GX 7, GX 11: Instruction Book

Download as pdf or txt
Download as pdf or txt
You are on page 1of 76

GX 7, GX 11

Instruction book

Downloaded from www.Manualslib.com manuals search engine


Downloaded from www.Manualslib.com manuals search engine
Atlas Copco

GX 7, GX 11

Instruction book

Copyright Notice
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and drawings.

This instruction book meets the requirements for instructions specified by the machinery
directive 98/37/EC and is valid for CE as well as non-CE labelled machines.

2007 - 11
No. 2920 7054 00

www.atlascopco.com

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Table of contents

1 Safety precautions..........................................................................................................5

1.1 SAFETY ICONS...................................................................................................................................5

1.2 SAFETY PRECAUTIONS DURING INSTALLATION...........................................................................................5

1.3 SAFETY PRECAUTIONS DURING OPERATION..............................................................................................6

1.4 SAFETY PRECAUTIONS DURING MAINTENANCE OR REPAIR...........................................................................8

2 General description......................................................................................................10

2.1 INTRODUCTION.................................................................................................................................10

2.2 AIR FLOW.......................................................................................................................................12

2.3 OIL SYSTEM....................................................................................................................................14

2.4 COOLING SYSTEM.............................................................................................................................15

2.5 REGULATING SYSTEM........................................................................................................................16

2.6 CONTROL PANEL .............................................................................................................................18

2.7 PROTECTION OF COMPRESSOR............................................................................................................20

2.8 AIR DRYER......................................................................................................................................22

3 Installation.....................................................................................................................23

3.1 INSTALLATION PROPOSAL...................................................................................................................23

3.2 DIMENSION DRAWINGS.......................................................................................................................26

3.3 ELECTRIC CABLE SIZE.......................................................................................................................32

3.4 ELECTRICAL CONNECTIONS ................................................................................................................32

3.5 ELECTRICAL DIAGRAMS......................................................................................................................38

3.6 PICTOGRAPHS.................................................................................................................................40

4 Operating instructions.................................................................................................41

4.1 INITIAL START-UP..............................................................................................................................41

4.2 STARTING.......................................................................................................................................43

4.3 STOPPING.......................................................................................................................................46

2 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

4.4 TAKING OUT OF OPERATION................................................................................................................48

5 Maintenance..................................................................................................................50

5.1 PREVENTIVE MAINTENANCE SCHEDULE..................................................................................................50

5.2 DRIVE MOTOR .................................................................................................................................51

5.3 OIL SPECIFICATIONS..........................................................................................................................51

5.4 OIL, FILTER AND SEPARATOR CHANGE .................................................................................................52

5.5 PDX/DDX FILTER CHANGE...............................................................................................................53

5.6 STORAGE AFTER INSTALLATION...........................................................................................................54

5.7 SERVICE KITS..................................................................................................................................54

6 Adjustments and servicing procedures.....................................................................55

6.1 AIR FILTER......................................................................................................................................55

6.2 COOLERS.......................................................................................................................................56

6.3 SAFETY VALVE ................................................................................................................................56

6.4 UNLOAD/STOP PRESSURE SWITCH .......................................................................................................57

6.5 BELT SET EXCHANGE AND TENSIONING ................................................................................................59

7 Problem solving............................................................................................................61

7.1 PROBLEM SOLVING...........................................................................................................................61

8 Technical data...............................................................................................................64

8.1 READINGS ON CONTROL PANEL...........................................................................................................64

8.2 SETTINGS FOR OVERLOAD RELAY AND FUSES.........................................................................................65

8.3 REFERENCE CONDITIONS AND LIMITATIONS............................................................................................65

8.4 COMPRESSOR DATA..........................................................................................................................66

9 Instructions for use of air receiver..............................................................................70

9.1 INSTRUCTIONS FOR USE.....................................................................................................................70

10 PED................................................................................................................................71

2920 7054 00 3

Downloaded from www.Manualslib.com manuals search engine


Instruction book

10.1 PRESSURE EQUIPMENT DIRECTIVES......................................................................................................71

4 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

1 Safety precautions

1.1 Safety icons

Explanation

Danger for life

Warning

Important note

1.2 Safety precautions during installation

All responsibility for any damage or injury resulting from neglecting these
precautions, or non-observance of the normal caution and care required for
installation, operation, maintenance and repair, even if not expressly stated, will
be disclaimed by the manufacturer.

General precautions
1. The operator must employ safe working practices and observe all related local work safety requirements
and regulations.
2. If any of the following statements does not comply with local legislation, the stricter of the two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorised, trained,
specialised personnel.
4. The compressor is not considered capable of producing air of breathing quality. For air of breathing quality,
the compressed air must be adequately purified according to local legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the compressor,
press the emergency stop button, switch off the voltage and depressurise the compressor. In addition, the
power isolating switch must be opened and locked.
6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never
use the air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme
caution and wear eye protection.

Precautions during installation


1. The machine must only be lifted using suitable equipment in accordance with local safety regulations.
Loose or pivoting parts must be securely fastened before lifting. It is strictly forbidden to dwell or stay in
the risk zone under a lifted load. Lifting acceleration and deceleration must be kept within safe limits.
Wear a safety helmet when working in the area of overhead or lifting equipment.
2. Place the machine where the ambient air is as cool and clean as possible. If necessary, install a suction
duct. Never obstruct the air inlet. Care must be taken to minimise the entry of moisture at the inlet air.
3. Any blanking flanges, plugs, caps and desiccant bags must be removed before connecting the pipes.

2920 7054 00 5

Downloaded from www.Manualslib.com manuals search engine


Instruction book

4. Air hoses must be of correct size and suitable for the working pressure. Never use frayed, damaged or
worn hoses. Distribution pipes and connections must be of the correct size and suitable for the working
pressure.
5. The aspirated air must be free of flammable fumes, vapours and particles, e.g. paint solvents, that can lead
to internal fire or explosion.
6. Arrange the air intake so that loose clothing worn by people cannot be sucked in.
7. Ensure that the discharge pipe from the compressor to the aftercooler or air net is free to expand under
heat and that it is not in contact with or close to flammable materials.
8. No external force may be exerted on the air outlet valve; the connected pipe must be free of strain.
9. If remote control is installed, the machine must bear a clear sign stating: DANGER: This machine is
remotely controlled and may start without warning.
The operator has to make sure that the machine is stopped and that the isolating switch is open and locked
before any maintenance or repair. As a further safeguard, persons switching on remotely controlled
machines shall take adequate precautions to ensure that there is no one checking or working on the
machine. To this end, a suitable notice shall be affixed to the start equipment.
10. Air-cooled machines must be installed in such a way that an adequate flow of cooling air is available and
that the exhausted air does not recirculate to the compressor air inlet or cooling air inlet.
11. The electrical connections must correspond to the local codes. The machines must be earthed and protected
against short circuits by fuses in all phases. A lockable power isolating switch must be installed near the
compressor.
12. On machines with automatic start-stop system or if the automatic restart function after voltage failure is
activated, a sign stating "This machine may start without warning" must be affixed near the instrument
panel.
13. In multiple compressor systems, manual valves must be installed to isolate each compressor. Non-return
valves (check valves) must not be relied upon for isolating pressure systems.
14. Never remove or tamper with the safety devices, guards or insulation fitted on the machine. Every pressure
vessel or auxiliary installed outside the machine to contain air above atmospheric pressure must be
protected by a pressure-relieving device or devices as required.
15. Pipework or other parts with a temperature in excess of 80˚C (176˚F) and which may be accidentally
touched by personnel in normal operation must be guarded or insulated. Other high-temperature pipework
must be clearly marked.
16. For water-cooled machines, the cooling water system installed outside the machine has to be protected by
a safety device with set pressure according to the maximum cooling water inlet pressure.
17. If the ground is not level or can be subject to variable inclination, consult the manufacturer.

