dian Department of Communications.
computing devices pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable Le present appareil numerique n'emet pas de bruits radi-
protection against such interference when devices are oelectriques depassant les limites applicables aux appa-
operated in a commercial environment. Operation of this reils numeriques de la classe A prescrites dans le
equipment in a residential area is likely to cause interfer- Reglement sur le brouillage radioelectrique edicte par le
ence, in which case the user will be required to correct ministere des Communications du Canada.
the interference at his or her own expense.
HARSH™, NIS™, Notifier Integrated Systems™, ONYXWorks™, and Pinnacle™ are all trademarks; and Acclimate®, Filtrex®, FlashScan®, NION®,
NOTIFIER®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a
trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of
the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.
©2005 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Please note this email address is for documentation feedback only. If you have any technical
issues, please contact Technical Services.
The installer should be familiar with the following documents and standards:
• NFPA 72-1999 Initiating Devices for Fire Alarm Systems
• NFPA 72-1999 Inspection, Testing and Maintenance for Fire Alarm Systems
• NFPA 72-1999 Notification Appliances for Fire Alarm Systems
Underwriters Laboratories
• UL 38 Manually Actuated Signaling Boxes
• UL 217 Smoke Detectors, Single and Multiple Station
• UL 228 Door Closers - Holders for Fire Protective Signaling Systems
• UL 268 Smoke Detectors for Fire Protective Signaling Systems
• UL 268A Smoke Detectors for Duct Applications
• UL 346 Waterflow Indicators for Fire Protective Signaling Systems
• UL 464 Audible Signaling Appliances
• UL 521 Heat Detectors for Fire Protective Signaling Systems
• UL 864 Standard for Control Units for Fire Protective Signaling Systems
• UL 1481 Power Supplies for Fire Protective Signaling Systems
• UL 1971 Visual Signaling Appliances
• UL 1076 Proprietary Burglar Alarm Systems
• UL 60950 Safety of Information Technology Equipment
Underwriters Laboratories of Canada (ULC)
• Standard CAN/ULC-S527-M99
• CAN/ULC-S524-M91 Standard for the Installation of Fire Alarm Systems
Other
• EIA-485 and EIA-232 Serial Interface Standards
• NEC Article 300 Wiring Methods
• NEC Article 760 Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction
• C22.1-98 The Canadian Electrical Code, Part 1
Document Number
(Form number if
Compatible Conventional Devices (Non-addressable) applicable)
Device Compatibility Document 51939 (74-3944)
Document Number
(Form number if
Fire Alarm Control Panel (FACP) and Main Power Supply Installation applicable)
XLS140 Installation, Operations, and Programming Manuals 51927 (95-7673),
51928 (85-0254),
51929 (85-0253)
Honeywell Voice Alarm System Manual 51931 (95-7674)
Honeywell SLC Wiring Manual 51932 (95-7675)
Note: For individual SLC Devices, refer to the SLC Wiring Manual
Document Number
(Form number if
Off-line Programming Utility applicable)
VeriFire™ Tools CD help file HONEYWELL-TCD
Document Number
(Form number if
Cabinets & Chassis applicable)
CAB-3/CAB-4 Series Cabinet Installation Document 15330
Battery/Peripherals Enclosure Installation Document 50295
Document Number
(Form number if
Power Supplies, Auxiliary Power Supplies & Battery Chargers applicable)
ACPS-2406 Installation Manual 51304
APS-6R Instruction Manual 50702
CHG-120 Battery Charger Manual 50641
FCPS-24 Field Charger/Power Supply Manual 50059
FCPS-24S Field Charger/Power Supply Manual (Sync) 51977
Document Number
(Form number if
Networking applicable)
XLS-NET Manual, Network Version 5.0 51991 (95-7680)
NCM-W/F Installation Document 51533
Document Number
(Form number if
System Components applicable)
Annunciator Control System Manual 15842
Annunciator Fixed Module Manual 15048
AFM-16A Annunciator Fixed Module Manual 15207
ACM-8R Annunciator Control Module Manual 15342
CAUTION:
! Information about procedures that could cause programming errors, runtime errors, or equipment
damage.
WARNING:
! Indicates information about procedures that could cause irreversible damage to the control panel,
irreversible loss of programming data or personal injury.
2.1.2 Options
Refer to Section 2.2 “System Components” for descriptions of the various optional modules.
• QWERTY silicone-rubber keypad with a 2x40 LCD display and eight indicator LEDs
• Optional LEM-320 provides a second SLC loop that is electrically identical to the one on the
main board
• Optional devices include: UDACT Universal Digital Alarm Communicator/Transmitter,
ACM-8R remote relay module to increase point capacity, audio and voice components, and
panel circuit modules
• Optional XLS-LCD-80 connected through an EIA-485 interface allows monitoring the
system—up to 6,000 feet (1,829 meters) from the control panel
*
1 2 3 4 5 6 7 8 9 0 NEXT
+
! @ = , % : . ? DETECTOR SELECTION
Q W E R T Y U I O P MODULE # PREVIOUS
SELECTION
–
nfs640-panel.cdr
Esc RECALL
A S D F G H J K L OUTPUT & LAST
ENTRY
(
Enter )
Z X C V B N M SPACE BATTERY
LEVELS / INCREMENT
NUMBER
Figure 2.1 XLS140 Control Panel with Optional Keypad/Display Unit Installed
TB3 - NAC#4
B+ B- A+ A-
nfs640-board2.cdr
J3 - LEM-320
J4 - KDM-2 Connector
Connection (SLC Loop #2)
+ - + - NO NC C NO NC C NO NC C NO NC C + - + - + - TX RX REF TX RX REF B+ A+ B- A-
B+ B- A+ A-
B+ B- A+ A-
B+ B- A+ A-
B+ B- A+ A-
Disable - Enable
Switches for
Backup Alarm
BATT+ BATT- EARTH NTRL HOT
nfs640-board2.cdr
System Switches - ‘No D72 - General D67 -LEM-320
Keyboard Operation’ Board Ground Ground Fault LED
SW2 - Acknowledge Fault LED
SW3 - Silence D82 - Power-on LED
SW4 - Reset (AC or battery)
A-size backbox 24.00 in (60.96 cm) wide Optional trim ring TR-A4
(one row) 20.00 in (50.8 cm) tall Opening: 24.062 in (61.118 cm) wide;
5.218 in (13.254 cm) deep 20.062 in (50.881 cm) tall.
Uses optional trim ring TR-A4 Molding width: 1.375 in (3.493 cm)
B-size backbox 24.00 in (60.96 cm) wide Optional trim ring TR-B4
(two rows) 28.5 in (72.39 cm) tall Opening: 24.062 in (61.118 cm) wide;
5.218 in (13.254 cm) deep 28.562 in (72.548 cm) tall.
Uses optional trim ring TR-B4 Molding width: 1.375 in (3.493 cm)
C-size backbox 24.00 in (60.96 cm) wide Optional trim ring TR-C4
(three rows) 37.125 in (94.297 cm) tall Opening: 24.062 in (61.118 cm) wide;
5.218 in (13.254 cm) deep 37.187 in (94.455 cm) tall.
