R911339613 01

Download as pdf or txt
Download as pdf or txt
You are on page 1of 40

Electric Drives Linear Motion and

and Controls Hydraulics Assembly Technologies Pneumatics Service

Rexroth IndraControl R911339613


Edition 01
VAP 01.1
Power Supply Unit
Operating Instructions
Bosch Rexroth AG VAP 01.1

Change Record
Edition Release Notes
Date
Edition 01 2014-08 First edition

Copyright
© Bosch Rexroth AG 2014
This document, as well as the data, specifications and other information set
forth in it, are the exclusive property of Bosch Rexroth AG. It may not be repro-
duced or given to third parties without its consent.
Liability
The specified data is intended for product description purposes only and shall
not be deemed to be a guaranteed characteristic unless expressly stipulated in
the contract. All rights are reserved with respect to the content of this docu-
mentation and the availability of the product.
Editorial Department
Development automation systems, control platform GW (MK/MePe)

RS-461dcaa53d9a7b1e0a6846a501d528df-1-en-US-4
VAP 01.1 Bosch Rexroth AG
Table of Contents

Table of Contents
Page
1 About this Documentation..................................................................... 1

2 Product Identification and Scope of Delivery........................................ 2


2.1 Product Identification............................................................................ 2
2.2 Scope of Delivery................................................................................... 2

3 Using the Safety Instructions................................................................. 2


3.1 Safety Instructions – Structure.............................................................. 2
3.2 Explaining Signal Words and Safety Alert Symbol................................. 3
3.3 Symbols Used........................................................................................ 4

4 Intended Use.......................................................................................... 4

5 Spare Parts, Accessories and Wear Parts.............................................. 5

6 Ambient Conditions............................................................................... 5

7 Technical Data....................................................................................... 6
7.1 Input...................................................................................................... 6
7.2 Buffer Time............................................................................................ 8
7.3 Output................................................................................................... 9
7.4 Failure Safety....................................................................................... 11
7.5 Protective Properties........................................................................... 11
7.6 Safety................................................................................................... 12
7.7 Insulation Resistance........................................................................... 12
7.8 Peak Current Strength......................................................................... 13
7.9 Charging Accumulators........................................................................ 14
7.10 Feeding-Back Load............................................................................... 14

8 Standards............................................................................................ 14
8.1 Standards used.................................................................................... 14
8.2 CE Marking........................................................................................... 14
8.2.1 Declaration of Conformity................................................................... 14
8.3 UL/CSA Certification............................................................................ 15

9 Interfaces............................................................................................. 16
9.1 Connector Panel.................................................................................. 16

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P I
Bosch Rexroth AG VAP 01.1
Table of Contents

Page
9.2 Protective Earth (PE) Terminal............................................................ 16

10 Mounting, Demounting and Electric Installation.................................. 17


10.1 Housing Dimensions............................................................................ 17
10.2 Installation Notes................................................................................. 17
10.3 Mounting.............................................................................................. 18
10.4 Demounting......................................................................................... 18
10.5 Electric Connection............................................................................. 19
10.5.1 Voltage Supply Scheme....................................................................... 19
10.5.2 Terminals and Wiring........................................................................... 21
10.5.3 Parallel Use to Increase Output Rate................................................... 21
10.5.4 External Input Protection..................................................................... 21
10.5.5 Two-Phase Operation.......................................................................... 22
10.6 Use in Tightly Sealed Housing.............................................................. 22
10.7 Installation Orientations...................................................................... 22

11 Commissioning.................................................................................... 24

12 Device Description............................................................................... 25

13 Error Causes and Troubleshooting...................................................... 25

14 Maintenance........................................................................................ 26
14.1 General Information............................................................................. 26
14.2 Regular Maintenance Tasks................................................................. 26

15 Ordering Information........................................................................... 26
15.1 Accessories and Spare Parts............................................................... 26
15.2 Type Code............................................................................................ 26

16 Disposal............................................................................................... 27
16.1 Return.................................................................................................. 27
16.2 Batteries and Accumulators................................................................. 28
16.3 Packaging............................................................................................. 28

17 Service and Support............................................................................ 28

Index.................................................................................................... 31

II DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
About this Documentation

1 About this Documentation


Overview on target groups and product phases
The activities, product phases and target groups that refer to the present docu-
mentation are highlighted in red color in the following figure.
Example:
In the product phase "Mounting", the "Mechanic/electrician" can execute the ac-
tivity "Install" using this documentation.

Product Mounting
Selection Engineering Commissioning Operation Decommissioning
phases (assembly/installation)

Presales Aftersales

Design engineer
Mechanic/
electrician
Programmer Programmer
Technologist Commissioning engineer
Target Process Technologist
groups specialist
Process specialist
Machine
operator
Maintenance Mechanic/
technician electrician
Service Disposal company
Select Unpack Parameterize Optimize Operate Dismount
Prepare Mount Program Test Maintain Dispose
Activities Design Install Configure Remove
faults
Construct Simulate
Create
the NC program

Fig. 1-1: Assigning the present documentation to the target groups, product phases and ac-
tivities of the target group

Purpose
This document instructs the technical staff of the machine manufacturer on how
to perform the mechanical and electrical installation safely and on how to com-
mission the device.
Required qualifications: Individual who is able to assess the tasks assigned and
identify possible safety risks owing to qualification in the subject, knowledge
and experience. The individual should also be familiar with the standards and
regulations.
Scope
This operating instruction applies to all variants whose type code starts with
"VAP…".

