GX 7, GX 11: Instruction Book
GX 7, GX 11: Instruction Book
GX 7, GX 11: Instruction Book
Instruction book
GX 7, GX 11
Instruction book
Copyright Notice
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and drawings.
This instruction book meets the requirements for instructions specified by the machinery
directive 98/37/EC and is valid for CE as well as non-CE labelled machines.
2007 - 11
No. 2920 7054 00
www.atlascopco.com
Table of contents
1 Safety precautions..........................................................................................................5
2 General description......................................................................................................10
2.1 INTRODUCTION.................................................................................................................................10
3 Installation.....................................................................................................................23
3.6 PICTOGRAPHS.................................................................................................................................40
4 Operating instructions.................................................................................................41
4.2 STARTING.......................................................................................................................................43
4.3 STOPPING.......................................................................................................................................46
2 2920 7054 00
5 Maintenance..................................................................................................................50
6.2 COOLERS.......................................................................................................................................56
7 Problem solving............................................................................................................61
8 Technical data...............................................................................................................64
10 PED................................................................................................................................71
2920 7054 00 3
4 2920 7054 00
1 Safety precautions
Explanation
Warning
Important note
All responsibility for any damage or injury resulting from neglecting these
precautions, or non-observance of the normal caution and care required for
installation, operation, maintenance and repair, even if not expressly stated, will
be disclaimed by the manufacturer.
General precautions
1. The operator must employ safe working practices and observe all related local work safety requirements
and regulations.
2. If any of the following statements does not comply with local legislation, the stricter of the two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorised, trained,
specialised personnel.
4. The compressor is not considered capable of producing air of breathing quality. For air of breathing quality,
the compressed air must be adequately purified according to local legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the compressor,
press the emergency stop button, switch off the voltage and depressurise the compressor. In addition, the
power isolating switch must be opened and locked.
6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never
use the air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme
caution and wear eye protection.
2920 7054 00 5
4. Air hoses must be of correct size and suitable for the working pressure. Never use frayed, damaged or
worn hoses. Distribution pipes and connections must be of the correct size and suitable for the working
pressure.
5. The aspirated air must be free of flammable fumes, vapours and particles, e.g. paint solvents, that can lead
to internal fire or explosion.
6. Arrange the air intake so that loose clothing worn by people cannot be sucked in.
7. Ensure that the discharge pipe from the compressor to the aftercooler or air net is free to expand under
heat and that it is not in contact with or close to flammable materials.
8. No external force may be exerted on the air outlet valve; the connected pipe must be free of strain.
9. If remote control is installed, the machine must bear a clear sign stating: DANGER: This machine is
remotely controlled and may start without warning.
The operator has to make sure that the machine is stopped and that the isolating switch is open and locked
before any maintenance or repair. As a further safeguard, persons switching on remotely controlled
machines shall take adequate precautions to ensure that there is no one checking or working on the
machine. To this end, a suitable notice shall be affixed to the start equipment.
10. Air-cooled machines must be installed in such a way that an adequate flow of cooling air is available and
that the exhausted air does not recirculate to the compressor air inlet or cooling air inlet.
11. The electrical connections must correspond to the local codes. The machines must be earthed and protected
against short circuits by fuses in all phases. A lockable power isolating switch must be installed near the
compressor.
12. On machines with automatic start-stop system or if the automatic restart function after voltage failure is
activated, a sign stating "This machine may start without warning" must be affixed near the instrument
panel.
13. In multiple compressor systems, manual valves must be installed to isolate each compressor. Non-return
valves (check valves) must not be relied upon for isolating pressure systems.
14. Never remove or tamper with the safety devices, guards or insulation fitted on the machine. Every pressure
vessel or auxiliary installed outside the machine to contain air above atmospheric pressure must be
protected by a pressure-relieving device or devices as required.
15. Pipework or other parts with a temperature in excess of 80˚C (176˚F) and which may be accidentally
touched by personnel in normal operation must be guarded or insulated. Other high-temperature pipework
must be clearly marked.
16. For water-cooled machines, the cooling water system installed outside the machine has to be protected by
a safety device with set pressure according to the maximum cooling water inlet pressure.
17. If the ground is not level or can be subject to variable inclination, consult the manufacturer.
Also consult following safety precautions: Safety precautions during operation and Safety
precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas. Processing
of any other gas requires additional safety precautions typical to the application which are not
included herein.
