Okken Solution Guide 2010

Download as pdf or txt
Download as pdf or txt
You are on page 1of 48

Okken

High dependability, low voltage switchboard

Solution guide
2010

http://www.panelbuilders.schneider-electric.com
Contents

Presentation 2
Solution overview 10

Functional units 12

Cubicles 28

Support tools 40

Okken performances 44

1
Presentation Fields of applications
Requirements and solutions

Petroleum, gas, Mines, metallurgy, Food-processing


petrochemical cement works

Requirements Continuity of supply Environment and safety Avaibility and performance


and safety

Solutions > Intelligence in the motor control > Specific “anti-corrosion” treatment > Tightness ensured by IP54
and the electrical distribution. on conductive parts. elements.
> Dependability. > Tightness ensured by IP54 > Fault prevention by intelligent
> Rapid restarting after an incident. guaranteed parts. motor control centers (iMCC).
> Internal arc protection.
> DEP Shell certification.

Nuclear Water treatment Marine and off-shore

Requirements Continuity of supply Continuity of supply Robustness and safety


and safety and environment

Solutions > Robustness to vibrations 5G. > Feeders on dsconnectable and > Robustness to vibrations.
> Internal arc protection. withdrawable systems. > Marine certification (DNV).
> Withdrawable solutions > Specific “anti-corrosion” treatment > Salty environment.
on conductive parts.

2
Presentation Fields of applications
Functions

High power incomings Electrical distribution Power factor compensation


and harmonic filtering

Motor control Variable speed drive


and soft starters

3
Presentation Okken solution
Motor Sys™ intelligent Power & Motor
Control Center (iPMCC)

Intelligent solutions for


fast and easy access to information from
anywhere, around the clock

Our MotorSys™ iPMCC solutions for continuous and critical processes were developed through
our specific expertise in energy and industrial process control management. Forming the
keystone of the energy efficiency
of your process units, they incorporate a range of functions to supply power (intelligent Power
Control Centre - iPCC), start up, control, protect and monitor your LV network electric motors
and loads (intelligent Motor Control Centre - iMCC). The breadth of the range ensures that all
types of continuous and critical process as well as specific requirements are covered.

1
Remote control and
1

monitoring of your installation


A continuous, real-time communication interface
with your control and monitoring systems for
energy management and
process control.

Our MotorSys™ iPMCC > MotorSys™ iPMCC solutions communicate


solutions help your teams with the major industrial local area networks on the
optimise the energy market (Ethernet TCP/IP, Profibus-DP, DeviceNet,
efficiency of your assets, Modbus, etc.).

offering the following > With data delivered in real time, your operational
and maintenance staff will have immediate access
benefits:
to the relevant information to control your motors
bbDependability, and electrical distribution locally or remotely.
even in severe industrial > Warning messages can be sent automatically
environments, to a mobile phone in the event of an alarm or
bbSafety of personnel group of alarms.
and assets, maintainability
and upgradability,
bb Lead time management 2Information for local operation,
and risk as well as cost maintenance and upgrading
reduction throughout your of your installation
installation's entire
Information on electrical distribution, motor operation
lifecycle.
and power consumption can be accessed.

> MotorSys™ iPMCC solutions can integrate a


dedicated human-machine interface (HMI) or
communicate via a personal computer directly on
the motor starters.

4
Presentation Okken solution
Motor Sys™ intelligent Power & Motor
Control Center (iPMCC)

3 Information for site engineering


With information delivered to ensure the traceability of electrical
distribution, motor operation and power consumption data,
installations are constantly improved.

> MotorSys™ iPMCC solutions make it easy to collect all the


statistics you need to develop effective plans covering the operation,
maintenance, optimisation and upgrading of your installations,
as well as energy efficiency.

MotorSysTM iPMCC
solutions integrate
perfectly into your site
network infrastructure,
whatever the
communication
protocol, but also into
energy management
control systems
and process
control systems
2

Example of a
MotorSysTM iPMCC
solution integrated
into a site
infrastructure

5
Presentation Okken solution
Innovation

70-M cubicles

Distribution busbar
Installed in a partitioned compartment at the rear of the drawers
area, it consists of 8 mm thick bars whose cross-section depend

ec tric upon the current to be distributed in the cubicle.

d e r El
nei ent
Functional units up to 630A are connected to the busbar by plug blocks.
Sch pat
Specific door for tap-off outlets make the busbar unaccessible except for the plugs of
the drawer.

The 2 busbars are linked together at the bottom with ther vertical busbars link
system.
This links are encapsulated in a metal sheet box with plastic covers.
The busbar can be single when all the drawers in the cubicle are full width.

Horizontal / vertical busbar association principle

Connections to the distribution busbars and fishplating are made without drilling.

Sliding fishplates ensures the link between 2 horizontal busbars.


Angle brackets secure the connection between the horizontal and the vertical
busbar.

The tightening screw devices used to secure the connection go through the gap
between the horizontal bars.

ctric
e r Ele
d
c h nei atent
S p

Auxiliaries connection

r ic
El ect Innovative mechanism allowing the auxiliary circuits to be connected with power
er
eid tent
disconnected for functionnal unit test.
h n
Sc pa

6
Presentation Okken solution
Innovation

Drawer positions
The “plug-in / test / draw-out” positions are mechanically marked by an
indexing device associated with a mechanical indicator on the drawer sides.

Plug-in
bb The functional unit is operational.
bb Power and auxiliaries are connected.

Test
bb The functional unit is not operational.
bb Only auxiliaries are connected.
bb Allow padlocking.
bb It allows the functional unit verification.
bb Allow maintenance on the process.

Draw out
bb The functional unit is not operational.
bb Power and auxiliaries are disconnected.
bb Allow maintenance on the process.

Withdrawn
bb The drawer can be fully extracted.
bb Allow quick replacement.
bb Allow switchboard live change.

Polyfast, safety and easy to implement.


The Polyfast supports the active portion of the moulded circuit breaker housing.

The partitions ensure electrical insulation between the


circuit breaker’s upstream connections and the plug-in
clamps.

A striker system causes the circuit breaker to open


when extracted and placement of the Polyfast with
power on.

The Polyfast allows the power and auxiliary circuits


wiring to be performed outside the switchboard.

7
Presentation Okken solution
Implementation

Reliability and flexibility


> 7 service index to adapt to the requirements of each
application.
> The switchboards must be type tested assemblies.
They have a complete electrical and mechanical
inspection before shipping.
> The addition or the removal of equipment is made
with power “ON”, without pre-equiping the switchboard.

Continuity of supply
> Withdrawable feeders (in rack) for rapid workings.
> The switchboards must be reconfigured live.
> Rapid restart after an incident.