Uses optional trim ring TR-C4 Molding width: 1.375 in (3.493 cm)
D-size backbox 24.00 in (60.96 cm) wide Optional trim ring TR-D4
(four rows) 45.75 in (1162.05 cm) tall Opening: 24.062 in (61.118 cm) wide;
5.218 in (13.254 cm) deep 45.812 in (114.775 cm) tall.
Uses optional trim ring TR-D4 Molding width: 1.375 in (3.493 cm)
Trim Rings: When using trim rings, mount backbox with at least 1 inch (2.54 cm) between wall surface and
front of backbox, to allow door to open fully past the trim ring.
The control panel and adjacent first-row modules mount in chassis CHS-M2, typically in the
first/top row of the backbox. Additional rows of modules can be mounted in chassis CHS-4N
and/or CHS-4L.
NOTE: If using the new CHS-M2 in a CAB-3 series backbox or in a CAB-4 series backbox
manufactured before October 2002, verify stud height and cut any stud that exceeds 0.375 in.
(9.525 mm) if a CPU is being mounted above it. See warning and instructions in Section 3.5.1
“Control Panel Circuit Board & Keypad/Display Unit”.
BMP-1 Blank Module Plate for covering an unused dress-panel position. Provides another option
for mounting modules such as TM-4, NCM-W, or NCM-F.
BP-4 Battery dress panel
VP-2B or MP-1B (with DP-1B) For covering top row(s) of backbox if control panel is mounted
in a lower row. MP-1B is also used to mount panel circuit modules.
the standard EIA-485 connection like an ACS device and mounts easily in standard module
locations within the cabinet or external boxes. Refer to the Transmitter Module TM-4 installation
document for further information and installation instructions.
Universal Zone Coder - UZC-256. A circuit board, used for NAC coding applications, that
provides three NAC output circuits and up to 256 zone codes. Refer to the UZC-256 Universal
Zone Coder and UZC-256 Programming manuals for further information and installation
instructions.
Field Charger/Power Supply - FCPS-24, FCPS-24S6, FCPS-24S8. Compact,
cost-effective remote power supply and battery charger with a filtered, 24 VDC output that can
drive up to four Notification Appliance Circuits (NACs). The FCPS-24S6/FCPS-24S8 can also
synchronize the NACs. Refer to the FCPS-24 Field Charger/Power Supply Manual or the
FCPS-24S Field Charger/Power Suppply Manual for further information and installation
instructions.
Battery Charger - CHG-120. Designed to charge lead-acid batteries that provide emergency
standby power for a Fire Alarm Control Panel. Provides two (2) output circuits for connection to
multiple loads. Can be mounted into the CAB-4 Series backbox or the XLS-LBB Battery Box.
Refer to the CHG-120 Battery Charger manual for further information and installation instructions.
Liquid Crystal Display - XLS-LCD-80. An alphanumeric display module that is an ancillary
device which has two basic modes of operation. In Terminal Mode it acts as a display interface and
in ACS Mode as an alphanumeric annunciator. Refer to the XLS-LCD-80 Liquid Crystal Display
manual for further information and installation instructions.
Remote Fire Annunciator - XLS-FDU-80. An 80-character LCD that displays all panel
information remotely. Refer to the XLS-FDU-80 Manual for further information and installation
information.
SCS-8 Series Smoke Control System. The Smoke Control Station (SCS-8) module uses
eight groups of four annunciator points for fan shutdown control or other heating, ventilation or air
conditioning functions. The Smoke Control Expander (SCE-8) is used to expand the SCS-8 by an
additional eight groups of four annunciator points. Only one expander can be used per SCS-8. The
Smoke Control Lamp Driver Station (SCS-8L) module uses eight groups of four annunciator points
for fan shutdown control or other heating, ventilation or air conditioning functions. Must be
mounted in custom graphic annunciator panel. The Smoke Control Expander (SCE-8L) is used to
expand the SCS-8L by an additional eight groups of four annunciator points. Only one expander
can be used per SCS-8L. Must be mounted in custom graphic annunciator panel. For more details
on the SCS Smoke Control System, refer to the SCS Manual.
NOTE: A blinking LED on an intelligent detector indicates communication between the detector
and the control panel.
Detectors
The FlashScan® algorithm provides high-speed communication between analog intelligent
devices, by polling in groups unless new information is reported. If one of the devices within the
group has new information, the control panel stops the group poll and concentrates on single points.
CLIP (Classic Loop Interface Protocol) is standard polling of each intelligent devices.
TC840M1021 (Acclimate™) Intelligent detector that combines a photoelectric sensing
chamber and fixed temperature heat detection (135°F/57.2°C). FlashScan capable.
TC847A1004 (TC847A1004A Canadian) Addressable, intelligent, single-ended beam smoke
detector with built-in sensitivity testing. Supports FlashScan and CLIP mode.
TC807B1059 (TC807B1059CDN Canadian) Addressable, intelligent smoke detector that
incorporates an ionization sensing chamber. Designed to provide open area protection. FlashScan
capable.
TC806B1076 (TC806B1076CDN Canadian) Analog, addressable intelligent smoke detector that
uses a photoelectric sensing chamber. Listed for use in ducts. Designed to provide open area
protection. FlashScan capable. The TC806B1084 adds thermal sensors that will alarm at a fixed
temperature of 135°F (57°C).
TC808B1041 (TC808B1041CDN Canadian) Intelligent thermistor sensing circuit for fast
response. Designed to provide open area protection with 50 foot spacing capability. A fixed
temperature sensor with 135°F fixed temperature alarm. FlashScan capable. The TC808B1058
(TC808B1058CDN Canadian) incorporates a thermal rate of rise of 15°F (9.4°C). FlashScan
capable. The TC808B1066 (TC808B1066CDN Canadian) is a high temperature sensor with 190°F
(87.8°C) fixed temperature alarm.
TC806D1011 Photoelectric Duct Detector. The TC806D1018 includes an alarm relay. The
TC806D1049 (TC806D1049CDN Canadian) and TC806D1056 (TC806D1056CDN Canadian)
are low-flow detectors.
TC844A1007 (Filtrex) A special smoke detector that provides early warning smoke detection in
hostile environments where traditional smoke detectors are not practical. CLIP mode only.
TC844A1015 (Filtrex) A special smoke detector that provides early warning smoke detection in
hostile environments where traditional smoke detectors are not practical. FlashScan and CLIP .
TC846A1005 Early detection laser detector, similar to the TC846A1013 Pinnacle, but limited to
CLIP mode operation only.
TC846A1013 Pinnacle Low Profile Laser Detector An advanced intelligent photoelectric
detector that uses a laser diode, special optics, and signal processing to obtain extremely high
sensitivity. FlashScan mode only.
Bases
Several bases, to which the detectors are affixed, are available:
14507371-001(14507371-001CDN Canadian) Standard U.S. Low-Profile base
14506414-002 (14506414-002CDN Canadian) Standard European flangeless base
B501BH, B501BHT Sounder base, includes 14506414-002/CDN Sounder base with temporal
sounder
B224RB, 14507371-003 (14507371-003CDN Canadian) Low Profile Intelligent relay bases
14507371-005 (14507371-005CDN Canadian) Low Profile Intelligent isolator bases
14507371-008 Filtrex base.