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 1/35
Bosch Rexroth AG VAP 01.1
Using the Safety Instructions

The type code specifications are located on the type plate of the device. Also re-
fer to chapter 2.1 "Product Identification" on page 2.
Related documents
We recommend the power supply unit VAP 01.1 for all Bosch Rexroth 24 volt de-
vices. For more information, refer to the respective operating instructions in the
media directory (http://www.boschrexroth.com/various/utilities/mediadirecto-
ry/).

2 Product Identification and Scope of Delivery


2.1 Product Identification
The type plate is located on the rear side or at the side of the device.
13026

7261 2
BTV40.1AHB-256S-P5C- 3
Made in Germany
Bosch rexroth Electric Drives and Controls GmbH

UN-FW 1 2 5 6
4 5 6
15 3 TYP: PCPNL PEN400J1287 IS110-T 10
MNR: 1070170021 -101 03W19 7 7261
4 MNR: 1070086255 -101
V-Nr: 1 FD: 05W01
UN IN 3AC 230V 50760Hz
8 7
UN: AC 230V / 115V 13
IN OUT 10/7,5/5/5/1,5/1,5A max. 11 IN: 0,7A / 1,4A
I-C-B-T-V 9 8 I-C-B-H-T-V
SN: 004012652
14
IND.CONT-EQ 17YB
SW-Version V0,002 10 XXXXXXXXXXXXXXXXX
9
Bosch Rexroth Electric Drives and Controls GmbH
D-6471 1 Erbach Made in Germany

12 12 16 15
D-64711 Erbach

16
IND.CONT.EQ 17YB
11
13
SN: 123456814 14

1 Logotype 9 Test marking


2 Division or plant number 10 Version number
3 Type designation code (type code) 11 CE mark
4 Parts number 12 Underwriters Laboratories Inc. mark
5 State of revision 13 Serial number as barcode
6 Date of manufacture (yyWww) 14 Serial number
7 Nominal voltage 15 Designation of origin
8 Nominal current 16 Company address
Fig. 2-1: Exemplary type plates

2.2 Scope of Delivery


● Power supply unit VAP 01.1
● Safety instructions

3 Using the Safety Instructions


3.1 Safety Instructions – Structure
The safety instructions are structured as follows:

2/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Using the Safety Instructions

Safety alert symbol Consequences and


Signal word source of danger
CAUTION Burns and chemical burns due to wrong
battery treatment!
Do not open the batteries and do not heat them over 80 °C.

Avoiding danger
Fig. 3-1: Safety instructions – Structure

3.2 Explaining Signal Words and Safety Alert Symbol


The safety instructions in this documentation contain specific signal words (dan-
ger, warning, caution, notice) and, if necessary, a safety alert symbol (according
to ANSI Z535.6-2006).
The signal word is meant to draw the reader's attention to the safety instruction
and signifies the degree of danger.
The safety alert symbol (a triangle with an exclamation point), which precedes
the signal words danger,warning and caution is used to alert the reader to per-
sonal injury hazards.

DANGER
In case of non-compliance with this safety instruction, death or serious injury
will occur.

WARNING
In case of non-compliance with this safety instruction, death or serious injury
can occur.

CAUTION
In case of non-compliance with this safety instruction, minor or moderate injury
could occur.

NOTICE
In case of non-compliance with this safety instruction, property damage could
occur.

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 3/35
Bosch Rexroth AG VAP 01.1
Intended Use

3.3 Symbols Used


Notes are displayed as follows:

This is a note.

Tips are displayed as follows:

This is a tip.

4 Intended Use
The Bosch Rexroth power unit supply VAP 01.1 is a compact 24 V power supply
unit for industrial use. We recommend the power supply unit VAP 01.1 to supply
the Bosch Rexroth components of the industrial automation with protective ex-
tra-low voltage supply. The power supply unit is designed for up to 240 watts.

NOTICE Danger of device damage if not the expressly


stated accessories, mounting parts, compo-
nents, cables, lines, software and firmware are
used.
The VAP 01.1 power supply units may only be used as intended and with the ac-
cessories and mounting parts specified in this documentation. Components that
are not expressly mentioned must neither be attached nor connected. The same
applies to cables and lines.
Only to be operated with the component configurations and combinations ex-
pressly defined and with the software and firmware specified in the correspond-
ing documentations.

Typical areas of application of the power supply unit VAP01.1:


● Voltage supply for 24 V control components
● Voltage supply for 24 V HMI
● Voltage supply for PC components
● Voltage supply for centralized and decentralized inputs and outputs
The power supply unit VAP 01.1 may only be operated under the assembly and
installation conditions, in the position of use and under the ambient conditions
(temperature, degree of protection, humidity, EMC, etc.) specified in this docu-
mentation.

4/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Ambient Conditions

5 Spare Parts, Accessories and Wear Parts


There are no spare parts, accessories and wear parts for the power supply unit
VAP 01.1.