Safety of people and


equipments
> Internal arc protection, in compliance with the
requirements of the strictest international regulations
(technical reports IEC 61641 and AS 3439-1).
> Continuity of supply guaranteed by limitation of
harmful effects of the internal arc in the switchboard.
> Quick repair of the area where the arc was confined.
> Safety of people and equipment guaranteed during
the occurrence of the fault.
> The busbar epoxy paint on the busbars prevents
flashover and propagation of the arc.

Withstand to the most


demanding environements Type tested
> The conductive parts treated for “anti-corrosion”
(according to IEC 721-3-3 standard).
Okken is totally type-tested in accordance with CEI
> Marine version for a saline environments withstand.
60439-1 and 61439-2
> IP54 tightness for the dusty and / or damp • Certified by independant labs:
environements. LOVAG, ASEFA, CESI and VIRLAB.
• As well as by a permanent control in Schneider Electric
> 2G and 5 G earthquake safety versions. test laboratories.
> Forced ventilation for environments with ambient • Type-tests are carried out:
o temperature-rise limit,
temperatures hotter than 45° C or for devices with o dielectric properties,
considerable heat loss. o short-circuit withstand,
o effectiveness of the protective circuit,
> DEP Shell certification for petrochemical industries.
o conformity of the clearance and creepage distances,
o mechanical operation,
o degree of protection.

8
Presentation Okken solution
Implementation

4 specific compliances 1 option

Standard 2G & 5G Marine Oil and gas Forced


For all applications. For seismic zones. For boats and offshore For DEP shell certified
ventilation
platforms. plants.
For busbar derating
optimisation (15%)

2 levels of protection

Cubicle partitioning Connection accessories


Protective screens (side partition + horizontal busbar At functional unit level, the Polyfast prevents the
screen) prevent tracking of an arc in the cubicle. propagation of an arc in the cubicle.

5 levels of service

Service Index 211 212 223 233 333


Shutting down only the concerned functional unit. Shutting down only the

Operation
concerned functional unit, but
test of the control system
possible before the resumed
operation.

Shutting down the whole switchboard. Shutting down only Shutting down only the concerned functional unit

Maintenance
the concerned without connections handlings.
functional unit with
connections
handlings.

Shutting Addition of a Addition of a functional unit without shutting down the switchboard, free
addition in non-equiped spare slots.
Evolution
down the functional unit in
whole pre-equiped spare
switchboard. slots.

4 levels of functional unit (FU) partitioning


Available forms 2b 3b 4a 4b
Busbars / fonctional units separation b b b b
Busbars / terminal blocks(1) separation for external conductors b b b b
Separation between functional units - b b b
Separation between terminal blocks(1) for external conductors - - b b
Terminal blocks separation for external conductors / functional units - - - b
(1) They are integral part of the functional unit.

9
Solution overview PCC device cubicles

wer ower
igh po High p Mixed
Very h ers eders eders
o m e r s / feed c o m ers / fe ers / fe
inc in in c o m
cubicle cubicle cubicle

Type of cubicle 230 115 115/70-2


In distribution 1750 / 3200 A
4500 / 7300 A 1750 / 4000 A
busbar
NT08-16 / NS800-1600 NT08-16 / NS800-1600
Incomers NW40b / 63b
NW08-40 NW08-32

Feeders NT08-16 / NS800-1600 NT08-16 / NS800-1600


> 630A NW40b / 63b
NW08-40 NW08-32
Distribution

bb disconnectable mounting plate


y 630A
bb disconnectable Polyfast
- -
bb plug-in Polyfast
bb drawer

10
ized n
Optim Optim
ized nsatio
omers
/ Compe witch
wer inc ers / onic Fuse-s
hig h p o le o w e r incom & harm s cubic
le
s cubic high p g feeder
filterin
le
feeder s cubic
feeder

Single NW Single NT/NS PFC 185


1600 / 3200 A 800 / 1600 A 6300 A 630 / 1500 A

NW08-32 NT08-16 - -

Power factor
NW08-32 NT08-16 Jean Müller
compensation

- - - -

11
Solution overview PCC device cubicles

tive al
Innova l electric
a
electric n ution
distrib le
u io
t s cubic
distrib s
r feeder
drawe

Type of cubicle 70-2 70-F


In distribution 1000 / 2100 A 2100 A
busbar
Incomers NT08-16 / NS800-1600 NT08-16

Feeders > 630A NT08-16 / NS800-1600 NT08-16


Distribution

bb disconnectable mounting plate bb fixed mounting plate for


y 630A
bb disconnectable Polyfast 1 NSX or NS100-630
bb plug-in Polyfast bb fixed mounting plate for
bb drawer 2 NSX100-250

- -
MCC

Okken 70-2
For electrical distribution, 70-2 is an innovative solution, robust,
reliable and secure.
Schneider Electric Polyfast® provide a high level of people safety
in the most difficult conditions.

12
Solution overview MCC device cubicles

d
ized fo
r
eders le spee
Optim ers / fe Variab f t
rawers Incom bicle drive &
s o
MCC d cu u bicle
c
starter

70-M 70-2 VSD - SS


2000 A 1000 / 2100 A -

- - -

- - -

- - -

bb disconnectable mounting bb fixed mounting plate


bb drawer y 250 kW plate y 37 kW y 400 kW
bb drawer y 250 kW bb drawer y 55 kW

Okken 70-M
For MCC application drawers, 70-M is an optimized solution, robust,
reliable and secure.
The 70-M satisfy the motor control needs ot the most demanding
processes.

13
Functional units Feeder’s Service Index

What does your installation need?


Because not all your applications have the same needs, Okken
allows you to choose the solution appropriate to the expected level
of service in terms of operation, maintenance and upgrading.

