Okken Solution Guide 2010
Okken Solution Guide 2010
Okken Solution Guide 2010
Solution guide
2010
http://www.panelbuilders.schneider-electric.com
Contents
Presentation 2
Solution overview 10
Functional units 12
Cubicles 28
Support tools 40
Okken performances 44
1
Presentation Fields of applications
Requirements and solutions
Solutions > Intelligence in the motor control > Specific “anti-corrosion” treatment > Tightness ensured by IP54
and the electrical distribution. on conductive parts. elements.
> Dependability. > Tightness ensured by IP54 > Fault prevention by intelligent
> Rapid restarting after an incident. guaranteed parts. motor control centers (iMCC).
> Internal arc protection.
> DEP Shell certification.
Solutions > Robustness to vibrations 5G. > Feeders on dsconnectable and > Robustness to vibrations.
> Internal arc protection. withdrawable systems. > Marine certification (DNV).
> Withdrawable solutions > Specific “anti-corrosion” treatment > Salty environment.
on conductive parts.
2
Presentation Fields of applications
Functions
3
Presentation Okken solution
Motor Sys™ intelligent Power & Motor
Control Center (iPMCC)
Our MotorSys™ iPMCC solutions for continuous and critical processes were developed through
our specific expertise in energy and industrial process control management. Forming the
keystone of the energy efficiency
of your process units, they incorporate a range of functions to supply power (intelligent Power
Control Centre - iPCC), start up, control, protect and monitor your LV network electric motors
and loads (intelligent Motor Control Centre - iMCC). The breadth of the range ensures that all
types of continuous and critical process as well as specific requirements are covered.
1
Remote control and
1
offering the following > With data delivered in real time, your operational
and maintenance staff will have immediate access
benefits:
to the relevant information to control your motors
bbDependability, and electrical distribution locally or remotely.
even in severe industrial > Warning messages can be sent automatically
environments, to a mobile phone in the event of an alarm or
bbSafety of personnel group of alarms.
and assets, maintainability
and upgradability,
bb Lead time management 2Information for local operation,
and risk as well as cost maintenance and upgrading
reduction throughout your of your installation
installation's entire
Information on electrical distribution, motor operation
lifecycle.
and power consumption can be accessed.
4
Presentation Okken solution
Motor Sys™ intelligent Power & Motor
Control Center (iPMCC)
MotorSysTM iPMCC
solutions integrate
perfectly into your site
network infrastructure,
whatever the
communication
protocol, but also into
energy management
control systems
and process
control systems
2
Example of a
MotorSysTM iPMCC
solution integrated
into a site
infrastructure
5
Presentation Okken solution
Innovation
70-M cubicles
Distribution busbar
Installed in a partitioned compartment at the rear of the drawers
area, it consists of 8 mm thick bars whose cross-section depend
d e r El
nei ent
Functional units up to 630A are connected to the busbar by plug blocks.
Sch pat
Specific door for tap-off outlets make the busbar unaccessible except for the plugs of
the drawer.
The 2 busbars are linked together at the bottom with ther vertical busbars link
system.
This links are encapsulated in a metal sheet box with plastic covers.
The busbar can be single when all the drawers in the cubicle are full width.
Connections to the distribution busbars and fishplating are made without drilling.
The tightening screw devices used to secure the connection go through the gap
between the horizontal bars.
ctric
e r Ele
d
c h nei atent
S p
Auxiliaries connection
r ic
El ect Innovative mechanism allowing the auxiliary circuits to be connected with power
er
eid tent
disconnected for functionnal unit test.
h n
Sc pa
6
Presentation Okken solution
Innovation
Drawer positions
The “plug-in / test / draw-out” positions are mechanically marked by an
indexing device associated with a mechanical indicator on the drawer sides.
Plug-in
bb The functional unit is operational.
bb Power and auxiliaries are connected.
Test
bb The functional unit is not operational.
bb Only auxiliaries are connected.
bb Allow padlocking.
bb It allows the functional unit verification.
bb Allow maintenance on the process.
Draw out
bb The functional unit is not operational.
bb Power and auxiliaries are disconnected.
bb Allow maintenance on the process.
Withdrawn
bb The drawer can be fully extracted.
bb Allow quick replacement.
bb Allow switchboard live change.