Accessories
RA400Z A Remote Single LED Annunciator that can be wired directly off of an addressable
detector for annunciation of that detector's alarm status.
NOTE: For a list of approved notification and initiating devices, refer to the Device Compatibility
Document.
• XP10-M supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor
normally open contact initiating devices. .
• XP6-MA enables an intelligent alarm system to monitor six zones of conventional two-wire
detectors.
For installation instructions, refer to the documentation provided with the modules.
Description
Below are descriptions of the Annunciator Modules and Expander Modules used with the control
panel.
Annunciator Control Module - ACM-8R Provides the control panel with a mappable relay
control module. Relays can be selected for mapping anywhere in the system memory (in groups of
eight). Provides eight Form-C relays with 5 A @ 125 VAC (resistive) or 5 A @ 30 VDC (resistive)
or 2 A @ 125 VAC (inductive) contacts. Tracks any group of eight zones within the system.
Refer to ACM-8R Annunciator Control Module manual for more information.
Lamp Driver Annunciator Module - LDM-32 Provides 32 alarm lamp driver outputs for
connection to a custom graphic annunciator. DIP switch selectable for 32 alarm outputs or 16
alarm/16 trouble outputs, and 16 switch inputs for control of system control functions as Signal
Silence and System Reset.
Refer to the LDM Series Lamp Driver Annunciator Modules manual for more information.
Lamp Driver Annunciator Expander Module - LDM-E32 Expands the LDM-32 by 32
system points, to a maximum of 64 points.
Lamp Driver Relay Expander Module - LDM-R32 Provides the LDM-32 or LDM-E32 with
32 dry Form-A (normally open) contacts.
2.8 Annunciators
The Annunciator Control System provides the control panel with 32 remote annunciators. The
number of points a particular annunciator can support is reflected in the part number. For example,
an ACM-24AT has 24 points and an ACM-48A has 48 points. The number of points on an
Annunciator Expander Module must match the number of points on the Annunciator Control
Module it is expanding. One Annunciator Fixed Module can also be used per system. Connections
are through an EIA-485 ACS Mode connection on the Control Panel.
NOTE: The XLS140 can only support 64 points per annunciator address regardless of the model
used.
Brief descriptions follow of specific modules used with the control panel. For detailed information,
refer to the specified product manual.
Description
Annunciator Fixed Module - AFM-16AT Contains 16 red alarm and 16 yellow trouble LEDs,
a system trouble LED, an Online/Power LED, and a local sounder, and switches for control panel
Acknowledge, Alarm Silence, and System Reset. Use the AFM-16AT for systems that require 16 or
fewer annunciation points.
Annunciator Fixed Module - AFM-32A Contains 32 red alarm LEDs, a system trouble LED,
an ON LINE/POWER LED, and a local panel sounder with a silence/acknowledge switch. The
AFM-32A is fixed at address 1, and will not accept expander modules.
Printer - PRN Series Printer The PRN is an optional printer that connects directly to the
control panel through an EIA-232 interface (TB14) and can be located up to 20 feet (6.1 m) from
the control panel. It creates a printed record (80 columns of data on standard 9" x 11" tractor-feed
paper) of all system events (alarm, trouble) and status changes within the system. The printout is
time-stamped with the current time-of-day and date.
Keltron Remote Printer The VS4095 is a two-color (red/black), 40-column, 24 VDC printer
that can print 50 messages in 90 seconds. This printer connects to the control panel through an
EIA-232 interface (TB14) and mounts in a separate cabinet next to the control panel. The VS4095
meets UL fire and security requirements for an ancillary device.
For more information, contact the manufacturer (Keltron Corp., Waltham, MA)
Display Terminal - CRT-2 This optional display terminal connects to the control panel through
an EIA-232 interface (TB15). The terminal can control and view events, points and history reports,
control the system (Acknowledge, Alarm Silence, and System Reset). The terminal displays 26
lines by 80 columns and can be located up to 50 feet (15.24 m) from the control panel within the
same room.
NOTE: The CRT cannot be connected at the same time as the network.
Auxiliary Relay Module - ARM-4 Provides four (4) auxiliary Form-C relays that can be
controlled by a CRM-4RK or CRE-4 relay module. Normally-open contacts rated for 20 A and the
normally-closed contacts are rated for 10 A at 125 VAC and 30 VDC (resistive). An Auxiliary
Power Harness (P/N 71092) is provided.
Configuration
XLS-VCC-1B Voice Control Center Basic equipment package for single-channel audio
evacuation system that includes: AMG-1 Audio Message Generator (with microphone), CHS-4L
Chassis, DPSW-1B Single-well Dress Panel, and Cable assemblies required to connect to control
panel.
XLS-VTCC-1B Voice/Telephone Control Center Basic equipment package for
single-channel audio evacuation system employing a Fire Fighter’s Telephone system that includes:
FFT-7 Fire Fighter’s Telephone, AMG-1 Audio Message Generator (with microphone), CHS-4L
Chassis, DPDW-1B Double-well Dress Panel, and Cable assemblies required to connect to control
panel.
XLS-TCC-1B Telephone Control Center Basic equipment package for a Fire Fighter’s
Telephone system with no voice evacuation or paging capabilities that includes: FFT-7 Fire
Fighter’s Telephone, CHS-4L Chassis, TBP-1B Blank Panels (2), DPDW-1B Double-well Dress
Panel, and Cable assemblies required to connect to control panel.
Descriptions
Audio Message Generator (AMG-1 & AMG-E) Provides a variety of tones and a built-in
microphone allows for paging through speaker circuits. Optionally, you can install up to four
digitally-recorded voice messages into the AMG-1: two factory prerecorded voice messages, two
user-defined messages. You can create both user-defined messages through the AMG-1 built-in
microphone, or download messages from a standard audio cassette recorder.
The AMG-E is an AMG-1 without a microphone. It is used for applications that require multiple
Audio Message Generators.
Fire Fighters Telephone (FFT-7 and FFT-7S) Provides the Voice Alarm System with fire
fighter's telephone capability. With these units, up to seven telephones can be used to hold a
simultaneous conversation. The FFT-7S does not provide paging capability.
Voice Control Module (VCM-4RK) Provides the system with up to four (4) Style Y (Class B)
or Style Z (Class A) speaker circuits, or up to four Style Y (Class B) telephone circuits. Moving a
jumper on the module configures it for driving FFT-7 circuits. When configured for telephone
circuits, the VCM-4RK accepts its signal directly from a Fire Fighters Telephone. Add an optional
Voice Control Expander (VCE-4) to the back of the module to provide four additional telephone or
speaker circuits.
Dual Channel Module (DCM-4RK) Provides the system with the capability to select one of
two types of audio sources for switching to a specified speaker circuit. The module provides up to
four circuits.
Audio Amplifiers The control panel uses three types of audio amplifiers with an installed Voice
Alarm System:
• AA-30 – Provides up to 30 watts of audio power for driving 25 Vrms speaker circuits.