Also consult following safety precautions: Safety precautions during operation and Safety
precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas. Processing
of any other gas requires additional safety precautions typical to the application which are not
included herein.
Some precautions are general and cover several machine types and equipment; hence some
statements may not apply to your machine.

1.3 Safety precautions during operation

All responsibility for any damage or injury resulting from neglecting these
precautions, or non-observance of the normal caution and care required for
installation, operation, maintenance and repair, even if not expressly stated, will
be disclaimed by the manufacturer.

6 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

General precautions
1. The operator must employ safe working practices and observe all related local work safety requirements
and regulations.
2. If any of the following statements does not comply with local legislation, the stricter of the two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorised, trained,
specialised personnel.
4. The compressor is not considered capable of producing air of breathing quality. For air of breathing quality,
the compressed air must be adequately purified according to local legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the compressor,
press the emergency stop button, switch off the voltage and depressurise the compressor. In addition, the
power isolating switch must be opened and locked.
6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never
use the air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme
caution and wear eye protection.

Precautions during operation


1. Use only the correct type and size of hose end fittings and connections. When blowing through a hose or
air line, ensure that the open end is held securely. A free end will whip and may cause injury. Make sure
that a hose is fully depressurized before disconnecting it.
2. Persons switching on remotely controlled machines shall take adequate precautions to ensure that there
is no one checking or working on the machine. To this end, a suitable notice shall be affixed to the remote
start equipment.
3. Never operate the machine when there is a possibility of taking in flammable or toxic fumes, vapours or
particles.
4. Never operate the machine below or in excess of its limit ratings.
5. Keep all bodywork doors shut during operation. The doors may be opened for short periods only, e.g. to
carry out routine checks. Wear ear protectors when opening a door.
6. People staying in environments or rooms where the sound pressure level reaches or exceeds 90 dB(A)
shall wear ear protectors.
7. Periodically check that:
• All guards are in place and securely fastened
• All hoses and/or pipes inside the machine are in good condition, secure and not rubbing
• There are no leaks
• All fasteners are tight
• All electrical leads are secure and in good order
• Safety valves and other pressure-relief devices are not obstructed by dirt or paint
• Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses, etc. are in good repair, free
of wear or abuse
8. If warm cooling air from compressors is used in air heating systems, e.g. to warm up a workroom, take
precautions against air pollution and possible contamination of the breathing air.
9. Do not remove any of, or tamper with, the sound-damping material.
10. Never remove or tamper with the safety devices, guards or insulations fitted on the machine. Every pressure
vessel or auxiliary installed outside the machine to contain air above atmospheric pressure shall be
protected by a pressure-relieving device or devices as required.

2920 7054 00 7

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Also consult following safety precautions: Safety precautions during installation and Safety
precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas. Processing
of any other gas requires additional safety precautions typical to the application which are not
included herein.
Some precautions are general and cover several machine types and equipment; hence some
statements may not apply to your machine.

1.4 Safety precautions during maintenance or repair

All responsibility for any damage or injury resulting from neglecting these
precautions, or non-observance of the normal caution and care required for
installation, operation, maintenance and repair, even if not expressly stated, will
be disclaimed by the manufacturer.

General precautions
1. The operator must employ safe working practices and observe all related local work safety requirements
and regulations.
2. If any of the following statements does not comply with local legislation, the stricter of the two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorised, trained,
specialised personnel.
4. The compressor is not considered capable of producing air of breathing quality. For air of breathing quality,
the compressed air must be adequately purified according to local legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the compressor,
press the emergency stop button, switch off the voltage and depressurise the compressor. In addition, the
power isolating switch must be opened and locked.
6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never
use the air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme
caution and wear eye protection.

Precautions during maintenance or repair


1. Always wear safety glasses.
2. Use only the correct tools for maintenance and repair work.
3. Use only genuine spare parts.
4. All maintenance work shall only be undertaken when the machine has cooled down.
5. A warning sign bearing a legend such as "work in progress; do not start" shall be attached to the starting
equipment.
6. Persons switching on remotely controlled machines shall take adequate precautions to ensure that there
is no one checking or working on the machine. To this end, a suitable notice shall be affixed to the remote
start equipment.
7. Close the compressor air outlet valve before connecting or disconnecting a pipe.
8. Before removing any pressurized component, effectively isolate the machine from all sources of pressure
and relieve the entire system of pressure.
9. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety precautions against
toxic vapours of cleaning liquids.
10. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by covering the parts
and exposed openings with a clean cloth, paper or tape.

8 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

11. Never weld or perform any operation involving heat near the oil system. Oil tanks must be completely
purged, e.g. by steam-cleaning, before carrying out such operations. Never weld on, or in any way modify,
pressure vessels.
12. Whenever there is an indication or any suspicion that an internal part of a machine is overheated, the
machine shall be stopped but no inspection covers shall be opened before sufficient cooling time has
elapsed; this to avoid the risk of spontaneous ignition of the oil vapour when air is admitted.
13. Never use a light source with open flame for inspecting the interior of a machine, pressure vessel, etc.
14. Make sure that no tools, loose parts or rags are left in or on the machine.
15. All regulating and safety devices shall be maintained with due care to ensure that they function properly.
They may not be put out of action.
16. Before clearing the machine for use after maintenance or overhaul, check that operating pressures,
temperatures and time settings are correct. Check that all control and shut-down devices are fitted and that
they function correctly. If removed, check that the coupling guard of the compressor drive shaft has been
reinstalled.
17. Every time the separator element is renewed, examine the discharge pipe and the inside of the oil separator
vessel for carbon deposits; if excessive, the deposits should be removed.
18. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture from entering
them, e.g. when steam-cleaning.
19. Make sure that all sound-damping material, e.g. on the bodywork and in the air inlet and outlet systems
of the compressor, is in good condition. If damaged, replace it by genuine material from the manufacturer
to prevent the sound pressure level from increasing.
20. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate bowls.
21. The following safety precautions are stressed when handling refrigerant:
• Never inhale refrigerant vapours. Check that the working area is adequately ventilated; if required, use
breathing protection.
• Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin with water. If
liquid refrigerant contacts the skin through clothing, never tear off or remove the latter; flush
abundantly with fresh water over the clothing until all refrigerant is flushed away; then seek medical
first aid.
22. Protect hands to avoid injury from hot machine parts, e.g. during draining of oil.

Also consult following safety precautions: Safety precautions during installation and Safety
precautions during operation.
These precautions apply to machinery processing or consuming air or inert gas. Processing
of any other gas requires additional safety precautions typical to the application which are not
included herein.
Some precautions are general and cover several machine types and equipment; hence some
statements may not apply to your machine.

2920 7054 00 9

Downloaded from www.Manualslib.com manuals search engine


Instruction book

2 General description

2.1 Introduction

Introduction
GX 7 and GX 11 are single-stage, oil-injected screw compressors.
The compressor is air-cooled and belt-driven by an electric motor. The compressor is enclosed in sound-
insulated bodywork. An easy-to-operate control panel (1) is provided, including the start/stop switch and the
emergency stop button. A cabinet housing the regulator, pressure switch and motor starter is integrated into
the bodywork.

Floor-mounted model
The compressor is installed directly on the floor.

Tank-mounted model

Front view, GX 7 and GX 11 Full-Feature

GX 7 and GX 11 are mounted on a large air receiver (AR) of 270 l (71.28 US gal / 59.40 Imp gal / 9.45 cu.ft)
or an optional air receiver of 500 l (132 US gal / 110 Imp gal / 17.50 cu.ft).