7
Presentation Okken solution
Implementation
Continuity of supply
> Withdrawable feeders (in rack) for rapid workings.
> The switchboards must be reconfigured live.
> Rapid restart after an incident.
8
Presentation Okken solution
Implementation
2 levels of protection
5 levels of service
Operation
concerned functional unit, but
test of the control system
possible before the resumed
operation.
Shutting down the whole switchboard. Shutting down only Shutting down only the concerned functional unit
Maintenance
the concerned without connections handlings.
functional unit with
connections
handlings.
Shutting Addition of a Addition of a functional unit without shutting down the switchboard, free
addition in non-equiped spare slots.
Evolution
down the functional unit in
whole pre-equiped spare
switchboard. slots.
9
Solution overview PCC device cubicles
wer ower
igh po High p Mixed
Very h ers eders eders
o m e r s / feed c o m ers / fe ers / fe
inc in in c o m
cubicle cubicle cubicle
10
ized n
Optim Optim
ized nsatio
omers
/ Compe witch
wer inc ers / onic Fuse-s
hig h p o le o w e r incom & harm s cubic
le
s cubic high p g feeder
filterin
le
feeder s cubic
feeder
NW08-32 NT08-16 - -
Power factor
NW08-32 NT08-16 Jean Müller
compensation
- - - -
11
Solution overview PCC device cubicles
tive al
Innova l electric
a
electric n ution
distrib le
u io
t s cubic
distrib s
r feeder
drawe
- -
MCC
Okken 70-2
For electrical distribution, 70-2 is an innovative solution, robust,
reliable and secure.
Schneider Electric Polyfast® provide a high level of people safety
in the most difficult conditions.
12
Solution overview MCC device cubicles
d
ized fo
r
eders le spee
Optim ers / fe Variab f t
rawers Incom bicle drive &
s o
MCC d cu u bicle
c
starter
- - -
- - -
- - -
Okken 70-M
For MCC application drawers, 70-M is an optimized solution, robust,
reliable and secure.
The 70-M satisfy the motor control needs ot the most demanding
processes.
13
Functional units Feeder’s Service Index
The application’s
continuity of service is:
Shutting down only the Shutting down only the Addition of a FU without
concerned FU concerned FU without shutting down the
Examples
I want to determine the I want to determine whether I want to determine whether my
consequences of mechanical my switchboard can satisfy a switchboard can be upgraded in
padlocking or electrical locking on maintenance requirement: the future:
my switchboard:
2 3 3
concerned functional unit* concerned. It should without powering down the
be replaced without disturbing with switchboard. This should be done
the connections. in a location without equipment,
within the limits stipulated by the
manufacturer.
plug-in feeder
I would like this operation to shut I would like the maintenance I would like to be able to add any
2
down only the functional unit* operation to be limited to the type of functional unit (protection)
2 3
concerned functional unit* concerned. The without powering down the
connections will have to be switchboard. This should be done
disconnected and reconnected in a location without equipment,
when it is replaced. within the limits stipulated by the
manufacturer.
disconnectable feeder
I would like this operation to I would like the maintenance I would like to be able to add any
shut down only the power to the operation to be limited to the type of functional unit (motor control
3 3 3
functional unit* concerned, but allow functional unit* concerned. It should or protection) without powering
the automated control system tests, be replaced without disturbing with down the switchboard.
which make it possible to test the the connections. This should be done in a location
installation in its entirety before without equipment, within the limits
withdrawable drawer
putting it back into service, to be stipulated by the manufacturer.
performed.
14
Compact NSX
fixed on mounting plate
Compact NSX
disconnectable
on Polyfast: SI=223
in drawer SI=333 70-M half width drawer SI=333 70-M full width drawer SI=333
15
Functional units Electrical distribution
In > 630 A
230 (single)
3200 < In < 4000 100 1 NW40 4000
115 (-3)
3 NW20-32 4000
115 (-2)(1)
1600 < In < 3200 100 3 NW08-16 3200
115 (-1)
1 NW08-32 3200
Single NW
800 < In < 1600 100 4 NT08-16 2100
NS 800-1600 A
70-2 70-F
80 1 NT08-16 2100
NS 800-1600 A
Single NT / NS
(1) These are recommended configurations. For extended one, please consult us.
