RTC48 Communication Quick Start Guide: 2. Wiring
RTC48 Communication Quick Start Guide: 2. Wiring
RTC48 Communication Quick Start Guide: 2. Wiring
Wiring
03/2013 1
+ 2 +
Safety Information –
–
SG
Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, 3
operate, or maintain it. +
The following special messages may appear throughout this documentation or on the equipment to warn of potential 4
–
hazards or to call attention to information that clarifies or simplifies a procedure.
3
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment
damage.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No
responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. This 3
document is not intended as an instruction manual for untrained persons. 1 Master
A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment 2 Shielded twist per cable
3 Zelio Temperature Controller
and its installation, and has received safety training to recognize and avoid the hazards involved. 4 RS485 Interface
1 CAUTION
UNINTENDED EQUIPMENT OPERATION
Connect only 1 side of the shielded wire (TWDXCAFJ010) to the Shielding Ground (SG) terminal so that current
RS-485 cannot flow to the shielded wire.
TWDXCAT3RJ TWDXCAT3RJ TWDXCAT3RJ TWDXCAT3RJ Failure to follow this instruction can result in equipment damage.
RJ45
Terminal block pin
Controller
YA (-) YB (+) SG
2 RTC48 RTC48 16 17 18
RTC48 RTC48 RTC48 RTC48
No. 1 No. 2 No. 3 No. 4 No. 31 YA (–)
YA (+)
Item Name SG
Modbus Parameter Description Relative Holding Setting Range Modbus Parameter Description Relative Holding Setting Range
Function Names Address Register function Names Address Register
Code code
03H/06H oLH OUT1 high limit 001CH 40029 OUT1 low limit value...100% 03H/06H SENS Input type 0044H 40069 0000H: K -200...1370 °C 000FH: K -320...2500 °F
0001H: K -200.0...400.0 °C 0010H: K -320.0...750.0 °F
03H/06H oLL OUT1 low limit 001DH 40030 0...OUT1 low limit value %
0002H: J -200...1000 °C 0011H: J -320...1800 °F
03H/06H HYS OUT1 ON/OFF hysteresis 001EH 40031 0.1...100.0 °C, Vdc voltage 0003H: R 0...1760 °C 0012H: R 0...3200 °F
1...1000, current input, 0004H: S 0...1760 °C 0013H: S 0...3200 °F
Decimal point ignored 0005H: B 0...1820 °C 0014H: B 0...3300 °F
03H/06H cAcT 001FH 40032 0006H: E -200...800 °C 0015H: E -320...1500 °F
OUT2 cooling mode 0000H: Air cooling
0007H: T -200.0...400.0 °C 0016H: T -320.0...750.0 °F
0001H: Oil cooling 0008H: N -200...1300 °C 0017H: N -320...2300°F
0002H: Water cooling 0009H: PL- 0...1390 °C 0018H: PL- 0...2500°F
OUT2 low limit value...100% 000AH: 0019H:
03H/06H oLH2 OUT2 high limit 0020H 40033
C(W/Re5-26) 0...2315 °C C(W/Re5-26) 0 to 4200 °F
03H/06H oLL2 OUT2 low limit 0021H 40034 0...OUT2 low limit value % 000BH: Pt100 -200.0...850.0 °C 001AH: Pt100 -320.0...1500.0 °F
03H/06H HYSb OUT2 ON/OFF hysteresis 0022H 40035 0.1...100.0 °C, Vdc voltage 000CH: JPt100 -200.0...500.0 °C 001BH: JPt100 -320.0...900.0 °F
1...1000, current input, 000DH: Pt100 -200...850 °C 001CH: Pt100 -320...1500 °F
Decimal point ignored 000EH: JPt100 -200...500 °C 001DH: JPt100 -320...900 °F
001EH: 4...20 mA -2000...10000
03H/06H AL1T Alarm 1 type 0023H 40036 0000H: No alarm action 001FH: 0...20 mA -2000...10000
0001H: High limit alarm 0020H: 0...1 V -2000...10000
0021H: 0...5 V -2000...10000