Making the right choice

Operation Maintenance Evolution


The switchboard
must permit Setting Checking Addition
Locking Cleaning Modifications
Padlocking Repairing Expansion

The application’s
continuity of service is:

 Not required Shutting down the whole


switchboard
Shutting down the whole
switchboard
Shutting down the whole
switchboard

Shutting down only the Shutting down only the Addition of a FU in

 Wanted concerned FU concerned FU with


connections handling
pre-equiped spare slots

Shutting down only the Shutting down only the Addition of a FU without
concerned FU concerned FU without shutting down the

 Essential Allows «test» position connections handling swwitchboard, free


addition in non-equiped
spare slots

Examples
I want to determine the I want to determine whether I want to determine whether my
consequences of mechanical my switchboard can satisfy a switchboard can be upgraded in
padlocking or electrical locking on maintenance requirement: the future:
my switchboard:

OPERATION MAINTENANCE EVOLUTION


I would like this operation to shut I would like the maintenance I would like to be able to add any
down only the functional unit* operation to be limited to the type of functional unit (protection)

2 3 3
concerned functional unit* concerned. It should without powering down the
be replaced without disturbing with switchboard. This should be done
the connections. in a location without equipment,
within the limits stipulated by the
manufacturer.
plug-in feeder

I would like this operation to shut I would like the maintenance I would like to be able to add any

2
down only the functional unit* operation to be limited to the type of functional unit (protection)

2 3
concerned functional unit* concerned. The without powering down the
connections will have to be switchboard. This should be done
disconnected and reconnected in a location without equipment,
when it is replaced. within the limits stipulated by the
manufacturer.
disconnectable feeder

I would like this operation to I would like the maintenance I would like to be able to add any
shut down only the power to the operation to be limited to the type of functional unit (motor control

3 3 3
functional unit* concerned, but allow functional unit* concerned. It should or protection) without powering
the automated control system tests, be replaced without disturbing with down the switchboard.
which make it possible to test the the connections. This should be done in a location
installation in its entirety before without equipment, within the limits
withdrawable drawer
putting it back into service, to be stipulated by the manufacturer.
performed.

14
Compact NSX
fixed on mounting plate

fixed device: SI=211

device on base: SI=232

Compact NSX
disconnectable

on Polyfast: SI=223

Compact NSX and C60


withdrawable

in drawer SI=333 70-M half width drawer SI=333 70-M full width drawer SI=333

15
Functional units Electrical distribution
In > 630 A

Selection of the functional unit


In (A) Icw max (kA) Max. qty of circuit breakers Type of circuit breaker Cubicle In vertical busbar (A)
per cubicle
4000 < In < 6300 150 1 NW40b-63b 7300

230 (single)
3200 < In < 4000 100 1 NW40 4000

115 (-3)
3 NW20-32 4000

115 (-2)(1)
1600 < In < 3200 100 3 NW08-16 3200

115 (-1)
1 NW08-32 3200

Single NW
800 < In < 1600 100 4 NT08-16 2100
NS 800-1600 A

70-2 70-F
80 1 NT08-16 2100
NS 800-1600 A

Single NT / NS
(1) These are recommended configurations. For extended one, please consult us.

16
Functional units Electrical distribution
In y 630 A

Selection of the functional unit


Withdrawability In (A) Device Max. qty of Max. modularity Cubicle
devices (1 module = 25 mm)
Drawer In < 63 C60 1 4 modules half width
SI = 333 63 < In < 125 NG125 1 8 modules half or full width (1)
816< In < 100 NSX100 1 8 modules half or full width

125 < In < 160 NSX160 1 8 modules full width


200 < In < 400 NSX 250-400 1 12 modules full width
400 < In < 630 NSX630 1 16 modules full width
70 - M 70-2
Disconnectable In < 63 C60 6 modules
mounting plate
SI = 223

70-2
Disconnectable Polyfast In < 400 NSX100-250 1 7 modules
SI = 223 400 < In < 630 NSX400-630 1 9 modules

70-2
Plug-in on Polyfast In < 400 NSX100-250 1 7 modules
SI = 233 400 < In < 630 NSX400-630 1 9 modules

70-2

Fixed In < 400 NSX100-250 2 8 modules


SI = 211 - 212 400 < In < 630 NSX400-630 1 10 modules

70-F

(1) depending on Iq

17
Functional units Power factor compensation and
harmonic filtering

Selection

U max = 415 V U max = 690 V

Varpact Custom Custom

few very few very few


polluted polluted polluted polluted polluted polluted polluted
polluted
network network network network network network network
network

Classic Comfort Harmony Varplus and SAH components Varplus


components

A wide selection for sensitive applications


Statistical studies determine the frequency of the solutions used, according to
the applications.
very frequently Classic Comfort Harmony
usually Pollution rate Gh/Sn y 15 % 15% < Gh/Sn y 25% 25% < Gh/Sn y 50%
occasionally Oil & Gas
Automotive
Water treatment
Mines & Minerals
Infrastructures
Tertiary
Marine & Off-shore
Agri-food
Sn: apparent power of the transformer.
Gh: apparent power of harmonics-generating loads (variable speed motors, static converters,
power electronics, etc.).

It is however recommended that measurements be carried out on site to check


that the correct solution is adopted.

A source of energy savings


Power factor correction means using your transformer and your facility at
maximum efficiency by reducing losses (iron, heat, etc.)

Power output by your transformer (kVA)


Cos ϕ 250 400 630 1000 1600
0.5 125 200 315 500 800
0.7 175 280 441 700 1120
0.9 225 360 567 900 1440
0.95 238 380 598 950 1520

18
Many configuration possibilities

bb As is the case with the other products in the Okken range, the power factor
correction and filtering column has been designed to integrate perfectly with a full
switchboard, 2350 or 2200 mm high.
bb The power factor correction and filtering elements can be protected as follows:
vv externally, by an NS630 circuit breaker in an adjacent cubicle,
vv internally, by an NS100 separate circuit breaker on each mounting plate.
bb The choice affects the number of mounting plates per column.

Selection of cubicle
Rated Type Power Cubicles Qty of
voltage (V) (kVAR) qty height width mounting
(mm) (mm) plates
415 without self up to 500 1 2200 650 4
1 2350 650 5
with integrated self up to 250 1 2200 650 4
1 2350 650 5
separated self up to 125 2 2200 650 4
2 2350 650 5
690 without self up to 500 1 2200 650 4
1 2350 650 5
separated self up to 250 3 2200 650 4
3 2350 650 5

19
Functional units Motor control

Solutions that integrate into


your installation, simply
Our MotorSysTM iPMCC solutions integrate perfectly into your site network infrastructure,
whatever the communication protocol, but also into all energy management control
systems and process control systems.

> Given the complexity of data flows and > Based on architectures that have been pre-
communication network infrastructures, from tested and pre-validated for an integration in the
instrumentation to corporate management systems, leading communication protocols used in process
simple to integrate and scalable solutions are the industry and infrastructures, our solutions help
natural choice. you rapidly and efficiently optimise the energy
efficiency of your assets.

Example of an Ethernet
communication architecture of a
MotorSysTM iPMCC solution, at
a process unit level

Innovation Bypass
switch in a Daisy
Chain Loop for
an optimum
dependability

20
Functional units Motor control

Overview of the MotorSysTM iPMCC solutions

We design with you the solution which meets your needs as well as
your process requirements.

iMCC Tesys T iMCC Tesys U MCC


MotorSysTM iPMCC Solutions Range 3 components 1 component 2 & 3 comp.