Some precautions are general and cover several machine types and equipment; hence some
statements may not apply to your machine.
All responsibility for any damage or injury resulting from neglecting these
precautions, or non-observance of the normal caution and care required for
installation, operation, maintenance and repair, even if not expressly stated, will
be disclaimed by the manufacturer.
6 2920 7054 00
General precautions
1. The operator must employ safe working practices and observe all related local work safety requirements
and regulations.
2. If any of the following statements does not comply with local legislation, the stricter of the two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorised, trained,
specialised personnel.
4. The compressor is not considered capable of producing air of breathing quality. For air of breathing quality,
the compressed air must be adequately purified according to local legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the compressor,
press the emergency stop button, switch off the voltage and depressurise the compressor. In addition, the
power isolating switch must be opened and locked.
6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never
use the air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme
caution and wear eye protection.
2920 7054 00 7
Also consult following safety precautions: Safety precautions during installation and Safety
precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas. Processing
of any other gas requires additional safety precautions typical to the application which are not
included herein.
Some precautions are general and cover several machine types and equipment; hence some
statements may not apply to your machine.
All responsibility for any damage or injury resulting from neglecting these
precautions, or non-observance of the normal caution and care required for
installation, operation, maintenance and repair, even if not expressly stated, will
be disclaimed by the manufacturer.
General precautions
1. The operator must employ safe working practices and observe all related local work safety requirements
and regulations.
2. If any of the following statements does not comply with local legislation, the stricter of the two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorised, trained,
specialised personnel.
4. The compressor is not considered capable of producing air of breathing quality. For air of breathing quality,
the compressed air must be adequately purified according to local legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the compressor,
press the emergency stop button, switch off the voltage and depressurise the compressor. In addition, the
power isolating switch must be opened and locked.
6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never
use the air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme
caution and wear eye protection.
8 2920 7054 00
11. Never weld or perform any operation involving heat near the oil system. Oil tanks must be completely
purged, e.g. by steam-cleaning, before carrying out such operations. Never weld on, or in any way modify,
pressure vessels.
12. Whenever there is an indication or any suspicion that an internal part of a machine is overheated, the
machine shall be stopped but no inspection covers shall be opened before sufficient cooling time has
elapsed; this to avoid the risk of spontaneous ignition of the oil vapour when air is admitted.
13. Never use a light source with open flame for inspecting the interior of a machine, pressure vessel, etc.
14. Make sure that no tools, loose parts or rags are left in or on the machine.
15. All regulating and safety devices shall be maintained with due care to ensure that they function properly.
They may not be put out of action.
16. Before clearing the machine for use after maintenance or overhaul, check that operating pressures,
temperatures and time settings are correct. Check that all control and shut-down devices are fitted and that
they function correctly. If removed, check that the coupling guard of the compressor drive shaft has been
reinstalled.
17. Every time the separator element is renewed, examine the discharge pipe and the inside of the oil separator
vessel for carbon deposits; if excessive, the deposits should be removed.
18. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture from entering
them, e.g. when steam-cleaning.
19. Make sure that all sound-damping material, e.g. on the bodywork and in the air inlet and outlet systems
of the compressor, is in good condition. If damaged, replace it by genuine material from the manufacturer
to prevent the sound pressure level from increasing.
20. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate bowls.
21. The following safety precautions are stressed when handling refrigerant:
• Never inhale refrigerant vapours. Check that the working area is adequately ventilated; if required, use
breathing protection.
• Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin with water. If
liquid refrigerant contacts the skin through clothing, never tear off or remove the latter; flush
abundantly with fresh water over the clothing until all refrigerant is flushed away; then seek medical
first aid.
22. Protect hands to avoid injury from hot machine parts, e.g. during draining of oil.
Also consult following safety precautions: Safety precautions during installation and Safety
precautions during operation.
These precautions apply to machinery processing or consuming air or inert gas. Processing
of any other gas requires additional safety precautions typical to the application which are not
included herein.
Some precautions are general and cover several machine types and equipment; hence some
statements may not apply to your machine.
2920 7054 00 9
2 General description
2.1 Introduction
Introduction
GX 7 and GX 11 are single-stage, oil-injected screw compressors.