16
Functional units Electrical distribution
In y 630 A
70-2
Disconnectable Polyfast In < 400 NSX100-250 1 7 modules
SI = 223 400 < In < 630 NSX400-630 1 9 modules
70-2
Plug-in on Polyfast In < 400 NSX100-250 1 7 modules
SI = 233 400 < In < 630 NSX400-630 1 9 modules
70-2
70-F
(1) depending on Iq
17
Functional units Power factor compensation and
harmonic filtering
Selection
18
Many configuration possibilities
bb As is the case with the other products in the Okken range, the power factor
correction and filtering column has been designed to integrate perfectly with a full
switchboard, 2350 or 2200 mm high.
bb The power factor correction and filtering elements can be protected as follows:
vv externally, by an NS630 circuit breaker in an adjacent cubicle,
vv internally, by an NS100 separate circuit breaker on each mounting plate.
bb The choice affects the number of mounting plates per column.
Selection of cubicle
Rated Type Power Cubicles Qty of
voltage (V) (kVAR) qty height width mounting
(mm) (mm) plates
415 without self up to 500 1 2200 650 4
1 2350 650 5
with integrated self up to 250 1 2200 650 4
1 2350 650 5
separated self up to 125 2 2200 650 4
2 2350 650 5
690 without self up to 500 1 2200 650 4
1 2350 650 5
separated self up to 250 3 2200 650 4
3 2350 650 5
19
Functional units Motor control
> Given the complexity of data flows and > Based on architectures that have been pre-
communication network infrastructures, from tested and pre-validated for an integration in the
instrumentation to corporate management systems, leading communication protocols used in process
simple to integrate and scalable solutions are the industry and infrastructures, our solutions help
natural choice. you rapidly and efficiently optimise the energy
efficiency of your assets.
Example of an Ethernet
communication architecture of a
MotorSysTM iPMCC solution, at
a process unit level
Innovation Bypass
switch in a Daisy
Chain Loop for
an optimum
dependability
20
Functional units Motor control
We design with you the solution which meets your needs as well as
your process requirements.
Protection
Short-circuit, Thermal overload, Overcurrent, Ground current
Current phase imbalance & phase loss
Current phase reversal
Undercurrent
Long start (stall) & Jam (locked rotor)
Motor temperature sensor
Rapid cycle lockout
Load shedding
Voltage phase imbalance, phase loss, & phase reversal
Undervoltage & Overvoltage, Underpower & Overpower, Under & Over power factor
Measurements
Line currents, Ground current, Average current, Current phase imbalance, Thermal
capacity level
Motor temperature sensor
Frequency
Line-to-line voltage, Line voltage imbalance, Average voltage
Active & Reactive power, Power factor, Active & Reactive power consumption
Operational modes
Consignment
Starters test position
Maintenance & Upgrade live
Control at motor level
PC set-up
Remote management
Local HMI
"Nominal current only" set-up (screwdriver)
21
Functional units Motor control
Selection of the functional unit -MotorSys MCC 1 component - rated 415 V - 50 Hz - IP31 / 35°C
In number of vertical modules (1 module = 25 mm)
Selection of the functional unit -MotorSys MCC 2 components - rated 415 V - 50 Hz - IP31 / 35°C
In number of vertical modules (1 module = 25 mm)
70 - M
Selection of the functional unit -MotorSys MCC 3 components - rated 415 V - 50 Hz - IP31 / 35°C
In number of vertical modules (1 module = 25 mm)
22
Selection of the functional unit - MotorSys MCC and iMCC 1 & 3 components - rated 415 V - 50 Hz - IP31 / 35°C
In number of vertical modules (1 module = 25 mm)
23
Functional units Motor control
Motor control - MotorSys MCC and iMCC 1 & 3 components - rated 690 V - 50 Hz - IP31 / 35°C
In number of vertical modules (1 module = 25 mm)
24
25
Functional units Variable speed drive and soft
starter
Altistart ATSU 01
Altistart ATS 48
bb The Altistart 48 soft start - soft stop unit is a controller with 6 thyristors, which is
used for the torque-controlled soft starting and stopping of three-phase squirrel cage
asynchronous motors.
bb The Altistart 48 must be selected on the basis of 3 main criteria:
vv the power supply voltage range (this catalogue deals only whith the devices
connected to a 415V or 690V network),
vv the power and the nominal current of the motor,
vv the type of application and the operating cycle.