6 Ambient Conditions
Operating temperature -25 °C to +70 °C (-13 °F to 158 °F) Reduced output current acc. to 6-1
Output current reduc- 3.2 W/°C 45-60 °C (113 °F to 140 °F)
tion 6 W/°C 60-70 °C (140 °F to 158 °F)
Storage temperature -40 to +85 °C (-40 °F to 185 °F) Storage and transport
Humidity 5 to 95 % r.H. (relative humidity) IEC 60068-2-30
Do not apply voltage in case of con-
densation
Sinusoidal vibration 2-17.8 Hz: ±1.6 mm; IEC 60068-2-6
17.8-500 Hz: 2 g
2 hours per axis
Shock 30 g 6 ms, 20 g 11 ms IEC 60068-2-27
3 bumps per direction,
18 bumps in total
Height 0 to 6.000 m (0 to 20 000 ft) Reduce output current or ambient
temperature above 2000 m sea level.
Output current reduc- 15 W/1000 m or 5 °C/1000 m Above 2000 m (6500 ft), refer to the
tion (for height) figure 6-2
Overvoltage category III EN 50178, heights up to 2000 m
II Heights from 2000 m to 6000 m
Contamination level 2 EN 50178, non-conducting

Tab. 6-1: Ambient conditions

12 A
1
10
2
8
6
4
2
3
0
-25 0 20 40 60 70°C

① Short-time ③ Ambient temperature


② Permanent
Fig. 6-1: Permitted output current depends on the ambient temperature at 24 V

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 5/35
Bosch Rexroth AG VAP 01.1
Technical Data

12 A
1
10 < 40 °C
< 50 °C 2
8 < 60 °C
6
4
2
0 3
0 2000 4000 6000 m

① Short-time ③ Height above sea level


② Tambient temperature
Fig. 6-2: Permitted output current depends on the height and the ambient temperature at
24 V

7 Technical Data
7.1 Input
AC input nom. 100-120 V AC Automatic input selection,
200-240 V AC TN-, TT-, IT mains
Also refer to the figure 7-4
AC input range 90-132 V AC 100-120 V range, continuous operation
180-264 V AC 200-240 V range, continuous operation
85-90 V AC Short runtime or with output current reduction
264-300 V AC < 0.5 seconds
Input frequen- nom. 50-60 Hz ±6 percent
cy

Tab. 7-1: Input

100 V AC 120 V AC 230 V AC


Input current typ. 4.34 A 3.73 A 2.23 A at 24 V, 10 A
Power factor① typ. 0.61 0.59 0.51 at 24 V, 10 A, refer to the figure 7-1
Crest factor② typ. 2,61 2,83 3,3 at 24 V, 10 A
Switch-on delay typ. 700 ms 800 ms 850 ms Refer to the figure 7-3
Rise times typ. 35 ms 35 ms 35 ms 0 mF, 24 V, 10 A, refer to the figure 7-3
typ. 75 ms 75 ms 75 ms 10 mF, 24 V, 10 A, refer to the figure 7-3
Switch-on over- max. 100 mV 100 mV 100 mV Refer to the figure 7-3
shoot

6/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Technical Data

100 V AC 120 V AC 230 V AC


Switch-on volt- typ. 80 V AC 80 V AC ns Stable value, refer to the figure 7-1
age
Switch-off volt- typ. 75 V AC 75 V AC ns Stable value, refer to the figure 7-1
age
① The power factor is the ratio of the true (or real) power to the apparent power in an AC
circuit.
② The crest factor is the mathematical ratio of the peak value to the RMS value of the input
current wave form.
Tab. 7-2: Input

1 2

3 4 5 6 7

AC 90 V 132 V 180 V 264 V

① POFF ⑥ Invalid range from 132 to 180 V. An op-


② Nominal input range eration within this range does not cause
③ Switch-off any damages
④ Switch-on ⑦ Valid range 200 to 240 V
⑤ Valid range 100 to 120 V ⑧ VON
Fig. 7-1: Input voltage range

1
6A
V
5 100
AC
4 V
120
3 AC
30 V
2 AC 2
1
0
2 3 4 5 6 7 8 9 10 11 12 A 2

① Input current, typical


② Output current
Fig. 7-2: Input current depends on the input voltage

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 7/35
Bosch Rexroth AG VAP 01.1
Technical Data

- 5%
2
5
3 4

① Input voltage ④ Rise time


② Output voltage ⑤ Overshoot
③ Switch-on delay
Fig. 7-3: Switch-on Response, Definitions

1
0.65
c
100 Va
0.6
120 Vac
0.55
0.5 230 Vac
0.45
0.4
0.35 2
2 3 4 5 6 7 8 9 10 11 12 A

① Power factor, typical


② Output current
Fig. 7-4: Power factor and output current

7.2 Buffer Time


100 V AC 120 V AC 230 V AC
Buffer time typ. 62 ms 107 ms 103 ms 5 A, 24 V, refer to the figure 7-5
typ. 23 ms 46 ms 47 ms 10 A, 24 V, refer to the figure 7-5
typ. 17 ms 35 ms 37 ms 12 A, 24 V, refer to the figure 7-5

Tab. 7-3: Buffer time

8/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Technical Data

1 a) 24 V 5 A typ.
120 ms a b) 24 V 5 A min. a
b c) 24 V 10 A typ.
100 d) 24 V 10 A min. b
e) 24 V 12 A min.
80
60 c
d c
40 e d
e
20
0
AC 85 100 120 180 230 V 2

① Buffer time
② Input voltage
Fig. 7-5: Buffer time vs. Input voltage

- 5%
3

① Input voltage ③ Output voltage


② Zero transition ④ Buffer time
Fig. 7-6: Switch-off response, definitions

7.3 Output
Output voltage nom. 24 V
Adjustment range Min. 24-28 V Guaranteed
Max. 30 V End position, potentiometer clockwise
Factory settings 24.1 V ±0,2%, at full load, cold unit
Power control Max. 70 mV 90 to 132 V AC or 180 to 264 V AC
Load control Max. 100 mV Static value, 0 A → 10 A → 0 A
Superimposed alternat- Max. 50 mVpp 20 Hz to 20 MHz, 50 ohms
ing and interference
voltage
Output capacity typ. 7 000 µF