10 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Ref. Name
1 Control panel
AF Air filter
AO Air outlet
AR Air receiver
Ca Air cooler
Co Oil cooler
Da Automatic drain
Dm1 Manual condensate drain
DR Dryer
E Compressor element
OF Oil filter
OS Oil separator
OT Oil separator tank

GX Full-feature
An air cooler (Ca) and an air dryer (DR) are integrated into the bodywork. A condensate drain system is
provided including a valve for automatic draining during operation (Da) and a manual drain valve (Dm1).

GX Pack
The compressor is not fitted with an air cooler, air dryer and condensate drain system as standard.

2920 7054 00 11

Downloaded from www.Manualslib.com manuals search engine


Instruction book

2.2 Air flow

Flow diagram

Air flow, GX 7 and GX 11 Pack (tank-mounted)

Air flow (Pack version):


Air drawn through filter (AF) and open inlet valve (IV) into compressor element (E) is compressed.
Compressed air and oil flow into oil separator/tank (OT). The air is discharged via minimum pressure valve
(Vp) towards the air outlet (AO).

12 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Air flow, GX 7 and GX 11 Full-Feature (tank-mounted)

Air drawn through filter (AF) and open inlet valve (IV) into compressor element (E) is compressed.
Compressed air and oil flow into oil separator/tank (OT). The air is discharged via minimum pressure valve
(Vp), air cooler (Ca) and air dryer (DR) towards the air outlet (AO).

2920 7054 00 13

Downloaded from www.Manualslib.com manuals search engine


Instruction book

2.3 Oil system

GX 7 and GX 11 Pack

GX 7 and GX 11 Full-Feature

Air pressure forces the oil from oil separator/tank (OT) through oil cooler (Co) and filter (OF) to compressor
element (E) and the lubrication points. In oil separator/tank (OT), most of the oil is removed centrifugally;
the rest is removed by separator (OS).

14 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

The oil system is fitted with a by-pass valve (BV). When the oil temperature is below the set-point of the
valve, the by-pass valve shuts off the oil supply from oil cooler. The by-pass valve starts opening the supply
from cooler (Co) when the oil temperature exceeds the setting of the valve. The setting of the by-pass valve
depends on the model. See the section Compressor data.

2.4 Cooling system

Cooling system

GX 7 and GX 11 Pack

The cooling system of the Pack version comprises oil cooler (Co). A fan (FN), mounted directly onto the
motor shaft, generates the cooling air in order to cool the oil.
An air cooler (Ca) is available as option.

2920 7054 00 15

Downloaded from www.Manualslib.com manuals search engine


Instruction book

GX 7 and GX 11 Full-Feature

The cooling system of the Full Feature version comprises oil cooler (Co) and air cooler (Ca). A fan (FN),
mounted directly onto the motor shaft, generates the cooling air in order to cool the oil and the compressed
air.

2.5 Regulating system

Main components

Detail view of unloader assembly (UA)

The main components of the regulating system are:


• Pressure switch, which opens and closes at preset pressure limits. See Protection of compressor
• Unloader (UA), including inlet valve (IV) and unloading valve (UV).

16 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

• Loading solenoid valve (Y1).


• The Elektronikon 001 regulator

Loading
As long as the working pressure is below the maximum limit, the solenoid valve is energised allowing control
air to flow to the unloader: the inlet valve opens completely and the unloading valve closes completely. The
compressor will run fully loaded (100% output).

Unloading
If the working pressure reaches the maximum limit, the solenoid valve is de-energised venting the control air:
the inlet valve closes completely and the unloading valve opens completely. The compressor will run fully
unloaded (0% output).
The GX 7 and GX 11 is equipped with the Elektronikon 001, an intelligent controller that will stop the
compressor after a variable period of unloaded operation:
• When the unloading pressure is reached after the first start and if there is no air consumption, the
compressor will run unloaded during 2 minutes and than stop.
• If there is a pressure request within the first 2 minutes after being stopped, the controller is expecting a
higher air consumption: the next time the unit will stop after 5 minutes of unloaded operation.
• If there is no pressure request earlier than 2 minutes after being stopped, the controller is expecting a lower
air consumption: the next time again it stops after 2 minutes of unloaded operation.
• If the compressor is stopped manually, it stops after 2 minutes unloaded operation.
The compressor will automatically restart when the net pressure drops to the minimum limit.

2920 7054 00 17

Downloaded from www.Manualslib.com manuals search engine


Instruction book

2.6 Control panel

Control panel GX 7 and GX 11

Symbol Description
RESET button.
Pressing the button cancels the stored alarm indication.
When pressing the button during more than 3 seconds, the central control unit is tested:
all the LEDs must be on.
START button.
Pressing the button switches on the compressor. The motor starts 25 seconds after the
button is pushed.
STOP button.
Pressing the button starts the compressor switch-off phase: the compressor runs idle
during 120 seconds (2 minutes) before stopping.

Symbol Led flashing Led on


The motor overload (FM1) has switched The NC contact of motor overload (FM1) is
off the motor. The NC contact of FM1 is closed again, but the fault is not yet reset.
open.
Not applicable Not applicable

18 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Symbol Led flashing Led on


The oil temperature switch (TSH) has The NC contact of the oil temperature switch is
switched off the motor. The NC contact closed again, but the fault is not yet reset.
is open.
On star/delta started compressors, -
during start-up (transitory: star
contactor energized)
- Compressor running loaded

General alarm -

Not enabled Not enabled

Compressor running unloaded (idle) -


before stopping
Compressor ready to start - (Stand-by) Compressor operating

- Main power on

To start up again after a protection has been triggered (alarm): press the RESET button,
followed by the START button (1).
The motor will start after a delay of 25 seconds.

Operation of the central control unit


The central control unit is programmed for Energy Saving. It will automatically start and stop the compressor,
depending on the need for compressed air. Before switching off, the compressor will run idle (unloaded). The
idling period decreases when the air consumption decreases, thus reducing idle running to a minimum. See
also Regulating system.

Reference Designation Function


1 Start button To start or stop the compressor. After the stop command,
2 Stop button the compressor will run unloaded for a period of 120
seconds and then stop.
Hm Hour meter Indicates the total running time.
Gdp Dew-point gauge Indicates the dew-point temperature.
Not installed on Pack versions
Gpa Working pressure The white pointer indicates the actual working pressure.
The red one indicates the maximum limit.
S3 Emergency stop button To stop the compressor immediately; only to be used in
the event of an emergency. Must be unlocked before
starting by pulling it out.

Only use emergency stop button (S3) in the event of an emergency.

2920 7054 00 19

Downloaded from www.Manualslib.com manuals search engine


Instruction book

2.7 Protection of compressor

Electric cubicle

Legend

Ref. Designation
(1) only on Full Feature versions
(2) only on multi-voltage versions

Ref. Designation
F1-2-3-4-10 Fuses (F10 only on Full Feature units - see (1) on figure)
FM1 Motor overload relay
KL Line contactor

20 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Ref. Designation
KY Star contactor
KD Delta contactor
T1 Transformer
KMD Dryer relay (only on FF versions - see (1) on figure)
XM1 Connection terminals (only available on multi-voltage versions - see (2) on figure)

Safety valve on the compressor and on the vessel

Reference Designation Function


TSH Temperature shut-down To shut down the compressor if the temperature at the
See also the switch outlet of the compressor element is too high.
Electrical diagrams
section
SV Safety valve To protect the air outlet system if the outlet pressure
exceeds the opening pressure of the valve.

2920 7054 00 21

Downloaded from www.Manualslib.com manuals search engine


Instruction book

2.8 Air dryer

Air Dryer

Wet compressed air enters the dryer and is further cooled by the outgoing, dried air (2). Moisture in the
incoming air condenses. The air then flows through heat exchanger (1) where refrigerant evaporates,
withdrawing heat from the air. The cold air then flows through condensate trap (4) which separates condensate
from the air. The condensate is automatically drained. The cold, dried air then flows through heat exchanger
(3), where it is warmed up by the incoming air.