Protection
Short-circuit, Thermal overload, Overcurrent, Ground current
Current phase imbalance & phase loss
Current phase reversal
Undercurrent
Long start (stall) & Jam (locked rotor)
Motor temperature sensor
Rapid cycle lockout
Load shedding
Voltage phase imbalance, phase loss, & phase reversal
Undervoltage & Overvoltage, Underpower & Overpower, Under & Over power factor

Measurements
Line currents, Ground current, Average current, Current phase imbalance, Thermal
capacity level
Motor temperature sensor
Frequency
Line-to-line voltage, Line voltage imbalance, Average voltage
Active & Reactive power, Power factor, Active & Reactive power consumption

High level functions


Custom logic at starter level
Advanced motor starting modes
Automatic restarting of motors
Fast Device Replacement

Connectivity & Communication architectures


Schneider Electric Process Control System, Energy Management and Control System, PLCs (1) interop. tested interop. tested interop. tested
Third-party Process Control System, Energy Management and Control System, PLCs (1)
Native Ethernet Modbus/TCP in Daisy Chain Loop, Multi-drop, Proxy
Native Profibus-DP, Native DeviceNet, Native Modbus-SL
Other protocols

Operational modes
Consignment
Starters test position
Maintenance & Upgrade live
Control at motor level
PC set-up
Remote management
Local HMI
"Nominal current only" set-up (screwdriver)

(1) PLC: Programmable Logic Controller Standard


Optional

21
Functional units Motor control

Selection of the functional unit -MotorSys MCC 1 component - rated 415 V - 50 Hz - IP31 / 35°C
In number of vertical modules (1 module = 25 mm)

Withdrawability Starter Power (kW) Circuit breaker Dimensions (1) Cubicle


min max
withdrawable drawer DOL 0,37 to 4 GV2L 4M/2 8M/2
SI = 333 5,5 GV2L 4M -
11 to 15 Tesys U 4M/2 8M/2
GV2L 4M/2 8M
18,5 to 30 GV3L 4M 8M
NS80HMA 8M -
NSX100 8M 12M
37 NS80HMA 8M -
NSX100 8M -
45 NSX100 8M -
55 to 90 NSX250 16M -
110 NSX250 16M -
132 NSX400 20M - 70 - M
160 NSX400 20M -
200 NSX630 20M -
250 NSX630 24M -

Selection of the functional unit -MotorSys MCC 2 components - rated 415 V - 50 Hz - IP31 / 35°C
In number of vertical modules (1 module = 25 mm)

Withdrawability Starter Power (kW) Circuit breaker Dimensions (1) Cubicle


min max
withdrawable drawer DOL 0,37 to 4 GV2P 4M/2 8M/2
SI = 333 5,5 GV2P 4M -
7,5 to 11 GV2P 4M/2 -
15 GV2P 4M/2 8M/2
18,5 to 30 GV3P 4M 8M

70 - M

Selection of the functional unit -MotorSys MCC 3 components - rated 415 V - 50 Hz - IP31 / 35°C
In number of vertical modules (1 module = 25 mm)

Withdrawability Starter Power (kW) Circuit breaker Dimensions (1) Cubicle


min max
withdrawable drawer DOL 0,37 to 4 GV2L 4M/2 8M/2
SI = 333 5,5 GV2L 4M -
7,5 to 11 GV2L 4M 8M
15 GV2L 4M/2 -
18,5 to 30 GV3L 4M 8M
NS80HMA 8M/2 8M
NSX100*MA 8M 12M
37 NS80HMA 8M -
NSX100*MA 8M -
45 NSX100*MA 8M 12M
55 to 75 NSX160*MA 8M -
90 NSX250*MA 16M -
110 NSX250*MA 16M - 70 - M
132 NSX400*MA 20M -
160 NSX400*MA 20M -
200 NSX630*MA 20M -
250 NSX630*MA 24M -

(1) depending on additional equipments

22
Selection of the functional unit - MotorSys MCC and iMCC 1 & 3 components - rated 415 V - 50 Hz - IP31 / 35°C
In number of vertical modules (1 module = 25 mm)

Withdrawability Starter Power (kW) Circuit breaker or fuse Dimensions Cubicle


withdrawable drawer DOL 0.37 to 9 Tesys U and GV2 3
SI = 333 GS2F and Compact NS80 6
11 to 15 Tesys U 3
GV2 4
GS2F and Compact NS80 6
18.5 GV3 4
GS2F and Compact NS80 6
22 to 30 GV3 4
GS2J and Compact NS80 6
37 GS2J and Compact NS80 6
45 Compact NSX100 6
GS2J 12
55 to 75 Compact NSX160 6
GS2L 12
90 to 110 GS2N and Compact NSX250 12
132 to 160 Compact NSX400 18
GS2QQ 24
200 to 220 Compact NSX630 18
GS2QQ 24
250 Compact NSX630 18
Reverse 0.37 to 7.5 Tesys U 3 70-2
GV2 and Compact NS80 6
9 to 15 Tesys U 3
GV2 6
NS80 12
18 to 30 GV3 6
NS80 12
37 NS80 12
45 NSX100 12
55 to 75 NSX160 12
90 to 110 NSX250 18
132 to 160 NSX400 24
200 to 250 NSX630 24
Υ∆ - Dalhander 0.37 to 9 GV2 6
Compact NS80 12
11 to 30 GV3 and Compact NS80 12
37 Compact NS80 12
45 Compact NSX100 12
55 to 75 Compact NSX160 18
90 to 110 Compact NSX250 24
132 to 160 Compact NSX400 2 x 18
200 to 250 Compact NSX630 2 x 18
2S 0.37 to 9 GV2 6
Compact NS80 12
11 to 30 GV3 and Compact NS80 12
37 Compact NS80 12
45 Compact NSX100 12
55 Compact NSX160 12
75 Compact NSX160 18
90 to 110 Compact NSX250 24
132 to 160 Compact NSX400 24
200 to 250 Compact NSX630 24

23
Functional units Motor control

Motor control - MotorSys MCC and iMCC 1 & 3 components - rated 690 V - 50 Hz - IP31 / 35°C
In number of vertical modules (1 module = 25 mm)