The compressor is air-cooled and belt-driven by an electric motor. The compressor is enclosed in sound-
insulated bodywork. An easy-to-operate control panel (1) is provided, including the start/stop switch and the
emergency stop button. A cabinet housing the regulator, pressure switch and motor starter is integrated into
the bodywork.
Floor-mounted model
The compressor is installed directly on the floor.
Tank-mounted model
GX 7 and GX 11 are mounted on a large air receiver (AR) of 270 l (71.28 US gal / 59.40 Imp gal / 9.45 cu.ft)
or an optional air receiver of 500 l (132 US gal / 110 Imp gal / 17.50 cu.ft).
10 2920 7054 00
Ref. Name
1 Control panel
AF Air filter
AO Air outlet
AR Air receiver
Ca Air cooler
Co Oil cooler
Da Automatic drain
Dm1 Manual condensate drain
DR Dryer
E Compressor element
OF Oil filter
OS Oil separator
OT Oil separator tank
GX Full-feature
An air cooler (Ca) and an air dryer (DR) are integrated into the bodywork. A condensate drain system is
provided including a valve for automatic draining during operation (Da) and a manual drain valve (Dm1).
GX Pack
The compressor is not fitted with an air cooler, air dryer and condensate drain system as standard.
2920 7054 00 11
Flow diagram
12 2920 7054 00
Air drawn through filter (AF) and open inlet valve (IV) into compressor element (E) is compressed.
Compressed air and oil flow into oil separator/tank (OT). The air is discharged via minimum pressure valve
(Vp), air cooler (Ca) and air dryer (DR) towards the air outlet (AO).
2920 7054 00 13
GX 7 and GX 11 Pack
GX 7 and GX 11 Full-Feature
Air pressure forces the oil from oil separator/tank (OT) through oil cooler (Co) and filter (OF) to compressor
element (E) and the lubrication points. In oil separator/tank (OT), most of the oil is removed centrifugally;
the rest is removed by separator (OS).
14 2920 7054 00
The oil system is fitted with a by-pass valve (BV). When the oil temperature is below the set-point of the
valve, the by-pass valve shuts off the oil supply from oil cooler. The by-pass valve starts opening the supply
from cooler (Co) when the oil temperature exceeds the setting of the valve. The setting of the by-pass valve
depends on the model. See the section Compressor data.
Cooling system
GX 7 and GX 11 Pack
The cooling system of the Pack version comprises oil cooler (Co). A fan (FN), mounted directly onto the
motor shaft, generates the cooling air in order to cool the oil.
An air cooler (Ca) is available as option.
2920 7054 00 15
GX 7 and GX 11 Full-Feature
The cooling system of the Full Feature version comprises oil cooler (Co) and air cooler (Ca). A fan (FN),
mounted directly onto the motor shaft, generates the cooling air in order to cool the oil and the compressed
air.
Main components
16 2920 7054 00
Loading
As long as the working pressure is below the maximum limit, the solenoid valve is energised allowing control
air to flow to the unloader: the inlet valve opens completely and the unloading valve closes completely. The
compressor will run fully loaded (100% output).
Unloading
If the working pressure reaches the maximum limit, the solenoid valve is de-energised venting the control air:
the inlet valve closes completely and the unloading valve opens completely. The compressor will run fully
unloaded (0% output).
The GX 7 and GX 11 is equipped with the Elektronikon 001, an intelligent controller that will stop the
compressor after a variable period of unloaded operation:
• When the unloading pressure is reached after the first start and if there is no air consumption, the
compressor will run unloaded during 2 minutes and than stop.
• If there is a pressure request within the first 2 minutes after being stopped, the controller is expecting a
higher air consumption: the next time the unit will stop after 5 minutes of unloaded operation.
• If there is no pressure request earlier than 2 minutes after being stopped, the controller is expecting a lower
air consumption: the next time again it stops after 2 minutes of unloaded operation.
• If the compressor is stopped manually, it stops after 2 minutes unloaded operation.
The compressor will automatically restart when the net pressure drops to the minimum limit.
2920 7054 00 17
Symbol Description
RESET button.
Pressing the button cancels the stored alarm indication.
When pressing the button during more than 3 seconds, the central control unit is tested:
all the LEDs must be on.
START button.