• AA-100 – Provides 100 watts of audio power for driving 25 Vrms and 70.7 Vrms speaker
circuits.
• AA-120 – Provides 120 watts of audio power for driving 25 Vrms speakers.
Each AA amplifies the audio signal coming in from an Audio Message Generator (AMG-1 or
AMG-E).
Audio Coupling Transformer ACT-1 Couples low-level audio to audio amplifiers or other
audio inputs, such as the AMG-1 Audio Message Generator. Provides Common Mode Noise
Rejection (CMNR), greatly reducing crosstalk from the SLCs. For more information and
installation instructions refer to the Voice Alarm System manual.
Audio Coupling Transformer ACT-2 When used with an AMG-1/-E, RM-1 and AA-30 this
unit provides a means to drive thousands of amplifiers in large audio system applications. The
ACT-2 provides electrical isolation between its input & output and attenuates the signal from
high-level audio to low-level audio. For more information and installation instructions refer to the
ACT-2 Product Installation Drawing.
Additional Devices
The following devices are not part of the Voice Control System, but are listed here for continuity.
Remote Microphone (RM-1 and RM-1SA) Provides paging capabilities to speaker systems
driven by the low level audio source of the AMG-1. The RM-1 assembly can be installed in a
CAB-4 Series backbox, while the RM-1SA is installed in a CAB-RM cabinet. For more
information and installation instructions see the RM-1 Series Remote Microphone installation
document.
Quad Intelligent Audio Transponder - XPIQ See product description on page 22.
CAUTION:
! Make sure to install system components in the sequence listed below. Failure to do so can damage
the control panel and other system components.
WARNING:
! This system contains static-sensitive components. Always ground yourself with a proper wrist strap
before handling any circuits. Use static-suppressive packaging to protect electronic assemblies
removed from the unit.
CAUTION:
! Unless you are familiar with the placement of components within this backbox, only use the knockout
locations provided for conduit entry.
CAB-4
Series
CAB-4
Backbox,
Series Keyholes
D-size
Backbox, 2 places
(four-row)
A-size
(one-row)
Mounting holes
nfs640cabinetmountingholes.cdr
2 places
The CHS-M2 accepts four layers of equipment, including the control panel. The control panel fills
three positions in the first-installed layer, its integral power supply occupies two positions in the
next two layers, and the optional display occupies the two left-most slots in the fourth layer (flush
with the door). Panel circuit modules and other modules of the same sizing can be mounted in
several layers, depending on the desired configuration; see Table 3.2 to determine hardware. Some
equipment, such as the XLS-NCA, may be door-mounted directly in front of the control panel. The
BMP-1 Blank Module Plate covers unused positions in a dress-panel, providing another mounting
location for some modules, such as TM-4 (see BMP-1 Product Installation Drawing for details).
Mounting location
for LEM-320
nfs640-chs-m2-11-03.wmf
KDM-2
NOTE: When designing the cabinet layout, consider separation of power-limited and
non-power-limited wiring as discussed in Section 3.11 “UL Power-limited Wiring Requirements”.
Control panel or Option board, 2nd layer 4 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.
Option board, 1st layer (includes LEM-320)
Option board, 2nd layer Option board, 3rd layer 4 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.
Chassis Option board, 4th layer Attaches directly to flanges on chassis. (Screws provided with option
(flush with door) boards & panel circuit modules)
Chassis Panel circuit module Attaches directly to flanges on chassis. (Screws provided with option
(flush with door) boards & panel circuit modules)
Chassis rail KDM-2 (lower edge) 2 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.
Dress panel Option board BMP-1 attaches to dress panel; option module attaches to BMP-1
DP-DISP or ADP-4B (screws provided with option module).
Note: The initial release of chassis CHS-M2 used L-brackets and stand-offs of different lengths than the current model; refer to
Doc. 51927, Rev A (Form Number 95-7673).
Table 3.2 Stand-off Lengths
NOTE: For initial release of XLS140, mounting instructions were different. Refer to the
installation manual shipped with the panel (Rev A).
1. Verify height of the mounting stud in the backbox. In older backboxes, the stud must be
shortened to prevent damage to the XLS140-CPU. All electronics must be removed from the
backbox before shortening. See instructions in the warning below.
WARNING:
! For retrofit applications, verify the height of the backbox’s mounting stud on left side under CPU, as
shown in Figure 3.3 below. Stud height must not exceed 0.375 in. (9.525 mm). Early versions of the
CAB-4 Series backboxes and all CAB-3 Series backboxes have studs that require shortening.
Failure to shorten this 0.625 in. (15.875 mm) mounting stud will cause damage to the control panel’s
CPU. Remove electronics from backbox, permanently mount empty CHS-M2 chassis to backbox,
apply nut to mounting stud to protect threading, then cut stud to proper length. Reinstall electronics
as discussed in the steps below.
WARNING:
! Do not cut without washers and nuts in place to protect threading. Wear protective eye covering.
CHS-M2-11-03-CAB-3.wmf
Figure 3.3 Using the Redesigned CHS-M2 with Older Backboxes
CAUTION:
! It is critical that all mounting holes of the XLS140 are secured with a screw or standoff to insure
continuity of Earth Ground.
CHS-M2-0604-assy.wmf
Attach two (0.937 inch, 23.8 mm) stand-offs
to chassis rail; screw keypad mounting
plate to the stand-offs.
Figure 3.4 Locating and Aligning Stand-offs for Keypad/Display and Panel Circuits
(Chassis CHS-M2 shown)
If the XLS140 and XLS-NCA are being used as a stand-alone pair, each device must be
programmed separately using VeriFire Tools in its off-line programming mode. Because the
VeriFire Tools computer also uses the network/service port, XLS140 and XLS-NCA must be
temporarily disconnected for programming. If the XLS140 with XLS-NCA is connected to a
network, there are two additional options for programming: either connect the VeriFire Tools
programming PC to the network port on the NCM board, or program the XLS140 through another
network node. (See VeriFire Tools on-line help for details.)
TB1
B+ A+ B- A-
TB1
XLS140-CPU.
3. Lay the LEM onto the standoffs and B+ A+ B- A-
connect the Loop Expander Module
(LEM) into the stacker-connector
attached to J3.
4. Attach LEM using screws provided with
the module.
Lem-slc.cdr
5. After LEM is mounted on the control
panel, connect the SLC loops to TB1 on LEM-320PCA J1
LEM-320 XLS140-CPU
Stacker-connector
J3
J1
CAUTION:
! If the stacker-connector is installed incorrectly, the short-pin end of the plug can fail to make a secure
connection when plugged through the back of the LEM.
NOTE: See the XLS-NET Manual and NCM Installation Document for wiring diagrams and
system configuration information. See the BMP-1 Product Installation Drawing if considering
mounting the module behind blank module plate in a dress plate or annunciator backbox.
NOTE: An option board can be mounted above a Loop Expander Module or Network Control
Module; for ease of access, be sure to complete installation of those devices before mounting a
second layer.
1. Slide the tabs at the bottom of the option board into slots on the chassis as shown in Figure 3.7.
2. Lay the board back onto the flanges so that the studs line up with mounting holes on the option
board.