22 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

3 Installation

3.1 Installation proposal

Important

Transport by a pallet truck

For transport with a fork truck, use the openings in the frame.
Move the compressor gently.

2920 7054 00 23

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Proposal

Installation proposal, GX 7 and GX 11

Action
1 Install the rubber pads (delivered loose with the compressor) to the compressor supports.
Install the compressor on a solid, level floor suitable for taking its weight.
The recommended minimum distance between the top of the unit and the ceiling is 900 mm (35.1
in).
The air receiver must not be bolted to the floor.
For tank-mounted units, the minimum distance between the wall and the back of the compressor
is 500 mm (19.5 in).
2 Position of the compressed air outlet valve.
Close the valve.
Connect the air net to the valve.
3 The pressure drop over the delivery pipe can be calculated from the following formula:
dp=(L x 450 x Qc1.85) / (d5 x P)
• dp=pressure drop (recommended maximum = 0.1 bar / 1.5 psi)
• L=length of delivery pipe in m
• d=inner diameter of the delivery pipe in mm
• P=absolute pressure at the compressor outlet in bar(a)
• Qc=free air delivery of the compressor in l/s

24 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Action
4 Ventilation: the inlet grids and ventilation fan should be installed in such a way that any recirculation
of cooling air to the compressor or dryer is avoided.
The air velocity to the grids must be limited to 5 m/s (200 in/s).
The required ventilation capacity to limit the temperature of the compressor room can be calculated
from the following formula:
Qv = 0.92 N / dT
• Qv=required ventilation capacity in m3/s
• N=nominal motor power of compressor in kW
• dT=temperature increase in compressor room
5 Position of the mains cable entry.
6 The drain pipes to the drain collector must not dip into the water of the drain collector.

2920 7054 00 25

Downloaded from www.Manualslib.com manuals search engine


Instruction book

3.2 Dimension drawings

Dimension drawings, GX 7 and GX 11

GX 7 and GX 11 Tank-mounted (270 l), Pack

26 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

GX 7 and GX 11 Tank-mounted (500 l, optional), Pack

2920 7054 00 27

Downloaded from www.Manualslib.com manuals search engine


Instruction book

GX 7 and GX 11 Tank-mounted (270 l), Full-Feature

28 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

GX 7 and GX 11 Tank-mounted (500 l, optional), Full-Feature

2920 7054 00 29

Downloaded from www.Manualslib.com manuals search engine


Instruction book

GX 7 and GX 11 Floor-mounted , Pack

30 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

GX 7 and GX 11 Floor-mounted , Full-Feature

Ref. Name
1 Cooling air outlet
2 Cooling air inlet
3 Location of supply cable entry
4 Manual drain (G 3/8 female)
5 Compressed air outlet (G 1/2 female)
6 Dryer air outlet
7 Dryer air inlet
8 Motor cooling air inlet
9 Outlet valve (delivered loose)

2920 7054 00 31

Downloaded from www.Manualslib.com manuals search engine


Instruction book

3.3 Electric cable size

Attention

Local regulations remain applicable if they are stricter than the values proposed below.
The voltage drop must not exceed 5% of the nominal voltage. It may be necessary to use
cables of a larger size than those stated to comply with this requirement.

GX 7 GX 11
Frequency Voltage Cable size Cable size
(Hz) (V)
IEC (mm2) (mm2)
50 200 16 (6 XLPE or EPR) 25 (16 XLPE or EPR)
50 230 10 16 (10 XLPE or EPR)
50 400 4 6
50 500 4 6
60 440/460 4 6
60 380 4 6
CSA/UL AWG AWG
60 200 6 6
60 208-230 / 460 8-8 / 10 6-6 / 8
60 575 12 10

3.4 Electrical connections

Always disconnect the power supply before working on the electrical circuit!

32 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

General instructions

Electrical connection, GX 7 and GX 11

Step Action
1 Install an isolating switch near the compressor.
2 Check the fuses and the setting of overload relay. See Settings for overload relay and
fuses.
3 If fitted, check transformers for correct connection.
4 Connect the power supply cables to terminals L1, L2 and L3 (1X0) and the neutral
conductor (if applicable) to terminal (N). Connect the earth conductor.

Specific instructions for GX 7 and GX 11 with 208 V / 230 V / 460 V cubicle


The standard voltage configuration for the compressor is mentioned on the data plate of the machine. When
the compressors leave the factory, the units are connected for 230 V / 3 phase.

2920 7054 00 33

Downloaded from www.Manualslib.com manuals search engine


Instruction book

To modify the wiring for an operating voltage of 208 V or 460 V , both compressor main cubicle and
transformer dryer cubicle should be rewired as described below:

1. Required modifications in the compressor cubicle:

Step Action
1 Adjust the motor overload (FM1) setting.
2 Rewire the control transformer (T1)
3 Replace the control fuses (F1) with the 10,3 x 38mm 1 A or 2 A fuses provided (see further).
4 Modify the motor terminal bridge configuration in the main cubicle for the desired voltage.
5 Replace the voltage sticker by the appropriate voltage sticker provided.
6 On FF units, replace the power fuses (F10 in the main cubicle, F11 in the power
transformer cubicle) with the CC type 5 A, respectively 7,5 A fuses provided.
7 Modify the power transformer terminal bridge configuration in the transformer cubicle for
the desired voltage.

To adjust the motor overload (FM1) setting, simply rotate the adjustment screw (1) on the front of the overload
relay to the required setting (see table below).

Adjustment screw of the motor overload

34 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

motor overload (FM1) settings 7,5 kW 11 kW


10 hp 15 hp
208V 36.3 48
230V (standard factory setting) 34.4 45
460V 16.9 22.5

To rewire the control transformer (T1), move the wire of the transformer to the terminal marked with the
desired voltage (208 V, 230 V or 460 V).

Replace the two fuses marked F1 by opening the fuse-holder an. Use the 2 A fuses for 208-230 V and the 1
A fuses for 460 V, supplied with the compressor.

Fuses fuse rating V 208 V 230 V 460 V Class


F1 600 V AC 2A 2A 1A UL class JDYX or JDYX2 10,3 x
38mm
F1 600 V AC 2A 2A 1A UL class JDYX or JDYX2 10,3 x
38mm
F2 250 V AC 3A 3A 3A UL class JDYX or JDYX2 5 x 20
mm
F3 250 V AC 1A 1A 1A UL class JDYX or JDYX2 5 x 20
mm
F3 250 V AC 1A 1A 1A UL class JDYX or JDYX2 5 x 20
mm
F10 600 V AC 7,5 A 7,5 A 5A UL guide JDDZ class CC type
FNQ-R 10,3 x 38 mm
F10 600 V AC 7,5 A 7,5 A 5A UL guide JDDZ class CC type
FNQ-R 10,3 x 38 mm

Note: fuses F10 are only applicable to FF units. See also Electric diagrams.

2920 7054 00 35

Downloaded from www.Manualslib.com manuals search engine


Instruction book

To modify the terminal bridge configuration to the motor, configure the terminal bridges for the desired voltage
(208 V, 230 V or 460V) according to the diagram below. The terminal bridges (1) can be easily removed
using a pair of pliers. Additional terminal bridges are provided with the compressor. The connections for 230
V are the factory standard.

Locate the yellow voltage labels provided with the compressor. Replace the existing label with the appropriate
voltage label (200-208 V, 230V or 460V).