Pressing the button switches on the compressor. The motor starts 25 seconds after the
button is pushed.
STOP button.
Pressing the button starts the compressor switch-off phase: the compressor runs idle
during 120 seconds (2 minutes) before stopping.
18 2920 7054 00
General alarm -
- Main power on
To start up again after a protection has been triggered (alarm): press the RESET button,
followed by the START button (1).
The motor will start after a delay of 25 seconds.
2920 7054 00 19
Electric cubicle
Legend
Ref. Designation
(1) only on Full Feature versions
(2) only on multi-voltage versions
Ref. Designation
F1-2-3-4-10 Fuses (F10 only on Full Feature units - see (1) on figure)
FM1 Motor overload relay
KL Line contactor
20 2920 7054 00
Ref. Designation
KY Star contactor
KD Delta contactor
T1 Transformer
KMD Dryer relay (only on FF versions - see (1) on figure)
XM1 Connection terminals (only available on multi-voltage versions - see (2) on figure)
2920 7054 00 21
Air Dryer
Wet compressed air enters the dryer and is further cooled by the outgoing, dried air (2). Moisture in the
incoming air condenses. The air then flows through heat exchanger (1) where refrigerant evaporates,
withdrawing heat from the air. The cold air then flows through condensate trap (4) which separates condensate
from the air. The condensate is automatically drained. The cold, dried air then flows through heat exchanger
(3), where it is warmed up by the incoming air.
22 2920 7054 00
3 Installation
Important
For transport with a fork truck, use the openings in the frame.
Move the compressor gently.
2920 7054 00 23
Proposal
Action
1 Install the rubber pads (delivered loose with the compressor) to the compressor supports.
Install the compressor on a solid, level floor suitable for taking its weight.
The recommended minimum distance between the top of the unit and the ceiling is 900 mm (35.1
in).
The air receiver must not be bolted to the floor.
For tank-mounted units, the minimum distance between the wall and the back of the compressor
is 500 mm (19.5 in).
2 Position of the compressed air outlet valve.
Close the valve.
Connect the air net to the valve.
3 The pressure drop over the delivery pipe can be calculated from the following formula:
dp=(L x 450 x Qc1.85) / (d5 x P)
• dp=pressure drop (recommended maximum = 0.1 bar / 1.5 psi)
• L=length of delivery pipe in m
• d=inner diameter of the delivery pipe in mm
• P=absolute pressure at the compressor outlet in bar(a)
• Qc=free air delivery of the compressor in l/s
24 2920 7054 00
Action
4 Ventilation: the inlet grids and ventilation fan should be installed in such a way that any recirculation
of cooling air to the compressor or dryer is avoided.
The air velocity to the grids must be limited to 5 m/s (200 in/s).
The required ventilation capacity to limit the temperature of the compressor room can be calculated
from the following formula:
Qv = 0.92 N / dT
• Qv=required ventilation capacity in m3/s
• N=nominal motor power of compressor in kW
• dT=temperature increase in compressor room
5 Position of the mains cable entry.
6 The drain pipes to the drain collector must not dip into the water of the drain collector.
2920 7054 00 25
26 2920 7054 00
2920 7054 00 27
28 2920 7054 00
2920 7054 00 29
30 2920 7054 00
Ref. Name
1 Cooling air outlet
2 Cooling air inlet
3 Location of supply cable entry
4 Manual drain (G 3/8 female)
5 Compressed air outlet (G 1/2 female)
6 Dryer air outlet
7 Dryer air inlet
8 Motor cooling air inlet
9 Outlet valve (delivered loose)
2920 7054 00 31
Attention
Local regulations remain applicable if they are stricter than the values proposed below.
The voltage drop must not exceed 5% of the nominal voltage. It may be necessary to use
cables of a larger size than those stated to comply with this requirement.
GX 7 GX 11
Frequency Voltage Cable size Cable size
(Hz) (V)
IEC (mm2) (mm2)
50 200 16 (6 XLPE or EPR) 25 (16 XLPE or EPR)
50 230 10 16 (10 XLPE or EPR)
50 400 4 6
50 500 4 6
60 440/460 4 6
60 380 4 6
CSA/UL AWG AWG
60 200 6 6
60 208-230 / 460 8-8 / 10 6-6 / 8
60 575 12 10
Always disconnect the power supply before working on the electrical circuit!