Altistart ATS 48
ATV61 ATV71
ventilation, hoisting,
air conditioning, handling,
pumping, … packing,
process machines,
lifts, ...
Altivar ATV 61 Altivar ATV 71 This catalogue deals only with 415V and 690V voltage.
26
Variable speed drive and soft starter - 415V
Withdrawability Switchgears Power (kW) Circuit breaker or fuse Dimensions Cubicle
Protection Switchgears
withdrawable drawer ATSU01 1,5 to 15 Tesys U - 4
SI = 333
27
Cubicles Associating cubicles and
compartments
72M
mm =
1800
vertical
busbar 66M
mm =
1650
device
installation
zone
28
Columns for rear connection (RC)
For rear connection (RC), a single compartment (depth 400 or 600 mm) is added at
the rear of the device cubicle, or else 2 compartments (depth 400 mm only) can be
necessary, depending on the size and quantity of cables to be connected.
RC columns panorama
switchboard depth switchboard depth switchboard depth
1000 mm 1200 mm 1400 mm
option column option column option column
device
cubicle
width
600 mm
device
cubicle
width
650 mm
device
cubicle
A device cubicle width
1150 mm
B cable compartment
20 30 40
Type of connection
BDC: bottom direct connection RC: rear connection TDC : top direct connection SC : side connection
29
Cubicles Presentation
Cubicle
The Okken switchboards consist of a framework and busbar assembly designed to
combine in the same cubicle functional units of varying technologies, grouping
both distribution and motor control applications.
Busbars
Busbar coating
Busbar coating none silver tin nickel epoxy
Horizontal busbar b b b b
Vertical busbar 115 b b b b
Vertical busbar 70 b b b
Vertical busbar 115 - 70 b b b
protection against ... ambiance ambiance arc
corrosives corrosives interne
Optimization
bb The busbar epoxy coating allows enhanced heat loss, up to 10%.
bb To increase busbar ln in hot environments and with an IP 41 or 54, cubicle
ventilation is strongly recommended.
Horizontal busbar
bb The vertical busbar has 2 centre-to-centre distances which guarantee amply sized
safety perimeters:
vv the 115 mm centre-to-centre distance corresponds to the optimised spacing of the
connection points of Masterpact NT / NS / NW circuit breakers,
vv the 70 mm centre-to-centre distance corresponds to the optimised spacing of the
double plug-in clamps of the PCC or MCC functional units.
bb The 115-70 combined busbar allows connection of a Masterpact NW08-32 type
circuit-breaker at the top of the cubicle and installation of MCC / PCC feeders in the
36 bottom modules.
Selection table
Allowable intensity at 35 °C IP31 (A) (kA eff.) Qty of bars
Bars section 40 x 10 mm
Single busbars
from 0 to 1900 50 2
from 1900 to 2500 80 3
from 2500 to 3200 100 4
from 3200 to 4000 100 6
Double busbars
from 4000 to 5000 100 2x3
from 5000 to 6300 100 2x4
from 6300 to 7300 150 2x5
30
Cubicles 230
Functional unit
Busbar for 230 cubicle
Dimensions
Type of distribution Type of connection Qty of cubicle
1 incomer or bb direct connection from the bottom 1
1 distribution feeder bb rear connection 1
2 incomers + 1 coupling bb rear connection 3
3
31
Cubicles 115
Functional unit
Vertical 115 busbar
bb mainly designed for high power columns
115mm
115mm
115mm
bb allows the installation of NW08-40, NT08-16/
NS800-1600 as incomers or feeders
bb installed at the rear of the switchgear cubicle,
throughout all its height
Dimensions
Type of distribution Circuit breaker Type of connection Qty of cubicle
1 incomer or Masterpact NW40 bb direct connection from the bottom 1
1 distribution feeder bb rear connection
Masterpact NW08-32 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection
Masterpact NT08-16 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection
2 incomers Masterpact NW40 bb direct connection from the bottom 2
+ 1 coupling bb rear connection 3
Masterpact NW08-32 bb direct connection from the top 2
bb direct connection from the bottom
bb rear connection
Masterpact NT08-16 bb direct connection from the top 2