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 9/35
Bosch Rexroth AG VAP 01.1
Technical Data

Output current nom. 12 A At 24 V, at < 45 ℃ ambient temperature, refer


to the figure 7-7
nom. 10 A At 24 V, at < 60 ℃ ambient temperature, refer
to the figure 7-7
At 28 V, at < 45 ℃ ambient temperature, refer
nom. 10.3 A to the figure 7-7
At 28 V, at < 60 ℃ ambient temperature, refer
nom. 8.6 A to the figure 7-7
Output rate nom. 288 W At < 45 ℃ ambient temperature
nom. 240 W At < 60 ℃ ambient temperature
Short circuit current Min. 14 A Load resistance 100 mOhms,
Refer to the figure 7-7
max. 18 A Load resistance 100 mOhms,
Refer to the figure 7-7

Tab. 7-4: Output

1 2
28 V
24
20
+60°C
16
+25°C
12 -25°C
8
4
0 3
0 2 4 6 8 10 12 14 16 18 20 A

① Output voltage ③ Output current


② Setting range
Fig. 7-7: Output voltage and output current, typical

Peak current capacity (up to several milliseconds)


The power supply unit VAP 01.1 can generate a peak current higher that the
specified short-time withstand current. The current consumption load can be
started and more power switches can be safely operated. The output capacitor
in the power supply unit provides additional current. During this process, the
capacitors are discharged causing a voltage drop at the output. For detailed
characteristics, refer to chapter 7.8 "Peak Current Strength" on page 13.
Voltage drop of peak typ. 24 V to 18.5 V At 20 A for 50 ms, resistive load
current typ. 24 V to 17.5 V At 50 A for 2 ms, resistive load
typ. 24 V to 12 V At 50 A for 5 ms, resistive load

Tab. 7-5: Peak current capacity

10/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Technical Data

100 V AC 120 V AC 230 V AC


Efficiency typ. 90,70 % 91,00 % 91,60 % 10 A, 24 V
Power loss typ. 5.8 W 8.4 W 7.5 W 0A
typ. 12.0 W 12.3 W 11.3 W 5 A, 24.5 V
typ. 25.1 W 24.1 W 22.4 W 10 A, 24.5 V
typ. 31.9 W 29.6 W 27.9 W 12 A, 24.5 V

Tab. 7-6: Efficiencies and losses

7.4 Failure Safety


100 V AC 120 V AC 230 V AC
Expected serv- Min. 38,000 h 50,000 h 75,000 h 40 ℃, 24 V, 10 A
ice life Min. 27,000 h 34,000 h 53,000 h 40 ℃, 24 V, 12 A
Min. 93,000 h 99,000 h 118,000 h 40 ℃, 24 V, 5 A
Min. 108,000 h 15 years 15 years 25 ℃, 24 V, 10 A
MTBF SN 612,000 h 638,000 h 821,000 h 40 ℃, 24 V, 10 A
29500, 520,000 h 542,000 h 698,000 h 40 ℃, 24 V, 12 A
IEC 61709 1,019,000 h 1,058,000 h 1,393,000 h 25 ℃, 24 V, 10 A

Tab. 7-7: Failure safety

7.5 Protective Properties


Output protection Electrically protected against overload, idling and short circuits
Output overvoltage pro- typ. 35 V DC If an internal power supply unit error occurs, a redundant
tection max. 39 V DC circuitry limits the maximum output voltage. The output is
shut down and the power supply unit tries to restart.
Output overcurrent pro- Electronically Refer to the figure 7-7
tection limited
Degree of protection IP 20 EN/IEC 60529
Protection against enter- > 3.5 mm E.g. screws, small parts
ing
Protection against over- Yes Output shutdown with automatic restart
temperature
Transient protection at MOV Metal oxide varistor
input
Internal input fuse T6.3 A H.B.C. Cannot be exchanged by user

Tab. 7-8: Protection properties

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 11/35
Bosch Rexroth AG VAP 01.1
Technical Data

7.6 Safety
Input and output separation Safety extra low voltage (SELV) IEC/EN 60950-1
Functional extra-low voltage EN 60204-1, EN 50178, IEC
with protective separation 60364-4-41
(PELV)
Doubled or increased insulation
Protection class I PE (grounding with protective func-
tion) connection required
Insulation strength > 5 MΩ Input to output, 500 V DC
Protective conductor resist- < 0.1 Ω Between housing and protective con-
ance ductor terminal
Touch current (leakage cur- Typ. 0.36 mA 100 V AC, 50 Hz, TN mains
rent) Typ. 0.50 mA 120 V AC, 60 Hz, TN mains
Typ. 0.64 mA 230 V AC, 50 Hz, TN mains
< 0.45 mA 110 V AC, 50 Hz, TN mains
< 0.62 mA 132 V AC, 60 Hz, TN mains
< 0.85 mA 264 V AC, 50 Hz, TN mains

Tab. 7-9: Safety

7.7 Insulation Resistance

1
L
N B
2
A +
-
C
3

① Input ③ Ground, PE
② Output
Fig. 7-8: Insulation resistance
A B C
Type test 60 s 2,500 V AC 3,000 V AC 500 V AC
Factory test 5s 2,500 V AC 2,500 V AC 500 V AC
Field test 5s 2,000 V AC 2,000 V AC 500 V AC

Tab. 7-10: Insulation resistance

12/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Technical Data

Type and factor tests


Type and factory tests made by the manufacturer. Do not repeat these checks in
the field!
Field test rules
Use suitable test equipment and apply voltage at a slow ramp. Connect L and N
like all output poles.
The output voltage is floating and is ohmically not connected to the ground.
To meet the requirements on the functional extra-low voltage with protective
separation (PELV) acc. to EN60204-1 § 6.4.1, the positive and the negative pole
or any other part of the output circuitry should be connected to the protective
conductor system. Thus, an immediate start of the load or that it cannot be
switched off anymore in case of undetected earth faults can be avoided.