32 2920 7054 00
General instructions
Step Action
1 Install an isolating switch near the compressor.
2 Check the fuses and the setting of overload relay. See Settings for overload relay and
fuses.
3 If fitted, check transformers for correct connection.
4 Connect the power supply cables to terminals L1, L2 and L3 (1X0) and the neutral
conductor (if applicable) to terminal (N). Connect the earth conductor.
2920 7054 00 33
To modify the wiring for an operating voltage of 208 V or 460 V , both compressor main cubicle and
transformer dryer cubicle should be rewired as described below:
Step Action
1 Adjust the motor overload (FM1) setting.
2 Rewire the control transformer (T1)
3 Replace the control fuses (F1) with the 10,3 x 38mm 1 A or 2 A fuses provided (see further).
4 Modify the motor terminal bridge configuration in the main cubicle for the desired voltage.
5 Replace the voltage sticker by the appropriate voltage sticker provided.
6 On FF units, replace the power fuses (F10 in the main cubicle, F11 in the power
transformer cubicle) with the CC type 5 A, respectively 7,5 A fuses provided.
7 Modify the power transformer terminal bridge configuration in the transformer cubicle for
the desired voltage.
To adjust the motor overload (FM1) setting, simply rotate the adjustment screw (1) on the front of the overload
relay to the required setting (see table below).
34 2920 7054 00
To rewire the control transformer (T1), move the wire of the transformer to the terminal marked with the
desired voltage (208 V, 230 V or 460 V).
Replace the two fuses marked F1 by opening the fuse-holder an. Use the 2 A fuses for 208-230 V and the 1
A fuses for 460 V, supplied with the compressor.
Note: fuses F10 are only applicable to FF units. See also Electric diagrams.
2920 7054 00 35
To modify the terminal bridge configuration to the motor, configure the terminal bridges for the desired voltage
(208 V, 230 V or 460V) according to the diagram below. The terminal bridges (1) can be easily removed
using a pair of pliers. Additional terminal bridges are provided with the compressor. The connections for 230
V are the factory standard.
Locate the yellow voltage labels provided with the compressor. Replace the existing label with the appropriate
voltage label (200-208 V, 230V or 460V).
36 2920 7054 00
2920 7054 00 37
38 2920 7054 00
2920 7054 00 39
3.6 Pictographs
Pictographs
Ref. Description
1 Working pressure
2 Hour meter
3 Dew-point temperature
4 Start
5 Stop
6 Warning: voltage
7 Lightly oil gasket of oil filter, screw filter on and tighten by hand
9 Warning: switch off voltage and depressurise compressor before carrying out maintenance
work
10 Warning: hot parts
11 Lock all doors of the bodywork and push the start button.
• If the sheet is pulled downwards: Stop the compressor immediately and switch
off the voltage.
• Reverse two incoming electric lines. Repeat the previous step.
• If the sheet is blown away the motor rotation direction is correct.
12 Manual condensate drain
13 Automatic condensate drain
40 2920 7054 00
4 Operating instructions
Safety
Moving
To safely move a Tank-mounted model, see Installation.
General preparation
Condensate drain, GX 7 up to GX 11
2920 7054 00 41
Step Action
1 Consult the installation instructions (see Installation).
2 Check that the electrical connections correspond to the local codes. The installation must
be earthed and protected against short circuits by fuses in all phases. An isolating switch
must be installed near the compressor.
3 Fit outlet valve (2), close it and connect the air net to the valve.
Connect condensate drain valve (Dm) and automatic drain outlet (Da) to a drain collector.
Close the valve.
Connect condensate drain valve (4) of the air receiver to a drain collector. Close the valve.
Oil system
Step Action
Check the oil level.
The oil level sight-glass (SG) should be between 1/4 and 3/4 full.
42 2920 7054 00
Start-up
Step Action
1 Affix sheet (5) explaining the procedure for checking the motor rotation direction to the
cooling air outlet of the compressor (consult Dimension drawings).
Switch on the voltage. Start the compressor and stop it immediately.
Check the rotation direction of the motor using sheet (5). If the motor rotation direction is
correct, the label on the top grating will be blown upwards. If the sheet remains in place,
the rotation direction is incorrect (see the pictographs on the label).