bb direct connection from the bottom
bb rear connection
32
Cubicles 115 / 70-2
Functional unit
Vertical 115-70-2 busbar
bb enables mixing, in a single Okken column, a
NW08-32 incomer and functional units up to 630 A
Dimensions
Type of distribution Circuit breaker Type of connection Qty of cubicle
1 incomer or Masterpact NW40 bb direct connection from the bottom 1
1 distribution feeder bb rear connection
Masterpact NW08-32 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection
Masterpact NT08-16 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection
33
Cubicles Mono NW
Functional unit
Vertical 115 busbar
bb mainly designed for high power columns
bb allows the installation of NW08-40, NT08-16/
NS800-1600 as incomers or feeders
bb installed at the rear of the switchgear cubicle,
throughout all its height
bb Single NW08-32 variant: height-reduced busbar
Dimensions
Type of distribution Circuit breaker Type of connection Qty of cubicle
1 incomer or Masterpact NW40 bb direct connection from the bottom 1
1 distribution feeder bb rear connection
Masterpact NW08-32 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection
Masterpact NT08-16 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection
34
Cubicles Mono NT / NS
Functional unit
Vertical 70 busbar
bb allows the installation of NT08-16/NS800-1600
bb installed at the rear of the switchgear cubicle,
throughout all its height
bb Single NT08-16/NS800-1600 variant: height-
reduced busbar
Dimensions
Type of distribution Type of connection Qty of cubicle
1 incomer or bb direct connection from the bottom 1
1 distribution feeder bb direct connection from the top
bb rear connection
35
Cubicles 70-M
Functional unit
Vertical 70-M busbar
bb specifically designed for 70-M drawers
bb installed at the rear of the drawers area
bb can be simple, for full-width drawers cubicle
Dimensions
All functional units
Type of functional unit Type of connection
Withdrawable in drawer bb side connection from the front
bb rear connection
36
Cubicles 70-2
Functional unit
Vertical 70 busbar
70 mm
70 mm
70 mm
bb allows the installation of NT08-16/NS800-1600 and
all the distribution feeders and motor control feeders
bb installed at the rear of the switchgear cubicle,
throughout all its height
Dimensions
Dimensions for electrical distribution > 630 A
Type of distribution Circuit breaker Type of connection Qty of cubicle
1 incomer or Masterpact NT08-16 bb side connection from the front 1
1 distribution feeder bb direct connection from the bottom 1
Compact NS800-1600 A bb direct connection from the top 1
bb rear connection 1
37
Cubicles 70-F
Functional unit
Vertical 70 busbar
bb allows the installation of NT08-16/NS800-1600 and
all the distribution feeders and motor control feeders
bb installed at the rear of the switchgear cubicle,
throughout all its heigh
Dimensions
Dimensions for electrical distribution > 630 A
Type of distribution Circuit breaker Type of connection Qty of cubicle
1 incomer or Masterpact NT08-16 bb side connection from the front 1
1 distribution feeder
bb direct connection from the bottom 1
bb direct connection from the top 1
bb rear connection 1
38
Cubicles 185 (Jean Müller)
Functional unit
Vertical 185 busbar
bb dedicated to Jean Müller fuse-switches installation
bb installed at the rear of a H2200 mm
switchgear cubicle, throughout all its height
Dimensions
All functional units
Type of functional unit Type of connection
Withdrawable in drawer bb side connection from the front
bb rear connection
39
Support tools Example of configuration
1
Customer’s needs
1250 A
250 A
100 A
35 kW
5,5 kW
1,5 kW
35 kW
5,5 kW
100 kW
150 kW
1,5 kW
1,5 kW
1,5 kW
1,5 kW
15 kW
1,5 kW
1,5 kW
15 kW
45 kW
5,5 kW
G
100 kVAR
3200 A
3200 A
800 A
40
Support tools Example of configuration
2
Determine the functional units
according to the following parameters:
bb In current,
bb voltage,
bb short-circuit current,
bb number of pole
3
bb type and technology of the functional units.