3. Attach the option board using screws provided with the module.
NOTE: See the BMP-1 Product Installation Drawing for details if considering mounting the
module behind blank module plate in a dress plate or annunciator backbox. This dress plate is
suitable for modules that do not need to be visible or accessible when the door is closed.
Module
Screw
Slots
nfs640-mnticm.cdr
Shown with CHS-M2 Shown with CHS-4N
Chassis CHS-4N
Single-space
blank plate
WARNING:
! Several sources of power can be connected to the control panel. Before servicing the control panel,
disconnect all sources of input power including the battery. While energized, the control panel and
associated equipment can be damaged by removing and/or inserting cards, modules, or
interconnecting cables.
3.6.1 Overview
Complete all mounting procedures and check all wiring before applying power. Electrical
connections include the following:
• Primary AC power source – 120 VAC, 50/60 Hz, 3.0 A (XLS140E uses 240 VAC, 50/60 Hz,
1.5 A) from line voltage source. Overcurrent protection for this circuit must comply with
Article 760 of the National Electrical Code (NEC) and/or local codes. Use 12 AWG (3.31
mm2) wire (maximum) with a 600-volt rating.
• Secondary power source – 24 VDC from batteries, installed in the control panel (or in an
optional battery cabinet). Secondary (battery) power is required to support the system during
loss of primary power.
• External power sources – 24 VDC power for Smoke Detectors (4 wire), NACs, and
Annunciators.
See Appendix B “Electrical Specifications” for details and overall installation guidelines.
TB2
Hot
Ground
(Earth)
Battery (-)
BATT –
nfs640-acdc.cdr
Battery (+)
BATT+
TB1
CAUTION:
! While checking AC power, make sure batteries are not connected.
Follow the sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is Step 16.
Component Status
Control panel circuit The green AC Power indicator on; the system Trouble indicator on because batteries are not connected.
board
Each panel circuit The yellow Trouble indicator may come on for approximately 10 seconds after applying AC power. (This
module only applies to an unconfigured system.)
Each auxiliary power The yellow Trouble indicator comes on because batteries are not connected.
supply
WARNING:
! Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and can destroy
fabrics. If contact is made with sulfuric acid, immediately flush skin or eyes with water for 15 minutes
and seek immediate medical attention.
WARNING:
! Do not connect the Battery Interconnect Cables (P/N 75560 and 75561) at this time. Make this
connection AFTER initial system primary powerup. Follow sequence of steps in Section 3.2
“Installation Checklist”, Table 3.1; this is Step 17.
Batteries (2) are installed in the control panel cabinet or in a separate battery cabinet which can be
mounted below the control panel or up to 20 feet (6.096 m) away from the control panel, in conduit
in the same room.
Connect the battery as follows (see Figure 3.10 above):
1. Install batteries (2) into bottom of cabinet or into separate battery cabinet.
2. Connect the red cable from TB1(+) on the control panel to the positive (+) terminal of one
battery.
3. Connect the black cable from TB1(–) on the control panel to the negative (–) terminal of the
other battery.
4. Connect the remaining cable between the negative (-) terminal on the first battery to the
positive (+) terminal on the second battery.
Non-resettable Resettable
Power Power
+ – + –
TB7
nfs640-dcout.cdr
Figure 3.11 Power Supply DC Outputs - TB7
24 VDC Resettable Power Circuit (Four-Wire Smoke Detectors). The power supply
provides a single 24 VDC filtered, power-limited, resettable power circuit for devices that require
resettable power (such as four-wire smoke detectors). This circuit is power-limited, but must be
supervised. To provide supervision, install a UL-listed end-of-line power supervision relay (such as
the EOLR-1) after the last device. Connect the power supervision relay normally open contact in
series with an Initiating Device Circuit (IDC). The four-wire power circuit energizes the power
supervision relay. When you reset the system, the control panel removes power from these
terminals for approximately 15 seconds.
Connect external field wires to the power supply terminals TB7 RESET(+) and (–) to provide up to
1.25 A of current for powering four-wire smoke detectors. See Figure 3.11 above.
24 VDC Non-resettable Power Circuit. The power supply provides one 24 VDC filtered,
power-limited, non-resettable power output, capable of up to 1.25 A. Use this circuit to power
devices that require low-noise 24 VDC power (such as annunciators or the TM-4).
Connect external field wires to power supply terminals TB7 NONRST(+)and(–) to provide up to
1.25 A of non-resettable current for powering external devices such as annunciators. See
Figure 3.11 above.
CAUTION:
! During system reset, power remains at terminals TB7 NONRST(+)and(–).
UL-listed ELR-2.2K,
1/2 W (supplied)
B+ B- A+ A-
TB6 - NAC#1
B+ B- A+ A-
TB5 - NAC#2
nfs640-nacout.cdr
B+ B– A+ A– B+ B– A+ A– B+ B– A+ A–
B+ B- A+ A-
TB4 - NAC#3
nfs640-NACS.cdr
NOTE: Any NAC can be programmed as a releasing circuit, but only one releasing device
per circuit is allowed. For more information, refer to Section 4.5 “Releasing Applications” in this
manual and the XLS140 Programming Manual. Refer to the Device Compatibility Document for
UL-listed compatible releasing devices. Sample connections for NAC terminals are shown in
Figure 3.13. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 3.1; this is part
of Step 6.
TB11
SW1 is set to Supervisory
TB8 TB9 TB10 SW1 SW5 SW5 is set to Security
Move switch to opposite
SUPV ALARM SECUR ALARM position to set to Alarm.
nfs640-relay.cdr
Figure 3.14 Form-C Relay Connections
SW6
DISAB ENAB
condition. If the main board’s microcontroller fails and
SW8
an alarm is reported by any detector or a monitor 2 4
SW9
module that has backup reporting enabled, the NAC
SW7
will turn on if the corresponding switch was enabled.
The alarm will activate during microcontroller failure
nfs640-sw6-9.cdr
regardless of the settings of Switch 6-9.
• Switch 6 - NAC#1
• Switch 7 - NAC#2
Figure 3.15 Backup Alarm
• Switch 8 - NAC#3 Switches
• Switch 9 - NAC#4
So, for example, if Switch 6 and Switch 8 were enabled at the time of an alarm during
microcontroller failure, NAC#1 and NAC#3 would activate. Follow sequence of steps in Section
3.2 “Installation Checklist”, Table 3.1; this is Step 7.
Figure 3.16 shows one configuration that meets these UL requirements. The first two rows of
modules are configured with at least a 0.25 inch (6.35 mm) separation between power-limited and
nonpower-limited wiring; AC and battery wiring is routed away from power-limited wiring.
Power-limited Circuits
Nonpower-
limited Power-limit
circuits ed
circuits
nfs640-pwrlmtwir.cdr
To cabinet-mounted battery
NOTE: AC and battery wiring are not power-limited. Maintain at least 0.25 inches (6.35 mm)
between power-limited and non power-limited circuit wiring. Install tie wraps and adhesive squares
to secure the wiring. Use a power-limited source for relay output on terminals TB8 – TB11.
Refer to Section 2.10 “Panel Circuit Modules” for a complete list of modules and their expanders.
