1 CWSJVZ Attachment en ENU

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Reason:

Incorrect parameters set in OB100/FB1


CALL "RUN_UP" , "gp_par"
MCPNum :=1
MCP1In : = P#E 16.0
MCP1Out : = P#A 16.0
MCP1StatSend : = P#A 400.0
MCP1StatRec : = P#A 404.0
Parameters MCP1StatSend and MCP1StatRec = max. A 124/ A 252 for PLC 315/317!

System response:
Diagnostic buffer of the PLC module, e.g. PLC 317-2DP 2AJ10:

Order number / designation Component Edition


6FC5 317-2AJ10-1AB0 Hardware 2218 20.71.30 06.02.2006
Firmware V 2.1.8
Module rack: 0
Slot: 2
Event 1 of 100: Event ID 16# 457F
STOP due to STOP command
Interruption point within the user program: Cyclic program (OB 1)
Priority class: 1
FB number: 15
Block address: 2
Existing operating status: RUN
Requested operating status: STOP (internal)
Internal error, incoming event
18:24:42:984 05.01.94

No entry made in the text database. Hex values are displayed.


Event ID: 16# A128
OB: 16# 01
PK: 16# 01
DatID 1/ 2: 16# 50 C0
Additional information 1 / 2 / 3: 16# 0002 0000 0043
Incoming event
18:24:42:980 05.01.94

Diagnostic buffer decoding leads to the following alarm:


Event ID: 16# A128 ==> A=Alarm, 1= incoming 28Hex =40dec
Additional information 1 / 2 / 3: 16# 0002 0000 0043 ==>
02Hex = 02dec
43Hex = 67dec
Ö incoming alarm 400267

This alarm is also displayed on the HMI.

Alarm description:
400267 access error
Explanation: MCP resp. handheld unit data could not be accessed
Response: Alarm display.
Remedy: Check MCP resp. handheld unit parameters of FB1.
Program continuation: Switch controller ON / OFF

Solution:
Configure parameters MCP1StatSend and MCP1StatRec to max. A 124 (PLC 315) resp.
max. A 252 (PLC 317).
Subject to change withput prior notice.
© Siemens AG 2008 Page 1 / 1 Edition: 14.03.2008
1-CWSJVZ-Attachment_en.doc