If the rotation direction is incorrect, switch off the voltage, open the isolating switch and
reverse two incoming electric lines.
2 Start and run the compressor for a few minutes. Check that the compressor operates
normally.
4.2 Starting
2920 7054 00 43
Pressure gauge
Control panel GX 7 up to GX 11
44 2920 7054 00
Step Action
1 Before starting, the oil level sight-glass (SG) should be between 1/4 and 3/4 full.
2 Switch on the voltage.
3 Open air outlet valve (2).
4 Push the start button (1). The motor starts running after 25 seconds and automatic
operation led (3) alights.
On compressors with a star-delta starter, the drive motor switches over from star to delta
10 seconds after starting.
The maximum number of motor starts must be limited to 20 per hour.
It is strongly recommended to operate the compressor with a load factor of more than 10%
to avoid condensate in the oil.
5 Regularly check the oil level. 10 to 15 minutes after stopping, the sight-glass (SG) should
be between 1/4 and 3/4 full.
If the oil level is too low, stop the compressor, depressurise the oil system by unscrewing
oil filler plug (FC) one turn and wait a few minutes. Remove the plug and top up the oil,
until the sight-glass is 3/4 full. Do not overfill. Fit and tighten plug (FC).
6 When automatic operation LED (3) is lit, the regulator is automatically controlling the
compressor, i.e. loading, unloading, stopping of the motors and restarting.
7 Regularly check the working pressure (Gpa) and the dew-point gauge (Gdp) (FF units).
8 Regularly check that condensate is drained (Da) during running.
During normal operation, the oil level should be at approximately half of the sightglass. Under
certain conditions it is possible that only foam is visible. In that case, the oil level can only be
checked after stopping, following the described procedure.
Always stop the compressor as explained in Stopping. Never use the emergency stop button
for normal stopping.
2920 7054 00 45
4.3 Stopping
46 2920 7054 00
Control panel GX 7 up to GX 11
Step Action
1 Push the stop button (2) on the control panel. The compressor will switch to unloaded
operation and stops after 120 seconds. The automatic operaion LED goes out.
To stop the compressor immediately in the event of an emergency, press button (S3). See
the Control panel section. After remedying the fault, unlock the button by pulling it out.
Only use emergency stop button in the event of an emergency. Avoid using the button for
normal stopping of the compressor.
2 Close air outlet valve (2) and switch off the voltage to the compressor.
3 Open condensate drain valve (Dm) for a few seconds to drain any condensate and then
close the valve.
Open condensate drain valve (4) of the air receiver for a few seconds to drain any
condensate and then close the valve.
The air dryer and the air receiver remain under pressure.
The PDX filter (if installed) remains under pressure.
If maintenance or repair work is necessary, consult the Problem solving section for all
relevant safety precautions.
2920 7054 00 47
This procedure should be carried out at the end of the compressor’s service life.
Step Action
1 Stop the compressor and close the air outlet valve (2).
48 2920 7054 00
Step Action
2 Switch off the voltage and disconnect the compressor from the mains.
3 Depressurise the compressor by opening plug (3) one turn.
Open condensate drain valve (Dm).
Open condensate drain valve (4) of the air reciever.
4 Shut off and depressurise the part of the air net which is connected to the outlet valve.
Disconnect the compressor air outlet valve from the air net.
5 Drain the oil and condensate circuits.
6 Disconnect the compressor condensate outlet and valve from the condensate net.
2920 7054 00 49
5 Maintenance
Warning
Warranty-Product Liability
Use only authorised parts. Any damage or malfunction caused by the use of unauthorised parts is not covered
by Warranty or Product Liability.
General
When servicing, replace all removed gaskets, O-rings and washers.
Intervals
Carry out maintenance at the interval which comes first. The local Atlas Copco Customer Centre may overrule
the maintenance schedule, especially the service intervals, depending on the environmental and working
conditions of the compressor.
The "longer interval" checks must also include the "shorter interval" checks.
50 2920 7054 00
Description
The motor bearings are greased for life.
It is strongly recommended to use Atlas Copco lubricants. See Preventive maintenance schedule for
recommended oil change intervals.
For part numbers, consult the Spare Parts List.
2920 7054 00 51
Important
Step Action
1 Run the compressor until warm. Stop the compressor, close the air outlet valve and switch
off the voltage. See Stopping.