Withdrawability Starter Power (kW) Circuit breaker or fuse Dimensions Cubicle


withdrawable drawer DOL 0.37 to 3 Tesys U and GV2 3
SI = 333 GS2F 6
Compact NS100 12
4 to 9 Tesys U and GV2 3
GS2J 6
Compact NS100 12
11 to 15 Tesys U 3
GV2 4
GS2J 6
Compact NS100 12
18.5 to 22 GV2 4
GS2J 6
Compact NS100 12
30 to 45 GS2J 6
Compact NS100 12
55 to 75 GS2L and Compact NS100 12
90 to 220 Compact NS400 18
GS2N 24
250 Compact NS400 18
GS2QQ 24
Reverse 0.37 to 15 Tesys U 3 70-2
GV2 6
Compact NS100 12
18.5 to 22 GV2 and Compact NS100 12
30 to 55 Compact NS100 12
75 Compact NS100 18
90 to 250 Compact NS400 24
Υ∆ - Dalhander 0.37 to 15 GV2 6
NS100 12
18.5 to 22 GV2 and Compact NS100 12
30 to 55 Compact NS100 12
75 Compact NS100 24
90 to 250 Compact NS400 2 x 18
2S 0.37 to 15 GV2 6
Compact NS100 12
18.5 to 22 GV2 and Compact NS100 12
30 to 55 Compact NS100 12
75 Compact NS100 24
90 to 250 Compact NS400 24

24
25
Functional units Variable speed drive and soft
starter

Altistart ATS U01


bb When combined with a TeSys U controller by means of a connector, the
Altistart U01 is a power option, including by-pass, which provides the «soft start/soft
stop» function.
bb Its choice criteria is the power of the motor to supply.
bb The Altistart U01 limits the starting torque and current peaks on starting, on
machines which do not require a high starting torque.

Altistart ATSU 01

Altistart ATS 48
bb The Altistart 48 soft start - soft stop unit is a controller with 6 thyristors, which is
used for the torque-controlled soft starting and stopping of three-phase squirrel cage
asynchronous motors.
bb The Altistart 48 must be selected on the basis of 3 main criteria:
vv the power supply voltage range (this catalogue deals only whith the devices
connected to a 415V or 690V network),
vv the power and the nominal current of the motor,
vv the type of application and the operating cycle.

Altistart ATS 48

Altivar ATV61 and 71


They have been designed for the following main applications:

ATV61 ATV71
ventilation, hoisting,
air conditioning, handling,
pumping, … packing,
process machines,
lifts, ...

Altivar ATV 61 Altivar ATV 71 This catalogue deals only with 415V and 690V voltage.

Circuit breaker and variable speed drive combination

From 75 kW, equipment configuration is different.

Speed drive is powered, either through a drawer


located in the 70-2 adjoining cubicle (fig. 1 and 2), or
through a dedicated 450 mm cubicle (fig. 3).

The speed drive cubicle can be either 650 mm (fig. 1)


or 1150 mm wide (fig. 2 and 3).

fig.1 fig.2 fig.3


Installation can be performed only in IP31 maximum.

26
Variable speed drive and soft starter - 415V
Withdrawability Switchgears Power (kW) Circuit breaker or fuse Dimensions Cubicle
Protection Switchgears
withdrawable drawer ATSU01 1,5 to 15 Tesys U - 4
SI = 333

ATS48 5.5 to 15 GV2 - 18


5.5 to 37 Compact NS80 - 18
45 to 55 NSX100-160 - 18

ATV61 0.75 to 5.5 GV2 - 12


7.5 to 18.5 GV3 - 18
0.75 to 18.5 Compact NS80 - 18

ATV71 0.75 to 5.5 GV2 - 12 70-2


7.5 GV3 - 12
11 to 15 GV3 - 18
0.75 to 18.5 Compact NS80 - 18

fixed mounting plate ATS 48 5.5 to 11 GV2 - 18


SI = 211 5.5 to 18.5 Compact NS80 - 18
22 t o 30 Compact NS80 - 24
30 to 55 Compact NSX 100-250 - 36
75 to 90 Compact NSX 100-250 - 48
75 to 90 Compact NSX 250-630 12 column - 650mm
110 to 220 Compact NSX 250-630 18 column - 650mm
ATV 61 0.75 to 5.5 GV2 - 18
5.5 to 7.5 GV3 - 18
11 t o 18.5 GV3 - 24
22 GV3 - 36
5.5 to 11 Compact NS80 - 18
15 to 18.5 Compact NS80 - 24
22 Compact NS80 - 36
30 to 37 Compact NS80 - 48
30 to 75 Compact NSX100-160 - 48
VSD - SS
75 to 110 Compact NSX250-400 12 column - 650mm
132 to 220 Compact NSX250-400 18 column - 650mm
250 Compact NSX250-400 18 column - 1150mm
280 to 400 Compact NS800 column - 450mm column - 1150mm
ATV71 0.37 to 5.5 GV2 - 18
5.5 to 11 GV3 - 18
15 to 18.5 GV3 - 24
22 GV3 - 36
5.5 to 11 Compact NS80 - 18
15 to 18.5 Compact NS80 - 24
22 Compact NS80 - 36
30 Compact NS80 - 48
30 to 75 Compact NSX100-250 - 48
75 to 110 Compact NSX250 12 column - 650mm
132 to 160 Compact NSX400 18 column - 650mm
200 to 315 Compact NSX400-630 18 column - 1150mm
355 to 400 Compact NS800 column - 450mm column - 1150 mm

Variable speed drive and soft starter - 690V


Withdrawability Switchgears Power (kW) Circuit breaker or fuse Dimensions Cubicle
Protection Switchgears
fixed mounting plate ATS48 11 to 18.5 GV2 - 48
SI = 211 11 to 160 Compact NS100-400 - 48
75 to 200 Compact NS400 18 column - 650mm

ATV61 2.2 to 11 GV2 - 36


11 to 30 Compact NS100-400 - 36
37 to 90 Compact NS100-400 - 48
75 to 200 Compact NS400 18 column - 650mm
250 to 315 Compact NS630b column - 450mm column - 1150mm

ATV71 1.5 to 15 GV2 - 36


11 to 30 Compact NS100 - 36
37 to 90 Compact NS100-400 - 48
75 to 160 Compact NS400 18 column - 650mm
200 Compact NS400 18 column - 1150mm VSD - SS
250 to 400 Compact NS630b column - 450mm column - 1150mm

27
Cubicles Associating cubicles and
compartments

Device cubicles architecture

Device installation zone :


bb in H2350 mm, this area represents a height of 72 modules of 25 mm, i.e.
horizontal 1800 mm,
busbar bb in H2200 mm, this area is reduced to 66 modules of 25 mm, i.e. 1650 mm.