Voltage labels for GX 7 and GX 11

2. Dryer transformer cubicle modifications


Remove the rear panel and the transformer box rear cover. Use fuses F11 only for a supply voltage of 460 V.
F11 is not to be used for a supply voltage of 208 - 230 V.

36 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Fuses V (AC/DC) 208V 230V 460V Class


F11 600 V AC / / 7,5 A UL guide JDDZ class CC type
FNQ-R 10,3 x 38 mm

2920 7054 00 37

Downloaded from www.Manualslib.com manuals search engine


Instruction book

3.5 Electrical diagrams

Electrical diagram, GX 7 and GX 11 IEC

38 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Electrical diagram, GX 7 and GX 11 CSA/UL

2920 7054 00 39

Downloaded from www.Manualslib.com manuals search engine


Instruction book

3.6 Pictographs

Pictographs

Ref. Description
1 Working pressure
2 Hour meter
3 Dew-point temperature
4 Start
5 Stop
6 Warning: voltage
7 Lightly oil gasket of oil filter, screw filter on and tighten by hand
9 Warning: switch off voltage and depressurise compressor before carrying out maintenance
work
10 Warning: hot parts
11 Lock all doors of the bodywork and push the start button.
• If the sheet is pulled downwards: Stop the compressor immediately and switch
off the voltage.
• Reverse two incoming electric lines. Repeat the previous step.
• If the sheet is blown away the motor rotation direction is correct.
12 Manual condensate drain
13 Automatic condensate drain

40 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

4 Operating instructions

4.1 Initial start-up

Safety

The operator must apply all relevant Safety precautions.

Moving
To safely move a Tank-mounted model, see Installation.

General preparation

Air outlet valve

Condensate drain, GX 7 up to GX 11

2920 7054 00 41

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Condensate drain valve, GX 7 and GX 11

Step Action
1 Consult the installation instructions (see Installation).
2 Check that the electrical connections correspond to the local codes. The installation must
be earthed and protected against short circuits by fuses in all phases. An isolating switch
must be installed near the compressor.
3 Fit outlet valve (2), close it and connect the air net to the valve.
Connect condensate drain valve (Dm) and automatic drain outlet (Da) to a drain collector.
Close the valve.
Connect condensate drain valve (4) of the air receiver to a drain collector. Close the valve.

Oil system

Oil level sight-glass, GX 7 and GX 11

Step Action
Check the oil level.
The oil level sight-glass (SG) should be between 1/4 and 3/4 full.

42 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Start-up

Label on the top

Step Action
1 Affix sheet (5) explaining the procedure for checking the motor rotation direction to the
cooling air outlet of the compressor (consult Dimension drawings).
Switch on the voltage. Start the compressor and stop it immediately.
Check the rotation direction of the motor using sheet (5). If the motor rotation direction is
correct, the label on the top grating will be blown upwards. If the sheet remains in place,
the rotation direction is incorrect (see the pictographs on the label).
If the rotation direction is incorrect, switch off the voltage, open the isolating switch and
reverse two incoming electric lines.
2 Start and run the compressor for a few minutes. Check that the compressor operates
normally.

4.2 Starting

Air outlet valve

2920 7054 00 43

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Condensate drain valve, GX 7 and GX 11

Pressure gauge

Dew-point temperature gauge

Control panel GX 7 up to GX 11

44 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Position of oil sight glass and filler plug on GX 7 and GX 11

Step Action
1 Before starting, the oil level sight-glass (SG) should be between 1/4 and 3/4 full.
2 Switch on the voltage.
3 Open air outlet valve (2).
4 Push the start button (1). The motor starts running after 25 seconds and automatic
operation led (3) alights.
On compressors with a star-delta starter, the drive motor switches over from star to delta
10 seconds after starting.
The maximum number of motor starts must be limited to 20 per hour.
It is strongly recommended to operate the compressor with a load factor of more than 10%
to avoid condensate in the oil.
5 Regularly check the oil level. 10 to 15 minutes after stopping, the sight-glass (SG) should
be between 1/4 and 3/4 full.
If the oil level is too low, stop the compressor, depressurise the oil system by unscrewing
oil filler plug (FC) one turn and wait a few minutes. Remove the plug and top up the oil,
until the sight-glass is 3/4 full. Do not overfill. Fit and tighten plug (FC).
6 When automatic operation LED (3) is lit, the regulator is automatically controlling the
compressor, i.e. loading, unloading, stopping of the motors and restarting.
7 Regularly check the working pressure (Gpa) and the dew-point gauge (Gdp) (FF units).
8 Regularly check that condensate is drained (Da) during running.

During normal operation, the oil level should be at approximately half of the sightglass. Under
certain conditions it is possible that only foam is visible. In that case, the oil level can only be
checked after stopping, following the described procedure.
Always stop the compressor as explained in Stopping. Never use the emergency stop button
for normal stopping.

2920 7054 00 45

Downloaded from www.Manualslib.com manuals search engine


Instruction book

4.3 Stopping

Air outlet valve

Condensate drain valve, Tank-mounted GX 7 and GX 11

46 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Control panel GX 7 up to GX 11

Step Action
1 Push the stop button (2) on the control panel. The compressor will switch to unloaded
operation and stops after 120 seconds. The automatic operaion LED goes out.
To stop the compressor immediately in the event of an emergency, press button (S3). See
the Control panel section. After remedying the fault, unlock the button by pulling it out.
Only use emergency stop button in the event of an emergency. Avoid using the button for
normal stopping of the compressor.

2 Close air outlet valve (2) and switch off the voltage to the compressor.
3 Open condensate drain valve (Dm) for a few seconds to drain any condensate and then
close the valve.
Open condensate drain valve (4) of the air receiver for a few seconds to drain any
condensate and then close the valve.
The air dryer and the air receiver remain under pressure.
The PDX filter (if installed) remains under pressure.
If maintenance or repair work is necessary, consult the Problem solving section for all
relevant safety precautions.

2920 7054 00 47

Downloaded from www.Manualslib.com manuals search engine


Instruction book

4.4 Taking out of operation

Air outlet valve

Condensate drain valve, Tank-mounted GX 7 and GX 11

Filler plug, GX 7 and GX 11

This procedure should be carried out at the end of the compressor’s service life.

Step Action
1 Stop the compressor and close the air outlet valve (2).

48 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Step Action
2 Switch off the voltage and disconnect the compressor from the mains.
3 Depressurise the compressor by opening plug (3) one turn.
Open condensate drain valve (Dm).
Open condensate drain valve (4) of the air reciever.
4 Shut off and depressurise the part of the air net which is connected to the outlet valve.
Disconnect the compressor air outlet valve from the air net.
5 Drain the oil and condensate circuits.
6 Disconnect the compressor condensate outlet and valve from the condensate net.

2920 7054 00 49

Downloaded from www.Manualslib.com manuals search engine


Instruction book

5 Maintenance

5.1 Preventive maintenance schedule

Warning

Before carrying out any maintenance, repair work or adjustments, proceed as


follows:
• Stop the compressor.
• Switch off the voltage and open the isolating switch.
• Close the air outlet valve and open the manual condensate drain valves.
• Depressurise the compressor.
For detailed instructions, see Problem solving.
The operator must apply all relevant Safety precautions.

Warranty-Product Liability
Use only authorised parts. Any damage or malfunction caused by the use of unauthorised parts is not covered
by Warranty or Product Liability.

General
When servicing, replace all removed gaskets, O-rings and washers.

Intervals
Carry out maintenance at the interval which comes first. The local Atlas Copco Customer Centre may overrule
the maintenance schedule, especially the service intervals, depending on the environmental and working
conditions of the compressor.
The "longer interval" checks must also include the "shorter interval" checks.