Steps 1 & 2
nfs640-pcmods.cdr
Steps 4 & 5
MODULE MODULE
TYPE TYPE
LAMPS LAMPS MODULE MODULE MODULE MODULE MODULE MODULE
TYPE TYPE TYPE TYPE TYPE TYPE
SWITCH SWITCH
LAMPS LAMPS
LAMPS LAMPS LAMPS LAMPS
SWITCH SWITCH
SWITCH SWITCH SWITCH SWITCH
Group of panel
modules in second
cabinet row
nfs640-icmribbon.cdr
TYPE TYPE
LAM PS LAMPS LAMPS LAMPS LAMPS LAMPS
LAM PS LAM PS
SWITCH SWITCH SWITCH SWITCH SWITCH SWITCH
SWITCH SWITCH
Group of panel
modules in third
cabinet row
ICM-4RK
J5
nfs640-icmconn.cdr
J6
J5
ICE-4
J6
nfs640-icmnac.cdr
J5 ICE-4
ICM-4RK/ICE-4 Jumpers
JP1
JP2
J5 J6
ICM4wire-YB.cdr
B+ A+ A– B– B+ A+ A– B– B+ A+ A– B– B+ A+ A– B–
CREEXPCO-RK.cdr
CONTROL CONTROL
RELAY RELAY
3.13.2 Installation
To install the Auxiliary Relay Module in the chassis:
• Select a mounting position for the module on the chassis.
• Install two (2) mounting stand-offs onto the studs of the chassis, at the selected location, as
shown in Figure 3.8 on page 38 and Figure 3.25. Tighten securely.
• Install three (3) support stand-offs, with screws, onto the PC board in the locations shown in
Figure 3.8 or in the two right-hand positions on the first row. Tighten securely.
• Position module over the stand-offs on the chassis; fasten the module to the chassis with the
two (2) retaining screws. Tighten securely.
• Connect one end of the Cable (P/N 71092) to plug P1 on the ARM-4.
Note: The other end of the cable is connected to jumper JP5 on the CRM-4RK or CRE-4.
• Connect all available external wiring at this time. Refer to Section 3.13.3 “Field Wiring an
Auxiliary Relay Module”.
Terminal
Assignments
(typ. 4 places)
NC NO C Com K1 K2 K3 K4 NC NO C
– + + + +
P2
P-1
Connection for
Cable P/N 71092 P1
ARM-4.cdr
Figure 3.25 ARM-4 Stand-off and Terminal Locations
NOTE: For more information, refer to Section 3.11 “UL Power-limited Wiring Requirements”.
The table contains contact ratings for relays K1-K4 on the ARM-4 module:
Contacts
Resistive Load Normally Open (N.O.) Normally Closed (N.C.)
125 VAC 20 A 10 A
30 VDC 20 A 10 A
NOTE: You can also use the EIA-232 printer interface with UL-listed information technology
equipment, such as personal computers, to monitor the control panel for supplementary
purposes.
This section contains information on connecting a printer to the control panel and for setting the
printer options.
Connecting a Remote PRN Series Printer
Remote printers require a 120 VAC, 50/60 Hz primary power source. If required for the fire alarm
system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a
secondary power source (battery backup). Because a secondary power source is not provided, use a
separate Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective Signaling. You
may use your building emergency power supply, so long as it meets the power continuity
requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB14 terminal block on the control
panel as shown in Figure 3.26.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the remote printer.
Tighten securely.
nfs640-prn5conn.cdr
Control Panel
TB14 TB15
Keltron printer
24 VDC
connections DB-25 connector
(14 AWG, on Keltron Printer
2.08 mm2) (female socket Terminate one end of
shown) shield at backbox
TB7
nfs640-keltconn.cdr
Control Panel
TB14 TB15
DB-25 connector
on CRT-2 (female
socket shown) Terminate one end of
shield at backbox
PRINTER PC/CRT
TX RX REF TX RX REF
Control
nfs640-crt2conn.cdr
Panel
TB14 TB15
NOTE: This section covers installation only; for information on how the CRT-2 functions as part
of the fire alarm system, see the XLS140 Operations Manual.
Table 3.7 Standard CRT-2 Settings for Use with XLS140 (Sheet 1 of 2)
Table 3.7 Standard CRT-2 Settings for Use with XLS140 (Sheet 2 of 2)
3.14.5 Connecting a PC
A PC can be hooked up to the Control Panel EIA-232 port (J1) to allow the VeriFire Tools
programming utility to upload and download the operating program of the control panel. Refer to
the insert in the VeriFire Tools CD and to the program’s on-line help function for instructions.
NOTE: Download operations that change the basic program of the control panel must be
performed by responsible service personnel in attendance at the control panel. After downloading
a program, test the control panel in accordance with NFPA 72-1999.
7 3 2
To EIA-232 port of next
CRT-2 or PRN (female socket shown)
Note: For wire requirements, see Table B.1 in Appendix B “Electrical Specifications”.
Wiring
Maximum wiring distance of an SLC using 12 AWG (3.31 mm2) wire is 12,500 feet (3810 meters)
total twisted-pair for Style 4, Style 6 and Style 7 circuits.
Capacity
The XLS140 provides one (1) SLC, with a total capacity of 318 intelligent/addressable devices:
• 01-159 intelligent detectors
• 01-159 monitor and control modules
An optional expander board provides one (1) additional SLC, with the same capacity.
Installation
This control panel supports one or two SLC loops; a second SLC loop is obtained by installing an
LEM-320 module. SLC loop #1 connects to TB16 on the control panel; SLC loop #2 connects to
TB1 on the LEM-320. For details on designing, installing and configuring SLC loops, see the SLC
Wiring Manual.
SLC1
B+ A+ B- A-
B+ A+ B- A- TB1
TB16
SLC Loop #1 Connections SLC Loop #2 Connections
on FACP’s main circuit board on Loop Expander Module
SLC B SLC A
4.1 Overview
NOTE: This application can also be done with the TM-4 Transmitter; refer to the Transmitter
Module TM-4 document for more details.
Ferrite cores
FACP Cabinet P/N 29090
TB13
24 VDC EIA-485
Nonresettable power (ACS Mode)
nfs640-udact.cdr
UDACT in ABS-8R
(shown with cover removed)
Figure 4.1 Typical Wiring Diagram for a Central Station Fire Alarm System
NOTE: Install a UL-listed 120 ohm End-of-Line resistor (P/N 71244) UDACT TB1 terminals 3
and 4 if this is the last or only device on EIA-485 line.
UDACT
XLS140
Protected Premises Unit
For bypass of security zones, use the DISABLE routine (covered in the Status Change section of
the XLS140 Operations Manual) for Security type devices.
WARNING:
! Damage can result from incorrect wiring connections.
Connect to
J10 “Tamper”
nfs640-sts1.cdr
4.4.4 Programming
The control panel can communicate with any number of security devices. To do so, program the
points as follows:
1. Select the address of the module(s) to be used for security.
2. Select the Type Code SECURITY.
NOTE: For detailed instruction on programming Type Codes, refer to the XLS140 Programming
Manual.