7.8 Peak Current Strength


Magnet coils, contactors and pneumatic modules are often equipped with a sta-
tionary coil and a pickup coil. The switch-on power requirement of a pickup coil
is many times higher than the requirement of the stationary coil. The power re-
quirement is normally also higher than the nominal output current (including the
power supplies). This also applies if the capacitive load is started.
Branch circuits are often protected by circuit breakers or fuses. In case of a
short circuit or overload in the branch circuit, a certain amount of overcurrent is
required to blow the fuse. The peak current strength ensures the safe operation
of the subsequent circuit breakers.
If the input voltage is switched-on before such an event occurs, the integrated
output capacitors in the power supply unit can provide additional current. Dis-
charging a capacitor causes a voltage drop at the output. Two typical voltage
drops are shown in the following example:

24 V 1 24 V

18,5 V 50 A 1
20 A
12 V

2 2
0A 0A
10 ms/DIV 1ms/DIV

① Output voltage
② Output current
Fig. 7-9: Peak load 20 A (resistive) for 50 ms; output voltage drops from 24 V to 18.5 V. Peak
load 50 A (resistive) for 5 ms; output voltage drops from 24 V to 12 V

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 13/35
Bosch Rexroth AG VAP 01.1
Standards

7.9 Charging Accumulators


The power supply unit VAP 01.1 may not be used to charge accumulators.

7.10 Feeding-Back Load


Devices such as decelerating motors and inductors can feed back voltage to the
power supply unit. This property is also called "electromotive force" (EMF).
The power supply unit VAP 01.1 is interference resistant. No malfunctions occur
if the voltage is fed back to the power supply unit irrespective of whether the
power supply unit is switched on or off.
The maximum fed-back voltage is 35 V DC. The fed-back energy can be calcula-
ted using the integrated output capacitor, see chapter 7.3 "Output" on page 9.

8 Standards
8.1 Standards used
Standard Meaning
EN 61558-2-17 Safety of power transformers
EN/IEC 60204-1 Safety of machinery
EN/IEC 61131-1 Programmable controllers

Tab. 8-1: Standards used

8.2 CE Marking

8.2.1 Declaration of Conformity

The electronic products described in the present operating instruction comply


with the requirements and the target of the following EU directive and with the
following harmonized European standards:
EMC Directive 2004/108/EC
The electronic products described in the present operating instruction are inten-
ded for use in industrial environments and comply with the following require-
ments:

14/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Standards

Standard Title Edition


DIN EN 61000-6-4 Electromagnetic Compatibility (EMC) September
(VDE 0839-6-4) Part: 6-4: Generic standards – Emission standard for indus- 2007
trial environments (IEC 61000-6-4:2006)
DIN EN 61000-6-2 Electromagnetic Compatibility (EMC) March 2006
(VDE 0839-6-2) Part: 6-2: Generic standards – Noise immunity for industrial
environments (IEC 61000-6-2:2005)

Tab. 8-2: Standards for electromagnetic compatibility (EMC)

Non-compliance with CE conformity due to modifications at the de-


vice.
The CE marking is only valid for the device in its delivery state. After
having modified the device, CE conformity is to be verified.

8.3 UL/CSA Certification

The devices are certified according to


● UL508 (Industrial Control Equipment) and
● C22.2 No. 142-M1987 (CSA)
UL file no. E239264
However, there can be combinations or extension stages with limited or missing
certification. Thus, verify the registration according to the UL marking on the de-
vice.

Loss of UL/CSA conformity due to modifications at the device.


UL and CSA marking applies only to the device in its delivery state.
After modifying the device, UL conformity and CSA conformity are to
be verified.

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 15/35
Bosch Rexroth AG VAP 01.1
Interfaces

9 Interfaces
9.1 Connector Panel

1 2

+ + – –
DC 24 V / 10 A

24-28 V

DC on

AC 100-120 / 200-240 V

N L

3
① Protective earth (PE) terminal ③ Connection terminal for input voltage
② Connection terminal for output voltage
Fig. 9-1: Connector panel of the power supply unit VAP 01.1

9.2 Protective Earth (PE) Terminal


Ensure a sufficient conductor cross section during protective earth wiring. Also
note EN 60204 Part 1 (maximum electric resistance and check of the protective
earth wiring).

WARNING Dangerous shock currents caused by insuffi-


cient PE connections!
PE connections must not be affected by mechanical, chemical or electrochemi-
cal influences. The connection must be permanently fix.