Preventive maintenance schedule for GX 7 and GX 11

Period Running hours Operation


Daily -- Check the oil level before starting. Drain the condensate after stopping.
For tank-mounted units, also drain the air vessel by means of the
manual drain valve (4), see Stopping.
3-Monthly -- Check for possible leaks.
“ 1000 Inspect the oil cooler, clean if necessary.
“ 1000 For Full-Feature versions: inspect the condenser of the dryer; clean if
necessary.
“ 1000 Inspect the air filter.
“ -- Inspect the condensate trap, clean the filter DA (for location of DA, see
Introduction.
“ -- For compressors with PDX filter: check the service indicator, replace
the filter if necessary.
-- 1000 Check the tension and the condition of the belts. Adjust, if necessary.

50 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Period Running hours Operation


Yearly -- Have the safety valve tested.
“ -- Have the operation of sensors, electrical interlockings and components
checked.
“ -- Have the temperature shut-down switch tested.
“ 4000 Replace the air filter.
“ 4000 Replace the oil filter.
“ 4000 Replace the oil separator.
“ 4000 For compressors with PDX filter, replace the filter.
“ 4000 If Atlas Copco Roto-Inject Fluid is used, change the oil.
“ 8000 If Atlas Copco Roto-Xtend Duty Fluid is used (indicated by a specific
label on the oil vessel), change the oil.
“ -- Clean the compressor.

5.2 Drive motor

Description
The motor bearings are greased for life.

5.3 Oil specifications

Never mix oils of different brands or types.

It is strongly recommended to use Atlas Copco lubricants. See Preventive maintenance schedule for
recommended oil change intervals.
For part numbers, consult the Spare Parts List.

Atlas Copco Roto-Inject Fluid


Atlas Copco Roto-Inject Fluid is special oil for oil-injected scroll and screw compressors which keeps the
compressor in excellent condition. Roto-Inject Fluid can be used for compressors operating at ambient
temperatures between 0˚C (32˚F) and 40˚C (104˚F)(see Service kits).

Atlas Copco Roto-Xtend Duty Fluid


Atlas Copco Roto-Xtend Duty Fluid is a high-quality synthetic lubricant for oil-injected scroll and screw
compressors which keeps the compressor in excellent condition. Roto-Xtend Duty Fluid can be used for
compressors operating at ambient temperatures between 0˚C (32˚F) and 40˚C (104˚F)(see Service kits).

2920 7054 00 51

Downloaded from www.Manualslib.com manuals search engine


Instruction book

5.4 Oil, filter and separator change

Important

Never mix oils of different brands or types.


If the compressor is exposed to external pollutants, is being used at high temperatures (oil
temperature above 90˚C / 194˚F) or is being used under severe conditions, it is advisable to
change the oil more frequently. Consult Atlas Copco.

Location of oil filter and separator

Step Action
1 Run the compressor until warm. Stop the compressor, close the air outlet valve and switch
off the voltage. See Stopping.
2 Depressurise the compressor by unscrewing filler plug (2) one turn to permit any pressure
in the system to escape. Remove the plug after the system is depressurised.
3 Depressurise the air receiver by opening drain valve (8).
4 Remove plug (5), drain the oil by opening drain valve (6). Close the valve and refit the plug
after draining. Deliver the drained oil to the local oil collection service.
5 Remove oil filter (7) and separator (1). Clean the seats on the manifold.
6 Oil the gaskets of the new filter and separator and screw them into place. Tighten firmly
by hand.
7 Fill oil separator/tank (3) with oil until the level reaches the middle of sight-glass (4). Ensure
no dirt gets into the system.
8 Refit and tighten filler plug (2).
9 Close drain valve (8) of the air receiver.
10 Run the compressor for a few minutes.
11 Stop the compressor and wait a few minutes to allow the oil to settle.
12 Check the oil level. Add oil if necessary.
If the oil level is too low, depressurise the system by unscrewing filler plug (2) one turn to
permit any pressure in the system to escape. Depressurise the air receiver by opening
drain valve (8).

52 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Step Action
13 Add oil as necessary. The sight-glass should be 3/4 full. Retighten plug (2) and close drain
valve (8) of the air receiver.

5.5 PDX/DDX filter change

Oil filler plug

GX 7 and GX 11

Drain valve, air receiver

GX 7 and GX 11

Step Action
1 Stop the compressor, close the air outlet valve, switch off the voltage and depressurise by
unscrewing oil filler plug (3) one turn to permit any pressure in the system to escape. See
Stopping.
If the compressor is fitted onto an air receiver, depressurise the air receiver by opening
condensate drain valve (4).
On floor-mouned units, depressurise the filter by loosing its drain valve.

2920 7054 00 53

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Step Action
2 Unscrew the filter bowl. A whistling noise will warn you if the bowl is not fully depressurised.
If this occurs, the bowl should be screwed back and the venting should be repeated.
3 Remove and discard the filter element.
4 Clean the bowl and replace its O-ring.
5 Fit the new filter element.
6 Refit the bowl.
7 Tighten oil filler plug (3).
8 Close condensate drain valve (4).

5.6 Storage after installation

If the compressor is stored without running from time to time, consult Atlas Copco as protective measures
may be necessary.

5.7 Service kits

For overhauling and for preventive maintenance, a wide range of service kits is available. Service kits comprise
all parts required for servicing the component and offer the benefits of genuine Atlas Copco parts while
keeping the maintenance budget low.
Also a full range of extensively tested lubricants, suitable for your specific needs is available to keep the
compressor in excellent condition.
Consult the Spare Parts List for part numbers.

54 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

6 Adjustments and servicing procedures

6.1 Air filter

Changing the air filter

Position of air filter for GX 7 and GX 11

Air filter change on GX 7 up to GX 11

Step Action
1 Stop the compressor, close the air outlet valve and switch off the voltage.
2 Remove the front panel and the top panel of the compressor housing.
3 Unscrew the filter cover (1) and remove the filter element. Discard the air filter element.
4 Fit the new element and screw on the filter cover.
5 Refit the top and front panels.

2920 7054 00 55

Downloaded from www.Manualslib.com manuals search engine


Instruction book

6.2 Coolers

GX 7 and GX 11

Step Action
1 Keep oil cooler (Co) clean to maintain the cooling efficiency.
For versions with air cooler: also keep cooler (Ca) clean to maintain the cooling efficiency.
2 Stop the compressor, close the air outlet valve and switch off the voltage. Remove any dirt
from the oil cooler (Co) with a fibre brush. For versions with air cooler: also remove any
dirt from the air cooler (Ca). Never use a wire brush or metal objects. Then clean using an
air jet.

6.3 Safety valve

Condensate drain valve, Tank-mounted GX 7 and GX 11

56 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Filler plug, GX 7 and GX 11

Testing
The valve can be tested on a separate compressed air line.
Before removing the safety valve, stop the compressor (see Stopping), close the air outlet valve, switch off
the voltage, open drain valves (4) (tank-mounted units) and the manual drain valve (5) (if fitted - on floor-
mounted units) and unscrew filler plug (3) one turn to permit any pressure in the system to escape.

If the valve does not open at the set pressure stamped on the valve, replace the valve.
No adjustments are allowed. Never run the compressor without a safety valve.

6.4 Unload/stop pressure switch

Pressure switch, GX 7 up to GX 11

2920 7054 00 57

Downloaded from www.Manualslib.com manuals search engine


Instruction book

The switch allows the operator to select the unloading/stopping pressure (see Regulating system).

Adjustment can only be carried out when the pressure switch is pressurised.

The loading/starting pressure is controlled by adjusting knob (2). Remove blocking device (3) and turn the
knob clockwise to raise the pressure, anti-clockwise to lower it. See also below drawing.
The pressure difference between unloading and loading is adjusted by means of the same knob. Push down
the knob and turn it clockwise to reduce the pressure difference, counter-clockwise to increase it.