UL-listed, normally-closed
security switch
XLS-MM-A
WARNING:
! Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!
4.5.1 Overview
This control panel can be used for agent release or preaction/deluge control applications. In a
properly configured system with compatible, listed actuating and initiating devices, this control
panel complies with the following NFPA standards for installation in accordance with the
acceptable standard:
Standard Covers
NFPA 12 CO2 Extinguishing Systems
NFPA 12A Halon 1301 Extinguishing Systems
NFPA 13 Sprinkler Systems
NFPA 15 Water Spray Systems
NFPA 16 Foam-Water Deluge and Foam-water Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 2001 Clean Agent Fire Extinguishing Systems
4.5.2 Programming
The control panel supports up to ten releasing software zones. You can map these zones to activate
Control Panel releasing outputs and XLS-CM-N/TC810N1013 modules. Program the XLS-CM-N/
TC810N1013 module for the appropriate type code according to the chart below:
4.5.3 Wiring
References to wiring diagrams for releasing applications:
To connect Refer to
A releasing device to the control panel. Section 4.5.4 “Connecting a Releasing Device to the Control Panel”.
A releasing device to the XLS-CM-N/ Section 4.5.5 “Connecting a Releasing Device to the XLS-CM-N/TC810N1013
TC810N1013 Module. Module”.
An NBG-12LRA Agent Release-Abort Station. Section 4.5.6 “Connecting an NBG-12LRA Agent Release-Abort Station”.
nfs640-relconn1.cdr
+
REL-2.2K (Use with Type Code
Rel Ckt ULC, or see Circuit
Note: See text below for circuit requirements. Requirement 4.)
WARNING:
! Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!
Compatible UL-listed
24 VDC releasing device 9 0
6 7 8 9 10
5
8
4
3
11
12 1 Non-resettable
– 7
2
TENS
1 0 1514
13
2 24 VDC Power
6 7 8 9
6 4
5
3 –
Brown Red 3
+ 5
2
10
4
+
Relconn-fcm.cdr
REL-47K ONES
ADDRESS
LOOP
(Use with Type Code
Rel Ckt ULC, N.C. Supervision
or see Circuit
Relay Contact Power Supervision
Requirement 3.)
Part of EOLR-1 Relay (EOLR-1)
XLS-CM-N
8
4
3 1 Non-resettable
– 2
7 TENS07 8
1
2 24 VDC Power
6 9
6
5
-
Relconn-TC810a.cdr
Brown Red
4
3 3
+ 5
2
10
4
+
REL-47K LOOP
ONES
ADDRESS
(Use with Type Code
Rel Ckt ULC, N.C. Supervision
or see Circuit Power Supervision
Requirement 3.) Relay Contact
Relay (EOLR-1)
Part of EOLR-1 TC810N1013
c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit.
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit
device wiring and any power-limited circuit wiring.
Violet Red
+ +
Normal Non-resettable +24 VDC
from main power supply
ELR mode R-47K Release
supervised and
–
NBG640-NBG12LRA.cdr
power-limited 1
XLS-CM-R/
6
TC810R1024
2 +
C.
5 4
N.C. N.O.
System
Common (–)
24 VDC power
from FACP’s
0
main power supply
24 VDC UL-listed 7- 1–
XLS-CM-N/
releasing device TC810N1013 2 +
6+ 3– –
Brown Red N.C. Supervision 4 +
REL-47K Relay Contact +
(use with Type Code
Rel Ckt ULC)
Power Supervision
Relay (EOLR-1)
NOTE: If using the on-board NACs, see Circuit Requirements for Section 4.5.4 “Connecting a
Releasing Device to the Control Panel” on page 65. If using XLS-CM-N/TC810N1013, see Circuit
Requirements for Section 4.5.5 “Connecting a Releasing Device to the XLS-CM-N/TC810N1013
Module” on page 66.
WARNING:
! Do not rely on disable/enable software settings to lockout releasing devices.
notification appliances active. Replace any battery with a terminal voltage less than 21.6 VDC
and reapply AC Power.
NOTE: The battery test requires fully charged batteries. If batteries are new or discharged due
to a recent power outage, allow the batteries to charge for 48 hours before testing.
WARNING:
! Batteries contain Sulfuric Acid which can cause severe burns to the skin and eyes and damage to
fabrics.
• If a battery leaks and contact is made with the Sulfuric Acid, immediately flush skin and/or
eyes with water for at least 15 minutes. Water and household baking soda provides a good
neutralizing solution for Sulfuric Acid.
• If Sulfuric Acid gets into eyes, seek immediate medical attention.
• Ensure proper handling of the battery to prevent short circuits.
• Take care to avoid accidental shorting of the leads from uninsulated work benches, tools,
bracelets, rings, and coins.
WARNING:
! Shorting the battery leads can damage the battery, equipment, and could cause injury to personnel.
Quantities List the number of devices powered by the Panel Output (TB2) and the Accessories
Output (TB6). Devices powered by the Accessories Output draw current directly from the panel.
Devices powered by the Panel Output draw current through the fire panel’s connection to the power
supply. Use these quantities to calculate total current draw of each set of devices in calculation
columns 1, 2, and 3.
Calculation Column 1 (Primary, Non-Fire Alarm Current in amps) Add the contents of
calculation column 1 to get the current drawn from the power supply during a non-alarm condition,
with AC power applied. This current draw cannot exceed 3 A without an auxiliary power supply.
Calculation Column 2 (Primary, Fire Alarm Current in amps) Calculation column 2 lets
the system designer determine the current load that the power supply must support during a fire
alarm. The total current draw during a fire alarm cannot exceed 6 A without an auxiliary power
supply.
Typically, a system should contain capacity to activate all output circuits and relays, and support
fire alarms on no less than 10% of Initiating Device Circuits, subject to the requirements of the
Authority Having Jurisdiction (AHJ).
The Control Panel provides power for Notification Appliance Circuits. Refer to the Device
Compatibility Document for 24 VDC notification appliances that are UL- and ULC-listed for fire
alarm systems.
Calculation Column 3 [Secondary (Battery) Non-Alarm Current] Column 3 lets the
system designer calculate the non-fire alarm current drawn from the secondary source in a non-fire
alarm condition during AC power loss.The non-fire alarm current is required to complete the
standby battery calculations. After summing all current draws, insert the total in Table A.3.
Current
Device Quantity Total Current/Type
(in amps)
APS-6R* [ ] X 6 =
†
AA-30 [ ] X 3 =
AA-1202 [ ] X 7.3 =
NOTE: The Secondary Fire Alarm Load cannot exceed the following:
• 9 A with BAT-12120 batteries (12 V, 12 AH).
• 12 A with BAT-12250 batteries (12 V, 26 AH).
• 20 A with BAT-12550 batteries (12 V, 55 AH).
NOTE: If using an auxiliary power supply such as APS-6R, ACPS-2406, or audio amplifiers,
refer to the documentation for that equipment.