16/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Mounting, Demounting and Electric Installation

10 Mounting, Demounting and Electric Installation


10.1 Housing Dimensions
60

131,7
124

111,5
121,3

60

1 2
① Front view
② Top View
Fig. 10-1: Housing dimensions

10.2 Installation Notes


● The power supply unit VAP 01.1 is intended for mounting rail mounting
● The LED display has to be visible
● Provide the following minimum distances for a sufficient cooling and mount-
ing:
– 50 mm to the bottom side
– 80 mm to the upper side
● Lay all connecting cables in loops
● Provide cables with strain relief
● Keep the biggest distance possible to noise sources when installing the pow-
er supply unit VAP 01.1

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 17/35
Bosch Rexroth AG VAP 01.1
Mounting, Demounting and Electric Installation

10.3 Mounting
1. Hang the power supply unit VAP 01.1 onto the mounting rail from above
and exert slight pressure to engage the UPS in the lower section of the
housing.
2. Mount end clamps on the mounting rail on both sides of the power supply
unit to avoid lateral motion in case of vibrations.
3. Connect and fix cables.

10.4 Demounting
1. Shut down connected devices.
2. Switch off supply voltage of the power supply unit.
3. Detach and remove cabling.
4. Release power supply unit.

18/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Mounting, Demounting and Electric Installation

10.5 Electric Connection

10.5.1 Voltage Supply Scheme

Min. 16 mm2 (green/yellow)


Incoming supply lines To control cabinet housing
16 mm2 (green/yellow)
To machine
6 mm2 (green/yellow)

PE
L3
L2
L1

All housing parts (functional earth)


N
W1

PE
PE
PE
PE

PE
U1
V1

PE star point
N

16 mm² (green/yellow)

Fuses, better motor circuit breaker


Overvoltage
400V 4 mm² (green/yellow) category III
Transformer acc. to
EN 60742 230V
N-conductor may Overvoltage
4 mm² (green/yellow) category II
L3.1
L1.1
L2.1

only be used if 1
PE
N

operator agrees! PE N U2 PE

E.g. drives Terminals are


insulated
4 mm² (green/yellow)

PE
N1
U2
N1
PE
U2

230 V supply, e.g.


operator terminal
Power supply unit
service socket(s)
VAP01.1H-W23
024-010-NN
Power supply unit
VAP01.1H-W23
024-010-NN DC 24 V
UL
Overvoltage DC 24 V
0 V UL
category I
UM
0 V UM

① PE bars are to be installed preferably on of the copper strips has to be at least


the mounting plate. For insulated PE equal to that of the incoming mains ca-
bars, connect both ends to the mount- ble.
ing plate using copper strips with a max- UL Logic voltage
imum length of 20 cm. The cross section UM Module voltage
Fig. 10-2: Power Routing 230 V

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 19/35
Bosch Rexroth AG VAP 01.1
Mounting, Demounting and Electric Installation

Overvoltage category I
Terminal block UK6-FSI/6 with
miniature circuit breaker TCP 2 A
UL+24V A
(PHOENIX CONTACT)
3
recommended
2
4
0 V UL
A
6 mm² (blue) Control

UM+24V A
Digital input and
output modules
1
FE
0 V UM
A 2
6 mm² (blue)

Control panel
1 1
2 2
FE

B 10 mm² (green/yellow)
PE bar

6 mm² Connect to FE of control panel


6 mm² Connect to FE of HMI or control
6 mm² Connect to FE of UPS

10 mm² (green/yellow)

FE Functional earth ② Polarity reversal of the connectors can


A Insulated terminal block result in device destruction (fire hazard)
B Non-insulated terminal block if no additional external protection is
① Easy to remove and visible provided. Reason: Grounding 0 V in the
device while grounding 0 V (PELV).
Fig. 10-3: Cabling

DANGER Danger of lethal injury due to hazardous electric


voltage
● Connect power supply units generating protective extra-low voltage (PELV)
(24 V) only to the supply voltages they are designed for. Note the overvoltage
categories, see fig. 10-2 "Power Routing 230 V" on page 19
● Do not apply supply voltage to the protective extra-low voltage.

20/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Mounting, Demounting and Electric Installation

10.5.2 Terminals and Wiring


Type Screw terminals
Solid wire 0.5-6 mm2
Stranded wires 0.5-4 mm2
American wire gauge 20-10 AWG
Cable markers Permitted, but not required
Insulation stripping length 7 mm / 6.985 mm
Screwdriver 3.5 mm slitted or pozidrive no. 2 (only for screw terminals)
Recommended tightening tor- 0.8 Nm, 7l b.in (only for screw terminals)
que

Tab. 10-1: Terminals and wiring


Installation notes:
● Use the suitable copper cable designed for an operating temperature of:
– 60°C for an ambient temperature of 45°C and
– 75°C for an ambient temperature of at least 60°C.
● Comply with the national installation codes and guidelines!
● Ensure that all stranded wires lead to the terminal connection!
● Depending on the conductor cross section, up to two wires with the same
maximum amperage are permitted in one connection (does not apply to pro-
tective earth conductors).
● Use this unit only with PE connection

10.5.3 Parallel Use to Increase Output Rate


To increase the output rate, another power supply unit may no be connected in
parallel.