58 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

6.5 Belt set exchange and tensioning

GX 7 and GX 11

Read the warning in the Preventive maintenance schedule section.

Checking the belt tension on GX 7 and GX 11

Step Action
1 Stop the compressor, close the air outlet valve and switch off the voltage
2 Remove the front door and the internal panel.
3 The tension is correct when a force of between 20 N (4.5 Ibf) and 25 N (5.63 Ibf) applied
at the midpoint of the belts causes a deflection of 5 mm (0.2 in).
4 Refit the bodywork panels.

Adjusting the tension of the drive belts for GX 7 and GX 11

Step Action
1 Stop the compressor, close the air outlet valve and switch off the voltage.
2 Remove the front door, the internal panel, the top cover and the pulley protection.
3 Loosen the 4 bolts (2) by one turn.
4 Adjust the belt tension by turning tensioning nut (1).
5 The tension is correct when a force of between 20 N (4.5 lbf) and 25 N (5.63 lbf) applied
at the midpoint of the belts causes a deflection of 5 mm (0.2 in).
6 Retighten bolts (2).
7 Refit the bodywork panels.

2920 7054 00 59

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Replacing the drive belts for GX 7 and GX 11

Step Action
The belts (3) must be replaced as a set, even if only one of the belts is worn. Only use
genuine Atlas Copco belts.

1 Stop the compressor, close the air outlet valve and switch off the voltage.
2 Remove the front door, the internal panel, the top cover, the pulley protection and the left
side panel.
3 Loosen the 4 bolts (2) by one turn.
4 Release the belt tension by loosening tensioning nut (1).
5 Remove the fan duct (4).
Remove the belts.
6 Install the new belts.
7 Tension belts (3) as described above.
8 Re-assemble the fan duct (4), the pulley protection and the internal protection panel.
9 Re-assemble left side and top panel cover.
10 Check the belt tension after 50 running hours.

60 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

7 Problem solving

7.1 Problem solving

Start/stop switch

GX 7 and GX 11

Air outlet valve

GX 7 and GX 11

2920 7054 00 61

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Oil filler plug

GX 7 and GX 11

Drain valve, air receiver

GX 7 and GX 11

Attention

Use only authorised parts. Any damage or malfunction caused by the use of unauthorised
parts is not covered by Warranty or Product Liability.
Apply all relevant Safety precautions.
Before carrying out any maintenance or repair work on the compressor: push the stop
button (2).
Wait until the compressor has stopped and switch off the voltage. See the Stopping
section.
Open the isolating switch to prevent an accidental start.
Close air outlet valve (2) and depressurise the compressor by opening the oil filler plug (3)
one turn.
Open manual condensate drain valves (4 and/or 5).
The air outlet valve (2) can be locked during maintenance or repair as follows:
• Close the valve.
• Remove the screw fixing the handle
• Remove the handle.
• Fit the screw.

62 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Faults and remedies


For all references given hereafter, see Air flow diagram, Initial start-up or Regulating system.
For GX 7 and GX 11

Condition Fault Remedy


1 Compressor starts running, but Solenoid valve (Y1) out of Replace valve
does not load after a delay time order
Inlet valve (IV) stuck in closed Have valve checked
position
Leak in control air flexibles Replace leaking flexible
Minimum pressure valve (Vp) Have valve checked
leaking (when net is
depressurised)
Timer out of order Replace timer
2 Compressor air output or Air consumption exceeds air Check equipment connected
pressure below normal output of compressor
Choked air inlet filter element Replace filter element
(AF)
Solenoid valve (Y1) Replace valve
malfunctioning
Leak in control air flexibles Replace leaking flexible
Inlet valve (IV) does not fully Have valve checked
open
Oil separator (OS) clogged Replace separator element
Safety valves leaking Replace valves
3 Air outlet temperature above Insufficient cooling air or Check for cooling air restriction or
normal cooling air temperature too improve ventilation of compressor
high room. Avoid recirculation of cooling
air. If installed, check capacity of
compressor room fan
Oil level too low Check and correct as necessary
Cooler clogged Clean cooler
Temperature switch Have switch tested
malfunctioning
Compressor element (E) out of Consult Atlas Copco
order

GX 7 up to GX 11 with air cooler

Condition Fault Remedy


1 Condensate is not discharged Discharge flexible clogged Check and correct as necessary
during loading
Float valve malfunctioning Remove float valve assembly, clean
or replace as necessary

2920 7054 00 63

Downloaded from www.Manualslib.com manuals search engine


Instruction book

8 Technical data

8.1 Readings on control panel

Pressure gauge GX 7 up to GX 11

Hourmeter

Dewpoint indicator

The readings mentioned below are valid under the reference conditions (see Reference
conditions and limitations).

Ref. Name
Gpa Air outlet pressure
Reading: Modulates between preset unloading/stopping pressure and loading pressure
Gdp Dew-point temperature
Reading: approx. 5˚C (41˚F) at 20˚C (68˚F) ambient temperature
Hm Hour meter
Reading: Total running time

64 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

8.2 Settings for overload relay and fuses

GX 7 and GX 11

Frequency Voltage (V) GX 7 GX 11


(Hz)
IEC Star-delta Overload relay Disc. switch + Overload relay Disc. switch +
FM1 (A) motor circuit FM1 (A) motor circuit
breaker (curve D) breaker (curve D)
+ residual current + residual current
device device
50 200 20.5 50 29.5 63
50 230 18 40 25.5 50
50 400 11 25 15 32
50 500 9 25 12 32
60 380 12 25 15.7 32
60 440/460 10 25 13.5 32
CSA/UL DOL Overload relay Main fuses (A) Overload relay Main fuses (A)
FM1 (A) (class J or RK) + FM1 (A) (class J or RK) +
Disc. switch size Disc. switch size
>=1,25 x FLA, see >=1,25 x FLA, see
conn. diagram. conn. diagram.
60 200 40 60 55 70
60 208-230/460 36.3-34.4/16.9 50-45 / 25 48-45 / 22.5 70 - 70 / 35
60 575 14 20 18.5 25

8.3 Reference conditions and limitations

Reference conditions

Air inlet pressure (absolute) bar 1


Air inlet pressure (absolute) psi 14.5
Air inlet temperature ˚C 20
Air inlet temperature ˚F 68
Relative humidity % 0
Working pressure bar(e) See Compressor data
Working pressure psi See Compressor data

Limitations

Maximum working pressure bar(e) See Compressor data


Maximum working pressure psig See Compressor data
Minimum working pressure bar(e) 4
Minimum working pressure psig 58
Maximum air inlet temperature ˚C 46

2920 7054 00 65

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Maximum air inlet temperature ˚F 115


Minimum ambient temperature ˚C 0
Minimum ambient temperature ˚F 32

8.4 Compressor data

50 Hz 7.5-13 bar (under reference conditions)

Compressor type GX7 GX11 GX7 GX11 GX7 GX11


Frequency Hz 50 50 50 50 50 50
Maximum bar(e) 7.5 7.5 10 10 13 13
(unloading)
pressure, Pack
Maximum psig 109 109 145 145 189 189
(unloading)
pressure, Pack
Maximum bar(e) 7.25 7.25 9.75 9.75 12.75 12.75
(unloading)
pressure, Full-
Feature
Maximum psig 105 105 141 141 185 185
(unloading)
pressure, Full-
Feature
Nominal working bar(e) 7 7 9.5 9.5 12.5 12.5
pressure
Nominal working psig 102 102 138 138 181 181
pressure
Set-point, ˚C 75 75 75 75 75 75
thermostatic valve
Set-point, ˚F 167 167 167 167 167 167
thermostatic valve
Temperature of air
leaving outlet valve
(approx.), Pack
• Tank-mounted ˚C 38 43 38 43 38 43
• Tank-mounted ˚F 100 109 100 109 100 109
• Floor-mounted ˚C 61.5 65 61.5 65 61.5 65
• Floor-mounted ˚F 143 149 143 149 143 149
Temperature of air ˚C 25 26 25 26 25 26
leaving outlet valve
(approx.), Full-
Feature
Temperature of air ˚F 77 79 77 79 77 79
leaving outlet valve
(approx.), Full-
Feature