72M
mm =
1800

vertical
busbar 66M
mm =
1650

device
installation
zone

Particular case of the 70-M device cubicle :

Double vertical busbar


Cubicle height 2200 mm 2350 mm
No. of poles 3P 3P+N 3P 3P+N
Available
64 modules 56 modules 68 modules 60 modules
modularity
Top link cover 100 mm 50 mm 150 mm
-
dimension (4 modules) (2 modules) (6 modules)
Bottom link cover 50 mm 150 mm 50 mm 150 mm
dimension (2 modules) (6 modules) (2 modules) (6 modules)

Single vertical busbar


Cubicle height 2200 mm 2350 mm
No. of poles 3P 3P+N 3P 3P+N
Available 64 modules 60 modules 68 modules 64 modules
modularity
Top link cover - 100 mm 50 mm 150 mm
dimension (4 modules) (2 modules) (6 modules)
Bottom link cover 50 mm 50 mm 50 mm 50 mm
dimension (2 modules) (2 modules) (2 modules) (2 modules)
Note: 1 module = 25 mm.

Particular case of the 115/70-2 device cubicle :


bb a conversion area of 8 modules of 25 mm, i.e. 200 mm, is dedicated to the change
of DBA of the vertical busbar,
zone bb the 115 device area is located at the top of the cubicle, and takes 9+19 modules of
evice
115-d m = 9+19
M
a 25 mm (i.e. 700 mm),
700 m r s io n are
e
conv bb the 70-2 device area is located at the bottom of the cubicle, and takes 36 modules
V-BB m = 8M
200 m of 25 mm in H2350 mm (i.e. 900 mm) and 30 modules of 25 mm in H2200 mm (i.e.
e
e zon H2350 m )
m) 750 mm).
devic
70-2 m = 36M 2200 mm
(
( H
900 m = 30M
m
750 m

28
Columns for rear connection (RC)

For rear connection (RC), a single compartment (depth 400 or 600 mm) is added at
the rear of the device cubicle, or else 2 compartments (depth 400 mm only) can be
necessary, depending on the size and quantity of cables to be connected.
RC columns panorama
switchboard depth switchboard depth switchboard depth
1000 mm 1200 mm 1400 mm
option column option column option column

device
cubicle
width
600 mm

device
cubicle
width
650 mm

device
cubicle
A device cubicle width
1150 mm
B cable compartment

C control device compartment

Columns for front connection (FC)

In case of a front-connected switchboard, the depth is unique allthrough its


length: 600 mm.
To the right of the device cubicle, compartments (width 350, 450 or 650 mm) are
added in order to give way for the cables and device connections, according to the
size and the quantity of cables to be connected.
A device cubicle Due to the position of the horizontal busbar, device connection can be made
indifferently from the top or from the bottom of the switchboard.
B cable compartment
C control device compartmnent

SC columns panorama (switchboard depth: 600 mm)


column width 800 mm column width 900 mm column width 1000 mm column width 1100 mm column width 1300 mm
column column option column option column option column

20 30 40

Type of connection

BDC: bottom direct connection RC: rear connection TDC : top direct connection SC : side connection

29
Cubicles Presentation

Cubicle
The Okken switchboards consist of a framework and busbar assembly designed to
combine in the same cubicle functional units of varying technologies, grouping
both distribution and motor control applications.

A whole host of configurations to satisfy the requirements of each site:


bb cubicles available in 2 heights, 5 widths and 2 depths, to allow integration in all
environments and ensure optimum installation modularity,
bb switchboard supplied by busbar trunking and/or cables,
bb front or rear, top and / or bottom connections,
bb choice of functional unit output partitioning:
vv incomers: forms 3b, 4b,
vv feeders: forms 2b, 3b, 4a, 4b,
bb possible customisation of panels, whose components may be delivered
unpainted.

Busbars
Busbar coating
Busbar coating none silver tin nickel epoxy
Horizontal busbar b b b b
Vertical busbar 115 b b b b
Vertical busbar 70 b b b
Vertical busbar 115 - 70 b b b
protection against ... ambiance ambiance arc
corrosives corrosives interne

Optimization
bb The busbar epoxy coating allows enhanced heat loss, up to 10%.
bb To increase busbar ln in hot environments and with an IP 41 or 54, cubicle
ventilation is strongly recommended.

Horizontal busbar
bb The vertical busbar has 2 centre-to-centre distances which guarantee amply sized
safety perimeters:
vv the 115 mm centre-to-centre distance corresponds to the optimised spacing of the
connection points of Masterpact NT / NS / NW circuit breakers,
vv the 70 mm centre-to-centre distance corresponds to the optimised spacing of the
double plug-in clamps of the PCC or MCC functional units.
bb The 115-70 combined busbar allows connection of a Masterpact NW08-32 type
circuit-breaker at the top of the cubicle and installation of MCC / PCC feeders in the
36 bottom modules.

Selection table
Allowable intensity at 35 °C IP31 (A) (kA eff.) Qty of bars
Bars section 40 x 10 mm
Single busbars
from 0 to 1900 50 2
from 1900 to 2500 80 3
from 2500 to 3200 100 4
from 3200 to 4000 100 6
Double busbars
from 4000 to 5000 100 2x3
from 5000 to 6300 100 2x4
from 6300 to 7300 150 2x5

30
Cubicles 230

Functional unit
Busbar for 230 cubicle

bb the 230 cubicle is dedicated to the installation


of a NW40b-63
bb height-reduced busbar

Rated current In (A) Nb of bars / phase Icw max (kA)


IP31 / 35°C
4530 2 x 3 x 40x10 100
5810 2 x 4 x 40x10 100
7320 2 x 6 x 40x10 150

Dimensions
Type of distribution Type of connection Qty of cubicle
1 incomer or bb direct connection from the bottom 1
1 distribution feeder bb rear connection 1
2 incomers + 1 coupling bb rear connection 3
3

31
Cubicles 115

Functional unit
Vertical 115 busbar
bb mainly designed for high power columns

115mm
115mm
115mm
bb allows the installation of NW08-40, NT08-16/
NS800-1600 as incomers or feeders
bb installed at the rear of the switchgear cubicle,
throughout all its height

Rated current In (A) Nb of bars / phase Icw max (kA)


IP31 / 35°C
1750 1 x 80x10 50
2780 2 x 80x10 100
3200 3 x 80x10 100
4090 3 x 120x10 100

Dimensions
Type of distribution Circuit breaker Type of connection Qty of cubicle
1 incomer or Masterpact NW40 bb direct connection from the bottom 1
1 distribution feeder bb rear connection
Masterpact NW08-32 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection
Masterpact NT08-16 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection
2 incomers Masterpact NW40 bb direct connection from the bottom 2
+ 1 coupling bb rear connection 3
Masterpact NW08-32 bb direct connection from the top 2
bb direct connection from the bottom
bb rear connection
Masterpact NT08-16 bb direct connection from the top 2
bb direct connection from the bottom
bb rear connection