2 Depressurise the compressor by unscrewing filler plug (2) one turn to permit any pressure
in the system to escape. Remove the plug after the system is depressurised.
3 Depressurise the air receiver by opening drain valve (8).
4 Remove plug (5), drain the oil by opening drain valve (6). Close the valve and refit the plug
after draining. Deliver the drained oil to the local oil collection service.
5 Remove oil filter (7) and separator (1). Clean the seats on the manifold.
6 Oil the gaskets of the new filter and separator and screw them into place. Tighten firmly
by hand.
7 Fill oil separator/tank (3) with oil until the level reaches the middle of sight-glass (4). Ensure
no dirt gets into the system.
8 Refit and tighten filler plug (2).
9 Close drain valve (8) of the air receiver.
10 Run the compressor for a few minutes.
11 Stop the compressor and wait a few minutes to allow the oil to settle.
12 Check the oil level. Add oil if necessary.
If the oil level is too low, depressurise the system by unscrewing filler plug (2) one turn to
permit any pressure in the system to escape. Depressurise the air receiver by opening
drain valve (8).
52 2920 7054 00
Step Action
13 Add oil as necessary. The sight-glass should be 3/4 full. Retighten plug (2) and close drain
valve (8) of the air receiver.
GX 7 and GX 11
GX 7 and GX 11
Step Action
1 Stop the compressor, close the air outlet valve, switch off the voltage and depressurise by
unscrewing oil filler plug (3) one turn to permit any pressure in the system to escape. See
Stopping.
If the compressor is fitted onto an air receiver, depressurise the air receiver by opening
condensate drain valve (4).
On floor-mouned units, depressurise the filter by loosing its drain valve.
2920 7054 00 53
Step Action
2 Unscrew the filter bowl. A whistling noise will warn you if the bowl is not fully depressurised.
If this occurs, the bowl should be screwed back and the venting should be repeated.
3 Remove and discard the filter element.
4 Clean the bowl and replace its O-ring.
5 Fit the new filter element.
6 Refit the bowl.
7 Tighten oil filler plug (3).
8 Close condensate drain valve (4).
If the compressor is stored without running from time to time, consult Atlas Copco as protective measures
may be necessary.
For overhauling and for preventive maintenance, a wide range of service kits is available. Service kits comprise
all parts required for servicing the component and offer the benefits of genuine Atlas Copco parts while
keeping the maintenance budget low.
Also a full range of extensively tested lubricants, suitable for your specific needs is available to keep the
compressor in excellent condition.
Consult the Spare Parts List for part numbers.
54 2920 7054 00
Step Action
1 Stop the compressor, close the air outlet valve and switch off the voltage.
2 Remove the front panel and the top panel of the compressor housing.
3 Unscrew the filter cover (1) and remove the filter element. Discard the air filter element.
4 Fit the new element and screw on the filter cover.
5 Refit the top and front panels.
2920 7054 00 55
6.2 Coolers
GX 7 and GX 11
Step Action
1 Keep oil cooler (Co) clean to maintain the cooling efficiency.
For versions with air cooler: also keep cooler (Ca) clean to maintain the cooling efficiency.
2 Stop the compressor, close the air outlet valve and switch off the voltage. Remove any dirt
from the oil cooler (Co) with a fibre brush. For versions with air cooler: also remove any
dirt from the air cooler (Ca). Never use a wire brush or metal objects. Then clean using an
air jet.
56 2920 7054 00
Testing
The valve can be tested on a separate compressed air line.
Before removing the safety valve, stop the compressor (see Stopping), close the air outlet valve, switch off
the voltage, open drain valves (4) (tank-mounted units) and the manual drain valve (5) (if fitted - on floor-
mounted units) and unscrew filler plug (3) one turn to permit any pressure in the system to escape.
If the valve does not open at the set pressure stamped on the valve, replace the valve.
No adjustments are allowed. Never run the compressor without a safety valve.
Pressure switch, GX 7 up to GX 11
2920 7054 00 57
The switch allows the operator to select the unloading/stopping pressure (see Regulating system).
Adjustment can only be carried out when the pressure switch is pressurised.
The loading/starting pressure is controlled by adjusting knob (2). Remove blocking device (3) and turn the
knob clockwise to raise the pressure, anti-clockwise to lower it. See also below drawing.