0002H: Low limit alarm 0022H: 1...5 V -2000...10000
0003H: H/L limits alarm 0023H: 0...10 V -2000...10000
0004H: H/L limit range 03H/06H coNT Direct/Reverse 0045H 40070 0000H: Reverse action
action 0001H: Direct action
0005H: Process high alarm
03H/06H AT_b AT bias 0047H 40072 Set value
0006H: Process low alarm
03H/06H ARW ARW 0048H 40073 Set value
0007H: High limit w/standby
03H/06H oRAT OUT1 004AH 40075 0...100
0008H: Low limit w/standby rate-of-change
0009H: H/L limits w/standby 03H/06H dPTM Backlight 0050H 40081 0000H: All are backlit 0003H: Action indicators backlit
0001H: PV display backlit 0004H: PV+SV displays backlit
03H/06H AL2T Alarm 2 type 0024H 40037 0002H: SV display backlit 0005H: PV+Action indicators backlit
The same as Alarm 1 type
0006H: SV+Action indicators backlit
03H/06H A1HY Alarm 1 hysteresis 0025H 40038 0.1...100.0 °C, Vdc voltage
03H/06H coLR PV color 0051H 40082 0000H: Green 0004H: When Alarm ON:
1...1000, current input, 0001H: Red Orange Red
Decimal point ignored 0002H: Orange 0005H: PV continuous change
0003H: When Alarm ON: 0006H: PV continuous
03H/06H A2HY Alarm 2 hysteresis 0026H 40039 0.1...100.0 °C, Vdc voltage Green Red change+ Alarm ON, Red
1...1000, current input,
Decimal point ignored 03H/06H cLRG PV color range 0052H 40083 Set value, Decimal point ignored
03H/06H dPTM Backlight time 0053H 40084 0...99
03H/06H A1dY Alarm 1 delay time 0029H 40042 0...10000 s
06H - Key operation 0070H 40113 0000H: No action
03H/06H A2dY Alarm 2 delay time 002AH 40043 0...10000 s change flag clearing 0001H: Clear all
03H/06H PSV Indication when output OFF 0032H 40051 0000H: OFF indication 03H - PV (Process 0080H 40129 Current PV (Process variable),
Variable) Decimal point ignored
0001H: No indication
03H - OUT1 MV 0081H 40130 OUT1 MV, Decimal point ignored
0002H: PV indication
0003H: PV+ Alarm action 03H - OUT2 MV 0082H 40131 OUT2 MV, Decimal point ignored
03H - SV (When SV 0083H 40132 Current SV (Desired value),
03H/06H RATU SV rise rate 0033H 40052 Set value, Decimal point ignored rises or falls) Decimal point ignored
03H/06H RATd SV fall rate 0034H 40053 Set value, Decimal point ignored 03H - Status flag 0085H 40134 20 : OUT1 0: OFF, 1: ON
(DC current output: Not fixed)
03H/06H dIIN Control OUT/OFF function 0037H 40056 0000H: Control output ON 2 : OUT2
1
0: OFF, 1: ON
0001H: Control output OFF 22 : Alarm 1 output 0: OFF, 1: ON
23 : Alarm 2 output 0: OFF, 1: ON
03H/06H MANU Auto/Manual control 0038H 40057 0000H: Automatic control 2 : Heater burnout alarm
6
0: OFF, 1: ON
output (When sensor burnout, 0: OFF)
0001H: Manual control
28 : Overscale 0: OFF, 1: ON
03H/06H - Manual control MV 0039H 40058 Set value 29 : Underscale 0: OFF, 1: ON
2 : Control output OUT/OFF
10
0: ON, 1: OFF
03H/06H A1LM Alarm 1 Energized/ 0040H 40065 0000H: Energized 211 : During AT/Auto-reset 0: OFF, 1: During AT/Auto-reset
De-energized 0001H: De-energized 212 : OUT/OFF key function 0: OUT/OFF function
1: Auto/Manual control
03H/06H A2LM Alarm 2 Energized/ 0041H 40066 0000H: Energized 214 : Auto/Manual control 0: Auto, 1: Manual
De-energized 0001H: De-energized 215 : Change in key operation 0: No, 1: Yes
2,2,2,2
4 5 7 13 Not used, Always 0
www.schneider-electric.com
© 2013 Schneider Electric. All rights reserved. HRB7810101-00