32
Cubicles 115 / 70-2

Functional unit
Vertical 115-70-2 busbar
bb enables mixing, in a single Okken column, a
NW08-32 incomer and functional units up to 630 A

Rated current In (A) Nb of bars / phase Icw max (kA)


IP31 / 35°C
zone 115-1
1750 1 x 80x10 50
2780 2 x 80x10 80
3200 3 x 80x10 80
zone 70-2
1750 1 x 80x10 80

Dimensions
Type of distribution Circuit breaker Type of connection Qty of cubicle
1 incomer or Masterpact NW40 bb direct connection from the bottom 1
1 distribution feeder bb rear connection
Masterpact NW08-32 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection
Masterpact NT08-16 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection

Dimensions for electrical distribution y 630 A


Compact NS / NSX
Type of functional unit Rating (A) No. of pole Type of connection
Disconnectable on Polyfast 100 to 630 3P / 4P bb side connection from the front
bb rear connection
Removable on Polyfast 100 to 630 3P / 4P bb side connection from the front
bb rear connection
Withdrawable in drawer 100 to 630 3P / 4P bb side connection from the front
bb rear connection
Small distribution (C60)
Type of functional unit Type of connection
Withdrawable in drawer bb side connection from the front
bb rear connection
Disconnectable on mounting plate bb side connection from the front

33
Cubicles Mono NW

Functional unit
Vertical 115 busbar
bb mainly designed for high power columns
bb allows the installation of NW08-40, NT08-16/
NS800-1600 as incomers or feeders
bb installed at the rear of the switchgear cubicle,
throughout all its height
bb Single NW08-32 variant: height-reduced busbar

Rated current In (A) Nb of bars / phase Icw max (kA)


IP31 / 35°C
1750 1 x 100x10 50
2780 2 x 100x10 100
3200 3 x 100x10 100

Dimensions
Type of distribution Circuit breaker Type of connection Qty of cubicle
1 incomer or Masterpact NW40 bb direct connection from the bottom 1
1 distribution feeder bb rear connection
Masterpact NW08-32 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection
Masterpact NT08-16 bb side connection from the front 1
bb direct connection from the top
bb direct connection from the bottom
bb rear connection

34
Cubicles Mono NT / NS

Functional unit
Vertical 70 busbar
bb allows the installation of NT08-16/NS800-1600
bb installed at the rear of the switchgear cubicle,
throughout all its height
bb Single NT08-16/NS800-1600 variant: height-
reduced busbar

Rated current In (A) Nb of bars / phase Icw max (kA)


IP31 / 35°C
1750 1 x 80x10 80

Dimensions
Type of distribution Type of connection Qty of cubicle
1 incomer or bb direct connection from the bottom 1
1 distribution feeder bb direct connection from the top
bb rear connection

35
Cubicles 70-M

Functional unit
Vertical 70-M busbar
bb specifically designed for 70-M drawers
bb installed at the rear of the drawers area
bb can be simple, for full-width drawers cubicle

Rated current In (A) No. of bars / phase Icw max (kA)


IP31 / 35°C
800 2 x 20 x 8 50
1250 2 x 30 x 8 75
2000 2 x 50 x 8 100

Dimensions
All functional units
Type of functional unit Type of connection
Withdrawable in drawer bb side connection from the front
bb rear connection

36
Cubicles 70-2

Functional unit
Vertical 70 busbar

70 mm
70 mm
70 mm
bb allows the installation of NT08-16/NS800-1600 and
all the distribution feeders and motor control feeders
bb installed at the rear of the switchgear cubicle,
throughout all its height

Rated current In (A) Nb of bars / phase Icw max (kA)


IP31 / 35°C
1010 1 x 40x10 50
1200 1 x 50x10 50
1750 1 x 80x10 80
2100 1 x 100x10 100

Dimensions
Dimensions for electrical distribution > 630 A
Type of distribution Circuit breaker Type of connection Qty of cubicle
1 incomer or Masterpact NT08-16 bb side connection from the front 1
1 distribution feeder bb direct connection from the bottom 1
Compact NS800-1600 A bb direct connection from the top 1
bb rear connection 1

Dimensions for functional units y 630 A


Small distribution (C60)
Type of functional unit Type of connection
Withdrawable in drawer bb side connection from the front
bb rear connection
Disconnectable on mounting plate bb side connection from the front

Other functional units


Type of functional unit Type of connection
Disconnectable on Polyfast bb side connection from the front
bb rear connection
Removable on Polyfast bb side connection from the front
bb rear connection
Withdrawable in drawer bb side connection from the front
bb rear connection

For specific applications (Marine, Seismic, DEP Shell and Nuclear).

37
Cubicles 70-F

Functional unit
Vertical 70 busbar
bb allows the installation of NT08-16/NS800-1600 and
all the distribution feeders and motor control feeders
bb installed at the rear of the switchgear cubicle,
throughout all its heigh

Rated current In (A) Nb of bars / phase Icw max (kA)


IP31 / 35°C
1010 1 x 40x10 50
1200 1 x 50x10 50
1750 1 x 80x10 80
2100 1 x 100x10 100

Dimensions
Dimensions for electrical distribution > 630 A
Type of distribution Circuit breaker Type of connection Qty of cubicle
1 incomer or Masterpact NT08-16 bb side connection from the front 1
1 distribution feeder
bb direct connection from the bottom 1
bb direct connection from the top 1
bb rear connection 1

Dimensions for electrical distribution y 630 A


Circuit breaker Rating (A) No. of pole Type of connection
Compact NSX 100 to 630 3P / 4P bb side connection from the front
bb rear connection
Compact NS 100 to 400 3P / 4P bb side connection from the front
bb rear connection

38
Cubicles 185 (Jean Müller)

Functional unit
Vertical 185 busbar
bb dedicated to Jean Müller fuse-switches installation
bb installed at the rear of a H2200 mm
switchgear cubicle, throughout all its height

Rated current In (A) Nb of bars / phase Icw max (kA)


IP35 / 35°C
630 1 x 40x10 80
800 1 x 50x10 80
1250 1 x 80x10 80
1500 1 x 100x10 80

Dimensions
All functional units
Type of functional unit Type of connection
Withdrawable in drawer bb side connection from the front
bb rear connection

