RAD-1 Catalog Page
RAD-1 Catalog Page
RAD-1 Catalog Page
Description
The Kele RAD-1 is a wall mounted remote alarm indication station
mounted on a stainless steel plate. Any contact closure alarm initiating
device that can switch 24 VAC or DC can be used with the RAD-1. When
24 VAC or DC is applied to the RAD-1 through an alarm initiating device,
the red alarm LED will light, the horn will sound and the alarm status relay
2 will energize. If an initial alarm delay has been set, when 24 VAC or DC
is applied, the red alarm LED will blink until the delay period has expired
when it will light continuously, the horn will sound continuously and the
relay will energize.During an alarm (24V applied to the RAD-1), the horn
may be silenced by momentarily pressing the silence switch. The alarm
LED will remain lighted, and the alarm status relay will remain energized
when the horn is silenced until the alarm condition is cleared (24V
removed). If an alarm repeat after silence time has been set, the horn will
ALARMS & INDICATION
SEQUENCE OF OPERATION
When 24 VAC or VDC is applied to the RAD-1 through an alarm-initiating
device, the red alarm LED will light, the horn will sound, and the alarm RAD-1
status relay will energize. If an initial alarm delay has been set, when
24 VAC or VDC is applied, the red alarm LED will blink until the delay
period has expired. Then it will light continuously, the horn will sound
continuously, and the relay will energize. If power is interrupted, the RAD-1
will reset to normal state. Wiring
During an alarm (24V applied to the RAD-1), the horn may be silenced
by momentarily pressing the silence switch. The alarm LED will remain
lighted, and the alarm status relay will remain energized when the horn
is silenced until the alarm condition is cleared (24V removed). If an alarm ON OFF
repeat after silence time has been set, the horn will re-sound at the end Alarm Repeat after
Silence Time*
8 4 Repeat
time in
of the repeat time. If the relay-follows-horn is set to ON, the alarm status SW6–SW8 OFF = No delay 7 2minutes
SW6 ON = 1 minute
relay will de-energize when the horn is silenced and re-energize when the SW7 ON = 2 minutes 6 1 (add)
SW8 ON = 4 minutes Alarm initiating
horn sounds at the end of the repeat-after-silence time. Initial Alarm Delay Time* 5 16 device
SW1–SW5 OFF = No delay
SW1 ON = 1 second 4 8 +
24 +
If a pulsed (instead of continuous tone) horn is desired, the horn-pulsed SW2 ON = 2 seconds 3 4
Delay
time in VAC/
SW3 ON = 4 seconds
can be set to ON. If both the horn pulsed switch and the relay-follow-horn SW4 ON = 8 seconds 2 2
seconds VDC
– –
(add)
switch are set to ON, the alarm status relay will energize and de-energize SW5 ON = 16 seconds
1 1 NO NO
with the pulsed horn.
Relay COM COM
Alarm
Relay to follow horn 5 RLY + HRN relay
Features
Alarm repeat
after silence ON = 10X OFF = 1X 4 DLY X 10 NC NC
Initial alarm ON = 10X OFF = 1X 3 RPT X 10
• Red alarm LED delay time
Horn ON = Pulse OFF=Continuous 2 PULSE
• Alarm horn, continuous tone or pulsed
1
• Alarm horn silence switch Silence Byass BYP
RAD-1
• Adjustable alarm delay time ON
• Adjustable alarm repeat time
• Alarm status SPDT relay
• Relay operates with the alarm horn option
• Silence bypass-user can disable the mute button
Specifications
Supply Voltage 24 VAC @ 100 mA or 24 VDC Alarm Relay SPDT, 0.5A @ 24 VAC, 1.0A
@ 34 mA @ 30 VDC, Follows horn or lamp
Alarm Delay Time None, or 1 to 31 seconds in one-second selectable
increments, or 10 to 310 seconds in Connections Screw terminals, 22 - 14 AWG wires
10-second increments Mounting Brushed stainless steel plate mounts to
Alarm Horn Continuous or pulsed tone, standard single junction box, with two
70 db min screws provided
Alarm Repeat Time None, or 1 to 7 in one-minute increments, Dimensions 4.5"H x 2.75"W x 1.0"D
or 10 to 70 minutes (11.4 x 7.0 x 2.5 cm)
in 10-minute increments Weight 0.19 lb (0.07 Kg)
Approvals RoHS
Warranty 18 months
ORDERING INFORMATION
MODEL DESCRIPTION
RAD-1 Remote alarm indication station