66 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Compressor type GX7 GX11 GX7 GX11 GX7 GX11


Nominal motor power kW 7.5 11 7.5 11 7.5 11
rating
Nominal motor power hp 10 15 10 15 10 15
rating
Dryer power kW 0.36 0.36 0.36 0.36 0.36 0.36
consumption at full
load, Full Feature
units
Dryer power hp 0.48 0.48 0.48 0.48 0.48 0.48
consumption at full
load, Full Feature
units
Oil capacity l 3 3.2 3 3.2 3 3.2
Oil capacity US gal 0.8 0.84 0.8 0.84 0.8 0.84
Oil capacity Imp gal 0.65 0.7 0.65 0.7 0.65 0.7
Oil capacity cu.ft 0.1 0.11 0.1 0.11 0.1 0.11
Sound pressure level dB(A) 65 67 65 67 65 67
(according to ISO
2151 (2004))

60 Hz 100-125 psi (under reference conditions)

Compressor type GX7 GX11 GX7 GX11


Frequency Hz 60 60 60 60
Maximum (unloading) pressure, bar(e) 7.4 7.4 9.1 9.1
Pack
Maximum (unloading) pressure, psig 107 107 132 132
Pack
Maximum (unloading) pressure, bar(e) 7.15 7.15 8.85 8.85
Full-Feature
Maximum (unloading) pressure, psig 103.7 103.7 128 128
Full-Feature
Nominal working pressure bar(e) 6.9 6.9 8.6 8.6
Nominal working pressure psig 100 100 125 125
Set-point, thermostatic valve ˚C 75 75 75 75
Set-point, thermostatic valve ˚F 167 167 167 167
Temperature of air leaving outlet
valve (approx.), Pack
• Tank-mounted ˚C 38 43 38 43
• Tank-mounted ˚F 100 109 100 109
• Floor-mounted ˚C 60 66 60 66
• Floor-mounted ˚F 140 151 140 151
Temperature of air leaving outlet ˚C 23 25 23 25
valve (approx.), Full-Feature
Temperature of air leaving outlet ˚F 73 77 73 77
valve (approx.), Full-Feature

2920 7054 00 67

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Compressor type GX7 GX11 GX7 GX11


Nominal motor power rating kW 7.5 11 7.5 11
Nominal motor power rating hp 10 15 10 15
Dryer power consumption at full kW 0.44 0.44 0.44 0.44
load, Full Feature units
Dryer power consumption at full hp 0.59 0.59 0.59 0.59
load, Full Feature units
Oil capacity l 3 3.2 3 3.2
Oil capacity US gal 0.8 0.84 0.8 0.84
Oil capacity Imp gal 0.65 0.7 0.65 0.7
Oil capacity cu.ft 0.1 0.11 0.1 0.11
Sound pressure level (according dB(A) 67 68 67 68
to ISO 2151 (2004))

60 Hz 150-175 psi (under reference conditions)

Compressor type GX7 GX11 GX7 GX11


Frequency Hz 60 60 60 60
Maximum (unloading) pressure, bar(e) 10.8 10.8 12.5 12.5
Pack
Maximum (unloading) pressure, psig 157 157 181 181
Pack
Maximum (unloading) pressure, bar(e) 10.55 10.55 12.25 12.25
Full-Feature
Maximum (unloading) pressure, psig 153 153 178 178
Full-Feature
Nominal working pressure bar(e) 10.3 10.3 12 12
Nominal working pressure psig 149 149 174 174
Set-point, thermostatic valve ˚C 75 75 75 75
Set-point, thermostatic valve ˚F 167 167 167 167
Temperature of air leaving outlet
valve (approx.), Pack
• Tank-mounted ˚C 38 43 38 43
• Tank-mounted ˚F 100 109 100 109
• Floor-mounted ˚C 60 66 60 66
• Floor-mounted ˚F 140 151 140 151
Temperature of air leaving outlet ˚C 23 25 23 25
valve (approx.), Full-Feature
Temperature of air leaving outlet ˚F 73 77 73 77
valve (approx.), Full-Feature
Nominal motor power rating kW 7.5 11 7.5 11
Nominal motor power rating hp 10 15 10 15
Dryer power consumption at full kW 0.44 0.44 0.44 0.44
load, Full Feature units
Dryer power consumption at full hp 0.59 0.59 0.59 0.59
load, Full Feature units

68 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

Compressor type GX7 GX11 GX7 GX11


Oil capacity l 3 3.2 3 3.2
Oil capacity US gal 0.8 0.84 0.8 0.84
Oil capacity Imp gal 0.65 0.7 0.65 0.7
Oil capacity cu.ft 0.1 0.11 0.1 0.11
Sound pressure level (according dB(A) 67 68 67 68
to ISO 2151 (2004))

2920 7054 00 69

Downloaded from www.Manualslib.com manuals search engine


Instruction book

9 Instructions for use of air receiver

9.1 Instructions for use

1 This vessel can contain pressurised air; this can be potentially dangerous if the equipment is
misused.
2 This vessel must only be used as compressed air/oil separator and must be operated within
the limits specified on the data plate.
3 No alterations must be made to this vessel by welding, drilling or other mechanical methods
without the written permission of the manufacturer.
4 The pressure and temperature of this vessel must be clearly indicated.
5 There is no intrinsic need for service inspection of the vessel when used within the design
limits for its intended application.
6 Corrosion must be prevented under the conditions of use. Condensation may accumulate
inside the tank and this must be drained every day. This may be done manually, by opening
the drain valve, or by means of the automatic drain, if fitted to the tank.
Nevertheless, a weekly check by opening of the manual drain valve is necessary.

70 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine


Instruction book

10 PED

10.1 Pressure equipment directives

Components subject to 97/23/EC Pressure Equipment Directive


Components subject to 97/23/EC Pressure Equipment Directive greater than or equal to category II

Compressor type Part number Description PED Class


GX7 and GX11 2200 9507 74 Safety valve IV
2200 9507 75 Safety valve IV
0830 1009 71 Safety valve IV
0830 1009 72 Safety valve IV

Overall rating
The compressors conform to PED smaller than category II.

2920 7054 00 71

Downloaded from www.Manualslib.com manuals search engine


Downloaded from www.Manualslib.com manuals search engine
Downloaded from www.Manualslib.com manuals search engine
What sets Atlas Copco apart as a company is our
conviction that we can only excel in what we do if we
provide the best possible know-how and technology
to really help our customers produce, grow and
succeed.
There is a unique way of achieving that - we simply
call it the Atlas Copco way. It builds on interaction,
on long-term relationships and involvement in the
customers’ process, needs and objectives. It means
having the flexibility to adapt to the diverse demands
of the people we cater for.
It’s the commitment to our customers’ business that
drives our effort towards increasing their productivity
through better solutions. It starts with fully supporting
existing products and continuously doing things
better, but it goes much further, creating advances in
technology through innovation. Not for the sake of
technology, but for the sake of our customer’s bottom
line and peace-of-mind.
That is how Atlas Copco will strive to remain the first
choice, to succeed in attracting new business and to
maintain our position as the industry leader.

No. 2920 7054 00

Downloaded from www.Manualslib.com manuals search engine

You might also like