Batteries
The control panel uses only sealed lead-acid batteries for secondary standby power. Maximum
battery capacity for the control panel’s integral main power supply is 55 AH. Batteries larger than
25 AH require the XLS-LBB or other UL-listed battery cabinet. The table below contains
specifications for batteries that can be used with the control panel; see also Appendix A.3.2
“Calculating the Battery Size”:
Charger Description Specifications
Main Power Supply An internal battery charger for 12 Dual Rate: High Charge: 29.1 VDC
AH to 55 AH Normal Float Charge: 27.6 VDC
Charging Current: 2.0 A max (1.5 A typical)
CHG-120 An external battery charger Dual Rate: High Charge: 28.1 VDC
Battery Charger designed to charge lead-acid Normal Float Charge: 27.6 VDC
batteries between 25 AH and 120 Charging Current: 4.5 A
AH
ACPS-2406 An internal battery charger for Normal Float Charge: 27.6 VDC
Auxiliary Charger/ 7AH to 25 AH Charging Current: 1.1 A max (0.750 A typical)
Power Supply
Output Relays
Output relays for Alarm, Trouble, Supervisory, and Security are available on power supply
terminals TB8, TB9, TB10, and TB11 respectively.
Contact ratings: 2.0 A @ 30 VDC (resistive)
Four-wire Smoke Detector Power
Control Panel terminals TB7 RESET (+) and (–) supply filtered, low-noise power for four-wire
smoke detectors. Specifications are:
• Nominal voltage: 24 VDC
• Maximum rated current: 1.25 A DC
• Maximum ripple voltage: 176 mVrms
Refer to the Device Compatibility Document for compatible 24 VDC detectors.
Power Output
Control Panel terminals TB7 NONRST (+) and (–) supply one (1) power-limited circuit available
to power external devices, such as notification appliances and annunciators.
• Nominal voltage: 24 VDC
• Maximum rated current: 1.25 A DC
• Maximum ripple voltage: 176 mVrms
Refer to the Device Compatibility Document for compatible devices and notification appliances.
NOTE: The Control Panel provides a total of 6.0 A of power in alarm (3 A in standby), shared by
all internal circuitry and external provisions (24 V resettable and non-resettable). For power
requirements, refer to the power supply calculation tables in Appendix A.
NOTE: If running an SLC in conduit with Notification Appliance Circuits, you can reduce
problems by exclusively using electronic sounders (such as the Spectralert or MA/SS-24 Series)
instead of more electronically noisy notification appliances (such as electromechanical bells or
horns).
Circuit Distance
Circuit Type
Function
Wire Requirements
(feet/meters) Typical Wire Type*
SLC Connects to Twisted-unshielded pair, 12 to 18 AWG 12,500 ft. (3,810 m) 12 AWG (3.31 mm2)
(power limited) intelligent and (3.31 to 0.82 mm2). 50 ohms maximum per 9,500 ft. (2,895.6 m) 14 AWG (2.08 mm2)
addressable length of Style 6 & 7 loops. 50 ohms per 6,000 ft. (1,828.8 m) 16 AWG (1.31 mm2)
modules. branch maximum for Style 4 loop. 3,700 ft. (1,127.76 m) 18 AWG (0.82 mm2)
EIA-485 Connects to Twisted-shielded pair with a characteristic 6,000/1829 16 AWG (1.31 mm2)
(power limited) XLS-LCD-80, impedance of 120 ohms. 18 AWG (0.82 (max)
ACS modules, mm2) minimum.
or TM-4
Transmitter
NAC XLS-CM-N/ 12-18 AWG (3.31 to 0.82 mm2). To meet 1.2 V drop, 12 to 18 AWG (3.31 to
Notification TC810N1013, At alarm current level, no more than a 1.2 or sized to provide 0.82 mm2)
Appliance XP6-C (power V drop at the end of the circuit, or sized to the minimum rated
Circuit limited) provide the minimum rated operating operating voltage of
voltage of the appliances used. the appliances used.
24 VDC Power To TM-4 12-18 AWG (3.31 to 0.82 mm2). To meet 1.2 volt drop 12 to 18 AWG (3.31 to
Runs Transmitter, Size wire so that no more than 1.2 V drop 0.82 mm2)
(power-limited) Annunciator and across wire run from supply source to end
XLS-CM-N/ of any branch.
TC810N1013
modules
CHG-120 External battery 12 AWG (3.31 mm2) in conduit 20/6.1 (max) 12 AWG (3.31 mm2)
charger
NOTE: Lightning arresters required on circuits extending between buildings; 999 meter length
maximum to meet UL 1459.
F NCM-W/F (Overview) 19
NFPA Applications
FCPS-24, FCPS-24S (Overview) 20
NFPA 72 Central or Remote Station Fire Alarm
Fire Fighters Telephone, see also Voice Alarm System
System 60
Manual 26
NFPA Applications (Overview) 59
Fire/Security Applications 61–63
Nonpower-limited circuits
FlashScan® (Overview) 21
UL wiring requirements 43, 44
Form-C relays 22, 23, 25, 42, 49, 78
Notification Appliance Circuits, see NACs
Four-wire Smoke Detector
Specifications 78 O
I Operating Power 79
Operational Checks 69
ICM-4RK (Overview) 25
Output relays
see also Panel Circuit Modules
Connections 22, 23, 25, 42, 49, 78
Installation
Specifications 78
Checklist 30
Preparation 29 P
J Panel Circuit Modules
ICM-4RK Connections 47
Jumper locations 16, 17
ICM-4RK Field-wiring 48
ICM-4RK 47
ICM-4RK Jumpers 47
K ICM-4RK Resistors 48
KDM-2 ICM-4RK/ICE-4 Connections 46
Installation steps 33 Installation steps 37, 44
Keltron printer (Overview) 25 Mounting Expander Boards 45
Keltron, see also Printers 52 Overview and complete list 25
Ribbon cables 45
L see also ICM-4RK, ICE-4, CRM-4RK, CRE-4,
LDM-32 (Overview) 23 VCM-4RK, DCM-4RK, VCE-4 44
LDM-R32 Periodic Testing 69
non-power-limited circuits 44 Power
LDM-R32 (Overview) 23 AC Power Checklist 40
LED locations 17 AC power connections 39, 40
LEM-320 (Overview) 19 AC specifications 77
lockout 69 Auxiliary Power 41
Loop Expander Module DC power connections 40, 41
Installation steps 36 Installation steps 39
Power specifications 39, 78
M power supervision relay 66, 67
Main power supply 15 Power supply calculations 71, 73, 74, 75, 76
Maintenance 69 Power-limited Wiring Requirements 43
microcontroller failure 43 primary display 14, 35
Monitor Modules (Overview) 22 Printers 55
Mounting Installation 51–55
LEM 36 Keltron printer Connections 52
Panel Circuit Modules 45 Overview 24
Multi-Input/Output Modules 22 PRN series (overview) 25
PRN series connections 51
N PRN settings 52
NACs (Notification Appliance Circuits) PRN/CRT combination 55
Backup option 43 Proprietary Security Alarm Applications
NAC Connections 42 Wiring 63
Releasing applications 42, 43, 64, 65 Protected Premises Unit 60
Specifications 78
NBG-12LRA 67 Q
NCM-W/F, see Networking Quad Intelligent Audio Transponder
Networking 37 see also XPIQ 22