1250 A
250 A
100 A
35 kW
5,5 kW
1,5 kW
35 kW
5,5 kW
100 kW
150 kW
1,5 kW
1,5 kW
1,5 kW
1,5 kW
15 kW
1,5 kW
1,5 kW
15 kW
45 kW
5,5 kW
G
100 kVAR
3200 A
3200 A
800 A
Type of functional
VVD
VVD
VVD
INC
INC
INC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
MC
ED
ED
ED
ED
ED
ED
ED
EC
units(1)
C
Technology
Polyfast
Polyfast
Polyfast
Polyfast
Polyfast
chassis
chassis
chassis
chassis
chassis
chassis
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
fixed
18
30
19
19
12
18
48
6
3
3
6
3
3
3
6
6
6
6
6
6
4
4
6
Cubicles,
1 cubicle
1 cubicle
115 / 70-2
1 cubicle
(1)To determine the dimensions of each functional unit, see the selection table.
INC: high power circuit-breaker incoming.
C: coupling.
EC: Power factor compensation and harmonic filtering.
ED: electrical distribution.
MC: motor control.
VVD = Variable speed drive and soft starter.
41
Support tools Design your installation
Front faces layout
Ground fastening
compulsory fastening point
optional fastening point
bb For connection by cables and fishplating of the horizontal busbar, provide 500 mm
above the switchboard.
bb When ceiling clearance is limited, provide a horizontal busbar of 3200 A maximum
(4 bars / phase) for fishplating and connection from the front of the switchboard.
Clearance above the switchboard. Rear connection. Front connection. Cubicle, width = 1150 mm.
42
Notes
43
Okken performances Futher technical information
General data
Standard environment
reference standards IEC 60439-1 / IEC 61439-2
IEC 60529
climatic resistance damp heat withstand IEC 60068-2-30
dry heat withstand IEC 60068-2-2
low temperature withstand IEC 60068-21
salt spray withstand IEC 60068-2-11
installation indoor
earthquake withstand IEC68-3-3 and IEC721-26
according to IBC 2000
HN20E53
environment (CEM) type 2
Mechanical data
cable entry top / bottom
access front / rear
degree of protection (IP) 22 / 31 / 41 /54
impact withstand index (IK) 10
form 2b / 3b / 4a / 4b
withdrawability FFD / WFD / WFW / WWW
dimensions (mm) height 2200 / 2350
width 600 / 650 / 800 / 900
1000 / 1100 / 1150 / 1300
depth 600 / 1000 / 1200 / 1400
installation modularity in height 2200 mm 66 modules of 25 mm
a cubicle height 2350 mm 72 modules of 25 mm
average weight cubicle 115 (2500A) ~ 850 kg
cublicle 70-M ~ 650 kg
cubicle 70-2 PCC ~ 700 kg
cubicle 70-2 MCC ~ 600 kg
cubicle 230 (6300A) ~ 1300 kg
panel coating epoxy / polyester powder (SP03)
polymerised, > 50 μ
framework galvanised
panelling colour RAL 1000
Electrical data
rated insulation voltage (Ui) 1000 V
rated operational voltage (Ue) 415 / 690 V CA
rated frequency (F) 50 / 60 Hz
rated impact withstand voltage (Uimp) 12 kV
rated auxiliary circuit voltage 230 V AC max.
surge category IV
degree of pollution 3
rated current (In) 6300 A
horizontal busbar rating 7300 A
vertical busbar rating 4000 and 2100 A
horizontal busbar short-term rated current (Icw) 1s 50 / 80 / 100 / 150 kA rms
rated peak current 110 / 176 / 220 / 330 kA peak
vertical busbar short-term rated current (Icw) 1s 50 / 80 / 100 kA rms
rated peak current 110 / 176 / 220 kA peak
rated conditional short-circuit current (lsc) up to 150 kA
internal arcing protection according to IEC 61641 100 kA eff 0.3 s
earthing diagram TT-IT-TNS-TNC
current limit of power incoming and outgoing feeders up to 6300 A
power limit of motor control feeders up to 250 kW 690 V
44
45
© 2010 - Schneider Electric - All rights reserved
Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35 rue Joseph Monier of the information given in this document.
CS 30323
F-92506 Rueil Malmaison Cedex
06-2010