The pressure difference between unloading and loading is adjusted by means of the same knob. Push down
the knob and turn it clockwise to reduce the pressure difference, counter-clockwise to increase it.
58 2920 7054 00
GX 7 and GX 11
Step Action
1 Stop the compressor, close the air outlet valve and switch off the voltage
2 Remove the front door and the internal panel.
3 The tension is correct when a force of between 20 N (4.5 Ibf) and 25 N (5.63 Ibf) applied
at the midpoint of the belts causes a deflection of 5 mm (0.2 in).
4 Refit the bodywork panels.
Step Action
1 Stop the compressor, close the air outlet valve and switch off the voltage.
2 Remove the front door, the internal panel, the top cover and the pulley protection.
3 Loosen the 4 bolts (2) by one turn.
4 Adjust the belt tension by turning tensioning nut (1).
5 The tension is correct when a force of between 20 N (4.5 lbf) and 25 N (5.63 lbf) applied
at the midpoint of the belts causes a deflection of 5 mm (0.2 in).
6 Retighten bolts (2).
7 Refit the bodywork panels.
2920 7054 00 59
Step Action
The belts (3) must be replaced as a set, even if only one of the belts is worn. Only use
genuine Atlas Copco belts.
1 Stop the compressor, close the air outlet valve and switch off the voltage.
2 Remove the front door, the internal panel, the top cover, the pulley protection and the left
side panel.
3 Loosen the 4 bolts (2) by one turn.
4 Release the belt tension by loosening tensioning nut (1).
5 Remove the fan duct (4).
Remove the belts.
6 Install the new belts.
7 Tension belts (3) as described above.
8 Re-assemble the fan duct (4), the pulley protection and the internal protection panel.
9 Re-assemble left side and top panel cover.
10 Check the belt tension after 50 running hours.
60 2920 7054 00
7 Problem solving
Start/stop switch
GX 7 and GX 11
GX 7 and GX 11
2920 7054 00 61
GX 7 and GX 11
GX 7 and GX 11
Attention
Use only authorised parts. Any damage or malfunction caused by the use of unauthorised
parts is not covered by Warranty or Product Liability.
Apply all relevant Safety precautions.
Before carrying out any maintenance or repair work on the compressor: push the stop
button (2).
Wait until the compressor has stopped and switch off the voltage. See the Stopping
section.
Open the isolating switch to prevent an accidental start.
Close air outlet valve (2) and depressurise the compressor by opening the oil filler plug (3)
one turn.
Open manual condensate drain valves (4 and/or 5).
The air outlet valve (2) can be locked during maintenance or repair as follows:
• Close the valve.
• Remove the screw fixing the handle
• Remove the handle.
• Fit the screw.
62 2920 7054 00
2920 7054 00 63
8 Technical data
Pressure gauge GX 7 up to GX 11
Hourmeter
Dewpoint indicator
The readings mentioned below are valid under the reference conditions (see Reference
conditions and limitations).
Ref. Name
Gpa Air outlet pressure
Reading: Modulates between preset unloading/stopping pressure and loading pressure
Gdp Dew-point temperature
Reading: approx. 5˚C (41˚F) at 20˚C (68˚F) ambient temperature
Hm Hour meter
Reading: Total running time
64 2920 7054 00
GX 7 and GX 11
Reference conditions
Limitations
2920 7054 00 65
66 2920 7054 00
2920 7054 00 67
68 2920 7054 00
2920 7054 00 69
1 This vessel can contain pressurised air; this can be potentially dangerous if the equipment is
misused.
2 This vessel must only be used as compressed air/oil separator and must be operated within
the limits specified on the data plate.
3 No alterations must be made to this vessel by welding, drilling or other mechanical methods
without the written permission of the manufacturer.
4 The pressure and temperature of this vessel must be clearly indicated.
5 There is no intrinsic need for service inspection of the vessel when used within the design
limits for its intended application.
6 Corrosion must be prevented under the conditions of use. Condensation may accumulate
inside the tank and this must be drained every day. This may be done manually, by opening
the drain valve, or by means of the automatic drain, if fitted to the tank.
Nevertheless, a weekly check by opening of the manual drain valve is necessary.
70 2920 7054 00
10 PED
Overall rating
The compressors conform to PED smaller than category II.
2920 7054 00 71