10.5.4 External Input Protection


The unit was tested and admitted for branch circuits up to 20 A. An external
protection is only required if the supply branch provides an amperage higher
than 20 A. In some countries, regional regulations can apply. Check the regional
regulations and guidelines.
A minimum value is required to avoid unwanted fuse switch-off when using ex-
ternal fuses.
B-characteristic value C-characteristic value
(slow-blow) (fast-blow)
Amperage Max. 20 A 20 A
Min. 10 A 6A

Tab. 10-2: External input protection

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 21/35
Bosch Rexroth AG VAP 01.1
Mounting, Demounting and Electric Installation

10.5.5 Two-Phase Operation

1
L1 AC

240 V +10% max.


2
L
Sicherung
L3 N
3 PE

L2 DC

① Power supply unit ③ Fuse


② Internally protected
Fig. 10-4: Schematically for a two-phase operation
Note for a two-phase operation:
1. A two-phase connection can be used as long as the supply voltage does
not exceed 240 V+10%.
2. Protect the N-input with a fuse or a circuit breaker. The N-input is not pro-
tected internally and connected to a phase conductor in this case.
For the recommended fuses and circuit breakers, refer to chapter 10.5.4 "Exter-
nal Input Protection" on page 21.

10.6 Use in Tightly Sealed Housing


If the power supply unit VAP 01.1 is installed in a tightly sealed housing, the
temperature inside the housing is higher than outside the housing. The tempera-
ture inside the housing defines the ambient temperature of the power supply
unit.
Installation results:
The power supply unit is located in the center of the box. There is no other heat
source in the box.
Housing Rittal Type IP66 box PK 9519 100, plastics, 180 × 180 × 165 mm
Load 24 V, 8 A; (= 80 %) load is outside the box
Input 230 V AC
Temperature inside the box 48.9 °C (measured with a distance of 2 cm of the housing, in the cen-
ter of the power supply unit)
Temperature outside the box 23,3 ℃
Temperature rise 25.6 K

Tab. 10-3: Technical data when using a tightly sealed housing

10.7 Installation Orientations


For mounting positions deviating from the mounting positions of the primary
connections at the ground and at the output, the continuous output rate or the

22/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Mounting, Demounting and Electric Installation

maximum ambient temperature can be limited. The degree of reduction deter-


mines the service life of the power supply unit. Two different current carrying
capacity curves are available for the continuous operation:
Curve A1: Recommended output current
Curve A2: Maximum output current (service life is half the service life of A1).

1 4
12 A A1
9
2 6
3
0
3 10 20 30 40 50 60 °C 5

① Output ④ Output current


② Power supply unit ⑤ Ambient temperature
③ Input
Fig. 10-5: Mounting position A: Standard position

1 4
12 A
9 A2
2 6 A1

3
0
3 10 20 30 40 50 60 °C 5

① Input ④ Output current


② Power supply unit ⑤ Ambient temperature
③ Output
Fig. 10-6: Mounting position B (reverse)

1
12 A
9
A2
6
A1
3
0
10 20 30 40 50 60°C 2

① Output current
② Ambient temperature
Fig. 10-7: Mounting position C (table-top mounting)

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 23/35
Bosch Rexroth AG VAP 01.1
Commissioning

4
12 A
9 A2
1 2 3 6 A1

3
0
10 20 30 40 50 60°C 5

① Input ④ Output current


② Power supply unit ⑤ Ambient temperature
③ Output
Fig. 10-8: Mounting position D (clockwise horizontal)

4
12 A
9 A2
A1
1 2 3 6
3
0
10 20 30 40 50 60 °C 5

① Output ④ Output current


② Power supply unit ⑤ Ambient temperature
③ Input
Fig. 10-9: Mounting position E (anticlockwise horizontal)

11 Commissioning
The power supply unit VAP 01.1 can be used directly. No configuration is re-
quired.

24/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Error Causes and Troubleshooting

12 Device Description

3
4

5
7 6
① Mounting rail suspension ⑤ Connection terminal for input voltage
② Connection terminal for output voltage ⑥ Additional PE connection
③ Adjusting screw for output voltage ⑦ Releasing the mounting rail suspension
④ LED operating display
Fig. 12-1: Device view

13 Error Causes and Troubleshooting


Device states are indicated at the front panel via LED.
Error Troubleshooting
Power supply unit not stable on mount- ● Use only mounting rails made of steel acc. to EN 60715
ing rail
No output voltage, LED operating dis- ● Input voltage not connected or outside the specified val-
play off ues
● Output voltage short-circuited

Tab. 13-1: Error causes and troubleshooting

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 25/35
Bosch Rexroth AG VAP 01.1
Ordering Information

14 Maintenance
14.1 General Information

NOTICE Loss of IP degree of protection due to incorrect


maintenance.
Ensure the IP degree of protection during maintenance!

14.2 Regular Maintenance Tasks


● Check all plug and terminal connections of the components for proper tight-
ness and possible damage at least once a year
● Check that no cables are broken or pinched
● Replace damaged parts immediately

15 Ordering Information
15.1 Accessories and Spare Parts
For ordering information on accessories and spare parts, refer to chapter 5
"Spare Parts, Accessories and Wear Parts" on page 5.