39
Support tools Example of configuration

1
Customer’s needs

single-wire diagramm of the installation


415 V - 3P+T - 70 kA - 3200 A
250 A
100 A
100 A
1250 A

1250 A

250 A
100 A
35 kW
5,5 kW
1,5 kW
35 kW
5,5 kW
100 kW
150 kW
1,5 kW
1,5 kW
1,5 kW
1,5 kW

15 kW
1,5 kW
1,5 kW

15 kW

45 kW
5,5 kW
G

100 kVAR
3200 A

3200 A

800 A

Main characteristics of the switchboard


Norme de référence IEC 61439-2
Tension d’isolement 1000 V
Tension de fonctionnement 380 / 415 V
Intensité du jeu de barres principal 3200 A
Intensité de court-circuit 70 kA
Intensité de crête 154 kA
Fréquence 50 Hz
Jeu de barres nombre de phases 3
matériau cuivre
isolation air
Forme 3
Degré de protection enveloppe extérieure IP 31
intérieur IP 20
Tension auxiliaire 230 V
Compensation d’énergie 100 kVAR
Nombre de gradins 8
Arrivée câble
Départ câble
Température ambiante 35 °C
Altitude ≤ 2000 m
Couleur extérieure du tableau RAL 7035

40
Support tools Example of configuration

2
Determine the functional units
according to the following parameters:
bb In current,
bb voltage,
bb short-circuit current,
bb number of pole

3
bb type and technology of the functional units.

Deduce the number and the type of


necessary cubicles

415 V - 3P+T - 70 kA - 3200 A


250 A
100 A
100 A
1250 A

1250 A

250 A
100 A
35 kW
5,5 kW
1,5 kW
35 kW
5,5 kW
100 kW
150 kW
1,5 kW
1,5 kW
1,5 kW
1,5 kW

15 kW
1,5 kW
1,5 kW

15 kW

45 kW
5,5 kW
G

100 kVAR
3200 A

3200 A

800 A

Type of functional
VVD

VVD
VVD
INC

INC

INC
MC
MC
MC
MC

MC
MC
MC
MC
MC
MC

MC
MC
MC
MC
ED
ED
ED
ED

ED

ED
ED

EC
units(1)
C

Technology
Polyfast
Polyfast
Polyfast

Polyfast
Polyfast
chassis
chassis
chassis
chassis
chassis
chassis
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer
drawer

drawer
drawer
drawer
drawer
drawer
fixed

No. of vertical fixed


modules
(1 module = 25 mm)
8 x 12.5
kVAR
12

18

30

19
19

12
18
48
6
3
3
6

3
3
3
6
6
6
6

6
6
4
4
6

Cubicles,
1 cubicle

1 cubicle
115 / 70-2
1 cubicle

height = 2350 mm,


1 cubicle 2 cubicles
rear connection 66 modules = 1 cubicle 70-M 26 modules = 1 cubicle 70-M
115 / 70-2 115
with around 10 %
of reserve

(1)To determine the dimensions of each functional unit, see the selection table.
INC: high power circuit-breaker incoming.
C: coupling.
EC: Power factor compensation and harmonic filtering.
ED: electrical distribution.
MC: motor control.
VVD = Variable speed drive and soft starter.

41
Support tools Design your installation
Front faces layout

Ground fastening
compulsory fastening point
optional fastening point

bb class 8.8 screws: M10 TH screws + washers


(∅ 25 mm external, thickness 3 mm) +
CS ∅ 10 mm contact washers

bb Front connection bb Rear connection D1000/1200 mm bb Rear compartment D1400 mm

bb 70-M front connection. bb 70-M rear connection.

Minimum clearances around switchboard

bb For connection by cables and fishplating of the horizontal busbar, provide 500 mm
above the switchboard.
bb When ceiling clearance is limited, provide a horizontal busbar of 3200 A maximum
(4 bars / phase) for fishplating and connection from the front of the switchboard.

Clearance above the switchboard. Rear connection. Front connection. Cubicle, width = 1150 mm.

42
Notes

43
Okken performances Futher technical information

General data
Standard environment
reference standards IEC 60439-1 / IEC 61439-2
IEC 60529
climatic resistance damp heat withstand IEC 60068-2-30
dry heat withstand IEC 60068-2-2
low temperature withstand IEC 60068-21
salt spray withstand IEC 60068-2-11
installation indoor
earthquake withstand IEC68-3-3 and IEC721-26
according to IBC 2000
HN20E53
environment (CEM) type 2

Mechanical data
cable entry top / bottom
access front / rear
degree of protection (IP) 22 / 31 / 41 /54
impact withstand index (IK) 10
form 2b / 3b / 4a / 4b
withdrawability FFD / WFD / WFW / WWW
dimensions (mm) height 2200 / 2350
width 600 / 650 / 800 / 900
1000 / 1100 / 1150 / 1300
depth 600 / 1000 / 1200 / 1400
installation modularity in height 2200 mm 66 modules of 25 mm
a cubicle height 2350 mm 72 modules of 25 mm
average weight cubicle 115 (2500A) ~ 850 kg
cublicle 70-M ~ 650 kg
cubicle 70-2 PCC ~ 700 kg
cubicle 70-2 MCC ~ 600 kg
cubicle 230 (6300A) ~ 1300 kg
panel coating epoxy / polyester powder (SP03)
polymerised, > 50 μ
framework galvanised
panelling colour RAL 1000

Electrical data
rated insulation voltage (Ui) 1000 V
rated operational voltage (Ue) 415 / 690 V CA
rated frequency (F) 50 / 60 Hz
rated impact withstand voltage (Uimp) 12 kV
rated auxiliary circuit voltage 230 V AC max.
surge category IV
degree of pollution 3
rated current (In) 6300 A
horizontal busbar rating 7300 A
vertical busbar rating 4000 and 2100 A
horizontal busbar short-term rated current (Icw) 1s 50 / 80 / 100 / 150 kA rms
rated peak current 110 / 176 / 220 / 330 kA peak
vertical busbar short-term rated current (Icw) 1s 50 / 80 / 100 kA rms
rated peak current 110 / 176 / 220 kA peak
rated conditional short-circuit current (lsc) up to 150 kA
internal arcing protection according to IEC 61641 100 kA eff 0.3 s
earthing diagram TT-IT-TNS-TNC
current limit of power incoming and outgoing feeders up to 6300 A
power limit of motor control feeders up to 250 kW 690 V

44
45
© 2010 - Schneider Electric - All rights reserved

Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation
35 rue Joseph Monier of the information given in this document.
CS 30323
F-92506 Rueil Malmaison Cedex

RCS Nanterre B 954 503 439


Capital social 896 313 776 €
www.schneider-electric.com Design: Schneider Electric
Photos: Schneider Electric
Printing :

06-2010

You might also like