15.2 Type Code


According to the type code, the power supply unit VAP 01.1 is available as the
following variant:

26/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Disposal

Abbrev. 1 2
Column 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5
Example: V A P 0 1 . 1 H - W 2 3 - 0 2 4 - 0 1 0 - N N

Product
VAP . . . . . . . .= VAP

Line
01 . . . . . . . . . . . . . . . .= 01

Design
1. . . . . . . . . . . . . . . . . . . . . .= 1

Type of construction
Top hat rail mounting. . . . . . .= H

Input voltage
100...120 V / 200...240 V, Autoselect = W23

Output voltage
DC 24 V. . . . . . . . . . . . . . . . . . . . . . . . . . . . .= 024

Output current
E.g., 10 A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .= 010

Other design
None. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .= NN
Fig. 15-1: Type code of the power supply unit VAP 01.1

16 Disposal
16.1 Return
For disposal, our products can be returned free of charge. However, the prod-
ucts must be free of remains like oil and grease or other impurities.
Furthermore, the products returned for disposal must not contain any undue
foreign substances or components.
Send the products free of charge to the following address:
Bosch Rexroth AG
Electric Drives and Controls
Bürgermeister-Dr.-Nebel-Straße 2
D-97816 Lohr am Main, Germany

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 27/35
Bosch Rexroth AG VAP 01.1
Service and Support

16.2 Batteries and Accumulators


Batteries and accumulators can be labeled with this symbol.

The symbol (crossed out wheel bin) indicates that batteries have to be
collected separately.
Within the EU, the end user is legally bound to return used batteries. Outside
the validity of the EU Directive 2006/66/EC, comply with the regulations.
Used batteries can contain hazardous substances, which can harm environment
and health when improperly stored or disposed.
After use, the batteries or accumulators in Rexroth products have to be dis-
posed according to the country-specific recycling system.

16.3 Packaging
The packaging material consists of cardboard, plastics, wood or styrofoam.
Packaging material can be recycled anywhere.
For ecological reasons, please do not return empty packages to Bosch Rexroth.

17 Service and Support


Our worldwide service network provides an optimized and efficient support.
Our experts offer you advice and assistance should you have any queries. You
can contact us 24/7.
Service Germany
Our technology-oriented Competence Center in Lohr, Germany, is responsible
for all your service-related queries for electric drive and controls.
Contact the Service Helpdesk & Hotline under:

Phone: +49 9352 40 5060


Fax: +49 9352 18 4941
E-mail: [email protected]
Internet: http://www.boschrexroth.com
Additional information on service, repair (e.g. delivery addresses) and training
can be found on our internet sites.
Service worldwide
Outside Germany, please contact your local service office first. For hotline num-
bers, refer to the sales office addresses on the internet.

28/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Service and Support

Preparing information
To be able to help you more quickly and efficiently, please have the following in-
formation ready:
● Detailed description of malfunction and circumstances resulting in the mal-
function
● Type plate name of the affected products, in particular type codes and serial
numbers
● Your contact data (phone and fax number as well as your email address)

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 29/35
Bosch Rexroth AG VAP 01.1

30/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG
Index

Index
A Intended use................................... 4
Accessories..................................... 5 Interfaces...................................... 16
Accessories and spare parts......... 26
Accumulators, charge................... 14 L
Ambient conditions......................... 5 Logic voltage................................. 19

B M
Buffer time...................................... 8 Maintenance................................. 26
Maintenance notes....................... 26
C Minimum distances....................... 17
CE marking................................... 14 Module voltage............................. 19
Commission.................................. 24 Mounting................................. 17, 18
Connection, electric..................... 19 Mounting positions....................... 22
Connector panel........................... 16 Mounting rail mounting................. 17

D O
Declaration of conformity............. 14 Ordering information.................... 26
Demounting............................ 17, 18 Output............................................ 9
Device description........................ 25 Overvoltage categories................. 19
Disposal........................................ 27
Documents, related........................ 2 P
Parallel use................................... 21
E Peak current capacity................... 10
Electric connection....................... 19 Peak current strength................... 13
Electric installation....................... 17 Power factor................................... 8
Electromotive force...................... 14 Power routing............................... 19
Error causes.................................. 25 Product identification..................... 2
External input protection.............. 21 Protective earth (PE) terminal...... 16
Protective properties.................... 11
F
Failure safety................................ 11 R
Feeding-back load......................... 14 Resistance.................................... 12

H S
Housing dimensions...................... 17 Safety............................................ 12
Safety alert symbol......................... 3
Safety instructions...................... 2, 3
I Scope.............................................. 1
Input protection............................ 21 Scope of delivery............................ 2
Input voltage range......................... 7 Signal words................................... 3
Installation.................................... 17 Spare parts..................................... 5
Installation notes.......................... 17 Standards..................................... 14
Installation orientations................ 22 Support
Installation, electric...................... 19 See service hotline.................. 28
Insulation resistance..................... 12 Switch-off response........................ 9

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 31/35
Bosch Rexroth AG VAP 01.1
Index

Switch-on response........................ 8
Symbols.......................................... 4

T
Target groups................................. 1
Technical data................................ 6
Input.......................................... 6
Output....................................... 9
Terminals...................................... 21
Two-phase operation.................... 22
Type code..................................... 26
Type plate....................................... 2

U
UL/CSA certification..................... 15
Use, intended................................. 4

V
Voltage supply.............................. 19
Voltage, input.................................. 7

W
Wear parts...................................... 5
Wiring........................................... 21

32/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P 33/35
Bosch Rexroth AG VAP 01.1

34/35 DOK-SUPPL*-VAP*01.1H**-IT01-EN-P
VAP 01.1 Bosch Rexroth AG

Notes
Bosch Rexroth AG
Electric Drives and Controls
P.O. Box 13 57
97803 Lohr, Germany
Bgm.-Dr.-Nebel-Str. 2
97816 Lohr, Germany
Tel. +49 9352 18 0
Fax +49 9352 18 8400
www.boschrexroth.com/electrics

DOK-SUPPL*-VAP*01.1H**-IT01-EN-P